Reznor ACR1500SE12, ACR2000SE9-1PH, ACR1000SE9, ACR2000SE18, ACR1200HE12 Installation And Operating Manual

...
INSTALLATION AND OPERATING MANUAL
ACR Recessed Air Curtain
Electrically Heated, Ambient & LPHW
WARNINGS
Nortek Global HVAC (UK) Limited equipment must be installed and maintained in accordance with the
requirements of the Codes of Practice or rules in force. All external wiring MUST comply with the codes of practice
or rules in force in the country of installation.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
hazardous atmospheres containing flammable vapours or combustible dust, containing chlorinated or halogenated
hydrocarbons, or in applications with airborne silicone substances.
Reznor® is a registered trademark of Nortek Global HVAC, LLC.
ErP
2018
Part No. D301051
Introduction.
elcome to the range of Airbloc ACR Recessed Air Curtains. Local regulations may vary in the country of use and it is the
W
installers responsibility to ensure that such regulations are satised
All installation and assembly procedures must be carried out by suitable competent persons. Commissioning and service procedures must be carried out by suitable qualied persons to the statutory regulations in the country of use.
When installing, commissioning and servicing is undertaken on these air curtains due care and attention is required to ensure that working at height regulations are adhered to, at the mounting heights specied.
All Dimensions shown are in mm unless otherwise stated.
PLEASE READ this document prior to installation and use. The safety of this heater is guaranteed only by the correct usage
in accordance with these instructions, therefore it is recommended that they are retained for future reference.
The manufacturer reserves the right to alter specications without prior notice.
Any reference made to Laws, Standards, Directives, Codes of Practice or other recommendations governing the application and installation of heating appliances and which may be referred to in Brochures, Specications, Quotations, and Installation, Operation and Maintenance manuals is done so for information and guidance purposes only and should only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations.
IMPORTANT NOTICE TO INSTALLERS
Installers should satisfy themselves that the gas pipework installation is carried out in accordance with all current legislation, Codes of Practice and recommendations .
Additionally it may be necessary to protect the gas valves which form part of the heater or burner assembly from potential pipe contamination particularly, but not exclusively, where copper gas pipework is used.
In instances where copper pipework is to be used for all or part of a gas pipework installation, including short length nal connections then we advise that installers consult with gas supplier or provider and satisfy themselves what additional precautions may be necessary.
Doc No. D301021 Page 2 of 64
Document Index.
1 Installation Requirements
1.1 Compliance Notice
1.2 Certicate of Conformity
1.3 General Product Information
1.4 Model Denition
1.5 General Requirements
1.6 Health and Safety
1.7 Delivery and pre-installation
1.8 Location
1.9 Clearance Distance
1.10 Electrical Supply
1.10.1 Electronic Controller
1.10.2 SmartElec3 Controller
2 Dimensions
2.1 ACR Air Curtain
2.2 Program keypad
2.3 Optional SmartElec3 Controller
3 Technical Specications
3.1 Electrical Heated, Std Capacity 6&9kW 1P
3.2 Electrical Heated, Std Capacity 9,12&18kW
3.3 Electrical Heated, High Capacity 12-18kW
3.4 Ambient, Std Capacity
3.5 Ambient, High Capacity
3.6 LPHW, Std Capacity
3.7 LPHW, High Capacity
3.8 Electronic Controller
3.9 SmartElec3 Controller
3.10 LPHW/Ambient Controller
4 Wiring Diagrams
4.1 Installer Wiring Electrically Heated 6&9kW 1P
4.2 Installer Wiring Electrically Heated 9,12&18kW 3P
4.3 Installer Wiring Ambient
4.4 Installer Wiring LPHW
4.5 Factory Wiring Electrically Htd 1000/1500 6kW 1P
4.6 Factory Wiring Electrically Htd 2000 9kW 1P
4.7 Factory Wiring Electrically Htd 1000/1500 9&12kW 3P
4.8 Factory Wiring Electrically Htd 1200/1800/2000 12&18 kW 3P
4.9 Factory Wiring Ambient ACR1000/1500 1P
4.10 Factory Wiring Ambient ACR2000/1200/1800 1P
4.11 Factory Wiring LPHW ACR1000/1500 1P
4.12 Factory Wiring LPHW ACR2000/1200/1800 1P
4.13 Network Wiring Ambient/LPHW
4.14 Network Wiring Electrically Htd
4.15 Installer Wiring SmartElec3
4.16 Factory Wiring ACR1000/1500 SmartElec3 Controller
4.17 Factory Wiring ACR1200/1800/2000 SmartElec3 Controller
4.18 Network Wiring SmartElec3
5 Installation Requirements
5.1 Mounting
5.2 Electrical Supply
5.3 Installation
5.4 Program Keypad
5.5 Option SmartElec3 Controller
5.6 LPHW only
5.6.1 3 Port Valve
5.7 Installation Wiring
6 Servicing & Maintenance Instructions
7 Spare Parts
7.1 General
7.2 Standard Controller
7.3 SmartElec3 Controller
7.4 Heating mediums
8 Fault Finding Guide
8.1 General
8.2 Electrical Heated
8.3 Standard Controller
8.4 Optional SmartElec3Controller
8.4.1 Fault Code chart
8.4.2 LED indication
9 Replacing Parts
9.1 Electrical Element SE
9.2 Electrical Element HE
9.3 Rotor/Motor SE
9.4 Rotor/Motor HE
9.5 LPHW Coil
10 User and Operating Instructions
10.1 Standard Keypad
10.1.1 Keypad Buttons
10.1.2 Operation
10.1.3 Standard Settings
10.1.4 Engineers Settings
10.1.4.1 Door Link Settings
10.1.4.2 Link-Group Interlock
10.1.4.3 All Controllers
10.2 LPHW/Ambient Controller
10.2.1 Keypad Buttons
10.2.2 Operation
10.2.3 Standard Settings
10.2.4 Engineers Settings
10.2.4.1 Door Link Settings
10.2.4.2 Link-Group Interlock
10.2.4.3 All Controllers
10.2.4.4 External Temperature
10.2.4.5 External Temperature Oset
10.2.4.6 Temperature Limits
10.2.4.7 Air Return & Pipe Cold Sensors
10.3 Optional SmartElec3 Controller
10.3.1 Keypad Buttons
10.3.2 Operation
10.2.2.1 Normal Mode Display
10.3.3 O Mode
10.3.4 Settings Mode
10.3.4.1 Activate Settings Display
10.3.4.2 Settings Display
10.3.5 Set Up Conguration
10.3.5.1 Set Fan Speed
10.3.5.2 Set Heat
10.3.5.3 Set Temperature
10.3.5.4 Networked Air Curtains
10.3.6 Engineers Settings
10.3.6.1 Door Link Settings
10.3.6.2 Link-group Interlock
10.3.6.3 All Air Curtains
10.3.6.4 External Temperature
Doc No. D301021 Page 3 of 64
Document Index cont.
10.3.6.5 External Temperature Oset
10.3.6.6 Temperature Limits
10.3.7 Power-up Manual Reset
10.3.8 Air Curtain Addressing
10.3.9 Keypad Sequences (standard controller)
10.3.10 Keypad Sequences (SmartElec controller)
Doc No. D301021 Page 4 of 64
1. Installation Requirements.
Isolate any electrical supply to the heater and controller before proceeding.
1.1 Compliance notices
he Airbloc ACR Recessed Air Curtain detailed herewith are
T
manufactured by Nortek Global HVAC (UK) Ltd. within a strictly controlled quality environment within the parameters of ISO 9001.
the use of the appliance so as to ensure its continued safe and ecient use.
Nortek Global HVAC (UK) Ltd. have a commitment to continuous improvement and therefore reserves the right to amend or change the specication of the Airbloc ACR Recessed Air Curtain range subject to compliance with the appropriate European, national, and local regulations.
Contained within the text of the manual, the words ‘Caution’ and ‘Warning’ are used to highlight certain points.
These instructions are only valid if the following country code is on the appliance GB. IE. If this code is not present on the appliance, it is necessary to refer to the technical instructions which will provide the necessary information concerning the modication of then appliance to the conditions of use for the country.
The Airbloc range has been tested and assessed for compliance with the following European Directives.
Machinery Directive: (2006/42/EC) Low Voltage Directive: (2006/95/EC) Electromagnetic Compatibility Directive: (2014/30/EU) Product Liability Directive: (85/374/EEC)
The manufacturer has taken reasonable and practical steps to ensure that Airbloc ACR Air Curtains are safe and without risk when properly used. These air curtains should only be used in the manner and purpose for which they were intended, and in accordance with the recommendations detailed herewith.
The ACR Air Curtains have been designed, manufactured, assembled, inspected, and tested, with safety and quality in mind, there are certain basic precautions which the installer and user should be aware of, and they are strongly advised to read the appropriate sections of the information pack accompanying the heater, prior to installation or use.
Nortek Global HVAC (UK) Ltd. supports all new products being supplied to their customers with a comprehensive information pack; this clearly denes mandatory instructions for the safe installation, use, and maintenance, of the appliance(s).
Where proprietary items are incorporated into Airbloc products, detailed information and instructions are also provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of such products supplied by Nortek Global HVAC (UK) Ltd., to ensure that they are familiar with the appropriate information/ manuals, supplied by the manufacturer, and that they are suitably aware of the purpose of the manuals and the safety instructions. In addition, operators must be suitably trained in
Caution is used when failure to follow or implement the instruction(s) can lead to premature failure or damage to the heater or its
component parts.
Warning is used when failure to heed or implement the instruction(s) can lead to not only component damage, but also to a hazardous
situation being created where there is a risk of personal injury.
The Airbloc ACR Recessed Air Curtain range conform to the following harmonised standards:
BS EN ISO 12100:2010 Safety of machinery. General principles for design. Risk assess-
ment and risk reduction
Safety of Machinery - Basic Concepts, General Principles for Design Technical Principles and Specications
BS EN 60204-1:2006+A1:2009 Safety of machinery. Electrical equipment of machines. Gener-
al requirements
BS EN 55014-1:2017 Electromagnetic compatibility. Requirements for household
appliances, electric tools and similar apparatus. Emission
BS EN 60335-2-102:2006+A2:2016 Household and similar electrical appliances. Safety. Particular
requirements for gas, oil and solid-fuel burning appliances having electrical connections
BS EN 60335-2-30:2009+A11:2012 Household and similar electrical appliances. Safety. Particular
requirements for room heaters and to the following European CE directives­2006/95/EC - low voltage; 2014/30/EU - electromagnetic compatibility.
Doc No. D301021 Page 5 of 64
1.2 Certicates of conformity
Certicates are available from the Quality Control Department at Nortek Global HVAC (UK) Ltd.
1.3 General product information
Models range from 1000mm to 2000mm in length, in both Standard and High capacity and are available in either Electrically heated, Ambient or LPHW. They are designed for discreet positioning in a suspended ceiling or bulkhead in the doorways of retail or commercial premises. Optional case for doorways with restricted space and no suspended ceiling/ bulkhead are available.
energy to the heating elements. This combined with the in­built intelligent sensor control, maintains a xed outlet temperature, thereby reducing energy consumption as compared to an air curtain without the SmartElec3 control.
Each air curtain is supplied with a fully electronic controller giving multi fan and heat settings (electrically operated units) via a simple key pad which can be mounted up to 100m from the air curtain.
Optional BMS time control, external, thermostats and door interlocks can be installed.
The programmer shown above allows the user to control either a single air curtain, or a network of up to 16 air curtains with the same settings, and provides the following functions:-
Heat On O or Auto via optional thermostat
O or Low, Medium and High Fan Speeds
For further details please refer to section 10.1
Alternatively on electrically heated models, the optional SmartElec3 control system consists of a base unit (installed within the air curtain) and a program panel that can be installed remote from the air curtain.
