Information and specifi cations outlined in this manual in effect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specifi cations or system design at any time without
The Right Fit for Comfort2P/N 240006980, Rev. R [02/2013]
notice and without incurring any obligation, whatsoever.
Page 3
RECEIVING INFORMATION
Shipping damage MUST be reported to the carrier IMMEDIATELY.
Examine exterior.
Remove cover and examine compressor and piping for signs of damage.
Inspection
Check shipment against bill of lading.
Verify equipment received as ordered.
Verify unit:
• Unit size and type correct per submittal sheet and
job requirements?
• Louver color correct, if special color specifi ed?
• Control box located on correct side?
• factory installed on front, left or right side
models 09–18;
• fi eld modifi able to left or right model 24 only;
• front side only models 30–36.
• Voltage correct?
• Wall sleeve correct for unit, and correct depth?
[Available in depths for walls of 6½ inches
(165 mm) or deeper, in increments of ½ inch
(12.7 mm)]
• Electric heat correct capacity, if used?
• Hydronic coil included, if required? Piping located
as required?
General Information
Installation shall be completed by qualifi ed agency.
this manual and warranty for future reference.
Installer review this manual to verify unit has been
installed correctly. Run unit for one complete cycle to
verify proper function.
To obtain technical service or warranty assistance
during or after installation, contact your local
representative.
Visit our web site www.retroaire.com for local
representative listing.
For further assistance call 1-800-325-5479.
When calling for assistance, please have following
information ready:
Model Number_________________________
Serial Number_________________________
Date of installation______________________
Retain
Inspect each component for damage. Concealed
damage must be reported to carrier within 15 days
of receipt of shipment.
Carrier must make proper notation on delivery
receipt of all damage identifi ed and complete carrier
inspection report.
Purchaser must notify Manufacturer’s Service
department of all damage and is responsible for fi ling
any necessary claims with carrier.
Customer Service : (800) 228-9364
P/N 240006980, Rev. R [02/2013]3Made in USA
Page 4
ot
workin
Become Familiar With Symbols
Identifying Potential Hazards.
IMPORTANT SAFETY INFORMATION
!
All fi eld wiring shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States - National Electrical Code, ANSI/NFPA
70
• Canada - CSA C22.1 Canadian Electrical Code Part 1.
!
WARNING
Fire, and electrical shock hazard. Improper
installation could result in death or serious injury.
Read this manual and understand all requirements
before beginning installation.
Become Familiar With Symbols
Identifying Potential Hazards.
!
DANGER
Indicates a hazardous situation which, if not
avoided, WILL result in death or serious injury.
!
WARNING
Tampering with VPRC/VPRH is dangerous and could
result in serious injury or death. Do not modify or
change this unit.
Safety Information
• Installation by qualifi ed personnel.
• Turn off electrical supply before servicing unit.
• Inspect all parts for damage prior to installation and
start-up.
• Do not use unit if it has damaged wiring, is n
working properly, or has been damaged or dropped.
• Connect to properly grounded electrical supply with
proper voltage as stated on rating plate.
• Have proper over current protection (i.e. time- delay
fuse/HACR Breaker) as listed on Rating Plate.
• Connect unit to properly grounded electrical supply.
Do not fail to properly ground this unit.
• Tampering voids all warranties.
ot
!
WARNING
Indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
NOTICE
Indicates information which should be followed to
ensure proper installation and operation.
The Right Fit for Comfort4P/N 240006980, Rev. R [02/2013]
11 Fresh air shutter
12 Return air fi lter (see Table 19,
Page 40 for dimensions)
Wall sleeve,
10
custom for application
6
Wall sleeve,
custom for application
Front — 30, 36
3
7
6
Control panel, typical
09–24
3
9
1 Indoor coil (behind fi lter)
2 Outdoor coil
3 Control/power box
4 24-volt connection strip
5 Line voltage power
entrances
6 Drain stub location — ¾”
I.D. connection
7 Motorized fresh air
damper switch
8 Return air fi lter (see
Table 19, Page 40 for
dimensions)
Control panel, typical
30, 36
4
5
7
4
Rear — 18
2
5
10
Rear — 09, 12, 19, 24
2
Rear — 30, 36
The Right Fit for Comfort8P/N 240006980, Rev. R [02/2013]
Transition Kit #
55002100
Page 9
GENERAL PRODUCT INFORMATION
Product Description
• Microprocessor Control Board
• VPRC/VPRH 09–36 single package vertical air
conditioner (SPVAC) and heat pump (SPVHP).
• R-410A refrigerant.
• Custom wall sleeve and outdoor louver.
• Insulated top-discharge indoor compartment.
• VPRC/VPRH vertical discharge allows ducting to top of
room(s).
• VPRC/VPRH models can be applied in non-ducted return
air applications. VPRC/VPRH 30-36 can also be applied
in ducted return air applications.
• VPRH models are limited-range heat pumps. Heat pump
operation will cease at approximately 40°F (4.4°C)
outdoor temperature.
Standard Controls And Components:
• Ability to utilize single or 2-stage thermostat for
VPRH emergency heat.
• Front-mounted control box standard for 09–36
(right or left-side mounting available for 09–24
• Field-Installed Accessories:
only).
• Manual fresh air damper for models 09–24,
motorized fresh air damper for models 30–36.
• Disposable return air fi lter for models 09–24.
Washable, reusable return air fi lter for models
30–36 only.
• Thermostatic drain pan valve for heat pump
operation condensate removal (VPRH 09, 12,
19–24 only).
• Air Systems
– Models VPRC/VPRH 09, 12, 19 & 24 blow air
across outdoor coil, models VPRC/VPRH 18, 30
& 36 draw air through outdoor coil.
• Condensate Removal
– VPRC/VPRH 09, 12, 19 & 24 — Outdoor blower
incorporates condensate slinger ring. Base pans
are designed to accommodate fi eld-installed
drain stub kit if necessary. Drain stub kits are
dependent upon application. Environments with
higher humidity levels may require drain stub
kits.
– VPRC/VPRH 18, 30 & 36 requires internal drain
system. Models VPRC/VPRH 18 are supplied
standard with overfl ow drain stub kit for fi eld
installation.
– VPRC/VPRH 30-36 outdoor coil side drain stub
is integral to base pan, allows easy connection
of drain line.
APPLICATION LIMITATIONS
• Contact manufacturer if units will be operated in
– Random start timer prevents multiple units
from simultaneous start-ups.
– Fan purge — fan remains on for 60 seconds
after heat/cool call is satisfi ed
– Anti-short-cycle compressor protection
prevents compressor from rapid cycling
– Freeze protection — prevents evaporator coil
freeze up, improving compressor reliability
– Low ambient lockout prevents compressor
operation in outdoor temperatures less than
40°F (4.4°C)
– Test operation — all timers are temporarily
suppressed to allow ease of testing or
troubleshooting
– Control board LED provides self-diagnostic
troubleshooting codes (see Sequence of
Operation, page 24)
– Hydronic heat plenum (coil included on models
09–24 only).
– Remote wall thermostat (digital 1-stage or
2-stage available).
– Return air access panel - optional solid panel
available for application with separate air
intake.
