Revo S2PH, S3PH User Manual

USER’S MANUAL
Rev. 02/2019
2PH
Solid-State Relay
From 60 to 90A - 120 to 210A
003
M-RS2-60-210
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com
REVO S 2PH from 60A to 210A User’s manual
3
Declaration of conformity
Declaration of conformity - Dichiarazione di Conformità
PRODUCT MANUFACTURER / PRODUTTORE:
CD Automation S.R.L.
Controllers, Drives & Automation
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com
Declare that the product / Dichiara che il prodotto:
Revo S 2PH 60-210A
PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica UTILIZZO: Controllo processi termici
FULFILS THE REQUIREMENTS OF THE STANDARD:
Electrical safety Standard EN60947-1 :2007 + A1 2011, A2 2014 EN60947-4-3:2014 Generic Emission standard EN60947-4-3:2014 Group 1 Class A emissions Generic Immunity standard EN60947-4-3:2014 Industrial Immunity
SODDISFA I REQUISITI DELLA NORMA:
Specica di sicurezza EN60947-1 :2007 + A1 2011, A2 2014
EN60947-4-3:2014
Specica sulle emissioni EN60947-4-3:2014 gruppo 1 emissioni classe A Specica sulle Immunità EN60947-4-3:2014 Immunità industriale
CDAutomation declares that The products above mentioned they are conforming to the directive CDAutomation dichiara che I prodotti sopra menzionati sono conformi alla direttiva Bassa Tensione (low Voltage) EMC directive updated 2014/30/EU,
Low Voltage Directive updated 2014/35/EU
Issued on: 20/03/2017 Data di emissione: 20/03/2017
Amministratore Unico e Legale Rappresentante
Claudio Brizzi
4
REVO S 2PH from 60A to 210A User’s manual
Important warnings for safety
This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
The installation should be performed by qualied persons.
In the manual are used symbols to give more evidence at the notes of safety and operativity for the attention for the user:
This icon is present in all the operational procedures where the Improper operation may result in serious personal injury or death by Electrical Shock Hazard Symbol (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.
Warning or Hazard that needs further explanation than the label on unit can provide. Consult User’s Guide for further information.
Unit is compliant with European Union directives.
See Declaration of Conformity for further details on Directives and Standards used for Compliance.
If available, unit is a Listed device per Underwriters Laboratories. It has been investigated to ANSI/UL® 508 standards for Industrial Control Switches and equivalent to CSA C22.2 #14. For more detail search for File E231578 on www.ul.com
ESD Sensitive product, use proper grounding and handling techniques when installing or servicing product.
Do not throw in trash, use proper recycling techniques or consult manufacturer for proper disposal.
A
“NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.
A “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
Safety notes
WARNING! To avoid damage to property and equipment, injury and loss of life, adhere to applicable
electricalcodes and standard wiring practices when installing and operating this product. Failure to do so could result in damage, injury and death.
AVERTISSEMENT! Pour éviter d’endommager la propriété et l’équipement, les blessures et la perte de vie, respecter les codes électriques en vigueur et les pratiques de câblage standard au moment de l’installation et de l’utilisation de ce produit. Dans le cas contraire, cela peut entraîner la mort, des blessures graves ou des dommages.
IND. CONT. EQ. E231578 2RD5
REVO S 2PH from 60A to 210A User’s manual
5
WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse
or other user serviceable component replacement must be performed only by properly qualied
personnel. Service personnel must read this manual before proceeding with work. While service is
being performed un-qualied personnel should not work on the unit or be allowed in the immediate
vicinity.
AVERTISSEMENT! Tous les services, y compris l’inspection, l’installation, le câblage, l’entretien, le dépannage, le remplacement de fusibles ou d’autres composants pouvant être réparés par l’utilisateur,
doivent être eectués uniquement par un personnel diment qualié. Le personnel de service doit lire ce manuel avant d’eectuer tout travail. Pendant que l’entretien est exécuté, tout personnel non qualié ne doit eectuer de travail sur l’appareil ni se trouver a proximité.
WARNING! When in use the power controller is connected to dangerous voltages. Do not remove the
protective covers without rst disconnecting and preventing power from being restored while servicing
the unit.
