Retro Aire VPRC09, VPRH09, VPRC12, VPRH12, VPRH18 Installation, Operation & Maintenance Manual

...
Page 1
Sing
e Right Fit for Comfort
VPRC / VPRH
Single Package Vertical Air Conditioner/Heat Pump
le Package Vertical Air Conditioner/Heat Pum
Installation,
Operation &
Maintenance Manual
ECR International Inc
2201 Dwyer Avenue
Utica, NY 13501
An ISO 9001-2008 Certifi ed Company
P/N 240006980, Rev. R [02/19/2013]
Page 2
TABLE OF CONTENTS
Receiving Information ................................................................................................... 3
Important Safety Information ......................................................................................... 4
Dimensional/Physical Data ............................................................................................. 5
Components ................................................................................................................ 8
General Product Information .......................................................................................... 9
Control Box Location ....................................................................................................10
Enclosure Preparation ..................................................................................................12
Wall Sleeve Installation ................................................................................................14
Typical Chassis And Wall Sleeve, Installation ...................................................................15
F
ront-Mounted Control Panel - Chassis And Wall Sleeve, Installation ..................................16
Side
-Mounted Control Panel - Chassis And Wall Sleeve, Installation ...................................17
Condensate Drain ........................................................................................................18
Electrical Connections ..................................................................................................19
Final Inspection And Start-Up ........................................................................................21
Sequence Of Operation.................................................................................................24
Maintenance ...............................................................................................................25
Troubleshooting ...........................................................................................................26
Electrical Specifi cations ................................................................................................28
Optional - Return Air Access Panel .................................................................................33
Optional - Hydronic Coil ...............................................................................................34
Optional Carrier 50QT/ET Replacement — Installation .......................................................37
Operational Performance Data .......................................................................................39
Start-Up Report ...........................................................................................................40
AHRI Certifi ed ™ is a
trademark of the Air-
Conditioning, Heating
and Refrigeration
Institute
Information and specifi cations outlined in this manual in effect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specifi cations or system design at any time without
The Right Fit for Comfort 2 P/N 240006980, Rev. R [02/2013]
notice and without incurring any obligation, whatsoever.
Page 3
RECEIVING INFORMATION
Shipping damage MUST be reported to the carrier IMMEDIATELY.
Examine exterior.
Remove cover and examine compressor and piping for signs of damage.
Inspection
Check shipment against bill of lading. Verify equipment received as ordered.
Verify unit:
• Unit size and type correct per submittal sheet and job requirements?
• Louver color correct, if special color specifi ed?
• Control box located on correct side?
• factory installed on front, left or right side models 09–18;
fi eld modifi able to left or right model 24 only;
• front side only models 30–36.
• Voltage correct?
• Wall sleeve correct for unit, and correct depth? [Available in depths for walls of 6½ inches (165 mm) or deeper, in increments of ½ inch (12.7 mm)]
• Electric heat correct capacity, if used?
• Hydronic coil included, if required? Piping located as required?
General Information
Installation shall be completed by qualifi ed agency. this manual and warranty for future reference.
Installer review this manual to verify unit has been installed correctly. Run unit for one complete cycle to verify proper function.
To obtain technical service or warranty assistance during or after installation, contact your local representative.
Visit our web site www.retroaire.com for local representative listing.
For further assistance call 1-800-325-5479. When calling for assistance, please have following
information ready: Model Number_________________________
Serial Number_________________________
Date of installation______________________
Retain
Inspect each component for damage. Concealed damage must be reported to carrier within 15 days of receipt of shipment.
Carrier must make proper notation on delivery receipt of all damage identifi ed and complete carrier inspection report.
Purchaser must notify Manufacturer’s Service department of all damage and is responsible for fi ling any necessary claims with carrier.
Customer Service : (800) 228-9364
P/N 240006980, Rev. R [02/2013] 3 Made in USA
Page 4
ot
workin
Become Familiar With Symbols Identifying Potential Hazards.
IMPORTANT SAFETY INFORMATION
!
All fi eld wiring shall conform to requirements of authority having jurisdiction or in absence of such requirements:
• United States - National Electrical Code, ANSI/NFPA 70
• Canada - CSA C22.1 Canadian Electrical Code Part 1.
!
WARNING
Fire, and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
Become Familiar With Symbols Identifying Potential Hazards.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury.
!
WARNING
Tampering with VPRC/VPRH is dangerous and could result in serious injury or death. Do not modify or change this unit.
Safety Information
• Installation by qualifi ed personnel.
• Turn off electrical supply before servicing unit.
• Inspect all parts for damage prior to installation and start-up.
• Do not use unit if it has damaged wiring, is n working properly, or has been damaged or dropped.
• Connect to properly grounded electrical supply with proper voltage as stated on rating plate.
• Have proper over current protection (i.e. time- delay fuse/HACR Breaker) as listed on Rating Plate.
• Connect unit to properly grounded electrical supply. Do not fail to properly ground this unit.
• Tampering voids all warranties.
ot
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
The Right Fit for Comfort 4 P/N 240006980, Rev. R [02/2013]
Page 5
DIMENSIONAL/PHYSICAL DATA
Figure 1 VPRC/ VPRH Dimensions — Inches (mm) - Models 09, 12, 19 & 24
Table 1 Nominal Capacities, Dimensions, Shipping Weights And Return Air Filter Sizes
Model
Dimension
A 7
B 40 (1016) 50 (1270)
C 21-
D 25 (635) 25 (635)
E 14
F 25 (635) 32 (813)
G 10
H 3
J 16
K 6
L 9-
09–12
in. (mm)
-5/8
(194) 6
7/16
(545) 26
-5/8
(372) 20
-5/16
(261) 11
-1/2
(89) 3
-1/2
(419) 21
-1/8
(156) 8-
5/8
(245) 12 (305)
19-24
in. (mm)
-1/2
(165)
-7/16
(672)
-5/8
(524)
-3/8
(289)
1/2
(89)
-9/16
(548)
3/16
(208)
Model
09
12
19
Straight cool/Limited Range Heat pump nominal
capacities
9,000 12,000 19,000 24,000 Btuh
2.6 3.5 5.6 7.0 kW
Shipping weight
pounds (kg)
(shipping weight =
unit weight + 60
lbs (27 kg)
190
(86)
190
(86)
300
(136)
Return Air Filter Dimensions
All models must have an air fi lter
installed prior to operation.
(406 x 635)
(406 x 635)
(406 x 635)
inches (mm)
Chassis
Mounted
16 x 25
16 x 25
16 x 25
Return Air
Access Panel
Mounted
20 x 20
(508 x 508)
20 x 20
(508 x 508)
20 x 30
(508 x 762)
M 4
N 12-1/2 (317) 12-1/2 (317)
O 8 3/4 (222) 13 3/4 (348)
P/N 240006980, Rev. R [02/2013] 5 Made in USA
-1/4
(108) 10
-3/8
(264)
24
300
(136)
16 x 25
(406 x 635)
20 x 30
(508 x 762)
Page 6
DIMENSIONAL/PHYSICAL DATA
Figure 2 VPRC/ VPRH Dimensions - Model 18
Table 2 Dimensions, Shipping Weights And Return Air Filter Sizes
Model
Dimension
A7­B 40 (1016)
18
in. (mm)
3/4
(197)
Straight cool/Limited Range Heat pump nominal
capacities
18,000 Btuh
5.3 kW
C21
-7/16
(545) D 25 (635) E14 F 24 G9 H3-
J 16­K6­L9
-13/16
-5/8
-13/16 1/2 1/2
1/8
-1/2
(376)
(625)
(249) (89) (419)
(156) (241)
Model
18
Shipping weight pounds
(kg)
(shipping weight = unit
weight + 60 lbs (27 kg)
260
(118)
All models must have an air fi lter installed
Chassis mounted
16 x 25
(406 x 635)
Return Air Filter Dimensions
inches (mm)
prior to operation.
Return air access panel
mounted
20 x 20
(508 x 508)
M4
-1/4
(108) N 12-1/2 (317) O 8-3/4 (222)
The Right Fit for Comfort 6 P/N 240006980, Rev. R [02/2013]
Page 7
DIMENSIONAL/PHYSICAL DATA
Figure 3 VPRC/ VPRH Dimensions - Models 30 & 36
Table 3 Dimensions, Shipping Weights And Return Air Filter Sizes - Models 30 & 36
Model
Dimension
30
in. (mm)
A8
3/4
(222) 8
36
in. (mm) 3/4
(222)
Straight Cool/Limited Range Heat Pump Nominal Capacities
30,000 36,000 Btuh
8.8 10.5 kW
B 56 (1422) 56 (1422) D 28 (711) 28 (711) E21 G 6
3/4
(553) 21
1/4
(159) 6
3/4
1/4
(553) (159)
Model
Shipping weight
pounds (kg)
(shipping weight = unit
weight + 60 lbs (27 kg)
Return air fi lter dimensions
inches (mm)
All models must have an air fi lter
installed prior to operation.
