Revo S2PH, S3PH User Manual

USER’S MANUAL
Rev. 02/2019
2PH
Solid-State Relay
From 60 to 90A - 120 to 210A
003
M-RS2-60-210
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com
REVO S 2PH from 60A to 210A User’s manual
3
Declaration of conformity
Declaration of conformity - Dichiarazione di Conformità
PRODUCT MANUFACTURER / PRODUTTORE:
CD Automation S.R.L.
Controllers, Drives & Automation
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com
Declare that the product / Dichiara che il prodotto:
Revo S 2PH 60-210A
PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità di controllo potenza elettrica UTILIZZO: Controllo processi termici
FULFILS THE REQUIREMENTS OF THE STANDARD:
Electrical safety Standard EN60947-1 :2007 + A1 2011, A2 2014 EN60947-4-3:2014 Generic Emission standard EN60947-4-3:2014 Group 1 Class A emissions Generic Immunity standard EN60947-4-3:2014 Industrial Immunity
SODDISFA I REQUISITI DELLA NORMA:
Specica di sicurezza EN60947-1 :2007 + A1 2011, A2 2014
EN60947-4-3:2014
Specica sulle emissioni EN60947-4-3:2014 gruppo 1 emissioni classe A Specica sulle Immunità EN60947-4-3:2014 Immunità industriale
CDAutomation declares that The products above mentioned they are conforming to the directive CDAutomation dichiara che I prodotti sopra menzionati sono conformi alla direttiva Bassa Tensione (low Voltage) EMC directive updated 2014/30/EU,
Low Voltage Directive updated 2014/35/EU
Issued on: 20/03/2017 Data di emissione: 20/03/2017
Amministratore Unico e Legale Rappresentante
Claudio Brizzi
4
REVO S 2PH from 60A to 210A User’s manual
Important warnings for safety
This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
The installation should be performed by qualied persons.
In the manual are used symbols to give more evidence at the notes of safety and operativity for the attention for the user:
This icon is present in all the operational procedures where the Improper operation may result in serious personal injury or death by Electrical Shock Hazard Symbol (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.
Warning or Hazard that needs further explanation than the label on unit can provide. Consult User’s Guide for further information.
Unit is compliant with European Union directives.
See Declaration of Conformity for further details on Directives and Standards used for Compliance.
If available, unit is a Listed device per Underwriters Laboratories. It has been investigated to ANSI/UL® 508 standards for Industrial Control Switches and equivalent to CSA C22.2 #14. For more detail search for File E231578 on www.ul.com
ESD Sensitive product, use proper grounding and handling techniques when installing or servicing product.
Do not throw in trash, use proper recycling techniques or consult manufacturer for proper disposal.
A
“NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.
A “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
Safety notes
WARNING! To avoid damage to property and equipment, injury and loss of life, adhere to applicable
electricalcodes and standard wiring practices when installing and operating this product. Failure to do so could result in damage, injury and death.
AVERTISSEMENT! Pour éviter d’endommager la propriété et l’équipement, les blessures et la perte de vie, respecter les codes électriques en vigueur et les pratiques de câblage standard au moment de l’installation et de l’utilisation de ce produit. Dans le cas contraire, cela peut entraîner la mort, des blessures graves ou des dommages.
IND. CONT. EQ. E231578 2RD5
REVO S 2PH from 60A to 210A User’s manual
5
WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse
or other user serviceable component replacement must be performed only by properly qualied
personnel. Service personnel must read this manual before proceeding with work. While service is
being performed un-qualied personnel should not work on the unit or be allowed in the immediate
vicinity.
AVERTISSEMENT! Tous les services, y compris l’inspection, l’installation, le câblage, l’entretien, le dépannage, le remplacement de fusibles ou d’autres composants pouvant être réparés par l’utilisateur,
doivent être eectués uniquement par un personnel diment qualié. Le personnel de service doit lire ce manuel avant d’eectuer tout travail. Pendant que l’entretien est exécuté, tout personnel non qualié ne doit eectuer de travail sur l’appareil ni se trouver a proximité.
WARNING! When in use the power controller is connected to dangerous voltages. Do not remove the
protective covers without rst disconnecting and preventing power from being restored while servicing
the unit.
