Response Alarms RE5000S Installation & Operating Handbook

Page 1
PROFESSIONAL
alarm systems
RE5000S
professional
Solar Wireless Intruder Alarm System
includes:
1 x Solar Wireless
Siren and Strobe 1 x Control Unit 1 x Passive Infra
Red Detector 1 x Magnetic Contact
Detector 1 x Remote Control 1 x Power Supply
INSTALLATION & OPERATING
HANDBOOK
INSTALLATION & OPERATING
HANDBOOK
Page 2
FOREWORD
Your decision to purchase an RE5000S Remote Control Wireless Intruder Alarm System represents a major and sensible step towards total protection of your premises, its contents and its occupants.
The RE5000S Wireless Intruder Alarm System complies with the requirements of BS 6799 Class 3 for Wire-free Intruder Alarm Systems. All components are designed and manufactured to provide a high standard of security protection and long, reliable service. In addition, the radio devices are tested and approved to ensure that they will not interfere with other radio equipment. The equipment complies with the Radio & Telecommunications Terminal Equipment Directive 1999/5/EC and with EC Directive 89/336/EC in respect of Electromagnetic Compatibility for a Domestic and Light Commercial Environment. No radio license is required, however the approved radio frequency is not protected from interference and may be withdrawn from use at any time subject to the DTI giving users an appropriate notice period.
The RE5000S Wireless Intruder Alarm System is purposely designed for ease of installation using only conventional tools. However, it is essential that the installer reads and fully understands the advice and procedures contained in this manual before proceeding with the installation.
During installation, it is important that the installer follows the procedures in sequence.
All components with the exception of the external Solar Wireless Siren & Strobe are suitable for indoor use only.
This manual should be retained by the user for future reference.
Tools and Equipment Required:
150mm flat blade screwdriver 150mm cross-head screwdriver Hammer Drill and 4mm and 5mm masonry drill bits
SAFETY WARNINGS
Before proceeding with the installation, please note the following safety warnings:
1. Always follow the manufacturers advice when using power tools; steps; ladders etc. and wear suitable protective equipment (eg. safety goggles) when drilling holes etc.
2. Before drilling holes in walls, check for hidden electricity cables and water pipes. The use of a cable/pipe locator may be advisable if an any doubt.
SYSTEM SECURITY
The system may be operated remotely from one or more Remote Controls, or by entering an Access Code at the control unit keypad. Care should be taken to ensure that your Remote Control Unit(s) are not lost as the finder could Disarm your alarm before you are able to re-code the system.
This system has been designed to both detect intruders and act as a strong deterrent to would-be intruders. However, we recommend that an Intruder Alarm System is always used in conjunction with good physical protection such as security window and door locks.
Response RE5000S Professional Alarm System
Page 3
1RE5000S Professional Alarm System
CONTENTS
Page No.
FOREWORD Inside Front Cover
INTRODUCTION & OVERVIEW 2
EXTENDING THE RE5000S SYSTEM 2
PLANNING AND EXTENDING YOUR WIRELESS ALARM SYSTEM 4
CONTROL UNIT
Indicators and Keypad 5 Location 5 Installation 6 Back-up Battery 7
SYSTEM HOUSE CODE 7
REMOTE CONTROL(S) 8
SETTING THE CONTROL UNIT HOUSE CODE 8
SETTING THE CONTROL UNIT TO TEST MODE 9
SYSTEM ZONING 9
WIRELESS PASSIVE INFRA RED DETECTOR(S)
Setting 10 Mounting 11 Testing 11
FITTING THE STANDARD MAGNETIC CONTACT DETECTOR(S) 12
INSTALLING AND SETTING THE EXTERNAL SOLAR WIRELESS SIREN & STROBE
Location 13 Installation 14 Setting 14 Initial Power-Up 14
PROGRAMMABLE FUNCTIONS
House Code 15 Instant/Delay Zone 16
Page No.
PROGRAMMABLE FUNCTIONS (cont)
Exit Delay Time 16 Alarm Autostop Time 16 Main User Access Code 16 Door-Chime Zone 17 Entry Delay Time 17 Part Arm Zone Omit 17 Exit Delay Tone 18 Quick Arm/Part Arm 18 Jamming Detection System 18 Siren Code 18 Second User Access Code 19
EXTERNAL CONNECTIONS 19
OPERATING INSTRUCTIONS
Fully Arming the System 20 Part Arming the System 21 Disarming the System 21 Disarming After an Intrusion 21
PERSONAL ATTACK, MEDICAL AND FIRE ALARM 21
BATTERY MONITORING 22
TESTING THE SYSTEM 22
MAINTENANCE
Control Unit 23 Solar Siren & Strobe 23 Rechargeable Batteries 23 Detectors & Remote Controls 23
TROUBLE SHOOTING 24
ALARM RECORD 26
EXTENDING YOUR RE5000S PROFESSIONAL WIRELESS ALARM SYSTEM 27
YOUR GUARANTEE Inside Back Cover
RE5000S SPECIFICATIONS Back Cover
Page 4
2 RE5000S Professional Alarm System
INTRODUCTION & OVERVIEW
The RE5000S Alarm System is designed to allow flexibility in configuring and using the system. The Detectors can be set to operate on any one of 6 Zones, to give an instant alarm or a variable timed entry delay. There is no limit to the number of detectors per Zone.
A normally closed, hard-wired Zone input is also available on Zone 6.
Part Arm allows only selected detection Zones to be armed. For example, for night time protection you can ‘Arm’ the downstairs areas, garage and outbuildings, whilst allowing you free access to the upstairs areas without activating your alarm.
The Control Unit is programmed and operated via its integral keypad. A Main User Access Code allows general operation (Arming/Disarming) and full access to the programming menu, whilst a Second User Access Code allows Arming/Disarming only and may therefore be entrusted to children, neighbours or guests.
Separate wireless zone inputs and wired output facilities are available for Medical Alert and Fire Alarm, and a multicore cable connection is supplied to allow full system status outputs to a security dialler or communicator.
The Control Unit also incorporates a sophisticated Jamming Detection Circuit with Jamming Counter and pre-alarm indication.
A Zoneable Door-Chime, Quick Arm Operation and Walk Test Facilities are also selectable via the Control Unit.
The RE5000S Wireless Intruder Alarm package contains all the components necessary to install a complete Intruder Alarm System within your premises. You can increase your protection by adding additional Wireless Passive Infra Red Detectors and Wireless Magnetic Contact Detectors either at the time of initial installation or at a future date. You may also wish to purchase additional
Remote Control Unit(s) for use by other members of your household. Full details of other accessories to extend your system are given on pages 27 and 28.