Chassis mounted
J 28 (711) 28 (711)
K11
L10
1/4
(286) 11
1/4
(260) 10
1/4 1/4
(286) (260)
30
36
430
(195)
430
(195)
16 x 25
(406 x 635)
16 x 25
(406x 635)
M 16 (406) 16 (406) N 1 5/8 (41) 1 5/8 (41)
Return air
access panel
mounted
20 x 30
(508 x 762)
20 x 30
(508 x 762)
P/N 240006980, Rev. R [02/2013] 7 Made in USA
Page 8
Return
Return
Supply
Supply
8
1
Return
11
COMPONENTS
Models 09–24 Models 30–36
1
Supply
Outside louver
12
8
3
4
Supply
Return
Outside louver
8
3
10
Front — 09, 12, 18, 19, 24
1 Indoor coil (behind lter) 2 Outdoor coil 3 Control/power box 4 Alternate control box location
(right or left side)
5 Thermostatic drain valve
(09, 12, 19 and 24 only)
6 24-volt connection strip 7 Power cord strain relief
(for units with power cords)
8 Line voltage power entrances
(for hard-wired units)
9 Optional disconnect switch 10 Drain stub location options
(front, right or left side) — ½” I.D. connection
11 Fresh air shutter 12 Return air lter (see Table 19,
Page 40 for dimensions)
Wall sleeve,
10
custom for application
6
Wall sleeve,
custom for application
Front — 30, 36
3
7
6
Control panel, typical
09–24
3
9
1 Indoor coil (behind lter) 2 Outdoor coil 3 Control/power box 4 24-volt connection strip 5 Line voltage power
entrances
6 Drain stub location — ¾”
I.D. connection
7 Motorized fresh air
damper switch
8 Return air fi lter (see
Table 19, Page 40 for dimensions)
Control panel, typical
30, 36
4
5
7
4
Rear — 18
2
5
10
Rear — 09, 12, 19, 24
2
Rear — 30, 36
The Right Fit for Comfort 8 P/N 240006980, Rev. R [02/2013]
Transition Kit #
55002100
Page 9
GENERAL PRODUCT INFORMATION
Product Description
Microprocessor Control Board
• VPRC/VPRH 09–36 single package vertical air conditioner (SPVAC) and heat pump (SPVHP).
• R-410A refrigerant.
• Custom wall sleeve and outdoor louver.
• Insulated top-discharge indoor compartment.
• VPRC/VPRH vertical discharge allows ducting to top of room(s).
• VPRC/VPRH models can be applied in non-ducted return air applications. VPRC/VPRH 30-36 can also be applied in ducted return air applications.
• VPRH models are limited-range heat pumps. Heat pump operation will cease at approximately 40°F (4.4°C) outdoor temperature.
Standard Controls And Components:
• Ability to utilize single or 2-stage thermostat for VPRH emergency heat.
• Front-mounted control box standard for 09–36 (right or left-side mounting available for 09–24
• Field-Installed Accessories:
only).
• Manual fresh air damper for models 09–24, motorized fresh air damper for models 30–36.
• Disposable return air fi lter for models 09–24. Washable, reusable return air fi lter for models 30–36 only.
• Thermostatic drain pan valve for heat pump operation condensate removal (VPRH 09, 12,
19–24 only).
Air Systems
– Models VPRC/VPRH 09, 12, 19 & 24 blow air
across outdoor coil, models VPRC/VPRH 18, 30 & 36 draw air through outdoor coil.
Condensate Removal
– VPRC/VPRH 09, 12, 19 & 24 — Outdoor blower
incorporates condensate slinger ring. Base pans are designed to accommodate fi eld-installed drain stub kit if necessary. Drain stub kits are dependent upon application. Environments with higher humidity levels may require drain stub kits.
– VPRC/VPRH 18, 30 & 36 requires internal drain
system. Models VPRC/VPRH 18 are supplied standard with overfl ow drain stub kit for fi eld installation.
– VPRC/VPRH 30-36 outdoor coil side drain stub
is integral to base pan, allows easy connection of drain line.
APPLICATION LIMITATIONS
• Contact manufacturer if units will be operated in
– Random start timer prevents multiple units
from simultaneous start-ups.
– Fan purge — fan remains on for 60 seconds
after heat/cool call is satisfi ed
– Anti-short-cycle compressor protection
prevents compressor from rapid cycling
– Freeze protection — prevents evaporator coil
freeze up, improving compressor reliability
– Low ambient lockout prevents compressor
operation in outdoor temperatures less than 40°F (4.4°C)
– Test operation — all timers are temporarily
suppressed to allow ease of testing or troubleshooting
– Control board LED provides self-diagnostic
troubleshooting codes (see Sequence of Operation, page 24)
– Hydronic heat plenum (coil included on models
09–24 only).
– Remote wall thermostat (digital 1-stage or
2-stage available).
– Return air access panel - optional solid panel
available for application with separate air intake.
– Models 09, 12, 19–24 only — Drain stub kit,
can be installed on front, right side or left side.
– Wall sleeve transition kit Model 30 only-
Needed when installing a VPRC/VPRH 30 in place of a VPAC/VPHP 30. See page 8. [Transition Kit 550002100]
temperatures outside ranges listed below.
Table 4 Ambient Air Limitations
OUTDOOR [Ambient air temperature °F (°C)]
COOLING HEATING
Minimum Maximum Maximum
Dry bulb Dry bulb Dry bulb
67 (19) 115 (46) 75 (24)
INDOOR [Ambient air temperature °F (°C)]
COOLING HEATING
Minimum Maximum Min. Max.
Dry
bulb
67 (19) 57 (14) 90 (32) 72 (22) 50 (10) 80 (27)
Wet bulb
Dry
bulb
Wet
bulb
Dry bulb
P/N 240006980, Rev. R [02/2013] 9 Made in USA
Page 10
CONTROL BOX LOCATION
Control Box Location
• VPRC/VPRH control box is factory mounted in front
position, unless otherwise specifi ed.
• Control box can be factory mounted for front, left or
right side applications on models 09–24.
• Control box is available only on front for models 30 and
36.
Figure 4 Optional Control Box Locations
Relocating Control Box
(Models 09, 12, 19, & 24) Field relocation of Control Box must be done prior to installing unit.
1.
2.
3.
4.
5.
6.
Front-mounted control box (standard)
Optional control box locations: right side or left side (can be relocated in the fi eld on models 09–12 and models
19–24)
7.
8.
9.
!
DANGER
Electrical shock hazard. Disconnect power to unit before servicing or accessing control compartment. Failure to do so will result in severe personal injury or death.
Determine desired location. Remove sheet metal panels from current control box
location, and desired control box location. Remove control knock-out from panel. Remove insulation directly behind knock-out. Use metal tape to seal opening in panel where control
box was originally located. Cut wire ties securing wire harness. Remove mounting screws holding control box in place. Relocate control box, and install mounting screws. Use wire ties to bundle and secure wire harness.
!
DANGER
Electrical shock hazard. Verify wires do not contact any sharp sheet metal edges, refrigeration tubing, outdoor fan motor, or any moving parts. Failure to do so will result in severe personal injury or death.
Figure 5 Front-Mounted Control Box
Only (Models 30 & 36)
Front-mounted control box only
Motorized fresh air damper switch
location
10.
Replace sheet metal panels.
The Right Fit for Comfort 10 P/N 240006980, Rev. R [02/2013]
Page 11
ENCLOSURE PREPARATION
Proper Clearances
• For proper air fl ow and sound levels minimum clearance of 4 inches (102 mm) [models 09–18] or 6 inches, (152 mm) [models 24–36] between enclosure and chassis be maintained (see Figure 6).
• For service, maintain minimum of 6 inches (152 mm) on both sides and front for non-ducted return air applications only.
• Ducted return air applications only require minimal spacing for service requirements.
Figure 6 Minimum Clearances
Minimum clearances [inches (mm)]
Model A B C
09, 12, 18
19, 24, 30, 36
A = distance from left side of unit to interior wall B = distance from right side of unit to interior wall C = distance from front of unit to interior wall
4
(102mm)4 (102mm)4 (102mm)
6
(152mm)6 (152mm)6 (152mm)
Rough Openings Access opening — allows unit insertion. Provide minimum
opening dimensions. (See Figure 21, Page 33, for dimensions of opening when using optional return access panel assembly.)
Table 5 Minimum Access Opening Dimensions
(Figure 6)
Model
09–12
18
19–24
30
36
Width
[inches (mm)]
Front
access
(front con-
trol panel)
26 1/8
(664)
26 1/8
(664)
26 1/8
(664)
28 9/16
(726)
28 9/16
(726)
Side access
(side con-
trol panel)
26 1/8
(664)
26 5/8
(676)
33 5/8
(854)
36 1/4
(921)
36 1/4
(921)
Height
[inches (mm)]
Without
hydronic
option
45 3/4
(1162)
45 3/4
(1162)
57 3/4
(1467)
58 3/4
(1492)
58 3/4
(1492)
hydronic
With
option
55 3/4
(1416)
55 3/4
(664)
69 3/4
(664)
N/A
N/A
NOTICE
Optional return air access panel assembly: Rough opening to enclosure, and enclosure dimensions must be sized to accept access panel door frame, when used. See page 34 for details.
Wall sleeve rough opening — rough opening in wall for wall sleeve and louver, must be correct dimension and exact position necessary for installation.
Table 6 VPRC/VPRH rough wall sleeve opening
Model Width [inches (mm)]
09–12 26 1/8 (664) 26 1/8 (664)
18 26 1/8 (664) 26 5/8 (676)
19–24 26 1/8 (664) 33 5/8 (854)
30 28 9/16 (726) 36 1/4 (921) 36 28 9/16 (726) 36 1/4 (921)
Height [inches
(mm)]
Platform
See Figure 7, Page 12 and Figure 10, Page 15 for details of platform and wall sleeve installation.
Platform height must make bottom of VPRC or VPRH chassis fl ush with bottom inside edge of wall sleeve. Platform surface must be ½ inch (13 mm) ABOVE bottom of wall sleeve rough opening.
Platform dimensions above will allow chassis base pan to align with bottom of wall sleeve.
Air fi lter
All models must have air fi lter installed prior to operation. Use chassis-mounted air fi lter provided, unless using. For optional return air access panel, remove and discard fi lter from unit and install access panel with supplied fi lter in place.
