THESE HEATERS MUST BE INSTALLED AND SERVICED BY TRAINED GAS
INSTALLATION AND SERVICE PERSONNEL ONLY. READ AND UNDERSTAND ALL
INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR
SER VICE THE DETROIT RADIANT PRODUCTS COMP ANY HEATER. FAILURE TO COMPLY
WITH THESE WARNINGS AND INSTRUCTIONS, AND THOSE ON THE HEATER, COULD
RESULT IN PERSONAL INJURY, DEATH, FIRE, ASPHYXIATION AND/OR PROPERTY
DAMAGE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
CAUTION! Heater may be hot. Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance. Note presence of flammable gas and
electrical shock hazard.
WARNING! Extinguish open flame while servicing heaters. Test for gas leaks with soap and
water solution only. Wear safety glasses while servicing unit.
FOR YOUR SAFETY!
IF YOU SMELL GAS:
1. Open windows.
2. Do not touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
Approval Standards and Certifications
Detroit Radiant Products units comply with or are certified by the following Organizations or
Standards:
- American National Standards (ANSI Z83.6)
- Occupational Safety and Health Act (OSHA)
- American Gas Association (AGA)
- International Approval Services (IAS)
IMPORTANT: Any alteration of the system or of the factory-authorized components specified
either in this manual or by Detroit Radiant Products Company voids all certification and warranties.
SHUTDOWN INSTRUCTIONS!
1. Open electrical circuit.
2. Rotate heater’s manual gas valve
knob to “OFF” position.
-Digital Multimeter - Used for troubleshooting & testing electrical circuits.
(Part 1A783 from Grainger)
-Flame Rectification Meter - Used for testing rectification of flame with the digital multimeter.
(Channel Products)
-Digital Manometer Kit - Used for taking gas pressure, digitally.
(Part 100281-21 from Dwyer Instruments)
-Liquid Manometer Kit - Used for taking gas pressure, via a liquid manometer.
(Part 115010-00 from Dwyer Instruments)
-Digital Hygro-Thermometer(Amprobe #TH-2) - Reads temperature from -10 to 50
(Part 1P124 from Grainger)
-Incline Manometer - Used for measuring pressure inside burner box. Provides data for pressure switch.
(Cat# 172 from Dwyer Instruments)
-1/4” Nut Driver - Can be used to remove screws holding top on.
(Part 5X509 from Grainger)
O
C and relative humidity from 5-95%.
-Pliers 8” - Tool for burner box access.
(Part 6C183 from Grainger)
-Pipe Wrench 8” - Can be used to disassemble gas train assembly.
(Part 4A497 from Grainger)
-Ratcheting Box Wrench - Can be used to remove orifice and bolts. (size 7/16” and 3/8”)
(Part 1AMW9 from Grainger)
-6” Steel Rule - Used for measuring air orifice size.
(Part 6C289 from Grainger)
-Terminals 1/4” Female - Extra female spade terminals.
-Barb Fitting - Fitting to take gas pressure at the valve.
-Vinyl Tubing - Tubing for pressure measurements. (size 5/16” x 3’)
-Jumpers/Connectors - Used to jump out the pressure switches.
-Self Tapping Screws - Extra Screws.
-Drill Bits 1-60, A-Z - Drill Bits 1-60, A-Z, for measuring gas orifice size (DMS).
-Manuals - DX, DX-2 or XTS Series Installation, Operation & Maintenance manuals (IOM’s).
1
Theory of Operation
Starting Circuit
When voltage is applied to L1 and L2, a circuit is completed from L1 via the blower motor to L2. The
blower fan is mounted in the control box and rated to supply sufficient air combustion.
Air pressure generated by the blower will cause the normally open burner pressure switch No. 1 to close.
Another circuit is completed from L1 to the hot surface ignition control and back to L2. There is a five
second delay , then the glo-bar is powered. After the glo-bar has been powered for 45 seconds, the control
causes the gas valve to open and initiates the ignition trial. Power to the glo-bar is shut off during the last
two or three seconds of the ignition trial.
Running Circuit
After ignition, the flame rod monitors the flame. As long as a flame is present, the valve is held open. If the
flame is lost, the control acts to close the valve within one second, and a new trial sequence identical to that
at start-up is initiated. If proof of flame is not established within 8.5 seconds, the unit will lock out. If
lockout occurs, the control can reset by briefly interrupting the power source.
