Nortek Global HVAC (UK) Limited equipment must be installed and maintained in accordance with the
requirements of the Codes of Practice or rules in force. All external wiring MUST comply with the codes of practice
or rules in force in the country of installation.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
Read instructions before installing or servicing this equipment. Gas-fired appliances are not designed for use in
hazardous atmospheres containing flammable vapours or combustible dust, containing chlorinated or halogenated
hydrocarbons, or in applications with airborne silicone substances.
Reznor® is a registered trademark of Nortek Global HVAC, LLC.
ErP
2018
Part No. D301051
Introduction.
elcome to the range of Airbloc ACR Recessed Air Curtains. Local regulations may vary in the country of use and it is the
W
installers responsibility to ensure that such regulations are satised
All installation and assembly procedures must be carried out by suitable competent persons. Commissioning and
service procedures must be carried out by suitable qualied persons to the statutory regulations in the country of use.
When installing, commissioning and servicing is undertaken on these air curtains due care and attention is
required to ensure that working at height regulations are adhered to, at the mounting heights specied.
All Dimensions shown are in mm unless otherwise stated.
PLEASE READ this document prior to installation and use. The safety of this heater is guaranteed only by the correct usage
in accordance with these instructions, therefore it is recommended that they are retained for future reference.
The manufacturer reserves the right to alter specications without prior notice.
Any reference made to Laws, Standards, Directives, Codes of Practice or other recommendations governing the
application and installation of heating appliances and which may be referred to in Brochures, Specications, Quotations,
and Installation, Operation and Maintenance manuals is done so for information and guidance purposes only and should
only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters
arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations.
IMPORTANT NOTICE TO INSTALLERS
Installers should satisfy themselves that the gas pipework installation is carried out in accordance
with all current legislation, Codes of Practice and recommendations .
Additionally it may be necessary to protect the gas valves which form part of the heater or burner
assembly from potential pipe contamination particularly, but not exclusively, where copper gas
pipework is used.
In instances where copper pipework is to be used for all or part of a gas pipework installation, including
short length nal connections then we advise that installers consult with gas supplier or provider and
satisfy themselves what additional precautions may be necessary.
Isolate any electrical supply to the heater and controller
before proceeding.
1.1 Compliance notices
he Airbloc ACR Recessed Air Curtain detailed herewith are
T
manufactured by Nortek Global HVAC (UK) Ltd. within a
strictly controlled quality environment within the parameters
of ISO 9001.
the use of the appliance so as to ensure its continued safe and
ecient use.
Nortek Global HVAC (UK) Ltd. have a commitment to
continuous improvement and therefore reserves the right
to amend or change the specication of the Airbloc ACR
Recessed Air Curtain range subject to compliance with the
appropriate European, national, and local regulations.
Contained within the text of the manual, the words ‘Caution’
and ‘Warning’ are used to highlight certain points.
These instructions are only valid if the following country code
is on the appliance GB. IE. If this code is not present on the
appliance, it is necessary to refer to the technical instructions
which will provide the necessary information concerning the
modication of then appliance to the conditions of use for the
country.
The Airbloc range has been tested and assessed for
compliance with the following European Directives.
The manufacturer has taken reasonable and practical steps to
ensure that Airbloc ACR Air Curtains are safe and without risk
when properly used. These air curtains should only be used in
the manner and purpose for which they were intended, and in
accordance with the recommendations detailed herewith.
The ACR Air Curtains have been designed, manufactured,
assembled, inspected, and tested, with safety and quality in
mind, there are certain basic precautions which the installer
and user should be aware of, and they are strongly advised to
read the appropriate sections of the information pack
accompanying the heater, prior to installation or use.
Nortek Global HVAC (UK) Ltd. supports all new products being
supplied to their customers with a comprehensive information
pack; this clearly denes mandatory instructions for the safe
installation, use, and maintenance, of the appliance(s).
Where proprietary items are incorporated into Airbloc
products, detailed information and instructions are also
provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of
such products supplied by Nortek Global HVAC (UK) Ltd., to
ensure that they are familiar with the appropriate information/
manuals, supplied by the manufacturer, and that they are
suitably aware of the purpose of the manuals and the safety
instructions. In addition, operators must be suitably trained in
Caution is used when failure to follow or
implement the instruction(s) can lead to
premature failure or damage to the heater or its
component parts.
Warning is used when failure to heed or
implement the instruction(s) can lead to not only
component damage, but also to a hazardous
situation being created where there is a risk of personal
injury.
The Airbloc ACR Recessed Air Curtain range conform to the
following harmonised standards:
BS EN ISO 12100:2010
Safety of machinery. General principles for design. Risk assess-
ment and risk reduction
Safety of Machinery - Basic Concepts, General Principles for
Design Technical Principles and Specications
BS EN 60204-1:2006+A1:2009
Safety of machinery. Electrical equipment of machines. Gener-
al requirements
BS EN 55014-1:2017
Electromagnetic compatibility. Requirements for household
appliances, electric tools and similar apparatus. Emission
BS EN 60335-2-102:2006+A2:2016
Household and similar electrical appliances. Safety. Particular
requirements for gas, oil and solid-fuel burning appliances
having electrical connections
BS EN 60335-2-30:2009+A11:2012
Household and similar electrical appliances. Safety. Particular
requirements for room heaters
and to the following European CE directives2006/95/EC - low voltage;
2014/30/EU - electromagnetic compatibility.
Doc No. D301021 Page 5 of 64
1.2 Certicates of conformity
Certicates are available from the Quality Control Department
at Nortek Global HVAC (UK) Ltd.
1.3 General product information
Models range from 1000mm to 2000mm in length, in both
Standard and High capacity and are available in either
Electrically heated, Ambient or LPHW. They are designed for
discreet positioning in a suspended ceiling or bulkhead in the
doorways of retail or commercial premises. Optional case for
doorways with restricted space and no suspended ceiling/
bulkhead are available.
energy to the heating elements. This combined with the inbuilt intelligent sensor control, maintains a xed outlet
temperature, thereby reducing energy consumption as
compared to an air curtain without the SmartElec3 control.
Each air curtain is supplied with a fully electronic controller
giving multi fan and heat settings (electrically operated units)
via a simple key pad which can be mounted up to 100m from
the air curtain.
Optional BMS time control, external, thermostats and door
interlocks can be installed.
The programmer shown above allows the user to control
either a single air curtain, or a network of up to 16 air curtains
with the same settings, and provides the following functions:-
• Heat On O or Auto via optional thermostat
• O or Low, Medium and High Fan Speeds
For further details please refer to section 10.1
Alternatively on electrically heated models, the optional
SmartElec3 control system consists of a base unit (installed
within the air curtain) and a program panel that can be
installed remote from the air curtain.
Usually, the program panel is mounted at a low level from
the air curtain for user access and to a maximum distance of
100m.
The base unit and program panel are linked by a pre-wired
low voltage cable as specied in these instructions.
The SmartElec3 factory tted base unit provides terminals
for 3 phase supply connection and sockets the low voltage
program panel cable. The SmartElec3 base unit rapidly pulses
The programmer shown above is the same as used on
standard air curtains and allows the user to control either a
single air curtain, or a network of up to 16 air curtains, each
with dierent settings if required, and provides the following
functions:-
• Heat On or O
• O or Low, Medium and High Fan Speeds
• Air Outlet Temperature.
For further details please refer to section 10.2
Note
Neither asbestos nor soft soldered joints are used in the
construction or manufacture of the Airbloc ACR Recessed Air
Curtain range. The materials selected for use can withstand
the mechanical, chemical, and thermal stresses which they will
be subject to during foreseen normal use when installed in
accordance with the manufacturers recommendations.
1.4 Model Denitions
ACR1000xxxx = ACR Airbloc 1M in length. 1200=1.2M;
1500=1.5M; 1800=1.8M; 2000=2.0M.
ACRxxxSxxx = ACR Airbloc Standard Capacity (up to 3M
from oor); H=High Capacity(up to 4m from oor)
ACRxxxxExx = ACR Airbloc Electrically heated.
e.g. ACR2000HE18-SM = ACR Airbloc Air Curtain, 2M long, 18kW
electrically heated high capacity c/w SmartElec Control.
Doc No. D301021 Page 6 of 64
1.5 General requirements
Caution
Before installation, check that the local distribution conditions,
nature of gas and pressure, and the current state adjustment
of the appliance are compatible.
Installation and assembly procedures must be carried
out by suitable competent persons. Commissioning and
service procedures must be carried out by suitable
qualied persons.
1.6 Health and Safety
Warning
Airbloc Air Curtains must be installed in accordance with any
relevant and Regulations. Due account should be taken of any
obligations arising from the Health and Safety at Works Act
1974 or relevant codes of practice. In addition the installation
must be carried out in accordance with the current IEE wiring
regulations and any other relevant British Standards and
Codes of Practice by a qualied installer. Isolate all electrical
supplies to the heater & controller before proceeding.
Warning
Unauthorised modications to the appliance, or departure
from the manufacturers guidance on intended use, or,
installation contrary to the manufacturers recommendations
may constitute a hazard.
Note
To ignore the warning and caution notices, and to ignore the
advice from the manufacturer on installation, commissioning,
servicing, or use, will jeopardise any applicable warranty,
moreover, such a situation could also compromise the safe
and ecient running of the appliance itself, and thereby
constitute a hazard.
The installation of the appliance must meet all the relevant
European, national, and local criteria.
Prior to installation the following points should be considered;
• The position and mounting height of the Air Curtain
for the optimum ecient distribution.