Usually, the program panel is mounted at a low level from the air curtain for user access and to a maximum distance of 100m.
The base unit and program panel are linked by a pre-wired low voltage cable as specied in these instructions.
The SmartElec3 factory tted base unit provides terminals for 3 phase supply connection and sockets the low voltage program panel cable. The SmartElec3 base unit rapidly pulses
The programmer shown above is the same as used on standard air curtains and allows the user to control either a
single air curtain, or a network of up to 16 air curtains, each with dierent settings if required, and provides the following functions:-
Heat On or O
O or Low, Medium and High Fan Speeds
Air Outlet Temperature.
For further details please refer to section 10.2
Note
Neither asbestos nor soft soldered joints are used in the construction or manufacture of the Airbloc ACR Recessed Air Curtain range. The materials selected for use can withstand the mechanical, chemical, and thermal stresses which they will be subject to during foreseen normal use when installed in accordance with the manufacturers recommendations.
1.4 Model Denitions
 ACR1000xxxx = ACR Airbloc 1M in length. 1200=1.2M;
1500=1.5M; 1800=1.8M; 2000=2.0M. ACRxxxSxxx = ACR Airbloc Standard Capacity (up to 3M
from oor); H=High Capacity(up to 4m from oor) ACRxxxxExx = ACR Airbloc Electrically heated.
A=Ambient; W=LPHW coils. ACRxxxx12 = ACR Airbloc 12kW coils. 6=6kW; 9=9kW;
12=12kW; 18kW.
-1ph sux = ACR Airbloc 230V Single phase supply (Std format =3pha)
-SM sux = ACR Airbloc SmartElec Energy Saving Controller (Std format=Standard AC/ACR Control)
e.g. ACR2000HE18-SM = ACR Airbloc Air Curtain, 2M long, 18kW electrically heated high capacity c/w SmartElec Control.
Doc No. D301021 Page 6 of 64
1.5 General requirements
Caution
Before installation, check that the local distribution conditions, nature of gas and pressure, and the current state adjustment of the appliance are compatible.
Installation and assembly procedures must be carried out by suitable competent persons. Commissioning and service procedures must be carried out by suitable qualied persons.
1.6 Health and Safety
Warning
Airbloc Air Curtains must be installed in accordance with any relevant and Regulations. Due account should be taken of any obligations arising from the Health and Safety at Works Act 1974 or relevant codes of practice. In addition the installation must be carried out in accordance with the current IEE wiring regulations and any other relevant British Standards and Codes of Practice by a qualied installer. Isolate all electrical supplies to the heater & controller before proceeding.
Warning
Unauthorised modications to the appliance, or departure from the manufacturers guidance on intended use, or, installation contrary to the manufacturers recommendations may constitute a hazard.
Note
To ignore the warning and caution notices, and to ignore the advice from the manufacturer on installation, commissioning, servicing, or use, will jeopardise any applicable warranty, moreover, such a situation could also compromise the safe and ecient running of the appliance itself, and thereby constitute a hazard.
The installation of the appliance must meet all the relevant European, national, and local criteria.
Prior to installation the following points should be considered;
The position and mounting height of the Air Curtain for the optimum ecient distribution.
The position of the Air Curtain relative to the electrical services, and any controllers.
The position of the Air Curtain relative to the low pressure hot water pipework where appropriate.
The position of the heater relative to service and maintenance requirements.
Caution
The air Curtain must not be installed within an area where the conditions are unsuitable, e.g. where the atmosphere is highly corrosive, has a high degree of salinity, or where high wind velocities may aect operation. Suitable protection should be provided for the appliance when it is located in a position where it may be susceptible to external mechanical damage.
Caution
For your own safety we recommend the use of safety boots and leather faced gloves when handling sharp or heavy items. The use of protective eye wear is also recommended.
 Sole liability rests with the installer to ensure that all site safety
procedures are adhered to during installation.
Sole liability rests with the installer to ensure that protective safety wear such as hand, eye, ear and head protection is used during installation of the product.
Do not rest anything especially ladders against the product.
1.7 Delivery and pre-installation checks.
On receipt of the Air Curtain, the following checks should be carried out;
The model is as per order.
That it is undamaged.
That it is suitable for the source gas supply.
That it is suitable for the electrical supply
If any of these points are not satised then contact should be made with the Sales Oce at Nortek Global HVAC (UK) Ltd as soon as possible by telephoning 01384 489700. In the case of claims for damage, this must be signed for as damaged and reported in writing within 24 hours of delivery, in order to comply with insurance criteria.
1.8 Location
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE THERE IS A CORROSIVE ATMOSPHERE.
Airbloc units should be installed horizontally directly over the door opening. It is recommended that the air curtain is installed on the inside of the building, within the open room space within the ceiling void or roof space.
Doc No. D301021 Page 7 of 64
Care must be taken to allow complete free air movement into the inlet grilles of the unit to ensure correct working operation of the air curtain. The discharge opening should be as close to the top of the door as possible and to cover the entire door width.
Remote unit is wired to the base unit via a pre-wired cable tted with RJ45 plugs.
1.10.2 SmartElec3 controller
Units can be mounted adjacent to each other to cover the full door opening across wider entrances.
1.9 Clearance distances
It is recommended that a minimum clearance of 100mm is allowed around the case. The clearance allows for cable entry and prevents combustible surfaces overheating.
The minimum mounting height (oor to grille) is 1.8m. The recommended maximum mounting height is 3m for standard and 4m for high capacity models.
1.10 Electrical Supply
For full electrical loadings, please refer to the individual technical data sheets within this manual.
It is recommended that the electrical supply to the base unit in the air curtain is via an appropriate switched isolator in accordance with the regulations in force in the country of use and must be via a fused isolator having a contact separation of greater than 3mm in all poles.
Electrically heated supply is 415V 3 phase, neutral and earth. Max cable inlet size is 10mm².
Keypad is wired to the base unit via a RJ45 pre-wired cable.
Networked air curtain interconnects via a RJ45 pre-wired cable.
BMS control, time switches, room thermostats and door interlocks can be installed at the discretion and responsibility of the installer.
All units must be wired in accordance with I.E.E regulations for the Electrical Equipment of Buildings and the installer should ensure that a suitable isolating switch is connected in the mains supply.
Warning
For safety reasons a good earth connection must ALWAYS be made to the heater and control box.
1.10.1 Ele ctronic co ntrol ler
Electrically heated supply is either 230V 1 phase (6 and 9kW options) or 415V 3 phase (9 to 18kW), Neutral and Earth. Max cable inlet size is 4mm² or 10mm² (refer to individual technical specication)
Ambient and LPHW supply is 230V 1 phase, Neutral and Earth. Max cable inlet size is 4mm².
Doc No. D301021 Page 8 of 64
2. Dimensions.
2.1 ACR Air Curtain Fig.1
DIM 'C'
DIM 'E'
DIM 'J'
DIM 'H'
DIM 'F'
DIM 'G'
DIM 'B'
DIM 'D'
DIM 'A'
ACR1000SE6/9;
Size
A 253 407
B 1220 1520 2020 1185 1785 2097
C 1182 1482 1982 115 0 1750 2059
D 395 550
E 454 608
F 1205 1505 2005 1150 1750 2082
G 1242 1542 2095 1210 1810 2140
H 160 180
J 200 220
ACR1000SW9;
ACR1000SA
ACR1500SE12;
ACR1500SW12;
ACR1500SA
ACR2000SE18;
ACR2000SW18;
ACR2000SA
ACR1200HE12;
ACR1200HW12;
ACR1200HA
ACR1800HE18;
ACR1800HW18;
ACR1800HA
Doc No. D301021 Page 9 of 64
ACR2000HE18;
ACR2000HW18;
ACR2000HA
2.2 Program keypad dimensions
The keypad is supplied with an industry standard plastic double surface mounted socket box. Alternatively the keypad can be ush mounted using a customer supplied metal ush box as shown below.
Fig.2. Using surface mount box
148
87
120 crs
43,5
Fig.3. Optional ush mount using metal conduit box
Doc No. D301021 Page 10 of 64
3. Technical Specications.
3.1 (Single Phase only) ACR1000SE6-1PH ACR1500SE6-1PH ACR2000SE9-1PH
General Data
Maximum height M 3.0 Door width 1.2 1.5 2.0 Heat Medium kW Electrical heated Heat settings 3 / 6 4.5 / 9 Fan type / dia Crossow / 100mm Fan settings 3 Speeds Switching type 3 tactile pushbuttons Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 230V 1ph 50Hz Total load kW (a) 6.1 (26.5) 9.1 (39.6) Motor power W 60 90 Max Starting current* amps 0.96 1.5 Max Running current* amps 0.65 0.75 External fuse size amps amps 32 45 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 10.0mm² MAX Mains terminal block position Top of PCB (L1, N,E) RJ45 socket position Centre of PCB (opposite mains input terminals)
Air Data
Low speed m³/ h 116 4 1475 2013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free eld
Dimensional Data
Length mm 1182 1482 1982 Depth (width) mm 395 Total height mm 200 Outlet length mm 112 5 1425 1945 Outlet depth (width) mm 85 Grille height mm 40 Mounting bracket centres length mm 1220 1520 2020 Side to 1st bracket centre mm 18 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
* Motor current only at high speed
Medium speed m³/h 1405 178 0 2432 High speed m³/h 1646 2085 2851 Low @ 0M m/s 4.3 5.4 Medium @ 0M m/s 5.6 6.9 High @ 0M m/s 7.0 8.4 High @ 1M m/s 3.5 4.2 High @ 2M m/s 1.6 2.1 High @ 3M m/s 0.8 1.0 Low speed °C 17 13 26 Medium speed °C 15 11 23 High speed °C 13 9 20 Low speed dBA 59 Medium speed dBA 62 High speed dBA 64
Doc No. D301021 Page 11 of 64
3.2 ACR1000SE9 ACR1500SE12 ACR2000SE18
General Data
Maximum height M 3.0 Door width 1.2 1.5 2.0 Heat Medium kW Electrical heated Heat settings 4.5 / 9 6 / 12 9 / 18 Fan type / dia Crossow / 100mm Fan settings 3 speeds Switching type 3 tactile pushbuttons Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 415V 3ph 50Hz Total load kW (a) 9.1 (12.6) 12.1 (16. 8) 18.1 (25. 2) Motor power W 60 90 Max Starting current* amps 0.96 1.5 Max Running current* amps 0.65 0.75 External fuse size amps amps 16 20 32 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required)
Cable terminal size 10.0mm² MAX Mains terminal block position Top of PCB (L1, L2, L3, N, E)
RJ45 socket position Centre of PCB (opposite mains input terminals) ** SmartElec3 Energy Saving Control 108221-RJ45
