RC/RH70 STRAIGHT COOL PACKAGED TERMINAL AIR CONDITIONER
INSTALLATION, OPERATION & MAINTENANCE GUIDE
P/N# 240001229, Rev. 1.2 [03/06]
Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!!
Examine the exterior. Remove cover and examine compressor and piping for signs of damage.
This manual is intended as an aid to qualified service
personnel for proper installation, operation, and maintenance
of the RetroAire R C/RH70 Packaged Terminal Ai r
Conditioner (PTAC). Read these instructions thoroughly
and carefully before attempting installation or operation.
Failure to follow these instructions may result in improper
installation, operation, service, or maintenance, possibly
resulting in fire, electrical shock, property damage, personal
injury, or death.
TO THE INSTALLER
(1) Retain this manual and warranty for future refer-
ence.
(2) Before leaving the premises, review this manual
to be sure the unit has been installed correctly and
run the unit for one complete cycle to make sure
it functions properly.
To obtain technical service or warranty assistance
during or after the installation of this unit, contact
your local representative.
retroaire.com for a local representative listing. For
further assistance call 1-800-228-9364.
When calling for assistance, please have the fol
lowing information ready:
Visit our website www.
-
Read all instructions before using the RetroAire
RC/RH70 PTAC. Install or locate this unit only
in accordance with these instructions. Use this
unit only for its intended use as described in this
manual.
Check the rating plate on the RetroAire RC/RH70
PTAC before installation to make certain the voltage shown is the same as the electric supply to
the unit.
The RetroAireRC/RH70 PTAC must be connected
only to a properly grounded electrical supply. Do
not fail to properly ground this unit.
Turn off the electrical supply before servicing the
RetroAire RC/RH70 PTAC.
Do not use the RetroAire RC/RH70 PTAC if it has
damaged wiring, is not working properly, or has
been damaged or dropped.
SAFETY INSTRUCTIONS
[Save these instructions]
• Model Number_________________________
• Serial Number_________________________
• Date of installation______________________
Recognize this symbol as an indication
!
The Right Fit For Comfort
of important safety information
!
DANGER
!
The RetroAire PTAC must:
Be connected to a properly grounded electri-
cal supply with the proper voltage as stated
on the rating plate.
Have proper over current protection (i.e.
time- delay fuse/HACR-Breaker) as listed
on the Rating Plate.
Failure to follow these instructions can result
in a fire, explosion, or electrical shock causing
property damage, personal injury, or death.
2
!
www.retroaire.com
Page 3
TABLE OF CONTENTS
To the Installer and Safety Instructions ................2
Warnings and Installer Responsibilities ...............3
This manual has been prepared to acquaint you with the
installation, operation and maintenance of this RetroAire
RC/RH70 PTAC and to provide important safety information in these areas.
We urge you to read all of the instructions thoroughly before
attempting the installation or operation of this unit. This
manual should be kept for future reference.
The manufacturer of this unit will not be liable for any dam
ages caused by failure to comply with the installation and
operating instructions outlined in this manual.
A rating plate identifying this RetroAire RC/RH70 PTAC
can be found on the unit. When referring to your unit, al
ways have the information listed on the rating plate readily
available.
MODIFICATION AND TAMPERING
DANGER
!
Tampering with the RetroAire RC/RH70 PTAC
is dangerous and may result in serious injury
or death. Tampering voids all warranties. Do
not attempt to modify or change this unit in
any way.
IMPORTANT SAFETY FEATURE
Power Cord With Integral Safety Protection
All PTACs rated 250
to the power supply are equipped with a power cord
with integral safety protection as standard. Providing
personal shock protection as well as arcing and
fire prevention, the device is designed to sense
any damage in the line cord and disconnect power
before a fire can occur. Tested in accordance with
Underwriters Laboratories, the cord set also offers a
unique “passive” operation, meaning the unit does not
require resetting if main power is interrupted.
WARNING - A DAMAGED POWER SUPPLY CORD
-
-
MUST BE REPLACED WITH A NEW CORD FROM
THE MANUFACTURER, AND NOT REPAIRED.
Each power cord should be checked before every
use. Follow the instructions in the order listed on the
device.
WARNING - DO NOT USE THE PRODUCT IF THE
UNIT FAILS THE TEST.
V or less that are cord connected
!
Completely read all instructions prior to assembling, installing, operating, or repairing
this product. Inspect all parts for damage prior to
installation and start-up. The RetroAire RC/RH70
PTAC must be installed ONLY by qualified instal-
lation personnel.