P/N 240006980, Rev. R [02/2013] 11 Made in USA
Page 12
000000
0
ENCLOSURE PREPARATION
Figure 7 Exploded View Of Typical Installation (Chassis shown is typical of models 09–24)
1
30/36 chassis
(models 09–24 shown at right)
6 10
10
1
9
2
5
4
7
3
6
9
The Right Fit for Comfort 12 P/N 240006980, Rev. R [02/2013]
8
Page 13
ENCLOSURE PREPARATION
Exploded View Of Typical Installation (Chassis shown is typical of models 09–24)
Access opening (for unit insertion/removal) — See unit dimensions in Figures 2, 3, 4, Pages 5-7. See Table 6, page 11 for minimum recommended opening dimensions. Allow for extra height of hydronic coil module, if used.
1
2
3
4
5
6
7
8
9
NOTE: Access opening will be in left or right side of enclosure for left or right-side-mounted control panel units (available option on models 09–24 only).
See Figure 6, Page 11 for minimum clearances around unit to determine minimum enclosure dimensions.
Wall sleeve opening to outside — See required dimensions in Table 7, Page 11. Platform (see page 11) — See Figure 10, Page 15 for required platform height. Platform must be
level. Wall sleeve (see page 14) — Wall sleeve must accommodate total wall thickness (from inside
surface of wall sleeve opening to surface of outside wall). Outside louver- — Outside louver attaches to wall sleeve with nuts placed on louver studs.
VPRC/VPRH chassis.
Control panel. Access opening must be on same side of unit as control panel. Thermostat connection terminal block located here
Optional return access panel assembly. See Figure 21, Page 33 for details and dimensions. Return air opening — VPRC/VPRH requires air fi lter on return air. Filter is located on chassis open-
ing unless optional return air access panel is used (for these applications, air fi lter is removed from chassis — fi lter is installed on access panel).
10
P/N 240006980, Rev. R [02/2013] 13 Made in USA
Hydronic coil option — See pages 35 to 37.
Page 14
WALL SLEEVE INSTALLATION
Verify Wall Sleeve Depth
Wall sleeve depth must be suitable for overall wall thickness. (Figure 8).
Consult manufacturer for available wall sleeves.
• Minimum wall sleeve depth is 6½ inch (165 mm)
overall wall thickness, and available in ½-inch (13­mm) increments for thicker walls.
• Wall thickness less than 6½ inches, wall sleeve will
penetrate into room, and will require interior framing adaptations for proper fi t.
Verify Openings And Enclosure
• Verify access opening size, wall sleeve opening size and enclosure size. See page 11.
• Verify wall sleeve opening is square by measuring corner to corner. Also
• Verify platform (if used) is at correct height and is level with wall sleeve opening. Adjust platform and framing as necessary. If opening and platform are not square, unit will not fi t properly to wall sleeve.
Assemble wall sleeve (09–24 only)
• Models 09–24 are supplied with tabbed-assembly wall sleeve.
• Follow instructions supplied with wall sleeve to assemble. Wall sleeve should look like that shown in Figure 9.
Figure 8 Determining wall sleeve depth
Specify overall wall thickness when ordering the wall sleeve — it will be supplied to meet the required depth.
Overall wall thickness
Foam gasket 1
1
X
/2
inch
/2
(13 X 13mm)
Outdoor louver
Drip edge will extend outside exterior wall when installed to guide condensate away from building
Lag Holes (4 on each
side)
VPRC/VPRH Wall Sleeve Assembly
Exterior wall
Wall sleeve
Cross Section of Typical Wall
Interior wall
Figure 9 Typical tabbed-assembly wall sleeve
(09–24)
Inside
• Wall sleeves for models 30–36 are factory assembled.
Secure the wall sleeve
• Slide wall sleeve into rough opening.
• Slide wall sleeve to one side of opening, preferably to side that is most plumb.
• Secure wall sleeve to this side of opening using screws through lag holes (see Figure 9), verify wall sleeve is level. Fill any gaps between wall sleeve and opening with shims to prevent distortion when screws are tightened.
• Secure wall sleeve to other side in same manner. Verify wall sleeve is both square and level before tightening screws.
Lag holes
(4 on each side)
Chassis studs
Outside View
The Right Fit for Comfort 14 P/N 240006980, Rev. R [02/2013]
Page 15
TYPICAL CHASSIS AND WALL SLEEVE, INSTALLATION
Figure 10 Typical VPRC/VPRH Installation, With Platform
Platform surface must be ½ inch (13 mm) ABOVE bottom of wall sleeve rough opening.
*NOTE: If replacing model VPAC/VPHP 30 with VPRC/ VPRH 30 raise platform surface additional 3/8 in. (10mm) to accommodate new wall sleeve.
To Install Outside Louver
• Install studs on inside of louver. Louvers will pass through clearance holes in wall sleeve fl ange.
• Place outside louver in position.
• Secure louver by installing nuts (supplied) on studs.
P/N 240006980, Rev. R [02/2013] 15 Made in USA
Page 16
F
RONT-MOUNTED CONTROL PANEL - CHASSIS AND WALL SLEEVE, INSTALLATION
GENERAL INSTALLATION CONTINUED
Hydronic Coil (Optional)
Figure 11 Foam Gasket & Weather Angles (09–
Install hydronic coil option BEFORE placing chassis in wall sleeve. See pages 35-37.
Inspect Foam Insulation
Verify foam insulation strips around condenser opening are intact. Replace if necessary. Foam insulation must be in place and in good condition to prevent air or water leakage or air recirculation. See Figure 11 and Figure 12.
Attach Weather Angles
Using screws provided, attach weather angle to each side of chassis as shown in Figures 11 and 12.
24) Front Control Panel Installations
Supply air connection (return is in front)
Punch hole through
Back Panel
gasket at lag holes
Foam gasket
Insert Chassis Into Wall Sleeve
• Slide chassis into wall sleeve, verify studs on wall sleeve slide through holes in back panel and weather angles.
• Attach ¼-20 nuts to studs that pass through weather angles, each side of chassis.
DO NOT attach nuts to studs that pass through back panel of chassis. This would make removal diffi cult.
• Chassis must be fi rmly attached to wall sleeve to prevent leakage or recirculation.
• See Figure 10, Page 15, for side view of typical completed installation.
Plenum and Duct Work
1.
Install plenum and duct work to supply air connection, all models.
2.
Install return air duct work, if applicable (VPRH/VPRC 30–36 only).
3.
For models 09–18, accessory 10-inch round duct collar is available.
– 1: return air inlet with fi lter installed – 2: supply air outlet – 3: optional supply air duct collar, 10-inch
(254mm) round
Foam gaskets (½ x ½ in)
Mounting holes (each side only)
Weather angle (one each side)
Punch holes in foam gaskets at locations of mounting holes in back panel and weather angles (see call outs in Fig­ure 13 and Figure 14).
Making it easier for wall sleeve studs to pass through holes when chassis is slid into place.
Figure 12 Foam Gasket & Weather Angles
(30–36) Front Control Panel Installations
Supply air connection (return is in front)
Back Panel
3
2
1
The Right Fit for Comfort 16 P/N 240006980, Rev. R [02/2013]
Foam gasket
Weather angle (one each side)
Mounting holes (each side only)
Page 17
SIDE
-MOUNTED CONTROL PANEL - CHASSIS AND WALL SLEEVE, INSTALLATION
Inspect Foam Insulation
Figure 13 Foam Gasket & Weather Angles
• Verify foam insulation strips around condenser opening are intact (see Figure 13 and 14). Replace if necessary.
• Foam insulation must be in place and in good condition to prevent leakage or recirculation.
Insert Chassis Into Wall Sleeve
Right-side-mounted control panel — remove right side panel.
Left-side-mounted control panel — remove left side panel.
• Slide chassis into wall sleeve, verify studs on wall sleeve slide through holes in back panel.
• Attach ¼-20 nuts to studs that pass through back panel.
• Chassis must be fi rmly attached to wall sleeve to prevent air or water leakage or air recirculation.
Attach Weather Angle
Right-side-mounted control panel
Foam gasket
Foam gaskets (½ x ½ in)
Mounting holes (each side only)
Weather angle (one each side)
A. Replace right side panel. B. See Figure 13 for location of right-side weather
angle.
Figure 14 Foam Gasket & Weather Angles
C. Using screws provided, attach weather angle to
chassis. See Figure 14. D. DO NOT install left-side weather angle. E. Attach ¼-20 nuts to studs that pass through
weather angle.
Left-side-mounted control panel A. Replace left side panel. B. See Figure 14 for location of right-side weather
angle.
C. Using screws provided, attach weather angle to
chassis. See Figure 14. D. DO NOT install right-side weather angle. E. Attach ¼-20 nuts to studs that pass through
weather angle.
• See Figure 9, Page 15, for side view of typical completed installation.
Supply air
connection
(return is in front)
Punch hole through gasket at lag holes
Back Panel
(09–24) Right-Side Control Panel Installations
Right side
panel
Back panel
(09–24) Left-Side Control Panel Installations
Supply air connection (return is in front)
Left side
panel
Punch hole through gasket at lag holes
Foam gasket
Weather angle (left side only)
Plenum And Duct Work
• Install plenum and duct work.
Punch holes in foam gaskets at locations of mounting holes in back panel and weather angles (see call outs in Figure 13 and 14).
Making it easier for wall sleeve studs to pass through holes when chassis is slid into place
P/N 240006980, Rev. R [02/2013] 17 Made in USA
Mounting holes in weather angle
Foam gasket
Page 18
CONDENSATE DRAIN
Condensate drain
1.
Models VPRC/VPRH 09,12,19, and 24 are designed so condensate generated during cooling operation is delivered to base pan, and picked up by outdoor fan’s slinger ring.
2.
Condensate is slung onto outdoor coil where it evaporates. Any excess condensate, or wind driven rain that enters base pan will overfl ow through notches located in rear of unit and run out wall sleeve, onto drip edge, and out of building.
3.