SmartElec3 Energy Saving Control wiring RJ45 (pre-wired cable required) Cable terminal size 10.0mm² Max Mains terminal block position Top of PCB ( L1, L2, L3, N, E) RJ45 socket position Centre of PCB (opposite mains input terminals)
Air Data
Low speed m³/ h 1164 1475 2013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free eld
Medium speed m³/ h 1405 178 0 2432 High speed m³/ h 1646 2085 2851 Low @ 0M m/s 4.3 5.4 Medium @ 0M m/s 5.6 6.9 High @ 0M m/s 7. 0 8.4 High @ 1M m/s 3.5 4.2 High @ 2M m/s 1.6 2.1 High @ 3M m/s 0.8 1.0 Low speed °C 26 25 21 Medium speed °C 23 22 20 High speed °C 20 19 19 Low speed dBA 59 Medium speed dBA 62 High speed dBA 64
Dimensional Data
Length mm 1182 14 82 1982 Depth (width) mm 395 Total height mm 200 Outlet length mm 1125 1425 1945 Outlet depth (width) mm 85 Grille height mm 40 Mounting bracket centres length mm 1220 1520 2020 Side to 1st bracket centre mm 18 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
* Motor current only at high speed **Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 12 of 64
3.3 ACR1200HE12 ACR1800HE18 ACR2000HE18
General Data
Maximum height M 4.0 Door width 1.2 1.8 2.0 Heat Medium kW Electrical heated Heat settings 6 / 12 9 / 18 Fan type / dia Crossow / 100mm Fan settings 3 speeds Switching type 3 tactile pushbuttons Weight kg 38.0 55.0 63.0
Electrical Data
Supply voltage 415V 3ph 50Hz Total load kW (a) 12.4 (17.3) 18.4 (25.6) Motor power W 370 Max Starting current* amps 5.0 Max Running current* amps 2.1 External fuse size amps amps 20 32 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 10.0mm² MAX Mains terminal block position Top of PCB ( L1, L2, L3, N, E) RJ45 socket position Centre of PCB (opposite mains input terminals) ** SmartElec3 Energy Saving Control 108221-RJ45 SmartElec3 Energy Saving Control wiring RJ45 (pre-wired cable required) Cable terminal size 10.0mm² Max Mains terminal block position Top of PCB (L1, L2, L3, N, E) RJ45 socket position Centre of PCB (opposite mains input terminals)
Air Data
Low speed m³/ h 130 0 1600 2900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free eld
Medium speed m³/ h 1850 2400 4100 High speed m³/ h 2300 3300 5000 Low @ 0M m/s 6.0 Medium @ 0M m/s 8.5 High @ 0M m/s 11. 0 High @ 1M m/s 5.4 5.5 5.2 High @ 2M m/s 3.6 3.7 3.6 High @ 3M m/s 2.6 2.5 2.4 High @ 4M m/s 1.5 1.6 1.4 Low speed °C 35 36 Medium speed °C 28 27 26 High speed °C 22 20 Low speed dBA 50 Medium speed dBA 55 High speed dBA 60
Dimensional Data
Length 1150 1750 2082 Depth (width) 550 Total height 227 Outlet length 1090 1690 2022 Outlet depth (width) 85 Grille height 6 Mounting bracket centres length 1185 1785 2117 Side to 1st bracket centre 17. 5 Mounting bracket centres height Flush with top of unit Top to 1st bracket centre Flush with top of unit
* Motor current only at high speed **Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 13 of 64
3.4 ACR1000SA ACR1500SA ACR2000SA
General Data
Maximum height M 3.0 Door width 1.2 1.5 2.0 Heat Medium kW Ambient Fan type / dia Crossow / 100mm Fan settings 3 Switching type 3 tactile pushbuttons Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 230V 1ph 50Hz Total load kW (a) 0.06 (0.26) 0.09 (0.4) Motor power W 60 90 Max Starting current* amps 0.96 1.5 Max Running current* amps 0.65 0.75 External fuse size amps amps 3 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 1.5mm² MAX Mains terminal block position Top right of PCB (L1, N, E) RJ45 socket position Right hand side of PCB (below mains input terminals)
Air Data
Low speed m³/ h 1164 1475 2013
Air Volume
Air Velocity
Noise level @ 1M in free eld
Medium speed m³/ h 1405 178 0 2432 High speed m³/ h 1646 2085 2851 Low @ 0M m/s 4.3 5.4 Medium @ 0M m/s 5.6 6.9 High @ 0M m/s 7. 0 8.4 High @ 1M m/s 3.5 4.2 High @ 2M m/s 1.6 2.1 High @ 3M m/s 0.8 1.0 Low speed dBA 59 62 Medium speed dBA 62 64 High speed dBA 64 66
Dimensional Data
Length mm 1182 14 82 1982 Depth (width) mm 395 Total height mm 200 Outlet length mm 1125 1425 1945 Outlet depth (width) mm 85 Grille height mm 40 Mounting bracket centres length mm 1220 1520 2020 Side to 1st bracket centre mm 18 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 14 of 64
3.5 ACR1200HA ACR1800HA ACR2000HA
General Data
Maximum height M 4.0 Door width 1.2 1.8 2.0 Heat Medium kW Ambient Fan type / dia Crossow / 100mm Fan settings 3 Switching type 3 tactile pushbuttons Weight kg 38.0 55.0 63.0
Electrical Data
Supply voltage 230V 1ph 50Hz Total load kW (a) 0.4 (1.61) Motor power W 370 Max Starting current* amps 5.0 Max Running current* amps 2.1 External fuse size amps amps 10 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 1.5mm² MAX
Mains terminal block position Top right of PCB (L1, N, E)
RJ45 socket position Right hand side of PCB (below mains input terminals)
Air Data
Low speed m³/ h 130 0 1600 2900
Air Volume
Air Velocity
Noise level @ 1M in free eld
Medium speed m³/ h 1850 2400 4100 High speed m³/ h 2300 3300 5000 Low @ 0M m/s 6.0 Medium @ 0M m/s 8.5 High @ 0M m/s 11. 0 High @ 1M m/s 5.4 5.5 5.2 High @ 2M m/s 3.6 3.7 3.6 High @ 3M m/s 2.6 2.5 2.4 High @ 4M m/s 1.5 1.6 1.4 Low speed dBA 50 Medium speed dBA 55 High speed dBA 60
Dimensional Data
Length mm 1150 1750 2082 Depth (width) mm 550 Total height mm 227 Outlet length mm 1090 1690 2022 Outlet depth (width) mm 85 Grille height mm 6 Mounting bracket centres length mm 1185 1785 2117 Side to 1st bracket centre mm 17.5 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 15 of 64
3.6 ACR1000SW9 ACR1500SW12 ACR2000SW18
General Data
Maximum height M 3.0 Door width 1.2 1.5 2.0 Heat Medium kW LPHW Heat settings 9 12 18 Fan type / dia Crossow / 100mm Fan settings 3 Switching type 3 tactile pushbuttons Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 230V 1ph 50Hz Total load kW (a) 0.06 (0.26) 0.09 (0.4) Motor power W 60 90 Max Starting current* amps 0.96 1.5 Max Running current* amps 0.65 0.75 External fuse size amps amps 3 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 1.5mm² MAX Mains terminal block position Top right of PCB (L1, N, E) RJ45 socket position Right hand side of PCB (below mains input terminals)
Air Data
Low speed m³/ h 1164 1475 2013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free eld
Medium speed m³/ h 1405 178 0 2432 High speed m³/ h 1646 2085 2851 Low @ 0M m/s 4.3 5.4 Medium @ 0M m/s 5.6 6.9 High @ 0M m/s 7. 0 8.4 High @ 1M m/s 3.5 4.2 High @ 2M m/s 1.6 2.1 High @ 3M m/s 0.8 1.0 Low speed °C 26 25 21 Medium speed °C 23 22 20 High speed °C 20 19 19 Low speed dBA 59 62 Medium speed dBA 62 64 High speed dBA 64 66
LPHW Data
LPHW ow l/s 0.20 0.40 Fluid pressure drop kPA 3.8 17.6 20 Flow & return connection mm 15 22 Inlet temperature °C 82 Outlet temperature °C 71
Dimensional Data
Length mm 1182 14 82 1982 Depth (width) mm 395 Total height mm 200 Outlet length mm 1125 1425 1945 Outlet depth (width) mm 85 Grille height mm 40 Mounting bracket centres length mm 1220 1520 2020 Side to 1st bracket centre mm 18 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
Doc No. D301021 Page 16 of 64
3.7 ACR1200HW12 ACR1800HW18 ACR2000HW18
General Data
Maximum height M 4.0 Door width 1.2 1.8 2.0 Heat Medium kW LPHW Heat settings 12 18 Fan type / dia Crossow / 100mm Fan settings 3 Switching type 3 tactile pushbuttons Weight kg 38.0 55.0 63.0
Electrical Data
Supply voltage 230V 1ph 50Hz Total load kW (a) 0.4 (1.6) Motor power W 370 Max Starting current* amps 5.0 Max Running current* amps 2.1 External fuse size amps amps 10 Programmer keypad pt.no. 108221-RJ45 Program keypad control wiring RJ45 (pre-wired cable required) Cable terminal size 1.5mm² MAX Mains terminal block position Top right of PCB (L1, N, E) RJ45 socket position Right hand side of PCB (below mains input terminals)
Air Data
Low speed m³/ h 130 0 1600 2900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free eld
Medium speed m³/ h 1850 2400 4100 High speed m³/ h 2300 3300 5000 Low @ 0M m/s 6.0 Medium @ 0M m/s 8.5 High @ 0M m/s 11. 0 High @ 1M m/s 5.4 5.5 5.2 High @ 2M m/s 3.6 3.7 3.6 High @ 3M m/s 2.6 2.5 2.4 High @ 4M m/s 1.5 1.6 1.4 Low speed °C 35 36 Medium speed °C 28 27 26 High speed °C 22 20 Low speed dBA 50 Medium speed dBA 55 High speed dBA 60
LPHW Data
LPHW ow l/s 0.27 0.40 0.40 Fluid pressure drop kPA 19 23 15 Flow & return connection mm 15 Inlet temperature °C 82 Outlet temperature °C 71
Dimensional Data
Length mm 1150 1750 2082 Depth (width) mm 550 Total height mm 227 Outlet length mm 1090 1690 2022 Outlet depth (width) mm 85 Grille height mm 6 Mounting bracket centres length mm 1185 1785 2117 Side to 1st bracket centre mm 17.5 Mounting bracket centres height mm Flush with top of unit Top to 1st bracket centre mm Flush with top of unit
Doc No. D301021 Page 17 of 64
3.8 Standard Program Controls
General Data
Sensor Input NTC
Protection 1 x 1A fuse for the protection of the fan switching devices.
Fan Output 3 o Relay for High, Medium and Low Fan setting 3A max 230vac
Screw terminals 4 for supply, 6 for elements output, 4 for fan output, 2 for
Connections
Supply 415 3Ph or 230V 1Ph dependent on model type.
Dimensions Program panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push Buttons 3 positive feedback tactile push buttons
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for ex­ternal door switch, 2 for 0-10v fan option, 2 for 0-5v fault output, 2 for lter blocked, 2 for unit temperature.
3.9 SmartElec3 Controls
General Data
Sensor Input NTC
Control Setpoint 16 to 35 ºC in steps of 1 degree
Temperature Control Proportional with 1ºC hysteresis
Minimum Power 0% to 99 %
Cycle Time 2 seconds xed
Protection 2 x high speed fuse for the protection of the heater switching devices
Fan Output 3 o Relay for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 5 for supply, 3 for heater output, 4 for fan output, 2 for BMS
Connections
Supply 415V AC 50/60Hz 5VA max.
Dimensions Program panel 146mm(L) x 85mm(W) x 38mm(D) max.
(time) control, 2 for sensor input, 2 for external thermal trip, 2 for external sensor, 2 for door, 2 for cooling fan on 24kW models. RJ45 comms connection to base unit via pre-wired cable.
Mounting Positions Program panel xing centres 80mm x 20mm
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push Buttons 3 positive feedback tactile push buttons
Doc No. D301021 Page 18 of 64
3.10 LPHW/Ambient Controls
General Data
Sensor Input NTC
Control Setpoint 16 to 35 ºC in steps of 1 degree
Temperature Control 0-10v valve output (proportional)
Cycle Time 2 seconds xed
Protection 1 x 1A fuse for the protection of the mains input
Fan Output 3 o Relays for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 3 for mains supply, 4 for fan output, 2 for BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for external
Connections
Supply 230 V 50/60Hz.
Dimensions Program panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
sensor, 2 for door., 2 for 0-10v motor drive, 2 for 0-10v fan option, 2 for 0-5v fault output, 2 for pipe cold input, 2 for unit temperature input, RJ45 comms connection to base unit via pre-wired cable.