The Right Fit For Comfort
WARNING
!
Note: Unit uses R22 refrigerant.
3
!
www.retroaire.com
Page 4
PRODUCT DESCRIPTION
REFRIGERATION CIRCUIT
The RetroAire RC/RH70 replacement chassis is a conditioner designed to allow owners of Emerson and Sears
Model 8T Over-the-Door or High Wall units to upgrade the
performance of their room conditioning and achieve current
efficiency standards.
This unit is available as a cooling only model or for those
who wish to upgrade to a heat pump, the RH 70 will fit the
existing wall opening. The heat pump version will reduce
energy costs during periods of outdoor temperature ranging
down to as low as 35°.
With Energy Efficiency ratings as high as 9.0, the
replacement of worn out and inefficient units becomes a
very attractive option. The RC/RH70 are sold with a wall
mounted thermostat, mounting brackets and electric heat
included, eliminating the need for optional equipment.
Whisper quiet operation improves the room ambiance
and a washable permanent filter makes service a snap. The
heavy gauge, Galvaneal steel construction of the cabinet
and baked enamel paint finish ensures long service life.
All RetroAire products are backed by EMI and ECR
International and are tested and rated in accordance with
ARI Standards 310 & 380 and UL 484. A full service parts
inventory is always available.
CAPACITIES
• High Efficiency, rotary compressor with a five-year
warranty.
• Heat Pump heating operates as low as 35° outdoor
temperature.
• Heat Pumps include adjustable change-over temperature point and emergency heat position.
OPTIONS
• The RC/RH 70 units are complete as delivered and
require no optional equipment. Electric heat option
can be either 2KW or 3KW.
INSTALLER SUPPLIED ITEMS
NOTE: Proper electrical supply (see unit rating place
on unit)
• Low voltage thermostat wire
• Optional wire mold to cover thermostat wire
• Outdoor condensate removal piping (required on
Heat pump-optional, on straight cool units with
electric heat)
The RC/RH70 Replacement Chassis are available in
nominal capacities of 9,000 & 12,000 Btuh.
AIR SYSTEMS
• Fan is forward curved type, directly mounted to the
motor shaft.
• Motors are PSC type with overheat protection.
• Air stream surfaces are insulated with ¼” fiberglass
or 1/8” Volara™.
• Filter is permanent, washable mesh.
HIGH EFFICIENCY HEAT EXCHANGER
Coil is seamless, copper tubing, arranged in staggered
configuration, with enhanced aluminum fins, tested to
460 psig. The tubes are mechanically expanded for
secure bonding to fin shoulders.
• Fasteners to mount chassis to outside of building
ITEMS FOR CONSIDERATION
(New Installation)
Select a location that will allow ease of electrical wiring for
power supply.
Locate on a wall that will supply the best airflow to room
being conditioned.
Routing of low voltage thermostat wire for room thermostat.
Building construction when cutting opening into wall.
The Right Fit For Comfort
4
www.retroaire.com
Page 5
SITE PREPARATION
NEW INSTALLATION
Select location to cut a 30
1
/4” x 10 5/8”opening in wall. Check
for electrical lines. Plumbing or heating equipment in wall
before cutting into wall
IMPORTANT!
Check for Electrical Lines BEFORE CUT-
TING INTO WALL
Run line voltage power to equipment site. Electrical plug
should be within 18” of either side of the EMI chassis. Refer
to unit rating plate for circuit ampacity and breaker/fuse size.
Use only HACR type breakers. Select the proper wire for
ampacity rating. Run low voltage wiring for wall-mounted
thermostat. All wires must be run in accordance with NEC
and local codes for class 2 wiring.
Run the following number of 24 Volt wires to thermostat
Straight cool with electric heat – 4 wires
Heat Pump with electric heat – 3 wires
It is common practice to run one (1) additional low voltage
wire.
Low voltage wires may be run inside the wall or along the
exposed wall and covered with wire molding.
REPLACEMENT OF EXISTING UNIT
1. Disconnect power. Unplug cord or turn off circuit
breaker. Disconnect power wires.
2. Remove and discard old unit from wall opening.
Clear opening of insulation or other debris. A clean,
level surface is necessary for proper mounting and
sealing of the RetroAire chassis. Check the size
of the wall opening. Minimum acceptable opening
is 30
½” wide, by 11” high.
