Nortek Global HVAC (UK) Limited equipment must be installed and maintained in accordance with the
requirements of the Codes of Practice or rules in force. All external wiring MUST comply with the codes of practice
or rules in force in the country of installation.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
Read instructions before installing or servicing this equipment. Gas-fired appliances are not designed for use in
hazardous atmospheres containing flammable vapours or combustible dust, containing chlorinated or halogenated
hydrocarbons, or in applications with airborne silicone substances.
Reznor® is a registered trademark of Nortek Global HVAC, LLC.
ErP
2018
Part No. D301051
Introduction.
elcome to the range of Airbloc ACR Recessed Air Curtains. Local regulations may vary in the country of use and it is the
W
installers responsibility to ensure that such regulations are satised
All installation and assembly procedures must be carried out by suitable competent persons. Commissioning and
service procedures must be carried out by suitable qualied persons to the statutory regulations in the country of use.
When installing, commissioning and servicing is undertaken on these air curtains due care and attention is
required to ensure that working at height regulations are adhered to, at the mounting heights specied.
All Dimensions shown are in mm unless otherwise stated.
PLEASE READ this document prior to installation and use. The safety of this heater is guaranteed only by the correct usage
in accordance with these instructions, therefore it is recommended that they are retained for future reference.
The manufacturer reserves the right to alter specications without prior notice.
Any reference made to Laws, Standards, Directives, Codes of Practice or other recommendations governing the
application and installation of heating appliances and which may be referred to in Brochures, Specications, Quotations,
and Installation, Operation and Maintenance manuals is done so for information and guidance purposes only and should
only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters
arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations.
IMPORTANT NOTICE TO INSTALLERS
Installers should satisfy themselves that the gas pipework installation is carried out in accordance
with all current legislation, Codes of Practice and recommendations .
Additionally it may be necessary to protect the gas valves which form part of the heater or burner
assembly from potential pipe contamination particularly, but not exclusively, where copper gas
pipework is used.
In instances where copper pipework is to be used for all or part of a gas pipework installation, including
short length nal connections then we advise that installers consult with gas supplier or provider and
satisfy themselves what additional precautions may be necessary.
Isolate any electrical supply to the heater and controller
before proceeding.
1.1 Compliance notices
he Airbloc ACR Recessed Air Curtain detailed herewith are
T
manufactured by Nortek Global HVAC (UK) Ltd. within a
strictly controlled quality environment within the parameters
of ISO 9001.
the use of the appliance so as to ensure its continued safe and
ecient use.
Nortek Global HVAC (UK) Ltd. have a commitment to
continuous improvement and therefore reserves the right
to amend or change the specication of the Airbloc ACR
Recessed Air Curtain range subject to compliance with the
appropriate European, national, and local regulations.
Contained within the text of the manual, the words ‘Caution’
and ‘Warning’ are used to highlight certain points.
These instructions are only valid if the following country code
is on the appliance GB. IE. If this code is not present on the
appliance, it is necessary to refer to the technical instructions
which will provide the necessary information concerning the
modication of then appliance to the conditions of use for the
country.
The Airbloc range has been tested and assessed for
compliance with the following European Directives.
The manufacturer has taken reasonable and practical steps to
ensure that Airbloc ACR Air Curtains are safe and without risk
when properly used. These air curtains should only be used in
the manner and purpose for which they were intended, and in
accordance with the recommendations detailed herewith.
The ACR Air Curtains have been designed, manufactured,
assembled, inspected, and tested, with safety and quality in
mind, there are certain basic precautions which the installer
and user should be aware of, and they are strongly advised to
read the appropriate sections of the information pack
accompanying the heater, prior to installation or use.
Nortek Global HVAC (UK) Ltd. supports all new products being
supplied to their customers with a comprehensive information
pack; this clearly denes mandatory instructions for the safe
installation, use, and maintenance, of the appliance(s).
Where proprietary items are incorporated into Airbloc
products, detailed information and instructions are also
provided as part of the information pack.
It is the responsibility of the installer, owner, user, or hirer, of
such products supplied by Nortek Global HVAC (UK) Ltd., to
ensure that they are familiar with the appropriate information/
manuals, supplied by the manufacturer, and that they are
suitably aware of the purpose of the manuals and the safety
instructions. In addition, operators must be suitably trained in
Caution is used when failure to follow or
implement the instruction(s) can lead to
premature failure or damage to the heater or its
component parts.
