Retroactive R10C, R20H, R35C, R35H, R45C Installation, Operation & Maintenance Manual

...
Page 1
R10C/H R20C/H R35C/H
R45C/H
e Right Fit for Comfort
and R20C with Fedders
Unizone Option
Packaged Terminal Air Conditioner (PTAC)
Packaged Terminal Heat Pump (PTHP)
Installation, Operation,
& Maintenance Manual
ECR International Inc 2201 Dwyer Avenue Utica, NY 13501 e-mail: info@RetroAire.com
An ISO 9001-2008 Certied Company
P/N 240010328, Rev. A [10/15/2013]
Page 2
TABLE OF CONTENTS
Receiving Information .................................................................................................... 3
Important Safety Information ......................................................................................... 4
Performance Data .......................................................................................................... 5
Dimensional/Physical Data .............................................................................................. 6
Product Description ....................................................................................................... 9
PTAC/PTHP Installation Preparation .................................................................................14
Installation Instructions — R10C | R10H ..........................................................................15
Installation Instructions — R20C| R20H ..........................................................................17
Installation Instructions — R20C With Fedders Uni-Zone Option ..........................................19
Installation Instructions — R35C| R35H ...........................................................................21
Installation Instructions — R45C | R45H ..........................................................................23
Sequence Of Operation .................................................................................................25
Inspection & Start-Up ...................................................................................................28
Maintenance ................................................................................................................34
Troubleshooting ...........................................................................................................36
Hydronic Heat Performance ............................................................................................37
Electrical Specications .................................................................................................38
Warranty .....................................................................................................................43
NOTICE
RetroAire™ replacement PTAC/PTHP is backed by ECR International and is tested and rated in accordance with: AHRI Standards 310/380 UL-484
Information and specications outlined in this manual in effect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specications or system design at any time without
The Right Fit for Comfort 2 P/N 240010328, Rev. A [10/15/2013]
notice and without incurring any obligation, whatsoever.
Page 3
RECEIVING INFORMATION
Shipping damage MUST be reported to the carrier IMMEDIATELY.
Examine exterior.
Remove cover and examine compressor and piping for signs of damage.
Inspection
Check shipment against bill of lading.
Verify equipment received as ordered.
Verify unit:
• Unit size and type correct per submittal sheet and job requirements?
• Voltage correct?
• Hydronic coil included, if required? Piping located as required?
• Factory installed options installed?
• All eld installed options included?
Inspect each component for damage. Concealed damage must be reported to carrier within 15 days of receipt of shipment.
• Carrier must make proper notation on delivery receipt
of all damage identied and complete carrier inspection report.
Purchaser must notify Manufacturer’s Service department of all damage and is responsible for ling any necessary claims with carrier.
General Information
Installation shall be completed by qualied agency. this manual and warranty for future reference.
Installer review this manual to verify unit has been installed correctly. Run unit for one complete cycle to verify proper function.
To obtain technical service or warranty assistance during or after installation, contact your local representative.
Visit our web site www.retroaire.com for local representative listing.
For further assistance call 1-800-325-5479.
When calling for assistance, please have following information ready:
Model Number_________________________
Serial Number_________________________
Date of installation______________________
Retain
Customer Service : (800) 228-9364
P/N 2400103028, Rev. A [10/15/2013] 3 Made in USA
Page 4
IMPORTANT SAFETY INFORMATION
All eld wiring shall conform to requirements of authority having jurisdiction or in absence of such requirements:
• United States - National Electrical Code, ANSI/NFPA 70
• Canada - CSA C22.1 Canadian Electrical Code Part 1.
!
WARNING
Fire, explosion, and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
Become Familiar With Symbols
Identifying Potential Hazards.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury.
Safety Information
• Installation by qualied personnel.
• Turn off electrical supply before servicing unit.
• Inspect all parts for damage prior to installation and start-up.
• Do not use unit if it has damaged wiring, is not working properly, or has been damaged or dropped.
• Connect to properly grounded electrical supply with proper voltage as stated on rating plate.
• Have proper over current protection (i.e. time- delay fuse/HACR Breaker) as listed on Rating Plate.
• Connect unit to properly grounded electrical supply. Do not fail to properly ground this unit.
• Tampering voids all warranties.
!
WARNING
Tampering with PTAC/PTHP is dangerous and could result in serious injury or death. Do not modify or change this unit.
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
The Right Fit for Comfort 4 P/N 240010328, Rev. A [10/15/2013]
Page 5
Table 1 Performance Data - Cooling
PERFORMANCE DATA
Models
R10C R20C
R35C
R45C
R_ _C 09
R_ _C 12
R_ _C 15
R_ _C 18 D 208/230 15600 (4.6) 7.7 0.67
Voltage
A 115 9000 (2.7) 9.0 D 208/230 E 267/277 440 (207.7 A 115 11900 (3.5)
D 208/230 E 267/277
D 208/230
E 267/277 450 (212.4)
Cooling
Capacity
Btuh (kW) CFM (L/S) CFM (L/s) dBa lbs (Kg)
9400 (2.8) 8.9
11700 (3.4)
14400 (4.2) 7.8 0.69
Table 2 Performance Data - Heating
Models
R10H R20H
R35H R45H
Voltage
Cooling
Capacity
Btuh (kW)
EER
Indoor
Air Flow
Cooling
CFM (L/S) Btuh (kW)
Sensible
EER
8.4 0.66
Heat
Ratio
0.79
Heating
Capacity
Indoor Air
Flow
440 (207.7) 350 (165.2)
400 (188.8) 350 (165.2) 440 (207.7)
400 (188.8)
380 (179.3)
Indoor
Air Flow
COP
Heating
CFM (L/S) CFM (L/S) dBa
Fresh Air
Inlet Flow
35 (17) 75 140 (63.5)
50 (24) 69 140 (63.5)
60 (28) 70 140 (63.5)
95 (45) 69
Sensible
Heat
Ratio
Outdoor
Sound
Fresh Air
Flow
Level
Shipping
Weight
140 (63.5)
Outdoor
Sound
Level
Shipping
Weight
lbs
(Kg)
R_ _H 09
R_ _H 12
R_ _H 15
D 208/230
E 267/277
D 208/230
E 267/277
D 208/230
E 267/277
8800 (2.6)
9400 (2.8)
11400 (3.3)
14000 (4.1)
Table 3 Nominal Capacities
9,000 12,000 15,000 18,000 Btuh
8.9
350 (165.2) 8500 (2.5
8.8
440 (207.7) 9100 (2.7) 450 (212)
350 (165.2)
8.4
400 (188.8) 450 (212)
400 (188.8)
7.8
450 (212.4)
11200 (3.3) 2.6
14200 (4.2)
2.7
2.5
400 (189)
400 (189)
450 (212)
500 (236)
0.79
0.66
0.69 60 (28) 7070
Straight Cooling Nominal Capacities
2.6 3.5 4.4 5.3 kW
Heat Pump Nominal Capacities
35 (17)
50 (24) 69
75
140
(63.5)
9,000 12,000 15,000 Btuh
2.6 3.5 4.4 kW
P/N 2400103028, Rev. A [10/15/2013] 5 Made in USA
Page 6
DIMENSIONAL/PHYSICAL DATA
Figure 1 R10C
R10H Dimensions - Inches (mm)
Figure 2 R20C
R20H Dimensions - Inches (mm)
The Right Fit for Comfort 6 P/N 240010328, Rev. A [10/15/2013]
Page 7
CABINET
WALL SLEEVE
AIR FILTER 8" x 30"
PERMANENT
ALUMINUM MESH
[374]
14 3/4"
[100]
4"
[25]
1"
26"
[660]
43"
1091
47"
[1194]
[464]
18 1/4"
DIMENSIONAL/PHYSICAL DATA
Figure 3 R20C With Fedders Unizone Option - Dimensions - Inches (mm)
[102]
4"
Figure 4 R35C
R35H Dimensions - Inches (mm)
P/N 2400103028, Rev. A [10/15/2013] 7 Made in USA
Page 8
DIMENSIONAL/PHYSICAL DATA
Figure 5 R45C
R45H Dimensions - Inches (mm)
The Right Fit for Comfort 8 P/N 240010328, Rev. A [10/15/2013]
Page 9
PRODUCT DESCRIPTION
Figure 6 R10C
Rating
Plate
R10H Chassis
Aquastat Connection
(Factory) Installed
Hydronic Connection
Electrical
Diagram
jumper
MTR Valve
Valve Switch (Hydronic Only)
Fresh Air
Switch
(FAS)
Thermostat
Hydronic
NO/NC Switch
Valve Orientation
Switch (VOS)
Line
Cord
Fan
Cycle
Switch
(FCS)
High
Pressure
Switch
(HPS) reset
Fresh Air
Switch
(FAS)
Unit Mount
Fan
Speed
Switch
(FSS)
System
Switch
(SS)
Remote
Fan
Speed
Switch
(FSS)
Figure 7 R20C
Fresh Air
Switch
(FAS)
Fresh Air
Switch
(FAS)
Thermostat
R20H Chassis
Remote Mount
Fan
Speed
Switch
(FSS)
Fan Speed Switch
(FSS)
System
Switch
(SS)
Line
Cord
High Pressure
Switch (HPS)
reset
Rating
Plate
Electrical Diagram
Fan Cycle
Switch (FCS)
Aquastat Connection
(Factory) Installed
jumper
Hydronic
Connection
MTR Valve
P/N 2400103028, Rev. A [10/15/2013] 9 Made in USA
Page 10
PRODUCT DESCRIPTION
Figure 8 R20C With Fedders Uni-Zone Option
Fresh Air
Switch
(FAS)
Unit mount & Remote Mount
System
Switch
(SS)
Line
Cord
Fan
Speed
Switch
(FSS)
High
Pressure
Switch
(HPS)
Cord
Fan
Cycle
Switch
(FCS)
Aquastat
W/ Jumper
MTR Valve
Line
Rating
Plate
Electrical
Diagram
Figure 9 R35C
High
Pressure
Switch
(HPS)
MTR Valve
Aquastat
W/ Jumper
Fan
Cycle
Switch
(FCS)
R35H Chassis
Electrical
Diagram
Hydronic
NO/NC Switch
Valve Orientation
Switch (VOS)
Rating
Plate
Fresh
Air
Switch
Line
Cord
System
Switch
(SS)
Fan
Speed
Switch
(FSS)
Fresh Air
Switch
(FAS)
Unit Mount
Thermostat
Remote
Fan
Speed
Switch
(FSS)
The Right Fit for Comfort 10 P/N 240010328, Rev. A [10/15/2013]
Page 11
PRODUCT DESCRIPTION
Figure 10 R45C
Electrical
Diagram
Rating
Plate
R45H Chassis
Aquastat
W/ Jumper
MTR Valve
Line
Cord
Fan
Cycle
Switch
(FCS)
High
Pressure
Switch
(HPS)
Fresh Air Switch
(FAS)
Thermostat
Fresh Air
Switch
(FAS)
Unit Mount
Fan
Speed
Switch
(FSS)
System
Switch
(SS)
Remote Mount
Fan
Speed
Switch
(FSS)
P/N 2400103028, Rev. A [10/15/2013] 11 Made in USA
Page 12
PRODUCT DESCRIPTION
Product Description
• RetroAire Replacement Packaged Terminal Air Condition/Heat Pumps units are straight cooling (PTAC) or heat pump systems (PTHP).