The items included in your RE5000S package are shown opposite:-
EXTENDING THE RE5000S SYSTEM
The following additional accessories are available to enhance your system and provide further protection and a higher level of security where required.
Part No. Description
RE5000P Wireless Passive Infra
Red Detector
RE5000R Remote Control Unit
RE5000M Wireless Magnetic Contact
Detector
RE5000MHW Wireless Magnetic Contact
Detector with optional hard-wired input facility
RE5000SD Wireless Smoke Detector
RE5000SS Additional Solar Wireless
Siren & Strobe
RE5000D Dummy Siren & Strobe
RE5000MP Medical Alert Pendant
RE5000AD Security Dialler
Page 5
RE5000S Professional Alarm System 3
Control Unit with
Communicator
Wiring Interface
Control Unit in-line
Mains adaptor
Also included:-
Installation and operating manual
All necessary fixings
Window warning stickers
Solar Wireless Siren & Strobe
(incorporating rechargeable battery)
Rechargeable Batteries
(fitted in the Control Unit
and the Siren & Strobe)
Detector and Remote
Control Alkaline Batteries
Wireless Passive Infra Red Detector
(RE5000P)
Wireless Standard Magnetic
Contact Detector (RE5000M)
Wireless Remote
Control (RE5000R)
Page 6
RE5000S Professional Alarm System4
For even greater protection you can install as many PIRs and Magnetic Contact Detectors as and when you require. The RE5000S Alarm System
is designed to give you protection for a two bedroomed house. Just add additional detectors where further protection is needed.
PLANNING AND EXTENDING YOUR WIRELESS ALARM SYSTEM
PART ARM
Protect either all of your home or just the areas you choose. For example, for night time protection you can have downstairs plus the garage and shed ON whilst upstairs is OFF. This allows you to occupy upstairs areas without activating your alarm.
PLANNING YOUR INSTALLATION
Before attempting to install your RE5000S Wireless Alarm System it is important to study your security requirements and plan your installation, including Zoning and Entry/Exit routes.
Each property will have its own layout, the diagram shown is intended as a guide.
Page 7
CONTROL UNIT
INDICATORS AND KEYPAD
LOCATION
When choosing a suitable location for the Control Unit, the following points should be considered.
1. Ensure that the Control Unit is within a protected area with the system Armed, ie: an intruder cannot reach the Control Unit without opening a protected door or being detected by a movement detector.
2. The position selected must be within reach of a 13A socket, or fused connection unit.
Note: Ensure that the adaptor will not be removed from the socket or accidentally switched off, when the system is in use.
3. The Control Unit should be close to the entry/exit door but not visible from the door or windows.
4. Do not locate the Control Unit closer than 1 metre to any large metallic object eg: mirrors, radiators, fridge-freezers, etc.
5. Locate the Control Unit in an easily accessible position, between 1.5 and 2 metres above floor level and in a position where it will be seen each day.
RE5000S Professional Alarm System 5
View of Control Unit Indicators and Keypad
Page 8
INSTALLATION
Remove the fixing bracket securing screw and slide the fixing bracket off of the keyhole slots at the top of the Control Unit. Hold the fixing bracket level in position on the wall and mark the 3 fixing bracket holes on the wall. Drill 3 x 4mm diameter fixing holes; fully insert the plastic wall plugs supplied and secure the bracket to the wall using the three fixing screws.
An in-line DC Mains Adaptor and Cable are supplied with the Control Unit. To connect the Mains Adaptor
proceed as below:
1. Select a suitable location for the Mains Adaptor (eg: a mains supply cupboard). Using the adaptor fixing bracket as a template, mark and drill 2 x 4mm diameter holes, insert the wall plugs and secure the adaptor to the wall using the fixing bracket and double sided tape.
2. Remove the battery compartment cover and back­up battery. Lead the adaptor DC output cable along the Cable Channel in the rear of the Control Unit and plug the jack plug into the jack socket in the battery compartment.
3. Plug the 13A plug into a local socket. Alternatively, the plug can be removed and the mains lead connected to a fused connection unit (fused 3 amps) as follows:-
The wires in the mains lead are coloured in accordance with the following code:
NEUTRAL = Blue
LIVE = Brown
If the colours of the wires in the mains lead do not correspond with the markings identifying
6 RE5000S Professional Alarm System
Rear view of Control Unit/Fixing Bracket
View inside Terminal/Battery Compartment
Page 9
the terminals on your equipment proceed as follows:
The wire which is coloured Brown must be connected to the terminal which is marked with the letter L or coloured Red. The wire coloured blue must be connected to the terminal which is marked with the letter N or coloured Black.
The power supply adaptor is double insulated and does not require an Earth ( ) connection.
If you use a 13 amp fused connection unit or another plug, a 3 amp BS1362 fuse must be fitted.
MAINS ELECTRICITY CAN KILL. -
If you are in any doubt about connecting the Mains Adaptor to your power supply we recommend that you consult a qualified electrician. All works must be carried out in accordance with the IEE Regulations.
4. The green power indicator will illuminate steadily, indicating that the Control Unit is powered from the mains supply. (It is normal for the Mains Adaptor to appear warm to the touch when in use).
The Control Unit incorporates a Non Volatile Memory, which will memorise all settings indefinitely even when all power has been removed. To enable this facility to operate, the memory link must be set to the ON position.
In the event that you wish to revert the Control Unit to factory Default settings, remove all power (mains and back-up battery), set the memory link to OFF and reapply power. In all other circumstances the memory link should be left ON for full system security.
If any hard-wired connections are to be made at the Control Unit (eg: Zone 6 input, Hard-wired Siren, Telephone Dialler/Communicator etc) it is recommended that these are made AFTER the initial installation and programming of the Control Unit.
BACK-UP BATTERY
The Control Unit has provision for a 1.2 Ahr rechargeable Back-up Battery. The purpose of the battery is to supply emergency power to the Control Unit in the event of a failure of the mains supply. The Back-up Battery is capable of providing emergency power to the Control
Unit for a period of approx. 8 hours and will automatically recharge on restoration of the supply.
1. To fit the Back-up Battery, connect the battery leads red to red (+) and black to black (-) and place the battery into the battery compartment.
2. In the event of a mains failure the green power indicator will flash, showing that the Control Unit is powered by battery only.
3. Refit the battery compartment cover. Hook the Control Unit onto the backplate keyhole fixings, slide into place and secure using the fixing bracket screw.