Warning is used when failure to heed or
implement the instruction(s) can lead to not only
component damage, but also to a hazardous
situation being created where there is a risk of personal
injury.
The Airbloc ACR Recessed Air Curtain range conform to the
following harmonised standards:
BS EN ISO 12100:2010
Safety of machinery. General principles for design. Risk assess-
ment and risk reduction
Safety of Machinery - Basic Concepts, General Principles for
Design Technical Principles and Specications
BS EN 60204-1:2006+A1:2009
Safety of machinery. Electrical equipment of machines. Gener-
al requirements
BS EN 55014-1:2017
Electromagnetic compatibility. Requirements for household
appliances, electric tools and similar apparatus. Emission
BS EN 60335-2-102:2006+A2:2016
Household and similar electrical appliances. Safety. Particular
requirements for gas, oil and solid-fuel burning appliances
having electrical connections
BS EN 60335-2-30:2009+A11:2012
Household and similar electrical appliances. Safety. Particular
requirements for room heaters
and to the following European CE directives2006/95/EC - low voltage;
2014/30/EU - electromagnetic compatibility.
Doc No. D301021 Page 5 of 64
1.2 Certicates of conformity
Certicates are available from the Quality Control Department
at Nortek Global HVAC (UK) Ltd.
1.3 General product information
Models range from 1000mm to 2000mm in length, in both
Standard and High capacity and are available in either
Electrically heated, Ambient or LPHW. They are designed for
discreet positioning in a suspended ceiling or bulkhead in the
doorways of retail or commercial premises. Optional case for
doorways with restricted space and no suspended ceiling/
bulkhead are available.
energy to the heating elements. This combined with the inbuilt intelligent sensor control, maintains a xed outlet
temperature, thereby reducing energy consumption as
compared to an air curtain without the SmartElec3 control.
Each air curtain is supplied with a fully electronic controller
giving multi fan and heat settings (electrically operated units)
via a simple key pad which can be mounted up to 100m from
the air curtain.
Optional BMS time control, external, thermostats and door
interlocks can be installed.
The programmer shown above allows the user to control
either a single air curtain, or a network of up to 16 air curtains
with the same settings, and provides the following functions:-
• Heat On O or Auto via optional thermostat
• O or Low, Medium and High Fan Speeds
For further details please refer to section 10.1
Alternatively on electrically heated models, the optional
SmartElec3 control system consists of a base unit (installed
within the air curtain) and a program panel that can be
installed remote from the air curtain.
Usually, the program panel is mounted at a low level from
the air curtain for user access and to a maximum distance of
100m.
The base unit and program panel are linked by a pre-wired
low voltage cable as specied in these instructions.
The SmartElec3 factory tted base unit provides terminals
for 3 phase supply connection and sockets the low voltage
program panel cable. The SmartElec3 base unit rapidly pulses
The programmer shown above is the same as used on
standard air curtains and allows the user to control either a
single air curtain, or a network of up to 16 air curtains, each
with dierent settings if required, and provides the following
functions:-
• Heat On or O
• O or Low, Medium and High Fan Speeds
• Air Outlet Temperature.
For further details please refer to section 10.2
Note
Neither asbestos nor soft soldered joints are used in the
construction or manufacture of the Airbloc ACR Recessed Air
Curtain range. The materials selected for use can withstand
the mechanical, chemical, and thermal stresses which they will
be subject to during foreseen normal use when installed in
accordance with the manufacturers recommendations.
1.4 Model Denitions
ACR1000xxxx = ACR Airbloc 1M in length. 1200=1.2M;
1500=1.5M; 1800=1.8M; 2000=2.0M.
ACRxxxSxxx = ACR Airbloc Standard Capacity (up to 3M
from oor); H=High Capacity(up to 4m from oor)
ACRxxxxExx = ACR Airbloc Electrically heated.
e.g. ACR2000HE18-SM = ACR Airbloc Air Curtain, 2M long, 18kW
electrically heated high capacity c/w SmartElec Control.