Models VPRH 09,12,19, and 24 are also equipped with thermostatic drain valve located on bottom of base pan. Valve opens when outdoor temperatures reach 50°F (10°C), and allows any residual condensate or wind driven rain in base pan to run out wall sleeve as stated above. Protects outdoor fan from damage during heat pump operation.
Figure 15 Drain Stub Location - Models 09–
24 (Optional On Models 09, 12, 19 And 24; Included And Required On Model
18)
4.
Accessory drain stub kit is available for models VPRC/ VPRH 09,12,19,and 24. Optional fi eld installed kit is designed for use with building’s internal drain system, and must be installed prior to operation. See Figure 15 for available stub locations on base pan, and connection size. If unit is equipped with additional drain stub in base-pan, connect drain stub to building’s internal condensate removal system.
5.
Model VPRC/VPRH 18 is supplied with drain stub that must be fi eld installed on unit, and connected to building’s internal drain system prior to operation. See Figure 15 for locations on base pan, and connection size.
6.
Models VPRC/VPRH 30 and 36 are supplied with drain stub that must be fi eld installed, and connected to building’s internal drain system prior to operation. See Figure 16 for location on base pan, and connection size.
7.
Drain stub must be connected to internal condensate removal system.
8.
Use of internal condensate drain stub requires connection to be lower than base pan weep holes, located near bottom of condenser coil.
Figure 16 Drain Stub Location (Models 30–36)
¾” ID tube connection — front of drain pan
Movable drain stub, ½” ID tube connection may be located on front, right or left side of unit. Swap gasketed drain stub plate with blanking plate to relocate to alternate location.
The Right Fit for Comfort 18 P/N 240006980, Rev. R [02/2013]
Page 19
ELECTRICAL CONNECTIONS
Electrical Connections
!
WARNING
Electrical shock hazard. Disconnect all power before removing chassis, performing any cleaning, servicing, or maintenance. Failure to do so could result in death or serious injury.
Refer to wiring diagram attached to unit for wiring details. All fi eld wiring shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States
• National Electrical Code, ANSI/NFPA 70
• Canada
• CSA C22.1 Canadian Electrical Code Part 1.
• Check VPRC/VPRH ratings.
• Installer is responsible for ensuring VPRC/VPRH units are installed in accordance with all applicable national and local codes.
• Check rating plate for circuit ampacity.
• Size breaker(s) or fuse size(s) accordingly.
A. Use only HACR type breakers or time delay fuses. B. Select proper wire for breaker or fuse size used. C. Some units require more than one power supply. D. If plug and receptacle are used, check for proper
t.
E. Check nameplate and wiring diagram for further
instructions and wire connections.
F. Each unit is equipped for 24v wall thermostat
connection.
Power Cord With Integral Safety Protection
All VPRC/VPRH units that are cord connected to power supply are equipped with power cord with integral sensor:
• Provides personal shock protection.
• Provides arcing and fi re prevention.
• Senses any damage in line cord and disconnects power before fi re can occur.
Tested in accordance with Underwriters Laboratories, cord set also offers unique “passive” operation, unit does not require resetting if main power is interrupted.
Disconnect Switch (
Disconnect switch ensures all power to control box is disconnected for servicing, resetting if main power is interrupted.
• Each power cord must be tested before use. Follow test instructions in order listed on plug of power supply cord.
• DO NOT use product if power supply cord fails test.
• DO NOT attempt to repair damaged power supply cord.
Replace with new cord from manufacturer only.
Choosing Thermostat
Manufacturer offers choice of single-stage or two-stage mercury-free thermostat compatible with all models of VPRC/VPRH. (Use two-stage thermostat for VPRH units equipped with electric heat option.)
• RetroAire™ thermostats have digital readout with temperature control range from 45°F (7°C) to 90°F (32°C).
• When using fi eld sourced thermostat use ONLY 24v heat/cool thermostat.
Optional)
NOTICE
Cooling-Only With Electric Or Hydronic Heat
only)
VPRC/VPRH units are wired for 230v primary voltage from manufacturer. Transformer must be rewired by installer if job site voltage is 208v.
P/N 240006980, Rev. R [02/2013] 19 Made in USA
• Select thermostat compatible with cooling/electric heat system.
• Thermostat should have “R”, “Y”, “W” and “G” terminals.
(VPRC
Page 20
ELECTRICAL CONNECTIONS
Heat Pump With Electric Heat (VPRH only)
Single-Stage Thermostat
Select thermostat compatible with cooling/single stage heat/heat pump system.
• Thermostat should have “R”, “Y”, “O” and “G” terminals. RetroAire™ units are single stage heating only.
• Electric heat and heat pump will not operate simultaneously.
Two-Stage Thermostat
Two-stage heat pump thermostat can be used with VPRH units.
• See wiring diagram for connections.
• VPRH units are designed to operate as single stage heat pumps — will alternate between heat pump and electric heat to meet heat demand.
Thermostat Wiring
The Right Fit for Comfort 20 P/N 240006980, Rev. R [02/2013]
Page 21
!
FINAL INSPECTION AND START-UP
!
CAUTION
Moving parts can cause injury. Use caution when testing unit. Failure to do so could result in minor or moderate injury.
1.
Do not operate unit without fi lter in place or use as temporary heating/cooling source during construction.
2.
Plug in line cord, if supplied, or hard wire line voltage power to the unit. Refer to unit rating plate for proper voltage and amperage/fuse size.
3.
Unit may require two power supplies (check nameplate and wiring diagram for further instructions.)
4.
Connect low voltage wires from thermostat to unit. Follow wire diagram for details.
5.
Turn power on and check for proper operation.
Before Operating This Unit:
☐ Read and understand this manual. ☐ Verify electrical supply matches electrical require-
ments of unit, and unit is properly grounded.
☐ Examine control box. Verify all wire connections are
secure, and control board jumpers are in proper positions. See Page 28.
☐ Verify indoor blower wheels and outdoor fan blades
are secured to their motor shafts.
☐ Ensure all sheet metal panels are in place and se-
cure.
☐ Verify drain stub, if used, is secure to base pan, and
condensate drain is functioning properly.
☐ Verify chassis is properly fi tted to wall sleeve, and
securely mounted to surrounding framing.
Cooling
5.
Set wall thermostat to cool mode. Set thermostat below room temperature setting.
6.
After few minutes of operation, cool air should discharge from grilles.
7.
Thermostat can be set at desired setting with selector switch in heat or cool position.
8.
Verify unit is level.
9.
Check condensate removal by pouring water into base pan, put unit in cooling mode, with condenser fan running, see if water is picked up by slinger ring and thrown onto outdoor coil. (Models VPRC/VPRH 09–24 only)
10.
If condensate is routed to internal drain, verify drain is functioning properly.
11.
Verify there is nothing interfering with room discharge air or return air.
Manual Fresh Air Shutter
Manual fresh air shutter allows user to move fresh air into space to be conditioned. Damper handle is located below indoor coil on service panel (models 09–24 Only).
Motorized Fresh Air Damper
Motorized damper is used on models 30–36. Damper operating switch is located on control box. See Figure 5, Page 10.
Heating
1.
Set wall thermostat to heat mode.
2.
Set thermostat above room setting.
3.
After few minutes of operation, warm air should discharge from grilles.
4.
Do not operate unit when panels are removed.
P/N 240006980, Rev. R [02/2013] 21 Made in USA
Page 22
FINAL INSPECTION & START-UP
General
Installation and wiring shall be in accordance with requirements of authority having jurisdiction In absence of such requirements refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1: Safety Standard for Electrical Installations.
Units Rated 208/230V:
• RetroAire unit is wired for 230v primary voltage from
manufacturer.
• Transformer must be rewired by installer if job site
voltage is 208v.
• Change transformer tap from orange to red. See wiring
diagram for details.
Setting Control Board Jumpers
Control board has two sets of factory installed jumper pins on control board, HP jumper and TEST jumper.
HP Jumper — selects heat pump or straight cooling. Pins determine whether unit operates as straight cooling or
as heat pump. See Figures 17 and 19.
• Jumper right pin to center pin for heat pump operation.
• Jumper left pin to center pin for straight cooling
operation.
Figure 18 TEST jumper (selects normal or
TEST Jumper
— selects normal or test mode
Figure 17 HP Jumper (selects heat pump or
straight cooling)
Heat Pump Mode
(Jumper center & Bottom pins)
HP
Straight
Cool Mode
(Jumper center
& Top pins)
HP
test mode)
NOTICE
Do not leave unit operating with TEST jumper in TEST position.
• Jumper is for testing only. See Figure 18 and 19.
• When jumper pins are jumped together, all timers are
eliminated (example — anti-short cycle, purge, etc.).
• May be used for fi eld testing. Units are factory set with
jumper on only one pin (normal operation position).
Normal operation (pins not jumped)
Test mode (pins jumped)
The Right Fit for Comfort 22 P/N 240006980, Rev. R [02/2013]
Page 23
FINAL INSPECTION & START-UP
Figure 19 Circuit Board
TEST JUMPER
HEAT PUMP
JUMPER
P/N 240006980, Rev. R [02/2013] 23 Made in USA
Page 24
SEQUENCE OF OPERATION
Initial Power-Up Or Power Restoration
When power is applied, either for fi rst time or after power failure, board will initialize.
• During initialization, LED1 will be lit continuously for approximately 5 seconds.
• Following initialization, random-start timer is initiated. This timer adds randomly selected 5-120 seconds to start-up sequence, reducing possibility of multiple units starting at same time.
• Once random start timer has expired, 180-second anti­short-cycle timer is initiated. LED1 blinks two-fl ash code. (Anti-short-cycle timer prevents compressor from rapid cycling.)
• After the anti-short-cycle timer expires, LED1 blinks a one-blink code, indicating normal operation.
