Ignition Conversion Kits to Convert Models F and B with Standing Pilot to
Spark-Ignited, Intermittent Safety Pilot System With or Without Lockout
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, injury, or death. Read the installation instructions thoroughly
before installing this equipment.
Description/
Application
IMPORTANT
NOTE: These
are not gas
conversion
kits, ignition
conversion only.
NOTE: A unit with a
vent damper (Option
AV7) requires P/N
257010, an ignition
controller for
intermittent spark
pilot with lockout
The ignition conversion kits in this form are for Model F and Model B unit heaters equipped
with standing pilot and single stage gas valve. Before beginning conversion, determine
that your kit is compatible with your heater. Spark-ignited, intermittent safety pilot systems
without lockout are not available with propane gas; propane gas requires 100% lockout.
IGNITION CONVERSION KIT SELECTION CHART for Models F and B
Kits to convert from standing pilot to spark-
ignited, intermittent recycling safety pilot
ModelGas TypeKit P/NModelGas TypeKit P/N
F/B 25-165
F/B 200-250100526F/B 200-250100529
F 300-400; B 300100527F 300-400; B 300100530
B 400102348B 400102349
(without lockout)
100525F/B 25-165
Natural
See pages 7-8 for a parts
listing of each kit.
Kits to convert from standing pilot to
spark-ignited, intermittent safety
with 100% lockout
100528
Natural
F/B 25-200
F 250-400; B 250-300100532
B 400102350
Propane
100531
(Option AH3)
WARNING: This ignition conversion kit is to be installed by a qualied agency in
accordance with these instructions and in compliance with all codes and requirements
of authorities having jurisdiction. Failure to follow instructions could result in death,
serious injury, and or property damage. The qualied agency performing this work
assumes responsibility for this installation.
Instructions for
Installing Ignition
Conversion Kit
1. Turn off the gas supply at a shutoff valve upstream of the combination valve and turn
off the electrical supply.
2.Change Combination Valve
Disconnect the main gas line, the wires and the pilot tubing from the valve and remove the
valve. Install the valve provided with the kit being sure that the gas ow through the valve
is in the proper direction and that the valve is in an allowable orientation. Follow the valve
manufacturer’s instructions and, if applicable, the replacement valve kit instructions for
details on installing the valve.
Reconnect the main gas line. Do not reconnect the pilot tubing or wires at this time.
WARNING: The operating valve is the primary safety shutoff.
The gas supply line must be free of dirt or scale before connecting the unit to ensure positive closure.
3. Install the Ignition Controller (See FIGURE 1 for location.)
Attach the ignition controller mounting bracket to the rear of the heater using the holes in
the cabinet and the #10x3/8” screws in the kit. Position the ignition controller on the bracket
with the wire terminals across the bottom. Use the #8x5/8” screws to attach the ignition
controller to the bracket.
Form CP-F/B-IGN, P/N100550 (Rev 3), Page 1
Page 2
Instructions
(cont’d)
Replacement Controller, either
P/N 257009 or 257010
FIGURE 1 - Ignition
Control Location
FIGURE 2 - Bottom
Access Panel Open
FIGURE 3 - Pilot
Spark Gap
Transformer
Ignition
Terminal Strip
4. Change Pilot
Remove the two screws located at the rear bottom of the
heater that retain the bottom access panel. Allow the bottom panel to hinge down from the front.
The bottom of the pilot is now visible (See FIGURE 4A,
below.) Remove the screws holding the match-lit pilot
and remove the pilot assembly.
The match-lit pilot consisted of the pilot with hood and the ame-sensing thermocouple.
The new spark pilot assembly has a hooded pilot, a ame sensor rod, and an ignitor. Before
installing the pilot, verify the correct spark gap between the pilot hood and the ignitor. See
FIGURE 3. The spark gap must be maintained at .100”. The spark gap is set by the manufacturer and should be correct, but it is wise to recheck before installation. If adjustment is
required, hold the ceramic base with a pair of pliers while adjusting the rod.