• Both PTAC and PTHP congurations t wall sleeves of units listed on front cover.
• Heat pumps (PTHP) operate in mechanical heat mode down to outdoor temperature of 40°F (4.4°C). Below 40°F (4.4°C) heating is accomplished by auxiliary heat option.
Retroaire PTAC/PTHP
• R-410A refrigerant.
• High-efciency rotary compressors.
• Two fan speeds.
• Positive condensate re-evaporation.
• PTAC/PTHP units are available in nominal sizes of 9,000 Btuh, (2.6kW) 12,000 Btuh (3.5kW) or 15,000 Btuh (4.4kW).
• PTAC units (straight cooling only) are available at 18,000 Btuh (5.3kW).
• Coefcient of performance (COP) ratings 2.90 for heat pumps.
Standard Controls And Components
Construction
• Chassis constructed of 20 gauge galvanized steel.
• Condenser bafe options accommodate extended wall sleeve applications. (Consult manufacturer).
• Powder-coated condenser and evaporator drain pan.
• Foam strip seal for supply air duct.
• Weather strip insulation.
Air Systems
• Thermally-protected motor PSC type.
• Indoor fan forward curved type, directly mounted to motor shaft.
Controls
• Unit-mounted operating controls include thermostat, fan speed control, heat/cool switch, fan cycle switch, fresh air switch (if equipped).
• Use of 1-stage or 2-stage thermostat. 2 stage thermostat is capable of activating emergency heat if auxiliary heat source is available.
• Low ambient protection — see "Microprocessor control board" for details.
• Ability to control a normally-open or normally-closed motor valve switch (on hydronic heat units only). Valve controls must be ordered for 24V or line voltage.
• All hydronic heat units include molex plugs for connection of hydronic valve motor.
• Remote mount controls include fan speed control and fresh air switch (if equipped).
• Equipped with manual reset high pressure switch which prevents abnormal high pressure operation.
Microprocessor Control Board
• Universal control board used in straight cooling, electric resistance heat, hydronic heat, or cooling/heat pump applications.
• Random start timer prevents multiple units from simultaneous startups after power interruption or on initial power-up.
• Fan purge — fan remains on for 60 seconds after heat/ cool is satised.
• Anti-short-cycle compressor protection prevents compressor from rapid cycling.
• Freeze-protection prevents evaporator coil freeze up.
• Low ambient lockout prevents compressor operation in outdoor temperatures less than 40°F (4.4°C). (On PTHP units supplied with unit-mounted control, control causes automatic changeover to auxiliary heat, if installed.)
• Test operation — all timers are temporarily suppressed to allow ease of testing or troubleshooting.
• Control board LED provides self-diagnostic troubleshooting codes, see "Sequence of operation."
• Unit mount controls include eld selection switch to control indoor fan by either cycling with compressor operation or continuously with unit.
Condensate Removal
• Outdoor fan incorporates condensate slinger ring. Condensate is thrown onto coil, where it evaporates.
• Thermostatic drain pan valve for condensate elimination when outdoor temperature drops below 60°F (15°C) (heat pump units only).
The Right Fit for Comfort 12 P/N 240010328, Rev. A [10/15/2013]
Page 13
PRODUCT DESCRIPTION
Manufacturer Installed Options (Consult manufacturer)
• 265/277V(12 and 15 only)
• 115V (09 &12 Models Only)
• Corrosion-resistant coil option — used for seacoast and harsh-environment usage; coated aluminum n/copper tube condenser coil.
• Motorized fresh-air damper
• Supplemental electric heat
• Hydronic heat controls
• Front air intake
Field-Installed Accessories
• Hydronic heat — coil assembly is shipped loose for eld installation.
• Remote wall thermostat — digital 1-stage or 2-stage available.
• Wall sleeves, louvers, and cabinets.
• Control - delays fan start-up until coil reaches 100°F (38°C) to virtually eliminate "cold" blow condition.
• Hydronic control valve , water 2 way & 3 way.
• Hydronic control valve, steam 2 way.
• Hydronic Isolation valve, 1/2 in sweat connection.
P/N 2400103028, Rev. A [10/15/2013] 13 Made in USA
Page 14
PTAC/PTHP INSTALLATION PREPARATION
!
WARNING
Electrical shock hazard. Before opening existing unit, open power supply disconnect switch. Secure switch in open position during installation. Attach sign stating "DO NOT TURN ON".
Unplug existing unit at wall outlet on plug and receptacle connection units. DO NOT plug new unit until installation is complete and start-up checklist is completed.
Failure to follow these instructions could result in death or serious injury.
!
WARNING
Moving parts if not avoided, could result in death or serious injury. Avoid contact with moving parts when testing or servicing unit.
Electrical Supply
• All eld wiring shall conform to requirements of authority having jurisdiction or in absence of such requirements:
Electrical Power Connection
1.
Verify RetroAire unit rating plate for circuit ampacity and required breaker or fuse size.
2.
Verify existing breaker or fuse is correct size.
Replace breaker or fuse if incorrectly-sized.
Breakers shall be type HACR only.
3.
Cord-connected units — verify wall outlet is correct rating. Outlet's blade conguration must match cord supplied with RetroAire unit.
4.
Hard-wired units — verify power wiring is correctly sized. Inspect existing wiring for cuts or frayed wires. Replace any damaged wiring.
Remove Old Chassis
1.
Disconnect power or unplug cord before proceeding.
2.
Remove front of existing room enclosure to expose old chassis.
3.
Loosen tie-down bolts or screws and remove old chassis.
• United States - National Electrical Code, ANSI/NFPA 70
• Canada - CSA C22.1 Canadian Electrical Code Part 1.
UNITS RATED 208/230V — RetroAire unit is wired for 230v primary voltage from manufacture. Transformer must be rewired by installer if jobsite voltage is 208v. Change transformer tap from orange to red. See wiring diagram for details.
• Protect with separate branch circuit protected by fuse or breaker. Refer to unit rating plate for proper wire and breaker or fuse size.
• Use of extension cords is prohibited.
• DO NOT connect RetroAire unit to circuit with incorrectly-sized over current protection device.
• All cord-connected 265 volt units must be plugged into receptacles within unit subbase or chassis.
Verify existing wall sleeve/enclosure:
• Use RetroAire replacement PTAC/PTHP's with metal wall sleeves.
• Secure existing front panels by screws that prevent contact with all parts.
• Minor dimensions of openings must not exceed ½ inch (12.5mm).
NOTICE
Dispose of old chassis following existing State and/or Federal regulations.
4.
Inspect wall sleeve/cabinet for rust, holes, or damage. A. Clean wall sleeve of any dirt.
B. Repair any damage.
C. Verify proper drainage of condensate or
rainwater to exterior of building.
5.
Remove or repair old weather seals. Make note of location for installation of new seals.
6.
Check wall sleeve/cabinet to ensure all drain holes are open and:
A. Wall sleeve/enclosure is level left to right
B. Back is pitched to outside by ½ in (12.5mm)
maximum.
7.
Inspect outdoor louver for minimum free area of 70%. Remove any obstructions before installing new chassis.
8.
Read and understand all instructions in this manual before attempting installation or operation.
• Dimensions of indoor air discharge grill shall be not less than 26” x 4”. Grill shall separate top surface of chassis from top surface of discharge grill by minimum of 1 in (25.4mm).
