Response Alarms SA3 Installation & Operating Manual

Installation & Operating Manual
SA3
6 Zone Wirefree
Alarm System
1
2
3
4
5
6
7
*
0
#
8
ENTER
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 5 ZONE 6 FIRE TAMPER
9
FOREWORD
All components in this wirefree Alarm System are
designed and manufactured to provide a high standard of security protection and long, reliable service.
The system is designed for ease of installation using only conventional domestic tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual and plans the system before proceeding with the installation.
During installation, it is important that the procedures described in this manual are followed in sequence.
This manual should be retained in a safe place for
future reference.
IMPORTANT
All components, with the exception of the External
Solar Siren are suitable for mounting in dry interior locations only.
DECLARATION
Novar ED&S hereby declares that this wirefree alarm
system is in compliance with the essential requirements and other relevant provisions of the Radio and Telecommunications Terminal Equipment (R&TTE) directive, 1999/5/EC.
No radio operating licence is required for this equipment.
Tools and Equipment Required:
No.0 Philips Screwdriver Drill
No.1 Philips Screwdriver Bradawl No.2 Philips Screwdriver Small Spirit Level 5 & 6mm Masonry Drill Bits
DEVICE RANGE
The quoted range of the system devices (see
component specification on rear cover) is measured in ideal conditions. Any solid object (e.g. walls, ceilings, reinforced PVC doors etc) placed between the transmitter devices and the Receiver(s) will reduce the transmission range of the devices.
The amount by which the range will be reduced is dependant upon the nature of the barrier. e.g.
Wall Type Range Reduction
Dry-lined partition wall: 10-30%
Single layer brick wall: 20-40% Double layer brick wall: 30-70% Metal Panel/Radiator: 90-100%
Note: The effect on the range of multiple walls is
cumulative. i.e. if there are two brick walls in the way, the range will be reduced by up to 40% by each wall.
SYSTEM SECURITY
This system has been designed to both detect
intruders and act as a strong deterrent to would-be intruders when installed correctly.
Please remember that given adequate knowledge and time it is possible to overcome any alarm system and we therefore recommend that an Intruder Alarm is used in conjunction with good physical protection such as security window and door locks.
All units in the system are encoded to operate together using an 8 bit House Code which is configured by the user/installer to provide the unique identification code for your installation. The system House Code can be changed at any time by the user.
The system is operated from one or more Remote Control units and/or the Control Panel. Care should be taken to ensure that your Remote Control Unit(s) are not lost or the User Access Codes for the Control Panel do not become known to other people as this will compromise the security of your system. In either event the system house code and User Access Codes should be changed as soon as possible.
SAFETY
Always follow the manufacturers advice when using
power tools; steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes etc.
Before drilling holes in walls, check for hidden electricity cables and water pipes, the use of a cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned on a firm stable surface at the correct angle and suitably secured before use.
The use of ear defenders is advisable when working in close proximity to the Siren due to the high sound level produced by this device.
SA3 6 Zone Wirefree Alarm SystemFriedland
IMPORTANT: All units in your system must be set
to the same House Code which must be changed from the factory supplied setting.
CONTENTS
Page No.
KIT CONTENTS 2
INTRODUCTION AND OVERVIEW
3
System Arming
3
Entry/Exit Delay
3
Zones
3
Zone Lockout
3
Tamper Protection
4
Jamming Detection
4
Battery Monitoring
4
System House Code
4
PLANNING AND EXTENDING YOUR WIREFREE ALARM SYSTEM
5
REMOTE CONTROL UNIT
6
General Information
6
Configuring the Remote Control
7
CONTROL PANEL
7
Positioning the Control Panel
7
Installing the Control Panel
7
Configuring the Control Panel House Code
8
Testing the Control Panel & Remote Control
9
PASSIVE INFRA-RED (PIR) MOVEMENT DETECTORS
10
Positioning the PIR Movement Detectors
10
Installing and Configuring the PIR Movement Detectors
11
Testing the PIR Movement Detectors
12
MAGNETIC CONTACT DETECTORS
12
Positioning the Magnetic Contact Detectors
13
Installing and Configuring the Magnetic Contact Detectors
13
Testing the Magnetic Contact Detectors
14
EXTERNAL SOLAR SIREN
14
General Information
14
Positioning the Solar Siren
15
Installing and Configuring the Solar Siren
15
Power-up of the Solar Siren
16
Testing the Solar Siren
17
Page No.