– Models 09, 12, 19–24 only — Drain stub kit,
can be installed on front, right side or left side.
– Wall sleeve transition kit Model 30 only-
Needed when installing a VPRC/VPRH 30
in place of a VPAC/VPHP 30. See page 8.
[Transition Kit 550002100]
temperatures outside ranges listed below.
Table 4 Ambient Air Limitations
OUTDOOR [Ambient air temperature °F (°C)]
COOLINGHEATING
MinimumMaximumMaximum
Dry bulbDry bulbDry bulb
67 (19)115 (46)75 (24)
INDOOR [Ambient air temperature °F (°C)]
COOLINGHEATING
MinimumMaximumMin.Max.
Dry
bulb
67 (19) 57 (14) 90 (32) 72 (22) 50 (10) 80 (27)
Wet
bulb
Dry
bulb
Wet
bulb
Dry bulb
P/N 240006980, Rev. R [02/2013]9Made in USA
Page 10
CONTROL BOX LOCATION
Control Box Location
• VPRC/VPRH control box is factory mounted in front
position, unless otherwise specifi ed.
• Control box can be factory mounted for front, left or
right side applications on models 09–24.
• Control box is available only on front for models 30 and
36.
Figure 4 Optional Control Box Locations
Relocating Control Box
(Models 09, 12, 19, & 24) Field relocation of Control Box
must be done prior to installing unit.
1.
2.
3.
4.
5.
6.
Front-mounted
control box
(standard)
Optional control box
locations: right side or
left side (can be relocated
in the fi eld on models
09–12 and models
19–24)
7.
8.
9.
!
DANGER
Electrical shock hazard. Disconnect power to unit
before servicing or accessing control compartment.
Failure to do so will result in severe personal injury
or death.
Determine desired location.
Remove sheet metal panels from current control box
location, and desired control box location.
Remove control knock-out from panel.
Remove insulation directly behind knock-out.
Use metal tape to seal opening in panel where control
box was originally located.
Cut wire ties securing wire harness.
Remove mounting screws holding control box in place.
Relocate control box, and install mounting screws.
Use wire ties to bundle and secure wire harness.
!
DANGER
Electrical shock hazard. Verify wires do not contact
any sharp sheet metal edges, refrigeration tubing,
outdoor fan motor, or any moving parts. Failure to
do so will result in severe personal injury or death.
Figure 5 Front-Mounted Control Box
Only (Models 30 & 36)
Front-mounted
control box only
Motorized fresh
air damper switch
location
10.
Replace sheet metal panels.
The Right Fit for Comfort10P/N 240006980, Rev. R [02/2013]
Page 11
ENCLOSURE PREPARATION
Proper Clearances
• For proper air fl ow and sound levels minimum clearance
of 4 inches (102 mm) [models 09–18] or 6 inches, (152
mm) [models 24–36] between enclosure and chassis be
maintained (see Figure 6).
• For service, maintain minimum of 6 inches (152 mm)
on both sides and front for non-ducted return air
applications only.
• Ducted return air applications only require minimal
spacing for service requirements.
Figure 6 Minimum Clearances
Minimum clearances [inches (mm)]
ModelABC
09, 12, 18
19, 24, 30, 36
A = distance from left side of unit to interior wall
B = distance from right side of unit to interior wall
C = distance from front of unit to interior wall
4
(102mm)4 (102mm)4 (102mm)
6
(152mm)6 (152mm)6 (152mm)
Rough Openings
Access opening — allows unit insertion. Provide minimum
opening dimensions. (See Figure 21, Page 33, for
dimensions of opening when using optional return access
panel assembly.)
Table 5 Minimum Access Opening Dimensions
(Figure 6)
Model
09–12
18
19–24
30
36
Width
[inches (mm)]
Front
access
(front con-
trol panel)
26 1/8
(664)
26 1/8
(664)
26 1/8
(664)
28 9/16
(726)
28 9/16
(726)
Side access
(side con-
trol panel)
26 1/8
(664)
26 5/8
(676)
33 5/8
(854)
36 1/4
(921)
36 1/4
(921)
Height
[inches (mm)]
Without
hydronic
option
45 3/4
(1162)
45 3/4
(1162)
57 3/4
(1467)
58 3/4
(1492)
58 3/4
(1492)
hydronic
With
option
55 3/4
(1416)
55 3/4
(664)
69 3/4
(664)
N/A
N/A
NOTICE
Optional return air access panel assembly: Rough
opening to enclosure, and enclosure dimensions
must be sized to accept access panel door frame,
when used. See page 34 for details.
Wall sleeve rough opening — rough opening in wall
for wall sleeve and louver, must be correct dimension and
exact position necessary for installation.
See Figure 7, Page 12 and Figure 10, Page 15 for details of
platform and wall sleeve installation.
Platform height must make bottom of VPRC or VPRH
chassis fl ush with bottom inside edge of wall sleeve.
Platform surface must be ½ inch (13 mm) ABOVE bottom
of wall sleeve rough opening.
Platform dimensions above will allow chassis base pan to
align with bottom of wall sleeve.
Air fi lter
All models must have air fi lter installed prior to operation.
Use chassis-mounted air fi lter provided, unless using. For
optional return air access panel, remove and discard fi lter
from unit and install access panel with supplied fi lter in
place.
P/N 240006980, Rev. R [02/2013]11Made in USA
Page 12
000000
0
ENCLOSURE PREPARATION
Figure 7 Exploded View Of Typical Installation (Chassis shown is typical of models 09–24)
1
30/36 chassis
(models 09–24
shown at right)
610
10
1
9
2
5
4
7
3
6
9
The Right Fit for Comfort12P/N 240006980, Rev. R [02/2013]
8
Page 13
ENCLOSURE PREPARATION
Exploded View Of Typical Installation (Chassis shown is typical of models 09–24)
Access opening (for unit insertion/removal) — See unit dimensions in Figures 2, 3, 4, Pages 5-7.
See Table 6, page 11 for minimum recommended opening dimensions. Allow for extra height of
hydronic coil module, if used.
1
2
3
4
5
6
7
8
9
NOTE: Access opening will be in left or right side of enclosure for left or right-side-mounted
control panel units (available option on models 09–24 only).
See Figure 6, Page 11 for minimum clearances around unit to determine minimum enclosure
dimensions.
Wall sleeve opening to outside — See required dimensions in Table 7, Page 11.
Platform (see page 11) — See Figure 10, Page 15 for required platform height. Platform must be
level.
Wall sleeve (see page 14) — Wall sleeve must accommodate total wall thickness (from inside
surface of wall sleeve opening to surface of outside wall).
Outside louver- — Outside louver attaches to wall sleeve with nuts placed on louver studs.
VPRC/VPRH chassis.
Control panel. Access opening must be on same side of unit as control panel. Thermostat
connection terminal block located here
Optional return access panel assembly. See Figure 21, Page 33 for details and dimensions.
Return air opening — VPRC/VPRH requires air fi lter on return air. Filter is located on chassis open-
ing unless optional return air access panel is used (for these applications, air fi lter is removed
from chassis — fi lter is installed on access panel).
10
P/N 240006980, Rev. R [02/2013]13Made in USA
Hydronic coil option — See pages 35 to 37.