• The position of the Air Curtain relative to the electrical
services, and any controllers.
• The position of the Air Curtain relative to the low
pressure hot water pipework where appropriate.
• The position of the heater relative to service and
maintenance requirements.
Caution
The air Curtain must not be installed within an area where the
conditions are unsuitable, e.g. where the atmosphere is highly
corrosive, has a high degree of salinity, or where high wind
velocities may aect operation. Suitable protection should
be provided for the appliance when it is located in a position
where it may be susceptible to external mechanical damage.
Caution
For your own safety we recommend the use of safety boots
and leather faced gloves when handling sharp or heavy items.
The use of protective eye wear is also recommended.
Sole liability rests with the installer to ensure that all site safety
procedures are adhered to during installation.
Sole liability rests with the installer to ensure that protective
safety wear such as hand, eye, ear and head protection is used
during installation of the product.
Do not rest anything especially ladders against the product.
1.7 Delivery and pre-installation checks.
On receipt of the Air Curtain, the following checks should be
carried out;
• The model is as per order.
• That it is undamaged.
• That it is suitable for the source gas supply.
• That it is suitable for the electrical supply
If any of these points are not satised then contact should be
made with the Sales Oce at Nortek Global HVAC (UK) Ltd as
soon as possible by telephoning 01384 489700. In the case of
claims for damage, this must be signed for as damaged and
reported in writing within 24 hours of delivery, in order to
comply with insurance criteria.
1.8 Location
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE
THERE IS A CORROSIVE ATMOSPHERE.
Airbloc units should be installed horizontally directly over
the door opening. It is recommended that the air curtain is
installed on the inside of the building, within the open room
space within the ceiling void or roof space.
Doc No. D301021 Page 7 of 64
Care must be taken to allow complete free air movement into
the inlet grilles of the unit to ensure correct working operation
of the air curtain. The discharge opening should be as close
to the top of the door as possible and to cover the entire door
width.
Remote unit is wired to the base unit via a pre-wired cable
tted with RJ45 plugs.
1.10.2 SmartElec3 controller
Units can be mounted adjacent to each other to cover the full
door opening across wider entrances.
1.9 Clearance distances
It is recommended that a minimum clearance of 100mm is
allowed around the case. The clearance allows for cable entry
and prevents combustible surfaces overheating.
The minimum mounting height (oor to grille) is 1.8m. The
recommended maximum mounting height is 3m for
standard and 4m for high capacity models.
1.10 Electrical Supply
For full electrical loadings, please refer to the individual
technical data sheets within this manual.
It is recommended that the electrical supply to the base unit
in the air curtain is via an appropriate switched isolator in
accordance with the regulations in force in the country of use
and must be via a fused isolator having a contact separation of
greater than 3mm in all poles.
Electrically heated supply is 415V 3 phase, neutral and earth.
Max cable inlet size is 10mm².
Keypad is wired to the base unit via a RJ45 pre-wired cable.
Networked air curtain interconnects via a RJ45 pre-wired
cable.
BMS control, time switches, room thermostats and door
interlocks can be installed at the discretion and responsibility
of the installer.
All units must be wired in accordance with I.E.E regulations for
the Electrical Equipment of Buildings and the installer should
ensure that a suitable isolating switch is connected in the
mains supply.
Warning
For safety reasons a good earth connection must ALWAYS be
made to the heater and control box.
1.10.1 Ele ctronic co ntrol ler
Electrically heated supply is either 230V 1 phase (6 and 9kW
options) or 415V 3 phase (9 to 18kW), Neutral and Earth. Max
cable inlet size is 4mm² or 10mm² (refer to individual technical
specication)
Ambient and LPHW supply is 230V 1 phase, Neutral and
Earth. Max cable inlet size is 4mm².
Doc No. D301021 Page 8 of 64
2. Dimensions.
2.1 ACR Air Curtain Fig.1
DIM 'C'
DIM 'E'
DIM 'J'
DIM 'H'
DIM 'F'
DIM 'G'
DIM 'B'
DIM 'D'
DIM 'A'
ACR1000SE6/9;
Size
A253407
B122015202020118517852097
C118214821982115 017502059
D395550
E454608
F120515052005115017502082
G124215422095121018102140
H160180
J200220
ACR1000SW9;
ACR1000SA
ACR1500SE12;
ACR1500SW12;
ACR1500SA
ACR2000SE18;
ACR2000SW18;
ACR2000SA
ACR1200HE12;
ACR1200HW12;
ACR1200HA
ACR1800HE18;
ACR1800HW18;
ACR1800HA
Doc No. D301021 Page 9 of 64
ACR2000HE18;
ACR2000HW18;
ACR2000HA
2.2 Program keypad dimensions
The keypad is supplied with an industry standard plastic double surface mounted socket box. Alternatively the
keypad can be ush mounted using a customer supplied metal ush box as shown below.
Fig.2. Using surface mount box
148
87
120 crs
43,5
Fig.3. Optional ush mount using metal conduit box
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWElectrical heated
Heat settings3 / 64.5 / 9
Fan type / diaCrossow / 100mm
Fan settings3 Speeds
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)6.1 (26.5)9.1 (39.6)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3245
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB (L1, N,E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h116 414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Dimensional Data
Lengthmm118214821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112 514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Medium speedm³/h1405178 02432
High speedm³/h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7.08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C171326
Medium speed°C151123
High speed°C13920
Low speeddBA59
Medium speeddBA62
High speeddBA64
Doc No. D301021 Page 11 of 64
3.2 ACR1000SE9ACR1500SE12ACR2000SE18
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWElectrical heated
Heat settings4.5 / 96 / 129 / 18
Fan type / diaCrossow / 100mm
Fan settings3 speeds
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage415V 3ph 50Hz
Total load kW (a)9.1 (12.6)12.1 (16. 8)18.1 (25. 2)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps162032
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB (L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
** SmartElec3 Energy Saving Control108221-RJ45
SmartElec3 Energy Saving Control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² Max
Mains terminal block positionTop of PCB ( L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C262521
Medium speed°C232220
High speed°C201919
Low speeddBA59
Medium speeddBA62
High speeddBA64
Dimensional Data
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
**Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 12 of 64
3.3 ACR1200HE12ACR1800HE18ACR2000HE18
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWElectrical heated
Heat settings6 / 129 / 18
Fan type / diaCrossow / 100mm
Fan settings3 speeds
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage415V 3ph 50Hz
Total load kW (a)12.4 (17.3)18.4 (25.6)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps2032
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB ( L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
** SmartElec3 Energy Saving Control108221-RJ45
SmartElec3 Energy Saving Control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² Max
Mains terminal block positionTop of PCB (L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speed°C3536
Medium speed°C282726
High speed°C2220
Low speeddBA50
Medium speeddBA55
High speeddBA60
Dimensional Data
Length115017502082
Depth (width)550
Total height227
Outlet length109016902022
Outlet depth (width)85
Grille height6
Mounting bracket centres length118517852117
Side to 1st bracket centre17. 5
Mounting bracket centres heightFlush with top of unit
Top to 1st bracket centreFlush with top of unit
* Motor current only at high speed
**Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 13 of 64
3.4ACR1000SAACR1500SAACR2000SA
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWAmbient
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.06 (0.26)0.09 (0.4)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speeddBA5962
Medium speeddBA6264
High speeddBA6466
Dimensional Data
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 14 of 64
3.5ACR1200HAACR1800HAACR2000HA
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWAmbient
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.4 (1.61)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps10
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speeddBA50
Medium speeddBA55
High speeddBA60
Dimensional Data
Lengthmm115017502082
Depth (width)mm550
Total heightmm227
Outlet lengthmm109016902022
Outlet depth (width)mm85
Grille heightmm6
Mounting bracket centres lengthmm118517852117
Side to 1st bracket centremm17.5
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 15 of 64
3.6 ACR1000SW9ACR1500SW12ACR2000SW18
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWLPHW
Heat settings91218
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.06 (0.26)0.09 (0.4)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C262521
Medium speed°C232220
High speed°C201919
Low speeddBA5962
Medium speeddBA6264
High speeddBA6466
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
Doc No. D301021 Page 16 of 64
3.7 ACR1200HW12ACR1800HW18ACR2000HW18
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWLPHW
Heat settings1218
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.4 (1.6)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps10
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speed°C3536
Medium speed°C282726
High speed°C2220
Low speeddBA50
Medium speeddBA55
High speeddBA60
Lengthmm115017502082
Depth (width)mm550
Total heightmm227
Outlet lengthmm109016902022
Outlet depth (width)mm85
Grille heightmm6
Mounting bracket centres lengthmm118517852117
Side to 1st bracket centremm17.5
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
Doc No. D301021 Page 17 of 64
3.8 Standard Program Controls
General Data
Sensor InputNTC
Protection1 x 1A fuse for the protection of the fan switching devices.
Fan Output3 o Relay for High, Medium and Low Fan setting 3A max 230vac
Screw terminals 4 for supply, 6 for elements output, 4 for fan output, 2 for
Connections
Supply415 3Ph or 230V 1Ph dependent on model type.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
DisplayThree 7-segment LCD red for parameter display
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for external door switch, 2 for 0-10v fan option, 2 for 0-5v fault output, 2 for lter
blocked, 2 for unit temperature.