Note: The DX-2 Series heaters have added indicator lights to assist in troubleshooting and ignition sequence.
1. Provide 1 sq. in. of free air for every
5000 BTU/H of input.
2. Correct with proper gas input.
1. Address ventilation concerns.
2. Address ventilation concerns.
3. Address ventilation concerns/repair.
4. Tighten tube clamps to 50-100 ft. lb.
Refers to DX or XTS Series Heaters
without Indicator Lights
11
12
13
Refers to all Heaters
10
1 - Thermostat Closed, Fan Does Not Operate
If the thermostat is closed (on) and heater does not operate, check the following:
1.1
Check the building’s main circuit breaker or fuse box. The problem may be a blown fuse or circuit.
1.2
Thermostat Operation: Verify the thermostat is allowing power to be sent to the heater. Confirm by
measuring the voltage to the heater using a volt meter (See picture below). If there is no power , the
problem is in the thermostat and it should be replaced. If power is at the heater, continue on to the
next step.
1.3
Check the electrical connections leading to the fan. Be sure that the wire nuts are tight.
1.4
Using the voltmeter, check to be sure power is going to the fan (pg. 8, pic. 5). If there is power , try
cleaning and oiling (SAE-20 oil) the motor. If fan still not working, it is faulty.
2 x 4 Junction Box
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
Picture 1.2
11
2 - Thermostat Closed, Fan Operates, No Glo-Bar Energization
(This step is applicable for all models)
2.1
Locate any disconnected or loose wires and repair.
2.2
The normally open Burner Pressure Switch is located on the fan side of the heater (pg. 8, pic. 1 ). This switch
must be closed before the glo-bar can be energized. *Bypass this switch (pg. 19, #6) to check for proper function.
Once bypassed, reinstall the cover and test the heater. If it works, there is a problem with the burner pressure
switch or what it is sensing, and you should continue with step 2.2.1. If bypassing this pressure switch does not
make the heater work, continue with step 2.3.
2.2.1
Be sure lid is on correctly and gasket is intact.
2.2.2
Make sure the clear vinyl tube that bleeds pressure to the outside of the heater is clean and clear of
obstructions.
2.2.3
Make sure the heater’s vent cap is in place and in good condition. Also, check for obstructions within the
cap.
NOTE: Excessive winds may cause properly operating safety pressure switches to shut down the heater. Heaters ducted through (on either the
intake or exhaust sides) the roof may be deprived of the air necessary to pressurize the burner box. This “chimney effect” will typically not
allow the burner pressure switch to close. Heaters vented through a sidewall may see too much back-pressure, thus opening the exhaust
pressure switch. In either case, the caps need to be shielded to lessen the effects of high winds.
2.2.4
Make sure the heater’s baffle is located properly. It should be found at the exhaust end of the emitter tube.
2.2.5
The fan may not be accurately pressurizing the heater. Clean obstructions from the air -intake pipe and cap
(pg. 8, pic. 8). Clean the squirrel cage. Oil the motor (SAE-20). Examine and clean the fan blades
(pg. 8, pic. 5). Once the fan is completely clean, retry the heater, without bypassing the Burner Pressure
Switch. If the glo-bar is still not energizing, continue with Step 2.2.6.
2.2.6
If steps 2.2.1 - 2.2.4 were performed and the heater still won’t properly function, the burner pressure switch
is faulty .
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
12
2 - Thermostat Closed, Fan Operates, No Glo-Bar Energization (cont.)
(This step is applicable for all models)
2.3
The Exhaust Pressure Switch is located on the valve side of the heater (pg. 8, pic. 4). *Bypass this switch
(pg. 19, #6). If the heater works with the exhaust pressure switch bypassed, the problem is with this switch or what
it is sensing and you should continue with step 2.3.1. If bypassing this switch does not cause the heater to work,
continue with step 2.4.
2.3.1
Be sure the lid is on correctly and tightly and the gasket is in intact.
2.3.2
Check to make sure the clear vinyl tube that bleeds pressure to the outside of the heater is clean and clear of
obstructions.
2.3.3
Clean any obstructions from the emitter tube, exhaust tube and vent cap.
2.3.4
Check to make sure the heater’s baffle is located properly. It should be found at the exhaust end of the
emitter tube.