3. Inspect power supply for damage to wiring. Deter
mine circuit ampacity to assure proper connection
to RetroAire chassis. Check unit rating plate for
circuit ampacity and breaker or fuse size. Use only
HACR type breakers.
IMPORTANT:
Unit should have its own plug. Never
run an extension line cord.
RC/RH70 INSTALLATION KIT
• 1 Installation Manual
• 4 #8x3/8 Screws
• 1 7/8 to 3/8 Bushing
HYDRONIC
ONLY
• 1 Nipple, Galv. 1 ½ x ¼
MOUNTING THE UNIT
1. Attach mounting angle
brackets (Figures # 1 &
2) to chassis, keeping the
short side to the unit.
NOTE:
When brackets are
mounted to wall, the unit
should pitch outward approximately 1/2” to 1/4” to aid
in the removal of condensate
by use of the condensate fan
slinger ring. (Figure #2)
INSTALLATION INSTRUCTIONS
• 1 Thermostat, One Stage
• Mounting Bracket
Figure 1
3/4”
Mount this
side to unit
Figure 2
Mounting Angle
OPTIONAL¼”nipple for
condensate removal piping,
3/8” MPT. Either side.
Pfitch down
½” to ¼”
2. From the outside, slide unit into opening in wall. Secure
the unit to the wall from the outside, through the wall
mounting angles on the unit chasses. (Figure #2) Use
the appropriate anchoring device for building construction type. (Not supplied by RetroAire.) Inspect unit for
pitch. (Figure #2)
3. Seal unit to building with caulk, insulating foam or other
weatherproofing material.
The Right Fit For Comfort
1”
5
www.retroaire.com
Page 6
INSTALLATION INSTRUCTIONS Continued
CONDENSATE REMOVAL (Stright Cool Only)
When the heat pump model is run in the heating mode, the
outdoor side to the unit will produce condensate water which
must be removed. To remove condensate: Remove rubber
plug on either side of base pan of the outdoor side. This
will allow the water to drain out of the chassis. The water
may need to be piped away from the area to prevent safety
problems. When running condensate removal piping, a 3/8”
MPT pipe may be threaded into the chassis.
ELECTRICAL CONNECTIONS
High Voltage Connection
All wiring should be in accordance with the National Electric Code (NEC) and the local building codes.
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure
it in an open position during installation. On a plug and
receptacle connection, keep the unit unplugged until
installation is complete.
WARNING
!
!
(Figure #2)
LOW VOLTAGE Connection
Place the 7/8” x 3/8” plastic bushing provided in cabinet
hole above line cord connection.
Route leads through this bushing.
When left side connections are used, cut low volt leads to
desired length for connection outside unit. Wire lengths
provided are for right-hand connection.
NOTE* When using the right side connections for low
volt wiring, it is necessary to route these wires along
with the line cord. You will need to secure down at the
tie base and wire tie along the line cord where necessary to prevent movement.
Using wire nuts supplied in junction box, make electrical
connection L1, L2, and ground. Replace junction box
cover.
FINAL INSPECTION AND STARTUP
1. Inspect the existing wiring for any deficiencies such as
cut or frayed wires. Replace such wiring if found.
2. Check the unit rating plate for circuit ampacity and
breaker or fuse size. Use only HACR type breakers.
Select the proper wire for the ampacity rating.
3. If plug and receptacle are used, check the compatibility. The
chassis can be hard wired or direct connected as well.
4. Each unit must have a separate branch ciruit protected
by a fuse or breaker. Refer to the unit rating plate for
the proper wire and breaker or fuse size. Use of exten-sion cords is prohibited.
DANGER
!
The RetroAire PTAC must:
Be connected to a properly grounded electrical supply
with the proper voltage as stated on the rating plate.
Use the proper maximum over current protection
device stated on the rating plate.
!
When the unit is first powered up, high humidity conditions can cause condensation to form on the discharge
grill. Keep doors and windows closed to reduce humidity
and condensation will evaporate.
1. Make sure the chassis is level. Check by pouring water
into the drain pan and making certain it flows through
the drain hoses to the condenser side of the unit.
2. Plug or hard wire line voltage to unit.
IMPORTANT: Follow the information provided on
the rating plate for voltage and amperage/fuse size
for proper supply.
3. Attach the front panel to the existing cabinet enclosure.
4. Turn the power on.
5. Check for proper operation (i.e., cooling, optional fresh
air, and heating if supplied).
CAUTION
!
!
The use of extension cords is prohibited.