Note: If you accidentally trigger the rear anti­tamper switch whilst fitting the control unit enter
to cancel the alarm.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to activate or disarm your system, you must set your system to accept encrypted radio signals only from your own Detector(s) and Remote Control Unit(s). This is done by setting a series of 3 position miniature switches in the Detectors and Remote Control Unit(s) to a special combination (House Code’) selected by yourself, and programming the Control Unit to recognise only this House Code combination.
IMPORTANT
In order for all detectors, Remote Control Unit(s) and accessories to communicate with the Control Unit, it is essential that the same House Code combination is used for all components. (Except the Solar Siren & Strobe and Medical Alert Pendant where fitted).
Inside your Remote Control(s) and Detectors you will find a series of 3 position miniature switches. Your House Code is set by moving each of the first 6 switches (numbered 1-
6) to a random sequence of ‘+’, ‘o’ or ‘–’ settings.
Note: When setting the miniature switches in each item of equipment, ensure that each switch clicks into position, especially in the centre oposition. Use the tip of a ball point pen or a small screw driver to move each switch in turn.
RE5000S Professional Alarm System 7
Page 10
REMOTE CONTROL(S)
One Remote Control Unit is supplied in the standard RE5000S package. However, additional Remote Control Unit(s) can be purchased separately, if required. The Remote Control Unit(s) are used to Arm and Disarm the System.
The Remote Control Unit also incorporates a personal attack button. This sounds the alarm at any time whether the system is Armed or not. Just press
and the alarm will sound. If this is activated by mistake you can cancel the alarm by pressing and releasing the Disarm button on the Remote Control.
Any number of Remote Control Unit(s) can be used with your system, providing they are all coded with the system House Code. To set the House Code and fit the battery, proceed as follows.
1. Remove the fixing screw from the back of the Remote Control Unit and carefully separate the two halves of the unit.
2. Fit the 12 Volt Alkaline battery supplied with the negative (-) towards the battery spring.
3. Set miniature switches 1-6 to a random combination of
+, o or ‘-settings. This is your House Code’.
Make a careful note of the setting of each switch as this information will be needed when you set up other items in your system.
Note: miniature switches 7 and 8 do not form part of the House Code and should be set in the
‘-’
position in the Remote Control.
Take care not to touch the printed circuit board or allow dust or moisture to enter the Remote Control Unit, as this may damage the electronic components.
4. Reassemble the two halves of the unit and secure using the fixing screw.
SETTING THE CONTROL UNIT HOUSE CODE
To enable the Control Unit to receive the radio signals from your Remote Control(s) and Detectors, the system House Code must be programmed into the Control Unit’s memory. The Control Unit learns the system House Code from the Remote Control. Ensure that a battery has been fitted and a House Code has been set in the Remote Control and then proceed as follows:-
1. Ensure that only the Control Unit’s top green mains power indicator LED is illuminated.
2. Enter . The
Control Unit is now in programming Mode. The Full Arm and Part Arm LED’s will now be illuminated and all the Zone LED’s will flash.
3.
Enter . The Zone LED’s will extinguish. (Unless a House Code has already been set in which case the LED’s will indicate the code set).
4. To set the Control Unit House Code, (or to change the House Code to the new code) simply press the Disarm (Blue) button on your Remote Control.
8 RE5000S Professional Alarm System
View Inside Remote Control
Page 11
The Control Unit will acknowledge the signal by bleeping twice and memorise the House Code set in the Remote Control. The Zone LED’s 1-6 will now indicate the House Code switch setting selected for each switch 1-6 in the Remote Control as follows:-
+= LED ONo= LED FLASHING ‘-’ = LED OFF
5. Once the House Code has been set, press twice to exit programming mode.
Note: It is possible to manually programme theHouse Code into the Control Unit, if a Remote Control is not available or not required - Refer to Programmable Functions - page 15.
SETTING THE CONTROL UNIT TO TEST MODE
Before installing Magnetic Contact Detectors, Passive Infra Red Detectors or other accessories you should set the Control Unit to Test mode. This will help to ensure that the correct House Code is used and to establish the radio range.
1. Press and hold the button, until the Control
Unit emits 2 bleeps and the Full Arm and Part Arm LED’s flash.
2. The system is now in Test mode.
3. Now, each time the Control Unit receives a
valid radio signal from a Detector or Remote Control, the Control Unit will emit 2 two-tone chimes and the associated Zone LED will flash for approximately 3 seconds.
To test the radio range of the Control Unit’s receiver, press and release the Disarm (Blue) button on the Remote Control from in and around the property and from all locations where you plan to install the Detectors and check that the Control Unit acknowledges the signals by emitting the two-tone chime (and flashing the Medical Alert (Zone 8) LED for 3 seconds).
The Control Unit should be left in Test mode whilst the detectors and other accessories are set up and installed. However, if you wish to exit the Test mode, press and hold the button until the unit emits 2 bleeps and the Arm/Part Arm LED’s extinguish.
SYSTEM ZONING
The RE5000 Detectors can be set to operate on any one of 6 Zones. There is no limit to the number of Detectors that can be installed on a Zone, although we recommend that only one Detector is installed per Zone for ease of alarm verification. Alternatively where more than 6 Detectors are installed, group all the Detectors in one area/room on the same Zone.
Zone selection is set on each Detector using the 3 position miniature switches 7 and 8, as follows:-
In addition to a Radio Detection Alarm input on Zone 6, facilities are available on the Control Unit Terminal block to also hard-wire a normally closed (open on alarm) circuit on Zone 6. The hard-wired Zone should be wired across terminals Zone 6 and GRD on the Control Unit terminal block.
Zone 6 also monitors the Control Unit Tamper Circuits, ie Control Unit fixing/battery cover Tamper switch and (where fitted) hard-wired siren tamper return.
Separate Zone inputs are available for Fire Alarm
(Zone 7) and Medical Alert (Zone 8). These Zones are pre-programmed into the RE5000SD Smoke Detectors and RE5000MP Medical Alert Pendant respectively. These devices cannot be assigned to different Zones.
RE5000S Professional Alarm System 9
Page 12
WIRELESS PASSIVE INFRA RED DETECTOR(S)
One Passive Infra Red Detector is supplied in the standard RE5000S package. However, additional Passive Infra Red Detectors can be purchased separately, if required. Passive Infra Red Detectors are designed to detect movement within a protected area. The Detector element detects differences in the infra red radiation when a person moves within the protected area. If movement is detected, a radio signal is transmitted to the Control Unit to activate the alarm.