EXTERNAL CONNECTIONS
17
TESTING THE SYSTEM
17
Initial Testing
17
Testing An Installed System
17
FACTORY DEFAULTS
18
Reset Factory Default Conditions
19
PROGRAMMING
19
User Access Code
19
System House Code
19
Instant/Delay Zones
20
Entry/Exit Delay
20
Alarm Duration
20
Part-Arm
20
Zone Lockout
21
Entry/Exit Warning Tone
21
Jamming Detection
21
NO/NC Relay Contacts
22
Zone Operating Modes
22
OPERATING INSTRUCTIONS
23
Arming The System
23
Part-Arming The System
23
Disarming The System
23
Personal Attack (PA) Alarm
24
Tamper
24
Siren Service Mode
24
Siren Operating Mode
24
Battery Monitoring
25
MAINTENANCE
25
ALARM RECORD
26
TROUBLE SHOOTING
27
EXTENDING YOUR ALARM SYSTEM
29
COMPONENT SPECIFICATION
Back Cover
1SA3
KIT CONTENTS
The Alarm System should contain the following
components.
1xExternal Solar Siren 1xControl Panel 1xRemote Control 2xPIR Movement Detectors 2xMagnetic Contact Detectors
Also included:
Power Supply Adaptor
Installation & Operating Manual Fixing pack Batteries
EXTENDING THE ALARM SYSTEM
The following additional accessories are available to
enhance your system and provide further protection and a higher level of security where required.
Component: Product Code
Two Magnetic Contact Detectors
and one Remote Control SU1
Tw o Passive Infra-Red Movement Detectors SU2
Tw o Remote Controls SU3
Two Magnetic Contact Detectors SU4
Remote Keypad SU5
External Solar Siren SU6
Full details of these accessories are given on page 29.
2 SA3
1
2
3
4
5
6
7
*
0
#
8
ESC
ENTER
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 5 ZONE 6 FIRE TAMPER
9
WP1.2-6
External Solar Siren
Control Panel
Magnetic
Contact
Detector
Remote
Control
PIR Movement
Detector
6V/1.2Ahr
Sealed lead acid battery
(supplied fitted in
Solar Siren)
9V PP3 Alkaline
battery
(for PIR Detectors)
3V CR2032 Lithium Cell (for Remote Control and
Magnetic Contact
Detectors)
INTRODUCTION AND OVERVIEW
SYSTEM ARMING
The system has a full ‘Arm’ and a ‘Part-Arm’ mode.
Full ARM will arm all zones while the ‘Part-Arm’ will only arm the zones that are enabled for “Part-Arm”.
For example:
The system could be configured such that during night
time, ‘Part-Arm’ would arm only zones protecting the lower floor and outbuildings leaving the upper floor free for movement without triggering the alarm.
However, when the property is left un-occupied, the full ‘Arm’ mode will arm all zones to protect the entire property, (i.e. upper and lower floors and outbuildings).
ENTRY/EXIT DELAY
Each zone can be programmed to be Armed in either
Instant or Delay mode.
Usually the zone covering the main entrance door and the route to and from the Control Panel would be configured in Delay mode. This allows time for the user to exit the property after setting the system at the Control Panel or to Disarm the system before an alarm condition is triggered when re-entering the property. The remaining zones would be configured as Instant allowing them to initiate an alarm immediately a detector on the zone is triggered.
Delay Armed zones will not become fully armed until after the Entry/Exit delay period has expired. When a
detector on a Delay Armed zone is triggered, an alarm condition will not be triggered until after the Entry/Exit period has elapsed. If the system is not disarmed during the delay period, an alarm condition will occur when the delay period expires.
Instant Armed zones are immediately able to initiate an alarm as soon as the system begins to arm.