3.9 SmartElec3 Controls
General Data
Sensor InputNTC
Control Setpoint16 to 35 ºC in steps of 1 degree
Temperature ControlProportional with 1ºC hysteresis
Minimum Power0% to 99 %
Cycle Time2 seconds xed
Protection2 x high speed fuse for the protection of the heater switching devices
Fan Output3 o Relay for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 5 for supply, 3 for heater output, 4 for fan output, 2 for BMS
Connections
Supply415V AC 50/60Hz 5VA max.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
(time) control, 2 for sensor input, 2 for external thermal trip, 2 for external
sensor, 2 for door, 2 for cooling fan on 24kW models. RJ45 comms connection
to base unit via pre-wired cable.
Mounting PositionsProgram panel xing centres 80mm x 20mm
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
DisplayThree 7-segment LCD red for parameter display
Temperature Control0-10v valve output (proportional)
Cycle Time2 seconds xed
Protection1 x 1A fuse for the protection of the mains input
Fan Output3 o Relays for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 3 for mains supply, 4 for fan output, 2 for BMS (time) control,
2 for sensor input, 2 for external thermal trip, 2 for external
Connections
Supply230 V 50/60Hz.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
sensor, 2 for door., 2 for 0-10v motor drive, 2 for 0-10v fan option, 2 for 0-5v
fault output, 2 for pipe cold input, 2 for unit temperature input, RJ45 comms
connection to base unit via pre-wired cable.
DisplayThree 7-segment LCD red for parameter display
4.1 Installer Wiring - Electrically Heated 6 & 9kW SINGLE PHASE ONLY
he program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
T
trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked eg. ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
It is recommended that this cable is run separately within its own
Mains Supply
FAN
L1
3 N
1 2
BASE UNIT
(located in air curtain)
ON
1 2 3 4
Pre-wired RJ45 plugs
& lead
SELECT
HE
HEHE HE
L2
B
A
RS485 Comms
HE HE
AB
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
L3
SYS
TEMP
FAN
External
FAULT
AB
FILTER
TIMER
STAT
N
DOOR
EXT
Pressure
Switch
External
Switch
(BMS)
Remove appropriate link
before connecting any
optional switches
CHASSIS
EARTH
Sensor
Programmer
Keypad
TerminalDescriptionCable
NNeutral
10mm² max
L1Phase 1 (or 1 Phase supply)
Pcb TerminalDescriptionCable
DoorOption door contact
1.5mm² max
Timer BMSOption external switch
Protection
External circuit breaker with the appropriate rating should be
installed for the protection of the installation.
Doc No. D301021 Page 20 of 64
Door
Switch
900640 CWL R1
PCB Terminal DescriptionCable
ExtOption internal/external sensor (supplied)
Filter blockOption lter blocked switch
Fail o/pFault output (0-5v)
1.5mm²
max
FanOption 0-10v fan output
Pcb FusesRating (A)
F1T1H (slow blow)
4.2 Installer Wiring - Electrically Heated 9, 12 & 18kW THREE PHASE ONLY
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
415v 3 ph + N 50hZ
Mains Supply
FACTORY
INSTALLED
FAN
L1
3
N
1 2
BASE UNIT
(located in air curtain)
ON
2 3 4
1
HE
AB
HE
RS485 Comms
HE
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
B
SYS
TEMP
L3
FAN
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
EARTH LINK.
DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
SELECT
Programmer
Keypad
TerminalDescriptionCable
NNeutral
L1Phase 1
10mm² max
L2Phase 2
L3Phase 3
Pcb TerminalDescriptionCable
DoorOption door contact
1.5mm² max
Timer/BMSOption external switch
External
Pressure
Switch
Sensor
External
Switch
(BMS)
Remove appropriate link
before connecting any
optional switches
Door
Switch
900641 CWL
PCB Terminal DescriptionCable
ExtOption internal/external sensor (supplied)
Filter blockOption lter blocked switch
Fail o/pFault output (0-5v)
FanOption 0-10v fan output
Pcb FusesRating (A)
F1T1H (slow blow)
1.5mm²
max
Protection
External circuit breaker with the appropriate rating should be
installed for the protection of the installation.
Doc No. D301021 Page 21 of 64
4.3 Installer Wiring - Ambient
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
BASE UNIT
(located in air curtain)
N
OUTPUT
STAT
TIMER
RETURN
DOOR
AIR
PIPE
COLD
EXT
N
L
E
RS485 Comms
230v 1ph + N
50hZ Mains
Supply
CHASSIS
EARTH
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
AIR
OUTLET
VALVE
FAN
3
2
1
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL
ON
2 3 4
1
FAN
0-10v
0-10v
FILTER
FAULT
Remove appropriate
link before connecting
any optional switches
External
Switch
(BMS)
Door
Switch
TerminalDescriptionCable
NNeutral
L1 Phase supply
Pcb TerminalDescription
DoorOption door contact
Timer BMSOption external switch
ExtOption internal/external sensor (supplied)
1.5mm²
max
SELECT
Programmer
Keypad
TerminalDescriptionCable
Filter blockOption lter blocked switch
Fail o/pFault output (0-5v)
Fan 0 -10vOption 0-10v fan output
Valve 0-10vOption 0-10v valve output
Pcb FusesRating (A)
F1T1H (slow blow)
900638 CWL
1.5mm²
max
Doc No. D301021 Page 22 of 64
Protection
External circuit breaker with the appropriate rating should be
installed for the protection of the installation.
4.4 Installer Wiring - LPHW
The program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
It is recommended that this cable is run separately within its own trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
BASE UNIT
(located in air curtain)
N
OUTPUT
STAT
TIMER
RETURN
DOOR
AIR
PIPE
COLD
EXT
N
L
E
RS485 Comms
230v 1ph + N
50hZ Mains
Supply
CHASSIS
EARTH
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
Pre-wired RJ45 plugs
& lead
AIR
OUTLET
VALVE
FAN
3
2
1
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL
ON
2 3 4
1
FAN
0-10v
0-10v
FILTER
FAULT
Modulating
Valve
Remove appropriate
External
Pressure
link before connecting
any optional switches
Switch
External
Switch
(BMS)
Door
Switch
TerminalDescriptionCable
NNeutral
L1 Phase supply
Pcb Terminal Description
DoorOption door contact
Timer BMSOption external switch
Ext Option internal/external sensor (supplied)
Air returnOption sensor
External circuit breaker with the appropriate rating should be
installed for the protection of the installation.
900639 CWL
1.5mm²
max
Doc No. D301021 Page 23 of 64
4.5 Factory Wiring - Electrically heated ACR1000/ACR1500 6kW SINGLE PHASE ONLY
R(B)
L(M)
L(B)
R(M)
L(T)
Elements
Fan Motor
BASE UNIT
(located in air curtain)
900658 IWL
23N
1
FAN
ON
2 3 4
1
Outlet
Sensor
L1
HE
HE
B
A
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
RS485 Comms
Overheat 1
HE
B
SYS
TEMP
Overheat 2
FAN
L3
FAULT
HE
A
HE
B
FILTER
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
Sensor
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
The element output is connected to the terminal blocks
marked “L1 A”, “L2 A&B”, L3 A&B” “N”
The fan output is connected to a 4 way connector marked
“Fan1, 2, 3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
TerminalDescription
NNeutral
L1 Phase supply
L1A ,L 2 A&B2 thirds heating elements
L3 A&B1 third heating elements
Pcb TerminalDescription
StatThermal overheat trip
Ext Option internal/external sensor (supplied)
Fan 1Fan - Low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
FilterFactory link
TimerFactory link
DoorFactory link
Doc No. D301021 Page 24 of 64
4.6 Factory Wiring - Electrically heated ACR2000 9kW SINGLE PHASE ONLY
R(B)
L(M)
L(B)
R(M)
L(T)
Elements
Fan Motor
900659 IWL
L1
3
N
2
1
FAN
BASE UNIT
(located in air curtain)
ON
2 3 4
1
Outlet
Sensor
HE
HE
B
A
HE
L2
A
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
RS485 Comms
Overheat 1
HE
B
SYS
TEMP
Overheat 2
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
Sensor
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
The element output is connected to the terminal blocks
marked “L1 A”, “L2 A&B”, L3 A&B”
The fan output is connected to a 4 way connector marked
“Fan1, 2, 3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
TerminalDescription
NNeutral
L1 Phase supply
L1A ,L 2 A&B2 thirds heating elements
L3 A&B1 third heating elements
Pcb TerminalDescription
StatThermal overheat trip
Ext Option internal/external sensor (supplied)
Fan 1Fan - Low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
FilterFactory link
TimerFactory link
DoorFactory link
Doc No. D301021 Page 25 of 64
4.7 Factory Wiring - Electrically heated ACR1000/ACR1500 9 & 12kW THREE PHASE ONLY
Elements
Fan Motor
BASE UNIT
(located in air curtain)
900660 IWL
3
2
1
FAN
ON
2 3
4
1
Outlet
Sensor
FACTORY
INSTALLED
EARTH LINK.
CHASSIS
EARTH
DO NOT REMOVE
HE
HE
L1
B
A
N
RS485 Comms
HE
HE
L2
B
A
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
SYS
TEMP
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
900641 CWL
Sensor
Overheat 1
Overheat 2
The element output is connected to the right and left side of
each terminal block marked “HE A” & “HE B”
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
TerminalDescription
L1,L2 & L3 HE AOne half of heating elements
L1,L2 & L3 HE BSecond half of heating elements
Pcb TerminalDescription
StatThermal Overheat trip
ExtOption internal/external sensor (supplied)
NNeutral
Fan 1Fan - low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
FilterFactory link
TimerFactory link
DoorFactory link
Doc No. D301021 Page 26 of 64
4.8 Factory Wiring - Electrically heated ACR1200/1800/2000 HE 12 & 18kW
ACR 2000 SE 18kW THREE PHASE ONLY
Elements
HE
Fan Motor
L1
3
N
1 2
FAN
BASE UNIT
(located in air curtain)
ON
2 3 4
1
HE
B
A
RS485 Comms
HE
HE
L2
B
A
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
SYS
TEMP
FAN
L3
FAULT
HE
A
FILTER
HE
B
TIMER
STAT
N
DOOR
EXT
CHASSIS
EARTH
FACTORY
INSTALLED
EARTH LINK.