The recommended position for a Passive Infra Red Detector is in the corner of a room mounted between
1.8m and 2m from the floor. At this height, the detector will detect movement up to 5m at 180° and 14m at 110°. Also, in this position, the 180°/110° fan­shaped detection patterns can normally offer greater protection than mounting on a flat wall. Before selecting a position for a Passive Infra Red Detector, the following points should be noted:
1. Do not position a Detector facing a window or direct sunlight. Passive Infra Red Detectors are not suitable for use in conservatories, or draughty areas.
2. Do not position a detector directly above any source of heat, eg. fire, radiators, boiler, etc.
3. Where possible, keep pets out of areas protected by Passive Infra Red Detectors. If this is not possible, alternative mounting arrangements may be required.
4. Where possible, mount the Detector such that the logical path of an intruder would cut across the fan patterns rather than directly towards the Detector to obtain best detector sensitivity.
SETTING THE WIRELESS PASSIVE INFRA RED DETECTOR(S)
Any number of Passive Infra Red Detectors can be used with your system, providing they are all coded with the system House Code and are within radio range of the Control Unit. To set the Passive Infra Red Detector, proceed as follows:
10 RE5000S Professional Alarm System
Page 13
ENSURE THAT THE CONTROL UNIT IS STILL IN TEST MODE.
1. Remove the battery cover by sliding it down
and pulling it forward. DO NOT USE A SCREW
DRIVER.
2. Using a ball-point pen, set the miniature switches 1-6 inclusive to the pre-determined House Code.
3. Determine the Zone on which each Detector is to operate and set miniature switches 7 and 8 to correspond to the required Zone. (Refer to System Zoning page 9).
4. Fit the 9 volt alkaline battery supplied to the battery terminals.
Note: As soon as the battery is connected, a two-tone chime will be emitted from the Control Unit siren and the appropriate Zone LED will flash for 3 seconds. This confirms that the House Code and Zoning is correct.
5. With the battery cover off, hold the Detector at the proposed installation position, press and release the anti-tamper microswitch. Providing the proposed location is within radio range of the Control Unit, the two-tone chime will be repeated. After the battery has been connected for approx 60 seconds the Infra Red Detector will become active causing the Control Unit to give a two-tone chime every time movement is detected.
6. Leave the battery cover off, remove the battery and proceed to mount the Detector as described.
7. Leave the Control Unit in Test mode.
MOUNTING THE WIRELESS PASSIVE INFRA RED DETECTOR(S)
1. Remove the screw (in the battery compartment) holding the wall bracket to the Detector.
2. Slide the bracket down and remove the wall bracket from the Detector as shown.
3. Hold the wall bracket in position and mark the two mounting holes. (For corner mounting drill pilot holes in the wall bracket chamfers as shown).
4. Drill two 4mm diameter holes and insert the plastic wall plugs supplied.
5. Screw the wall bracket to the wall using the screws supplied.
6. Position the Detector on the locating pin and slide down, then fix the Detector to the wall bracket using the holding screw.
Note: The normal detector mounting position is with the battery compartment downwards. However, if the detector is fitted in a room where pets have access, mount the Detector with the battery compartment upwards at a height of 1m from the floor. This will shorten the detection range but allow pets to move about the floor area without activating the Detector.
TESTING THE WIRELESS PASSIVE INFRA RED DETECTOR(S)
ENSURE THAT THE CONTROL UNIT IS STILL IN TEST MODE.
1. Refit the battery in the Detector but do not replace the cover. The Control Unit will emit a two-tone chime and the Detector LED will illuminate for a 60 second warm up period.
2. During the warm up period, leave the protected area and ensure that no movement takes place in this area for at least 60 seconds. Now, by walking into the protected area the Detector LED will flash and the Control Unit will emit a two-tone chime each time the Detector senses movement. This Walktest facility will enable you to check that movement can be detected in all areas of the room.
3. Once the detection range has been verified, refit the battery cover ensuring that the battery lead wires are not trapped in the process.
RE5000S Professional Alarm System 11
PIR - fixings for corner mounting
Page 14
FURTHER TEST:
1. When the battery cover is fitted, once again leave the protected area and ensure that no movement takes place for at least 60 seconds.
2. Walk into the protected area. The Control Unit will emit a two-tone chime.
Note: When the Detector is fully installed, ie. battery cover is refitted, the unit will not detect movement for approximately 60 seconds after each activation. In normal operation, with the battery cover on, the red LED below the detector window will not illuminate upon detection of movement.
Leave the Control Unit in Test Mode and proceed to install your remaining detectors.
FITTING THE STANDARD MAGNETIC CONTACT DETECTOR(S)
One standard Magnetic Contact Detector is supplied in the RE5000S package. However, additional Magnetic Contact Detectors can be purchased separately if required. Any number of Magnetic Contact Detectors can be used with your system providing they are all coded with the system House Code and are within radio range of the Control Unit. Magnetic Contact Detectors can be fitted to protect doors or windows, as required.
To set the House Code and fit the battery, proceed as follows:
ENSURE THAT THE CONTROL UNIT IS STILL IN TEST MODE.
1. Remove the battery cover by sliding it off. DO
NOT USE A SCREW DRIVER.
2. Set the miniature switches 1 to 6 inclusive to the pre-determined House Code’.
3. Determine the Zone on which the Detector is to operate and set miniature switches 7 and 8 to correspond to the required Zone. (Refer to System Zoning page 9).
4. Fit the 12 volt alkaline battery supplied with the negative towards the battery spring.
Note: As soon as the battery is fitted, a two-tone chime will be emitted from the Control Unit siren
and the appropriate Zone LED will flash for 3 seconds. This confirms that the House Code and Zoning is correct.
12 RE5000S Professional Alarm System
Page 15
5. Hold the Contact Detector at the correct position on the door or window, then press and release the anti-tamper switch. Providing the Detector is within radio range of the Control Unit, the two-tone chime will be repeated, for another 3 seconds.
When fitting the detector to a metal door or window, under exceptional circumstances, it may be necessary to space the Magnet/ Detector off the metal surface using a plastic or wooden spacer to achieve the necessary radio range.
6. Remove the battery, then using the double sided tape OR the screws provided, mount the magnet to the door and the Detector to the door frame (or vice-versa, if required). Ensure that the arrow on the Magnet lines up with the line on the Detector and that the gap between the Detector and the Magnet is less than 5mm. When using the screws for mounting the Detector, ensure that the small countersunk screw is used within the battery compartment and that the screw is driven flush with the inside of the casing.
7. Refit the battery and battery cover. (The two­tone chime sound will be repeated at the Control Unit).
8. Test the operation by opening and closing the door/window. The red LED on the Detector will illuminate for approximately 1 second and the Control Unit will emit a two-tone chime each time the detector is openedand closed’.