Doc No. D301021 Page 6 of 64
1.5 General requirements
Caution
Before installation, check that the local distribution conditions,
nature of gas and pressure, and the current state adjustment
of the appliance are compatible.
Installation and assembly procedures must be carried
out by suitable competent persons. Commissioning and
service procedures must be carried out by suitable
qualied persons.
1.6 Health and Safety
Warning
Airbloc Air Curtains must be installed in accordance with any
relevant and Regulations. Due account should be taken of any
obligations arising from the Health and Safety at Works Act
1974 or relevant codes of practice. In addition the installation
must be carried out in accordance with the current IEE wiring
regulations and any other relevant British Standards and
Codes of Practice by a qualied installer. Isolate all electrical
supplies to the heater & controller before proceeding.
Warning
Unauthorised modications to the appliance, or departure
from the manufacturers guidance on intended use, or,
installation contrary to the manufacturers recommendations
may constitute a hazard.
Note
To ignore the warning and caution notices, and to ignore the
advice from the manufacturer on installation, commissioning,
servicing, or use, will jeopardise any applicable warranty,
moreover, such a situation could also compromise the safe
and ecient running of the appliance itself, and thereby
constitute a hazard.
The installation of the appliance must meet all the relevant
European, national, and local criteria.
Prior to installation the following points should be considered;
• The position and mounting height of the Air Curtain
for the optimum ecient distribution.
• The position of the Air Curtain relative to the electrical
services, and any controllers.
• The position of the Air Curtain relative to the low
pressure hot water pipework where appropriate.
• The position of the heater relative to service and
maintenance requirements.
Caution
The air Curtain must not be installed within an area where the
conditions are unsuitable, e.g. where the atmosphere is highly
corrosive, has a high degree of salinity, or where high wind
velocities may aect operation. Suitable protection should
be provided for the appliance when it is located in a position
where it may be susceptible to external mechanical damage.
Caution
For your own safety we recommend the use of safety boots
and leather faced gloves when handling sharp or heavy items.
The use of protective eye wear is also recommended.
Sole liability rests with the installer to ensure that all site safety
procedures are adhered to during installation.
Sole liability rests with the installer to ensure that protective
safety wear such as hand, eye, ear and head protection is used
during installation of the product.
Do not rest anything especially ladders against the product.
1.7 Delivery and pre-installation checks.
On receipt of the Air Curtain, the following checks should be
carried out;
• The model is as per order.
• That it is undamaged.
• That it is suitable for the source gas supply.
• That it is suitable for the electrical supply
If any of these points are not satised then contact should be
made with the Sales Oce at Nortek Global HVAC (UK) Ltd as
soon as possible by telephoning 01384 489700. In the case of
claims for damage, this must be signed for as damaged and
reported in writing within 24 hours of delivery, in order to
comply with insurance criteria.
1.8 Location
WARNING:
THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE
THERE IS A CORROSIVE ATMOSPHERE.
Airbloc units should be installed horizontally directly over
the door opening. It is recommended that the air curtain is
installed on the inside of the building, within the open room
space within the ceiling void or roof space.
Doc No. D301021 Page 7 of 64
Care must be taken to allow complete free air movement into
the inlet grilles of the unit to ensure correct working operation
of the air curtain. The discharge opening should be as close
to the top of the door as possible and to cover the entire door
width.
Remote unit is wired to the base unit via a pre-wired cable
tted with RJ45 plugs.
1.10.2 SmartElec3 controller
Units can be mounted adjacent to each other to cover the full
door opening across wider entrances.
1.9 Clearance distances
It is recommended that a minimum clearance of 100mm is
allowed around the case. The clearance allows for cable entry
and prevents combustible surfaces overheating.
The minimum mounting height (oor to grille) is 1.8m. The
recommended maximum mounting height is 3m for
standard and 4m for high capacity models.
1.10 Electrical Supply
For full electrical loadings, please refer to the individual
technical data sheets within this manual.
It is recommended that the electrical supply to the base unit
in the air curtain is via an appropriate switched isolator in
accordance with the regulations in force in the country of use
and must be via a fused isolator having a contact separation of
greater than 3mm in all poles.
Electrically heated supply is 415V 3 phase, neutral and earth.