Figure 20 Indicator LED1
LED1
Cooling Operation
• If room temperature is above thermostat setting, reversing valve (VPRH only) will be energized.
• Compressor and outdoor fan will start provided Anti­Short Cycle Timer has timed out from initial power-up, power restoration or previous compressor on cycle.
• Operation will continue until room temperature satisfi es thermostat. Once room temperature falls below set point by 3 ºF (2 ºC), compressor, outdoor fan motor and reversing valve (VPRH only) will de­energize.
• As soon as compressor is de-energized, anti-short­cycle timer will be initialized and prevent compressor from starting again for another 180 seconds.
• While anti-short-cycle timer is active, LED1 is set to blink two-fl ash code.
• After anti-short-cycle timer expires, LED1 is set to blink one-blink code, indicating normal operation.
Mechanical Heating (VPRH only)
• If outdoor coil temperature remains above 25°F (-4°C), compressor and outdoor fan will start provided anti-short-cycle timer has timed out from initial power­up, power restoration or previous compressor on cycle. Operation will continue until room temperature satisfi es thermostat.
• Once room temperature rises above set point by 3 °F (2°C), compressor and outdoor fan motor will de­energize.
• As soon as compressor is de-energized, anti­short-cycle timer will be initialized and will prevent compressor from starting again for another 180 seconds. While anti-short-cycle timer is active, LED1 blinks two-fl ash code. After anti-short-cycle timer expires, LED1 fl ashes one-blink code, indicating normal operation.
Auxiliary Heating
• If outdoor coil temperature falls to 25°F (-4°C) or
Fan Operation
Some thermostats are equipped with auto/on fan switch.
• When switch is placed in on position indoor fan will run continuous.
• When switch is in auto position indoor fan will cycle with call for heating or cooling.
Fan purge (auto mode only) — after room thermostat has been satisfi ed, purge feature allows indoor fan to remain on for additional 60 seconds. Increases
effi ciency by pulling remaining energy from unit.
The Right Fit for Comfort 24 P/N 240006980, Rev. R [02/2013]
below for 180 seconds during heating call, compressor and outdoor fan motor will be de-energized and auxiliary heat will be energized.
• Anti-short-cycle timer will be initiated, prohibiting compressor operation for 180 seconds.
• LED1 will fl ash three-blink code, indicating auxiliary heat operation. Heating operation with auxiliary heat will continue until outdoor coil sensor reaches 50°F (10°C).
Hydronic Heating
• With call for heat, signal from processor board will activate water or steam valve and indoor fan.
• Signal to water or steam valve will continue until room temperature rises above set point by 3°F (2°C).
Page 25
MAINTENANCE
!
WARNING
Electrical shock hazard. Disconnect power to VPRC/VPRH before servicing or accessing control compartment. Failure to do so could result in severe personal injury or death.
NOTICE
Perform regular service and maintenance by qualifi ed service agency at least once every 12 months to assure safe, trouble free operation and maximum effi ciency .
NOTICE
Verify proper operation after servicing.
Maintenance Schedule
Manufacturer recommends performing following inspections and maintenance on monthly basis. Units installed in harsh or dirty environments will require more frequent inspections and maintenance.
Disconnect power to unit and remove necessary access panels:
☐ Clean or replace indoor air fi lter. ☐ Inspect chassis interior for rodent or insect
infestation. Clean if necessary.
☐ Clean & fl ush condensate drain pan and chassis
base pan.
Repair if necessary.
Seasonal Start-Up And Maintenance
Beginning of cooling and heating seasons, complete mechanical check should be performed and maintenance/ inspections performed as described below.
Disconnect power to unit and remove necessary access panels:
1.
Remove access panel. Visually inspect equipment. Look for obvious changes in unit such as damaged coils or evidence of extended wear on any moving parts.
2.
Check for unusual odors or leaks (examples: burnt motor windings, water, or refrigerant). Verify base pan is clean.
3.
Clean or replace return air fi lter as needed. Allowing dust to collect on fi lter. Check fi lter at least once month. Some environments may require more frequent replacement, depending on particulate in air stream.
4.
Inspect all electrical connections for frayed wires and poor connections.
5.
Check fan motors and blower assemblies. Verify screws and motor mounting hardware are tight.
6.
Centrifugal fan blades and blower cage brush and/or vacuum as necessary.
7.
Inspect both indoor and outdoor coils. Use fi n comb to straighten out any damaged fi ns.
NOTICE
Do not use solvent based cleaner to clean coils, some solvents will produce noxious odor when unit is in operation.
☐ If applicable, verify condensate drain is functioning
properly.
☐ Inspect refrigeration tubing, especially braze joints,
for signs of refrigerant leaks (oil residue). Repair if necessary.
☐ Inspect indoor and outdoor coils. Verify dirt or debris
have not collected on fi ns. Clean if necessary . T ake care not to damage coil fi ns when cleaning. Use fi n comb to straighten any bent fi ns.
☐ Examine control box. Verify all wire connections are
secure.
☐ Verify indoor blower wheels and outdoor fan blades
are secured to their motor shafts.
☐ Verify dirt or debris have not collected on indoor
blower wheels and outdoor fan blades. Use vacuum and soft brush to clean if necessary.
☐ Verify any ductwork connected to unit is secure and
free of air leaks.
☐ If unit has hydronic option installed, inspect piping,
especially braze joints, for signs of water leaks.
8.
Look for oil leaks or stains on or around all braze joints and refrigerant lines. Presence of oil here indicates potentially serious problem (such as refrigerant leak).
9.
Inspect and clean drain pan and drain line(s). Use of anti-fungicide tablet to keep condensate system free from bacterial contaminants is recommended.
10.
Verify unit is level for proper operation. Building and equipment may settle, causing shift in direction of condensate fl ow. (Note that bottom of wall sleeve is pitched downward to shed water to outside. Verify any shifting does not interfere with proper drainage.)
11.
Verify weep holes along rear fl ange of base pan are free of debris.
12.
Verify seal around unit is not broken or damaged.
13.
Air leaks may make the conditioned area uncomfortably drafty or produce noises. Visually inspect foam gasket between wall and unit, taking note of separation between air inlet for condenser and condenser coil discharge. These two areas must be sealed off from each other. If you experience poor cooling operation or erratic operation, check for air recirculation at condenser coil.
14.
Replace access panels and reconnect electrical power.
P/N 240006980, Rev. R [02/2013] 25 Made in USA
Page 26
TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Disconnect power to unit before servicing or accessing control compartment. Failure to do so could result in severe personal injury or death.
Symptom Suggestion
No heat or cooling • Check to see if unit has power and if thermostat is satisfi ed. If
thermostat is not satisfi ed, call your installing contractor or service contractor.
Thermostat calls for cooling, but cool air is not coming out of unit.
Light on circuit board is blinking.
Circuit board light is blinking 3 or 4 times, but there is no freeze condition.
Thermostat is satisfi ed, but fan is still running.
Thermostat calls for heat, but no heat comes out of unit.
Thermostat calls for heat while in heat pump mode, but heated air is not coming out of unit.
• Check for continuity between thermostat and unit. Verify 24V ac is present across terminals C and R.
• Verify high pressure switch located in outdoor section has not been tripped. If tripped, press switch button to restart compressor.
• Some units are equipped with LCDI (Leakage current detection interrupt) line cord. Verify this line cord is reset by pressing reset button at line cord plug.
• Note: If evaporator fan is operational and all of above suggested procedures have been followed, and there is still no cooling being supplied by unit, contact trained heating and cooling professional.
• Circuit board uses light for diagnostic purposes. Blinking codes are as follows:
– 1 blink = normal operation – 2 blinks = compressor lockout (ASCT — Anti-short cycle timer) – 3 blinks = outdoor freeze condition – 4 blinks = indoor freeze condition – 5 blinks = simultaneous Y and W call (Straight cool units only)
• Verify sensors have not been damaged. R emove sensor wires from control board and make resistance measurements, compare to following sensor resistances. Indoor and outdoor coil sensor wires are labelled, as is control board.
– 77 °F = 10KOhms – 50F = 19.9KOhms – 35F = 30KOhms – 30F = 34.4KOhms
• If thermostat is set to auto mode, once thermostat is satisfi ed, fan will stay energized for extra 60 seconds to purge unit of excess cool or warm air in plenum.
• If thermostat fan switch is set to ON, fan will stay energized regardless of whether thermostat is satisfi ed or not. Only way to turn fan off is to turn unit off or turn thermostat fan switch to AUTO.
• Units equipped with electric heaters have temperature limit switch to prevent electric heater from reaching unsafe temperatures. If after calling for heating, heater is not energized, check for continuity across limit. If limit is open, replace if with equivalent limit switch.
• Verify unit has power or thermostat has been satisfi ed. If unit has power and thermostat is satisfi ed, turn thermostat few degrees above room temperature.
• Verify LCDI line cord has not tripped. (See Page 19.)
• While in heat pump mode, verify thermostat is not energizing O terminal. Retroaire units are designed to work in heat pump mode when 24vac is present across Y and C. Verify heat pump jumper on control board is jumping two pins labeled “HP” (see control board jumper locations, Figure 17, Page 22).
• Verify there are no freeze conditions. Refer to blinking codes question above for more information.
Have qualifi ed technician conduct troubleshooting procedures.
NOTICE
The Right Fit for Comfort 26 P/N 240006980, Rev. R [02/2013]
Page 27
TROUBLESHOOTING
Indoor Motor Speed Tap Selection
• For information on indoor motor speed tap selection, please refer to “Indoor Motor Speed Tap Selection Chart” label attached to chassis of VPRC/VPRH (Table 8).
• Models’ VPRC/VPRH 09–36 motors are factory-wired for corresponding units as described in 230V column Table 8.
• Make speed tap changes as required by job site voltage and/or external static pressure (ESP).