Note: To conserve power and maximise battery life
the PIR Detector will only detect movement if there has been no movement detected within the previous 2 minutes. Consequently the PIR Detector will not become active until the protected area has been free from movement for more than 2 minutes.
ZONES
The system incorporates 6 wirefree Alarm Zones for
the connection of the system detectors that are used to independently monitor different areas of the property. In addition to standard intruder protection, each zone may also be configured to operate in one of three other modes:
- ‘Personal Attack’ mode provides 24 hour monitoring of any Personal Attack (PA) switches incorporated into the system.
- ‘24-hour Intruder’ mode provides 24 hour intruder protection for areas where continuous monitoring is required, (e.g. gun cupboards).
- ‘Fire’ mode provides 24 hour monitoring of any Fire/Smoke detectors incorporated into the system.
ZONE LOCKOUT
If a detector on an active zone is triggered while the
system is armed an alarm condition will occur. After the programmed alarm duration has expired the alarm will stop and the system will automatically reset. Subsequent detectors triggered will again initiate an alarm condition. If a single zone initiates an alarm condition more than three times then that zone will be ‘Locked Out’ and any further alarm signals from that zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if
required.
SA3 3
Full Arm
Part-Arm
INTRODUCTION
TAMPER PROTECTION
All system devices (except any Remote Control
Units) incorporate Tamper protection features to protect against unauthorised attempts to interfere with the device.
Any attempt to remove the battery cover from any device (except a Remote Control) or to remove the Solar Siren or Control Panel from the wall will initiate an alarm condition (unless the system is in Test or Programming modes), even if the system is Disarmed.
JAMMING DETECTION
In order to detect any attempts to illegally jam the
radio channel used by your alarm system, a special jamming detection function is incorporated into the Control Panel and Solar Siren. If this feature is enabled, and the radio channel is jammed continuously for 30 seconds, when the system is armed, the Solar Siren will emit a pre-alarm series of rapid bleeps for 5 seconds. If the jamming continues for a further 10 seconds or more a full alarm condition will occur. In addition if the system is jammed for more than three periods of 10 seconds in a 5 minute interval, this will also generate a Full Alarm condition.
The Jamming Detection circuit is designed to permanently scan for jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detection function permanently enabled.
Note: The jamming detection features incorporated
into the Control Panel and optional Solar Siren operate independently.
BATTERY MONITORING
All devices powered by non-rechargeable batteries
incorporate a battery level monitoring feature which will warn of a low battery status. In addition the Control Panel will also indicate a low battery status within any Passive Infra-Red or Magnetic Contact Detector on the system. The batteries on any device indicating a low battery status should be replaced immediately.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to
operate or disarm your system, you must configure your system to accept radio signals only from your own system devices. This is done by setting a series of eight miniature (DIP) switches in all devices (except the Control Panel) to the same ON/OFF combination (the House Code) selected by the user/installer. The Control Panel is then programmed to operate only with devices set to this House Code. All detectors and Remote Control Unit(s) must be configured with the same House Code in order for the system to operate correctly.
Inside the Siren, Detectors and Remote Control Unit is a series of 8 DIP switches.
The House Code is set up by moving each of the 8 switches in each device to the same randomly selected ON/OFF sequence. When setting the DIP switches, ensure that each switch ‘clicks’ fully into position. Use the tip of a ballpoint pen or a small screwdriver to move each switch in turn.
SA34
e.g.
Switch 1 = set to ON position
ON
1 2 3 4 5 6 7 8
INTRODUCTION
Note: It is recommended that the system House
Code is always changed to a code other than the factory default.
Before attempting to install your Alarm System it is
important to study your security requirements and plan your installation.
PIR Movement Detectors are used to protect the main areas of the property, (e.g. lounge, study, hallway and landing). Magnetic Contact Detectors are typically used to protect the main access points to the property, (e.g. front door, back door, patio doors). However, they can also be used to protect other vulnerable doors/windows or access doors to important rooms.
TYPICAL INSTALLATION
The following example below shows typical property
incorporating the suggested positions for the External Siren, PIR and Magnetic Detectors. Use this as a guide for your installation in conjunction with the detailed positioning requirements for each device provided in the appropriate installation sections in this manual for planning your intruder alarm system.