Failure to follow these instructions can result in a fire,
explosion or electrical shock causing property dam
age, personal injury or death.
The Right Fit For Comfort
6. Check to be sure nothing will interfere with the room
discharge air or the return air to the units (i.e., curtains
or drapes that obstruct the air flow or plush carpeting
-
that can obstruct the return air (see below)). Items like
these can cause serious damage to the chassis and
can void the warranty.
6
www.retroaire.com
Page 7
SEQUENCE OF OPERATION
UNIT MOUNTED AND
REMOTE THERMOSTAT CONTROLS
RetroAire units can be equipped with unit mounted or
remote controlled thermostats. Turning the unit mounted
thermostat knob to the far left will produce the warmest
room temperature while turning it all the way to the right
will produce the coolest. These settings can be adjusted
for personal comfort.
CAUTION
!
Avoid rotating the thermostat knob back and forth
from heating to cooling. This causes the compressor to cycle on and off rapidly and WILL cause
damage to the compressor. Allow the compressor
to remain off for at least three minutes prior to
restarting the unit.
COOLING CYCLE
1. Place system switch in the “COOL” position.
2. Rotate thermostat knob (Figure A) clockwise until the
compressor fans start running and cold air begins to
flow from the unit. For a colder room temperature,
continue turning the thermostat knob
let the unit continue operating to cool the room and
remove humidity. If a warmer room temperature is
desired, rotate the thermostat knob counter-clockwise
until the compressor cycles off.
!
clockwise and
IMPORTANT: Room temperature must be below
85º F to energize the heater.
3. Place system switch in the “OFF” position. All operation should stop.
MOTORIZED FRESH AIR DAMPER
(Optional)
The optional motorized fresh air damper allows the operator
to move fresh air into the space to be conditioned. This is
done by placing the damper door switch in the
tion, opening the damper door and allowing fresh air to be
moved into the space. To stop the flow of fresh air, simply
place the switch in the “NO” position.
CHANGEOVER T-STATS
(Heat Pump Only)
On units with a changeover thermostat, the compressor
can run to an outdoor temperature of 40° F and then shut
off. Electric heat will then energize and assume the heat
ing demand until the temperature of the outdoor air rises
to approximately 50° F.
FAN CYCLE SWITCH
This option allows the operator of the
have the evaporator fan cycle or run continuously. With the
switch in the cycling position the evaporator fan will only run
when the unit is calling for heat or cooling. When the switch
is in the “CONSTANT” position, the evaporator fan will run
continuously unless the unit is physically turned off.
CONDENSATE REMOVAL
Dual Motor PTAC to
“YES” posi-
-
IMPORTANT:
65º F for the compressor to operate.
3. Place system switch in the “OFF” position. All operation should stop.
1. Place system switch in the “HEAT” position.
2. Rotate thermostat knob counter-clockwise until the
indoor fans start running and the electric coil starts
emitting heat. The condenser fans do not run during
the heating cycle unless the chassis is a heat pump.
After the unit starts running and the area gets warmer,
turn the thermostat knob clockwise until a slight click
is heard and the electric heater turns off. If a warmer
room temperature is desired, continue turning the knob
counter-clockwise and let the unit continue operating.
If a cooler room temperature is desired, rotate the
thermostat knob clockwise until the electric heater
cycles off.
The Right Fit For Comfort
The room temperature must be above
HEATING CYCLE - ELECTRIC
The Dual Motor PTAC has a drain connection at each end
of the condensate drain pan. This allows the condensate to
drain through the bulkhead to the area near the condenser
fan. The condenser fan has a slinger ring that picks up the
condensate and slings it on the hot condenser coil where it
evaporates. On heat pump models condensate can form on
the outdoor coil during the heat pump cycle. A temperature
sensitive valve in the base pan will allow condensate to flow
to an internal piping system or external drain kit (supplied
by others).
AQUASTAT CONNECTION
(Optional)
All straight cool Dual Motor PTACs are supplied with a
standard high volt aquastat connection. The connection
is located on the bottom or side with a black jumper wire
installed in molex. To wire option take jumper wire and cut
in half. Then connect 2 field supplied wires to the cut ends
of jumper and wire to aquastat (see wiring diagram for more
information). If option is not being used simply leave jumper
wire connected to unit.
7
www.retroaire.com
Page 8
OPERATION AND MAINTENANCE
Before servicing the RetroAire Dual Motor PTAC, be
sure to turn off electrical power to the unit. Failure to
do so can result in a fire, explosion or electrical shock
causing property damage, personal injury or death.