AVERTISSEMENT! Au moment de l’utilisation, le régulateur de puissance est connecté a des tensions dangereuses. Ne retirer aucun couvercle de protection sans d’abord débrancher l’appareil et ainsi empêcher l’alimentation d’être rétablie pendant l’entretien.
WARNING! Do not use in aerospace or nuclear applications.
AVERTISSEMENT! Ne pas utiliser pour les applications aérospatiales ou nucléaires.
WARNING! The power controller’s protection rating is IP20 with all covers installed and closed. It must
be installed in an enclosure that provides all the necessary additional protections appropriate for the environment and application.
AVERTISSEMENT! L’indice de protection du régulateur de puissance est de IP20 lorsque les couvercles sont installés et fermés. L’appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l’environnement et l’application.
WARNING! Ground the power controller via the provided protective earth grounding terminal. Verify
ground is within impedance specications. This should be veried periodically.
AVERTISSEMENT! Mise a la terre du régulateur de puissance par le biais de la borne de prise de terre
de protection fournie. Vérier que la prise de terre est conforme aux spécications de l’impédance. Cela doit être vérié périodiquement.
WARNING! Electric Shock Hazard: when the power controller has been energized, after shutting o the
power, wait at least one minute for internal capacitors to discharge before commencing work that brings you in to contact with power connections or internal components.
AVERTISSEMENT! Risque de décharges électriques: lorsque le régulateur de puissance est mis sous tension, après avoir été éteint, attendre au moins une minute pour que les condensateurs internes se déchargent avant de commencer tout travail incluant le contact avec les connexions électriques ou les composants internes.
WARNING! The installation must be protected by electromagnetic circuit breakers or by fuses. The
semiconductor fuses located inside the power controller are classied for UL as supplementary
protection for semiconductor devices. They are not approved for branch circuit protection.
AVERTISSEMENT! L’installation doit être protégée par des disjoncteurs électromagnétiques ou des fusibles. Les fusibles pour semi-conducteurs situés a l’intérieur du régulateur de puissance sont classés UL comme protection supplémentaire pour les dispositifs pour semi-conducteurs. Ils ne sont pas approuvés pour la protection des circuits de dérivation.
WARNING! When making live voltage or current measurements, use proper personal protective
equipment for the voltages and arc-ash potentials involved.
6
REVO S 2PH from 60A to 210A User’s manual
AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés.
WARNING! Verify the voltage and current ratings of the power controller are correct for the application.
AVERTISSEMENT! Vérier que les valeurs de tension et de courant du régulateur de puissance sont
correctes pour l’application.
CAUTION: To avoid compromising the insulation, do not bend wire or other components beyond their
bend radius specications.
ATTENTION: Pour éviter de compromettre l’isolation, ne pas plier le l ou tout autre composant au-delà de ses spécications en matière de rayon de courbure.
CAUTION: Protect the power controller from high temperature, humidity and vibrations.
ATTENTION: Protéger le régulateur de puissance contre les températures élevées, l’humidité et les
vibrations.
CAUTION: The power controller warranty is void if the tested and approved fuses are not used.
ATTENTION: La garantie du régulateur de puissance est nulle si aucun fusible testé et approuvé n’est
utilisé.
CAUTION: Only trained and authorized personnel should access and handle the internal electronics and they must follow proper electro-static prevention procedures.
ATTENTION: Seul le personnel formé et autorisé peut accéder aux composants électroniques internes et les gérer, et il doit se conformer a des procédures de prévention électrostatique appropriées.
CAUTION: Install an appropriately sized RC lter across contactor coils, relays and other inductive
loads.
ATTENTION: Installer un ltre RC de dimensions appropriées sur les bobines du contacteur, les relais et
autres charges par induction.
NOTE: Provide a local disconnect to isolate the power controller for servicing.
REMARQUE: Fournir une déconnexion locale an d’isoler le régulateur de puissance pour l’entretien.
NOTE: The nominal current is specied for ambient temperatures at or below 40° C. Ensure the application
design allows for adequate cooling of each power controller. The power controller must be mounted vertically. The cooling design must prevent air heated by one power controller from causing power controllers mounted above to exceed the ambient operating temperature limit. When power controllers are mounted side by side allow a minimum spacing of 15mm between them.
