Reznor 300000 BTU Furnace User Manual

9.0 Commissioning and Start-Up (cont'd)
9.3 Check
installation after start-up:
Observe burner ame at full re. Natural gas ame should be about 1-1/2" in height
with blue coloring. Propane gas ame should be approximately the same length with blue coloring. Yellow tipping may appear on propane gas. If yellow extends beyond 1/2 to 3/4", adjust air shutters. See Paragraph 8.6. If shutter adjustment will not reduce yellowing, check for gas leaks at the control manifold or orice tting.
Turn the unit off and on, pausing two minutes between each cycle. Observe
for smooth ignition. On two-stage or modulating burner systems, manipulate
temperature adjustment slowly up and down to see if control is sequencing or modulating properly. Raising temperature setting drives burner on or to full re.
Using a manometer or slant gauge readable up to 14" w.c., check orice manifold
for operating pressure on full re. Natural gas should be 3.5" w.c. at this point. Propane should be 10" w.c. at this point. Variations from these pressures are not recommended, as ignition and efciency performance can be adversely affected by improper pressure adjustment. See Paragraph 6.2.
Place "Owner's Envelope" containing Limited Warranty Card, this booklet, and
any optional information in an accessible location near the heater. Follow the instructions on the envelope.
DANGER
The gas burner in this gas-red equipment is designed and equipped to provide safe, controlled
complete combustion. However, if the installation does not permit the burner to receive the proper supply of combustion air, complete combustion may not occur. The result is incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe operation of separated-
combustion, indirect-red gas burning equipment requires a sealed, properly operating vent system which vents all ue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING
WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.
the installation codes and instructions. Combustion air at the burner should be regulated only
SOUNDNESS AND FUNCTION; MAINTAIN IT IN PROPER OPERATING CONDITION.
10.0 Maintenance
and Service
10.1 Maintenance
Schedule
Form I-SC, P/N 207696 R12, Page 34
WARNING
If you turn off the power supply, turn off the gas. See Hazard Levels,
page 2.
This unit will operate with a minimum of maintenance. To ensure long life and satis­factory performance, a furnace that is operating under normal conditions should be inspected every four months. If the furnace is operating in an area where an unusual amount of dust or soot or other impurities are present in the air, more frequent inspec­tion is recommended.
The following procedures should be carried out at least annually (See Paragraphs
10.2.1-10.2.7 for instructions).
Check the gas valve to ensure that gas ow is being shut off completely. Clean the heat exchanger both internally and externally. Check the pilot burner and main burners for scale, dust, or lint accumulation.
Clean as needed.
Check the vent/combustion air system; inspect all joints. Replace any parts that do
not appear sound.
Check the wiring for any damaged wire. Replace damaged wiring. (See Paragraph
7.0 for wiring requirements.)
CAUTION: When cleaning, wearing eye protection is recommended.
NOTE: Use only factory-authorized replacement parts.
10.2 Maintenance
Procedures
CAUTION: DO NOT bottom out the gas valve regulator adjusting screw. This can result in unregulated manifold pressure causing excess
overre and heat
exchanger failure.
10.2.1 Gas Valve
WARNING
The operating valve is the prime safety shutoff. All gas supply lines must be free of dirt or scale before connecting to the unit to ensure
positive closure. See Hazard Levels, page 2.
Remove external dirt accumulation and check wiring connections. The combination gas valve must be checked annually to ensure that the valve is shutting off gas ow completely.
Instructions:
1) Locate the 1/8” FPT INLET pressure tap on the combination valve (FIGURE 34).
2) With the manual valve turned off to prevent ow to the gas valve, connect a
manometer to the 1/8” inlet pressure tap in the valve. NOTE: A manometer (uid­lled gauge) with an inches water column scale is recommended.
FIGURE 34 -
Top View of Gas Valves
Single-
Stage Valve
1/8" INLET
Pressure Tap
Two-Stage Valve
1/8" INLET
Pressure Tap
1/8” Outlet
Pressure Tap
1/8” Outlet
Pressure Tap
10.2.2 Vent/ Combustion Air System
10.2.3 Burner Rack Removal Instructions
3) With the eld-installed manual valve remaining closed, turn the thermostat up
to re the unit and allow the unit to go through one trial for ignition. Reset the thermostat to shut the unit off. Observe the manometer for two to three minutes for an indication of gas pressure. No pressure should be indicated on the manometer. If the manometer indicates a gas pressure, the eld-installed manual gas valve must be replaced or repaired before the combination gas valve can be checked.