• For all models, outdoor openings must prevent contact of all moving parts by means of louvers or grills, with minor dimension not exceeding 1 in (25.4mm).
The Right Fit for Comfort 14 P/N 240010328, Rev. A [10/15/2013]
Page 15
INSTALLATION INSTRUCTIONS - R10C | R10H
Installation - R10C R10H
1.
Verify existing wall thickness — distance from condenser coil to outdoor louver varies with sleeve depth.
• Unit(s) ship standard with 1-3/8" (35mm) & 1-1∕8” (38mm) bafes. Figure 9.
• Optional condenser-side air bafe kit for chassis installation in deeper-than-standard wall sleeves is available.
2.
Verify weather angles — Slide unit into wall sleeve.
• If supply duct on cooling chassis does not line up with supply vent on room cabinet, adjust or change factory installed weather angle on top and sides. Allow for adjustment to align supply vent when mounting unit to wall sleeve Figure 11.
• Slide unit back in wall sleeve to verify proper t after adjustment.
3.
Install bafes — Slide unit back out of wall sleeve. Remove both supplied sets of bafes from kit bag. Install only one set of left and right side bafes on condenser coil by completing following steps:
A. Verify bafes come in contact with outdoor louver. B. Verify bafes are directed inward toward center of
coil Figure 13.
C. Secure bafes tightly into existing holes of
condenser coil using screws provided.
Figure 11 Weather Angles (in factory location)
Figure 12 Weather Angles Reversed to Gain
Extra Depth
NOTICE
Install correct condenser air bafes or performance may be impaired.
4.
Apply 2” x 1-1∕2” open-cell foam strips around supply air duct to ensure all conditioned air is delivered into room Figure 13. Failure to do so results in recirculation of conditioned air through cabinet causing unit to short cycle and coil to freeze.
5.
Apply 1” x 1” open-cell foam strips to weather angle. Prevents outside air from entering around chassis to room from sides and top of cabinet.
Install strips between wall sleeve and cooling chassis Figure 14. Verify solid air seal between wall sleeve and chassis. Air leakage from outdoor to indoor will result in system problems (example — coils freezing, short cycling, and constant running of unit).
6.
Connecting (optional) hydronic coil controls — If hydronic heat option has been ordered, eld install hydronic coils on new unit.
A. Hydronic coils are not factory installed. B. Old unit coil can be located in subbase, under
or above chassis in special attachment. It is necessary to know where coil is to be located and physical size of coil if ordered for replacement. Install new coil in same manner as coil it is replacing.
Figure 13 Direction of Bafes and Foam
In
stallation
P/N 2400103028, Rev. A [10/15/2013] 15 Made in USA
Page 16
INSTALLATION INSTRUCTIONS - R10C | R10H
• Remove 2-position connector assembly from kit bag supplied with unit (2 yellow wires attached).
• Connect 2-position connector to 2-position connection located on bottom of control box panel.
7.
Field install (optional) Aquastat
A. Remove black jumper wire located on bottom panel
of control box (also terminated with 2-position
connector).
B. Cut jumper wire in middle and splice Aquastat to
jumper.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
8.
Secure chassis
• Verify all seals are properly located,
• Verify correct bafes are attached to condenser coil, and properly orientated,
• Slide unit into nal position and tighten tie down bolts or screws.
9.
Hard-wired units — If unit is hard wired, follow instructions on pages 40-44 to verify existing wiring and over current protection.
A. Remove line cord wires from PTAC/PTHP power
entrance terminals.
B. Route power supply wiring through strain-relief
bushing and connect leads to power entrance terminals.
C. Secure strain-relief clamp. (If wiring is through
conduit, insert conduit through control box knockout and secure in place.)
D. DO NOT turn on power until completing instructions
in "Inspection and Startup" on page 28.
10.
Do not plug in line cord, Follow instructions in "Inspection and Startup".
Figure 14 Foam tape Installation Against
Wall Sleeves
The Right Fit for Comfort 16 P/N 240010328, Rev. A [10/15/2013]
Page 17
INSTALLATION INSTRUCTIONS — R20C| R20H
Installation - R20C R20H
1.
Verify existing wall thickness — distance from condenser coil to outdoor louver varies with sleeve depth.
• Standard air bafes are included with each unit to accommodate most installation requirements.
• Other air bafe kits are available from manufacturer (for unique applications).
2.
Verify Weather Angle — Slide unit into wall sleeve.
• If supply duct on cooling chassis does not line up with supply vent on room cabinet, it may be necessary to reverse the manufacturer installed weather angles on top and sides.
• This will allow approximately 1” of adjustment for alignment with supply vent when mounting unit to wall sleeve. See Figures 15 and 16. Slide the unit back in the wall sleeve to verify proper t.
Adjustable Weather Angle
Dimension "A" 8 5/8” 7 7/8” 9 11/16”
Dimension "B" 9 1/2” 10 1/4” 8 7/16”
Dimensions are calculated without foam gaskets. (1) Standard position — Factory installed. (2) Position for Climate Master 702 and 703.
INSTALLATION FOR NEW CONSTRUCTION
(1)
(1)
(2)
8”
10 1/8”
(2)
Figure 15 Weather Angle - Factory Location
Figure 16 Weather Angles Reversed to Gain
Extra Depth
3.
Install bafes — Slide unit back out of wall sleeve. Remove both supplied sets of bafes from kit bag. Install only one set of left and right side bafes on condenser coil as follows:
A. Verify bafes come in contact with outdoor louver. B. Verify bafes are directed inward toward center of
coil Figure 17.
C. Secure bafes into existing holes of condenser coil
using screws provided.
NOTICE
Install correct condenser air bafes or performance may be impaired.
4.
Apply ½” x ½” open-cell foam strips around supply air duct to ensure all conditioned air is delivered into room Figure 17. Failure to do so results in recirculation of conditioned air through cabinet causing unit to short cycle and coil to freeze.
5.
Apply 1” x 1” open-cell foam strips to weather angle. Prevents outside air from entering around chassis to room from sides and top of cabinet.
Install strips between wall sleeve and cooling chassis Figure 18. Verify solid air seal between wall sleeve and chassis. Air leakage from outdoor to indoor will result in system problems (example — coils freezing, short cycling, and constant running of unit).
Figure 17 D i r e c t i o n o f B a f  e s a n d F o a m
Installation
P/N 2400103028, Rev. A [10/15/2013] 17 Made in USA
Page 18
INSTALLATION INSTRUCTIONS — R20C| R20H
6.
Connect (optional) hydronic coil controls — If hydronic heat option has been ordered, hydronic coils will need to be eld installed on new unit.
A. Hydronic coils are not factory installed and need to
be ordered and eld installed on new unit.
B. Coil with old unit can be located in subbase, under
or above chassis in special attachment. It is necessary to know where coil is to be located and physical size of coil if ordered for replacement. New coil should be installed in same manner as coil it is replacing.
• Remove 2-position connector assembly from kit bag supplied with unit (2 yellow wires attached).
• Connect 2-position connector to 2-position connection located on bottom of control box panel.
7.
Field install (optional) Aquastat
A. Remove black jumper wire located on bottom panel
of control box (also terminated with 2-position
connector).
B. Cut jumper wire in middle and splice Aquastat to
jumper.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
8.
Secure chassis
• Verify all seals are properly located,
Figure 18 Foam tape installation against wall
sleeve
• correct bafes are attached to condenser coil, and properly orientated,
• slide unit into nal position and tighten tie down bolts or screws as necessary.
9.
Hard-wired units — If unit is hard wired, follow instructions on pages 37-39 to verify existing wiring and over current protection.
A. Remove line cord wires from PTAC/PTHP power
entrance terminals.
B. Route power supply wiring through strain-relief
bushing and connect leads to power entrance terminals.
C. Secure strain-relief clamp. (If wiring is through
conduit, insert conduit through control box knockout and secure in place.)
D. DO NOT turn on power until completing instructions
in "Inspection and Startup" on page 28.
10.
Do not plug in line cord, Follow instructions in "Inspection and Startup".
The Right Fit for Comfort 18 P/N 240010328, Rev. A [10/15/2013]
Page 19
INSTALLATION INSTRUCTIONS — R20C WITH FEDDERS UNI-ZONE OPTION
Installation - R20C w/Fedders Uni-Zone Option
1.
Verify existing wall thickness — distance from condenser coil to outdoor louver varies with sleeve depth.
• Standard air bafes are included with each unit to accommodate most installation requirements.
• Optional condenser side bafe kit is available from manufacturer for installation in deeper than standard walls.
• Weather angles should need no adjustment.
2.
Verify air supply alignment — Slide unit into wall sleeve.
• Supply duct on cooling chassis should line up with supply vent on room cabinet.
3.
Install bafes — Slide unit back out of wall sleeve. Remove supplied bafes from kit bag. Install left and right side bafes on condenser coil as follows:
A. Verify bafes come in contact with outdoor louver. B. Verify bafes are directed inward toward center of
coil Figure 19.
C. Secure bafes into existing holes of condenser coil
using screws provided.
Figure 19 Bafe Direction and Foam
Installation
1/2" x 1/2" Foam Tape
Mount to rear
edge
Baes Directed
Inward
Toward Coil
Weather Angle
Control Box
1" x 1"
Foam Tape
Mount to rear
edge
NOTICE
Install correct condenser air bafes or performance may be impaired.
4.
Install weather angle supplied on side of unit. Secure with provided screws. Face insulation toward interior of building.