Install the spark pilot assembly being sure that the pilot burner is extended toward the
burner tube. Be sure to include the pilot shield that is used only with the spark pilot assembly. (See FIGURES 4A, 4B, and 4C.)
Controller
location
Valve
FIGURE 4A - (1) Remove the
match-lit pilot assembly.
FIGURE 4C (3) Spark Pilot
Installed
Form CP-F/B-IGN, Page 2
FIGURE 4B - (2) Install the pilot shield and spark pilot
assembly with pilot burner extending toward the
burner tube.
Pilot
Shield
Pilot
Burner
Pilot Shield
Pilot Assembly with Flame Probe
Page 3
CAUTION:
Control, P/N
257010, with
lockout is
required with
a vent damper.
The controller
has a safety
feature that
once it is used
with a vent
damper, it
will no longer
operate a unit
without a vent
damper.
Attach one end of the ame sensor wire (150°C red silicone wire) to the ame probe on
the pilot assembly. Attach the other end of the ame sensor wire to Terminal “SENSE” on
the ignition controller. Attach the free end of the high tension spark wire (wire attached to
the ignitor on the pilot assembly) to the spike (“SPARK”) terminal on the ignition controller.
Push the wire rmly so that the spike is fully inserted and the wire secure.
Connect the pilot tubing to the gas valve. Position the tubing, high tension wire and ame
sensor wire in a location where they will not interfere with gas or air entering the burner or
be pinched by the bottom panel. Do not wrap the high tension wire and the ame sensor
wire together. The tubing and the wires may be routed through the opening for the manifold
pipe.
5. Wiring (Follow the appropriate new wiring diagram label in the kit.)
Remove the outer left heater side panel (left when facing the rear of the heater), revealing
the wiring.
Using the wires on the heater and the new wire assemblies in the kit, make the connections according to the instructions below and the new wiring diagram label in the kit.
(a) Replace transformer – Models with standard 115 volt supply require a transformer
change when converting to spark ignition. Models with optional 208, 230 or 460 supply voltage do not require a transformer change. If your unit requires a transformer
change, disconnect the wires from the transformer and remove the transformer from
the heater. (See FIGURE 1.) To install the new transformer, through the “large” hole in
the side panel for mounting the transformer, slide the Tinnerman clips over the transformer screw holes. Insert the new transformer in the mounting hole and fasten with
the 1-3/4” long screws included in the kit. Reconnect the brown wire from the terminal
strip and the line voltage yellow and black wires. Do not reconnect the blue wire.
(b) ECO (Energy Cutoff) Wiring – The ECO wiring on a unit with a standard pilot is
routed through the rear of the heater. When the unit is converted to spark, the ECO
wiring must be re-routed through the side panel. Follow these instructions to re-route
and reconnect the ECO wires (Refer to Wiring Diagram on page 6):
(1) On the rear of the heater (fan panel), remove the Heyco device (strain relief bush-
ing) that holds the two red wires going through the fan panel. (These wires were
disconnected from the gas valve in Step 2.)
(2) On the side of the heater, remove the small fan/limit control access panel (See
FIGURE 5). Reach through the access hole and pull both red wires completely
through the fan panel into the heater where the ECO is located. One of these
wires will be used on the converted heater, but the other must be replaced with
the longer red wire in the conversion kit. Carefully disconnect one of the wires
from the ECO control and discard that wire. The red ECO wire in the kit has two
different terminals. Connect the end with the straight insulated terminal to the
ECO control.
(3) Remove the Heyco device (See FIGURE 5) from the inner side panel. Add the two
red ECO wires to the fan and limit wires that are already there. Using pliers, rein-
FIGURE 5 - Outer
Side Panel Removed
Showing Access to
ECO Wiring through
the Fan/Limit
Control Access
Panel (panel is
removed)
Add the ECO wires
to the Heyco device
holding the fan and
Limit
Control
Fan
Control
limit wires.
ECO Device
FIGURE 6 - Rear View of
a Model F showing ECO
Wire Conguration after
Conversion
Fan
Control
Form CP-F/B-IGN, P/N100550 (Rev 3), Page 3
ECO
Device
Limit
Control
Page 4
Instructions
(cont’d)
(b) ECO (Energy Cutoff) Wiring (cont’d)
stall the Heyco device. Check to be sure that none of the wires (ECO, fan or limit)
come in contact with the heat exchanger tubes.