Display Three 7-segment LCD red for parameter display
Push Buttons 3 positive feedback tactile push buttons
Doc No. D301021 Page 19 of 64
4. Wiring Diagrams.
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
230v 50hZ
4.1 Installer Wiring - Electrically Heated 6 & 9kW SINGLE PHASE ONLY
he program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
T
trunking to avoid external interference. External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked eg. ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
It is recommended that this cable is run separately within its own
Mains Supply
FAN
L1
3 N
1 2
BASE UNIT
(located in air curtain)
ON
1 2 3 4
Pre-wired RJ45 plugs
& lead
SELECT
HE
HE HE HE
L2
B
A
RS485 Comms
HE HE
A B
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
L3
SYS
TEMP
FAN
External
FAULT
A B
FILTER
TIMER
STAT
N
DOOR
EXT
Pressure
Switch
External
Switch
(BMS)
Remove appropriate link before connecting any optional switches
CHASSIS
EARTH
Sensor
Programmer
Keypad
Terminal Description Cable
N Neutral
10mm² max
L1 Phase 1 (or 1 Phase supply)
Pcb Terminal Description Cable
Door Option door contact
1.5mm² max
Timer BMS Option external switch
Protection
External circuit breaker with the appropriate rating should be installed for the protection of the installation.
Doc No. D301021 Page 20 of 64
Door
Switch
900640 CWL R1
PCB Terminal Description Cable
Ext Option internal/external sensor (supplied)
Filter block Option lter blocked switch
Fail o/p Fault output (0-5v)
1.5mm² max
Fan Option 0-10v fan output
Pcb Fuses Rating (A)
F1 T1H (slow blow)
4.2 Installer Wiring - Electrically Heated 9, 12 & 18kW THREE PHASE ONLY
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’ (contacts closed to enable). Remove relevant factory tted jumper for any optional input.
415v 3 ph + N 50hZ
Mains Supply
FACTORY
INSTALLED
FAN
L1
3
N
1 2
BASE UNIT
(located in air curtain)
ON
2 3 4
1
HE
A B
HE
RS485 Comms
HE
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
B
SYS
TEMP
L3
FAN
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
EARTH LINK.
DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
SELECT
Programmer
Keypad
Terminal Description Cable
N Neutral
L1 Phase 1
10mm² max
L2 Phase 2
L3 Phase 3
Pcb Terminal Description Cable
Door Option door contact
1.5mm² max
Timer/BMS Option external switch
External
Pressure
Switch
Sensor
External
Switch
(BMS)
Remove appropriate link before connecting any optional switches
Door
Switch
900641 CWL
PCB Terminal Description Cable
Ext Option internal/external sensor (supplied)
Filter block Option lter blocked switch
Fail o/p Fault output (0-5v)
Fan Option 0-10v fan output
Pcb Fuses Rating (A)
F1 T1H (slow blow)
1.5mm² max
Protection
External circuit breaker with the appropriate rating should be installed for the protection of the installation.
Doc No. D301021 Page 21 of 64
4.3 Installer Wiring - Ambient
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’ (contacts closed to enable). Remove relevant factory tted jumper for any optional input.
BASE UNIT
(located in air curtain)
N
OUTPUT
STAT
TIMER
RETURN
DOOR
AIR
PIPE
COLD
EXT
N L E
RS485 Comms
230v 1ph + N 50hZ Mains Supply
CHASSIS
EARTH
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
AIR
OUTLET
VALVE
FAN
3
2
1
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL
ON
2 3 4
1
FAN
0-10v
0-10v
FILTER
FAULT
Remove appropriate link before connecting any optional switches
External
Switch
(BMS)
Door
Switch
Terminal Description Cable
N Neutral L 1 Phase supply
Pcb Terminal Description
Door Option door contact Timer BMS Option external switch
Ext Option internal/external sensor (supplied)
1.5mm² max
SELECT
Programmer
Keypad
Terminal Description Cable
Filter block Option lter blocked switch Fail o/p Fault output (0-5v) Fan 0 -10v Option 0-10v fan output Valve 0-10v Option 0-10v valve output
Pcb Fuses Rating (A)
F1 T1H (slow blow)
900638 CWL
1.5mm² max
Doc No. D301021 Page 22 of 64
Protection
External circuit breaker with the appropriate rating should be installed for the protection of the installation.
4.4 Installer Wiring - LPHW
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’ (contacts closed to enable). Remove relevant factory tted jumper for any optional input.
BASE UNIT
(located in air curtain)
N
OUTPUT
STAT
TIMER
RETURN
DOOR
AIR
PIPE
COLD
EXT
N L E
RS485 Comms
230v 1ph + N 50hZ Mains Supply
CHASSIS
EARTH
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
AIR
OUTLET
VALVE
FAN
3
2
1
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL
ON
2 3 4
1
FAN
0-10v
0-10v
FILTER
FAULT
Modulating
Valve
Remove appropriate
External
Pressure
link before connecting any optional switches
Switch
External
Switch
(BMS)
Door
Switch
Terminal Description Cable
N Neutral L 1 Phase supply
Pcb Terminal Description
Door Option door contact Timer BMS Option external switch Ext Option internal/external sensor (supplied) Air return Option sensor
1.5mm² max
Sensor
SELECT
Programmer
Keypad
Terminal Description Cable
Pipe cold Option sensor Fail o/p Fault output (0-5v) Fan Option 0-10v fan output Valve Option 0-10v valve output Filter block Option lter blocked switch
Pcb Fuses Rating (A)
F1 T1H (slow blow)
Protection
External circuit breaker with the appropriate rating should be installed for the protection of the installation.
900639 CWL
1.5mm² max
Doc No. D301021 Page 23 of 64
4.5 Factory Wiring - Electrically heated ACR1000/ACR1500 6kW SINGLE PHASE ONLY
R(B)
L(M)
L(B)
R(M)
L(T)
Elements
Fan Motor
BASE UNIT
(located in air curtain)
900658 IWL
23N
1
FAN
ON
2 3 4
1
Outlet
Sensor
L1
HE
HE
B
A
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
RS485 Comms
Overheat 1
HE
B
SYS
TEMP
Overheat 2
FAN
L3
FAULT
HE
A
HE
B
FILTER
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
Sensor
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
The element output is connected to the terminal blocks marked “L1 A”, “L2 A&B”, L3 A&B” “N”
The fan output is connected to a 4 way connector marked “Fan 1, 2, 3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
Terminal Description
N Neutral L 1 Phase supply L1A ,L 2 A&B 2 thirds heating elements L3 A&B 1 third heating elements
Pcb Terminal Description
Stat Thermal overheat trip Ext Option internal/external sensor (supplied) Fan 1 Fan - Low speed Fan 2 Fan - medium speed Fan 3 Fan - high speed Filter Factory link Timer Factory link Door Factory link
Doc No. D301021 Page 24 of 64
4.6 Factory Wiring - Electrically heated ACR2000 9kW SINGLE PHASE ONLY
R(B)
L(M)
L(B)
R(M)
L(T)
Elements
Fan Motor
900659 IWL
L1
3
N
2
1
FAN
BASE UNIT
(located in air curtain)
ON
2 3 4
1
Outlet
Sensor
HE
HE
B
A
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
RS485 Comms
Overheat 1
HE
B
SYS
TEMP
Overheat 2
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
Sensor
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
The element output is connected to the terminal blocks marked “L1 A”, “L2 A&B”, L3 A&B”
The fan output is connected to a 4 way connector marked “Fan 1, 2, 3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
Terminal Description
N Neutral L 1 Phase supply L1A ,L 2 A&B 2 thirds heating elements L3 A&B 1 third heating elements
Pcb Terminal Description
Stat Thermal overheat trip Ext Option internal/external sensor (supplied) Fan 1 Fan - Low speed Fan 2 Fan - medium speed Fan 3 Fan - high speed Filter Factory link Timer Factory link Door Factory link
Doc No. D301021 Page 25 of 64
4.7 Factory Wiring - Electrically heated ACR1000/ACR1500 9 & 12kW THREE PHASE ONLY
Elements
Fan Motor
BASE UNIT
(located in air curtain)
900660 IWL
3
2
1
FAN
ON
2 3
4
1
Outlet
Sensor
FACTORY
INSTALLED
EARTH LINK.
CHASSIS
EARTH
DO NOT REMOVE
HE
HE
L1
B
A
N
RS485 Comms
HE
HE
L2
B
A
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
SYS
TEMP
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
900641 CWL
Sensor
Overheat 1
Overheat 2
The element output is connected to the right and left side of each terminal block marked “HE A” & “HE B”
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
Terminal Description
L1,L2 & L3 HE A One half of heating elements
L1,L2 & L3 HE B Second half of heating elements
Pcb Terminal Description
Stat Thermal Overheat trip
Ext Option internal/external sensor (supplied)
N Neutral
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Filter Factory link
Timer Factory link
Door Factory link
Doc No. D301021 Page 26 of 64
4.8 Factory Wiring - Electrically heated ACR1200/1800/2000 HE 12 & 18kW ACR 2000 SE 18kW THREE PHASE ONLY
Elements
HE
Fan Motor
L1
3
N
1 2
FAN
BASE UNIT
(located in air curtain)
ON
2 3 4
1
HE
B
A
RS485 Comms
HE
HE
L2
B
A
FAULT = OPTIONAL 5vDC OUTPUT FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
SYS
TEMP
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
900661 IWL
Outlet
Sensor
Overheat 1
The element output is connected to the right and left side of each terminal block marked “HE A” & “HE B”
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
Sensor
Overheat 2
Terminal Description
L1,L2 & L3 HE A One half of heating elements
L1,L2 & L3 HE B Second half of heating elements
Pcb Terminal Description
Stat Thermal Overheat trip
Ext Option internal/external sensor (supplied)
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Filter Factory link
Timer Factory link
Door Factory link
Doc No. D301021 Page 27 of 64
4.9 Factory Wiring - Ambient ACR1000SA/ACR1500SA
Fan Motor
BASE UNIT
(located in air curtain)
3
N
2
1
FAN
ON
2 3 4
1
AIR
OUTLET
VALVE
0-10v
FAN
0-10v
FAULT
FILTER
TIMER
STAT
RETURN
DOOR
AIR
PIPE
COLD
EXT
FACTORY INSTALLED EARTH LINK.
N L E
RS485 Comms
DO NOT REMOVE
CHASSIS
EARTH
FACTORY INSTALLED
SENSOR (EXT) OPTIONAL,
DISCONNECT IF NOT
Sensor
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The motor thermal trip is connected to a 2 way connector marked “Stat”
900656 IWL
REQUIRED
Sensor
Pcb Terminal Description
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Filter Factory link
Timer Factory link
Door Factory link
Stat Motor thermal trip
Doc No. D301021 Page 28 of 64
Ext Option internal/external sensor (supplied)
Air outlet Air outlet sensor
4.10 Factory Wiring - Ambient ACR1200HA/ACR1800HA/ACR2000HA ACR2000SA
BASE UNIT
(located in air curtain)
Fan Motor
ON
1
2 3 4
1
2
FAN
3
N
N L E
RS485 Comms
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
CHASSIS
EARTH
AIR
OUTLET
VALVE
0-10v
FAN
0-10v
FILTER
FAULT
TIMER
FACTORY INSTALLED SENSOR (EXT) OPTIONAL, DISCONNECT IF NOT REQUIRED
Sensor
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
STAT
RETURN
DOOR
AIR
PIPE
COLD
EXT
Sensor
Pcb Terminal Description
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
900657 IWL
Filter Factory link
Timer Factory link
Door Factory link
Ext Option internal/external sensor (supplied)
Air outlet Air outlet sensor
Doc No. D301021 Page 29 of 64
4.11 Factory Wiring - LPHW ACR1000SW/ACR1500SW
Fan Motor
BASE UNIT
(located in air curtain)
3
N
2
1
FAN
ON
2 3 4
1
AIR
OUTLET
VALVE
0-10v
FAN
0-10v
FAULT
FILTER
TIMER
STAT
RETURN
DOOR
AIR
PIPE
COLD
EXT
FACTORY INSTALLED EARTH LINK.