5.
Apply ½” x ½” open-cell foam strips around supply air duct to ensure all conditioned air is delivered into room Figure 14. Failure to do so results in recirculation of conditioned air through cabinet causing unit to short cycle and coil to freeze.
6.
Apply 1” x 1” open-cell foam strips to weather angle. Prevents outside air from entering around chassis to room from sides and top of cabinet.
Install strips between wall sleeve and cooling chassis Figure 19. Verify solid air seal between wall sleeve and chassis. Air leakage from outdoor to indoor will result in system problems (example — coils freezing, short cycling, and constant running of unit).
7.
Connect (optional) hydronic coil controls — If hydronic heat option has been ordered, hydronic coils will need to be eld installed on new unit.
A. Hydronic coils are not factory installed and need to
be ordered and eld installed on new unit.
B. Coil with old unit can be located in subbase, under
or above chassis in special attachment. It is necessary to know where coil is to be located and physical size of coil if ordered for replacement. Install new coil in same manner as coil it is replacing.
P/N 2400103028, Rev. A [10/15/2013] 19 Made in USA
Page 20
INSTALLATION INSTRUCTIONS — R20C WITH FEDDERS UNI-ZONE OPTION
• Remove 2-position connector assembly from kit bag supplied with unit (2 yellow wires attached).
• Connect 2-position connector to 2-position connection located on bottom of control box panel.
8.
Field install (optional) Aquastat
A. Remove black jumper wire located on bottom panel
of control box (also terminated with 2-position
connector).
B. Cut jumper wire in middle and splice Aquastat to
jumper.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
9.
Secure chassis
• Verify all seals are properly located.
• Verify correct bafes are attached to condenser coil, and properly orientated.
• Slide unit into nal position and tighten tie down bolts or screws.
10.
Hard-wired units — If unit is hard wired, follow instructions on pages 37-39 to verify existing wiring and over current protection.
A. Remove line cord wires from PTAC/PTHP power
entrance terminals.
B. Route power supply wiring through strain-relief
bushing and connect leads to power entrance terminals.
C. Secure strain-relief clamp. (If wiring is through
conduit, insert conduit through control box knockout and secure in place.)
D. DO NOT turn on power until completing instructions
in "Inspection and Startup" on page 28.
11.
Do not plug in line cord, Follow instructions in "Inspection and Startup".
The Right Fit for Comfort 20 P/N 240010328, Rev. A [10/15/2013]
Page 21
INSTALLATION INSTRUCTIONS — R35C| R35H
Installation - R35C
1.
Verify existing wall thickness — distance from condenser coil to outdoor louver varies with sleeve depth.
• Chassis includes ½" air bafe to accommodate the most common condenser coil to outdoor louver requirements.
• Optional condenser-side air bafe kit for chassis installation in deeper than standard walls is available from manufacturer.
2.
Verify air supply alignment — slide unit into wall­sleeve. Supply duct on the cooling chassis should line up with supply vent on room cabinet.
3.
Install bafes — Slide unit back out of wall sleeve. Remove supplied bafes from kit bag. Install only one set of left and right side bafes on condenser coil by completing following steps:
A. Verify bafes come in contact with outdoor louver. B. Verify bafes are directed inward toward center of
coil Figure 20.
C. Secure bafes tightly into existing holes of
condenser coil using screws provided.
Figure 20 Direction Of Bafes and Foam
Installation
Install 2" x ¹∕₂" foam tape
Figure 21 Front View of Chassis
NOTICE
Install correct condenser air bafes or performance may be impaired.
4.
Apply 1” x 1” open-cell foam strips to weather angle. Prevents outside air from entering around chassis to room from sides and top of cabinet.
Install strips between wall sleeve and cooling chassis. See Figure 20. Verify solid air seal between wall sleeve and chassis. Air leakage from outdoor to indoor will result in system problems (example — coils freezing, short cycling, and constant running of unit).
R35C/H is equipped with a bracket allowing unit to be adjusted up and down in the chassis of un-leveled wall sleeves. Adjust leveler leg to desired height and tighten down using bolts supplied on bracket . See Figure 21.
5.
Connecting (optional) hydronic coil controls — If hydronic heat option has been ordered, hydronic coils will need to be eld installed on new unit.
A. Hydronic coils are not factory installed and need to
be ordered.
B. Coil with old unit can be located in subbase, under
chassis in special attachment. It is necessary to know where coil is to be located and physical size of coil if ordered for replacement. New coil should be installed in same manner as coil it is replacing.
C. Remove 2-position connector assembly from kit
bag supplied with unit (2 yellow wires attached).
D. Connect 2-position connector to 2-position
connection located on bottom of control box panel.
P/N 2400103028, Rev. A [10/15/2013] 21 Made in USA
Page 22
INSTALLATION INSTRUCTIONS — R35C| R35H
6.
Field install (optional) Aquastat
A. Remove black jumper wire located on bottom panel
of control box (also terminated with 2-position connector).
B. Cut jumper wire in middle and splice control to
jumper.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
7.
Secure chassis
• Verify all seals are properly located.
• Verify correct bafes are attached to condenser coil, and properly orientated.
• Slide unit into nal position and tighten tie down bolts or screws.
8.
Hard-wired units — If unit is hard wired, follow in­structions on pages 38-40 to verify existing wiring and over current protection.
A. Remove line cord wires from PTAC/PTHP power
entrance terminals.
B. Route power supply wiring through strain-relief
bushing and connect leads to power entrance ter­minals.
C. Secure strain-relief clamp. (If wiring is through
conduit, insert conduit through control box knock­out and secure in place.)
D. DO NOT turn on power until completing instructions
in "Inspection and Startup" on page 28.
9.
Do not plug in line cord, Follow instructions in "Inspection and Startup".
The Right Fit for Comfort 22 P/N 240010328, Rev. A [10/15/2013]
Page 23
INSTALLATION INSTRUCTIONS — R45C | R45H
Installation - R45C/R45H
1.
Verify existing wall thickness — distance from condenser coil to outdoor louver varies with sleeve depth.
• Two sets of air bafes are included to accommodate most installation requirements.
• Air bafe kits are available from the manufacturer for unique for applications. Have wall sleeve depth available when ordering to ensure proper bafe size.
2.
Verify Weather Angle
• Slide unit into wall sleeve.
• If supply duct on cooling chassis does not line up with supply vent on room cabinet, reverse factory installed weather angle on top and sides allowing approximately 1” of adjustment for alignment with supply vent when mounting unit to wall sleeve. See Figures 22 and 23.
• Slide unit back into wall sleeve and verify proper t.
3.
Install Bafes - Slide unit back out of wall sleeve. Locate both sets of bafes from kit bag supplied with unit. Install only one set of left and right side bafes on condenser coil by completing following steps:
• Choose the proper tting bafes for your application verify bafes selected come in contact with outdoor louver.
Figure 22 Factory Located Weather Angle
Figure 23 Weather Angles Reversed To Gain
Extra Distance
• Verify bafes are directed inward toward center of coil. See Figure 24.
• Secure bafes tightly into existing holes of condenser coil using provided screws.
NOTICE
Install correct condenser air bafes or performance may be impaired.
4.
Apply ½” x ½” open-cell foam strips around supply air duct to ensure all conditioned air is delivered into room. See Figure 24. Failure to do so results in recirculation of conditioned air through cabinet causing unit to short cycle and coil to freeze.
5.
Apply 1” x 1” open-cell foam strips to weather angle. Prevents outside air from entering around chassis to room from sides and top of cabinet.
Install strips between wall sleeve and cooling chassis Figure 24. Verify solid air seal between wall sleeve and chassis. Air leakage from outdoor to indoor will result in system problems (example — coils freezing, short cycling, and constant running of unit).
6.
Connecting (optional) hydronic coil controls — If hydronic heat option has been ordered, hydronic coils will need to be eld installed on new unit.
A. Hydronic coils are not factory installed and need to
be ordered.
Figure 24 Direction Of Bafes And Foam
Installation
P/N 2400103028, Rev. A [10/15/2013] 23 Made in USA
Page 24
INSTALLATION INSTRUCTIONS — R45C | R45H
B. Coil with old unit can be located in subbase, under
or above chassis in special attachment. It is necessary to know where coil is to be located and physical size of coil if ordered for replacement. New coil should be installed in same manner as coil it is replacing.
C. Remove 2-position connector assembly from kit
bag supplied with unit (2 yellow wires attached).
D. Connect 2-position connector to 2-position
connection located on bottom of control box panel.
7.
Field install (optional) Aquastat
A. Remove black jumper wire located on bottom panel
of control box (also terminated with 2-position connector).
B. Cut jumper wire in middle and splice Aquastat to
jumper.
C. Place connector back into original location. Refer to
wiring diagram on unit for details.
8.
Secure chassis
• Verify all seals are properly located.
• Verify correct bafes are attached to condenser coil, and properly orientated.
• Slide unit into nal position and tighten tie down bolts or screws.
9.
Hard-wired units — If unit is hard wired, follow instructions on pages 38-40 to verify existing wiring and over current protection.
A. Remove line cord wires from PTAC/PTHP power
entrance terminals.
B. Route power supply wiring through strain-relief
bushing and connect leads to power entrance terminals.
C. Secure strain-relief clamp. (If wiring is through
conduit, insert conduit through control box knockout and secure in place.)