REMARQUE: Le courant nominal est précisé pour des températures ambiantes égales ou inférieures
a 40°C. S’assurer que la conception de l’application permette le refroidissement adéquat de chaque
régulateur de puissance. Le régulateur de puissance doit être monté verticalement. La conception de
refroidissement doit empêcher l’air chaué par le régulateur de puissance de dépasser la limite de
température de fonctionnement ambiante de la part des régulateurs de puissance montés au-dessus. Lorsque les régulateurs de puissance sont montés côte a côte, il faut conserver un espacement minimal de 15 mm entre les deux.
NOTE: Use only copper cables and wires rated for use at 90°C or greater.
REMARQUE: N’utiliser que des cables et des ls en cuivre pour l’utilisation a 90°C ou plus.
REVO S 2PH from 60A to 210A User’s manual
7
Maintenance
In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the fans. The frequency of this servicing depends on environmental pollution. Also check periodically if the screw for the power cables and safety earth are tightened correctly (See Connection Diagram)
Warranty condition
Producer gives a 12 months warranty to its products.
The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty product should be shipped to Producer at customer’s cost and our Service will evaluate if product is under warranty terms.
Substituted parts remain of Producer property.
Return Material Authorization (RMA)
Customers wishing to return any items, whether they are incorrectly supplied, faulty or damaged in transit,
must rst complete a Return Material Authorisation (RMA) form to obtain an RMA number from the Service
Department. A full repair service is available for customers. Prior to submitting the RMA form and returning products, customers are recommended to contact the technical support team to determine whether the issue can be resolved with telephone support.
How the RMA service works
The RMA form and details are availableon our web sites:
https://www.cdautomation.com/returns-material-authorisation/
When completing the RMA form, please be as specic as possible about the problem, including any pertinent
application details. The more information given, the more quickly and more thoroughly the problem can be solved. The minimum information required is:
1. The Full Model Number
2. Quantity of units being returned
3. The units Serial Number(s)
4. A description of the problem (“faulty” or “unknown” is not sucient)
8
REVO S 2PH from 60A to 210A User’s manual
Declaration of conformity ..................................................3
Important warnings for safety
..............................................4
Maintenance
...............................................................7
Basic Connections
.........................................................10
Identication and Order Code
.............................................11
2.1. Identication of the unit .........................................................11
2.2. Order code
......................................................................12
Technical Specications ...................................................13
3.1 General features .................................................................13
3.2 Input features
...................................................................13
3.3 Output features (power device)
..................................................13
3.4 Fan Specication (60-90A)
.......................................................13
3.5 Fan Specication (120-210A)
.....................................................13
3.6 Environmental installation conditions
............................................14
3.7 Derating curve
...................................................................14
Installation ................................................................15
4.1 Dimensions and weight ..........................................................15
4.2 Fixing holes
......................................................................16
Wiring instructions ........................................................17
5.1 Terminals Positions 2Ph 60-90A Size .............................................17
5.2 Terminals Positions 2Ph 120-210A Size
...........................................18
5.3 Thermal Switch (OPTION)
.......................................................19
5.4 Power Terminals
.................................................................20
5.5 Command Terminals
.............................................................20
5.6 Connection Diagram for 3 phases (control on 2 phases) from 60 to 90A
..........22
5.7 Connection Diagram for 3 phases (control on 2 phases) from 120 to 210A
.........23
Led status and alarms .....................................................24
1
2
3
4
5
6
Summary
REVO S 2PH from 60A to 210A User’s manual
9
Heater Break alarm and SCR short circuit..................................24
7.1 Heater break Calibration procedure..............................................24
7.2 HB Alarm contact
................................................................25
Input setting...............................................................26
8.1 Input calibration procedure......................................................27
Firing type.................................................................28
9.1 Zero Crossing (ZC) with SSR input ................................................28
9.2 Burst Firing (BF) with Analog Input
...............................................28
9.3 Burst Firing settings
.............................................................29
Internal Fuse ..............................................................30
10.1 Fuses Replacement.............................................................31
Trouble shooting ..........................................................32
7
8
9
10
11
10
REVO S 2PH from 60A to 210A User’s manual
Basic Connections
Star wiring with resistive load (control on two phases)
V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load
Delta wiring with resistive load (control on two phases)
V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load
1
I=
P
1,73V
I=
P
1,73V
V
V
REVO S 2PH from 60A to 210A User’s manual
11
Identification and Order Code
2.1. Identication of the unit
Caution: Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product.