N L E
RS485 Comms
DO NOT REMOVE
CHASSIS
EARTH
Sensor
900662 IWL
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The motor thermal trip is connected to a 2 way connector marked “Stat”
Sensor
Sensor
FACTORY INSTALLED SENSORS (AIR RETURN, PIPE COLD, EXT) OPTIONAL, DISCONNECT IF NOT REQUIRED
Sensor
Pcb Terminal Description
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Filter Factory link
Timer Factory link
Door Factory link
Stat Motor thermal trip
Air return Sensor (supplied)
Pipe cold Sensor (supplied)
Doc No. D301021 Page 30 of 64
Ext Option internal/external sensor (supplied)
Air outlet Air outlet sensor
4.12 Factory Wiring - LPHW ACR1200HW/ACR1800HW/ACR2000HW ACR2000SW18
BASE UNIT
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
CHASSIS
EARTH
Fan Motor
(located in air curtain)
3
N
2
1
FAN
ON
2 3 4
1
N L E
RS485 Comms
AIR
OUTLET
Sensor
900645 IWL
VALVE
0-10v
FAN
0-10v
FAULT
FILTER
TIMER
STAT
Sensor
RETURN
DOOR
AIR
PIPE
COLD
EXT
Sensor
FACTORY INSTALLED
FACTORY INSTALLED SENSOR (EXT) OPTIONAL,
SENSORS (EXT,
DISCONNECT IF NOT
PIPE COLD, AIR RE TURN )
REQUIRED
OPTIONAL, DISCONNECT
Sensor
IF NOT REQUIRED
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
Pcb Terminal Description
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Filter Factory link
Timer Factory link
Door Factory link
Air return Sensor (supplied)
Pipe cold Sensor (supplied)
Ext Option internal/external sensor (supplied)
Air outlet Air outlet sensor
Doc No. D301021 Page 31 of 64
4.13 Network Wiring - Ambient/LPHW
AIR
OUTLET
External
Switch
(BMS)
Switch
AIR
OUTLET
VALVE
0-10v
Door
VALVE
0-10v
(located in air curtain 1)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
(located in air curtain 2)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
STAT
DOOR
STAT
DOOR
Programmer
Keypad
SELECT
AIR
EXT
RETURN
PIPE
COLD
AIR
EXT
RETURN
PIPE
COLD
N L E
RS485 Comms
N L E
RS485 Comms
Sensor
Pre-wired RJ45 plugs
& leads
Networking
This diagram refers only to the wiring of 2 or more networked air curtains. (maximum 16 air curtains per control panel). For mains wiring refer to section 4 of this manual ‘installer wiring details’.
The program panel is connected to the base unit in the rst air curtain via pre-wired lead tted with RJ45 plugs.
Each subsequent air curtain is wired with the same type of lead.
Max length 100m. (Total length of cable
used between program panel and last air curtain in network).
It is recommended that this control cable is run separately within its own trunking if possible to avoid external interference.
Note: All air curtains connected within the network system can be controlled under the user settings of the single keypad.
For more information on setup and control please refer to section 10 ‘User and Operating Instructions’.
External
Switch
(BMS)
Switch
AIR
OUTLET
External
Switch
(BMS)
Door
VALVE
0-10v
(located in air curtain 3)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
STAT
DOOR
AIR
RETURN
PIPE
COLD
EXT
Sensor
N L E
RS485 Comms
To subsequent air curtains
(maximum of 16 )
Sensor
ON AN INDIVIDUAL BASIS!
Doc No. D301021 Page 32 of 64
4.14 Network Wiring - Electrically heated
Sensor
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 1)
External
Pressure
Remove appropriate link
Door
Switch
(BMS)
Switch
External
Switch
Networking
This diagram refers only to the wiring of 2 or more networked air curtains. (maximum 16 air curtains per control panel). For mains wiring refer to section 4 of this manual ‘installer wiring details’.
The program panel is connected to the base unit in the rst air curtain via pre-wired lead tted with RJ45 plugs.
RS485 Comms
Each subsequent air curtain is wired with the same type of lead.
& lead
Sensor
Pre-wired RJ45 plugs
SELECT
Max length 100m. (Total length of cable
used between program panel and last air curtain in network).
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 2)
External
Pressure
Remove appropriate link
Keypad
Programmer
It is recommended that this control cable is run separately within its own trunking if possible to avoid external interference.
Door
Switch
(BMS)
Switch
External
Switch
Note: All air curtains connected within the network system can be controlled under the user settings of the single keypad.
RS485 Comms
For more information on setup and control please refer to section 10 ‘User and Operating Instructions’.
Sensor
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 3)
RS485 Comms
External
Pressure
Remove appropriate link
Door
Switch
(BMS)
Switch
External
Switch
Doc No. D301021 Page 33 of 64
4.15 Installer wiring SmartElec3 control.
BASE UNIT
(located in air curtain)
415v 50Hz
MAINS SUPPLY
CHASSIS EARTH
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
Sensor
Optional
Sensor
Door
Switch
Programmer
Keypad
SELECT
3
N
2
1
FAN
L1
terminals as
supplied
Pre-wired RJ45 cable
and plugs
900643 CWL
ON
1
2 3 4
TIMER
HE
L2
DOOR
J2J1
B.M.S.
Enable
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
N
DOOR
EXT
Interconnecting wiring
The program panel is connected to the base unit via a pre-wired RJ45 cables as shown and supplied in 2, 10, 20, 30, 50 and 100m lengths.
It is recommended that this control cable is run separately within its own trunking where possible to avoid external
interference.
Optional wiring External switch (ie BMS enable) to be volt free and wired via normally open contacts to terminal pair ‘ TI M E R’. (Contacts closed
to enable). Remove factory tted jumper J1.
Door switch to be volt free and wired via normally closed contacts to terminal pair ‘DOOR’. (Contacts open to enable door mode). Remove factory tted jumper. refer section 10.2.6.1 - Door link settings.
Internal/external sensor to be wired to terminal pair ‘EXT’. refer section 10.2.6.4 - External Temperature.
Protection
There are two high speed fuses on the base unit to protect the switching thyristors for the heater. An external circuit breaker with the appropriate rating should be installed for the protection of the installation.
Terminal Description Cable
N Neutral
L1 3 Phase supply
L2 3 Phase supply
10mm² max
L3 3 Phase supply
E Mains Earth
Timer BMS pair (volt -free)
Door Door interlock pair, n.c. (volt free)
1.5mm² max
Ext Option internal/external sensor pair (supplied)
Doc No. D301021 Page 34 of 64
4.16 Factory Installed Wiring. ACR1000/ACR1500 with SmartElec3 Control.
Fan motor
3
N
2
1
FAN
L1
BASE UNIT
(located in air curtain)
HE
L2
ON
2 3 4
1
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
N
DOOR
EXT
INSTALLED
EARTH LINK.
DO NOT REMOVE
CHASSIS EARTH
FACTORY
900653 IWL
Outlet
Sensor
The heater element outputs are connected to the right hand side of three terminal blocks and are marked ‘HE’. (See below).
The fan output is connected to a 4 way terminal block marked ‘N, 1, 2 and 3’.
The sensor input (air sensor) is connected to 2 terminals marked ‘TEMP’ on the base unit. The sensor is not polarity sensitive.
The external thermal trip (volt-free) is connected to 2 terminals marked ‘STAT’ on the base unit. The terminals are not polarity sensitive.
J1
J2
Sensor
Optional
Sensor
q
Overheat 1qOverheat 2
Terminal Description Cable
HE Heating elements phase 1
HE Heating elements phase 2
HE Heating elements phase 3
N Neutral to fan
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
Tem p Air sensor pair (non-polarised)
Stat Ext thermal trip pair, n.c. (volt-free)
Ext Option internal/external sensor (supplied)
Comms Keypad/network connectors RJ45
10mm² max
1.5mm² max
Doc No. D301021 Page 35 of 64
4.17 Factory Installed Wiring. ACR1200/ACR1800HE/ACR2000HE with SmartElec3 Control
Fan motor
FACTORY INSTALLED EARTH LINK. DO NOT REMOVE
3
N
2
1
FAN
L1
HE
L2
BASE UNIT
(located in air curtain)
ON
2 3 4
1
900663 IWL
Outlet
Sensor
The heater element outputs are connected to the right hand side of three terminal blocks and are marked ‘HE’. (See below).
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
J1 J2
CHASSIS
N
DOOR
EXT
EARTH
Optional
Sensor
Sensor
q
Overheat 1qOverheat 2
The fan output is connected to a 4 way terminal block marked ‘N, 1, 2 and 3’.
The sensor input (air sensor) is connected to 2 terminals marked ‘TEMP’ on the base unit. The sensor is not polarity sensitive.
The external thermal trip (volt-free) is connected to 2 terminals marked ‘STAT’ on the base unit. The terminals are not polarity sensitive.
Doc No. D301021 Page 36 of 64
Terminal Description Cable
HE Heating elements phase 1
10mm² maxHE Heating elements phase 2
HE Heating elements phase 3
N Neutral to fan
Fan 1 Fan - low speed
Fan 2 Fan - medium speed
Fan 3 Fan - high speed
1.5mm² max
Tem p Air sensor pair (non-polarised)
Stat Ext thermal trip pair, n.c. (volt-free)
Ext Option external sensor (supplied)
Comms Keypad/network connectors RJ45
4.18 Network Wiring with SmartElec3 Control.
Pre-wired RJ45 cable and plugs
BASE UNIT (air curtain '0')
Comms
RS485
TEMP
TIMER
STAT
DOOR
EXT
Sensor
Optional
Sensor***
Door
Switch**
B.M.S.
Enable*
Programmer
Keypad
BASE UNIT (air curtain '1')
Comms
RS485
TEMP
TIMER
terminals as
STAT
DOOR
EXT
TIMER
J1
Sensor
Optional
Sensor***
Switch**
To subsequent air curtains
(maximum of 16)
supplied
DOOR
J2
Door
SELECT
This diagram refers only to the wiring of 2 or more networked air curtains. (maximum 16 air curtains per control panel). For mains wiring refer to section 4 of this manual ‘installer wiring details’.
The program panel is connected to the base unit in the air curtain via pre-wired RJ45 cable/plugs. These cables are available in 2, 10, 20, 30, 50 and 100m lengths. It is recommended that this control cable is run separately within its own trunking to avoid external interference.
Max cable run in any network must not exceed 110m in total including program panel cable.
Note: All air curtains connected within the network system will operate under the settings of the single keypad.
Any air curtain within the network can be connected with and respond to the following optional circuits: * External switch (ie BMS enable) where required, to be volt free and wired in PARALLEL via normally open contacts to each
terminal pair ‘ T I M ER ’. (Contacts closed to enable). Only air curtain(s) wired this way will respond to the enable signal. Remove factory tted jumpers J1. (NOTE: terminals are polarity sensitive)
** Door switches where required, to be volt free and wired to INDIVIDUAL base units via normally closed contacts to each terminal pair ‘DOOR’. (Contacts open to enable door mode). Only air curtain(s) wired this way will respond to the door mode. Remove factory tted jumper J2. refer section 10.2.6.1 - Door link settings. *** Internal/external sensors, where required, to be wired to INDIVIDUAL base units to each terminal pair ‘EXT’. Only air curtain(s) wired this way will respond to the sensor setting. If a sensor is tted to more than one air curtain then the value is displayed as an average. refer section 10.2.6.4 - External temperature.
Doc No. D301021 Page 37 of 64
5. Installation Details.
5.1 Mounting
irbloc units should be installed horizontally directly over
A
the door opening. They are designed for discreet positioning in a suspended ceiling or bulkhead in the doorways of retail or commercial premises. The unit can also be mounted within an optional case for doorways with restricted space or no suspended ceiling or bulkhead.