D. DO NOT turn on power until completing
instructions in "Inspection and Startup" on page
28.
10.
Do Not Plug Line Cord In, If In Used Condition.
Follow instructions in "Inspection and Startup".
The Right Fit for Comfort 24 P/N 240010328, Rev. A [10/15/2013]
Page 25
SEQUENCE OF OPERATION
General R_ _C units are straight cool, single stage air conditioners
available with electric or hydronic heat. R_ _H units are limited range, single stage heat pump.
Mechanical compression heating (heat pump mode) is locked out at outdoor temperatures of approximately 35ºF (1.7ºC) and below. Below these ambient temperatures, auxiliary electric or hydronic heat will be used.
Microprocessor Control Board Thermostat and control connections are made to control board.
A. Two conguration jumpers are located
on board, see Figure 25. Heat Pump Conguration Jumper is 3 pin jumper.
• Straight Cool units R_ _C, the jumper should be located on the outside two pins.
Heat Pump units R_ _H, the jumper should be located on the inside two pins.
B. Second conguration jumper “TEST” allows for
control’s internal timers to be by-passed for test purposes. Placing jumper on two pins enables test mode.
C. Status LED (Light Emitting Diode)
• LED1 is located on center of board. Series of blinks communicates status of board. Between blink sequence is separation of approximately 2 seconds. Status Code is listed below.
Figure 25 Control Board
TEST
Cong.
Jumper
LED
Indicator
Light
Heat
Pump
Cong.
Jumper
Trouble
Code
Status
(Blinks)
1
2
3
4
5
Normal Operation
Anti-Short Cycle Timer Active
Outdoor Coil Freeze Protection
Indoor Coil Freeze Protection
Simultaneous “Y” and “W” Call
Initial Power-Up or Power Restoration
When power is applied to unit, either for rst time or after power failure, board will initialize itself.
1.
During initialization, LED1 will be lit continuously for approximately 5 seconds.
2.
Following initialization, random start timer is initiated. Timer adds randomly selected 5-120 seconds to start­up sequence, reducing possibility of multiple units starting at same time.
3.
Once random start timer has expired, 180 second Anti-Short Cycle Timer is initiated and Processor Board Trouble Code LED is set to blink 2 ash code. Timer prevents compressor from rapid cycling.
4.
After Anti-Short Cycle Timer expires, Processor Board Trouble Code LED is set to blink 1 blink Trouble Code, indicating normal operation.
P/N 2400103028, Rev. A [10/15/2013] 25 Made in USA
Page 26
SEQUENCE OF OPERATION
R_ _C / R_ _H; Cooling Operation
( For unit mount controls)
1.
System Switch [SS] set to “Cool”, and Fan Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor starts.
2.
Fan Cycle Switch [FCS] set to “Off” (Cycling Fan Operation), indoor fan motor starts with call for cooling from internal thermostat [T’stat].
3.
Units equipped with optional Motorized Fresh Air Damper, and active Fresh Air Switch [FAS], damper opens with call for indoor fan.
4.
Room temperature below thermostat setting fan operation continues as noted above.
5.
Room temperature above thermostat setting, reversing valve is energized, compressor and outdoor fan starts provided Anti-Short Cycle Timer has timed out from initial power-up, power restoration or previous compressor on cycle. Operation continues until room temperature satises thermostat.
6.
Once room temperature falls below set point by 3ºF (2ºC), compressor, outdoor fan motor and reversing valve are de-energized.
7.
FCS is set to “Off”, indoor fan continues to operate for 60 seconds after compressor stops.
8.
If FCS set to “On”, indoor fan continues to operate.
9.
As soon as compressor is de-energized, Anti-Short Cycle Timer is initialized and prevents compressor from starting again for another 180 seconds.
10.
While Anti-Short Cycle Timer is active, Processor Board Trouble Code LED is set to blink 2 ash code.
11.
After Anti-Short Cycle Timer expires, Processor Board Trouble Code LED is set to blink 1 blink Trouble Code, indicating normal operation.
NOTICE
Remote-Mount Cooling Operation depends on features of wall-mounted thermostat. By default fan will cycle with call for cooling.
For thermostats with AUTO / ON fan switch, fan runs continuously if this is “ON” (Continuous Fan Operation). Fan will cycle with call for cooling if this is set to “AUTO” (Cycling Fan Operation).
In cooling units will not start if indoor air temperature is 60ºF (15.5 ºC) or below or if outdoor temperature is below 40ºF (4.5ºC).
R_ _C / R_ _ H; Heating Operation
1.
System Switch [SS] set to “Heat”, and Fan Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor starts.
2.
If Fan Cycle Switch [FCS] is set to “Off” (Cycling Fan Operation), indoor fan motor starts with call for heat from internal thermostat [T’stat].
3.
Unit equipped with optional Motorized Fresh Air Damper, and is active with Fresh Air Switch [FAS], damper opens with call for indoor fan.
4.
If room temperature is above thermostat setting fan operation continues as noted above.
5.
If room temperature is below thermostat setting, action of unit depends on outdoor temperature and freeze sensor status.
NOTICE
Remote-Mount Heating Operation depends on features of wall-mounted thermostat. By default fan cycles with call for Heating.
For thermostats with AUTO / ON fan switch, fan runs continuously if this is “ON” (Continuous Fan Operation).
Fan cycles with call for heating if this is set to “AUTO” (Cycling Fan Operation).
• R_ _H; Mechanical Heating “Heat Pump"
1.
Outdoor coil temperature remains above 25 ºF (-4ºC), compressor and outdoor fan start provided Anti-Short Cycle Timer has timed out from initial power-up, power restoration or previous compressor on cycle. Operation continues until room temperature satises thermostat.
2.
Once room temperature rises above set point by 3ºF (2ºC), compressor and outdoor fan motor will de-energize.
3.
FCS set to “Off”, indoor fan continues to operate for 60 seconds after compressor stops.
4.
FCS set to “On”, indoor fan continues to operate.
5.
As soon as compressor is de-energized, Anti-Short Cycle Timer initializes and prevents compressor from starting again for another 180 seconds.
6.
While Anti-Short Cycle Timer is active, Processor Board Trouble Code LED is set to blink 2 ash code.
7.
After Anti-Short Cycle Timer expires, Processor Board Trouble Code LED is set to ash 1 blink Trouble Code, indicating normal operation.
The Right Fit for Comfort 26 P/N 240010328, Rev. A [10/15/2013]
Page 27
SEQUENCE OF OPERATION
• R_ _H; Auxiliary Heating “Electric” or “Hydronic”
1.
Outdoor coil temperature falls to 25ºF (-4ºC) or below for 180 seconds at anytime during heating call, compressor and outdoor fan motor are de-energized and auxiliary heat is energized.
2.
Anti-Short Cycle Timer is initiated, prohibiting compressor operation for 180 seconds.
3.
Processor Board Trouble Code LED ashes 3 blink Trouble Code, indicating auxiliary heat operation. Heating operation with auxiliary heat continues until outdoor coil sensor reaches 50ºF (10ºC).
• “Electric Heat”
1.
System Switch [SS] set to “Heat”, and Fan Cycle Switch [FCS] set to “On” (Continuous Fan Operation), indoor fan motor will start.
2.
Fan Cycle Switch [FCS] set to “Off” (Cycling Fan Operation), indoor fan motor starts with call for heating from internal thermostat [T’stat].
3.
Unit equipped with optional Motorized Fresh Air Damper, and activated with Fresh Air Switch [FAS], damper opens with call for indoor fan.
4.
Room temperature above thermostat setting fan operation continues as noted above.
5.
Room temperature below thermostat setting, electric heater is energized until room temperature satises thermostat.
6.
Once room temperature increases above set point by 3ºF (2ºC), electric heaters de-energize.
• “Hydronic Heat”
• “Remote Wall Thermostat Controls”
A. Cooling and Heating operate identical to unit
mount controls. B. See remote control manuals for control details. C. Remote units do not use system switch, or FCS.
1.
FCS set to “On” (Continuous Fan Operation) and unit has Control, indoor fan and fresh air motorized damper operation are controlled by Control.
2.
Control senses temperature of 80 ± 5ºF (26 ± 3ºC) or below, indoor fan will shut down and motorized damper closes fresh air door.
3.
With call for heat, signal from processor board activates water or steam valve.
4.
Unit equipped with eld installed Control [AS], indoor fan start is delayed until hydronic coil reaches 100 ± 5ºF (38 ± 3ºC).
5.
Signal to water or steam valve continues until room temperature rises above set point by 3ºF (2ºC).
6.
FCS set to “Off”, indoor fan continues to operate for 60 seconds or until hydronic coil temperature sensed by Control reaches 80 ± 5ºF (26 ± 3ºC), whichever occurs rst.
7.
FCS set to “On”, indoor fan de-energizes if Control senses temperature of 80 ± 5ºF (26 ± 3ºC) or below.
P/N 2400103028, Rev. A [10/15/2013] 27 Made in USA
Page 28
INSPECTION & START-UP
Before Operating Unit
Read and understand contents of this manual.
Install unit per instructions outlined in this manual
and all applicable local and national codes.
☐ Verify electrical supply matches electrical
requirements of unit, and unit is properly grounded.
☐ Examine control box. Verify all wire connections
are secure, and control board jumpers are in proper positions. See "Electrical Connections" Page 29.
☐ Verify chassis is properly tted to wall sleeve and
securely mounted to surrounding framing.