4) If the manometer does not indicate gas pressure, slowly open the eld-installed manual gas valve. After the manometer's indicated gas pressure has reached equilibrium, close the manual shutoff valve. Observe the gas pressure. There should be no loss of gas pressure on the manometer. If the manometer indicates a loss of pressure, replace the combination gas valve before placing the heater in
operation.
NOTE: Operational pressure settings and instructions for checking pressure settings are in Paragraph 6.2. Check at least once a year. Inspect all joints, seams, and terminal caps. Clean grills and screens.
Replace any parts that need to be replaced.
1. Turn off the gas supply.
2. Turn off the electric supply.
3. Remove control access side panel.
4. Disconnect the pilot tubing and ame sensor lead.
5. Mark and disconnect electric valve leads.
6. Uncouple the union in the gas supply.
7. Remove sheetmetal screws in the top corners of the burner rack assembly.
8. Pull "drawer-type" burner rack out of the furnace.
To disassemble the burner rack:
1. Remove Carryover System --
Natural Gas - remove the ash carryover system from the "manifold end" of the burner rack NOTE: Natural gas burner racks manufactured prior to Series 6 have a lighter tube carryover system. Break the lighter tube connection at the orice and remove the
supply tubing, the drip shield and the lighter tube.
Form I-SC, P/N 207696 R12, Page 35
10.0 Maintenance and Service (cont'd)
10.2 Maintenance Procedures (cont'd)
10.2.3 Burner Rack Removal Instructions (cont'd)
Propane - break the lighter tube connection at the regulator and remove the lighter
tube orice supply tubing; remove the retaining screws in the drip shield and the shield; remove the retaining screws and slide out the lighter tube.
2. Pull main burners horizontally away from injection opening and lift out.
3. Remove manifold bracket screws and remove manifold.
4. Remove the main burner orices.
5. Remove screws and lift out pilot burner. Follow the instructions in Paragraph 10.2.3 to clean. To re-assemble and replace,
reverse the above procedures being careful not to create any unsafe conditions.
CAUTION: When cleaning, wearing eye protection is recommended.
Cleaning Pilot and Main Burners
In the event the pilot ame is short and/or yellow, check the pilot orice for blockage caused by lint or dust accumulation. Remove the pilot orice and clean with air pres­sure. DO NOT REAM THE ORIFICE. Check and clean the aeration slot in the pilot
burner.
Clean the metal sensing probe and the pilot hood with an emery cloth and wipe off the ceramic insulator. Check the spark gap; spark gap should be maintained to 7/64". After the pilot is cleaned, blow any dirt away with compressed air. Clean main burners and burner orices using air pressure. Use an air nozzle to blow out scale and dust accumulation from the burner ports. Alternately blow through the burner ports and the venturi. Use a ne wire to dislodge any stubborn particles in the burner ports. Do not use anything that might change the port size.
Clean the burner rack carryover systems with air pressure.
10.2.4 Spark Ignition
System
FIGURE 35 - Spark Gap
The ignition controller provides the high voltage spark to ignite the pilot service and also acts as the ame safety device. After ignition of the pilot gas, the controller electroni­cally senses the pilot ame. A separate solid metal probe in the pilot burner assembly is used to sense the ame. A low voltage DC electrical signal is imposed on the metal probe which is electrically insulated from ground. When the pilot ame impinges on the sensing probe, the ame acts as a conduction path to ground. This completes the DC circuit; the ignition controller responds by energizing the main gas valve. Proper
operation of the electronic spark ignition system requires a minimum ame sig­nal of .2 microamps as measured by a microampmeter.
CAUTION: Due to high voltage on pilot spark wire and pilot electrode,
do not touch when energized. See Hazard Levels, page 2.
If no spark occurs, check the following: a) Voltage between Terminals TH and 7 should be at least 20 volts and no higher
than 32 volts. Refer to Troubleshooting (Paragraph 10.3) if no voltage is observed. b) Short to ground in the high tension lead and/or ceramic insulator. c) Pilot spark gap should be approximately .100". (See FIGURE 35.)
Form I-SC, P/N 207696 R12, Page 36
Top
View
NOTE: When checking for spark with the pilot burner assembly removed from the burner rack, the pilot assembly must be grounded to the heater for proper spark. If the above conditions are normal and no spark occurs, replace the ignition control-
ler.
Side
View
Loading...
+ 4 hidden pages