DO NOT REMOVE
900661 IWL
Outlet
Sensor
Overheat 1
The element output is connected to the right and left side of
each terminal block marked “HE A” & “HE B”
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The thermal trips are connected to a 2 way connector marked
“Stat”
Sensor
Overheat 2
TerminalDescription
L1,L2 & L3 HE AOne half of heating elements
L1,L2 & L3 HE BSecond half of heating elements
Pcb TerminalDescription
StatThermal Overheat trip
ExtOption internal/external sensor (supplied)
Fan 1Fan - low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
FilterFactory link
TimerFactory link
DoorFactory link
Doc No. D301021 Page 27 of 64
4.9 Factory Wiring - Ambient ACR1000SA/ACR1500SA
Fan Motor
BASE UNIT
(located in air curtain)
3
N
2
1
FAN
ON
2 3 4
1
AIR
OUTLET
VALVE
0-10v
FAN
0-10v
FAULT
FILTER
TIMER
STAT
RETURN
DOOR
AIR
PIPE
COLD
EXT
FACTORY
INSTALLED
EARTH LINK.
N
L
E
RS485 Comms
DO NOT REMOVE
CHASSIS
EARTH
FACTORY INSTALLED
SENSOR (EXT) OPTIONAL,
DISCONNECTIF NOT
Sensor
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
The motor thermal trip is connected to a 2 way connector
marked “Stat”
The fan output is connected to a 4 way connector marked
“Fan 1,2,3 & N”
Pcb TerminalDescription
Fan 1Fan - low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
FilterFactory link
TimerFactory link
DoorFactory link
Air returnSensor (supplied)
Pipe coldSensor (supplied)
ExtOption internal/external sensor (supplied)
Air outletAir outlet sensor
Doc No. D301021 Page 31 of 64
4.13 Network Wiring - Ambient/LPHW
AIR
OUTLET
External
Switch
(BMS)
Switch
AIR
OUTLET
VALVE
0-10v
Door
VALVE
0-10v
(located in air curtain 1)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
(located in air curtain 2)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
STAT
DOOR
STAT
DOOR
Programmer
Keypad
SELECT
AIR
EXT
RETURN
PIPE
COLD
AIR
EXT
RETURN
PIPE
COLD
N
L
E
RS485 Comms
N
L
E
RS485 Comms
Sensor
Pre-wired RJ45 plugs
& leads
Networking
This diagram refers only to the wiring of 2 or
more networked air curtains. (maximum 16 air
curtains per control panel). For mains wiring
refer to section 4 of this manual ‘installer wiring
details’.
The program panel is connected to the base unit
in the rst air curtain via pre-wired lead tted
with RJ45 plugs.
Each subsequent air curtain is wired with the
same type of lead.
Max length 100m. (Total length of cable
used between program panel and last air curtain
in network).
It is recommended that this control cable is run
separately within its own trunking if possible to
avoid external interference.
Note: All air curtains connected within the
network system can be controlled under the user
settings of the single keypad.
For more information on setup and control
please refer to section 10 ‘User and Operating
Instructions’.
External
Switch
(BMS)
Switch
AIR
OUTLET
External
Switch
(BMS)
Door
VALVE
0-10v
(located in air curtain 3)
ON
2 3 4
1
FAN
0-10v
FILTER
TIMER
FAULT
STAT
DOOR
AIR
RETURN
PIPE
COLD
EXT
Sensor
N
L
E
RS485 Comms
To subsequent air curtains
(maximum of 16 )
Sensor
ON AN INDIVIDUAL BASIS!
Doc No. D301021 Page 32 of 64
4.14 Network Wiring - Electrically heated
Sensor
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 1)
External
Pressure
Remove appropriate link
Door
Switch
(BMS)
Switch
External
Switch
Networking
This diagram refers only to the wiring of 2 or
more networked air curtains. (maximum 16 air
curtains per control panel). For mains wiring
refer to section 4 of this manual ‘installer wiring
details’.
The program panel is connected to the base unit
in the rst air curtain via pre-wired lead tted
with RJ45 plugs.
RS485 Comms
Each subsequent air curtain is wired with the
same type of lead.
& lead
Sensor
Pre-wired RJ45 plugs
SELECT
Max length 100m. (Total length of cable
used between program panel and last air curtain
in network).
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 2)
External
Pressure
Remove appropriate link
Keypad
Programmer
It is recommended that this control cable is run
separately within its own trunking if possible to
avoid external interference.
Door
Switch
(BMS)
Switch
External
Switch
Note: All air curtains connected within the
network system can be controlled under the user
settings of the single keypad.
RS485 Comms
For more information on setup and control
please refer to section 10 ‘User and Operating
Instructions’.
Sensor
optional switches
before connecting any
EXT
N
B
HE
A
HE
DOOR
STAT
TIMER
FILTER
FAULT
FAN
SYS
TEMP
(located in air curtain 3)
RS485 Comms
External
Pressure
Remove appropriate link
Door
Switch
(BMS)
Switch
External
Switch
Doc No. D301021 Page 33 of 64
4.15 Installer wiring SmartElec3 control.
BASE UNIT
(located in air curtain)
415v 50Hz
MAINS SUPPLY
CHASSIS
EARTH
FACTORY INSTALLED
EARTH LINK. DO NOT
REMOVE
Sensor
Optional
Sensor
Door
Switch
Programmer
Keypad
SELECT
3
N
2
1
FAN
L1
terminals as
supplied
Pre-wired RJ45 cable
and plugs
900643 CWL
ON
1
2 3 4
TIMER
HE
L2
DOOR
J2J1
B.M.S.
Enable
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
N
DOOR
EXT
Interconnecting wiring
The program panel is connected to the base unit via a pre-wired RJ45 cables as shown and supplied in 2, 10, 20, 30, 50 and
100m lengths.
It is recommended that this control cable is run separately within its own trunking where possible to avoid external
interference.
Optional wiring
External switch (ie BMS enable) to be volt free and wired via normally open contacts to terminal pair ‘ TI M E R’. (Contacts closed
to enable). Remove factory tted jumper J1.
Door switch to be volt free and wired via normally closed
contacts to terminal pair ‘DOOR’. (Contacts open to enable
door mode). Remove factory tted jumper.
refer section 10.2.6.1 - Door link settings.
Internal/external sensor to be wired to terminal pair ‘EXT’.
refer section 10.2.6.4 - External Temperature.
Protection
There are two high speed fuses on the base unit to protect
the switching thyristors for the heater. An external circuit
breaker with the appropriate rating should be installed for
the protection of the installation.
4.16 Factory Installed Wiring. ACR1000/ACR1500 with SmartElec3 Control.
Fan motor
3
N
2
1
FAN
L1
BASE UNIT
(located in air curtain)
HE
L2
ON
2 3 4
1
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
N
DOOR
EXT
INSTALLED
EARTH LINK.
DO NOT REMOVE
CHASSIS
EARTH
FACTORY
900653 IWL
Outlet
Sensor
The heater element outputs are connected to the right
hand side of three terminal blocks and are marked ‘HE’.
(See below).
The fan output is connected to a 4 way terminal block
marked ‘N, 1, 2 and 3’.
The sensor input (air sensor) is connected to 2 terminals
marked ‘TEMP’ on the base unit. The sensor is not polarity
sensitive.
The external thermal trip (volt-free) is connected to 2
terminals marked ‘STAT’ on the base unit. The terminals
are not polarity sensitive.
J1
J2
Sensor
Optional
Sensor
q
Overheat 1qOverheat 2
TerminalDescriptionCable
HEHeating elements phase 1
HEHeating elements phase 2
HEHeating elements phase 3
NNeutral to fan
Fan 1Fan - low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
Tem pAir sensor pair (non-polarised)
StatExt thermal trip pair, n.c. (volt-free)
ExtOption internal/external sensor (supplied)
CommsKeypad/network connectorsRJ45
10mm²
max
1.5mm²
max
Doc No. D301021 Page 35 of 64
4.17 Factory Installed Wiring. ACR1200/ACR1800HE/ACR2000HE with SmartElec3 Control
Fan motor
FACTORY INSTALLED
EARTH LINK. DO NOT
REMOVE
3
N
2
1
FAN
L1
HE
L2
BASE UNIT
(located in air curtain)
ON
2 3 4
1
900663 IWL
Outlet
Sensor
The heater element outputs are connected to the right
hand side of three terminal blocks and are marked ‘HE’.
(See below).
HE
Comms
RS485
L3
TEMP
HE
TIMER
STAT
J1J2
CHASSIS
N
DOOR
EXT
EARTH
Optional
Sensor
Sensor
q
Overheat 1qOverheat 2
The fan output is connected to a 4 way terminal block
marked ‘N, 1, 2 and 3’.
The sensor input (air sensor) is connected to 2 terminals
marked ‘TEMP’ on the base unit. The sensor is not polarity
sensitive.
The external thermal trip (volt-free) is connected to 2
terminals marked ‘STAT’ on the base unit. The terminals
are not polarity sensitive.