• Speed tap changes may need to be changed from manufacturer settings. Manufacturer will not be liable for any system problems that could arise if motor speed is not changed to match application.
Table 7 VPRC/VPRH Indoor motor speed tap
selection chart
Model
09
12
18, 19,
24
30
36
Tap Key — Red (Low) — Blu (Med) — Blk (High)
ESP
In. w.c. (mm
w.c.)
0.1 (3)
0.2 (5)
0.3 (8) Blu
0.1 (3)
0.2 (5)
0.3 (8) Blk
0.1 (3)
0.3 (8)
0.1 (3)
0.2 (5)
0.3 (8)
0.1 (3)
0.3 (8)
230V 208V 197V
Red
Blu
Blk Blk Blk0.2 (5)
Blu Blu
Blk Blk Blk0.2 (5)
Red
Blu
Red
Blu Blu Blk
Blu Blk
P/N 240006980, Rev. R [02/2013] 27 Made in USA
Page 28
ELECTRICAL SPECIFICATIONS
Table 9 Legend For Electrical Specifi cations
FLA
H-WIRE
HA
Hp
Htr #
IFM
LRA
Max
MCA
Full Load Amps
Hard Wired
Heater Amps
Horse Power
Heater Option Number (see Figure 1)
Indoor Fan Motor
Locked Rotor Amps
Maximum
Maximum Circuit Ampacity
Min
MOCP
OFM
RLA
TCA
THA
Volt
W
Minimum
Maximum Over current Protection Device Amps (HACR-type breakers or time-delay fuses)
Outdoor Fan Motor
Rated Load Amps
Total Cooling Amps
Total Heating Amps
Voltage
Watts
Table 8 NEMA Specifi cations Non-Locking/Receptacles
The Right Fit for Comfort 28 P/N 240006980, Rev. R [02/2013]
Page 29
ELECTRICAL SPECIFICATIONS
Table 10 VPRC/VPRH 09 Electrical Specifi cation
Power
Supply
Volt —
1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/
230V
265V 240 3.32 18.8 0.56 0.07 1.2 0.125
Compressor
197 3.9 20 0.80 0.07 0.72 0.125
* THA value applies to hydronic heat only, Htr #8.
Indoor
Fan Motor
Outdoor
Fan Motor
Electric Heat Unit Electrical Ratings
0 or 8
3
4
5
0 or 8
2
3
4
208 N/A N/A 230 N/A N/A 208 2454 11.8 12.6 15.7 230 3000 13.0 13.8 17.3 280 3271 15.7 16.5 20.7 230 4000 17.4 18.2 22.7 208 4089 19.7 20.5 25.6 230 5000 21.7 22.5 28.2 265 N/A N/A 277 N/A N/A 265 2655 10.0 10.58 13.2 277 2901 10.5 11.03 13.8 265 3752 14.2 14.72 18.4
277 4100 14.8 15.36 19.2 265 4576 17.3 17.83 22.3
277 5000 18.1 18.61 23.3
0.8* 6.4 15 6–15P
5.42
0.56 6.0
5.08
20 6–20P
25 6–30P
30 6–30P
15
H-WIRE
20
25
Table 11 VPRC/VPRH 12 Electrical Specifi cations
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/
230V
**208/
230V
265V 240 4.6 20 0.56 0.07 1.2 0.125
Compressor
197 5.2 27 0.80 0.07 0.7 0.09
197 5.1 24 0.80 0.07 0.7 0.09
Indoor Fan
Motor
Outdoor
Fan Motor
Electric Heat Unit Electrical Ratings
0 or 8
0 or 8
0 or 8
208 N/A N/A 230 N/A N/A 208 2454 11.8 12.6 15.7
3
230 3000 13.0 13.8 17.3 280 3271 15.7 16.5 20.7
4
230 4000 17.4 18.2 22.7 208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2 208 N/A N/A 230 N/A N/A 208 2454 11.8 12.6 15.7
3
230 3000 13.0 13.8 17.3 280 3271 15.7 16.5 20.7
4
230 4000 17.4 18.2 22.7 208 4089 19.7 20.5 25.6
5
230 5000 21.7 22.5 28.2 265 N/A N/A 277 N/A N/A 265 2655 10.0 10.58 13.2
2
277 2901 10.5 11.03 13.8 265 3752 14.2 14.72 18.4
3
277 4100 14.8 15.36 19.2 265 4576 17.3 17.83 22.3
4
277 5000 18.1 18.61 23.3
0.8* 8.1 15 6–15P
6.7
0.8* 7.9 15 6–15P
6.6
0.56 7.6
6.36
20 6–20P
25 6–30P
30 6–30P
20 6–20P
25 6–30P
30 6–30P
15
H-WIRE
20
25
** Compressor subject to availability (REV. “B”)
P/N 240006980, Rev. R [02/2013] 29 Made in USA
Page 30
ELECTRICAL SPECIFICATIONS
Table 12 VPRC/VPRH 18 Electrical Specifi cations
Power
Supply
Volt 1–60
Compressor
Indoor Fan
Motor
Outdoor
Fan Motor
Electric Heat Unit Electrical Ratings
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208 N/A N/A 230 N/A N/A 208 2454 11.8 12.8 16.0
3
230 3000 13.0 14.0 17.6 280 3271 15.7 16.7 20.9
4
230 4000 17.4 18.4 23.0 208 4089 19.7 20.7 25.8
5
230 5000 21.7 22.7 28.4
1.0* 10.0 15 6–15P
8.3
6.86 8.4 15
265 3752 14.2 14.7 18.4 20
3
277 4100 14.8 15.4 19.2 20 265 4576 17.3 17.8 22.3 25
4
277 5000 18.1 18.6 23.3 25
6.86
208/
230V
197 6.5 43 1.0 0.15 0.8 0.125
265V 240 5.8 46 0.56 0.07 0.5 0.17
0 or 8
0 or 8 265 N/A N/A
* THA value applies to hydronic heat only, Htr #8.
20 6–20P
25 6–30P
30 6–30P
H-Wire
Table 13 VPRC/VPRH 19 Electrical Specifi cations
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/
230V
265V 240 7.1 43 1.3 0.25 1.3 0.25
Compressor
197 7.3 48 1.5 0.25 1.30 0.25
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 or 8
0 or 8 265 N/A N/A
208 N/A N/A
230 N/A N/A
208 2454 11.8 13.3 16.6
3
230 3000 13.0 14.5 18.2
280 3271 15.7 17.2 21.5
4
230 4000 17.4 18.9 23.6
208 4089 19.7 21.2 26.4
5
230 5000 21.7 23.2 29.0
208 5725 27.5 29.0 36.3
7
230 7000 30.4 31.9 39.9
208 8178 39.3 40.8 51.0
1
230 10,000 43.5 45.0 56.2
265 3752 14.2 15.5 19.3 20
3
277 4100 14.8 16.1 20.1 25
265 4576 17.3 18.6 22.3 25
4
277 5000 18.1 19.4 24.2 25
265 6635 25.0 26.3 32.9 35
7
277 7250 26.2 27.5 34.3 35
265 9152 34.5 35.8 44.8 50
1
277 10,000 36.1 37.4 46.8 50
1.5* 14.6 15 6–15P
10.1
9.7 11.5 15
6.86
20 6–20P
25 6–30P
30 6–30P
40
60
H-Wire
* THA value applies to hydronic heat only, Htr #8.
The Right Fit for Comfort 30 P/N 240006980, Rev. R [02/2013]
Page 31
ELECTRICAL SPECIFICATIONS
Table 14 VPRC/VPRH 24 Electrical Specifi cations
Power Supply Volt —
1–60
Volt Min RLA LRA FLA Hp FLA Hp
208/
230V
265V 240 8.0 46 1.3 0.25 1.3 0.25
Compressor
197 9.4 54.0 1.5 0.25 1.30 0.25
Indoor
Fan
Motor
Outdoor
Fan
Motor
Electric Heat Unit Electrical Ratings
Htr
Volt W HA TCA THA MCA MOCP Plug
#
208 N/A N/A
0 or
8
230 N/A N/A 208 2454 11.8 13.3 16.6
3
230 3000 13.0 14.5 18.2 280 3271 15.7 17.2 21.5
4
230 4000 17.4 18.9 23.6 208 4089 19.7 21.2 26.4
5
230 5000 21.7 23.2 29.0 208 5725 27.5 29.0 36.3
7
230 7000 30.4 31.9 39.9 208 8178 39.3 40.8 51.0
1
230 10,000 43.5 45.0 56.2
0 or
265 N/A N/A
8
265 3752 14.2 15.5 19.3 20
3
277 4100 14.8 16.1 20.1 25 265 4576 17.3 18.6 23.2 25
4
277 5000 18.1 19.4 24.2 25 265 6635 25.0 26.3 34.3 35
7
277 7250 26.2 27.5 34.0 35 265 9152 34.5 35.8 44.8 50
1
277 10,000 36.1 37.4 46.8 50
1.5* 14.6 20 6–20P
12.2
9.7 11.4 15
6.86
20 6–20P
25 6–30P
30 6–30P
40
60
H-Wire
* THA value applies to hydronic heat only, Htr #8.
P/N 240006980, Rev. R [02/2013] 31 Made in USA
Page 32
ELECTRICAL SPECIFICATIONS
Table 15 VPRC/VPRH 30 Electrical Specifi cations
Power
Supply
Volt —
1–60
Volt Min RLA LRA FLA Hp FLA Hp
208/
230V
265V 240 10.5 67 2.3 1.4
Compressor
197 13.0 74 3.0
* THA value applies to hydronic heat only, Htr #8.