PLANNING AND EXTENDING YOUR WIREFREE
ALARM SYSTEM
LED Control Panel
Magnetic Contact Detector
Magnetic Contact Detector
External Solar Siren
PIR Movement
Detector
PIR Movement
Detector
Remote Control
SHED
LOUNGE
GROUND FLOOR
GARAGE
KITCHEN
HALL
DINNING
ROOM
PIR Movement Detector
PIR Movement Detector
PIR Movemen
t
Detector
Back Door
SA3 5
INTRODUCTION
SA36
Typical Installation using only detectors supplied:
1.
Place the 1st Magnetic Contact detector (set on Zone 1) on the front door.
2.
Place the 1st PIR Detector (also set on Zone 1) in the hall covering the Control Panel and routes between downstairs rooms.
3.
Place the 2nd Magnetic Contact detector (set on Zone 2) on the back or Patio doors.
4.
Place the 2nd PIR Detector either
i) downstairs in the main living room containing most
valuables, (set on Zone 3), or
ii) upstairs on the landing covering the access
routes between bedrooms and the stairs, (set on Zone 5). This will be inactive if Part-Arm is used.
The system may be expanded with additional detectors, Remote Controls and Keypads to provide even greater protection. However the following rules should be followed:
a) Any detectors covering the main door and the route
to the Control Panel should be set on zone 1 only.
b) Any detectors covering the remainder of the lower
floor should be set on zones 2 to 4 only.
c) Any detectors placed upstairs should be set on
zones 5 or 6 only.
The system default settings are pre-configured to provide a basic functional system to suit most typical basic installations:
Zone 1 is configured as a Delay zone with a 30s
entry/exit delay.
As soon as installation is complete, this should be changed to your own code that only you and other system users know.
All other zones are instant.
The system has a 3 minute alarm duration.
Zone Lockout is enabled.
PART-ARM is configured to operate with detectors
on zones 1 to 4 only. Detectors on zones 5 & 6 are inactive in part-arm.
Note: If you wish to change the system configuration
away from the above example and system default settings and customise it to your own unique requirements then refer to the Programming section on page 19.
REMOTE CONTROL UNIT
The Remote Control Unit(s) are used to Arm, Part-Arm
and Disarm the system.
The Remote Control Unit also incorporates a Personal Attack (PA) switch. Activating the PA switch on the side of the Remote Control will immediately initiate a Full Alarm condition whether the system is Armed or Disarmed. The alarm can be cancelled by pressing the ’DISARM’ button on the Remote Control or via the Control Panel.
Any number of Remote Control Units can be used with your system, providing they are all coded with the system House Code.
The Remote Control is powered by a CR2032 type Lithium cell which under normal conditions will have an expected life in excess of 1 year. Under normal battery conditions the LED on the Remote Control will only illuminate when a button is pressed. However, under low-battery conditions this LED will continue to flash after the button has been released. When this occurs the battery should be replaced as soon as possible.
Slide up to operate
Transmit LED
Personal Attack
Arm
Part-Arm
Disarm
INSTALLATION
Note:
All system components must be set to the
same House Code.
IMPORTANT:
All system components must be set to the same
House Code.
The default User Access Code for the Control Panel is "1234", this should be changed to your own code that only you and other system users know as soon as installation is complete.
CONFIGURING THE REMOTE
CONTROL
1.
Remove the rear cover by undoing the small screw on the rear of the Remote Control.
2. Select and record a random combination of ‘ON’ and ‘OFF’ positions for the DIP switches. This will be the system House Code that enables all elements of your transmitters to communicate with the Control Panel.
IMPORTANT: The House Code for your system
should be changed from the factory default setting.
3.
Ensure that the jumper link located immediately below the House Code DIP switches is fitted in position for use with this alarm system.
4.
Insert the battery under the clip ensuring that the +ve terminal faces upwards away from the PCB.
5. Replace the rear cover and fixing screw. Do not over tighten the screw as this could damage the thread.
CONTROL PANEL
Outside View of Control panel
POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control
Panel, the following points should be considered.