Doc No. D301021 Page 36 of 64
TerminalDescriptionCable
HEHeating elements phase 1
10mm² maxHEHeating elements phase 2
HEHeating elements phase 3
NNeutral to fan
Fan 1Fan - low speed
Fan 2Fan - medium speed
Fan 3Fan - high speed
1.5mm² max
Tem pAir sensor pair (non-polarised)
StatExt thermal trip pair, n.c. (volt-free)
ExtOption external sensor (supplied)
CommsKeypad/network connectorsRJ45
4.18 Network Wiring with SmartElec3 Control.
Pre-wired RJ45 cable and plugs
BASE UNIT
(air curtain '0')
Comms
RS485
TEMP
TIMER
STAT
DOOR
EXT
Sensor
Optional
Sensor***
Door
Switch**
B.M.S.
Enable*
Programmer
Keypad
BASE UNIT
(air curtain '1')
Comms
RS485
TEMP
TIMER
terminals as
STAT
DOOR
EXT
TIMER
J1
Sensor
Optional
Sensor***
Switch**
To subsequent air curtains
(maximum of 16)
supplied
DOOR
J2
Door
SELECT
This diagram refers only to the wiring of 2 or more networked air curtains. (maximum 16 air curtains per control panel). For
mains wiring refer to section 4 of this manual ‘installer wiring details’.
The program panel is connected to the base unit in the air curtain via pre-wired RJ45 cable/plugs. These cables are available in
2, 10, 20, 30, 50 and 100m lengths. It is recommended that this control cable is run separately within its own trunking to avoid
external interference.
Max cable run in any network must not exceed 110m in total including program panel cable.
Note: All air curtains connected within the network system will operate under the settings of the single keypad.
Any air curtain within the network can be connected with and respond to the following optional circuits:
* External switch (ie BMS enable) where required, to be volt free and wired in PARALLEL via normally open contacts to each
terminal pair ‘ T I M ER ’. (Contacts closed to enable). Only air curtain(s) wired this way will respond to the enable signal. Remove
factory tted jumpers J1. (NOTE: terminals are polarity sensitive)
** Door switches where required, to be volt free and wired to INDIVIDUAL base units via normally closed contacts to each
terminal pair ‘DOOR’. (Contacts open to enable door mode). Only air curtain(s) wired this way will respond to the door mode.
Remove factory tted jumper J2. refer section 10.2.6.1 - Door link settings.
*** Internal/external sensors, where required, to be wired to INDIVIDUAL base units to each terminal pair ‘EXT’. Only air
curtain(s) wired this way will respond to the sensor setting. If a sensor is tted to more than one air curtain then the value is
displayed as an average. refer section 10.2.6.4 - External temperature.
Doc No. D301021 Page 37 of 64
5. Installation Details.
5.1 Mounting
irbloc units should be installed horizontally directly over
A
the door opening. They are designed for discreet
positioning in a suspended ceiling or bulkhead in the
doorways of retail or commercial premises. The unit can also
be mounted within an optional case for doorways with
restricted space or no suspended ceiling or bulkhead.
Care must be taken to allow complete free air movement
into the inlet grilles of the unit to ensure correct working
operation of the air curtain. The discharge opening should
be as close to the top of the door as possible and to cover the
entire door width.
Units can be mounted adjacent to each other to cover the full
door opening across wider entrances.
5.2 Electrical Supply.
the points of attachment to the building are sound.
Verication with the consultant/architect or owner of the
building is recommended to ensure that a sound,
mechanically stable installation can be achieved.
All attachments must be capable of supporting the weight of
the product detailed in Section 3.
Step 1
Before tting or wiring the air curtain, ensure casing faces as
below and see general installation guidance notes.
These units are suitable for connection to a 415 Volt, 50Hz 3
phase and neutral supply for Electrically heated 9-18kW
models or 230/240 Volt 50 Hz single phase supply for
Electrically heated 6kW, 9kW, Ambient and LPHW models.
Electrically heated models consume 6kW and 9kW at 230 volts
and 9kW, 12kW & 18kW at 415 volts when switched to the full
heat position depending on their model and capacity size.
The appliance should be connected to the supply via an
appropriate switched fused double pole isolator having a
contact separation of greater than 3mm. Test for correct
operation and ret the cover.
For connection to the mains supply it will be necessary to
open the hinged lid from the unit. The base unit is located on
a base plate. It will be necessary to connect the mains supply
and the lead from the remote key pad prior to retting the
cover. Wire in accordance to diagrams in section 4.1 to 4.4
For optional SmartElec3 controller, wire as shown in diagrams
4.15 to 4.18
Step 2
Using a 4mm Allen key slacken the captive M6 Allen screws at
the side of the grille.
For safety reasons, a sound earth connection must
always be made to the unit before it is put to use. The unit
should be wired in accordance with IEE Regulations for the
Electrical Equipment of Buildings.
5.3 Installation.
It is the sole responsibility of the installer to ensure that
Doc No. D301021 Page 38 of 64
Step 3
Step 6
Access to the inside of the air curtain grille can be made. Open
the grille. The grille is hinged to prevent the inner frame from
dropping.
Step 4
The grille assembly can now be removed from the case to
allow tting of the product in the ceiling recess. Remove the
screws from the outer frame to the top of the product case.
Either drop rods or catenary wire (available from
manufacturer) can be used to fasten the air curtain to the
ceiling support structure.
Note When using drop rods the casing mounting brackets
are slotted and the mounting plates provided must be used on
assembly.
Step 5
Attachment of the air curtain to the ceiling structure is by
means of the two brackets attached to the side of the air
curtain. The brackets may be removed to assist in passing the
air curtain through the recess then reattached when in-situ.
Step 7
The height between the ceiling face and the face of the air
curtain case needs to be adjusted to approx 40mm to enable the grille assembly to t ush with the ceiling. Adjust
accordingly.
Doc No. D301021 Page 39 of 64
After tting the product in the ceiling recess and adjusting the
height to ensure that the grille sits ush to the ceiling (when
re-tted) take the grille assembly and ret using the screws
removed during Step 5.
5.4 Program Keypad
The Electronic base unit is pre-installed inside the air curtain.
All the external electrical connections are via screw terminals
onto this unit.
The program keypad can either be installed on a standard
double surface box, or recessed using a double ush conduit
box.
Fig.5 Conduit box ush mounting
5.5 Option SmartElec3 Controller
The SmartElec3 base unit is pre-installed inside the air curtain.
All the external electrical connections except for the keypad
are via screw terminals onto this base unit.
Fig. 4. Surface mount dimensions.
148
43,5
87
120 crs
Alternatively, the program panel can be ush wall mounted
with the addition of a suitable conduit box as shown in Fig 8.
The SmartElec3 program panel is identical to the standard
program panel and will auto detect a Smartcom base unit
when plugged in.
The distance between the base unit and the program
panel can be up to 100m maximum.
Doc No. D301021 Page 40 of 64
5.6 Installation details - LPHW only
Fig. 6. Typical schematic of a 3 port valve system
To avoid risk of transit damage to the ow and return
connections, ON LPHW STANDARD CAPACITY ONLY the
heating coil is provided loose inside the case together with
the air deector plate and side supports.
NOTE: HIGH CAPACITY LPHW COILS ARE PRE-FITTED.
To install, unpack the loose items and identify the two side
supports as shown below and t to the inner side of the case
using the screws provided.
Note The side supports are handed.
The coils can be handed for right or left hand exit by
turning the coil through 180°. Prior to installation decide if
you require left hand or right hand exit of the ow and return
pipes from the product and then x the coil in position using
the screws provided.
The LPHW copper tubing connections are as shown in g.12
below and are 15mm outside diameter. Ensure correct water
seal ttings are used. We recommend the use of a suitable
water mains isolation valve to ease any maintenance.
Fig.12 LPHW connections.
FLOW/RETURN
CONNECTIONS
After tting the coil and side supports t the air deector plate
to the side supports and rotor cut-o plate using the screws
provided.
Carefully close the grille and ret the xing screw.
Test product as shown in the User Instructions.
Doc No. D301021 Page 41 of 64
5.6.1 Three Port Valve
An optional 3 port valve (supplied by others) can be used on
the ow and return pipes to divert the hot water from the unit
when not in use.
The valve must be tted in accordance with the
manufacturers instructions.
When used in conjunction with the LPHW
programmer, the 3 port valve can be wired into the base unit
to open the valve when heat is selected (see section 4.5). This
valve must operate on 0-10v DC.
Note: This option can not operate with a SmartElec
unit.
5.7 Installation wiring
With the grille door open, connect the electrical supply and
program panel interconnecting wiring/factory supplied cables
to the relevant terminals on the controller base unit.
Connect any interconnecting wiring/factory supplied cables
to the programme panel.
Connect any optional wiring as required.
Customer wiring terminals.
For full details see wiring diagrams in section 4. Ensure the
correct diagram is used based on the information from the air
curtain data plate and optional manufactures information.
Install the ACR unit using drop rods as previously described.
The sides of the case simply ‘wrap’ around the exposed body
of the air curtain xing at two edges (all four edges in the case
of the 2000mm), with screws.
5.8 Installation details - optional Case
The ACR unit can also be mounted within an optional
pre-coated outer case for use in doorways with restricted
space or areas with no suspended ceiling or bulkhead.
The cases either come in two halves (as shown) for the
1000mm and 1500mm or four individual sides for the
2000mm.
Doc No. D301021 Page 42 of 64
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE
THERE IS A CORROSIVE ATMOSPHERE.