Care must be taken to allow complete free air movement into the inlet grilles of the unit to ensure correct working operation of the air curtain. The discharge opening should be as close to the top of the door as possible and to cover the entire door width.
Units can be mounted adjacent to each other to cover the full door opening across wider entrances.
5.2 Electrical Supply.
the points of attachment to the building are sound. Verication with the consultant/architect or owner of the building is recommended to ensure that a sound, mechanically stable installation can be achieved.
All attachments must be capable of supporting the weight of the product detailed in Section 3.
Step 1
Before tting or wiring the air curtain, ensure casing faces as below and see general installation guidance notes.
These units are suitable for connection to a 415 Volt, 50Hz 3 phase and neutral supply for Electrically heated 9-18kW models or 230/240 Volt 50 Hz single phase supply for Electrically heated 6kW, 9kW, Ambient and LPHW models.
Electrically heated models consume 6kW and 9kW at 230 volts and 9kW, 12kW & 18kW at 415 volts when switched to the full heat position depending on their model and capacity size.
The appliance should be connected to the supply via an appropriate switched fused double pole isolator having a contact separation of greater than 3mm. Test for correct operation and ret the cover.
For connection to the mains supply it will be necessary to open the hinged lid from the unit. The base unit is located on a base plate. It will be necessary to connect the mains supply and the lead from the remote key pad prior to retting the cover. Wire in accordance to diagrams in section 4.1 to 4.4
For optional SmartElec3 controller, wire as shown in diagrams
4.15 to 4.18
Step 2
Using a 4mm Allen key slacken the captive M6 Allen screws at the side of the grille.
For safety reasons, a sound earth connection must always be made to the unit before it is put to use. The unit should be wired in accordance with IEE Regulations for the Electrical Equipment of Buildings.
5.3 Installation.
It is the sole responsibility of the installer to ensure that
Doc No. D301021 Page 38 of 64
Step 3
Step 6
Access to the inside of the air curtain grille can be made. Open the grille. The grille is hinged to prevent the inner frame from dropping.
Step 4
The grille assembly can now be removed from the case to allow tting of the product in the ceiling recess. Remove the screws from the outer frame to the top of the product case.
Either drop rods or catenary wire (available from manufacturer) can be used to fasten the air curtain to the ceiling support structure.
Note When using drop rods the casing mounting brackets are slotted and the mounting plates provided must be used on assembly.
Step 5
Attachment of the air curtain to the ceiling structure is by means of the two brackets attached to the side of the air curtain. The brackets may be removed to assist in passing the air curtain through the recess then reattached when in-situ.
Step 7
The height between the ceiling face and the face of the air curtain case needs to be adjusted to approx 40mm to en­able the grille assembly to t ush with the ceiling. Adjust accordingly.
Doc No. D301021 Page 39 of 64
After tting the product in the ceiling recess and adjusting the height to ensure that the grille sits ush to the ceiling (when re-tted) take the grille assembly and ret using the screws removed during Step 5.
5.4 Program Keypad
The Electronic base unit is pre-installed inside the air curtain. All the external electrical connections are via screw terminals onto this unit.
The program keypad can either be installed on a standard double surface box, or recessed using a double ush conduit box.
Fig.5 Conduit box ush mounting
5.5 Option SmartElec3 Controller
The SmartElec3 base unit is pre-installed inside the air curtain. All the external electrical connections except for the keypad are via screw terminals onto this base unit.
Fig. 4. Surface mount dimensions.
148
43,5
87
120 crs
Alternatively, the program panel can be ush wall mounted with the addition of a suitable conduit box as shown in Fig 8.
The SmartElec3 program panel is identical to the standard program panel and will auto detect a Smartcom base unit when plugged in.
The distance between the base unit and the program
panel can be up to 100m maximum.
Doc No. D301021 Page 40 of 64
5.6 Installation details - LPHW only
Fig. 6. Typical schematic of a 3 port valve system
To avoid risk of transit damage to the ow and return connections, ON LPHW STANDARD CAPACITY ONLY the heating coil is provided loose inside the case together with the air deector plate and side supports.
NOTE: HIGH CAPACITY LPHW COILS ARE PRE-FITTED.
To install, unpack the loose items and identify the two side supports as shown below and t to the inner side of the case using the screws provided.
Note The side supports are handed.
The coils can be handed for right or left hand exit by turning the coil through 180°. Prior to installation decide if you require left hand or right hand exit of the ow and return pipes from the product and then x the coil in position using the screws provided.
The LPHW copper tubing connections are as shown in g.12 below and are 15mm outside diameter. Ensure correct water seal ttings are used. We recommend the use of a suitable water mains isolation valve to ease any maintenance.
Fig.12 LPHW connections.
FLOW/RETURN CONNECTIONS
After tting the coil and side supports t the air deector plate to the side supports and rotor cut-o plate using the screws provided.
Carefully close the grille and ret the xing screw.
Test product as shown in the User Instructions.
Doc No. D301021 Page 41 of 64
5.6.1 Three Port Valve
An optional 3 port valve (supplied by others) can be used on the ow and return pipes to divert the hot water from the unit when not in use.
The valve must be tted in accordance with the manufacturers instructions.
When used in conjunction with the LPHW programmer, the 3 port valve can be wired into the base unit to open the valve when heat is selected (see section 4.5). This valve must operate on 0-10v DC.
Note: This option can not operate with a SmartElec
unit.
5.7 Installation wiring
With the grille door open, connect the electrical supply and program panel interconnecting wiring/factory supplied cables to the relevant terminals on the controller base unit.
Connect any interconnecting wiring/factory supplied cables to the programme panel.
Connect any optional wiring as required.
Customer wiring terminals.
For full details see wiring diagrams in section 4. Ensure the correct diagram is used based on the information from the air curtain data plate and optional manufactures information.
Install the ACR unit using drop rods as previously described.
The sides of the case simply ‘wrap’ around the exposed body of the air curtain xing at two edges (all four edges in the case of the 2000mm), with screws.
5.8 Installation details - optional Case
The ACR unit can also be mounted within an optional pre-coated outer case for use in doorways with restricted space or areas with no suspended ceiling or bulkhead.
The cases either come in two halves (as shown) for the 1000mm and 1500mm or four individual sides for the 2000mm.
Doc No. D301021 Page 42 of 64
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE THERE IS A CORROSIVE ATMOSPHERE.
6. Service & Maintenance.
ALWAYS ENSURE THAT THE EXTERNAL MAINS ELECTRICITY SUPPLY IS SWITCHED OFF BEFORE COMMENCING ANY MAINTENANCE ON THIS HEATER
To obtain the best results from the heater, it is essential to avoid the accumulation of dust and dirt within the unit on the air inlet and discharge grilles. For this reason regular cleaning is necessary, paying particular attention to the removal of dirt build up on the rotor blades.
Cleaning of the fan is best carried out with a soft brush.
A single drop of light oil should be applied to the motor bearing from time to time.
The product should be serviced annually. Servicing shall be undertaken by a competent person. Airbloc oer a service facility, call 01384 489700.
Step 1
Using a 4mm Allen key slacken the captive M6 Allen screws at the side of the grille.
Step 2
Open the grille. The grille is hinged to prevent the inner frame from dropping. Access to the inside of the air curtain grille can be made.
Step 3
With a soft brush clean away any dust from the motor and elements.
Check all connections and components for soundness or signs of deterioration and replace as necessary.
Re-assemble and test.
Doc No. D301021 Page 43 of 64
7. Spare Parts.
Note Any spare part components that are not approved by Nortek Global HVAC (UK) LTD could invalidate the approval of
the appliance and invalidate the warranty.
7.1 General
Item Desc.
Motor 100003 100012 100535
Rotor Left Hand*
Rotor Right Hand*
Thermal Cut Out
(where reqd)
ACR1000SE06/
ACR1000SE09 ACR1000SW9/
ACR1000SA
ACR1500SE06/ ACR1500SE12/
ACR1500SW12/
ACR1500SA
ACR2000SE09/ ACR2000SE18/
ACR2000SW18/
ACR2000SA
ACR1200HE12/
ACR1200HW12/
ACR1200HA
ACR1800HE18/
ACR1800HW18/
ACR1800HA
100001 100006 100010 100539 100540
100002 100007 100011 100536 100537
900001
* Right hand & left hand when viewed from outside the building looking into the door opening.
7.2 Standard Controller
Due to the nature of it’s construction, it is not advisable to repair damaged electronic components on either the base unit
or programmer (keypad).
Program Panel
108221-RJ45
Base Unit STDELECBU45 (electric) LPHWBU45 (LPHW+ambient)
Outside Air Sensor
Doc No. D301021 Page 44 of 64
SC-OS
7.3 SmartElec3 Controller
Due to the nature of it’s construction, it is not advisable to repair damaged electronic components on either the SELEC3BU45 base unit or AC-ACRRP45 programmer
Item Desc. All models
Program Panel
Panel P.C .B .
Base Unit
Heat Sensor
Fuse
108221-RJ45
AC-ACRRP45
SELEC3BU45
SELEC2HS
900471
Item Desc. All models
Control Fuse
Outdoor Sensor
900473
SC/OS
2M RJ45-CABLE-2
Data cable c/w plugs
10M RJ45- CABLE-10 20M RJ45-CABLE-20 30M RJ45-CABLE-30 50M RJ45-CABLE-50
100M RJ45-CABLE-100
7.4 Heat Mediums
Electric Element
Item Rating 6kW 9kW 12kW 18kW
SE 1Pha 101565/107817 107818 - ­length 1.0m/1.5m 2.0m - ­HE 3Pha - 100004 100008 100013 length - 1.0m 1.5m 2.0m HE 3Pha - - 100526 100527 length
LPHW coil
- - 1.0m 1.5m
Item Rating 9kW 12kW 18kW
SE 100197 101280 100199 length 1.0m 1.5m 2.0 HE 103680 103607 length
1.0m 1.5m
Doc No. D301021 Page 45 of 64
8. Fault Finding.
8.1 General
f the air curtain does not operate after running through the
I
detail provided in Section 10, then a suitably competent service engineer should be called to identify the nature of the fault.
Note The manufacturer operates a service function from the
address provided in these instructions.
All air curtains are tted with fuse protection and motor thermal protection.
Other faults in relation to the element, motor and wiring should be identied using conventional fault nding techniques.
In the event that electrical components are replaced, please ensure that electrical safety checks in accordance with the regulations in force in the country of use are undertaken.
been cleared.
Apart from the communication failure alarm which could be due to a broken connection of the data link and air curtain not found alarm, which could be due to incorrect addressing, all other alarms will cause the base unit to switch o the heater output.
The SmartElec3 base unit is protected from any short circuit on the air sensor or heat sink sensor as the error will cause the temperature to rise and trigger over temperature alarm.
There are ve basic checks to perform should ‘X--’ appear on the program panel display. These are as follows:
1: Continuity: Use a multimeter to check continuity between each end of all four cores at the plugs
8.2 Electrically heated units only.
For the service engineer, please note that there are two thermal cut-outs incorporated in the air curtain which, if tripped, need to be manually reset. The cut-outs are located in the airow near to the elements on the left and right.
Re-setting the thermal cut-out may help to identify the nature of the fault however we do not recommend a re-set without a thorough investigation into why the cut-out operated.
Fig. 13. Thermal Cut-out
2: Short circuit: Use a multimeter to check that there are no short circuits between any of the four cores.
N.B. This test should be done with both ends of the cable disconnected to avoid false readings.
3: Plugs: Check that the plugs are rmly seated on the circuit board in both the program panel and on the base unit.
4: Addressing: (network versions only). If two or more air curtains are networked, check that each base unit has a unique address as described in section 10.2.8.
5: Network cables: Ensure that the total run of all cables in the network does not exceed 110m including the cable to the program panel.