1.
The Control Panel should be located in a position out of sight of potential intruders and in a safe location, but easily accessible for system operation.
2.
The Control Panel should be mounted on a sound flat surface to ensure that the rear tamper switch on the Control Panel is closed when the Panel is mounted. The Control Panel should be mounted at a convenient height of between 1.5 and 2m and in a position where it will be seen each day.
Note: If small children are in the household, a
further consideration should be given to keeping the units out of their reach.
3. It is recommended that the Control Panel should be positioned such that the Exit/Entry tone (emitted by the Control Panel) can be heard from outside the property.
4. The Control Panel should be mounted within a protected area so that any intruder cannot reach the Control Panel without opening a protected door or passing through an area protected by a PIR movement detector when the system is armed.
5. The Control Panel must be located within reach of a mains socket.
6.
Do not locate the Control Unit closer than 1m to any large metallic object, (e.g. mirrors, radiators, etc) as this may affect the radio range of the Control Panel.
INSTALLING THE CONTROL PANEL
1.
Undo the two captive fixing screws on top of the panel and open the cover. The cover is hinged along the bottom edge.
2.
Unclip and remove the two back-up batteries on either side of the panel.
3.
Hold the Control Panel in position on the wall and mark the positions of the four fixing holes. Remove the Panel and drill four 5mm holes and fit the 25mm Wall Plugs.
Note: The wall plugs supplied with the product are
not suitable for plasterboard walls, if mounting the Control Panel onto plasterboard use appropriate wall plugs.
IMPORTANT: Do not drill the fixing holes with the
Control Panel in position; as the resulting dust and vibration may damage the Control Panel’s internal components and invalidate the guarantee.
House Code
DIP Switches
Jumper Link
Battery Clip
Battery
Zone LEDs
Status LED
s
Keypad
ENTER
ESC
123
4
5
6
789
0
*
#
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 5 ZONE 6 FIRE TAMPER
SA3 7
INSTALLATION
4.
Fit two 18mm No.4 screws into the top holes until almost fully home and hang the Control panel over these screws using the two keyhole slots in the top corners of the panel casing.
5. Route the cable from the Power Supply Unit up behind and on the right hand side of the Control Panel and connect the plug to the DC power socket in the panel, (see diagram above). Ensure that the cable is not trapped between the panel and the wall.
6.
Fix the Panel to the wall using two 18mm No.4 screws in the lower two fixing holes in the panel and tighten the upper fixing screws until they just grip the casing. Do not over tighten the fixing screws as this could damage or distort the casing.
7.
Ensure that the "Reset" and the "Hard-Wired Siren tamper detect" jumper links are set in the OFF position.
8.
Connect battery leads to both back-up batteries and refit batteries.
Battery 1 (left): Red lead to +ve battery terminal
Blue lead to –ve battery terminal
Battery 2 (right): Blue lead to +ve battery terminal
Black lead to –ve battery terminal
IMPORTANT: Take care when connecting battery
leads to the batteries as connecting incorrectly could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that the
unit is being operated from the back-up batteries and that mains supply is not present.
9.
Close the lid of the Control Panel and tighten the captive fixing screws.
10.
Plug in and switch ON the Power Supply Unit, (the Power LED should illuminate).
Note: If the Panel Tamper alarm sounds during the
installation reset the alarm by pressing:
, ,
on the Control Panel.
CONFIGURING THE CONTROL
PANEL HOUSE CODE
With unit in Standby mode (Power LED only illuminated).
1. Press
, ,
1
2
3 4
ENTER
8 SA3
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
Upper Keyhol
e
Fixing Hole
-
ve Terminal
(Black Lead)
+ve Terminal (Blue Lead)
Reset Jumper Link P1
Power Supply Jack Socket
Upper Keyhole
Fixing Hole
+ve Terminal
(Red Lead)
-
ve Terminal (Blue Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply Cable Route
Inside View of Control Panel
1
2
3 4
ENTER
User Access Code
User Access Code
INSTALLATION
Loading...
+ 22 hidden pages