Max cable inlet size is 10mm².
Keypad is wired to the base unit via a RJ45 pre-wired cable.
Networked air curtain interconnects via a RJ45 pre-wired
cable.
BMS control, time switches, room thermostats and door
interlocks can be installed at the discretion and responsibility
of the installer.
All units must be wired in accordance with I.E.E regulations for
the Electrical Equipment of Buildings and the installer should
ensure that a suitable isolating switch is connected in the
mains supply.
Warning
For safety reasons a good earth connection must ALWAYS be
made to the heater and control box.
1.10.1 Ele ctronic co ntrol ler
Electrically heated supply is either 230V 1 phase (6 and 9kW
options) or 415V 3 phase (9 to 18kW), Neutral and Earth. Max
cable inlet size is 4mm² or 10mm² (refer to individual technical
specication)
Ambient and LPHW supply is 230V 1 phase, Neutral and
Earth. Max cable inlet size is 4mm².
Doc No. D301021 Page 8 of 64
2. Dimensions.
2.1 ACR Air Curtain Fig.1
DIM 'C'
DIM 'E'
DIM 'J'
DIM 'H'
DIM 'F'
DIM 'G'
DIM 'B'
DIM 'D'
DIM 'A'
ACR1000SE6/9;
Size
A253407
B122015202020118517852097
C118214821982115 017502059
D395550
E454608
F120515052005115017502082
G124215422095121018102140
H160180
J200220
ACR1000SW9;
ACR1000SA
ACR1500SE12;
ACR1500SW12;
ACR1500SA
ACR2000SE18;
ACR2000SW18;
ACR2000SA
ACR1200HE12;
ACR1200HW12;
ACR1200HA
ACR1800HE18;
ACR1800HW18;
ACR1800HA
Doc No. D301021 Page 9 of 64
ACR2000HE18;
ACR2000HW18;
ACR2000HA
2.2 Program keypad dimensions
The keypad is supplied with an industry standard plastic double surface mounted socket box. Alternatively the
keypad can be ush mounted using a customer supplied metal ush box as shown below.
Fig.2. Using surface mount box
148
87
120 crs
43,5
Fig.3. Optional ush mount using metal conduit box
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWElectrical heated
Heat settings3 / 64.5 / 9
Fan type / diaCrossow / 100mm
Fan settings3 Speeds
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)6.1 (26.5)9.1 (39.6)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3245
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB (L1, N,E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h116 414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Dimensional Data
Lengthmm118214821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112 514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Medium speedm³/h1405178 02432
High speedm³/h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7.08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C171326
Medium speed°C151123
High speed°C13920
Low speeddBA59
Medium speeddBA62
High speeddBA64
Doc No. D301021 Page 11 of 64
3.2 ACR1000SE9ACR1500SE12ACR2000SE18
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWElectrical heated
Heat settings4.5 / 96 / 129 / 18
Fan type / diaCrossow / 100mm
Fan settings3 speeds
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage415V 3ph 50Hz
Total load kW (a)9.1 (12.6)12.1 (16. 8)18.1 (25. 2)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps162032
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB (L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
** SmartElec3 Energy Saving Control108221-RJ45
SmartElec3 Energy Saving Control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² Max
Mains terminal block positionTop of PCB ( L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C262521
Medium speed°C232220
High speed°C201919
Low speeddBA59
Medium speeddBA62
High speeddBA64
Dimensional Data
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
**Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 12 of 64
3.3 ACR1200HE12ACR1800HE18ACR2000HE18
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWElectrical heated
Heat settings6 / 129 / 18
Fan type / diaCrossow / 100mm
Fan settings3 speeds
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage415V 3ph 50Hz
Total load kW (a)12.4 (17.3)18.4 (25.6)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps2032
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² MAX
Mains terminal block positionTop of PCB ( L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
** SmartElec3 Energy Saving Control108221-RJ45
SmartElec3 Energy Saving Control wiringRJ45 (pre-wired cable required)
Cable terminal size10.0mm² Max
Mains terminal block positionTop of PCB (L1, L2, L3, N, E)
RJ45 socket positionCentre of PCB (opposite mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speed°C3536