(4) Connect the red ECO wire with the 90° insulated terminal to the transformer. If
a new transformer was not installed, disconnect the blue wire to make this connection. If a new transformer was installed, make the connection on the 24V side
where the blue wire had been connected to the old transformer.
(5) At the terminal strip (See FIGURE 1), disconnect and discard the blue wire. At the
same place on the terminal strip, connect the other red ECO wire.
(6) Re-attach the small fan and limit control access panel.
(c) Combination Gas Valve – Connect the blue, black, and brown wires from the igni-
tion control. Attach the blue wire either to the P, TH-TR or PV terminal, depending on
the gas valve model. Attach the black wire to either M, TH or MV terminal. Attach the
brown wire to the terminal marked either C, TR or PV-MV (See Diagram, page 6).
6. Change the Lighting Instruction Plate and the Wiring Diagram on Heater
Lighting Instruction Plate – The new lighting instruction plate is self-adhesive and can be
placed over the original lighting instruction plate. Make sure the surface of the old instruction plate is clean and dry. Remove the backing and adhere the new lighting instruction
plate so that it covers the original standing pilot instruction plate.
Wiring Diagram – The new wiring diagram is also self-adhesive and is made to cover the
original diagram on the heater.
If the heater is a Model F; a Model B with a direct drive blower motor; a Model B with a beltdriven blower with a motor without a contactor; or a Model B with a belt driven blower with
a motor with a contactor, select the diagram that matches the heater. Remove the backing
and adhere it over the diagram on the heater.
If the heater is a Model B with a belt-driven blower with a motor with a starter, contact your
Reznor Representative, providing the complete model number, the serial number, and the
number of the wiring diagram originally supplied on the heater. When the custom wiring
diagram arrives, verify that it matches, remove the backing, and adhere it over the wiring
diagram on the heater.
FIGURE 7 - Proper
Flame Adjustment
Form CP-F/B-IGN, Page 4
7. Check the main gas line for leaks using a commercial leak detecting uid or a rich
soap and water solution. Leaks are indicated by the presence of bubbles.
WARNING: All components of gas supply must be leak tested
prior to placing equipment in service. NEVER TEST FOR LEAKS
WITH AN OPEN FLAME. Failure to comply could result in severe
personal injury, property damage or death.
Turn on the electric and the gas. Relight, following the instructions on the new lighting
instruction plate.
WARNING: In the event of improper ignition, wait at least ve
minutes before attempting to relight heater.
Check all gas connections including the pilot connections for leaks, If a leak cannot be
stopped by tightening, replace the part.
Observe the pilot ame through the pilot lighting hole. The ame should extend ½ to 1” past
the ame sensing device (FIGURE 7).
To adjust the pilot ame, remove the pilot adjustment cover screw from the combination
valve. Turn the inner adjustment screw clockwise to decrease or counterclockwise to
increase the pilot ame. Replace the cover screw after adjustment to prevent gas leakage.
8. Adjust Manifold Pressure
Depending on how the unit was originally equipped, the correct pressure adjustment may
depend on the area of the country in terms of elevation. Check the elevation listed on the
rating plate.
Page 5
If the rating plate indicates 0-2000 ft, and the installation is located at 0-2000 ft, follow
a)
the instructions to check the manifold pressure to be sure that it is 3.5 inches w.c. for
natural gas or 10.0 inches w.c. for propane.
If the rating plate indicates a higher elevation the elevation adjustment was made at the
b)
factory by an orice change. Follow the instructions to check the manifold pressure to be
sure that it is 3.5 inches w.c. for natural gas or 10.0 inches w.c. for propane.
If the rating place indicates 0-2000 ft and the actual elevation is higher, determine the
c)
correct manifold pressure for the elevation and follow the instructions to set the valve
outlet pressure.
Manifold Pressure Settings by Elevation
Elevation RangesNatural Gas Propane
FeetMeters(inches W.C.)