Note: In addition to the Standard RE5000M Magnetic Detector, the RE5000MHW Detector is available and incorporates facilities to accept hard-wired normally closed and normally open circuit inputs, in addition to the standard Contact Detector operation. Refer to page 27 for further details.
Once you have completed installing all your Detectors, take the Control Unit out of Test mode by pressing and holding the button until the Control Unit emits 2 bleeps and the Arm/Disarm LED’s extinguish.
INSTALLING AND SETTING THE EXTERNAL SOLAR WIRELESS SIREN & STROBE
The Solar Siren & Strobe Unit should be fitted to the outside of the building in a position that is clearly visible and at a height which is relatively inaccessible to an intruder.
The Solar Siren & Strobe incorporates a solar panel which will maintain a charge to the integral 6V 1.2Ahr sealed lead acid rechargeable battery during daylight hours. During the night a negligible amount of energy is released by the rechargeable battery to operate the Siren & Strobe. The Solar Siren & Strobe is self­maintainable during darkness and long winter periods.
LOCATION
To provide the optimum amount on daylight to the Solar Panel, you should ideally mount the Solar Siren & Strobe on a south facing wall. However, an easterly or westerly position will suffice.
Although the Solar Siren & Strobe is designed to work on any aspect wall, for optimum performance you should refrain from siting the unit on a north facing wall where possible. Shadows cast by neighbouring walls, trees and roof overhangs should also be avoided. Where applicable, the Solar Siren & Strobe should be positioned a minimum of twice the width of the eaves overhang below the eaves. Remember that in winter the sun is lower in the sky and you should avoid winter shadows where possible.
RE5000S Professional Alarm System 13
Page 16
The Solar Siren & Strobe contains a sophisticated radio receiver. However, reception of radio signals can be affected by the presence of metallic objects within the vicinity of the Solar Siren & Strobe. It is therefore important to mount the Solar Siren & Strobe a minimum distance of 1m radius away from any external or internal metalwork, ie. external drainpipes, gutters and internal radiators, mirrors etc.
INSTALLATION
Remove the holding screw from the base of the housing and carefully hinge off the front cover. All electronic components are housed within the front cover.
Use the rear backplate as a template to mark the position of the four fixing holes on the external wall. Drill four 5mm diameter holes and insert the plastic wall plugs. Mount the backplate using the four screws provided.
SETTINGS
Undo the 3 screws holding the dip switch cover in place and remove the cover.
SIREN CODE
To enable the Control Unit to operate and control the external Siren & Strobe you need to set a Siren Code in the Solar Siren, which will also be programmed into the Control Unit during programming.
Using a ball point pen set the miniature dip switches 1-8 to a random sequence of ‘ON’s’ and OFF’s’. Make a note of the Siren Code dip switch settings as
this will be needed when programming the Siren Code into the Control Unit.
Note: When the Siren & Strobe is viewed as shown above (solar panel at top) the dip switches are upside down.
ALARM DURATION
This is the maximum length of time that the Solar Siren & Strobe alarm will sound for, following activation. Alarm duration can be set for either 3 or 15 minutes. Set dip switch 9 OFF for 3 minutes or ON for 15 minutes.
Refit the dip switch cover securely.
Note: Following activation into alarm condition the Solar Siren & Strobe will continue to sound until either the Control Unit is Disarmed, or the Control Unit autostop time expires, or until the Siren & Strobe alarm duration time expires; whichever occurs first.
INITIAL POWER-UP
Once you have completed setting your Siren Code and alarm duration time, connect the 9V PP3 initial power-up battery to the clip-on connectors. Connect the rechargeable battery to the charging leads red to red (+) and black to black (-).
14 RE5000S Professional Alarm System
View of inside Solar Siren & Strobe
Page 17
Hinge the front cover locating tabs over the top edge of the backplate, push the base of the Siren cover into place and secure with the lower fixing screw.
IMPORTANT
Ensure that the rear tamper switch is closed when you fit the siren cover to the back-plate (eg. listen for the switch to click). If the switch does not close this will prevent the Solar Siren from operating correctly. If necessary, remove the siren cover again to adjust the screw on the back-plate tamper knob to ensure the switch closes on assembly. The Tamper Switch is inoperative until the Siren has received a start and stop’ signal from the Control Unit.
Note: Once the batteries have been connected, the unit will be operational and it is important that the solar panel receives sufficient light to maintain the battery charge. Also, the unit should not be repeatedly set into alarm as this could rapidly drain the battery.
PROGRAMMABLE FUNCTIONS
The Control Unit incorporates 13 programmable functions which are selected and set via the Control Unit’s keypad. A factory Default setting is incorporated for each programmable function. The system incorporates a non­volatile memory which memorises all the user programmable settings in the event of a total power down.
In the event that you wish to revert the Control Unit to factory Default settings, remove all power (mains and back-up battery), set the memory link to OFF and reapply power. In all other circumstances the memory link should be left ON for full system security.
IMPORTANT
As all programmable functions have a Default setting it is important that each function is selected and set to the user’s requirements on initial installation.
The Control Unit has an initial Default Main User Access Code (the code that operates the system) of
.
To enter the Programming mode and change each programmable function, proceed as follows:-
Enter .
The Full Arm and Part Arm LED’s will illuminate and all the Zone LED’s will flash to indicate the system is in programming mode.
Note: If you make an error when entering your settings, press once to exit the programming function then enter the function number followed by
and re-enter your correct settings.
To exit the Programming mode at any time enter
.
1. HOUSE CODE
The House Code setting enables the Control Unit to receive signals only from its associated detectors.
The House Code is usually self-learned from the Remote Control on initial installation (see page 8) and further programming is therefore not required.
However, if a Remote Control is not available the House Code can be programmed into the Control Unit as follows:-
With the Control Unit in Programming mode Enter
. The Zone LEDs 1-6 will indicate the House Code switch setting selected for each switch 1-6 as follows:-
Switch set + - Zone LED ON Switch set o - Zone LED FLASHING Switch set ‘-’ - Zone LED OFF
Factory Default
All switches set to ‘-’; all LED’s OFF’.
To enter/change the system House Code, refer to the miniature switch 1-6 settings in your Detectors. Make a note of each switch setting and enter the setting of each switch in turn as follows:-
For switch setting +- Press
For switch setting o- Press
For switch setting ‘-’ - Press
For example: For House Code:-
RE5000S Professional Alarm System 15
or Current Main User Access Code
Page 18
The Zone LED’s 1-6 will indicate the new House Code switch setting selected for each switch 1-6 as follows:-
+ - LED ONo - LED FLASHING ‘-’ - LED OFF
Press to memorise the House Code setting and to revert to the Programming mode.