Verify chassis is level:
Pour water into drain pan.
Verify water ows through drain hoses to
condenser side of unit.
☐ Verify indoor blower wheels and outdoor fan
blades are secured to their motor shafts, and rotate freely.
Any obstruction of supply air, including use of deector bafes, may cause condensate to form on louver or cabinet (see Figure 38, page 31).
Figure 26 Proper Air Flow Example
☐ Verify all sheet metal panels are in place and
secure.
Attach front panel to existing cabinet enclosure.
Verify nothing interferes with room discharge air
or return air of units. Examples:
– Check for curtains or drapes that obstruct air
ow. See Figures 26 and 27.
– Check for plush carpeting that can obstruct
return air.
– Items like these can cause serious damage to
chassis.
For optimum performance of your PTAC/PTHP, avoid restricting air ow. Position of curtains or drapes over supply air grille may cause air to recirculate without cooling room. Unit will short cycle and may cause premature compressor failure.
Figure 27 Restricted Air Flow Diagram
The Right Fit for Comfort 28 P/N 240010328, Rev. A [10/15/2013]
Page 29
INSPECTION & START-UP
Electrical Connections
!
WARNING
Electrical shock hazard. Disconnect all power before removing chassis, performing any cleaning, servicing, or maintenance. Failure to do so could result in death or serious injury
Refer to wiring diagram attached to unit for wiring details. All eld wiring shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States
• National Electrical Code, ANSI/NFPA 70
• Canada
• CSA C22.1 Canadian Electrical Code Part 1.
UNITS RATED 208/230V — RetroAire unit is wired for 230v primary voltage from manufacturer.
Transformer must be rewired by installer if jobsite voltage is 208v.
Change transformer tap from orange to red. See wiring diagram for details.
Figure 28 TEST Jumper (selects heat pump or
straight cooling)
HP
Straight
Cool Mode
Mode
(jumper center
& top pins)
Heat Pump
Mode
(jumper center
& Btm. pins)
HP
HP
Setting Control Board Jumpers
Control board has two sets of factory installed jumper pins
Figure 29 TEST Jumper (selects heat pump or
on control board, HP jumper and TEST jumper.
HP Jumper — to select heat pump or straight cooling Pins determine whether unit operates as straight cooling or
as heat pump. See Figures 28 and 29.
• Jumper right pin to center pin for heat pump operation.
• Jumper left pin to center pin for straight cooling operation.
TEST Jumper — to select normal or test mode Jumper is for use in testing only. See Figures 29 and 30.
• When
JUMPER
pins are jumpered together, all timers are eliminated (example — anti-short cycle, purge, etc.).
• Used mainly used for production line testing. May be used for eld testing.
• Units are factory set with jumper on only one pin (normal operation position).
Test mode
(pins jumpered)
straight cooling)
Normal operation
(pins not jumpered)
TEST
NOTICE
Do not leave unit operating with TEST jumper in TEST position.
P/N 2400103028, Rev. A [10/15/2013] 29 Made in USA
Page 30
INSPECTION & START-UP
Start Up
1.
Verify unit is secure and level.
2.
Heat pump units only — Verify thermostatic drain pan valve is operating correctly. Valve should be closed if temperature is above 60°F and open if temperature is below 60°F.
3.
Test optional fresh air damper. Set damper door switch to "YES" position, verify damper opens and allows fresh air to be moved into space. Set damper door switch to "NO" position. Verify ow of air into space has stopped. Fresh air will only be available when indoor fan is running.
4.
Verify HP jumper is set correctly for unit type. See Figure 28, page 29
5.
Set TEST jumper to test mode. Will disable time delays, including anti-short-cycle and purge times. See Figure 30.
6.
Verify unit is wired according to instructions, including requirements on page 28.
7.
Connect Electric power to unit .
8.
Turn on unit to check for proper operation. Check con­densate removal by pouring water into base pan, place unit in cooling mode, and with condenser fan running, verify water is picked up by slinger ring and thrown onto outdoor coil.
Figure 30 Circuit Board
TEST JUMPER
NOTICE
Compressor will not start until anti-short time period has elapsed. On power-up, there will be delays for control board initialization and random-start timing. See “Sequence of Operation” on page 25.
Unit-Mounted Thermostat
1.
Use system switch to place PTAC/PTHP in either COOL, HEAT, or
in all positions.
2.
Use fan speed switch to place fan in either LOW or HIGH speed. heating and cooling.
3.
Test operation of Fan Cycle switch (toggle switch on side of control box), with switch set at ON (continuous fan operation) or AUTO (cycling with thermostat) for both heating and cooling. Set switch in desired position.
4.
Rotate thermostat knob to left to increase setpoint temperature, or right to decrease. Turning unit-mount­ed thermostat knob to far left will produce warmest room temperature, while turning it way to right will produce coolest. Setting can be adjusted for personal comfort.
OFF
position. See Figure 31. Test operation
Test operation in both positions for
HEAT
PUMP
JUMPER
Figure 31 Mount Control
THERMOSTAT KNOB
The Right Fit for Comfort 30 P/N 240010328, Rev. A [10/15/2013]
Page 31
INSPECTION & START-UP
NOTICE
DO NOT rotate thermostat knob back and forth from heating to cooling. This causes compressor to cycle on and off rapidly and will cause damage to compressor. Allow compressor to remain off for at least three minutes prior to restarting unit.
Remote-Mounted Thermostat
1.
Use thermostat to place PTAC/PTHP in either COOL, HEAT, or OFF position. Test operation in all positions.
2.
If thermostat is tted with fan switch, set as desired places fan in either ON, OFF, or AUTO. Test operation in all positions.
3.
Check thermostat calibration for both heating and cooling operation.
Straight Cooling PTAC's
Cooling Cycle
1.
Place thermostat or system switch in COOL position.
2.
Adjust thermostat to cooler temperature until indoor fan starts running. Compressor and outdoor fan should turn on and cold air begin to ow from unit. Let unit continue operating to cool room and remove humidity.
3.
After unit starts running and space gets cooler, adjust thermostat to warmer temperature until compressor cycles off.
4.
If colder room temperature is desired, adjust thermo­stat to cooler temperature setting, turning compressor and both fans back on.
5.
If warmer room temperature is desired, adjust ther­mostat to warmer temperature setting. Compressor and outdoor fan stops and indoor fan switches off after sixty-second purge time has elapsed.
6.
Place thermostat or system switch in the OFF position. All operation should stop.
NOTICE
Room temperature must be above 65°F (18°C) for compressor to operate in cooling mode on PTAC's with unit mounted controllers.
Heating Cycle — Electric Option
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat for warmer temperature until indoor fan starts running and electric heater coil starts emitting heat.
3.
Outdoor fan does not run during heating cycle.
4.
After unit starts running and space gets warmer, adjust thermostat to cooler temperature until electric heater turns off.
5.
Warmer room temperature is desired, adjust thermostat to warmer temperature setting, turn electric heater back on.
6.
Cooler room temperature is desired, thermostat to cooler temperature setting electric heater turns off. Indoor fan will switch off after sixty-second purge time has elapsed.
7.
Place thermostat or system switch in OFF position. All operation should stop.
adjust
until
NOTICE
Room temperature must be below 85°F (29.4°C) to energize heater on PTAC's with unit-mounted controllers.
Heating Cycle — Hydronic Option
Verify motor valve is rated for correct voltage. RetroAire units with unit mount controls will power hydronic valve that is same voltage as unit (ex: unit rated 208/230v will power 208/230v).
Switch is provided on control box to change from NO to NC. Verify wiring diagram (located on unit) and voltage application for specic unit.
Other valve congurations and voltage options are available. Consult Manufacturer if unit voltage does not match your valve application.
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat to warmer temperature.
– Signal from processor board activates water or
steam valve.
– Motorized valve opens and allows hot water or
steam to run through coil.
– Indoor fans run, blowing air through hydronic
NOTICE
When unit is rst powered up, high humidity conditions can cause condensation to form on discharge grill. Keep doors and windows closed to reduce humidity, condensation will evaporate.
P/N 2400103028, Rev. A [10/15/2013] 31 Made in USA
coil. Units equipped with Control, indoor fan and motorized damper operation will be delayed until hydronic coil reaches 100 ± 5°F (38 ± 3°C).
– Signal to water or steam valve will continue
until room temperature rises above setpoint by 3°F (2°C).
Page 32
INSPECTION & START-UP
3.
After unit starts running and area is warmer, adjust thermostat to cooler temperature, hydronic valve will close and indoor fan will switch off after sixty-second purge time has elapsed.
4.
For warmer room temperature, adjust thermostat to warmer temperature setting, which opens hydronic valve and turns on indoor fan.
5.
For cooler room temperature, adjust thermostat to cooler temperature setting. Hydronic valve closes and indoor switches off after sixty-second purge time has elapsed.
6.
Place thermostat or system switch in OFF position. All operation should stop.
NOTICE
Room temperature must be below 85°F (29°C) for hydronic heater to operate on PTAC's with unit­mounted controllers.
Hydronic valve is 24Vac normally open valve. Should power be interrupted, valve will default to open position.
Testing Completion For Cooling-Only PTAC's
If TEST jumper was set to test mode verify it is set back to normal operation. See Figure 29, page 29.
NOTICE
Do not leave unit operating with TEST jumper in TEST position. Prolonged operation with unit on test mode will cause damage to internal components.
5.