0- 2000 1-6103.510.0
2001-3000911-9152.87.7
3001-4000916-12202.57.1
4001-50001221-15252.36.4
5001-60001526-18302.15.8
6001-70001831-21351.95.2
7001-80002136-24401.74.6
8001-90002441-27451.54.1
Instructions:
With the manual valve positioned to prevent ow to the main burners, connect a
1)
manometer to the 1/8” pipe outlet pressure tap in the valve. Use a water column
manometer that is readable to the nearest tenth of an inch. NOTE: A manometer (uid-
lled gauge) is recommended rather than a spring type gauge due to the difculty of
maintaining calibration of a spring type gauge.
Remove the cap from the pressure adjusting screw and adjust the manifold pressure
2)
to the pressure determined to be correct for the installation. Cycle the main burners
once or twice to properly seat the adjustment spring in the valve.
WARNING: Manifold gas pressure must never exceed 3.5” w.c.
for natural gas or 10” w.c. for propane gas.
Measure the manifold pressure. If further adjustment is necessary, correct pressure setting
3)
by turning the regulator screw IN (clockwise) to increase pressure. Turn regulator screw
OUT (counterclockwise) to decrease pressure. When the pressure is correct, remove the
manometer and replace the cap. Check for leaks at the pressure tap tting.
CAUTION: DO NOT bottom out the gas valve regulator adjustment screw. This can result in unregulated manifold pressure
causing excess overre and heat exchanger failure.
With the heater operating, determine that the inlet pressure to the heater is between 5 and
3)
14 inches w.c. for natural gas or between 11 and 14 inches w.c. for propane gas. Take this
reading as close as possible to the heater. (Most heaters are equipped with gas valves
that have an inlet pressure tap.) If the inlet pressure is not within the specied range the
inlet pressure must be corrected and the manifold pressure re-checked.
If the gas valve has been adjusted for operation above 2000 ft, nd the high altitude
4)
manifold pressure label in the kit. Using a permanent marker, ll-in the pressure setting
and adhere the label to the heater in a conspicuous location close to the gas valve.
9. Check for reliable and safe operation by operating the heater for several complete
cycles. CHECK FOR PROPER OPERATION OF ALL SAFETY FEATURES.
WARNING: Wait at least ve minutes before attempting to relight
heater in the event of pilot outage or improper ignition.
10. Replace the side panel and close the bottom access panel. Restore the heater to
normal operation. If a thermostat with a heat anticipator is used, it should be reset to
approximately .8 amperes.
Form CP-F/B-IGN, P/N100550 (Rev 3), Page 5
Page 6
L1
(HOT)
R
24V
LINE VOLT
BR
GROUND TERMINAL
(TERMINAL STRIP)
L2
(COM)
BR
R
SET ANT. AT 0.8 AMPS
SINGLE STAGE THERMOSTAT
W1
R
W1
YY
LIMIT
CONTROL
Y
BR
R
BK
FIELD WIRING
TERMINAL STRIP
FACTORY WIRING
- TURN ON MAIN AND PILOT MANUAL GAS VALVES.
- TURN ON POWER TO UNIT.
- SET THERMOSTAT AT DESIRED SETTING.
- THERMOSTAT CALLS FOR HEAT FIRING UNIT AT FULL RATE AFTER PILOT
PROVING SEQUENCE.
BR
BLOCKED VENT
MANUAL RESET
SWITCH
Y
- FAN CONTROL SENSES HEAT EXCHANGER TEMPERATURE, ENERGIZING THE
FAN OR BLOWER MOTOR.
CONTROL
TRANSFORMER
UNIT WIRING
FIELD WIRING
WIRE CONNECTOR
CRIMP TERMINAL
R
ENERGY CUT-OFF
(PRIOR TO AUGUST 1999)
*
USED ON UNITS PRODUCED
AFTER APRIL 1991
*
- FOR CONTINUOUS FAN OPERATION SET S/W SWITCH AT "ON" POSITION.