2. INSTANT/DELAY ZONE
Any Zone can be set to give an entry delay when the appropriate Detector(s) are triggered, eg. to allow access to the Control Unit for manual disarming. (The length of the entry delay period is programmed separately - see 7 below).
With the Control Unit in Programming mode Enter
.
The Zone LEDs 1-6 will indicate the status of each Zone:-
Zone LED ON= Delay Zone Zone LED OFF= Instant Zone
Factory default:-
Zones 1 and 2 Entry Delay Zones 1 and 2 LED’s ON’.
To add or delete a Delay Zone, press the number of the Zone to illuminate or extinguish the appropriate Zone LED.
Press to memorise the setting and to revert to the programming mode.
3. EXIT DELAY TIME
When the system is fully armed either at the Control Unit or via a Remote Control, the system will ignore all detectors for a preset Exit Delay time, to allow you to leave the premises.
Note: There is no exit delay when the system is Part Armed.
With the Control Unit in Programming mode Enter
.
A Zone LED will illuminate to indicate the setting:-
Factory default:-
30 seconds - Zone 3 LED ON’.
To change the setting, press the appropriate key to illuminate the associated Zone LED:-
Enter to memorise the setting and to revert to the Programming mode.
4. ALARM AUTOSTOP TIME
This is the length of time that the alarm will sound for when activated. A fully silent alarm option is also available. (If accidentally triggered, the alarm can be stopped at any time using the Remote Control or by disarming at the Control Unit keypad).
Note: The maximum length of time that the external Solar Siren & Strobe will sound for when activated is set within the Solar Siren & Strobe to either 3 or 15 minutes - refer to Installing and Setting the External Solar Siren & Strobe for details.
With the Control Unit in Programming mode Enter
. A Zone LED will illuminate to indicate the setting:- (factory default 60 seconds - Zone 2 LED ON). To change the setting press the appropriate key to illuminate the associated Zone LED:- (Note no LED will be illuminated if a silent alarm is selected).
Press to memorise the setting and to revert to the Programming mode.
5. MAIN USER ACCESS CODE
The Control Unit is supplied with a preset Main User Access Code of . This code
allows general operation (Arming/Disarming etc) AND programming/re-programming of the system at the Control Unit. However, for security reasons, it is essential that you change the Main User Access Code to another four-digit number which only you and other users of the system will know and use (usually a number with a personal significance is easier to remember).
Note: a separate Second User Access Code is also available which will allow only Arming/Disarming at the Control Unit. You may therefore wish to allow
16 RE5000S Professional Alarm System
Page 19
general use of the system to be via this second code (eg. for children, guests, cleaners etc) and to retain the Main User Access Code for your personal use in re-programming the system. To change the Main User Access Code:-
With the Control Unit in programming mode Enter
. No Zone LED’s will be illuminated.
Enter your new Access Code.
The Zone LED’s 1-4 will illuminate as each digit is entered.
Press to memorise the setting and to revert to Programming mode.
6. DOOR-CHIME ZONE
It is possible to programme the Control Unit to emit a two-tone door-chime tone when a Magnetic Detector is opened, with the system in Disarmed mode. This facility may therefore be used to monitor Entry/Exit doors when the system is not armed. The facility is Zonal, ie: if there are 2 Magnetic Detectors on one Zone, both detectors will operate the chime tone. It is not possible to use PIR Detectors or the Zone 6 Hard Wired input to generate the chime tone.
To set the Zone(s) on which the chime will operate make a note of the Zone of the appropriate magnetic detector(s) and proceed as follows:-
With the Control Unit in Programming mode Enter
. The Zone LED’s 1-6 will indicate the
status of each Zone:-
Zone LED ON= Door-Chime ON Zone Zone LED OFF= Door-Chime OFF Zone
Factory default:-
Zone 1 Door-Chime ON Zone 1 LED ON’.
To add or delete a door-chime Zone press the number of the Zone to illuminate or extinguish the appropriate Zone LED.
Press to memorise the setting and to revert to the Programming mode.
7. ENTRY DELAY TIME
When entering an entry delay Zone with the system Armed or Part Armed, the system will be inactive for a preset Entry Delay time to allow you time to disarm the system by entering your access code at the Control Unit, or using the Remote Control.
During the entry delay period, the Control Unit sounder will emit an intermittent bleep tone and the appropriate Zone LED(s) will flash to indicate that the system has been triggered by a delay Zone detector.
With the Control Unit in Programming mode, Enter
.
A Zone LED will illuminate to indicate the setting
Factory default:-
30 seconds - Zone 3 LED ON’.
To change the setting press the appropriate key to illuminate the associated Zone LED:-
Press to memorise the setting and to revert to the Programming mode.
8. PART ARM ZONE OMIT
Any of the Zones 1-6 can be omitted (ie inactive) when the system is Part Armed. This will enable you to arm only the selected (active) Zones when you Part Arm the system.
With the Control Unit in Programming mode Enter
the Zone LEDs 1-6 will illuminate to indicate the Zones which are omitted (inactive) when the system is Part Armed:-
Factory default:-
Zone 1 omitted - Zone 1 LED ON’.
To add or delete an omitted Zone, press the number of the Zone to illuminate or extinguish the appropriate Zone LED.
Press to memorise the setting and to revert to the Programming mode.
RE5000S Professional Alarm System 17
Page 20
9. EXIT DELAY TONE
During the Exit delay period the Control Unit may be set to either remain silent or to give an intermittent bleep tone.
With the Control Unit in Programming mode Enter
.
Zone 1 LED will indicate the setting:-
LED ON - intermittent bleep delay tone selected LED OFF- silent exit delay selected.
Factory default:-
intermittent bleep tone ON - Zone 1 LED ON’.
Press to select silent exit delay
Press to select intermittent bleep delay tone.
Press to memorise the setting and revert to the Programming mode.
10. QUICK ARM/PART ARM
Quick Arm allows the Control Unit to be Armed or Part Armed by simply pressing and holding the Arm or Part Arm key for 5 seconds removing the need to enter an access code first.
With the Control Unit in Programming mode Enter
.
Zone 1 LED will indicate the setting:-
LED OFF - Quick Arm OFF LED ON - Quick Arm ON
Factory default:-
Quick Arm OFF - Zone 1 LED OFF
Press to select Quick ARM ON
Press to select Quick ARM OFF
Press to memorise the setting and to revert to the Programming mode.