Page 14
WALL SLEEVE INSTALLATION
Verify Wall Sleeve Depth
Wall sleeve depth must be suitable for overall wall
thickness. (Figure 8).
Consult manufacturer for available wall sleeves.
• Minimum wall sleeve depth is 6½ inch (165 mm)
overall wall thickness, and available in ½-inch (13mm) increments for thicker walls.
• Wall thickness less than 6½ inches, wall sleeve will
penetrate into room, and will require interior framing
adaptations for proper fi t.
Verify Openings And Enclosure
• Verify access opening size, wall sleeve opening size and
enclosure size. See page 11.
• Verify wall sleeve opening is square by measuring
corner to corner. Also
• Verify platform (if used) is at correct height and is level
with wall sleeve opening. Adjust platform and framing
as necessary. If opening and platform are not square,
unit will not fi t properly to wall sleeve.
Assemble wall sleeve (09–24 only)
• Models 09–24 are supplied with tabbed-assembly wall
sleeve.
• Follow instructions supplied with wall sleeve to
assemble. Wall sleeve should look like that shown in
Figure 9.
Figure 8 Determining wall sleeve depth
Specify overall wall thickness when
ordering the wall sleeve — it will be
supplied to meet the required depth.
Overall wall
thickness
Foam gasket
1
1
X
/2
inch
/2
(13 X 13mm)
Outdoor louver
Drip edge will extend
outside exterior wall
when installed to
guide condensate
away from building
Lag Holes
(4 on each
side)
VPRC/VPRH Wall
Sleeve Assembly
Exterior
wall
Wall
sleeve
Cross Section of
Typical Wall
Interior
wall
Figure 9 Typical tabbed-assembly wall sleeve
(09–24)
Inside
• Wall sleeves for models 30–36 are factory assembled.
Secure the wall sleeve
• Slide wall sleeve into rough opening.
• Slide wall sleeve to one side of opening, preferably to
side that is most plumb.
• Secure wall sleeve to this side of opening using screws
through lag holes (see Figure 9), verify wall sleeve is
level. Fill any gaps between wall sleeve and opening
with shims to prevent distortion when screws are
tightened.
• Secure wall sleeve to other side in same manner. Verify
wall sleeve is both square and level before tightening
screws.
Lag holes
(4 on each side)
Chassis
studs
Outside View
The Right Fit for Comfort14P/N 240006980, Rev. R [02/2013]
Page 15
TYPICAL CHASSIS AND WALL SLEEVE, INSTALLATION
Figure 10 Typical VPRC/VPRH Installation, With Platform
Platform surface must be ½ inch (13 mm) ABOVE
bottom of wall sleeve rough opening.
*NOTE: If replacing model VPAC/VPHP 30 with VPRC/
VPRH 30 raise platform surface additional 3/8 in.
(10mm) to accommodate new wall sleeve.
To Install Outside Louver
• Install studs on inside of louver. Louvers will pass
through clearance holes in wall sleeve fl ange.
• Place outside louver in position.
• Secure louver by installing nuts (supplied) on studs.
P/N 240006980, Rev. R [02/2013]15Made in USA
Page 16
F
RONT-MOUNTED CONTROL PANEL - CHASSIS AND WALL SLEEVE, INSTALLATION
GENERAL INSTALLATION CONTINUED
Hydronic Coil (Optional)
Figure 11 Foam Gasket & Weather Angles (09–
Install hydronic coil option BEFORE placing chassis in wall
sleeve. See pages 35-37.
Inspect Foam Insulation
Verify foam insulation strips around condenser opening are
intact. Replace if necessary. Foam insulation must be in
place and in good condition to prevent air or water leakage
or air recirculation. See Figure 11 and Figure 12.
Attach Weather Angles
Using screws provided, attach weather angle to each side
of chassis as shown in Figures 11 and 12.
24) Front Control Panel Installations
Supply air connection
(return is in front)
Punch hole through
Back Panel
gasket at lag holes
Foam gasket
Insert Chassis Into Wall Sleeve
• Slide chassis into wall sleeve, verify studs on wall sleeve
slide through holes in back panel and weather angles.
• Attach ¼-20 nuts to studs that pass through weather
angles, each side of chassis.
• DO NOT attach nuts to studs that pass through back
panel of chassis. This would make removal diffi cult.
• Chassis must be fi rmly attached to wall sleeve to
prevent leakage or recirculation.
• See Figure 10, Page 15, for side view of typical
completed installation.
Plenum and Duct Work
1.
Install plenum and duct work to supply air connection,
all models.
2.
Install return air duct work, if applicable (VPRH/VPRC
30–36 only).
3.
For models 09–18, accessory 10-inch round duct collar
is available.
– 1: return air inlet with fi lter installed– 2: supply air outlet– 3: optional supply air duct collar, 10-inch
(254mm) round
Foam gaskets
(½ x ½ in)
Mounting holes
(each side only)
Weather angle
(one each side)
Punch holes in foam gaskets at locations of mounting holes
in back panel and weather angles (see call outs in Figure 13 and Figure 14).
Making it easier for wall sleeve studs to pass through holes
when chassis is slid into place.
Figure 12 Foam Gasket & Weather Angles
(30–36) Front Control Panel
Installations
Supply air
connection
(return is in
front)
Back Panel
3
2
1
The Right Fit for Comfort16P/N 240006980, Rev. R [02/2013]
Foam gasket
Weather angle
(one each
side)
Mounting
holes (each
side only)
Page 17
SIDE
-MOUNTED CONTROL PANEL - CHASSIS AND WALL SLEEVE, INSTALLATION
Inspect Foam Insulation
Figure 13 Foam Gasket & Weather Angles
• Verify foam insulation strips around condenser opening
are intact (see Figure 13 and 14). Replace if necessary.
• Foam insulation must be in place and in good condition
to prevent leakage or recirculation.
Insert Chassis Into Wall Sleeve
• Right-side-mounted control panel — remove right
side panel.
• Left-side-mounted control panel — remove left side
panel.
• Slide chassis into wall sleeve, verify studs on wall sleeve
slide through holes in back panel.
• Attach ¼-20 nuts to studs that pass through back
panel.
• Chassis must be fi rmly attached to wall sleeve to
prevent air or water leakage or air recirculation.
Attach Weather Angle
• Right-side-mounted control panel
Foam gasket
Foam gaskets
(½ x ½ in)
Mounting holes
(each side only)
Weather angle
(one each side)
A. Replace right side panel.
B. See Figure 13 for location of right-side weather
angle.
Figure 14 Foam Gasket & Weather Angles
C. Using screws provided, attach weather angle to
chassis. See Figure 14.
D. DO NOT install left-side weather angle.
E. Attach ¼-20 nuts to studs that pass through
weather angle.
• Left-side-mounted control panel
A. Replace left side panel.
B. See Figure 14 for location of right-side weather
angle.
C. Using screws provided, attach weather angle to
chassis. See Figure 14.
D. DO NOT install right-side weather angle.
E. Attach ¼-20 nuts to studs that pass through
weather angle.
• See Figure 9, Page 15, for side view of typical
completed installation.