REDUNDANT GAS VALVE
ALTERNATE W.R. OR ROBERTSHAW
BL
P
BK
BR
MAIN
PILOT
M
C
PV
PILOT
MV
PV-MV
MAIN
REDUNDANT GAS VALVE
HONEYWELL
BL
BK
IGNITION
CONTROLLER
PROBE
GRD
SPARK
FLAME SENSING
24V
MV/PV
GND BURNER
24V GND
MV
SENSE
TH
PV
G
UNIT CHASSIS
GROUND
OPTIONAL VENT DAMPER
FIELD INSTALLED
BR
RR
ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.
- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.
TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.
- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE
A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR ENERGY
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING
- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED
- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT:
- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:
FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.
FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).
FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).
THERMOSTAT
CUTOFF OR SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.
- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.
BY OTHERS: NONE
CONTROL SWITCH
NOTES
USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25
TIMES THE MAXIMUM TOTAL INPUT AMPS.
- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH
- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.
- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE
SPARK GAP.
ON UNITS EQUIPPED WITH LOCKOUT CONTROL, IF PILOT IS NOT
ESTABLISHED WITHIN 120 SECONDS. THE UNIT LOCKS OUT FOR ONE
HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO
THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)
CONTROLLER FOR OPTIONAL VENT DAMPER
(APPLIES ONLY TO CONTROLLER WITH LOCKOUT)
NEW WIRE PROVIDED WITH THE IGNITION
LINE VOLTAGE ON HEATER
WHITE - W
PURPLE - PR
BLUE - BL
GREEN - G
YELLOW - Y
ORANGE - O
RED - R
BROWN - BR
BLACK - BK
WIRING CODE
OPERATING SEQUENCE
NOTE: Minimum flame proving
signal strength is 0.2 microamps.
Typical Wiring Diagram - Intermittent Spark Pilot
with or without Lockout, Single-Stage Heating
Field and Replacement Wiring Notes
1. Dotted wiring supplied by others.
2. Thermostat supplied as optional equipment.
3. Use 14 gauge wire for line wiring to unit.
4. Use 18 gauge wire for control wiring on unit.
5. Line and blower or fan control branch circuit wire sizes should be of a size to
prevent voltage drops beyond 5% of supply line voltage.
FIELD CONTROL WIRING
Length and Gauge
Total Wire
Length
Distance from
Unit to Control
Recommended
Wire Gauge
150’ (46M)75’ (23M)18 gauge
250’ (76M)125’ (38M)16 gauge
350’ (107M) 175’ (53M)14 gauge
Form CP-F/B-IGN, Page 6
Page 7
Parts Lists - Ignition Conversion Kits for Models F and B
NOTE: These kits are ignition conversion kits only; NOT gas conversion kits.
WARNING: These kits are for Reznor Models F and B only. Do not use them on any
other products.
SECTION 1 - Kits to convert natural gas units from standing pilot to spark-ignited, intermittent safety pilot
without lockout, Option AH2 (not applicable to propane units – propane requires pilot with lockout).
Ignition Conversion Kit P/N 100525
Applies to: Model F 25-165, Natural Gas; Model B 25-165, Natural Gas
QtyP/NDescription
196307 Gas Valve, 1/2”, M/H #VR8204-M1000 (Single stage)
1257474 Ignition Controller Assy including:
1257009Ignition Control Non-Lockout, UTEC 1003-638A
1133108Black Wire Assy (I.C. “MV”)
198215Brown Wire Assy (I.C. “MV/PV”)
198214Blue Wire Assy (I.C. “PV”)
1257074Green Wire Assy (I.C. “GND BURNER”)
198215Brown Wire Assy I.C. “24V GND”)
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assembly (I.C. “TH”)
1173307 Black Wire Assembly (I.C. “TH”)
197204 Pilot Shield
197534 Pilot Assy, Johnson #Q9OFF-1
198044 Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246 #10 x 3/8” lg Screws (to attach bracket to heater)
4195638 #8 x 3/8” lg Screws (to attach control to bracket)
1102708 Transformer, 35 VA, Basler #BE141640-RAK
2103152 Screws, #6 x 1-3/4” lg (for mounting transformer)
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assy (I.C. “TH”)
1173307 Black Wire Assy (I.C. “TH”)
197204 Pilot Shield
197534 Pilot Assy, Johnson #Q9OFF-1
198044 Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246 #10 x 3/8” lg Screws (to attach bracket to heater)
4195638 #8 x 3/8” lg Screws (to attach control to bracket)
1102708 Transformer, 35 VA, Basler #BE141640-RAK
2103152 Screws, #6 x 1-3/4” lg (for mounting transformer)
2111233 Clips, Tinnerman #C6310-6Z-4 (for transformer screws)
196101 Lighting Instruction Plate
1100550 Instruction Sheet CP-F/B-IGN
Wiring Diagrams (select the one that matches the heater):
1258173 For Model F 200-250
1258174 For Model B 200-250 w/direct drive motor &l B 50-165 w/belt drive motor (no contactor)
1258175 For Model B 200-250 with belt drive motor with contactor
1Special Consult factory for Wiring Diagram fFor Model B with a starter.