If a panel has never before been run, it automatically starts in engineer’s mode when rst powered-up. To exit this mode, press and hold the button.
Alternatively, the engineer’s mode automatically self-clears after approximately 10 minutes of non-activity on the buttons.
8.3 Standard Controller.
For fault codes refer to SmartElec3 fault table on next page.
8.4 SmartElec3 Controllers.
The SmartElec3 control raises an alarm if any of its inputs are outside their normal working scope. Alarms are displayed on the program panel as a code with a prex “E” . The rst number represents the air curtain address. See chart over.
As the alarms are mutually exclusive, the rst alarm code displayed on the program panel will stay on until the fault has
Doc No. D301021 Page 46 of 64
The system can be reset by powering-up the panel whilst holding down both the and buttons.
The display shows the ‘start’ pattern but then goes blank.
Release the buttons. The display resumes and the system nds only those air curtains which are actually connected and working.
If appears on the display, press and hold the button for a few seconds then release. The display will then return to the normal mode.
8.4.1 SmartElec3/Standard Fault Codes
# = Air curtain address #_ _, #E1, #E2, #E5 and #E6 codes also apply to standard controller.
Code Description Symptom Possible Cause Remedy
# _ _
# E1
# E2
# E3
# E4
# E5
# E6
Communications failure No control on unit
Air sensor failed Fan operating, no heat
Air sensor temp too high Fan operating,no heat
Heatsink too hot Fan operating, no heat
Heatsink sensor failure Fan operating, no heat
Ext. temp sensor failure
Overheat stat open circuit
Unit runs but no ex­ternal temperature control
Fan operating, no heat Overheat stat open circuit Replace overheat thermostat
Bad data cable connection Damaged cable
Air sensor cable disconnected Air sensor broken
High ambient air temperature Incorrect impeller rotation Motor failure
High ambient air temp/faulty base unit
Heatsink sensor wiring disconnected/faulty
Heatsink sensor faulty
External temperature sensor faulty
Check data cables and plugs Replace damaged cable
Check cable Replace air sensor
Check ventilation Check rotation of impeller Check motor, replace if
necessary
Replace SmartElec base unit
Check wiring Replace SmartElec base unit
Repair faulty wiring Replace faulty sensor
8.4.2 SmartElec3 base unit LED indicator location/function
Note: Standard controller LEDs have the same function and are in similar positions on the PCB.
Doc No. D301021 Page 47 of 64
9. Parts Replacement.
Warning
Ensure electrical power is isolated from the product.
For access follow steps 1 - 4 as stated in Section 6
9.1 Electrical element replacement SE.
Step 1
Using a 4mm Allen key slacken the M6 Allen screws at the side of the grille. Access to the inside of the air curtain grille can be made. Open the grille. The grille is hinged to prevent the inner frame from dropping.
9.2 Electrical element replacement HE.
Step 2
Disconnect element wires and if necessary remove cut-o plate xing screws.
Step 3
Remove element top xing screws. Locate and remove element xing screws by inserting a screwdriver through the hole indicated below.
Step 1
Using a 4mm Allen key slacken screws securing the grille. Remove 4 screws securing the top of the case and remove. Slacken two hinging bolts on both ends. Remove three bolts securing the access plate. Carefully hinge down the access plate.
Note: Take the weight as access plate swings down.
Step 2
Carefully remove connections to the elements, noting wiring conguration.
Step 4
Lift out element cartridge, replace as required.
Doc No. D301021 Page 48 of 64
Step 3
Remove two bolts securing elements.
Step 4
Lift out element cartridge, replace as required.
9.3 Rotor and motor replacement SE
Step 1
Using a 4mm Allen key slacken the M6 Allen screws at the side of the grille. Access to the inside of the air curtain grille can be made. Open the grille. The grille is hinged to prevent the inner frame from dropping.
Step 4
Using a 2.5mm Allen key, slacken the rotor hub grub screw.
Note: when retting ensure that the grub screw bears on the
at of the motor shaft.
Step 5
Push the rotor support bracket away from the rotor to release the rotor bearing.
Step 2
Remove fastenings securing the motor end of the deector plate, including the single side screw (arrowed).
Step 3
Remove the four screws securing the rotor support bracket and the opposite end of the deector plate. Remove plate.
Step 6
Lift the rotor clear of the motor shaft then remove it from the air curtain.
Step 7
Disconnect fan motor cables from the terminals arrowed including the earth which is bolted to the chassis. (SmartElec shown over).
Fan terminals (similar position on LPHW)
Doc No. D301021 Page 49 of 64
Step 8
Remove the four 10mm bolts securing the motor to its bracket.
Carefully hinge down the access plate.
Note Take the weight as access plate swings down.
Step 2
Remove 6 screws securing access panel and carefully remove panel.
Step 9
Swing the movable bracket clear and remove the motor.
Step 3
Remove 8 bolts securing wheel assembly.
Step 4
Turn retaining latch to release chassis.
9.4 Rotor and motor replacement HE
Step 1
Using a pozidrive screwdriver undo screws securing the grille and remove.
Remove 4 screws securing the top of the case and remove. Slacken two hinging bolts on both ends.
Remove three bolts securing the access plate.
Doc No. D301021 Page 50 of 64
Step 5
Holding handle, carefully pull motor and air wheel assembly forward.
Step 6
Remove screw securing rotor bearing plate. Repeat for opposite side.
Step 8
Disconnect the wires from the motor to the controller base unit.
Fan terminals (similar position on LPHW)
Step 9
Remove the bolts securing the motor to the chassis.
Step 7
Slacken grub screw securing rotors to the motor shaft, remove rotor.
Repeat for opposite rotor.
Remove motor from air curtain.
Replace motor in reverse order. Carefully close the grille and ret the xing screw.
Test product as shown in the User Instructions.
9.5 LPHW coil replacement.
Step 1
Using a 4mm Allen key slacken screws securing the grille. Remove 4 screws securing the top of the case and remove. Slacken two hinging bolts on both ends. Remove three bolts securing the access plate. Carefully hinge down the access plate.
Note: Take the weight as access plate swings down.
Doc No. D301021 Page 51 of 64
Step 2
Disconnect ow/return connections with appropriate tools.
Step 3
Remove the air deector plate and the side support plates, retaining the screws.
Step 4
Remove coil xing screws from the outside of the air curtain body.
Step 5
Withdraw the coil.
Replace LPHW coil in reverse order.
Doc No. D301021 Page 52 of 64
10. User Instructions.
10.1 Standard Controller (electrically heated)
10.1.1 Keypad Buttons
‘1’ denotes the AIR CURTAIN ADDRESS, and ‘27’ the current outlet temperature.
If the display is set to ‘H1’ (half heat) then the display unit will show:
The ‘dot’ after the air curtain number denotes heat setting 1. If the display is set to ‘H2’ (full heat) then the display unit will
show:
The ‘dot’ after the temperature number denotes heat setting
2.
If an external temperature sensor is tted then the display will also show:
The button will allow you to navigate.
The button will allow you to increase the setting.
The button will allow you to decrease the setting.
10.1.2 Operation
On rst power up, the display will show and have the following default settings:
F. 0 (no fan)
H. 0 (no heat)
16 (°C. Heat set point)
The small ‘zero’ shows a sensor detected and it’s current temperature reading.
10.1.3 Standard Settings
Press the button. This will cause the display to brighten and display air curtain number and it’s fan speed eg.
Press the or buttons to increase/decrease the desired setting between F0, 1, 2, or 3.
Pressing the button again will display the air curtain number and it’s heat setting eg.
Press the or buttons to increase/decrease the desired setting between H0, 1, or 2.
If no air curtains are detected the display will show:
Note: Subsequent power ups will retain any entered settings in the display internal memory.
In normal operation the display will show for example:
Pressing the button again will loop back to start if only one air curtain is connected to the display unit. If there is more than one connected the display unit will then show the settings for the next air curtain in the network and so on.
10.1.4 Engineers Settings
To turn on the engineers settings press and hold the button until the display goes blank then press the button.
The display unit will now display ’Eng’ briey.
Doc No. D301021 Page 53 of 64
This will disappear after a period of 10 minutes of inactivity on the keypad.
On pressing the button the display unit now works in the same way as standard for the fan and heat settings, but then an adjustable control temperature setting appears (if external sensor tted).
This control works by reading the temperature at the sensor and comparing it to the set point. The temperature is then controlled by automatically switching the controller outputs between H0, H1, and H2, thus maintaining reasonable heat control.
Press the or buttons to increase/decrease the desired setting between C0, or 1-7 (see table below).
If the air curtain is set to eg.:
This denotes that air curtain ‘1’ is set to be the master for door and BMS interlocks. If interrogated all other air curtains will then display eg.
This denotes a unit that is not the master.
Pressing the button again advances to the door link settings.
10.1.4.1 Door Link Settings
Two settings are available for use when the door link circuit terminals are open circuit (PCB link removed). The rst of these is displayed as:
‘1’ is the air curtain address and ‘d2’ denotes fan speed 2. Press the or buttons to increase/decrease the desired
setting between d0, 1, 2, or 3. The second is displayed as:
‘1’ is the air curtain address and ‘t1’ denotes heat setting 1. Press the or buttons to increase/decrease the desired setting between t0, 1 or 2.
‘C’ interlocks setting
1 2 4
‘L’ interlocks setting
1 2 4
To set more than one interlock, add the appropriate numbers together, eg. ‘C3’ above works on timer and door interlocks.
If a controller is not the master, all three interlock links
must be in place.
Eect
Timer/BMS interlock Door interlock Stat interlock
Eect
Not used Not used Blocked lter interlock
10.1.4.3 All Controllers
Pressing the button again advances to the link group interlock settings.
10.1.4.2 Link-Group Interlock
If there is more than one air curtain connected to the display then there are two sets of interlocks available to enable a single air curtain in a group to be the ‘master’ controller based on links used.
‘1’ is the air curtain address and ‘C0’ is the default setting (no interlock set)
Doc No. D301021 Page 54 of 64
This setting can be accessed from the engineers settings whilst the external temperature indication is showing (see previous page). This is displayed as:
This allows a single group of settings to be copied to all controllers in a network. Individual settings can still be used at a later date if required.
Quick Options
1. Immediate turn o:
Press and hold the button for two seconds, the display will go blank then the air curtain(s) will turn o.
2. Re-scan/Engineers mode:
Press and hold the button for two seconds, the display will go blank, then press The display will show the controller type in the rst digit and the number of air curtains in the fourth digit. Release both buttons and then press any button to continue, the panel is now in Engineers mode.
‘1’ denotes the air curtain address, and ‘27’ the current outlet temperature.
If the display is delivering power then the display will show:
3. Turn on Engineers mode:
Press and hold the button for two seconds, the display will go blank, then press the display will show ‘Eng’, Release both buttons.
4. Turn o Engineers mode:
Press and hold the button for two seconds, the display will go blank, then release.
5. Air curtain addressing: See section 10.2.8
10.2 LPHW/Ambient Controller
10.2.1 Keypad Buttons
If an external temperature sensor is tted then the display will also show:
10.2.3 Standard Settings
Press the button. This will cause the display to brighten and display air curtain number and it’s set point temperature eg:
Pressing the button again will show the fan settings eg:
Pressing the button again will show the heat settings eg:
The button will allow you to navigate.
The button will allow you to increase the setting.
The button will allow you to decrease the setting.
10.2.2 Operation
On rst power up, the display will show and have the following default settings:
F. 0 (no fan)
H. 0 (no heat)
16 (°C. Heat set point)
If no air curtains are detected the display will show:
Note: Subsequent power ups will retain any entered
settings in the display internal memory.
In normal operation the display will show for example:
10.2.4 Engineers Settings
To turn on the engineers settings press and hold the button until the display goes blank, then press the button.
The display unit will now display ’Eng’ briey.