Supply air
connection
(return is in front)
Punch hole through
gasket at lag holes
Back Panel
(09–24) Right-Side Control Panel
Installations
Right side
panel
Back panel
(09–24) Left-Side Control Panel
Installations
Supply air
connection
(return is in front)
Left side
panel
Punch hole through
gasket at lag holes
Foam gasket
Weather angle
(left side only)
Plenum And Duct Work
• Install plenum and duct work.
Punch holes in foam gaskets at locations of mounting
holes in back panel and weather angles (see call outs
in Figure 13 and 14).
Making it easier for wall sleeve studs to pass through
holes when chassis is slid into place
P/N 240006980, Rev. R [02/2013]17 Made in USA
Mounting holes in
weather angle
Foam
gasket
Page 18
CONDENSATE DRAIN
Condensate drain
1.
Models VPRC/VPRH 09,12,19, and 24 are designed
so condensate generated during cooling operation is
delivered to base pan, and picked up by outdoor fan’s
slinger ring.
2.
Condensate is slung onto outdoor coil where it
evaporates. Any excess condensate, or wind driven
rain that enters base pan will overfl ow through notches
located in rear of unit and run out wall sleeve, onto
drip edge, and out of building.
3.
Models VPRH 09,12,19, and 24 are also equipped with
thermostatic drain valve located on bottom of base
pan. Valve opens when outdoor temperatures reach
50°F (10°C), and allows any residual condensate or
wind driven rain in base pan to run out wall sleeve
as stated above. Protects outdoor fan from damage
during heat pump operation.
Figure 15 Drain Stub Location - Models 09–
24 (Optional On Models 09, 12, 19 And
24; Included And Required On Model
18)
4.
Accessory drain stub kit is available for models VPRC/
VPRH 09,12,19,and 24. Optional fi eld installed kit is
designed for use with building’s internal drain system,
and must be installed prior to operation. See Figure
15 for available stub locations on base pan, and
connection size. If unit is equipped with additional
drain stub in base-pan, connect drain stub to building’s
internal condensate removal system.
5.
Model VPRC/VPRH 18 is supplied with drain stub that
must be fi eld installed on unit, and connected to
building’s internal drain system prior to operation. See
Figure 15 for locations on base pan, and connection
size.
6.
Models VPRC/VPRH 30 and 36 are supplied with drain
stub that must be fi eld installed, and connected to
building’s internal drain system prior to operation. See
Figure 16 for location on base pan, and connection
size.
7.
Drain stub must be connected to internal condensate
removal system.
8.
Use of internal condensate drain stub requires
connection to be lower than base pan weep holes,
located near bottom of condenser coil.
Figure 16 Drain Stub Location (Models 30–36)
¾” ID tube connection — front of drain pan
Movable drain stub, ½” ID tube connection may be
located on front, right or left side of unit.
Swap gasketed drain stub plate with blanking plate to
relocate to alternate location.
The Right Fit for Comfort18P/N 240006980, Rev. R [02/2013]
Page 19
ELECTRICAL CONNECTIONS
Electrical Connections
!
WARNING
Electrical shock hazard. Disconnect all power
before removing chassis, performing any cleaning,
servicing, or maintenance. Failure to do so could
result in death or serious injury.
Refer to wiring diagram attached to unit for wiring details.
All fi eld wiring shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States
• National Electrical Code, ANSI/NFPA 70
• Canada
• CSA C22.1 Canadian Electrical Code Part 1.
• Check VPRC/VPRH ratings.
• Installer is responsible for ensuring VPRC/VPRH units
are installed in accordance with all applicable national
and local codes.
• Check rating plate for circuit ampacity.
• Size breaker(s) or fuse size(s) accordingly.
A. Use only HACR type breakers or time delay fuses.
B. Select proper wire for breaker or fuse size used.
C. Some units require more than one power supply.
D. If plug and receptacle are used, check for proper
fi t.
E. Check nameplate and wiring diagram for further
instructions and wire connections.
F. Each unit is equipped for 24v wall thermostat
connection.
Power Cord With Integral Safety Protection
All VPRC/VPRH units that are cord connected to power
supply are equipped with power cord with integral sensor:
• Provides personal shock protection.
• Provides arcing and fi re prevention.
• Senses any damage in line cord and disconnects
power before fi re can occur.
Tested in accordance with Underwriters Laboratories, cord
set also offers unique “passive” operation, unit does not
require resetting if main power is interrupted.
Disconnect Switch (
Disconnect switch ensures all power to control box is
disconnected for servicing, resetting if main power is
interrupted.
• Each power cord must be tested before use. Follow test
instructions in order listed on plug of power supply cord.
• DO NOT use product if power supply cord fails test.
• DO NOT attempt to repair damaged power supply cord.
Replace with new cord from manufacturer only.
Choosing Thermostat
Manufacturer offers choice of single-stage or two-stage
mercury-free thermostat compatible with all models of
VPRC/VPRH. (Use two-stage thermostat for VPRH units
equipped with electric heat option.)
• RetroAire™ thermostats have digital readout with
temperature control range from 45°F (7°C) to 90°F
(32°C).
• When using fi eld sourced thermostat use ONLY 24v
heat/cool thermostat.
Optional)
NOTICE
Cooling-Only With Electric Or Hydronic Heat
only)
VPRC/VPRH units are wired for 230v primary voltage
from manufacturer. Transformer must be rewired by
installer if job site voltage is 208v.
P/N 240006980, Rev. R [02/2013]19Made in USA
• Select thermostat compatible with cooling/electric heat
system.
• Thermostat should have “R”, “Y”, “W” and “G”
terminals.
(VPRC
Page 20
ELECTRICAL CONNECTIONS
Heat Pump With Electric Heat (VPRH only)
Single-Stage Thermostat
Select thermostat compatible with cooling/single stage
heat/heat pump system.
• Thermostat should have “R”, “Y”, “O” and “G” terminals.
RetroAire™ units are single stage heating only.
• Electric heat and heat pump will not operate
simultaneously.
Two-Stage Thermostat
Two-stage heat pump thermostat can be used with VPRH
units.
• See wiring diagram for connections.
• VPRH units are designed to operate as single stage heat
pumps — will alternate between heat pump and electric
heat to meet heat demand.
Thermostat Wiring
The Right Fit for Comfort20P/N 240006980, Rev. R [02/2013]
Page 21
!
FINAL INSPECTION AND START-UP
!
CAUTION
Moving parts can cause injury. Use caution when
testing unit. Failure to do so could result in minor or
moderate injury.
1.
Do not operate unit without fi lter in place or use as
temporary heating/cooling source during construction.
2.
Plug in line cord, if supplied, or hard wire line voltage
power to the unit. Refer to unit rating plate for proper
voltage and amperage/fuse size.
3.
Unit may require two power supplies (check nameplate
and wiring diagram for further instructions.)
4.
Connect low voltage wires from thermostat to unit.
Follow wire diagram for details.
5.
Turn power on and check for proper operation.
Before Operating This Unit:
☐ Read and understand this manual.☐ Verify electrical supply matches electrical require-
ments of unit, and unit is properly grounded.
☐ Examine control box. Verify all wire connections are
secure, and control board jumpers are in proper
positions. See Page 28.