The identication’s label give all the information regarding the factory settings of the Thyristor unit, this label is on the unit, like represented in gure.
Verify that the product is the same thing as ordered.
2
12
REVO S 2PH from 60A to 210A User’s manual
CURRENT 4 5 6
description code
60A 0 6 0
75A 0 7 5
90A 0 9 0
120A 1 2 0
150A 1 5 0
180A 1 8 0
210A 2 1 0
MA X VO LTAGE 7
description code
480V 4
600V 6
690V 7
AUX VOLTAGE SUPPLY 8
description code
No Aux Voltage without HB and/or Analog Input up to 210A included
0
With HB and/or Analog Input on all unit ≤ 210A Aux Volt
12: 24V a c- dc
4
INPUT 9
description code
SSR S
0:10V dc V
4:20mA A
FIRING 10
description code
Zero Crossing ZC Z
Burst Firing 4 Cycles On at 50% Power Demand 4
Burst Firing 8 Cycles On at 50% Power Demand 8
Burst Firing 16 Cycles On at 50% Power Demand 6
CONTROL MODE 11
description code
Open Loop 0
FUSES & OPTION 12
description code
Fixed fuse Std for all Units >40A F
Fixed fuse Std + CT + HB H
FAN V OLTAG E 13
description code
Fan 115Vac 1
Fan 2 30Va c Std Version 2
Fan 2 4Vdc 3
APPROVALS 14
description code
CE EMC For European Market 0
CE EMC + cUL® listed and cULus 508® listed L
MANUAL 15
description code
None 0
Italian 1
English 2
German 3
French 4
VERSION 16
description code
Std Version 1
2.2. Order code
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
REVO S 2PH
R S 2 _ _ _ - _ _ _ _ _ _ _ _ _ _
REVO S 2PH from 60A to 210A User’s manual
13
Technical Specifications
3.1 General features
Cover and Socket material: PolymericV2
Utilization Category AC-51 AC-55b
IP Code 20
Method of Connecting Load in Delta, Load in Star
Auxiliary voltage: 12÷24V dc/ac (max 70mA) If requested
Relay output for Heater Break Alarm (only with HB option): 0.5A a 125VAC
3.2 Input features
Logic input SSR: 5 ÷ 30Vdc 18mA Max (ON >5Vdc OFF <4Vdc)
Logic input SSR with HB option: 4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
Analog Input V: 0 ÷ 10Vdc (15KW)
Analog Input A: 0 ÷ 20mA / 4 ÷ 20mA (100W)
Digital Input calib. (only with HB option): 12 ÷ 24V dc/ac (max 37mA)
3.3 Output features (power device)
Current Nominal
Voltage
range
(Ue)
Repetitive peak reverse voltage
(Uimp)
Latching
current
Max peak one cycle
Leakage
current
FUSE I2T
value
Suggested
A2s
(at500V)
Frequency
range
Power loss
Thyristor
+
Fuse
Isolation
Voltage
(Ui)
(A) (V) (480V) (600V) (mAe) (10msec.)
(A)
(mAe) tp=10msec (Hz) I=Inom (W) Vac
60 24÷600 1200 1600 600 1900 15 8680 47÷70 205 3000
90
24÷600 1200 1600 600 1900 15 8680 47÷70 290 3000 120 24÷600 1200 1600 600 1900 15 14280 47÷70 398 3000 150 24÷600 1200 1600 300 5000 15 17500 47÷70 409 3000 180 24÷600 1200 1600 300 5000 15 30800 47÷70 469 3000 210 24÷600 1200 1600 300 5000 15 53900 47÷70 598 3000
75A for UL
3.4 Fan Specication (60-90A)
Supply: 230Vac Standard Power 16W (1 Fan)
Supply: 115Vac Option Power 14W (1 Fan)
Supply: 24Vdc Option Power 7W (1 Fan)
3.5 Fan Specication (120-210A)
Supply: 230Vac Standard Power 32W (16W for 2 Fans)
Supply: 115Vac Option Power 28W (14W for 2 Fans)
Supply: 24Vdc Option Power 14W (7W for 2 Fans)
3
14
REVO S 2PH from 60A to 210A User’s manual
Derating
For higher cabinet temperature contact the producer of the unit
l max = l nominal x K
1
15 20 25 30 35 40 45 50 55
1,2
1
0,8
0,6
0,4
0,2
0
1 1 1 1
0,9
0,8
CABINET TEMPERATURE °C
K
3.6 Environmental installation conditions
Ambient temperature 0-40°C (32-104°F) at nominal current. Over 40°C -104°F use the derating curve.