NOTE: Excessive winds may cause properly operating safety pressure switches to shut down the heater. Heaters ducted through (on either the
intake or exhaust sides) the roof may be deprived of the air necessary to pressurize the burner box. This “chimney effect” will typically not
allow the burner pressure switch to close. Heaters vented through a sidewall may see too much back-pressure, thus opening the exhaust
pressure switch. In either case, the caps need to be shielded to lessen the effects of high winds.
2.3.5
If steps 2.3.1 - 2.3.4 were performed and the heater still won’t properly function, the exhaust pressure
switch is faulty .
2.4 (This step is applicable for DX & XTS models only)
Check the Circuit Board (pg. 8, pic. 3). Use a volt meter to ensure that power is actually entering the circuit
board. Turn of f the gas to the heater and *bypass both pressure switches (pg. 19, #6), as a heater with no cover will
not allow pressure switches to function properly. 120 volts exiting the circuit board indicates that the glo-bar is
faulty. If no voltage exits the circuit board, it is faulty.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
13
3 - Thermostat Closed, Fan & Glo-Bar Operate.
After 45 Seconds Glo-Bar Shuts Off, No Ignition.
(This step is applicable for DX & XTS models only)
3.1
Be sure that the gas valves inside and outside of the heater are turned to the ON position.
3.2
Locate and confirm that the gas orifice is not plugged with dirt, spider webs or rust.
3.3
Turn off the gas to the heater and *bypass both the Burner & Exhaust Pressure Switches (pg. 19, #6). Test
the voltage coming from the Circuit Board to the Gas Valve (pg. 8, pic. 6) using a volt meter. If there is 120
volts, the gas valve is faulty. If there is less than 102 volts or no voltage at all, the circuit board is faulty.
3.4
The inlet pressure entering the system may be too high. The maximum value for both natural and propane is
14” W.C.P. Correct this problem by either adjusting the building’s regulator down to 14” W.C.P. or by using
step-down regulators in the building’ s piping system.
NOTE: THE GAS VALVE IS ONLY RATED FOR 1/2 POUND (14 INCHES) OF PRESSURE.
IF USING A HIGH-PRESSURE REGULATOR, BE SURE IT IS LOCKING UP PRIOR TO THE
INLET PRESSURE REACHING 1/2 POUND.
3 - Thermostat Closed, Fan Operates.
Switches Light is Energized. No Glo-Bar Energization.
(This step is applicable for the DX-2 models only)
Check the Circuit Board (pg. 8, pic. 3). Use a volt meter to measure the voltage the circuit board is sending to the
glo-bar. This is done by hooking the voltmeters probes to the black and white wires leading from the circuit board
to the glo-bar. If the measurement is 102V or less, the circuit board is faulty. If it measures 120V, the glo-bar is
faulty.
NOTE: Do not unplug the glo-bar.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
14
4 - Thermostat Closed. Fan & Glo-Bar Operate. Ignition Occurs.
Burner Cycles Off & will not Recycle.
There are two possibilities:
1) The Burner cycles for 8 seconds and shuts off.
4.1
The polarity could be incorrect. Check the systems wiring (pg. 19, #3) (See installation-operation
manual wiring diagram).
4.2
The heater senses flame through ground. Therefore, the unit might not be properly grounded. The
wiring should be inspected (pg. 19, #4).
4.3
There may be loose connections somewhere within the heater, or, the Circuit Board may be faulty.
4.4
The gas pressure is too low. Check the manifold (section 6.1) pressure (pg. 8, pic. 6 & pg. 19, #2) for
appropriate pressure.
4.5
The flame rod might be faulty (pg. 8, pic. 7). Check for visible damage.
NOTE: IF THE PROBLEM IS EITHER THE CIRCUIT BOARD OR THE FLAME
ROD, ONE OR BOTH MIGHT NEED REPLACING.
2) The Burner cycles for more or less than 8 seconds and shuts off.
4.6
Follow steps 4.1 - 4.5.
4.7
The Exhaust Pressure Switch is located on the valve side of the heater (pg. 8, pic. 4). *Bypass this switch
(pg. 19, #6). If the heater works with the exhaust pressure switch bypassed, the problem is with this switch
or what it is sensing and you should continue with step 2.3.1 (located on page 13). If bypassing this switch
does not cause the heater to work, continue with step 2.4 (located on page 13).
4 - Thermostat Closed. Fan Operates. Switch Light &
Glo-Bar Energized. No Valve Light.
(This step is applicable for DX-2 models only)
Disconnected Valve Wire - The wire between the circuit board and the gas valve may be disconnected.