AVERTISSEMENT! Au moment de l’utilisation, le régulateur de puissance est connecté a des tensions dangereuses. Ne retirer aucun couvercle de protection sans d’abord débrancher l’appareil et ainsi empêcher l’alimentation d’être rétablie pendant l’entretien.
WARNING! Do not use in aerospace or nuclear applications.
AVERTISSEMENT! Ne pas utiliser pour les applications aérospatiales ou nucléaires.
WARNING! The power controller’s protection rating is IP20 with all covers installed and closed. It must
be installed in an enclosure that provides all the necessary additional protections appropriate for the environment and application.
AVERTISSEMENT! L’indice de protection du régulateur de puissance est de IP20 lorsque les couvercles sont installés et fermés. L’appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l’environnement et l’application.
WARNING! Ground the power controller via the provided protective earth grounding terminal. Verify
ground is within impedance specications. This should be veried periodically.
AVERTISSEMENT! Mise a la terre du régulateur de puissance par le biais de la borne de prise de terre
de protection fournie. Vérier que la prise de terre est conforme aux spécications de l’impédance. Cela doit être vérié périodiquement.
WARNING! Electric Shock Hazard: when the power controller has been energized, after shutting o the
power, wait at least one minute for internal capacitors to discharge before commencing work that brings you in to contact with power connections or internal components.
AVERTISSEMENT! Risque de décharges électriques: lorsque le régulateur de puissance est mis sous tension, après avoir été éteint, attendre au moins une minute pour que les condensateurs internes se déchargent avant de commencer tout travail incluant le contact avec les connexions électriques ou les composants internes.
WARNING! The installation must be protected by electromagnetic circuit breakers or by fuses. The
semiconductor fuses located inside the power controller are classied for UL as supplementary
protection for semiconductor devices. They are not approved for branch circuit protection.
AVERTISSEMENT! L’installation doit être protégée par des disjoncteurs électromagnétiques ou des fusibles. Les fusibles pour semi-conducteurs situés a l’intérieur du régulateur de puissance sont classés UL comme protection supplémentaire pour les dispositifs pour semi-conducteurs. Ils ne sont pas approuvés pour la protection des circuits de dérivation.
WARNING! When making live voltage or current measurements, use proper personal protective
equipment for the voltages and arc-ash potentials involved.
6
REVO S 2PH from 60A to 210A User’s manual
AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés.
WARNING! Verify the voltage and current ratings of the power controller are correct for the application.
AVERTISSEMENT! Vérier que les valeurs de tension et de courant du régulateur de puissance sont
correctes pour l’application.
CAUTION: To avoid compromising the insulation, do not bend wire or other components beyond their
bend radius specications.
ATTENTION: Pour éviter de compromettre l’isolation, ne pas plier le l ou tout autre composant au-delà de ses spécications en matière de rayon de courbure.
CAUTION: Protect the power controller from high temperature, humidity and vibrations.
ATTENTION: Protéger le régulateur de puissance contre les températures élevées, l’humidité et les
vibrations.
CAUTION: The power controller warranty is void if the tested and approved fuses are not used.
ATTENTION: La garantie du régulateur de puissance est nulle si aucun fusible testé et approuvé n’est
utilisé.
CAUTION: Only trained and authorized personnel should access and handle the internal electronics and they must follow proper electro-static prevention procedures.
ATTENTION: Seul le personnel formé et autorisé peut accéder aux composants électroniques internes et les gérer, et il doit se conformer a des procédures de prévention électrostatique appropriées.
CAUTION: Install an appropriately sized RC lter across contactor coils, relays and other inductive
loads.
ATTENTION: Installer un ltre RC de dimensions appropriées sur les bobines du contacteur, les relais et
autres charges par induction.
NOTE: Provide a local disconnect to isolate the power controller for servicing.
REMARQUE: Fournir une déconnexion locale an d’isoler le régulateur de puissance pour l’entretien.
NOTE: The nominal current is specied for ambient temperatures at or below 40° C. Ensure the application
design allows for adequate cooling of each power controller. The power controller must be mounted vertically. The cooling design must prevent air heated by one power controller from causing power controllers mounted above to exceed the ambient operating temperature limit. When power controllers are mounted side by side allow a minimum spacing of 15mm between them.