The front cabinet should remain on the unit at all times.
Service should be performed by a qualified service
agency.
Remote Thermostats:
A. Remote thermostats will require operation ac
cording to standard thermostat settings. Refer to
operating instructions of the particular thermostat
used.
B. Heat pump models will contain a change over
thermostat. The compressor will run until just
above freezing; then compressor will shut off and
the electric heat will come on until the temperature
of the condenser coil rises above freezing then
compressor will re-start.
DANGER
!
OPERATION
MAINTENANCE
!
-
2. Regular cleaning of the air filter is required. The
filter is removed by lifting the discharge louver and
locking top hinges in open position. Disconnect filter from clips. It may then be cleaned by a vacuum
cleaner or garden hose. Allowing dust to collect on
the filter will cause the unit to lose efficiency and
eventually malfunction. Check filter at least once
each month.
3. Vacuum dust from the return air grille surface when
cleaning the filter.
4. Clean the exterior of the cabinet as desired. Use
a mild household cleaner.
TROUBLESHOOTING GUIDE
A. If compressor will not start, check to see if the
thermostat is satisfied. If the thermostat is not
satisfied, check for proper wiring and that relays
are not damaged.
NOTE: CR/relay – cooling relay
HR/relay – heating relay
B. If there is no electric heat, check to see if heater
contacts pull in. Possible problems could be the
heat relay, limit switch or fuse link.
RetroAire units are designed and constructed for reliability
and long life with minimal maintenance. You can assure
peak operating efficiency by:
Service should be performed by a QUALIFIED service
agency.
RetroAire units are designed and constructed for reliability
and long life with minimal maintenance.
1. This unit is equip ment with a permanently lubricated
motor. Although oiling is not necessary, adding a
few drops through the oiling ports twice yearly will
extend the life of the motor. Do not over oil.
The Right Fit For Comfort
C. If you are unable to find any of these problems
consult with a factory for further information.
8
www.retroaire.com
Page 9
CLEANING AND MAINTENANCE
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when servicing a RetroAire Dual Motor PTAC.
CLEANING THE INTERIOR OF THE UNIT
1. Disconnect power from unit.
2. Remove access panels and do a visual inspec
tion of the unit, making sure to check for obvious
problems such as damaged coils or evidence of
extended wear on any moving part.
3. Check for unusual odors, oil leaks, or stains on or
around the coil and refrigerant lines. The presence
of oil here may indicate a potentially serious problem
such as a refrigerant leak.
4. Inspect all electrical connections. Look for frayed
wires and poor connections.
loose will eventually fail, causing a loss of performance or worse.
WARNING
!
!
-
Terminal ends that are
8. Inspect and clean the drain pan and drainline (if
any). Use of an anti-fungicide tablet is recommended to keep the condensate system free from
bacterial contaminants.
9. Check weep holes along the rear flange of the base
pan, making sure they are open.
10. Check the pitch of the unit. Over time the building
and equipment may settle, causing a shift in the
direction of the condensate flows. Ideally the unit
should pitch a minimum of 5° (at least ½”) to the
outside to allow for proper drainage.
11. Replace panels and reconnect electrical power.
12. Test unit operation.
CLEANING THE EXTERIOR
1. Clean the air filter
ing it from the unit and washing or vacuuming any
dust from its surface. Allowing dust to collect on
the filter will cause the PTAC to lose efficiency and
eventually malfunction.
at least once a month by remov-
5. Check fan motors and blower assemblies.
units may require a drop of light oil to motors and/
or bearing assemblies (look for oil cups). Check
setscrews and motor mounting hardware, making
sure they are tight.
6. Brush and/or vacuum the centrifugal fan blades
and blower cage assemblies. These parts must be
clean to operate efficiently.
7. Inspect and clean the indoor
using a fin comb, if necessary, to straighten any
damaged fins. these coils must be clean for proper
operation.
IMPORTANT:
on the indoor or outdoor coils. Some solvents can
produce a noxious odor when starting the fan or
electric heat.
Do not use a solvent-based cleaner
and outdoor coils,
Some
2. When cleaning the filter, be sure to vacuum any
dust from the return air grille surface as well.
3. Clean exterior of the cabinet as desired with a mild
soap or household cleaner.
IMPORTANT:
RetroAire Dual Motor PTAC, consult factory for availability and/or proper sizing.