Storage temperature -25°C to 70°C
-13°F to 158°F
Installation place Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
Altitude Up to 1000 meter over sea level. For higher altitude reduce the nominal current of 2% for each 100m over 1000m
Humidity From 5 to 95% without condense and ice
Pollution Level Up to 2nd Level ref. IEC 60947-1 6.1.3.2
3.7 Derating curve
REVO S 2PH from 60A to 210A User’s manual
15
Installation
Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product. Verify that the product is the same thing as ordered. The Thyristor unit must be always mounted in vertical position to improve air cooling on heat-sink. Maintain the minimum distances in vertical and in horizontal as represented. When more unit has mounted inside the cabinet maintain
the air circulation like represented in gure.
Sometimes is necessary installing a fan to have better air circulation.
4
≥5 cm
≥15 cm
≥2 cm
AIR
AIR
4.1 Dimensions and weight
Size W (mm) D (mm) H (mm) Weight (kg)
SR15 (60-90A) 93 170 273 3,6
SR16 (120-210A) 186 170 273 7
REVO S 2PH 60-90A (Size SR15) REVO S 2PH 120-210A (Size SR16)
W
D
H
W
D
H
16
REVO S 2PH from 60A to 210A User’s manual
71
260
165
260
5
5
5
5
5
5
5
5
4.2 Fixing holes
REVO S 2PH 60-90A (Size SR15) REVO S 2PH 120-210A (Size SR16)
REVO S 2PH from 60A to 210A User’s manual
17
Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions:
• The coil contactor, the relays and other inductive loads must be equipped with opportune RC lter.
• Use shielded bipolar cables for all the input and output signals.
• The signal cables must not be near and parallel to the power cables.
• Local regulations regarding electrical installation should be rigidly observed.
Use copper cables and wires rated for use at 90°C only.
Power cable torque (suggested)
Type
Connector
Type
Torque Lb-in
(N-m)
Wire Range mm²(AWG )
MAX Current
Terminals
Wire Terminals
UL Listed (ZMVV)
060
0
90
120
Screw M6 70.8 (8.0)
16(5) 25(3) 35(2)
150
Fork/Spade Terminal
Copper Tube Crimp.Lug
150 180 210
Screw M8 141,6 (16.0)
50(0)
70(00)
90(000)
250
Fork/Spade Terminal
Copper Tube Crimp.Lug
75A for UL
Cable dimensions of the Command Terminals
0.5 mm² (AWG 18)
Cable dimensions of the Earth (suggested)
16 mm² (AWG 6) up to 120A 25 mm² (AWG 4) up to 210A
5.1 Terminals Positions 2Ph 60-90A Size
5
Top view Down view
18
REVO S 2PH from 60A to 210A User’s manual
5.2 Terminals Positions 2Ph 120-210A Size
Top view
Down view
REVO S 2PH from 60A to 210A User’s manual
19
5.3 Thermal Switch (OPTION)
N.C. switch open when the heatsink temperature is 90°C +/- 5%
Terminal Description
TS Thermal Switch 1
TS Thermal Switch 2
20
REVO S 2PH from 60A to 210A User’s manual
5.4 Power Terminals
Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources.
Terminal Description
L1 Line Input Phase 1
T1 Load Output Phase 1
L3 Line Input Phase 3
T3 Load Output Phase 3
5.5 Command Terminals
Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources.