REMARQUE: Le courant nominal est précisé pour des températures ambiantes égales ou inférieures
a 40°C. S’assurer que la conception de l’application permette le refroidissement adéquat de chaque
régulateur de puissance. Le régulateur de puissance doit être monté verticalement. La conception de
refroidissement doit empêcher l’air chaué par le régulateur de puissance de dépasser la limite de
température de fonctionnement ambiante de la part des régulateurs de puissance montés au-dessus. Lorsque les régulateurs de puissance sont montés côte a côte, il faut conserver un espacement minimal de 15 mm entre les deux.
NOTE: Use only copper cables and wires rated for use at 90°C or greater.
REMARQUE: N’utiliser que des cables et des ls en cuivre pour l’utilisation a 90°C ou plus.
REVO S 2PH from 60A to 210A User’s manual
7
Maintenance
In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the fans. The frequency of this servicing depends on environmental pollution. Also check periodically if the screw for the power cables and safety earth are tightened correctly (See Connection Diagram)
Warranty condition
Producer gives a 12 months warranty to its products.
The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty product should be shipped to Producer at customer’s cost and our Service will evaluate if product is under warranty terms.
Substituted parts remain of Producer property.
Return Material Authorization (RMA)
Customers wishing to return any items, whether they are incorrectly supplied, faulty or damaged in transit,
must rst complete a Return Material Authorisation (RMA) form to obtain an RMA number from the Service
Department. A full repair service is available for customers. Prior to submitting the RMA form and returning products, customers are recommended to contact the technical support team to determine whether the issue can be resolved with telephone support.
How the RMA service works
The RMA form and details are availableon our web sites:
https://www.cdautomation.com/returns-material-authorisation/
When completing the RMA form, please be as specic as possible about the problem, including any pertinent
application details. The more information given, the more quickly and more thoroughly the problem can be solved. The minimum information required is:
1. The Full Model Number
2. Quantity of units being returned
3. The units Serial Number(s)
4. A description of the problem (“faulty” or “unknown” is not sucient)
8
REVO S 2PH from 60A to 210A User’s manual
Declaration of conformity ..................................................3
Important warnings for safety
..............................................4
Maintenance
...............................................................7
Basic Connections
.........................................................10
Identication and Order Code
.............................................11
2.1. Identication of the unit .........................................................11
2.2. Order code
......................................................................12
Technical Specications ...................................................13
3.1 General features .................................................................13
3.2 Input features
...................................................................13
3.3 Output features (power device)
..................................................13
3.4 Fan Specication (60-90A)
.......................................................13
3.5 Fan Specication (120-210A)
.....................................................13
3.6 Environmental installation conditions
............................................14
3.7 Derating curve
...................................................................14
Installation ................................................................15
4.1 Dimensions and weight ..........................................................15
4.2 Fixing holes
......................................................................16
Wiring instructions ........................................................17
5.1 Terminals Positions 2Ph 60-90A Size .............................................17
5.2 Terminals Positions 2Ph 120-210A Size
...........................................18
5.3 Thermal Switch (OPTION)
.......................................................19
5.4 Power Terminals
.................................................................20
5.5 Command Terminals
.............................................................20
5.6 Connection Diagram for 3 phases (control on 2 phases) from 60 to 90A
..........22
5.7 Connection Diagram for 3 phases (control on 2 phases) from 120 to 210A
.........23
Led status and alarms .....................................................24
1
2
3
4
5
6
Summary
REVO S 2PH from 60A to 210A User’s manual
9
Heater Break alarm and SCR short circuit..................................24
7.1 Heater break Calibration procedure..............................................24
7.2 HB Alarm contact
................................................................25
Input setting...............................................................26
8.1 Input calibration procedure......................................................27
Firing type.................................................................28
9.1 Zero Crossing (ZC) with SSR input ................................................28
9.2 Burst Firing (BF) with Analog Input
...............................................28
9.3 Burst Firing settings
.............................................................29
Internal Fuse ..............................................................30
10.1 Fuses Replacement.............................................................31
Trouble shooting ..........................................................32
7
8
9
10
11
10
REVO S 2PH from 60A to 210A User’s manual
Basic Connections
Star wiring with resistive load (control on two phases)
V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load
Delta wiring with resistive load (control on two phases)
V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load
1
I=
P
1,73V
I=
P
1,73V
V
V