Ignition Conversion Kit P/N 100530
Applies to: Model F 300-400, Natural Gas; Model B 300, Natural Gas
QtyP/NDescription
1222037
1257475 Ignition Controller Assy including:
1257010Ignition Control w/100% Lockout, UTEC 1003-514
1133108Black Wire Assy (I.C. “MV”)
198215Brown Wire Assy (I.C. “MV/PV”)
198214Blue Wire Assy (I.C. “PV”)
1257074Green Wire Assy (I.C. “GND BURNER”)
198215Brown Wire Assy I.C. “24V GND”)
1173303Red Wire Assy (I.C. “24V”)
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assy (I.C. “TH”)
1173307 Black Wire Assy (I.C. “TH”)
197204 Pilot Shield
197534 Pilot Assy, Johnson #Q9OFF-1
198044 Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246 #10 x 3/8” lg Screws (to attach bracket to heater)
4195638 #8 x 3/8” lg Screws (to attach control to bracket)
1102708 Transformer, 35 VA, Basler #BE141640-RAK
2103152 Screws, #6 x 1-3/4” lg (for mounting transformer)
Wiring Diagrams (select the one that matches the heater):
1258173 For Model F 300-400
1258175 For Model B 300 with belt drive motor with contactor
1Special Consult factory for Wiring Diagram for Model B with a starter.
Ignition Conversion Kit P/N 102349
Applies to: Model B 400, Natural Gas
QtyP/NDescription
1222037
1257475 Ignition Controller Assy including:
1257010Ignition Control w/100% Lockout, UTEC 1003-514
1133108Black Wire Assy (I.C. “MV”)
198215Brown Wire Assy (I.C. “MV/PV”)
198214Blue Wire Assy (I.C. “PV”)
1257074Green Wire Assy (I.C. “GND BURNER”)
198215Brown Wire Assy I.C. “24V GND”)
1173303Red Wire Assy (I.C. “24V”)
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assy (I.C. “TH”)
1173307 Black Wire Assy (I.C. “TH”)
197204Pilot Shield
197534Pilot Assy, Johnson #Q9OFF-1
198044Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246#10 x 3/8” lg Screws (to attach bracket to heater)
4195638 #8 x 3/8” lg Screws (to attach control to bracket)
196101Lighting Instruction Plate
1100550 Instruction Sheet CP-F/B-IGN
1Special Consult factory for Wiring Diagram for Model B with a starter.
Replacement Valve Kit including P/N 221525 Valve, W/R #36H32-441;
Compression Nut, P/N 97572; and Instruction Sheet, P/N 222038
Replacement Valve Kit including P/N 221525 Valve, W/R #36H32-441;
Compression Nut, P/N 97572; and Instruction Sheet, P/N 222038
258175 For Model B 400 with belt drive motor with contactor
The loose yellow wire is not used in this application.
The loose yellow wire is not used in this application.
The loose yellow wire is not used in this
application.
SECTION 3 - Ignition Conversion Kits to convert propane gas units from standing pilot to spark-ignited, intermittent pilot safety system with lockout, Option AH3.