6. Service & Maintenance.
ALWAYS ENSURE THAT THE EXTERNAL MAINS
ELECTRICITY SUPPLY IS SWITCHED OFF BEFORE COMMENCING
ANY MAINTENANCE ON THIS HEATER
To obtain the best results from the heater, it is essential
to avoid the accumulation of dust and dirt within the unit on
the air inlet and discharge grilles. For this reason regular
cleaning is necessary, paying particular attention to the
removal of dirt build up on the rotor blades.
Cleaning of the fan is best carried out with a soft brush.
A single drop of light oil should be applied to the motor
bearing from time to time.
The product should be serviced annually. Servicing shall be
undertaken by a competent person. Airbloc oer a service
facility, call 01384 489700.
Step 1
Using a 4mm Allen key slacken the captive M6 Allen screws at
the side of the grille.
Step 2
Open the grille. The grille is hinged to prevent the inner frame
from dropping. Access to the inside of the air curtain grille can
be made.
Step 3
With a soft brush clean away any dust from the motor and
elements.
Check all connections and components for soundness or signs
of deterioration and replace as necessary.
Re-assemble and test.
Doc No. D301021 Page 43 of 64
7. Spare Parts.
Note Any spare part components that are not approved by Nortek Global HVAC (UK) LTD could invalidate the approval of
the appliance and invalidate the warranty.
7.1 General
ItemDesc.
Motor100003100012100535
Rotor Left
Hand*
Rotor Right
Hand*
Thermal Cut
Out
(where reqd)
ACR1000SE06/
ACR1000SE09
ACR1000SW9/
ACR1000SA
ACR1500SE06/
ACR1500SE12/
ACR1500SW12/
ACR1500SA
ACR2000SE09/
ACR2000SE18/
ACR2000SW18/
ACR2000SA
ACR1200HE12/
ACR1200HW12/
ACR1200HA
ACR1800HE18/
ACR1800HW18/
ACR1800HA
100001100006100010100539100540
100002100007100011100536100537
900001
* Right hand & left hand when viewed from outside the building looking into the door opening.
7.2 Standard Controller
Due to the nature of it’s construction, it is not advisable to repair damaged electronic components on either the base unit
or programmer (keypad).
Program Panel
108221-RJ45
Base UnitSTDELECBU45 (electric) LPHWBU45 (LPHW+ambient)
Outside Air Sensor
Doc No. D301021 Page 44 of 64
SC-OS
7.3 SmartElec3 Controller
Due to the nature of it’s construction, it is not advisable to repair damaged electronic components on either the
SELEC3BU45 base unit or AC-ACRRP45 programmer
f the air curtain does not operate after running through the
I
detail provided in Section 10, then a suitably competent
service engineer should be called to identify the nature of the
fault.
Note The manufacturer operates a service function from the
address provided in these instructions.
All air curtains are tted with fuse protection and motor
thermal protection.
Other faults in relation to the element, motor and wiring
should be identied using conventional fault nding
techniques.
In the event that electrical components are replaced, please
ensure that electrical safety checks in accordance with the
regulations in force in the country of use are undertaken.
been cleared.
Apart from the communication failure alarm which
could be due to a broken connection of the data link and air
curtain not found alarm, which could be due to
incorrect addressing, all other alarms will cause the base unit
to switch o the heater output.
The SmartElec3 base unit is protected from any short circuit
on the air sensor or heat sink sensor as
the error will cause the temperature to rise and trigger over
temperature alarm.
There are ve basic checks to perform should ‘X--’
appear on the program panel display. These are as follows:
1: Continuity: Use a multimeter to check continuity between
each end of all four cores at the plugs
8.2 Electrically heated units only.
For the service engineer, please note that there are two
thermal cut-outs incorporated in the air curtain which, if
tripped, need to be manually reset. The cut-outs are located in
the airow near to the elements on the left and right.
Re-setting the thermal cut-out may help to identify the nature
of the fault however we do not recommend a re-set without a
thorough investigation into why the cut-out operated.
Fig. 13. Thermal Cut-out
2: Short circuit: Use a multimeter to check that there are no
short circuits between any of the four cores.
N.B. This test should be done with both ends of the cable
disconnected to avoid false readings.
3: Plugs: Check that the plugs are rmly seated on the circuit
board in both the program panel and on the base unit.
4: Addressing: (network versions only). If two or more air
curtains are networked, check that each base unit has a
unique address as described in section 10.2.8.
5: Network cables: Ensure that the total run of all cables in
the network does not exceed 110m including the cable to the
program panel.
If a panel has never before been run, it automatically starts in
engineer’s mode when rst powered-up. To exit this mode,
press and hold the button.
Alternatively, the engineer’s mode automatically self-clears
after approximately 10 minutes of non-activity on the
buttons.
8.3 Standard Controller.
For fault codes refer to SmartElec3 fault table on next page.
8.4 SmartElec3 Controllers.
The SmartElec3 control raises an alarm if any of its inputs are
outside their normal working scope. Alarms are displayed on
the program panel as a code with a prex “E” . The
rst number represents the air curtain address. See chart over.
As the alarms are mutually exclusive, the rst alarm code
displayed on the program panel will stay on until the fault has
Doc No. D301021 Page 46 of 64
The system can be reset by powering-up the panel whilst
holding down both the and buttons.
The display shows the ‘start’ pattern but then goes blank.
Release the buttons. The display resumes and the system
nds only those air curtains which are actually connected and
working.
If appears on the display, press and hold the
button for a few seconds then release. The display will then
return to the normal mode.
8.4.1 SmartElec3/Standard Fault Codes
# = Air curtain address
#_ _, #E1, #E2, #E5 and #E6 codes also apply to standard controller.
Code DescriptionSymptomPossible CauseRemedy
# _ _
# E1
# E2
# E3
# E4
# E5
# E6
Communications failureNo control on unit
Air sensor failedFan operating, no heat
Air sensor temp too high Fan operating,no heat
Heatsink too hotFan operating, no heat
Heatsink sensor failureFan operating, no heat
Ext. temp sensor failure
Overheat stat open
circuit
Unit runs but no external temperature
control
Fan operating, no heatOverheat stat open circuitReplace overheat thermostat
Bad data cable connection
Damaged cable
Air sensor cable disconnected
Air sensor broken
High ambient air temperature
Incorrect impeller rotation
Motor failure
High ambient air temp/faulty
base unit
Heatsink sensor wiring
disconnected/faulty
Heatsink sensor faulty
External temperature sensor
faulty
Check data cables and plugs
Replace damaged cable
Check cable
Replace air sensor
Check ventilation
Check rotation of impeller
Check motor, replace if
necessary
Replace SmartElec base unit
Check wiring
Replace SmartElec base unit
Repair faulty wiring
Replace faulty sensor
8.4.2 SmartElec3 base unit LED indicator location/function
Note: Standard controller LEDs have the same function and are in similar positions on the PCB.
Doc No. D301021 Page 47 of 64
9. Parts Replacement.
Warning
Ensure electrical power is isolated from the product.
For access follow steps 1 - 4 as stated in Section 6
9.1 Electrical element replacement SE.
Step 1
Using a 4mm Allen key slacken the M6 Allen screws at the side
of the grille. Access to the inside of the air curtain grille can be
made. Open the grille. The grille is hinged to prevent the inner
frame from dropping.
9.2 Electrical element replacement HE.
Step 2
Disconnect element wires and if necessary remove cut-o
plate xing screws.
Step 3
Remove element top xing screws. Locate and remove
element xing screws by inserting a screwdriver through the
hole indicated below.
Step 1
Using a 4mm Allen key slacken screws securing the grille.
Remove 4 screws securing the top of the case and remove.
Slacken two hinging bolts on both ends. Remove three bolts
securing the access plate. Carefully hinge down the access
plate.
Note: Take the weight as access plate swings down.
Step 2
Carefully remove connections to the elements, noting wiring
conguration.
Step 4
Lift out element cartridge, replace as required.
Doc No. D301021 Page 48 of 64
Step 3
Remove two bolts securing elements.
Step 4
Lift out element cartridge, replace as required.
9.3 Rotor and motor replacement SE
Step 1
Using a 4mm Allen key slacken the M6 Allen screws at the side
of the grille. Access to the inside of the air curtain grille can be
made. Open the grille. The grille is hinged to prevent the inner
frame from dropping.
Step 4
Using a 2.5mm Allen key, slacken the rotor hub grub screw.
Note: when retting ensure that the grub screw bears on the
at of the motor shaft.
Step 5
Push the rotor support bracket away from the rotor to release
the rotor bearing.
Step 2
Remove fastenings securing the motor end of the deector
plate, including the single side screw (arrowed).
Step 3
Remove the four screws securing the rotor support bracket
and the opposite end of the deector plate. Remove plate.
Step 6
Lift the rotor clear of the motor shaft then remove it from the
air curtain.
Step 7
Disconnect fan motor cables from the terminals arrowed
including the earth which is bolted to the chassis. (SmartElec
shown over).
Fan terminals (similar position on
LPHW)
Doc No. D301021 Page 49 of 64
Step 8
Remove the four 10mm bolts securing the motor to its
bracket.
Carefully hinge down the access plate.
Note Take the weight as access plate swings down.
Step 2
Remove 6 screws securing access panel and carefully remove
panel.
Step 9
Swing the movable bracket clear and remove the motor.
Step 3
Remove 8 bolts securing wheel assembly.
Step 4
Turn retaining latch to release chassis.
9.4 Rotor and motor replacement HE
Step 1
Using a pozidrive screwdriver undo screws securing the grille
and remove.
Remove 4 screws securing the top of the case and remove.
Slacken two hinging bolts on both ends.
Remove three bolts securing the access plate.