Indoor Fan
Motor
0.5
Outdoor
Fan Motor
1.3
0.25
Electric Heat Unit Electrical Ratings
Htr
Volt W HA TCA THA MCA MOCP Plug
#
208 N/A N/A
0
230 N/A N/A 208 4089 19.7 22.7 28.4 30
5
230 5000 21.7 24.7 31.0 35 280 6134 29.5 32.5 40.7
7
230 7500 32.6 35.6 44.5 208 8178 39.3 42.3 52.9 60
1
230 10,000 43.5 46.5 58.1 60
0 265 N/A N/A
265 4576 17.3 19.6 24.5 25
4
277 5000 18.1 20.4 25.5 30 265 6864 25.9 28.2 35.3 40
7
277 7500 27.1 29.4 36.8 40 265 9152 34.5 36.8 46.1 50
1
277 10,000 36.1 38.4 48.1 50
N/A 20.6 30
17.3
14.2 16.8 25
6.86
45
H-WIRE
Table 16 VPRC/VPRH 36 Electrical Specifi cations
Power
Supply
Voltage —
1/60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA* TCA THA* MCA* MOCP* Plug
208/
230V
265V 240 12 67 2.3 1.4
Compressor
197 13.6 88 3.0
Indoor
Fan
Motor
0.5
Outdoor
Fan Motor
1.3
0.25
Electric Heat Unit Electrical Ratings
208 N/A N/A
0
230 N/A N/A N/A 208 4089 19.7 22.7 28.4 30
5
230 5000 21.7 24.7 31.0 35 280 6134 29.5 32.5 40.7
7
230 7500 32.6 35.6 44.5 208 8178 39.3 42.3 52.9 60
1
230 10,000 43.5 46.5 58.1 60 208 12,268 19.7 / 39.3 22.7 / 39.3 28.4 / 49.2 30 / 50
A
230 15,000 21.7 / 43.5 24.7 / 43.5 31.0 / 54.4 35 / 60
0 265 N/A N/A
265 4576 17.3 19.6 24.5 30
4
277 5000 18.1 20.4 25.5 30 265 6864 25.9 28.2 35.3 40
7
277 7500 27.1 29.4 36.8 40 265 9152 34.5 36.8 46.1 50
1
277 10,000 36.1 38.4 48.1 50 265 13,729 17.3/34.5 19.6/34.5 24.5/43.2 30/45
A
277 15,000 18.1/36.1 20.4/36.1 25.5/45.2 30/50
17.9
15.7
N/A
14.2 16.8 25
* — Where two values are shown, data is displayed as Circuit 1 / Circuit 2
21.3 30
* THA value applies to hydronic heat only, Htr #8.
45
H-WIRE
The Right Fit for Comfort 32 P/N 240006980, Rev. R [02/2013]
Page 33
OPTIONAL - RETURN AIR ACCESS PANEL
Optional Return Air Access Panel (With
Filter)
• Verify installation will provide adequate clearance and access to control panel.
• Work closely with other trades to locate opening for
NOTICE
Install air fi lter installed prior to operation.
return air access panel.
• Return air access panel must be installed with enough room available to remove unit if necessary.
• Install frame with screws through lag holes into frame studs, level and plumb (Figure 21).
• Return air access panel is set onto frame, and held in place with 6 screws.
Figure 21 Return Air Access Panel (Available with solid doors if ducted return air is used;
available in standard white or consult manufacturer for custom colors)
Return air access panel part numbers
(includes items 2, 5 and 6 below)
09–18 Part # 240003010C 19–24 Part # 240003013C 30–36 Part # 240004439C
Table 17 Return Air Access Panel Dimensions — Inches (mm)
Model A B C D E F G H J K Item Description
Solid door panel (for ducted return air installations)
1
2
Door assembly, front view
Door assembly, rear view
3
4
Filter bracket (on back)
09–18 Std.
19–24 Std.
29 3/4
(756)28(711)
29 3/4
(756)
28
(711)
49 3/4
(1264)30(762)
61 3/4
(1569)
30
(762)
17 3/4
(451)
28
(711)
20 1/4
(514)
20 1/4
(514)
20
(508)
30
(762)
20
(508)50(1270)
20
62
(508)
(1518)
477/8
(1220)
597/8
(1518)
(O.D.)
Frame assembly (items 5a are lag holes, 3 per side)
5
6
Filter
30–36 Std.
35 7/8
(911)
341/8 (864)
62
(1575)
36 7/8
(918)
17 5/8
(448)
33
9
/16
(852)
30
(762)
20
(508)
62
3/16
60
(1524)
P/N 240006980, Rev. R [02/2013] 33 Made in USA
Page 34
OPTIONAL - HYDRONIC COIL
HH Series Hydronic Coil Option
7.
(Available for VPRC / VPRH models 09-24 only)
Install Hydronic Coil option to unit BEFORE placing chassis
8.
in wall sleeve.
1.
Coil package includes sheet metal enclosure.
2.
2- or 3-way motorized 24v water valve is available (models 09–24 only).
3.
Verify hydronic coil package is left, right or front
System duct work is connected to discharge opening on duct collar or plenum. Flex collar is advised.
aligned, matching control section alignment of unit on which it is to be installed.
4.
Coil package must be centered on top of VPRC/VPRH chassis. Verify it is centered over fan discharge and piping package is in correct position.
5.
Two “Z” mounting brackets are used to clamp hydronic enclosure to chassis top. Mount brackets to chassis top using holes provided. Allows chassis to be removed for service/maintenance without disturbing hydronic pack­age.
6.
Complete piping of hydronic package, including fi eld supplied shut off valves and other fi eld supplied items.
Install threaded rods through slots in brackets (Figure
23), place washer and nut on threaded rod, tighten nut. Secure upper end of threaded rod to angle iron or 2 x 4 inch (51 x 102 mm) wood.
Verify rods do not interfere with chassis plenum or duct work. Rods hold the hydronic package in place when chassis is removed for maintenance.
Figure 22 Hydronic Coil Dimensions
Dimensions — Inches (mm)
Models A B C C1 D E F G H J K
9–18
13
(330)8(203)19(483)17(432)
10
(254)
Diameter
18
(457)9(229)
½
(13)
10
(254)5(127)1½(38)
19–24
17
(432)12(305)23(533)21(533)
10
(254)
Diameter
22
(559)11(279)
½
(13)
13
(330)6½(165)1½(38)
The Right Fit for Comfort 34 P/N 240006980, Rev. R [02/2013]
Page 35
OPTIONAL - HYDRONIC COIL
Figure 23 Hydronic Coil Option (front/right application shown)
1.
10-inch round (254 mm) duct collar
2.
Chassis top panel
3.
Z brackets (factory-supplied)
4.
Z bracket mounting screws (included)
5.
Freezestat
6.
Freezestat setpoint adjustment screw
7.
½ x ½ inch foam gasket
8.
Mounting rods (fi eld-supplied & installed), 5/16-18 all- thread
9.
5/16-inch nuts (fi eld-supplied & installed)
10.
Optional ball valves and P/T ports — includes (2) ball valves and (2) P/T ports
11.
Optional automatic balancing valves (with dual P/T ports)
12.
½-inch copper piping (factory-assembled when valve option is specifi ed)
13.
Bleed valve
P/N 240006980, Rev. R [02/2013] 35 Made in USA
14.
Return line automatic balancing valve, with drain cock in y.
15.
Supply line automatic balancing valve
16.
Flanges and nuts — fl ange is factory-installed with this option; automatic balancing valves are shipped with the HH, and are fi eld installed
17.
P/T ports
18.
Optional 3-way motorized diverting valve (normally closed), factory piped as shown when ordered
19.
Plug with wires to motorized valve (factory-wired to valve when valve is ordered)
20.
Plug with wires to freezestat (factory-wired to freeze stat)
21.
Optional ball valves
Page 36
OPTIONAL - HYDRONIC COIL
Figure 24 VPRC/VPRH Hydrocoil Specifi cations (Entering Air Temperature on 70°F, dry bulb/58°F,
wet bulb)
Unit Size CFM (L/s) GPM (L/s)
1 (0.163)
2 (0.126) 8400 2.46 4.0 3 (0.189) 8900 2.61 8.7 1 (0.163)
09 300 (142)
12 400 (189)
18 500 (236)
19 700 (330)
24 700 (330)
Note 1
Head loss data above is for hydronic coil only. The optional motorized 3-way valve has a Cv of 4.0; the optional AutoFlow valves have a Cv of 7.0 at full open.
2 (0.126) 10900 3.19 3.9 3 (0.189) 11500 3.37 8.6 1 (0.163) 2 (0.126) 13500 3.95 3.9 3 (0.189) 14200 4.16 8.4 1 (0.163) 2 (0.126) 9800 2.87 4.0 3 (0.189) 10400 3.05 8.7 1 (0.163) 2 (0.126) 12700 3.72 3.9 3 (0.189) 13500 3.95 8.6 1 (0.163) 2 (0.126) 15700 4.60 3.9 3 (0.189) 16600 4.86 8.4 2 (0.126) 4 (0.252) 12200 3.57 15.2 6 (0.379) 12700 3.72 33.2 2 (0.126) 4 (0.252) 15800 4.63 14.9 6 (0.379) 16400 4.80 32.6 2 (0.126) 4 (0.252) 19400 5.68 14.7 6 (0.379) 20100 5.89 32.0 2 (0.126) 4 (0.252) 28400 8.32 8.4 6 (0.379) 30300 8.87 18.5 2 (0.126) 4 (0.252) 36700 10.75 8.3 6 (0.379) 39200 11.48 18.2 2 (0.126) 4 (0.252) 45100 13.21 8.2 6 (0.379) 48100 14.08 17.9 2 (0.126) 4 (0.252) 28400 8.32 8.4 6 (0.379) 30300 8.87 18.5 2 (0.126) 4 (0.252) 36700 10.75 8.3 6 (0.379) 39200 11.48 18.2 2 (0.126) 4 (0.252) 45100 13.21 8.2 6 (0.379) 48100 14.08 17.9
Entering H2O
Temp F C
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
Btu/h (kW)
7300 2.14 1.1
9500 2.78 1.1
11800 3.46 1.0
8300 2.43 1.1
10800 3.16 1.1
13400 3.92 1.0
10900 3.19 4.0
14200 4.16 3.9
17500 5.12 3.9
23800 6.97 2.2
30900 9.05 2.2
38000 11.13 2.2
23800 6.97 2.2
30900 9.05 2.2
38000 11.13 2.2
Head Loss, Ft/H2O
(see note 1)
The Right Fit for Comfort 36 P/N 240006980, Rev. R [02/2013]
Page 37
OPTIONAL CARRIER 50QT/ET REPLACEMENT — INSTALLATION
Condenser Louver Replacement
• Existing Carrier wall sleeve can be retained in all applications, provided VPRC/VPRH unit is installed as required for 50QT/ET option.