Terminal block M1 for SSR Input
Terminal M1 Description
1 Not connected
2 Not connected
3 Not connected
4 Not connected
5 Not connected
6 Not connected
7 - Input SSR
8 + Input SSR
9 Not connected
10 Not connected
11 Fan supply (230V standard – 115V option)
12 Fan supply (230V standard – 115V option)
REVO S 2PH from 60A to 210A User’s manual
21
Terminal block M1 for Analog Input or SSR input with HB
Terminal M1 Description
1 Aux – Voltage Supply for electronic boards 12-24V AC/DC
2 Aux – Voltage Supply for electronic boards 12-24V AC/DC
3 - Cal Ext. 12/24Vdc
4 + Cal Ext. 12/24Vdc
5 C –Common contact relay alarm output (see HB Alarm contact for cong.)
6 NC\NO –Normally Close\Open contact alarm relay output (see HB Alarm contact for cong.)
7 - Control Input (SSR/0-10Vdc/4-20mA)
8 + Control Input (SSR/0-10Vdc/4-20mA)
9 Not connected
10 Not connected
11 Fan supply (230V standard – 115V option,from 90 to 210A)
12 Fan supply (230V standard – 115V option,from 90 to 210A)
22
REVO S 2PH from 60A to 210A User’s manual
5.6 Connection Diagram for 3 phases (control on 2 phases) from 60 to 90A
Caution: this procedure must be performed only by qualied persons.
Note:
*
1 A suitable device must ensure that the unit can be electrically isolated from the supply (electromagnetic
circuit breaker or by fuse isolator), this allows the qualied people to work in safety.
*
2 Only for the HB option See par. “Heater break Alarm and SCR short circuit”.
*
3 The heat-sink must be connected to the earth.
*
4 Only for the Analog Input option, the analog input isn’t isolated from Aux Supply
a series connection between analog inputs of the units is not possible. With AC Aux supply is not possible to connect the zero terminal of Analog Input to the earth. With DC Aux supply is not possible to connect the zero of the power supply with the zero of analog input.
1
4
2
3
- +
- +- +
M1
SSR Input Only
SSR Input Only [ SSR
Input [ SSR 0/10Vdc / 4-20mA
CT+HB option
AUX 12-24 ac/dc
CAL Ext. 12-24Vdc
HB Alarm
Relay Out.
Fan Supply
Fan Supply
TO LOAD
Analog Input or SSR Input with HB
L1
L3
T1 T3
Down
Top
T1 T2 T3
T1 T2 T3
LOAD TYPE
Delta Star
REVO S 2PH from 60A to 210A User’s manual
23
5.7 Connection Diagram for 3 phases (control on 2 phases) from 120 to 210A
Caution: this procedure must be performed only by qualied persons.
Note:
*
1 A suitable device must ensure that the unit can be electrically isolated from the supply (electromagnetic
circuit breaker or by fuse isolator), this allows the qualied people to work in safety.
*
2 Only for the HB option See par. “Heater break Alarm and SCR short circuit”.
*
3 The heat-sink must be connected to the earth.
*
4 Only for the Analog Input option, the analog input isn’t isolated from Aux Supply
a series connection between analog inputs of the units is not possible. With AC Aux supply is not possible to connect the zero terminal of Analog Input to the earth. With DC Aux supply is not possible to connect the zero of the power supply with the zero of analog input.
1
4
2
3
- +
- +- +
M1
SSR Input Only
SSR Input Only [ SSR
Input [ SSR 0/10Vdc / 4-20mA
CT+HB option
AUX 12-24 ac/dc
CAL Ext. 12-24Vdc
HB Alarm
Relay Out.
Fan Supply
Fan Supply
TO LOAD
Analog Input or SSR Input with HB
L1 L3
T1 T3
Down
Top
T1 T2 T3
T1 T2 T3
LOAD TYPE
Delta Star
24
REVO S 2PH from 60A to 210A User’s manual
Led status and alarms
LED STATUS DESCRIPTION
ON
LED OFF (
) Load is NOT powered
LED ON (Green) (
) Load is powered
S.C.
LED OFF (
) Load OK
LED ON (Red) (
) SCR short circuit (only with HB option)
LED Flashing (Red) (
)
Over Temperature on heat sink
H.B.
LED OFF (
) Load OK
LED ON (Yellow) (
) Load Fault (only with HB option)
6
Heater Break alarm and SCR short circuit
(HB Option only)
Caution: to work properly the load must be powered at least about 160msec.
The Heater Break circuit read the load current with an Internal current transformer (C.T.). Minimum current is 10% of the current transformer size. If load current is below this value the Heater Break Alarm doesn’t work properly.
7.1 Heater break Calibration procedure
An automatic function sets the Heater Break Alarm. The auto setting function can be activated using the “CAL” button on front unit, or supply with 12-24Vdc the digital input “Cal Ext.” (See Connection Diagram).