Inspect and reconnect if necessary .
Faulty Circuit Board - If the valve wire is connected properly, the circuit board is faulty and must be
replaced.
NOTE: If the Valve Wire is properly connected and the heater fires, the valve light is faulty.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
15
5 - Thermostat Closed. Fan & Glo-Bar Operate. Ignition Occurs.
Energized. After 45 Secs., Glo-Bar Shuts Off. No Ignition.
(This step is applicable for DX-2 models only)
5.1
Be sure that the gas valves inside and outside of the heater are turned to the ON position.
5.2
Locate and confirm that the gas orifice is not plugged with dirt, spider webs or rust.
5.3
Bypass both the Burner & Exhaust Pressure Switches (pg. 19, #6) and then test the voltage coming from the
Circuit Board to the Gas Valve (pg. 8, pic.6) using a volt meter. If there is 120 volts, the gas valve is faulty. If
there is less than 102 volts or no voltage at all, the circuit board is faulty .
5.4
The inlet pressure entering the system may be too high. The maximum value for both natural and propane is
14” W.C.P. Correct this problem by either adjusting the building’s regulator down to 14” W.C.P. or by using
step-down regulators in the building’ s piping system.
NOTE: THE GAS VALVE IS ONLY RATED FOR 1/2 POUND (14 INCHES) OF PRESSURE.
IF USING A HIGH-PRESSURE REGULATOR, BE SURE IT IS LOCKING UP PRIOR TO THE
INLET PRESSURE REACHING 1/2 POUND.
6 - Heater’s Efficiency is Lacking
Usually , a heater lacking in efficiency has improper gas pressure, dirty parts or is a misapplication of the heater
itself.
6.1
If the manifold pressure is not high enough, (a minimum of 3.5” natural and 10” propane) the heater will not
deliver the desired amount of heat. Check the Manifold Pressure (pg. 8, pic. 6 and pg. 19, #1 & #2).
6.2
Locate and confirm the orifice is not plugged with dirt, spider webs or rust.
6.3
Check the burner assembly to make sure it is clear of any obstructions.
6.4
Be sure the reflector is in place and clean. Use a soft cloth and aluminum cleaner to clean the reflector .
6.5
Be sure the fan is clean and able to supply the appropriate amount of air to the heater . Clean any obstructions from
the air-intake pipe and cap. Clean the squirrel cage. Oil the motor (SAE-20). Examine and clean the fan blades.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
16
7 - Radiant Tube Leaking Burnt Gas
Obstructions in the heater may cause too much heat in a specific point, leading to holes or cracks. These
openings can cause burnt gas to leak out. If this problem is occurring, follow these steps:
Carefully inspect the length of all emitter tubes and clamps for any cracks, holes or loose connections. If any
part of the tube has an opening, it must be replaced immediately. Also check for blockages in the exhaust and
emitter tube.
8 - Condensation is Forming
If condensation is forming anywhere along the length of the emitter or exhaust pipe, check to make sure that it is
not excessive in length. Be sure that the heater has the appropriate manifold pressure (see 6.1, 4.4). Confirm the
use of adequate vent material (26 gauge minimum is required). Inspect the baffle location (it should be found at
the exhaust end of the emitter tube), insulate vent materials, and seal leaks around vent openings. Chemicals
burned through the combustion process can alter the exhaust by-products and temperature. See your heater’s
manual for air-intake specifications.
9 - Emitter Tube is Bowing
Normal operation of the heater will often cause expansion of the emitter tube. If there is no room for this to
occur, the tube will bow. If this is happening, follow steps 9.1 - 9.4.
9.1
Too little air will lead to shorter flame, causing it to burn hotter than normal. Be sure there is nothing blocking
the air intake and that the fan is clean (pg. 8, pics. 5 & 8).
9.2
Contaminated combustion air could alter the flame characteristics, overheating the tube and causing it to bow.
See your manual for air-intake specifications.
9.3
Too much gas may also overheat the tube and cause it to bow.Check the manifold (see 6.1) pressure (pg. 8, pic. 6).
9.4
If the heater is mounted so that it cannot expand lengthwise (ie. it is cemented into the wall at both ends), add a
16” section of flex on the inlet side of the heater and allow the exhaust to move freely through the wall.