☐ Verify indoor blower wheels and outdoor fan blades
are secured to their motor shafts.
☐ Ensure all sheet metal panels are in place and se-
cure.
☐ Verify drain stub, if used, is secure to base pan, and
condensate drain is functioning properly.
☐ Verify chassis is properly fi tted to wall sleeve, and
securely mounted to surrounding framing.
Cooling
5.
Set wall thermostat to cool mode. Set thermostat
below room temperature setting.
6.
After few minutes of operation, cool air should
discharge from grilles.
7.
Thermostat can be set at desired setting with selector
switch in heat or cool position.
8.
Verify unit is level.
9.
Check condensate removal by pouring water into base
pan, put unit in cooling mode, with condenser fan
running, see if water is picked up by slinger ring and
thrown onto outdoor coil. (Models VPRC/VPRH 09–24
only)
10.
If condensate is routed to internal drain, verify drain is
functioning properly.
11.
Verify there is nothing interfering with room discharge
air or return air.
Manual Fresh Air Shutter
Manual fresh air shutter allows user to move fresh air into
space to be conditioned. Damper handle is located below
indoor coil on service panel (models 09–24 Only).
Motorized Fresh Air Damper
Motorized damper is used on models 30–36. Damper
operating switch is located on control box. See Figure 5,
Page 10.
Heating
1.
Set wall thermostat to heat mode.
2.
Set thermostat above room setting.
3.
After few minutes of operation, warm air should
discharge from grilles.
4.
Do not operate unit when panels are removed.
P/N 240006980, Rev. R [02/2013]21Made in USA
Page 22
FINAL INSPECTION & START-UP
General
Installation and wiring shall be in accordance with
requirements of authority having jurisdiction In absence of
such requirements refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1:
Safety Standard for Electrical Installations.
Units Rated 208/230V:
• RetroAire unit is wired for 230v primary voltage from
manufacturer.
• Transformer must be rewired by installer if job site
voltage is 208v.
• Change transformer tap from orange to red. See wiring
diagram for details.
Setting Control Board Jumpers
Control board has two sets of factory installed jumper pins
on control board, HP jumper and TEST jumper.
HP Jumper — selects heat pump or straight cooling.
Pins determine whether unit operates as straight cooling or
as heat pump. See Figures 17 and 19.
• Jumper right pin to center pin for heat pump operation.
• Jumper left pin to center pin for straight cooling
operation.
Figure 18 TEST jumper (selects normal or
TEST Jumper
— selects normal or test mode
Figure 17 HP Jumper (selects heat pump or
straight cooling)
Heat Pump Mode
(Jumper center
& Bottom pins)
HP
Straight
Cool Mode
(Jumper center
& Top pins)
HP
test mode)
NOTICE
Do not leave unit operating with TEST jumper in
TEST position.
• Jumper is for testing only. See Figure 18 and 19.
• When jumper pins are jumped together, all timers are
• May be used for fi eld testing. Units are factory set with
jumper on only one pin (normal operation position).
Normal operation
(pins not jumped)
Test mode
(pins jumped)
The Right Fit for Comfort22P/N 240006980, Rev. R [02/2013]
Page 23
FINAL INSPECTION & START-UP
Figure 19 Circuit Board
TEST JUMPER
HEAT PUMP
JUMPER
P/N 240006980, Rev. R [02/2013]23Made in USA
Page 24
SEQUENCE OF OPERATION
Initial Power-Up Or Power Restoration
When power is applied, either for fi rst time or after power
failure, board will initialize.
• During initialization, LED1 will be lit continuously for
approximately 5 seconds.
• Following initialization, random-start timer is initiated.
This timer adds randomly selected 5-120 seconds to
start-up sequence, reducing possibility of multiple units
starting at same time.
• Once random start timer has expired, 180-second antishort-cycle timer is initiated. LED1 blinks two-fl ash
code. (Anti-short-cycle timer prevents compressor
from rapid cycling.)
• After the anti-short-cycle timer expires, LED1 blinks a
one-blink code, indicating normal operation.
Figure 20 Indicator LED1
LED1
Cooling Operation
• If room temperature is above thermostat setting,
reversing valve (VPRH only) will be energized.
• Compressor and outdoor fan will start provided AntiShort Cycle Timer has timed out from initial power-up,
power restoration or previous compressor on cycle.
• Operation will continue until room temperature
satisfi es thermostat. Once room temperature falls
below set point by 3 ºF (2 ºC), compressor, outdoor
fan motor and reversing valve (VPRH only) will deenergize.
• As soon as compressor is de-energized, anti-shortcycle timer will be initialized and prevent compressor
from starting again for another 180 seconds.
• While anti-short-cycle timer is active, LED1 is set to
blink two-fl ash code.
• After anti-short-cycle timer expires, LED1 is set to
blink one-blink code, indicating normal operation.
Mechanical Heating (VPRH only)
• If outdoor coil temperature remains above 25°F
(-4°C), compressor and outdoor fan will start provided
anti-short-cycle timer has timed out from initial powerup, power restoration or previous compressor on
cycle. Operation will continue until room temperature
satisfi es thermostat.
• Once room temperature rises above set point by 3 °F
(2°C), compressor and outdoor fan motor will deenergize.
• As soon as compressor is de-energized, antishort-cycle timer will be initialized and will prevent
compressor from starting again for another 180
seconds. While anti-short-cycle timer is active, LED1
blinks two-fl ash code. After anti-short-cycle timer
expires, LED1 fl ashes one-blink code, indicating
normal operation.
Auxiliary Heating
• If outdoor coil temperature falls to 25°F (-4°C) or
Fan Operation
Some thermostats are equipped with auto/on fan switch.
• When switch is placed in on position indoor fan will run
continuous.
• When switch is in auto position indoor fan will cycle
with call for heating or cooling.
• Fan purge (auto mode only) — after room thermostat
has been satisfi ed, purge feature allows indoor fan
to remain on for additional 60 seconds. Increases
effi ciency by pulling remaining energy from unit.
The Right Fit for Comfort24P/N 240006980, Rev. R [02/2013]
below for 180 seconds during heating call, compressor
and outdoor fan motor will be de-energized and
auxiliary heat will be energized.
• Anti-short-cycle timer will be initiated, prohibiting
compressor operation for 180 seconds.
• LED1 will fl ash three-blink code, indicating auxiliary
heat operation. Heating operation with auxiliary heat
will continue until outdoor coil sensor reaches 50°F
(10°C).
Hydronic Heating
• With call for heat, signal from processor board will
activate water or steam valve and indoor fan.
• Signal to water or steam valve will continue until room
temperature rises above set point by 3°F (2°C).
Page 25
MAINTENANCE
!
WARNING
Electrical shock hazard. Disconnect power to
VPRC/VPRH before servicing or accessing control
compartment. Failure to do so could result in severe
personal injury or death.
NOTICE
Perform regular service and maintenance by
qualifi ed service agency at least once every 12
months to assure safe, trouble free operation and
maximum effi ciency .
NOTICE
Verify proper operation after servicing.
Maintenance Schedule
Manufacturer recommends performing following
inspections and maintenance on monthly basis. Units
installed in harsh or dirty environments will require more
frequent inspections and maintenance.