The Heater Break calibration procedure is performed in this way:
• The Unit gives the maximum voltage output
• All LEDS are on, this means that calibration procedure is active
• The current value is stored in memory
• After about 15 second the unit comes back to the initial situation
If load current decreases for partial or total load failure (sensitivity 20%) the yellow LED HB become ON and alarm relay change status. If the unit is still in conduction with no input signal (LED green OFF) it means that there is a short circuit on thyristors and red LED (SC) become ON. If the load has been changed the Heater Break calibration procedure must be done again.
ON
S.C.
H.B.
CAL
7
REVO S 2PH from 60A to 210A User’s manual
25
7.2 HB Alarm contact
The Revo unit with HB option (if available), is supplied with Heater Break alarm contact normally opened (NO):
• In normal conditions (without alarm) and with auxiliary power supply, the contact to the terminals has opened (relay coil energized).
• In alarm condition or without auxiliary power supply the contact to the terminals is closed (relay coil not energized).
If you wish to change the alarm contact open the cover of the Master module (rst on
the left with terminal block) and set the jumper as shown in the next page, don’t set the other jumpers with factory settings.
Warning: Before operate, be sure that power and control cables are isolated from voltage sources.
L1
T1
L2
T2
MASTER
A B C
JP1
A B C
JP1
A - B =
NC
A B C
JP1 B - C =
NO
26
REVO S 2PH from 60A to 210A User’s manual
Input setting
The input type is already congured in line with customer requirements that are dened in the Order Code.
However, if you wish to change the input type (ex. from 0÷10V to 4÷20mA) set the jumpers as below represented
and then do the “Input calibration procedure”. Open the cover of the Master module (rst on the left with
terminal block) and set the jumper as shown, don’t set the other jumpers with factory settings not shown.
Important: The analog input isn’t isolated from Aux Supply. The series connection between analog inputs of the units is not possible. With AC Aux supply it’s not possible connect the zero terminal of Analog Input to the earth. With DC Aux supply is not possible to connect the zero of the power supply with the zero of analog input.
Warning: Before operate, be sure that power and control cables are isolated from voltage sources.
L1
T1
L2
T2
MASTER
8
There are two type of PCB board, for SSR Only Version board the other jumpers are not mounted on PCB.
A B C
SSR
JP2 A-B JP3 B-C JP6 A-B
JP2
JP3
JP6
JP8
JP7
JP9
A B C
JP2
JP3
JP6
SSR only
JP8 Close
JP9 Close
A B
JP8 JP9
JP2 B-C JP3 A-B JP6 B-C
A B C
JP2
JP3
JP6
0-10 Vdc
JP2 B-C JP3 B-C JP6 B-C
A B C
JP2
JP3
JP6
4-20 mA
REVO S 2PH from 60A to 210A User’s manual
27
8.1 Input calibration procedure
Warning: this procedure can be done just by specialized personnel
This procedure is needed only if you change the input type
ON
2sec.
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
0% Signal
100% Signal
Auxiliary power supply
OFF
Start TUNE
Mantain Key CAL pushed
and give the power supply
Release key
when red and yellow
led are ON
Yellow and Red leds
are ashing
Wait for more than 10 sec.
from start ashing
yellow and red leds
Within 10 sec. from start
ashing yellow and red leds
push again momentary
CAL Key
The leds will
stop ashing
SSR ANALOG
INPUT TYPE
SSR Input
is tuned
Yellow led only is
ashing, apply
0 input Signal
I.E.
: 0V for 0-10V
4mA for 4-20mA
Now press CAL Key again
Red led only is ashing, apply
10V for 0-10V input
or
20mA for 4-20mA input
Now press CAL Key again
End
TUNE
Analog input
is tuned
28
REVO S 2PH from 60A to 210A User’s manual
Firing type
Choose a correct ring type allows to optimize the thyristor unit for the installed load. The ring type has already congured in line with customer requirements, Zero Crossing for SSR input and Burst ring for Analog Input.
Caution: this procedure must be performed only by qualied persons.
9.1 Zero Crossing (ZC) with SSR input
ZC ring mode is used with Logic Output from temperature controllers and the Thyristor operates like a
contactor. The Cycle time is performed by temperature controller. ZC minimizes interferences because the Thyristor unit switches ON-OFF at zero voltage.