10 - Tube is Corroding
The tube would corrode if the air entering the heating system was not clean. See your heater’s manual for
combustion air intake instructions.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
17
11 - Visual Inspection of Burner Operation not Possible
From the ground, the burner inspection window should be visible. If it is not, the heater may be mounted upside
down. Confirm proper mounting and remount if necessary.
12 - Stack Sooting
Soot accumulation can be caused by the following:
12.1
If the air entering the system is not clean (see 6 & 8), soot will form.
12.2
Soot will form if there is not enough air entering the system. The air intake orifice and pipe must be clean and
clear of any obstructions (see 2.2.3) (pg. 8 pic. 8).
12.3
Too much gas entering the system will cause soot to form. Check the manifold (section 6.1) pressure
(pg. 8, pic.6 and pg. 19, #2) for the appropriate pressure.
12.4
Check the atmospheric vents on both pressure switches to be sure they are clean and clear . (see 2.3.2).
12.5
Be sure there is no excessive back pressure on the system. (Example - high winds, bird nest, snow, etc.)
13 - Odor or Fumes Present in Space
Odors present in the space being heated may be caused by a variety of products being used, stored or processed
in the space. These are usually cleaning solvents or sealers which are high in hydrocarbons (ie. parts cleaners,
transmission cleaners and floor sealers). In addition, propane burning forklifts can also add odors and carbon
monoxide to the space.
To cut down on these odors, a clean work environment has to be maintained. If it is necessary that these
solvents remain in the space, proper ventilation is required.
NOTE: If the heater is pulling intake air from the space, its integrity can be compromised by the
presence of these solvents, causing the same problems found in sections 8-12 of this guide.
Refer to warnings on cover prior to servicing the unit. Bypass safety pressur e switches for supervised troubleshooting purposes only.
*Do not leave switches bypassed while the heater is unattended or for normal operations.
Consult Detroit Radiant Products for further technical information
18
HOW TO...
1 - Take an Inlet Pressure Reading: (Always take the inlet pressure before taking the manifold pressure)
♦Follow the same procedures as taking a Manifold Pressure Reading (Step 2 below) except use
the inlet tap on the gas valve or the gas cock, located on the outside of the heater .
2 - Take a Manifold Pressure Reading:
♦Turn gas and power to the heater off.
♦Remove lid.
♦Locate outlet tap on gas valve (pg. 8, pic. 6).
♦Remove tap using a 3/16” allen wrench.
♦Insert a 1/8” pipe-thread barb fitting and run a hose to the outside of the burner box using the
5/16” capped hole next to the gas valve line opening, or, the 3/8” hole next to the conduit going
to the glo-bar box (newer models only).
♦Connect tube to a Manometer or Magnahelic.
♦Reinstall lid.
♦Fire heater.
♦The reading on the Manometer or Magnahelic is the manifold pressure.
3 - Check for Proper Polarity:
♦Turn off power to the heater.
♦Remove the cover of the 2x4 junction box on the outside of the heater - if applicable.
♦Locate the three wires inside - black, white & green.
♦Using a voltmeter, touch the black wire with one probe and the green wire with the other -
confirm 120V.
♦Using a voltmeter, touch the white wire with one probe and the green wire with the other -
confirm 0.0V.
♦If the previous step confirmed 120V, the polarity is reversed and must be corrected in the conduit
upstream from the heater.
4 - Test for Positive Ground:
♦Be sure that the ground (green) wire goes all the way back to the circuit panel.
♦If it does not, a qualified electrician must rerun this line.
5 - Test for Negative Pressure:
The building has a negative pressure if any of the following is occurring:
♦Building’ s door(s) shut very quickly with a loud bang.
♦Building’ s door(s) are dif ficult to open - as if they are suctioned shut.
♦The heater is fired and then turned off. The lid is removed and hot gases come
back into the heater box.
♦An incline manometer is set up with one hose outside of the building and one inside.
It’ s reading confirms a negative inside pressure.
6 - Bypassing a Switch:
♦Turn power off.
♦Disconnect both black wires attached to the safety switches with a 1/4” female spade.
♦Attach them to each other using alligator clips or electrical tape.
♦Be sure this connection touches nothing else, especially metal.
♦Turn power back on (Do not leave switches bypassed during normal heater operation).
19
KEY TP#ITEM KEYTP#ITEM
ALL TP-1 CONTROL BOX COVERALLTP-70 CONTROL BOX COVER GASKET(PER FOOT**)
20
DX/XTS Series Heaters
21
DX-2 Seres Heater
22
NOTES
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.