Warmer room temperature desired, adjust thermostat to a warmer temperature. The cooling mode will cease and the compressor and outdoor fan will stop. The indoor fan will switch off after the sixty-second purge time has elapsed.
6.
Place thermostat or system switch in OFF position. All operation stops.
NOTICE
Room temperature must be above 85°F (29°C) for compressor to operate in cooling mode on PTHP's with unit-mounted controllers.
7.
Place system switch in OFF position. All operation stops.
Heating Operation — Heat Pump Units — Outdoor Temperature Above 40°F (4°C)
1.
Place thermostat or system switch in HEAT position.
2.
Adjust thermostat to warmer temperature setting until indoor fan start to run. Compressor and outdoor fan turn on, warm air begins to ow.
3.
Unit starts to run and space gets warmer, adjust thermostat to cooler temperature until compressor cycles off.
4.
Warmer room temperature, adjust thermostat to warmer temperature setting turning indoor and outdoor fans, and compressor back on.
5.
Cooler room temperature is desired, adjust thermostat to cooler temperature setting. Heating mode ceases and compressor and outdoor fan stops. Indoor fan switches off after sixty-second purge time has elapsed.
NOTICE
Room temperature must be above 85°F (29°C) for
Heat Pump PTHP's
NOTICE
Unit equipped with reversing valve energized for
compressor to operate in cooling mode on PTHP's with unit-mounted controllers.
6.
Place thermostat or system switch in OFF position. All operation stops.
cooling and de-energized in heating mode.
NOTICE
Cooling Cycle — Heat Pump Units
1.
Place thermostat or system switch in COOL position.
2.
Adjust thermostat to cooler temperature until indoor fan starts running. Compressor and outdoor fan turn on and cold air begins to ow from unit. Let unit continue operating to cool room and remove humidity.
3.
Unit starts running and space gets cooler, adjust thermostat to warmer temperature until compressor cycles off.
4.
Colder room temperature desired, adjust thermostat to cooler temperature setting, turning the compressor and both fans back on.
The Right Fit for Comfort 32 P/N 240010328, Rev. A [10/15/2013]
Heat pump units are “Limited Range” equipped with back-up electric resistance heat. Limited Range heat pumps are designed to operate when outdoor temperatures are between 75°F(24°C) and 40°F (4°C) and with maximum indoor temperature of 85°F (29°C) . When outdoor temperature falls below 40°F (4°C) unit will switch from heat pump to electric resistance heat, or optional hydronic heat if selected. Electric heat or hydronic heat will remain heat source until outdoor temperatures rise above 50°F (10°C). RetroAire heat pumps (R_ _H) are single-stage heating units. Electric heat and heat pump will NOT operate simultaneously.
Page 33
INSPECTION & START-UP
Auxiliary Heating Operation — Heat Pump Units
— Outdoor Temperature Below 40°F (4C°) — Electric Option
1. Place
2.
3.
4.
5.
6.
thermostat or
Adjust thermostat to warmer temperature until indoor fans start running and electric coil starts emitting heat.
After unit starts running and space warms, adjust thermostat to cooler temperature until electric heater turns off.
Warmer room temperature is desired, adjust thermostat to warmer temperature setting, which turns electric heater back on.
Cooler room temperature is desired, thermostat to cooler temperature electric heater turns off. Indoor fan switches off after sixty-second purge time has elapsed.
Place thermostat or system switch in OFF position. All operation stops.
system switch in HEAT position.
adjust setting until
NOTICE
Room temperature must be below 85°F (29°C) to energize heater on PTHP's with unit-mounted controllers.
5 kW heat models only — in event limit switch opens and de-energizes electric heat, reset limit switch manually;
Turn power off
Remove control box cover.
Locate limit switch.
Push reset button in on the face of the switch. See
Figure 32, page 34.
– After unit starts running and space gets
warmer, hydronic valve closes and indoor fan switches off after sixty-second purge time has elapsed.
3.
After unit starts running and space gets warmer, adjust thermostat to cooler temperature setting, hydronic valve closes and indoor fan switches off after sixty-second purge time has elapsed.
4.
Desired warmer room temperature, thermostat to warmer temperature setting opens hydronic valve and turns on indoor fan.
5.
Desired cooler room temperature, adjust thermostat to cooler temperature setting. Hydronic valve closes and indoor fan switches off after sixty-second purge time has elapsed.
6.
Place thermostat or system switch in OFF position. All operation stops.
adjust
, which
NOTICE
Room temperature must be below 85°F (29°C) for hydronic heater to operate on PTHP's with unit­mounted controllers. Hydronic valve is 24Vac normally open valve. Should power be lost to unit, valve defaults to open position.
Completion Of Testing For Heat Pumps
Operation testing is complete. If TEST jumper was set to test mode verify it is set back to normal operation (see
Figure 28, page 29).
Auxiliary Heating Operation — Heat Pump Units —
Outdoor Temperature Below 40°F (4°C) — Hydronic Option
1. Place
2.
P/N 2400103028, Rev. A [10/15/2013] 33 Made in USA
thermostat or
Adjust thermostat to warmer temperature. Following occurs:
– Signal from processor board activates water or
steam valve.
– Motorized valve opens and allows hot water or steam
to run through coil.
– Indoor fans run, blowing air through hydronic coil
• Units equipped with Control, indoor fan and motorized damper operation will be delayed until hydronic coil reaches 100 ± 5°F (38 ± 3°C).
– Signal to water or steam valve continues until
room temperature rises above setpoint by 3°F (2°C).
system switch in HEAT position.
Page 34
MAINTENANCE
Monthly Inspection And Maintenance
!
WARNING
Electrical shock hazard — disconnect power to
To manually reset limit switch;
Remove control box cover. Locate limit switch. Push reset button in. See Figure 32, page 37.
replacement PTAC/PTHP before servicing or accessing control compartment. Failure to do so
Figure 32 Manual Reset Limit Switch
could result in severe personal injury or death.
Reset Button
NOTICE
It is illegal to discharge refrigerant into atmosphere. Use proper reclaiming methods and equipment when servicing RetroAire replacement PTAC/PTHP.
For optimum performance and reliability of your RetroAire replacement PTAC/PTHP, manufacturer recommends performing the following inspections and maintenance on a monthly basis. Units that are installed in harsh or dirty environments will require more frequent inspections and maintenance.
Disconnect power to unit and remove access panels.
Clean or replace indoor air lter.
Vacuum return air grille surface.
Inspect & clean chassis interior for rodent or insect
infestation.
☐ Clean & ush condensate drain pan and chassis
base pan.
☐ Verify condensate drain is functioning properly, if
applicable.
☐ Inspect refrigeration tubing, braze joints, for
signs of refrigerant leaks (oil residue). Repair if necessary.
☐ Inspect indoor and outdoor coils. Verify dirt
or debris have not collected on ns. Clean if necessary. Take care not to damage coil ns when cleaning. Use n comb to straighten any bent ns.
☐ Examine control box. Verify all wire connections
are secure.
☐ Verify indoor blower wheels and outdoor fan
blades are secured to their motor shafts.
☐ Verify dirt or debris have not collected on indoor
blower wheels and outdoor fan blades. Use vacuum and soft brush to clean if necessary.
☐ Units with hydronic option installed, inspect
piping, braze joints, for signs of water leaks. Repair if necessary.
☐ Clean exterior cabinet as desired with mild soap
or household cleaner.
5 kW heat models only — in event limit switch
opens and de-energizes electric heat, manually reset limit switch.
The Right Fit for Comfort 34 P/N 240010328, Rev. A [10/15/2013]
Clean or replace return air lter as needed. Allowing dust to collect on lter will cause unit to lose efciency and eventually malfunction. Check lter at least once month. Some environments may require more frequent replacement, depending on particulate in air stream.
If new air lter is needed for your RetroAire replacement PTAC/PTHP, consult manufacturer for availability and/or proper sizing.
Seasonal Start-Up And Maintenance
Perform complete mechanical check and maintenance inspections at beginning of cooling and heating season.
Disconnect power to unit and remove access panels.
• Perform inspections and maintenance dened in "Monthly Start-Up And Maintenance."
• Visually check equipment. Look for changes in unit such as damaged coils or evidence of extended wear on any moving parts.
• Check for unusual odors, oil leaks, or stains on or around coil and refrigerant lines. Presence of oil may indicate potentially serious problem such as refrigerant leak (example — burned motor windings, water, or
refrigerant).
• Verify base pan is clean.
• Inspect all electrical connections. Look for frayed wires and poor connections. Terminal ends that are loose will eventually fail, causing loss of performance or worse.
*Note:
Button will pop out when limit switch opens.
Push in to reset.
NOTICE
Page 35
MAINTENANCE
• Check fan motors and blower assemblies. Some units may require drop of light oil to motors and/or bearing assemblies (look for oil cups). Verify set-screws and motor mounting hardware are secure.
• Brush and/or vacuum centrifugal fan blades and blower cage assemblies.
• Inspect both indoor and outdoor coils. Use n comb to straighten any damaged ns. for proper operation.
Coils must be clean
Heat Pump Units — Temporary Emergency Heating Mode
Heat pump failure, control board can be forced into electric heat mode. This is temporary solution until heat
pump system is repaired.
NOTICE
Do not use solvent-based cleaner to clean coils, some solvents will produce noxious odor when unit is operating.