9.2 Burst Firing (BF) with Analog Input
The Burst Firing is similar to the Single Cycle, but consecutive cycles ON are selectable between 1 and 255,
with input signal equal at 50%. When is specied 1 the ring type is Single Cycle.
Burst Firing is a method zero crossing that it reduces the electromagnetic interferences because the thyristor switches at zero voltage crossing. The example show the Burst Firing with Burst cycles: 4.
Voltage Supply (V)
Load Voltage (V)
SSR from controller
ON OFF
9
Voltage Supply (V)
Load Voltage (V)
25%
50%
75%
100%
ON OFF
REVO S 2PH from 60A to 210A User’s manual
29
9.3 Burst Firing settings
The Burst Firing cycles is already congured in line with customer requirements that are dened in the Order
Code. However, if you wish to change the Burst Firing cycles (es. from 4 to 8) set the jumpers as below represented:
Warning: Before operate, be sure that power and control cables are isolated from voltage sources.
JP4
BF4 OPEN
BF8
A-B
BF16 B-C
JP5
JP4
A B C
A B C
30
REVO S 2PH from 60A to 210A User’s manual
Caution: High speed fuses are used only for the thyristor protection and can not be used to protect the installation.
Caution: The warranty of thyristor is null if no proper fuses are used. See tab.
Warning: When it is supply, the Thyristor unit is subject to dangerous voltage, don’t open the
Fuse-holder module and don’t touch the electric equipments.
Internal Fuse
The thyristor unit have internal fuse extrarapid at low I²t for the thyristor protection of against the short-circuits. The Fuses must have I²t 20% less than thyristor’s I²t. The warranty of thyristor is null if no proper fuses are used.
Type
Fuse Code
Spare Part
Current
(ARMS)
Vac
FUSE I2T value
Suggested A2s
(at500V)*
FUSE I2T value Suggested A2s
(at660V)
060 2 x 50 073 06.100 2 x 100 660 8680 12400
060 (only UL) L220971J 100 690 3998 6150 (690V)
075 (only UL) L220971J 100 690 3998 6150 (690V)
090 2 x 50 073 06.100 2 x 100 660 8680 12400
120 20 559 20.180 180 660 14280 20400
150 20 559 20.200 200 660 17500 25000
180 20 559 20.250 250 660 30800 44000
210 20 559 20.315 315 660 53900 77000
*
I2T are multiplied for K value in function of Vac at 500V K is equal to 0,7 (ex:12400 X 0,7 = 8680). At 660Vsc K is equal to 1.
1.2
1.0
0.8
0.6
0.4
0.2
0.7
500
200 400 600 800
Vac
(Line voltage)
K
10
REVO S 2PH from 60A to 210A User’s manual
31
10.1 Fuses Replacement
Open the cover and remove the screws
32
REVO S 2PH from 60A to 210A User’s manual
Trouble shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting. If you don’t succeed, contact us or your nearest distributor.
Symptom
Indication on front unit
Possible reasons
of the symptom
Actions
Load current
doesn’t ow
Green LED (ON) light OFF (
)
• No Auxiliary Voltage
• No input signal
• Reversed polarities of input signal
• Give auxiliary voltage supply (See Connection Diagram)
• Provide to give input signal
• Reverse the input signal polarity
Green LED (ON) light ON (
)
• Fuse failure
• Load connection interruption
• Load failure: The yellow led (HB) is light on (with HB option)
• Thyristor fault: The red led (SC) is light on (with HB option)
• Change the fuse
• Check the wiring
• Check the load
• Change the thyristor module
Load current ow also
without input signal
Red LED (SC) light ON (
)
• Wrong wiring
• SCR short circuit
• Check the wiring
• Change the thyristor module
Current ows at nominal
value but Yellow LED (HB/SC) is light on
Yellow LED (HB) light ON (
) or Red LED (SC) light ON ( )
• HB circuit not tuned
• Current transformers not properly wired
• Make HB calibration procedure
• Check current transformers wiring
Thyristor unit doesn’t work properly
• Auxiliary voltage supply out of limits
• Wrong input signal selection
• Wrong input signal calibration (out of range)
• Verify the auxiliary voltage supply
• Control input signal setting
• Check input setting
11
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: info@cdautomation.com - Web: www.cdautomation.com