Disconnect power to unit and remove necessary access
panels:
☐ Clean or replace indoor air fi lter.☐ Inspect chassis interior for rodent or insect
infestation. Clean if necessary.
☐ Clean & fl ush condensate drain pan and chassis
base pan.
Repair if necessary.
Seasonal Start-Up And Maintenance
Beginning of cooling and heating seasons, complete
mechanical check should be performed and maintenance/
inspections performed as described below.
Disconnect power to unit and remove necessary access
panels:
1.
Remove access panel. Visually inspect equipment.
Look for obvious changes in unit such as damaged coils
or evidence of extended wear on any moving parts.
2.
Check for unusual odors or leaks (examples: burnt
motor windings, water, or refrigerant). Verify base pan
is clean.
3.
Clean or replace return air fi lter as needed. Allowing
dust to collect on fi lter. Check fi lter at least once
month. Some environments may require more frequent
replacement, depending on particulate in air stream.
4.
Inspect all electrical connections for frayed wires and
poor connections.
5.
Check fan motors and blower assemblies. Verify screws
and motor mounting hardware are tight.
6.
Centrifugal fan blades and blower cage brush and/or
vacuum as necessary.
7.
Inspect both indoor and outdoor coils. Use fi n comb to
straighten out any damaged fi ns.
NOTICE
Do not use solvent based cleaner to clean coils,
some solvents will produce noxious odor when unit
is in operation.
☐ If applicable, verify condensate drain is functioning
properly.
☐ Inspect refrigeration tubing, especially braze joints,
for signs of refrigerant leaks (oil residue). Repair
if necessary.
☐ Inspect indoor and outdoor coils. Verify dirt or debris
have not collected on fi ns. Clean if necessary . T ake
care not to damage coil fi ns when cleaning. Use fi n
comb to straighten any bent fi ns.
☐ Examine control box. Verify all wire connections are
secure.
☐ Verify indoor blower wheels and outdoor fan blades
are secured to their motor shafts.
☐ Verify dirt or debris have not collected on indoor
blower wheels and outdoor fan blades. Use vacuum
and soft brush to clean if necessary.
☐ Verify any ductwork connected to unit is secure and
free of air leaks.
☐ If unit has hydronic option installed, inspect piping,
especially braze joints, for signs of water leaks.
8.
Look for oil leaks or stains on or around all braze joints
and refrigerant lines. Presence of oil here indicates
potentially serious problem (such as refrigerant leak).
9.
Inspect and clean drain pan and drain line(s). Use of
anti-fungicide tablet to keep condensate system free
from bacterial contaminants is recommended.
10.
Verify unit is level for proper operation. Building and
equipment may settle, causing shift in direction of
condensate fl ow. (Note that bottom of wall sleeve is
pitched downward to shed water to outside. Verify any
shifting does not interfere with proper drainage.)
11.
Verify weep holes along rear fl ange of base pan are
free of debris.
12.
Verify seal around unit is not broken or damaged.
13.
Air leaks may make the conditioned area
uncomfortably drafty or produce noises. Visually
inspect foam gasket between wall and unit, taking
note of separation between air inlet for condenser
and condenser coil discharge. These two areas must
be sealed off from each other. If you experience poor
cooling operation or erratic operation, check for air
recirculation at condenser coil.
14.
Replace access panels and reconnect electrical power.
P/N 240006980, Rev. R [02/2013]25Made in USA
Page 26
TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Disconnect power to unit
before servicing or accessing control compartment.
Failure to do so could result in severe personal
injury or death.
SymptomSuggestion
No heat or cooling• Check to see if unit has power and if thermostat is satisfi ed. If
thermostat is not satisfi ed, call your installing contractor or service
contractor.
Thermostat calls for cooling,
but cool air is not coming out of
unit.
Light on circuit board is
blinking.
Circuit board light is blinking 3
or 4 times, but there is no freeze
condition.
Thermostat is satisfi ed, but fan
is still running.
Thermostat calls for heat, but no
heat comes out of unit.
Thermostat calls for heat while in
heat pump mode, but heated air
is not coming out of unit.
• Check for continuity between thermostat and unit. Verify 24V ac is present
across terminals C and R.
• Verify high pressure switch located in outdoor section has not been tripped.
If tripped, press switch button to restart compressor.
• Some units are equipped with LCDI (Leakage current detection interrupt)
line cord. Verify this line cord is reset by pressing reset button at line
cord plug.
• Note: If evaporator fan is operational and all of above suggested
procedures have been followed, and there is still no cooling being supplied
by unit, contact trained heating and cooling professional.
• Circuit board uses light for diagnostic purposes. Blinking codes are as
follows:
– 1 blink = normal operation– 2 blinks = compressor lockout (ASCT — Anti-short cycle timer)– 3 blinks = outdoor freeze condition– 4 blinks = indoor freeze condition– 5 blinks = simultaneous Y and W call (Straight cool units only)
• Verify sensors have not been damaged. R emove sensor wires from control
board and make resistance measurements, compare to following sensor
resistances. Indoor and outdoor coil sensor wires are labelled, as is control
board.
• If thermostat is set to auto mode, once thermostat is satisfi ed, fan will
stay energized for extra 60 seconds to purge unit of excess cool or warm
air in plenum.
• If thermostat fan switch is set to ON, fan will stay energized regardless
of whether thermostat is satisfi ed or not. Only way to turn fan off is to
turn unit off or turn thermostat fan switch to AUTO.
• Units equipped with electric heaters have temperature limit switch to
prevent electric heater from reaching unsafe temperatures. If after calling
for heating, heater is not energized, check for continuity across limit. If
limit is open, replace if with equivalent limit switch.
• Verify unit has power or thermostat has been satisfi ed. If unit has power
and thermostat is satisfi ed, turn thermostat few degrees above room
temperature.
• Verify LCDI line cord has not tripped. (See Page 19.)
• While in heat pump mode, verify thermostat is not energizing O terminal.
Retroaire units are designed to work in heat pump mode when 24vac
is present across Y and C. Verify heat pump jumper on control board
is jumping two pins labeled “HP” (see control board jumper locations,
Figure 17, Page 22).
• Verify there are no freeze conditions. Refer to blinking codes question
above for more information.
Have qualifi ed technician conduct troubleshooting
procedures.
NOTICE
The Right Fit for Comfort26P/N 240006980, Rev. R [02/2013]
Page 27
TROUBLESHOOTING
Indoor Motor Speed Tap Selection
• For information on indoor motor speed tap selection,
please refer to “Indoor Motor Speed Tap Selection
Chart” label attached to chassis of VPRC/VPRH
(Table 8).
• Models’ VPRC/VPRH 09–36 motors are factory-wired
for corresponding units as described in 230V column
Table 8.
• Make speed tap changes as required by job site
voltage and/or external static pressure (ESP).
• Speed tap changes may need to be changed from
manufacturer settings. Manufacturer will not be liable
for any system problems that could arise if motor
speed is not changed to match application.
Table 7 VPRC/VPRH Indoor motor speed tap
selection chart
Model
09
12
18, 19,
24
30
36
Tap Key — Red (Low) — Blu (Med) — Blk (High)
ESP
In. w.c. (mm
w.c.)