• If the compressor will not start, check to see if the
thermostat is satisfied. If the thermostat is not
satisfied, check for proper wiring and make sure
that relays are not damaged.
• If there is no electric heat, see if heater contacts
pull in. Possible problems could be the heat relay,
limit switch, or fuse link.
• If you are unable to find any of these problems,
contact the factory for further information.
IMPORTANT: Due to RetroAire’s on going development programs, designs and specifications may change without notice.
Please consult factory for the latest information and submittal data before making any job site updates.
Dimensions
RC70 Performance Data*
Unit
Size
Cooling
BtuhEER’s
Heat Pump
Btuh
098,6008.68,5002.8270
1211,5009.011,0002.7270
* Due to the ongoing product developm ent and use of
alternate components (compressors, motors, etc.) to meet
production requirements, performance data is subject to
change without notice. Consult factory for most current
performance data.
COP
Evaporator
CFM Hi
RC70 Electrical Specifications
Model
Number
9
12
Voltage/Hz/
Phase
115/60/1
208/230/60/1
265/60/1
115/60/1
208/230/60/1.40.300.7.1254.826.35.906.9151976-20P
265/60/1
Evap MotorCond Motor Compressor
FLAHPFLAHPRLA LRA
.75.301.6.1257.444.09.7511.5151046-15P
.40.300.7.1253.820.04.906.3151976-15P
.40.300.7.1253.318.64.405.4152407-20P
.75.301.6.1259.754.012.0514.5201045-15P
.40.300.7.1254.228.05.306.2152407-20P
RC70 Optional Electric Heat Specifications
Heater No. VoltageWattsBtuhAmps
2081,6505,9007.98.410.4156-15P
2
3
2302,0007,1008.79.211.4156-15P
2652,7009,50010.210.713.3157-20P
115
2082,5008,80012.012.515.5206-20P
2303,00010,50013.013.516.8206-20P
2654,00013,90015.115.619.4207-20P
2774,40015,30015.916.420.4207-20P
7502,8506.57.08.7155-15P
NEMA SpecificationsNon-Locking/Receptacles
Total Heat
Amps
Total
Amps
MCA
Ampacity Max Fuse Line Cord
Max
Fuse
Voltage
Min
Line
Cord
The Right Fit For Comfort
10
www.retroaire.com
Page 11
ALL PRODUCT LIMITED WARRANTY
Enviromaster International Corporation LLC (EMI) warrants to the purchaser/owner, that the EMI products
will be free from defects in material and workmanship under the normal use and maintenance for a period of
twelve months for all components, and (60) months on unit compressors from date of the original installation
or 15 months for all components and 63 months on unit compressors from the date of original sale whichever
comes first.
WHAT WE WILL COVER
EMI will replace any defective part returned to EMI’s approved service organization with a new or rebuilt part
at no charge. The replacement part assumes that unused portion of this warranty.
WHAT WE DON’T COVER
THIS WARRANTY DOES NOT INCLUDE LABOR or other costs incurred for repairing, removing, installing,
shipping, servicing, or handling of either defective or replacement parts.
EMI IS NOT RESPONSIBLE FOR
• Normal maintenance
• Damage or repairs required as a consequence of faulty installation or application by others.
• Failure to start due to voltage conditions, blown fuses, open circuit breakers, or other damages due to
the inadequacy or interruption of electrical service.
• Damage or repairs needed as a consequence of any misapplication, abuse, improper servicing, unauthorized alteration, or improper operation.
• Damage as a result of floods, winds, fires, lightning, accidents, corrosive atmosphere, or other conditions beyond the control of EMI.
• Parts not supplied or designated by EMI.
• Products installed outside the United States or Canada.
• Any damages to person or property of whatever kind, direct or indirect, special or consequential,
whether resulting from use or loss of use of the product.
LIMITATION OF WARRANTIES
This Warranty is exclusive and in lieu of any implied warranties of merchantability and fitness for a particular
purpose and all other warranties express or implied. The remedies provided for in this warranty are exclusive
and shall constitute the only liabilities on the part of EMI including any statements made by any individual
which shall be of no effect.
FOR SERVICE OR REPAIR:
1) Contact the installer
2) Call the nearest distributor
3) Contact the factory
ENVIROMASTER INTERNATIONAL LLC
5780 Success Drive, Rome, NY 13440
Email: info@retroaire.com
The Right Fit For Comfort
11
www.retroaire.com
Page 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.