Doc No. D301021 Page 50 of 64
Step 5
Holding handle, carefully pull motor and air wheel assembly
forward.
Step 6
Remove screw securing rotor bearing plate.
Repeat for opposite side.
Step 8
Disconnect the wires from the motor to the controller base
unit.
Fan terminals (similar position on
LPHW)
Step 9
Remove the bolts securing the motor to the chassis.
Step 7
Slacken grub screw securing rotors to the motor shaft, remove
rotor.
Repeat for opposite rotor.
Remove motor from air curtain.
Replace motor in reverse order. Carefully close the grille and
ret the xing screw.
Test product as shown in the User Instructions.
9.5 LPHW coil replacement.
Step 1
Using a 4mm Allen key slacken screws securing the grille.
Remove 4 screws securing the top of the case and remove.
Slacken two hinging bolts on both ends.
Remove three bolts securing the access plate.
Carefully hinge down the access plate.
Note: Take the weight as access plate swings down.
Doc No. D301021 Page 51 of 64
Step 2
Disconnect ow/return connections with appropriate tools.
Step 3
Remove the air deector plate and the side support plates,
retaining the screws.
Step 4
Remove coil xing screws from the outside of the air curtain
body.
Step 5
Withdraw the coil.
Replace LPHW coil in reverse order.
Doc No. D301021 Page 52 of 64
10. User Instructions.
10.1 Standard Controller (electrically heated)
10.1.1 Keypad Buttons
‘1’ denotes the AIR CURTAIN ADDRESS, and ‘27’ the current
outlet temperature.
If the display is set to ‘H1’ (half heat) then the display unit will
show:
The ‘dot’ after the air curtain number denotes heat setting 1.
If the display is set to ‘H2’ (full heat) then the display unit will
show:
The ‘dot’ after the temperature number denotes heat setting
2.
If an external temperature sensor is tted then the display will
also show:
The button will allow you to navigate.
The button will allow you to increase the setting.
The button will allow you to decrease the setting.
10.1.2 Operation
On rst power up, the display will show
and have the following default settings:
• F. 0 (no fan)
• H. 0 (no heat)
• 16 (°C. Heat set point)
The small ‘zero’ shows a sensor detected and it’s current
temperature reading.
10.1.3 Standard Settings
Press the button. This will cause the display to brighten
and display air curtain number and it’s fan speed eg.
Press the or buttons to increase/decrease the desired
setting between F0, 1, 2, or 3.
Pressing the button again will display the air curtain
number and it’s heat setting eg.
Press the or buttons to increase/decrease the desired
setting between H0, 1, or 2.
If no air curtains are detected the display will show:
Note: Subsequent power ups will retain any entered settings
in the display internal memory.
In normal operation the display will show for example:
Pressing the button again will loop back to start if only
one air curtain is connected to the display unit. If there is
more than one connected the display unit will then show the
settings for the next air curtain in the network and so on.
10.1.4 Engineers Settings
To turn on the engineers settings press and hold the
button until the display goes blank then press the button.
The display unit will now display ’Eng’ briey.
Doc No. D301021 Page 53 of 64
This will disappear after a period of 10 minutes of inactivity on
the keypad.
On pressing the button the display unit now works in the
same way as standard for the fan and heat settings, but then
an adjustable control temperature setting appears (if external
sensor tted).
This control works by reading the temperature at the sensor and
comparing it to the set point. The temperature is then controlled
by automatically switching the controller outputs between H0,
H1, and H2, thus maintaining reasonable heat control.
Press the or buttons to increase/decrease the desired
setting between C0, or 1-7 (see table below).
If the air curtain is set to eg.:
This denotes that air curtain ‘1’ is set to be the master for door
and BMS interlocks. If interrogated all other air curtains will
then display eg.
This denotes a unit that is not the master.
Pressing the button again advances to the door link
settings.
10.1.4.1 Door Link Settings
Two settings are available for use when the door link circuit
terminals are open circuit (PCB link removed). The rst of these
is displayed as:
‘1’ is the air curtain address and ‘d2’ denotes fan speed 2.
Press the or buttons to increase/decrease the desired
setting between d0, 1, 2, or 3.
The second is displayed as:
‘1’ is the air curtain address and ‘t1’ denotes heat setting 1.
Press the or buttons to increase/decrease the desired
setting between t0, 1 or 2.
‘C’ interlocks
setting
1
2
4
‘L’ interlocks
setting
1
2
4
To set more than one interlock, add the appropriate numbers
together, eg. ‘C3’ above works on timer and door interlocks.
If a controller is not the master, all three interlock links
must be in place.
Eect
Timer/BMS interlock
Door interlock
Stat interlock
Eect
Not used
Not used
Blocked lter interlock
10.1.4.3 All Controllers
Pressing the button again advances to the link group
interlock settings.
10.1.4.2 Link-Group Interlock
If there is more than one air curtain connected to the display
then there are two sets of interlocks available to enable a
single air curtain in a group to be the ‘master’ controller based
on links used.
‘1’ is the air curtain address and ‘C0’ is the default setting (no
interlock set)
Doc No. D301021 Page 54 of 64
This setting can be accessed from the engineers settings
whilst the external temperature indication is showing (see
previous page). This is displayed as:
This allows a single group of settings to be copied to all
controllers in a network. Individual settings can still be used at
a later date if required.
Quick Options
1. Immediate turn o:
Press and hold the button for two seconds, the display
will go blank then the air curtain(s) will turn o.
2. Re-scan/Engineers mode:
Press and hold the button for two seconds, the display
will go blank, then press The display will show the
controller type in the rst digit and the number of air curtains
in the fourth digit. Release both buttons and then press any
button to continue, the panel is now in Engineers mode.
‘1’ denotes the air curtain address, and ‘27’ the current outlet
temperature.
If the display is delivering power then the display will show:
3. Turn on Engineers mode:
Press and hold the button for two seconds, the display
will go blank, then press the display will show ‘Eng’,
Release both buttons.
4. Turn o Engineers mode:
Press and hold the button for two seconds, the display
will go blank, then release.
5. Air curtain addressing: See section 10.2.8
10.2 LPHW/Ambient Controller
10.2.1 Keypad Buttons
If an external temperature sensor is tted then the display will
also show:
10.2.3 Standard Settings
Press the button. This will cause the display to brighten
and display air curtain number and it’s set point temperature
eg:
Pressing the button again will show the fan settings eg:
Pressing the button again will show the heat settings eg:
The button will allow you to navigate.
The button will allow you to increase the setting.
The button will allow you to decrease the setting.
10.2.2 Operation
On rst power up, the display will show
and have the following default settings:
• F. 0 (no fan)
• H. 0 (no heat)
• 16 (°C. Heat set point)
If no air curtains are detected the display will show:
Note: Subsequent power ups will retain any entered
settings in the display internal memory.
In normal operation the display will show for example:
10.2.4 Engineers Settings
To turn on the engineers settings press and hold the
button until the display goes blank, then press the button.
The display unit will now display ’Eng’ briey.
This will disappear after a period of 10 minutes of inactivity on
the keypad.
On pressing the button again the display unit now works
in the same way as standard for the fan and heat settings. The
next press of will advance to the ‘door link’ settings if
only one air curtain is connected, or ‘link group interlocks’ if
more than one air curtain is connected.
10.2.4.1 Door Link Settings
Two settings are available for use when the door link circuit
terminals are open circuit (PCB link removed). The rst of these
Doc No. D301021 Page 55 of 64
is displayed as:
10.2.4.3 All controllers
‘1’ is the air curtain address and ‘d2’ denotes fan speed 2.
Press the or buttons to increase/decrease the desired
setting between d0, 1, 2, or 3.
The second is displayed as:
‘1’ is the air curtain address and ‘t1’ denotes heat setting 1.
Press the or buttons to increase/decrease the desired
setting between t0, 1, 2, 3 etc. where 0 is heat o
1 is 5C
2 is 10C
3 is 15C
Pressing the button again advances to the link group
interlock settings.
10.2.4.2 Link-Group Interlock
If there is more than one air curtain connected to the display
then there are two sets of interlocks available to enable a
single air curtain in a group to be the ‘master’ controller based
on links used.
‘C’ interlocks
setting
1
2
4
‘L’ interlocks
setting
1
2
4
This setting can be accessed from the engineers settings
whilst the external temperature indication is showing (see
previous page). This is displayed as:
This allows a single group of settings to be copied to all
controllers in a network. Individual settings can still be used at
a later date if required.
Eect
Timer/BMS interlock
Door interlock
Stat interlock
Eect
Not used
Not used
Blocked lter interlock
10.2.4.4 External Temperature
‘1’ is the air curtain address and ‘C0’ is the default setting (no
interlock set)
Press the or buttons to increase/decrease the desired
setting between C0, or 1-7 (see table below).
If the air curtain is set to eg.:
This denotes that air curtain ‘1’ is set to be the master for door
and BMS interlocks. If interrogated all other air curtains will
then display eg.
This denotes a unit that is not the master.
To set more than one interlock, add the appropriate numbers
together, eg. ‘C3’ above works on timer and door interlocks.
Display will show eg:
This will only be displayed if there is an external sensor tted,
and shows the external sensor temperature set point. Once
set the air curtain will turn o when it reaches the set point.
The temperature then has to drop 3C before the air curtain
turns back on again.
10.2.4.5 External Temperature Oset
Display will show eg:
If the outside temperature falls to zeroC, this setting shows
the temperature offset above zero. This will temporarily
raise the temperature setting 6C above the actual set point.
Possible settings are 0-9 where 0 is off if this function is not
required.