0.1 (3)
0.2 (5)
0.3 (8)Blu
0.1 (3)
0.2 (5)
0.3 (8)Blk
0.1 (3)
0.3 (8)
0.1 (3)
0.2 (5)
0.3 (8)
0.1 (3)
0.3 (8)
230V208V197V
Red
Blu
BlkBlkBlk0.2 (5)
BluBlu
BlkBlkBlk0.2 (5)
Red
Blu
Red
Blu
Blu
Blk
Blu
Blk
P/N 240006980, Rev. R [02/2013]27Made in USA
Page 28
ELECTRICAL SPECIFICATIONS
Table 9 Legend For Electrical Specifi cations
FLA
H-WIRE
HA
Hp
Htr #
IFM
LRA
Max
MCA
Full Load Amps
Hard Wired
Heater Amps
Horse Power
Heater Option Number (see Figure 1)
Indoor Fan Motor
Locked Rotor Amps
Maximum
Maximum Circuit Ampacity
Min
MOCP
OFM
RLA
TCA
THA
Volt
W
Minimum
Maximum Over current Protection Device
Amps
(HACR-type breakers or time-delay fuses)
Outdoor Fan Motor
Rated Load Amps
Total Cooling Amps
Total Heating Amps
Voltage
Watts
Table 8 NEMA Specifi cations Non-Locking/Receptacles
The Right Fit for Comfort28P/N 240006980, Rev. R [02/2013]
* — Where two values are shown, data is displayed as Circuit 1 / Circuit 2
21.330
* THA value applies to hydronic heat only, Htr #8.
45
H-WIRE
The Right Fit for Comfort32P/N 240006980, Rev. R [02/2013]
Page 33
OPTIONAL - RETURN AIR ACCESS PANEL
Optional Return Air Access Panel (With
Filter)
• Verify installation will provide adequate clearance and
access to control panel.
• Work closely with other trades to locate opening for
NOTICE
Install air fi lter installed prior to operation.
return air access panel.
• Return air access panel must be installed with enough
room available to remove unit if necessary.
• Install frame with screws through lag holes into frame
studs, level and plumb (Figure 21).
• Return air access panel is set onto frame, and held in
place with 6 screws.
Figure 21 Return Air Access Panel (Available with solid doors if ducted return air is used;
available in standard white or consult manufacturer for custom colors)
Return air access panel part numbers
(includes items 2, 5 and 6 below)
09–18 Part # 240003010C
19–24 Part # 240003013C
30–36 Part # 240004439C
Table 17 Return Air Access Panel Dimensions — Inches (mm)
ModelABCDEFGHJKItemDescription
Solid door panel (for ducted return air installations)
1
2
Door assembly, front view
Door assembly, rear view
3
4
Filter bracket (on back)
09–18 Std.
19–24 Std.
29 3/4
(756)28(711)
29 3/4
(756)
28
(711)
49 3/4
(1264)30(762)
61 3/4
(1569)
30
(762)
17 3/4
(451)
28
(711)
20 1/4
(514)
20 1/4
(514)
20
(508)
30
(762)
20
(508)50(1270)
20
62
(508)
(1518)
477/8
(1220)
597/8
(1518)
(O.D.)
Frame assembly (items 5a are lag holes, 3 per side)
5
6
Filter
30–36 Std.
35 7/8
(911)
341/8
(864)
62
(1575)
36 7/8
(918)
17 5/8
(448)
33
9
/16
(852)
30
(762)
20
(508)
62
3/16
60
(1524)
P/N 240006980, Rev. R [02/2013]33Made in USA
Page 34
OPTIONAL - HYDRONIC COIL
HH Series Hydronic Coil Option
7.
(Available for VPRC / VPRH models 09-24 only)
Install Hydronic Coil option to unit BEFORE placing chassis
8.
in wall sleeve.
1.
Coil package includes sheet metal enclosure.
2.
2- or 3-way motorized 24v water valve is available
(models 09–24 only).
3.
Verify hydronic coil package is left, right or front
System duct work is connected to discharge opening on
duct collar or plenum. Flex collar is advised.
aligned, matching control section alignment of unit on
which it is to be installed.
4.
Coil package must be centered on top of VPRC/VPRH
chassis. Verify it is centered over fan discharge and
piping package is in correct position.
5.
Two “Z” mounting brackets are used to clamp hydronic
enclosure to chassis top. Mount brackets to chassis top
using holes provided. Allows chassis to be removed for
service/maintenance without disturbing hydronic package.
6.
Complete piping of hydronic package, including fi eld
supplied shut off valves and other fi eld supplied items.
Install threaded rods through slots in brackets (Figure
23), place washer and nut on threaded rod, tighten
nut. Secure upper end of threaded rod to angle iron or
2 x 4 inch (51 x 102 mm) wood.
Verify rods do not interfere with chassis plenum or
duct work. Rods hold the hydronic package in place
when chassis is removed for maintenance.
Figure 22 Hydronic Coil Dimensions
Dimensions — Inches (mm)
ModelsABCC1DEFGHJK
9–18
13
(330)8(203)19(483)17(432)
10
(254)
Diameter
18
(457)9(229)
½
(13)
10
(254)5(127)1½(38)
19–24
17
(432)12(305)23(533)21(533)
10
(254)
Diameter
22
(559)11(279)
½
(13)
13
(330)6½(165)1½(38)
The Right Fit for Comfort34P/N 240006980, Rev. R [02/2013]
Head loss data above is for hydronic coil only. The optional motorized 3-way valve has a Cv of 4.0; the optional
AutoFlow valves have a Cv of 7.0 at full open.
• Existing Carrier wall sleeve can be retained in all
applications, provided VPRC/VPRH unit is installed as
required for 50QT/ET option.
• Condenser louver must be modifi ed or replaced unless
it is aluminum vertical-bar type with no plastic or
metal block-off as shown in Figure 25. Two other
louver types are used on Carrier units.
• If you have aluminum vertical bar type louver with
metal or plastic block-off (Figure 26), remove block-off
for louver to function with VPRC/VPRH or use louver
provided with VPRC/VPRH.
• If louver is stamped sheet metal (Figure 27), it must
be removed and replaced with standard VPRC/VPRH
louver provided with unit or warranty will be voided.
Modify the louver application as needed for proper fi t
and function of VPRC/VPRH.
Installing VPRC/VPHC Into An Existing
Wall Sleeve/Enclosure
• Replacing another manufacturer’s unit with VPRC/
VPRH chassis requires certain modifi cations due to unit
installation into existing wall sleeve and enclosure.
• Installer is responsible for proper installation practices
when installing VPRC/VPRH in existing wall sleeve/
enclosure.
• Manufacturer will not be responsible for installation
when accessories not included in supplied installation
package are used.
!
DANGER
Electrical shock hazard — Verify power to existing
unit (Carrier 50QT/ET) is disconnected before
removing. Failure to do so will result in severe
personal injury or death.
Figure 25 Aluminum Vertical Bar Louver
Without Block-Off, Can Be Used
With The VPRC/VPRH as is
Figure 26 Aluminum Vertical Bar Louver
With Block-Off, Block-Off Must Be
Removed To Use With VPRC/VPRH
Removing the metal or
plastic block-off usually
only requires drilling
out a few pop rivets
and is generally an
easy task.