11. JAMMING DETECTION SYSTEM
In order to detect any attempts to jam the radio channel used with your alarm system a sophisticated Jamming Detection system is incorporated into the Control Unit. If this feature is selected and the radio channel is
continuously jammed for more than 30 seconds the Control Unit sounder will emit a Pre Alarm series of rapid bleeps for 5 seconds. If the system is Armed and the Jamming continues for a further 10 seconds or more; or a total of 30 seconds of Jamming is detected within a 5 minute period, a full alarm will occur indicated by the Internal and External alarms sounding, but no Zone LED’s ON.
The jamming detection circuit is designed to permanently scan for illegal jamming signals. However, it is possible that it may detect other local radio interference operating legally or illegally on the same frequency. If it is planned to operate the jamming detection feature we recommend that the system is monitored for false jamming alarms for at least 2 weeks prior to leaving the Jamming Detect function on permanently.
With the Control Unit in Programming mode Enter
.
Zone 1 LED will indicate the setting:-
LED OFF- Jamming Detection System OFF LED ON - Jamming Detection System ON
Factory default:-
Jamming Detection OFF, Zone 1 LED OFF’.
Press to select Jamming Detection ON
Press to select Jamming Detection OFF
Press to memorise the setting and to revert to the Programming mode.
12. SIREN CODE (AND OPTIONAL MEDICAL
ALERT PENDANT CODE)
A small radio transmitter is incorporated within the RE5000S Control Unit to operate and control the external Solar Siren & Strobe. To enable the Control Unit to communicate with the external Solar Siren & Strobe the Siren Code set in the external Siren (see page 14) needs to be programmed into the Control Unit.
The (optional) Medical Alert Pendant(s) to be used with the system must also be set to the Siren Code in order that the pendant radio signal is sent to both the Control Unit and the external Siren & Strobe,
18 RE5000S Professional Alarm System
Page 21
thereby ensuring that the signal is correctly received. For full details of the setting and operation of the optional Medical Alert Pendant refer to the instructions supplied with the unit.
To programme the Siren Code into the Control Unit, with the Control Unit in Programming mode Enter
. The Zone LEDs 1-8 will indicate the Siren Code switch setting selected for each 2 position switch as follows:-
Switch set ON- Zone LED ON Switch set OFF- Zone LED OFF
Factory default:-
All switches set to ON - all LED’s ON’.
To enter/change the Siren Code, refer to the miniature switch 1-8 settings previously set in your Solar Siren & Strobe (and /or Medical Alert Pendant(s) and enter the setting of each switch in turn as follows:-
For switch set ON press
For switch set OFF press
For example; for Siren Code:-
The Zone LED’s 1-8 will indicate the new Siren Code switch setting selected for each switch 1-8 as follows:-
switch ON- LED ON switch OFF - LED OFF
Press to memorise the Siren Code setting and to revert to the programming mode.
13. SECOND USER ACCESS CODE
The Control Unit is supplied with a Preset Second User Access Code of . This code allows Arming/Part Arming and Disarming only at the Control Unit and may therefore be entrusted to children, guests or neighbours; or alternatively this code could be
used for day to day operation, with the Main User Access Code reserved for re-programming only. However you plan to use the system, for security reasons it is essential that you change the Second User Access Code to another four digit number which only you and other users of the system will know and use. (Again, a number with a personal significance will be easier to remember).
With the Control Unit in Programming mode Enter
.
No Zone LED’s will be illuminated.
Enter your new Second User Access Code.
The Zone LEDs 1-4 will illuminate as each digit is entered.
Press to memorise the setting and to revert to the Programming mode.
Programming of your Control Unit is now complete. Exit Programming mode by pressing
again.
EXTERNAL CONNECTIONS
The Control Unit incorporates a terminal block and Communication Interface Cable to facilitate external connection of a Hard-wired Siren, Telephone Dialler/Communicator, or a Hard-wired Zone 6 Trigger input. Before making any connections, ensure that the memory link is in the ON position and then remove all power (mains and back up battery).
Note: Any unused cores of the interface cable must be cut back; insulated or made safe to prevent short circuits.
After making your external connections reconnect the power supply and back-up battery and refit the Control Unit to it’s wall fixing bracket.
Wiring interconnections should comply with the appropriate requirements of BS4737 part 1 in respect of cable type and installation methods.
Full details of the Control Unit terminal block connections and Communicator Interface Cable connection are shown overleaf:-
RE5000S Professional Alarm System 19
Page 22
OPERATING INSTRUCTIONS
IMPORTANT
The System cannot be Armed, Part Armed or put into Test mode if any previous low battery or alarm indication has not been cleared, (indicated by any Zone LED’s flashing) or if a Magnetic Detector is open (indicated by the appropriate Zone LED’s illuminating steadily). When an attempt is made to Arm the system under any of these conditions the Control Unit will emit 3 rapid bleeps.
For a low battery condition, replace the detector battery prior to clearing the indication. To clear a low battery or alarm indication Enter the Main User or Second User Access Code, followed by . A low battery or alarm indication cannot be cleared using the Remote Control Unit.
FULLY ARMING THE SYSTEM
When leaving the premises, the system must be fully armed. However, before doing so, check that all windows are closed and locked, all protected doors are closed and Passive Infra Red Detectors are not obstructed. Ensure that pets are restricted to areas not protected by Passive Infra Red Detectors or that suitable precautions have been taken to allow for pets.
The system may be fully armed either at the Control Unit or using a Remote Control. If Arming at the Control Unit, you must first Enter your 4 digit Access Code (Main User or Second User Code) then press . Alternatively, if Quick Arm has been programmed, press and hold the button for 5 seconds. If arming using a Remote Control Unit simply press the green Full Arm button. If the System exit tone has been set for ON the Control Unit sounder will emit an intermittent bleep tone and the Full Arm LED will flash for the duration of the preset exit time, Arming automatically when the exit time expires.
All occupants must leave the premises before the exit time has expired. If for any reason you are unable to leave the premises before the exit time has expired, you will need to disarm the system, then Re-Arm. Failure to do so will cause a full alarm if any protected door is opened or movement is detected by a Passive Infra Red Detector.
20 RE5000S Professional Alarm System
Control Unit Terminal Block Connections
Communicator Interface Cable Connection
Page 23
When fully armed the Full Arm LED will be illuminated steadily.
PART ARMING THE SYSTEM
If you are remaining in the premises, you may arm all the Zones which have not been omitted, by selecting Part Arm. This will permit free access to the omitted Zone areas.