This will disappear after a period of 10 minutes of inactivity on the keypad.
On pressing the button again the display unit now works in the same way as standard for the fan and heat settings. The next press of will advance to the ‘door link’ settings if only one air curtain is connected, or ‘link group interlocks’ if more than one air curtain is connected.
10.2.4.1 Door Link Settings
Two settings are available for use when the door link circuit terminals are open circuit (PCB link removed). The rst of these
Doc No. D301021 Page 55 of 64
is displayed as:
10.2.4.3 All controllers
‘1’ is the air curtain address and ‘d2’ denotes fan speed 2. Press the or buttons to increase/decrease the desired
setting between d0, 1, 2, or 3. The second is displayed as:
‘1’ is the air curtain address and ‘t1’ denotes heat setting 1. Press the or buttons to increase/decrease the desired setting between t0, 1, 2, 3 etc. where 0 is heat o
1 is 5C 2 is 10C 3 is 15C Pressing the button again advances to the link group
interlock settings.
10.2.4.2 Link-Group Interlock
If there is more than one air curtain connected to the display then there are two sets of interlocks available to enable a single air curtain in a group to be the ‘master’ controller based on links used.
‘C’ interlocks setting
1 2 4
‘L’ interlocks setting
1 2 4
This setting can be accessed from the engineers settings whilst the external temperature indication is showing (see previous page). This is displayed as:
This allows a single group of settings to be copied to all controllers in a network. Individual settings can still be used at a later date if required.
Eect
Timer/BMS interlock Door interlock Stat interlock
Eect
Not used Not used Blocked lter interlock
10.2.4.4 External Temperature
‘1’ is the air curtain address and ‘C0’ is the default setting (no interlock set)
Press the or buttons to increase/decrease the desired setting between C0, or 1-7 (see table below).
If the air curtain is set to eg.:
This denotes that air curtain ‘1’ is set to be the master for door and BMS interlocks. If interrogated all other air curtains will then display eg.
This denotes a unit that is not the master. To set more than one interlock, add the appropriate numbers
together, eg. ‘C3’ above works on timer and door interlocks.
Display will show eg:
This will only be displayed if there is an external sensor tted, and shows the external sensor temperature set point. Once set the air curtain will turn o when it reaches the set point. The temperature then has to drop 3C before the air curtain turns back on again.
10.2.4.5 External Temperature Oset
Display will show eg:
If the outside temperature falls to zeroC, this setting shows the temperature offset above zero. This will temporarily raise the temperature setting 6C above the actual set point. Possible settings are 0-9 where 0 is off if this function is not required.
If a controller is not the master, all three interlock links must be in place.
Doc No. D301021 Page 56 of 64
10.2.4.6 Temperature Limits
The next two displays eg:
These show the permissible upper and lower limits for setting the external temperature sensor set point. This is useful for allowing the end user limited control over this setting. The maximum (default 35C) may be set anywhere between the current minimum and 50C, and the minimum (default 16C) may be set anywhere between 3C and the current maximum.
10.2.4.7 Air Return and Pipe Cold Sensors
The readings from these sensors is not shown on the display, and unless both are connected there is no eect on the heating control. When both sensors are connected they operate as follows: When the heating is rst turned on the temperature readings from the sensors should be close together, two minutes later there should be a dierence of at least 2C. If there is no dierence then the controller assumes that there is no ow then turns the heating o.
Doc No. D301021 Page 57 of 64
10.3 Option SmartElec3 Controller
10.3.1 Keypad buttons
During normal operation, press and hold the button for approximately two seconds. The display blanks until you release the button. The heating and fans are now turned o. Releasing the button in less than this time and the action has no eect.
Where multiple air curtains exist in a network, this action
turns o all air curtains.
The buttons have the following functions:
Press the select button to allow navigation.
Press the + button to increase a setting.
Press the - button to decrease a setting.
10.3.2 Operation
10.3.2.1 Normal mode displays
First power up
No air curtains found
Curtain address and temperature set point
10.3.2.2 Normal Operation
10.3.4 Settings Mode
10.3.4.1 Activate settings display
To enter the Settings mode press the button. This will illuminate the screen. Press the button till the desired setting is shown.
By pressing the button it will also advance to the next setting.
Note: If a setting has been altered by using the or
buttons, it must be conrmed by pressing the button.
10.3.4.2 Settings displays
Press the button to advance through the settings. The displays will scroll as follows:
During normal operation mode the display is dimmed.
Pressing the button, will put the panel into active mode. If
During normal operation the unit will display for example:
where ‘0’ is the curtain address, and ‘25’ the
temperature measured for the unit.
Where multiple air curtains exist in a network, the display scrolls through each unit in turn, changing approximately once every second.
If the air curtain is in operation and under heat demand, a ‘decimal point’ is shown after the air curtain address.
Quick Options
These are identical to the quick settings for the standard controller so please refer to that section of the manual.
10.3.3 OFF mode.
Where multiple air curtains exist in a network and controlled from a single keypad, these will be detected and displayed in turn, for example:
Any air curtain in the network can be accessed by pressing the
button when it’s address appears on the display.
The settings can then be accessed as previously described.
Doc No. D301021 Page 58 of 64
10.3.5 Set-up congurations
10.3.5.1 Set fan speed
when it’s address appears on the display.
The settings can then be changed as previously described.
Once the display becomes illuminated press the the button once. Display shows the fan speed.
Press to increase fan speed.
Press to decrease fan speed.
Three speeds and an ‘o’ setting are available:
Speed 1 Speed 2
Speed 3 Fan ‘o’
10.3.5.2 Set heat
Press the button again Display shows the heat setting.
Press to set heat ‘on’.
Press to set heat ‘o’.
If no button pressed for 2 seconds, display will revert to normal user. e.g.
10.3.5.3 Set temperature
10.3.6 Engineers settings
Other options are available in engineer’s mode.
To access the engineers mode either: press and hold the button for a few seconds until the display goes blank, then press briey. The display will show
or Power-up the system with the and buttons pressed
and release when the display goes blank the display will show
As in normal mode, Engineers set-up mode is started by pressing the button whereupon the display will illuminate. Advance through the normal modes settings of temperature, fan and heat by pressing the button.
Pressing the button again advances to further options to allow other settings of the system. The engineers set-up options listed herewith depend various factors e.g. optional door switch, multiple air curtains etc.
Notes: If a panel has never before been run, it automatically
starts in engineer’s mode when rst powered-up.
Engineer’s mode automatically self-clears after
approximately 10 minutes of non-activity on the buttons.
10.3.6.1: Door link settings:
Press the button once to allow changes to be made.
Press to increase temperature set point. (max 35°C )
Press to decrease temperature set point. (min 16°C)
Display shows for example:
10.3.5.4 Networked air curtains
Where multiple air curtains exist in a network and controlled from a single keypad, these will be detected and displayed in turn, for example:
Any air curtain in the network can be accessed by pressing
This provides an alternative fan speed and heat setting which is activated only when the door link is open circuit.
The fan speed is accessed by pressing the the button until the display shows: Use the and buttons to change the setting.
Fan OFF
Fan speed 1
Fan speed 2
Fan speed 3
The temperature setting when the door link is open circuit is accessed by pressing the button until the display shows:
Use the and buttons to alter the temperature value.
Doc No. D301021 Page 59 of 64
Heat OFF
5°C
10.3.6.3 All controllers
This function is accessed by pressing the button until the display shows
10°C
15°C
20°C
25°C
30°C
35°C
10.3.6.2 Link-group interlock
If there is more than one air curtain, a group interlock option may be set. This provides an alternative fan speed and heat setting when activated by certain external connections on individual air curtains.
This function is accessed by pressing the button until the display shows (where ’0’ is the air curtain address to be used as a master unit for interlocks.)
Using this setting all air curtains in a network respond to the same settings. Settings for individual air curtains can still be changed if required.
10.3.6.4 External temperature
This is only displayed if the factory supplied optional external temperature sensor is connected to the air curtain.
This function is accessed by pressing the button until the display shows:
Use the and buttons to change to the desired temperature setting.
If the external temperature is equal to the set temperature, all air curtains are turned o. The temperature must then drop to 3°C below the set temperature before the air curtains are turned back on.
Note: for multiple air curtains - more than one can have an external sensor connected. When this is the case the sensor values are displayed as an average. (If one external sensor goes faulty, the average is worked out from the remaining working ones).
See table to follow for possible settings.
Default setting
or Master setting range
Other air curtains
See table below for possible settings.
Master setting Function
1 Timer/BMS interlock
2 Door interlock
3 Timer/BMS/door interlock
4 Stat interlock
5 Timer/BMS/stat interlock
6 Stat/door interlock
10.3.6.5 External temperature oset
This function is accessed by pressing the button until the display shows:
This setting allows the temperature setpoint to be automatically increased as the external temperature falls to, or below, zero. For instance, a setting of 4 means a +4°C oset at 0°C. The maximum oset is 9°C. If this feature is not required the setting should be:
7 Timer/BMS/stat/door interlock
Doc No. D301021 Page 60 of 64
Note: When more than one air curtain is used, this feature
will only work under the ’all controllers’ setting.
10.3.6.6 Temperature limits
This function is accessed by pressing the button until the display shows:
and respectively i.e. maximum and minimum set limits for set temperature.
Use the and buttons to change to the desired limit temperature settings.
The maximum (default 35°C) may be set any where between the current minimum and 50°C, and the minimum, (default 16°C) may be set anywhere between 3°C and the current maximum.
To exit the engineers mode press and hold the button for a few seconds.
Power-up Manual Reset.
10.3.7 Power-up Manual Reset
The system can be reset by powering-up the panel whilst holding down the and buttons. The display shows the ‘start’ pattern but then goes blank.
Release the buttons where upon the display resumes and the system addressing commences, nding only those air curtains which are actually connected and working.
If appears on the display, press and hold the button for a few seconds then release. The display will then return to the normal mode.
10.3.8 Air curtain addressing (standard and SmartElec)
All air curtains work on an address to communicate with the keypad and are supplied with an default address of ‘0’.
Where multiple air curtains exist in a network they must be re-addressed using a unique address (0-9/A-F). This is achieved using a 4 way bitswitch mounted on the base unit PCB (see photo on following page.
g. 16. Air curtain address numbers
The black shaded areas represent the switch position.
This example shows the air curtain set to No.8
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE THERE IS A CORROSIVE ATMOSPHERE
Bitswitch location on PCB
The keypad will check all addresses on rst power up and this is displayed as the rst digit on the display (in a network set up, all addressees will be viewed in rotation).
Note: If any address is altered after initial power up or an air curtain removed after initial installation, the keypad will also retain the original address although unable to respond.
To remove this unwanted address(s) follow the details in 10.3.7
Doc No. D301021 Page 61 of 64
10.3.9 Keypad sequences (standard /LPHW)
Standard - Normal set-up
LPHW - Normal displayStandard - Normal display
LPHW - Normal set-up
Standard - Engineers mode display
LPHW - Engineers mode display
Doc No. D301021 Page 62 of 64
LPHW - Engineers mode set-up
Standard - Engineers mode set-up
10.3.10 Keypad sequences (SmartElec controller)
Engineers mode display
Normal set-up
Doc No. D301021 Page 63 of 64
Engineers mode set-up
Normal display
AFFIX AGENTS DETAILS HERE
Registered in England No˚ 1390934 Registered Office: The Colmore Building, 20 Colmore Circus Queensway, Birmingham, West Midlans, B4 6AT
Document reference number: D301051
Nortek Global HVAC (UK) LTD
Fens Pool Avenue, Brierley Hill
West Midlands, DY5 1QA
United Kingdom
Tel: +44 (0) 1384 489 250
Fax: +44 (0) 1384 489 707
Email: reznorsales@nortek.com
Web: www.reznor.eu/
Replaces Document reference number: D301021 R1
Loading...