• Condenser louver must be modifi ed or replaced unless it is aluminum vertical-bar type with no plastic or metal block-off as shown in Figure 25. Two other louver types are used on Carrier units.
• If you have aluminum vertical bar type louver with metal or plastic block-off (Figure 26), remove block-off for louver to function with VPRC/VPRH or use louver provided with VPRC/VPRH.
• If louver is stamped sheet metal (Figure 27), it must be removed and replaced with standard VPRC/VPRH louver provided with unit or warranty will be voided. Modify the louver application as needed for proper fi t and function of VPRC/VPRH.
Installing VPRC/VPHC Into An Existing Wall Sleeve/Enclosure
• Replacing another manufacturer’s unit with VPRC/ VPRH chassis requires certain modifi cations due to unit installation into existing wall sleeve and enclosure.
• Installer is responsible for proper installation practices when installing VPRC/VPRH in existing wall sleeve/ enclosure.
• Manufacturer will not be responsible for installation when accessories not included in supplied installation package are used.
!
DANGER
Electrical shock hazard — Verify power to existing unit (Carrier 50QT/ET) is disconnected before removing. Failure to do so will result in severe personal injury or death.
Figure 25 Aluminum Vertical Bar Louver
Without Block-Off, Can Be Used With The VPRC/VPRH as is
Figure 26 Aluminum Vertical Bar Louver
With Block-Off, Block-Off Must Be Removed To Use With VPRC/VPRH
Removing the metal or plastic block-off usually only requires drilling out a few pop rivets and is generally an easy task.
Figure 27 Stamped Metal Louver
Cannot Be Used With The VPRC/ VPRH — Use Standard Louver Shipped With VPRC/VPRH, Adapting Installation As Needed For Fit And Function
For proper installation into existing wall sleeve/enclosure, complete following steps as listed.
1.
Remove existing Carrier 50QT/ET unit from wall sleeve.
2.
Inspect wall sleeve. Verify it is free of dirt or debris and is in good condition. If condition is beyond repair, it must be replaced.
NOTICE
Carrier series use internal drain system. Verify existing drain system is in working condition and able to move condensate freely.
P/N 240006980, Rev. R [02/2013] 37 Made in USA
Page 38
OPTIONAL CARRIER 50QT/ET REPLACEMENT — INSTALLATION
VPRC/VPRH Models 09–12 only
1.
Attach three baffl es included in chassis kit to back of condenser coil. See Figure 29.
VPRC/VPRH Model 18
1.
Installer must fabricate and install air diverter to separate inlet and discharge outdoor air.
2.
Diverter must extend to condenser louvers. Failure to do so will create air recirculation between condenser discharge and intake creating compressor failure due to continued operation at high pressures, as well as decreasing unit’s capacity and effi ciency from rated values.
Models 09–18
3.
Install provided drain stub on unit’s base at front. See Figure 14, Page 18. Do not mount drain stub on side, unit inserts too deeply into Carrier wall sleeve. (If this
location is not acceptable, contact manufacturer for alternatives.) Connect drain stub to suitable drain.
4.
Insert VPRC/VPRH chassis 13 inches (330 mm) into wall sleeve. Verify it is level. When unit is in position, fasten in place permanently by mechanical means. Shimming chassis into position (i.e., by using wooden platform). If unit is completely removed, re-level to ensure proper condensate drainage.
5.
Verify seal is air tight between chassis and existing wall sleeve around condenser section. Manufacturer recommends using expandable foam or closed cell foam to create seal, preventing air bypass around chassis adversely affecting effi ciency, operation, and reliability of unit. Seal also prevents inclement weather from entering wall sleeve/interior of building.
6.
Install high and low voltage wiring to VPRC/VPRH unit. Refer to wiring diagram on the for wire connections.
7.
Connect supply air ductwork to VPRC/VPRH unit.
8.
Turn power on to unit.
9.
Confi rm operation by cycling unit several times, verify operation.
10.
Replace all trim and components.
NOTICE
Level chassis so condensate or wind-driven rain will fl ow from base pan. Installer, test and confi rm condensate fl ow into drain. Manufacturer recommends pouring water into base pan prior to operating unit to verify drain is operating properly.
Figure 28 Model 18 Add Diverter Extension
Add extension from separator baffl e to outside louver.
Use foam gaskets or other means to ensure tight seal. Required to prevent outdoor air recirculation inside existing wall sleeve.
Figure 29 Baffl es On Back Of Condenser Coil
Top Baffl e
Left
Baffl e
The Right Fit for Comfort 38 P/N 240006980, Rev. R [02/2013]
Right
Baffl e
Condenser Coil
Page 39
OPERATIONAL PERFORMANCE DATA
Table 18 VPRC/VPRH 09–36 Performance Data
INSTALLATION FOR NEW CONSTRUCTION
Model
Cooling
Btuh (kW)
Sensible
Heat Ratio
EER
Heat Pump
Btuh (kW)
COP
Air Flow vs External Static Pres-
0.10 in. w.c.
(2.5 mm
w.c.)
sure
Static Pressure
0.20 in. w.c.
(5.1 mm
w.c.)
0.30 in.
(7.6 mm
w.c.)
w.c.
Fresh
Air Inlet Flow
Outdoor
Sound
Level
VPRC09
VPRH09
VPRC12
VPRH12
VPRC18
VPRH18
VPRC19
VPRH19
9,000
(2.64)
9,000
(2.64)
12,000
(3.51)
12,000
(3.51)
17,200
(5.04)
17,200
(5.04)
18,400
(5.39)
18,400
(5.39)
CFM (L/s) CFM (L/s) CFM (L/s)
0.75 9.0 N/A N/A 330 (156) 300 (142) 250 (118)
0.75 9.0 9,000 (2.64) 3.0 330 (156) 300 (142) 250 (118)
0.70 9.0 N/A N/A 440 (208) 385 (182) 350 (165)
0.70 9.0
0.71 9.0 N/A N/A 600 (283) 550 (260) 500 (236)
0.71 9.0
0.73 9.0 N/A N/A 710 (335) 650 (307) 600 (283)
0.73 9.0
11,400
(3.34)
16,200
(4.75)
16,400
(4.81)
3.0 440 (208) 385 (182) 350 (165)
3.0 600 (283) 550 (260) 500 (236)
3.0 710 (335) 650 (307) 600 (283)
CFM
(L/s)
30 65
35 75
40 71
50 69
dBa
VPRC24
VPRH24
VPRC30
VPRH30
VPRC36
VPRH36
P/N 240006980, Rev. R [02/2013] 39 Made in USA
23,200
(6.80)
23,200
(6.80)
31,600
(9.26)
31,600
(9.26)
35,600
(10.43)
35,600
(10.43)
0.73 9.0 N/A N/A 710 (335) 650 (307) 600 (283)
0.73 9.0
0.69 9.0 N/A N/A
0.69 9.0
0.73 9.0 N/A N/A
0.73 9.0
21,600
(6.33)
32,000
(9.38)
36,000
(10.55)
3.0 710 (335) 650 (307) 600 (283)
3.0
3.0
1,190
(562)
1,190
(562)
1,350
(637)
1,350
(637)
1,170
(552)
1,170
(552)
1,290
(609)
1,290
(609)
1,130 (533)
1,130 (533)
1,210 (571)
1,210 (571)
60 70
95 69
95 69
Page 40
START-UP REPORT
In order for Technical Service to better serve you, please complete the following information.
Include Model Number, Serial Number, and Date of installation. Have this information ready when calling. Technical Support Department: (800) 228-9364
Model Number Date:
Technician:
Serial Number Mode: Cooling
Indoor Section Notes Evaporator Entering Air – DB Evaporator Entering Air – WB Evaporator Leaving Air – DB Evaporator Leaving Air – WB
Outdoor Section Entering Air Leaving Air Temperature Split
Operating Pressures Compressor Suction – PSIG Compressor Discharge – PSIG
Power Input Compressor – Volts Compressor – Amps OD Fan Motor – Volts OD Fan Motor – Amps ID Fan Motor – Volts ID Fan Motor – Amps Total Volts Total Amps
Temperatures – Degrees F° Compressor Suction Compressor Discharge Liquid Out Cond. Liquid before Expansion Suction out Evaporator
Capacity Calculations
DB – Temp Split at evap.
Test Summary Compressor Superheat Sub Cooling
The Right Fit for Comfort 40 P/N 240006980, Rev. R [02/2013]
Page 41
NOTES
P/N 240006980, Rev. R [02/2013] 41 Made in USA
Page 42
NOTES
The Right Fit for Comfort 42 P/N 240006980, Rev. R [02/2013]
Page 43
NOTES
P/N 240006980, Rev. R [02/2013] 43 Made in USA
Page 44
ECR International Inc
2201 Dwyer Avenue
Utica, NY 13501
e-mail: info@RetroAire.com
An ISO 9001-2008 Certifi ed Company
Loading...