If a controller is not the master, all three interlock links
must be in place.
Doc No. D301021 Page 56 of 64
10.2.4.6 Temperature Limits
The next two displays eg:
These show the permissible upper and lower limits for setting
the external temperature sensor set point. This is useful for
allowing the end user limited control over this setting. The
maximum (default 35C) may be set anywhere between the
current minimum and 50C, and the minimum (default 16C)
may be set anywhere between 3C and the current maximum.
10.2.4.7 Air Return and Pipe Cold Sensors
The readings from these sensors is not shown on the
display, and unless both are connected there is no eect on
the heating control. When both sensors are connected they
operate as follows: When the heating is rst turned on the
temperature readings from the sensors should be close
together, two minutes later there should be a dierence of at
least 2C. If there is no dierence then the controller assumes
that there is no ow then turns the heating o.
Doc No. D301021 Page 57 of 64
10.3 Option SmartElec3 Controller
10.3.1 Keypad buttons
During normal operation, press and hold the button for
approximately two seconds. The display blanks until you
release the button. The heating and fans are now turned o.
Releasing the button in less than this time and the action has
no eect.
Where multiple air curtains exist in a network, this action
turns o all air curtains.
The buttons have the following functions:
Press the select button to allow navigation.
Press the + button to increase a setting.
Press the - button to decrease a setting.
10.3.2 Operation
10.3.2.1 Normal mode displays
First power up
No air curtains found
Curtain address and temperature set point
10.3.2.2 Normal Operation
10.3.4 Settings Mode
10.3.4.1 Activate settings display
To enter the Settings mode press the button. This will
illuminate the screen. Press the button till the desired
setting is shown.
By pressing the button it will also advance to the next
setting.
Note: If a setting has been altered by using the or
buttons, it must be conrmed by pressing the button.
10.3.4.2 Settings displays
Press the button to advance through the settings. The
displays will scroll as follows:
During normal operation mode the display is dimmed.
Pressing the button, will put the panel into active mode. If
During normal operation the unit will display for example:
where ‘0’ is the curtain address, and ‘25’ the
temperature measured for the unit.
Where multiple air curtains exist in a network, the display
scrolls through each unit in turn, changing approximately once
every second.
If the air curtain is in operation and under heat demand,
a ‘decimal point’ is shown after the air curtain
address.
Quick Options
These are identical to the quick settings for the standard
controller so please refer to that section of the manual.
10.3.3 OFF mode.
Where multiple air curtains exist in a network and controlled
from a single keypad, these will be detected and displayed in
turn, for example:
Any air curtain in the network can be accessed by pressing the
button when it’s address appears on the display.
The settings can then be accessed as previously described.
Doc No. D301021 Page 58 of 64
10.3.5 Set-up congurations
10.3.5.1 Set fan speed
when it’s address appears on the display.
The settings can then be changed as previously described.
Once the display becomes illuminated press the the
button once. Display shows the fan speed.
Press to increase fan speed.
Press to decrease fan speed.
Three speeds and an ‘o’ setting are available:
Speed 1 Speed 2
Speed 3 Fan ‘o’
10.3.5.2 Set heat
Press the button again Display shows the heat setting.
Press to set heat ‘on’.
Press to set heat ‘o’.
If no button pressed for 2 seconds, display will revert to
normal user. e.g.
10.3.5.3 Set temperature
10.3.6 Engineers settings
Other options are available in engineer’s mode.
To access the engineers mode either: press and hold the
button for a few seconds until the display goes blank, then
press briey. The display will show
or
Power-up the system with the and buttons pressed
and release when the display goes blank the display will show
As in normal mode, Engineers set-up mode is started by
pressing the button whereupon the display will
illuminate. Advance through the normal modes settings of
temperature, fan and heat by pressing the button.
Pressing the button again advances to further options to
allow other settings of the system. The engineers set-up
options listed herewith depend various factors e.g. optional
door switch, multiple air curtains etc.
Notes: If a panel has never before been run, it automatically
starts in engineer’s mode when rst powered-up.
Engineer’s mode automatically self-clears after
approximately 10 minutes of non-activity on the buttons.
10.3.6.1: Door link settings:
Press the button once to allow changes to be made.
Press to increase temperature set point. (max 35°C )
Press to decrease temperature set point. (min 16°C)
Display shows for example:
10.3.5.4 Networked air curtains
Where multiple air curtains exist in a network and controlled
from a single keypad, these will be detected and displayed in
turn, for example:
Any air curtain in the network can be accessed by pressing
This provides an alternative fan speed and heat setting which
is activated only when the door link is open circuit.
The fan speed is accessed by pressing the the button until
the display shows: Use the and buttons
to change the setting.
Fan OFF
Fan speed 1
Fan speed 2
Fan speed 3
The temperature setting when the door link is open circuit is
accessed by pressing the button until the display shows:
Use the and buttons to alter the temperature value.
Doc No. D301021 Page 59 of 64
Heat OFF
5°C
10.3.6.3 All controllers
This function is accessed by pressing the button until the
display shows
10°C
15°C
20°C
25°C
30°C
35°C
10.3.6.2 Link-group interlock
If there is more than one air curtain, a group interlock option
may be set. This provides an alternative fan speed and heat
setting when activated by certain external connections on
individual air curtains.
This function is accessed by pressing the button until the
display shows (where ’0’ is the air curtain address
to be used as a master unit for interlocks.)
Using this setting all air curtains in a network respond to the
same settings. Settings for individual air curtains can still be
changed if required.
10.3.6.4 External temperature
This is only displayed if the factory supplied optional external
temperature sensor is connected to the air curtain.
This function is accessed by pressing the button until the
display shows:
Use the and buttons to change to the desired
temperature setting.
If the external temperature is equal to the set temperature, all
air curtains are turned o. The temperature must then drop
to 3°C below the set temperature before the air curtains are
turned back on.
Note: for multiple air curtains - more than one can have an
external sensor connected. When this is the case the sensor values
are displayed as an average. (If one external sensor goes faulty,
the average is worked out from the remaining working ones).
See table to follow for possible settings.
Default setting
or Master setting range
Other air curtains
See table below for possible settings.
Master settingFunction
1Timer/BMS interlock
2Door interlock
3Timer/BMS/door interlock
4Stat interlock
5Timer/BMS/stat interlock
6Stat/door interlock
10.3.6.5 External temperature oset
This function is accessed by pressing the button until the
display shows:
This setting allows the temperature setpoint to be
automatically increased as the external temperature falls to, or
below, zero. For instance, a setting of 4 means a +4°C oset at
0°C. The maximum oset is 9°C. If this feature is not required
the setting should be:
7Timer/BMS/stat/door interlock
Doc No. D301021 Page 60 of 64
Note: When more than one air curtain is used, this feature
will only work under the ’all controllers’ setting.
10.3.6.6 Temperature limits
This function is accessed by pressing the button until the
display shows:
and respectively
i.e. maximum and minimum set limits for set temperature.
Use the and buttons to change to the desired limit
temperature settings.
The maximum (default 35°C) may be set any where between
the current minimum and 50°C, and the minimum, (default
16°C) may be set anywhere between 3°C and the current
maximum.
To exit the engineers mode press and hold the button for
a few seconds.
Power-up Manual Reset.
10.3.7 Power-up Manual Reset
The system can be reset by powering-up the panel whilst
holding down the and buttons. The display shows the
‘start’ pattern but then goes blank.
Release the buttons where upon the display resumes and the
system addressing commences, nding only those air curtains
which are actually connected and working.
If appears on the display, press and hold the
button for a few seconds then release. The display will then
return to the normal mode.
10.3.8 Air curtain addressing (standard and
SmartElec)
All air curtains work on an address to communicate with the
keypad and are supplied with an default address of ‘0’.
Where multiple air curtains exist in a network they must be
re-addressed using a unique address (0-9/A-F). This is achieved
using a 4 way bitswitch mounted on the base unit PCB (see
photo on following page.
g. 16. Air curtain address numbers
The black shaded areas represent the switch position.
This example shows the
air curtain set to No.8
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE
THERE IS A CORROSIVE ATMOSPHERE
Bitswitch location on PCB
The keypad will check all addresses on rst power up and this
is displayed as the rst digit on the display (in a network set
up, all addressees will be viewed in rotation).
Note: If any address is altered after initial power up or an
air curtain removed after initial installation, the keypad will also
retain the original address although unable to respond.
To remove this unwanted address(s) follow the details in 10.3.7
Doc No. D301021 Page 61 of 64
10.3.9 Keypad sequences (standard /LPHW)
Standard - Normal set-up
LPHW - Normal displayStandard - Normal display
LPHW - Normal set-up
Standard - Engineers mode display
LPHW - Engineers mode display
Doc No. D301021 Page 62 of 64
LPHW - Engineers mode set-up
Standard - Engineers mode set-up
10.3.10 Keypad sequences (SmartElec controller)
Engineers mode display
Normal set-up
Doc No. D301021 Page 63 of 64
Engineers mode set-up
Normal display
AFFIX AGENTS DETAILS HERE
Registered in England No˚ 1390934
Registered Office: The Colmore Building, 20 Colmore Circus Queensway, Birmingham, West Midlans, B4 6AT
Document reference number: D301051
Nortek Global HVAC (UK) LTD
Fens Pool Avenue, Brierley Hill
West Midlands, DY5 1QA
United Kingdom
Tel: +44 (0) 1384 489 250
Fax: +44 (0) 1384 489 707
Email: reznorsales@nortek.com
Web: www.reznor.eu/
Replaces Document reference number: D301021 R1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.