Medium speed°C282726
High speed°C2220
Low speeddBA50
Medium speeddBA55
High speeddBA60
Dimensional Data
Length115017502082
Depth (width)550
Total height227
Outlet length109016902022
Outlet depth (width)85
Grille height6
Mounting bracket centres length118517852117
Side to 1st bracket centre17. 5
Mounting bracket centres heightFlush with top of unit
Top to 1st bracket centreFlush with top of unit
* Motor current only at high speed
**Sux with –SM for SmartElec3 Energy Saving Control.
Doc No. D301021 Page 13 of 64
3.4ACR1000SAACR1500SAACR2000SA
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWAmbient
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.06 (0.26)0.09 (0.4)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speeddBA5962
Medium speeddBA6264
High speeddBA6466
Dimensional Data
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 14 of 64
3.5ACR1200HAACR1800HAACR2000HA
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWAmbient
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.4 (1.61)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps10
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speeddBA50
Medium speeddBA55
High speeddBA60
Dimensional Data
Lengthmm115017502082
Depth (width)mm550
Total heightmm227
Outlet lengthmm109016902022
Outlet depth (width)mm85
Grille heightmm6
Mounting bracket centres lengthmm118517852117
Side to 1st bracket centremm17.5
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
* Motor current only at high speed
Doc No. D301021 Page 15 of 64
3.6 ACR1000SW9ACR1500SW12ACR2000SW18
General Data
Maximum heightM3.0
Door width1.21.52.0
Heat MediumkWLPHW
Heat settings91218
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg28.034.049.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.06 (0.26)0.09 (0.4)
Motor powerW6090
Max Starting current*amps0.961.5
Max Running current*amps0.650.75
External fuse size ampsamps3
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h116414752013
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h1405178 02432
High speedm³/ h164620852851
Low @ 0Mm/s4.35.4
Medium @ 0Mm/s5.66.9
High @ 0Mm/s7. 08.4
High @ 1Mm/s3.54.2
High @ 2Mm/s1.62.1
High @ 3Mm/s0.81.0
Low speed°C262521
Medium speed°C232220
High speed°C201919
Low speeddBA5962
Medium speeddBA6264
High speeddBA6466
Lengthmm118214 821982
Depth (width)mm395
Total heightmm200
Outlet lengthmm112514251945
Outlet depth (width)mm85
Grille heightmm40
Mounting bracket centres lengthmm122015202020
Side to 1st bracket centremm18
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
Doc No. D301021 Page 16 of 64
3.7 ACR1200HW12ACR1800HW18ACR2000HW18
General Data
Maximum heightM4.0
Door width1.21.82.0
Heat MediumkWLPHW
Heat settings1218
Fan type / diaCrossow / 100mm
Fan settings3
Switching type3 tactile pushbuttons
Weightkg38.055.063.0
Electrical Data
Supply voltage230V 1ph 50Hz
Total load kW (a)0.4 (1.6)
Motor powerW370
Max Starting current*amps5.0
Max Running current*amps2.1
External fuse size ampsamps10
Programmer keypadpt.no.108221-RJ45
Program keypad control wiringRJ45 (pre-wired cable required)
Cable terminal size1.5mm² MAX
Mains terminal block positionTop right of PCB (L1, N, E)
RJ45 socket positionRight hand side of PCB (below mains input terminals)
Air Data
Low speedm³/ h130 016002900
Air Volume
Air Velocity
Delta T
Noise level @ 1M in free
eld
Medium speedm³/ h185024004100
High speedm³/ h230033005000
Low @ 0Mm/s6.0
Medium @ 0Mm/s8.5
High @ 0Mm/s11. 0
High @ 1Mm/s5.45.55.2
High @ 2Mm/s3.63.73.6
High @ 3Mm/s2.62.52.4
High @ 4Mm/s1.51.61.4
Low speed°C3536
Medium speed°C282726
High speed°C2220
Low speeddBA50
Medium speeddBA55
High speeddBA60
Lengthmm115017502082
Depth (width)mm550
Total heightmm227
Outlet lengthmm109016902022
Outlet depth (width)mm85
Grille heightmm6
Mounting bracket centres lengthmm118517852117
Side to 1st bracket centremm17.5
Mounting bracket centres heightmmFlush with top of unit
Top to 1st bracket centremmFlush with top of unit
Doc No. D301021 Page 17 of 64
3.8 Standard Program Controls
General Data
Sensor InputNTC
Protection1 x 1A fuse for the protection of the fan switching devices.