• Look for oil leaks or stains on or around all braze joints and refrigerant lines. Presence of oil indicates potentially serious problem (such as a refrigerant leak).
• Inspect and clean drain pan and drain line(s). Use of anti-fungicide tablet to keep condensate system free from bacterial contaminants is recommended.
• Verify unit pitch. Building and equipment may settle, causing shift in direction of condensate ow. Unit should pitch minimum of 5°(at least ½”) to outside allowing for proper drainage.
Troubleshooting Sensors
1.
2.
• Locate circuit board in control section of unit.
• Locate terminals where outdoor sensor connects to circuit board.
• Use small needle nose type pliers, disconnect one side of sensor from circuit board. 2-stage thermostat will provide Emergency heat.
• Circuit board sees this as outdoor coil freeze condition energizing electric resistance heater on call for heat.
• See "Manual Reset Limit Switch". See Figure 34, page 34 to reset limit switch if needed.
See Figure 33 for location of sensor connections to control board.
If temperature response of indoor or outdoor sensor is not correct, disconnect sensor from control board and check sensor resistance. Replace sensor if resistance is not close to values in Table 4.
• Check weep holes along rear ange of base pan to ensure free of debris.
• Check seal around unit is not broken or damaged.
NOTICE
Air leaks make conditioned area uncomfortable drafty or produce noise. Visually inspect foam gasket between wall and unit, taking note of separation between air inlet for condenser and condenser coil discharge. These areas must be sealed off from each other. If you experience poor cooling operation or erratic operation, check for air recirculation at condenser coil.
• Replace access panels and reconnect electrical power.
• Test unit operation.
Table 4 Sensor Resistance Values
Resistance, K ohms
77 (25°C) 10.0 K
50 (10°C) 19.9 K
35 (1.6°C) 30.0 K
30 (-1.1°C) 34.4 K
Figure 33 Sensor Connections On Control
Board
Indoor Sensor Connections
Outdoor Sensor Connections
P/N 2400103028, Rev. A [10/15/2013] 35 Made in USA
Page 36
Troubleshooting
TROUBLESHOOTING
!
WARNING
Fire, explosion, and electrical shock hazard. Troubleshooting procedures shall be conducted by a qualied technician. Improper installation could result in death or serious injury.
Symptom Suggestion
No heat or cooling
Thermostat calls for cooling, no cool air is coming from unit.
Light on circuit board is blinking.
Circuit board light is blinking 3 or 4 times, there is no freeze condition. (See Table 13, page 38)
Thermostat is satised, fan is still running.
• Verify unit has power and thermostat is satised. If thermostat is not satised, call your installing contractor or service contractor.
• Verify continuity between thermostat and unit. Verify 24 Vac is present across terminals C and R.
• Check outdoor coil for dirt debris, remove any foreign material. Locate high pressure switch reset button and push button.
• Some units are equipped with LCDI (Leakage Current Detection Interrupt) line cord. Verify line cord is reset by pressing reset button at line cord plug.
Note: If evaporator fan is operational and above suggested procedures have been followed, and there is no cooling being supplied by unit, contact trained heating and cooling professional.
Circuit board uses light for diagnostic purposes. Code determination: 1 blink = normal operation 2 blinks = compressor lockout (ASCT — Anti-Short Cycle Timer) 3 blinks = outdoor freeze condition 4 blinks = indoor freeze condition 5 blinks = simultaneous Y and W call (Straight cooling units only)
• Verify sensors have not been damaged.
• Remove sensor wires from control board and take resistance measurements, compare to following sensor resistances. Indoor and outdoor coil sensor wires and control board are labeled.
• Verify sensors are correctly wired.
77°F = 10KOhms 50°F = 19.9KOhms 35°F = 30KOhms 30°F = 34.4KOhms
• Thermostat set to Auto mode, once thermostat is satised, fan stays energized for extra 60 seconds to purge unit of excess cool or warm air in plenum.
• If thermostat fan switch is set to ON, fan stays energized regardless of thermostat being satised or not. To turn fan off turn unit off or turn thermostat fan switch to AUTO.
Units equipped with electric heaters have temperature limit switch to prevent electric
Thermostat calls for heat, no heat comes from unit.
heater from reaching unsafe temperatures. After calling for heat, heater is not energized, check for continuity across limit. If limit is open, replace with equivalent limit switch. Auto reset / Manual reset Switch (Requires trained professional)
• Verify unit has power or thermostat has been satised. If unit has power and thermostat is satised, turn thermostat few degrees above room temperature.
• Verify LCDI line cord has not tripped.
Thermostat calls for heat while in heat pump mode, heated air is not coming from unit.
• Verify thermostat while in heat pump mode is not energizing O terminal. RetroAire units are designed to work in heat pump mode when 24vac is present across Y and C.
• Verify heat pump jumper on control board is jumping two pins labeled “HP”. See control board jumper locations, Figure 28, page 29.
• Verify there are no freeze conditions. See "Circuit board light is blinking" above for more information.
The Right Fit for Comfort 36 P/N 240010328, Rev. A [10/15/2013]
Page 37
HYDRONIC HEAT PERFORMANCE
Table 5 R10 | R20 | R35 | R45 C/H hydronic heat * —
performance 104-101 (single row
coil)
P/N 2400103028, Rev. A [10/15/2013] 37 Made in USA
Page 38
ELECTRICAL SPECIFICATIONS
Table 6 R10, R20, R35, R45, - 9.000 Btu Electrical Specications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 7.5 47 1.4 0.09 1.4 0.125 N/A N/A N/A N/A 10.5 N/A 12.4 15 5-15P
115V 104 8.0 45.6 1.4 0.09 1.6 0.125 N/A N/A N/A N/A 11 N/A 13.0 20 5-15P
208/ 230V 197 4.0 22.2 0.6 0.08 0.71 0.09 0 N/A N/A N/A 5.3 N/A 6.3 15 6-15P
208/ 230V 197 3.9 20 0.6 0.08 0.71 0.09
265V 240 3.32 18.8 0.67 0.08 0.71 0.09
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2 15
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
5 N/A N/A N/A N/A N/A N/A N/A
Table 7 R10, R20, R35, R45 - 12,000 BTU Electrical Specications
N/A 6.2 15 6–15P
5.2
N/A N/A N/A N/A
4.7
15 6–15P
20 6–20P
25 6-30P
30 6-30P
7-20P
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
115V 104 10.8 53 1.4 0.09 1.6 0.125 0 N/A N/A N/A 13.8 N/A 16.5 25 5-20P
115V 104 12.7 63 1.4 0.09 1.25 0.125 0 N/A N/A N/A 15.4 N/A 18.5 30 5-20P
208/ 230V 197 5.6 29 0.6 0.08 0.71 0.09
265V 240 4.6 20 0.67 0.08 0.71 .09
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
5 N/A N/A N/A N/A N/A N/A N/A
N/A 8.3 15 6–15P
6.9
N/A 7.1
6.0
15 6–15P
20 6–20P
25 6-30P
30 6-30P
15
7-20P
The Right Fit for Comfort 38 P/N 240010328, Rev. A [10/15/2013]
Page 39
ELECTRICAL SPECIFICATIONS
Table 8 R10, R20, R35, R45, - Cooling Capacity 15 Electrical Specications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/ 230V
265V 240 6 28 0.67 0.08 0.71 0.09
Compressor
197 7.4 33 0.6 0.08 0.71 0.09
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
5 N/A N/A N/A N/A N/A N/A N/A
N/A 10.6 15 6–15P
8.7
N/A 8.9
7.4
15 6–15P
20 6–20P
25 6-30P
30 6-30P
15
Table 9 R10, R20, R35, R45 - Cooling Capacity 18 Electrical Specications
Power Supply
Volt — 1–60
Volt Min RLA LRA FLA Hp FLA Hp Htr # Volt W HA TCA THA MCA MOCP Plug
208/ 230V
265V 240 N/A N/A N/A N/A N/A N/A
Compressor
197 8.3 44 0.6 0.08 0.71 0.09
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat Unit Electrical Ratings
0 N/A N/A N/A
208 1636 7.9 8.5 10.4
2
230 2000 8.7 9.3 11.5
208 2454 11.8 12.4 15.3
3
230 3000 13 13.6 16.9
208 3271 15.7 16.3 20.3
4
230 4000 17.4 18 22.3
208 4089 19.7 20.3 25.2
5
230 5000 21.7 22.3 27.8
0 N/A N/A N/A
2 265 2655 10 10.7 13.2 15
3 265 3983 15 15.7 19.5 20
4 265 5310 20 20.7 25.7 30 7-30P
5 N/A N/A N/A N/A N/A N/A N/A
N/A 11.7 15 6–15P
9.6
N/A N/A N/A N/A
N/A
15 6–15P
20 6–20P
25 6-30P
30 6-30P
7-20P
7-20P
P/N 2400103028, Rev. A [10/15/2013] 39 Made in USA
Page 40
ELECTRICAL SPECIFICATIONS
The Right Fit for Comfort 40 P/N 240010328, Rev. A [10/15/2013]
Page 41
NOTES
P/N 2400103028, Rev. A [10/15/2013] 41 Made in USA
Page 42
NOTES
The Right Fit for Comfort 42 P/N 240010328, Rev. A [10/15/2013]
Page 43
Page 44
ECR International Inc
2201 Dwyer Avenue
Utica, NY 13501
e-mail: info@RetroAire.com
An ISO 9001-2008 Certied Company
Loading...