Figure 27 Stamped Metal Louver
Cannot Be Used With The VPRC/
VPRH — Use Standard Louver
Shipped With VPRC/VPRH,
Adapting Installation As Needed
For Fit And Function
For proper installation into existing wall sleeve/enclosure,
complete following steps as listed.
1.
Remove existing Carrier 50QT/ET unit from wall
sleeve.
2.
Inspect wall sleeve. Verify it is free of dirt or debris
and is in good condition. If condition is beyond repair,
it must be replaced.
NOTICE
Carrier series use internal drain system. Verify
existing drain system is in working condition and
able to move condensate freely.
Attach three baffl es included in chassis kit to back of
condenser coil. See Figure 29.
VPRC/VPRH Model 18
1.
Installer must fabricate and install air diverter to
separate inlet and discharge outdoor air.
2.
Diverter must extend to condenser louvers. Failure to
do so will create air recirculation between condenser
discharge and intake creating compressor failure due
to continued operation at high pressures, as well as
decreasing unit’s capacity and effi ciency from rated
values.
Models 09–18
3.
Install provided drain stub on unit’s base at front. See
Figure 14, Page 18. Do not mount drain stub on side,
unit inserts too deeply into Carrier wall sleeve. (If this
location is not acceptable, contact manufacturer for
alternatives.) Connect drain stub to suitable drain.
4.
Insert VPRC/VPRH chassis 13 inches (330 mm) into
wall sleeve. Verify it is level. When unit is in position,
fasten in place permanently by mechanical means.
Shimming chassis into position (i.e., by using wooden
platform). If unit is completely removed, re-level to
ensure proper condensate drainage.
5.
Verify seal is air tight between chassis and existing
wall sleeve around condenser section. Manufacturer
recommends using expandable foam or closed cell
foam to create seal, preventing air bypass around
chassis adversely affecting effi ciency, operation, and
reliability of unit. Seal also prevents inclement weather
from entering wall sleeve/interior of building.
6.
Install high and low voltage wiring to VPRC/VPRH unit.
Refer to wiring diagram on the for wire connections.
7.
Connect supply air ductwork to VPRC/VPRH unit.
8.
Turn power on to unit.
9.
Confi rm operation by cycling unit several times, verify
operation.
10.
Replace all trim and components.
NOTICE
Level chassis so condensate or wind-driven
rain will fl ow from base pan. Installer, test and
confi rm condensate fl ow into drain. Manufacturer
recommends pouring water into base pan prior to
operating unit to verify drain is operating properly.
Figure 28 Model 18 Add Diverter Extension
Add extension from separator
baffl e to outside louver.
Use foam gaskets or other means
to ensure tight seal. Required to
prevent outdoor air recirculation
inside existing wall sleeve.
Figure 29 Baffl es On Back Of Condenser Coil
Top Baffl e
Left
Baffl e
The Right Fit for Comfort38P/N 240006980, Rev. R [02/2013]
Right
Baffl e
Condenser Coil
Page 39
OPERATIONAL PERFORMANCE DATA
Table 18 VPRC/VPRH 09–36 Performance Data
INSTALLATION FOR NEW CONSTRUCTION
Model
Cooling
Btuh (kW)
Sensible
Heat
Ratio
EER
Heat Pump
Btuh (kW)
COP
Air Flow vs External Static Pres-
0.10 in.
w.c.
(2.5 mm
w.c.)
sure
Static Pressure
0.20 in.
w.c.
(5.1 mm
w.c.)
0.30 in.
(7.6 mm
w.c.)
w.c.
Fresh
Air
Inlet
Flow
Outdoor
Sound
Level
VPRC09
VPRH09
VPRC12
VPRH12
VPRC18
VPRH18
VPRC19
VPRH19
9,000
(2.64)
9,000
(2.64)
12,000
(3.51)
12,000
(3.51)
17,200
(5.04)
17,200
(5.04)
18,400
(5.39)
18,400
(5.39)
CFM (L/s) CFM (L/s)CFM (L/s)
0.759.0N/AN/A330 (156)300 (142)250 (118)
0.759.09,000 (2.64)3.0330 (156)300 (142)250 (118)
0.709.0N/AN/A440 (208)385 (182)350 (165)
0.709.0
0.719.0N/AN/A600 (283)550 (260)500 (236)
0.719.0
0.739.0N/AN/A710 (335)650 (307)600 (283)
0.739.0
11,400
(3.34)
16,200
(4.75)
16,400
(4.81)
3.0440 (208)385 (182)350 (165)
3.0600 (283)550 (260)500 (236)
3.0710 (335)650 (307)600 (283)
CFM
(L/s)
3065
3575
4071
5069
dBa
VPRC24
VPRH24
VPRC30
VPRH30
VPRC36
VPRH36
P/N 240006980, Rev. R [02/2013]39Made in USA
23,200
(6.80)
23,200
(6.80)
31,600
(9.26)
31,600
(9.26)
35,600
(10.43)
35,600
(10.43)
0.739.0N/AN/A710 (335)650 (307)600 (283)
0.739.0
0.699.0N/AN/A
0.699.0
0.73 9.0 N/A N/A
0.739.0
21,600
(6.33)
32,000
(9.38)
36,000
(10.55)
3.0710 (335)650 (307)600 (283)
3.0
3.0
1,190
(562)
1,190
(562)
1,350
(637)
1,350
(637)
1,170
(552)
1,170
(552)
1,290
(609)
1,290
(609)
1,130 (533)
1,130 (533)
1,210 (571)
1,210 (571)
6070
9569
9569
Page 40
START-UP REPORT
In order for Technical Service to better serve you, please
complete the following information.
Include Model Number, Serial Number, and Date of
installation. Have this information ready when calling.
Technical Support Department: (800) 228-9364
Model NumberDate:
Technician:
Serial NumberMode:Cooling
Indoor SectionNotes
Evaporator Entering Air – DB
Evaporator Entering Air – WB
Evaporator Leaving Air – DB
Evaporator Leaving Air – WB
Outdoor Section
Entering Air
Leaving Air
Temperature Split
Power Input
Compressor – Volts
Compressor – Amps
OD Fan Motor – Volts
OD Fan Motor – Amps
ID Fan Motor – Volts
ID Fan Motor – Amps
Total Volts
Total Amps
Temperatures – Degrees F°
Compressor Suction
Compressor Discharge
Liquid Out Cond.
Liquid before Expansion
Suction out Evaporator
Capacity Calculations
DB – Temp Split at evap.
Test Summary
Compressor Superheat
Sub Cooling
The Right Fit for Comfort40P/N 240006980, Rev. R [02/2013]
Page 41
NOTES
P/N 240006980, Rev. R [02/2013]41Made in USA
Page 42
NOTES
The Right Fit for Comfort42P/N 240006980, Rev. R [02/2013]
Page 43
NOTES
P/N 240006980, Rev. R [02/2013]43Made in USA
Page 44
ECR International Inc
2201 Dwyer Avenue
Utica, NY 13501
e-mail: info@RetroAire.com
An ISO 9001-2008 Certifi ed Company
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.