Ignition Conversion Kit P/N 100531
Applies to: Model F 25-200, Propane; Model B 25-200, Propane
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assy (I.C. “TH”)
1173307 Black Wire Assy (I.C. “TH”)
197204Pilot Shield
197535Pilot Assy, Johnson #Q9OFF-2
198044Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246#10 x 3/8” lg Screws (to attach bracket to heater)
4195638 #8 x 3/8” lg Screws (to attach control to bracket)
1102708 Transformer, 35 VA, Basler #BE141640-RAK
2103152 Screws, #6 x 1-3/4” lg (for mounting transformer)
2111233 Clips, Tinnerman #C6310-6Z-4 (for transformer screws)
196101Lighting Instruction Plate
1100550 Instruction Sheet CP-F/B-IGN
Wiring Diagrams (select the one that matches the heater):
1258173 For Model F 25-200
1258174 For Model B 25-200 w/direct drive motor and B 50-165 w/belt drive motor (no contactor)
1258175 For Model B 75-200 with belt drive motor with contactor
1Special Consult factory for Wiring Diagram for Model B with a starter.
Ignition Conversion Kit P/N 100532
Applies to: Model F 250-400, Propane; Model B 250-300, Propane
QtyP/NDescription
1221634
1257475 Ignition Controller Assy including:
1257010Ignition Control w/100% Lockout, UTEC 1003-514
1133108Black Wire Assy (I.C. “MV”)
198215Brown Wire Assy (I.C. “MV/PV”)
198214Blue Wire Assy (I.C. “PV”)
1257074Green Wire Assy (I.C. “GND BURNER”)
198215Brown Wire Assy I.C. “24V GND”)
1173303Red Wire Assy (I.C. “24V”)
1257014Red Wire Assy (I.C.”SENSE”)
1122655 Yellow Wire Assy (I.C. “TH”)
1
197204Pilot Shield
197535Pilot Assy, Johnson #Q9OFF-2
198044Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012 Controller Bracket
264246#10 x 3/8” lg Screws (to attach bracket to heater)
4 195638 #8 x 3/8” lg Screws (to attach control to bracket)
1102708 Transformer, 35 VA, Basler #BE141640-RAK
2103152 Screws, #6 x 1-3/4” lg (for mounting transformer)
2111233 Clips, Tinnerman #C6310-6Z-4 (for transformer screws)
196101Lighting Instruction Plate
1100550 Instruction Sheet CP-F/B-IGN
Wiring Diagrams (select the one that matches the heater):
1258173 For Model F 250-400
1258174 For Model B 250 with belt drive motor (no contactor)
1258175 For Model B 250-300 with belt drive motor with contactor
1Special Consult factory for Wiring Diagram for Model B with a starter.
Ignition Conversion Kit P/N 102350
Applies to: Model B 400, Propane
QtyP/NDescription
1221634
1257475Ignition Controller Assy including:
1257010Ignition Control w/100% Lockout, UTEC 1003-514
1133108Black Wire Assy (I.C. “MV”)
198215Brown Wire Assy (I.C. “MV/PV”)
198214Blue Wire Assy (I.C. “PV”)
1257074Green Wire Assy (I.C. “GND BURNERr”)
198215Brown Wire Assy I.C. “24V GND”)
1173303Red Wire Assy (I.C. “24V”)
1257014Red Wire Assy (I.C.”SENSE”)
1122655Yellow Wire Assy (I.C. “TH”)
1
197204Pilot Shield
197535Pilot Assy, Johnson #Q9OFF-2
198044Red Wire Assy (ECO to Transformer) 18 ga. x 20”, 150°C w/2 Terminals
1257012Controller Bracket
264246#10 x 3/8” lg Screws (to attach bracket to heater)
4195638#8 x 3/8” lg Screws (to attach control to bracket)
196101Lighting Instruction Plate
1100550Instruction Sheet CP-F/B-IGN
1258175For Model B 400 with belt drive motor with contactor
1SpecialConsult factory for Wiring Diagram for Model B 400 with a starter.