Fan Output3 o Relay for High, Medium and Low Fan setting 3A max 230vac
Screw terminals 4 for supply, 6 for elements output, 4 for fan output, 2 for
Connections
Supply415 3Ph or 230V 1Ph dependent on model type.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
DisplayThree 7-segment LCD red for parameter display
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for external door switch, 2 for 0-10v fan option, 2 for 0-5v fault output, 2 for lter
blocked, 2 for unit temperature.
3.9 SmartElec3 Controls
General Data
Sensor InputNTC
Control Setpoint16 to 35 ºC in steps of 1 degree
Temperature ControlProportional with 1ºC hysteresis
Minimum Power0% to 99 %
Cycle Time2 seconds xed
Protection2 x high speed fuse for the protection of the heater switching devices
Fan Output3 o Relay for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 5 for supply, 3 for heater output, 4 for fan output, 2 for BMS
Connections
Supply415V AC 50/60Hz 5VA max.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
(time) control, 2 for sensor input, 2 for external thermal trip, 2 for external
sensor, 2 for door, 2 for cooling fan on 24kW models. RJ45 comms connection
to base unit via pre-wired cable.
Mounting PositionsProgram panel xing centres 80mm x 20mm
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
DisplayThree 7-segment LCD red for parameter display
Temperature Control0-10v valve output (proportional)
Cycle Time2 seconds xed
Protection1 x 1A fuse for the protection of the mains input
Fan Output3 o Relays for High, Medium and Low Fan setting 3A max 230Vac
Screw terminals 3 for mains supply, 4 for fan output, 2 for BMS (time) control,
2 for sensor input, 2 for external thermal trip, 2 for external
Connections
Supply230 V 50/60Hz.
DimensionsProgram panel 146mm(L) x 85mm(W) x 38mm(D) max.
Temperature5 to 50 ºC operating; -20 to 65 ºC storage
sensor, 2 for door., 2 for 0-10v motor drive, 2 for 0-10v fan option, 2 for 0-5v
fault output, 2 for pipe cold input, 2 for unit temperature input, RJ45 comms
connection to base unit via pre-wired cable.
DisplayThree 7-segment LCD red for parameter display
4.1 Installer Wiring - Electrically Heated 6 & 9kW SINGLE PHASE ONLY
he program panel is connected to the base unit via a pre-wired RJ45 cable max length 100m.
T
trunking to avoid external interference.
External switch inputs (eg Timer) to be volt free and wired via normally open contacts to terminal pair marked eg. ‘timer’
(contacts closed to enable). Remove relevant factory tted jumper for any optional input.
It is recommended that this cable is run separately within its own
Mains Supply
FAN
L1
3 N
1 2
BASE UNIT
(located in air curtain)
ON
1 2 3 4
Pre-wired RJ45 plugs
& lead
SELECT
HE
HEHE HE
L2
B
A
RS485 Comms
HE HE
AB
FAULT = OPTIONAL 5vDC OUTPUT
FAN = OPTIONAL 10vDC FAN CONTROL OUTPUT
L3
SYS
TEMP
FAN
External
FAULT
AB
FILTER
TIMER
STAT
N
DOOR
EXT
Pressure
Switch
External
Switch
(BMS)
Remove appropriate link
before connecting any
optional switches
CHASSIS
EARTH
Sensor
Programmer
Keypad
TerminalDescriptionCable
NNeutral
10mm² max
L1Phase 1 (or 1 Phase supply)
Pcb TerminalDescriptionCable
DoorOption door contact
1.5mm² max
Timer BMSOption external switch
Protection
External circuit breaker with the appropriate rating should be
installed for the protection of the installation.
Doc No. D301021 Page 20 of 64
Door
Switch
900640 CWL R1
PCB Terminal DescriptionCable
ExtOption internal/external sensor (supplied)
Filter blockOption lter blocked switch
Fail o/pFault output (0-5v)
1.5mm²
max
FanOption 0-10v fan output
Pcb FusesRating (A)
F1T1H (slow blow)
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.