The system may be set on Part Arm either at the Control Unit or using a Remote Control Unit. If setting on Part Arm at the Control Unit, you must first Enter your 4 digit access code (Main User or Second User Code) then press . Alternatively, if Quick Arm has been programmed, press and hold the button for 5 seconds. If arming from the Remote Control Unit, simply press the orange Part Arm button.
The LEDs associated with the Part Arm Zone(s) will illuminate for 5 seconds. (Any Zone LED not lit indicates that that Zone has been omitted and will not be active in Part Arm mode). After the 5 seconds the LEDs will extinguish and the Part Arm LED will illuminate steadily to indicate that the system is Part Armed.
You must leave all protected Zones before expiry of the 5 second arming time. If for any reason you are unable to leave the protected areas within the arming time, you will need to disarm the system then re-arm. Failure to do so will cause a full alarm if any protected door is opened or movement is detected by a Passive Infra Red Detector set to operate in Part Arm.
When part armed, the Part Arm LED will be illuminated steadily.
DISARMING THE SYSTEM
Upon entering an Entry Delay Zone, the Control Unit sounder will emit an intermittent bleep tone and the appropriate Zone LED(s) will flash for the Preset Entry Delay period.
You may disarm the system by pressing the blue disarm button on the Remote Control Unit or by proceeding immediately to the Control Unit and entering your 4 digit Access Code (Main User or Second User Code) followed by .
Note: If the system is not disarmed during the Entry Delay Period a full alarm will occur. When using the
Remote Control Unit, you may be able to disarm the system from outside the premises before entering. Establish the operational range of the Remote Control Unit before using this method.
DISARMING AFTER AN INTRUSION
A full alarm condition (Control Unit Siren and external Siren and Strobe operating) will be initiated following an intrusion. This condition will continue until expiry of the preset ‘Auto-Stop’ and/or Alarm Duration times, whereby the Control Unit Siren and external Siren and Strobe respectively will cease. The Appropriate Zone LED(s) will flash to indicate the Zone(s) which triggered the alarm. The Control Unit will now immediately re­arm itself. In the event of a further intrusion the Control Unit will once again initiate a full alarm condition and the above process is repeated.
If a full alarm condition is initiated accidentally the alarm can be cancelled immediately by pressing the blue disarm button on your Remote Control or by entering your 4 digit Access Code (Main User or Second User Code) followed by at the Control Unit.
IMPORTANT
Following disarming of the system after an Alarm activation, make a careful note of the zone LED indications to assist with tracing the cause of the alarm. The Control Unit MUST then be reset by entering your 4 digit Access Code (Main User or Second User Code) followed by .
The system CANNOT be rearmed until the Control Unit has been reset.
PERSONAL ATTACK, MEDICAL AND FIRE ALARM
A full alarm condition can be initiated by the user at any time (system armed or disarmed) in the event of threat or danger as follows:
PERSONAL ATTACK:- Press the red button on your Remote Control.
The Control Unit will initiate a full alarm and Zone 8 LED will flash.
RE5000S Professional Alarm System 21
Page 24
FIRE ALARM:- Press and hold the button on the Control Unit for 3 seconds. The Control Unit will initiate a full alarm. A special Fire Alarm tone will sound at the Control Unit and Zone 7 LED will flash. A Fire Alarm can also be initiated from an optional Smoke Detector ref RE5000SD.
MEDICAL ALERT:- Press and hold the button on the Control Unit for 3 seconds. The Control Unit will initiate a full alarm. A special Medical Alert tone will be sounded at the Control Unit and Zone 8 LED will flash. A Medical Alert can also be initiated using the optional Medical Alert Pendant Ref: RE5000MP.
When connected to a Security Dialler or Communicator, separate alarm outputs are available to Communicate Intruder, Personal Attack/Medical Alert or Fire Alarm situations.
To cancel any of the above alarms, Enter your 4 digit Main User or Second User Access Code followed by
.
Note: An Alarm Condition can also be stopped by pressing the blue Disarm button on your Remote Control. However, the Control Unit must still be reset by entering the Main User or Second User Access Code followed by before the Control Unit can be armed again.
BATTERY MONITORING
The System will continuously monitor the battery condition of all PIR and Magnetic Contact Detectors, Medical Pendants and Smoke Detectors. If the voltage level of any battery falls unacceptably low, a radio signal will automatically be transmitted to the Control Unit and the low battery and appropriate Zone LED’s will flash, and the control unit will emit two bleeps every minute.
To identify a PIR Detector with a low battery, leave each protected area for at least 60 seconds. If, when you re-enter the area, the PIR LED flashes on detection of movement, this indicates a low battery. The batteries in the Magnetic Contact Detectors can be checked by operating the detector (opening and closing the protected door/window) and observing the LED on the Detector. If the LED is dim or does not illuminate, the battery needs to be replaced. In the event of a low
battery condition clear the low battery indication, then set the Control Unit to Test mode (see page 9). Replace the battery as required and ensure that the Test chime is emitted when the battery is inserted. Remember to take the Control Unit out of Test mode when you have finished.
Note: When replacing PIR Detector batteries, fit PP3 alkaline type. Rechargeable batteries should NOT be fitted. For areas subject to seasonal low ambient temperatures (eg. garages, sheds etc) we recommend the use of PP3 Lithium batteries (order code RE3005B) in PIR Detectors.
TESTING THE SYSTEM
You may test your system at any time, however, it is recommended that the system is tested at regular intervals not exceeding three months. You cannot readily test the system using the Remote Control Unit. You must set the Control Unit into Test mode by pressing and holding the button on the Control Unit until the Control Unit emits 2 bleeps and the Full Arm and Part Arm LED’s flash.
Before testing areas protected by Passive Infra Red Detectors, ensure that the area is completely clear of occupants, including pets. Wait 60 seconds before testing areas protected by Passive Infra Red Detectors and also allow 60 seconds between tests.
When a Passive Infra Red Detector is activated, or a protected door or window is opened or closed the Control Unit will emit 2 x two-tone chimes and the associated Zone LED will flash for approximately 3 seconds.
On completion of testing, return to the normal disarmed mode of operation by pressing and holding the button until the Control Unit emits 2 bleeps and the Full Arm/Part Arm LED’s extinguish.
To test the external Solar Siren & Strobe ensure that the Control Unit is out of Test mode, then press the red button on the Remote Control Unit to activate the Control Unit Siren and External Siren & Strobe. Allow the alarm to sound for at least 15 seconds then press the blue disarm button on the Remote Control to de-activate. Clear the Control Unit Alarm Activated light by entering your Main User or
22 RE5000S Professional Alarm System
Page 25
Second User Access code followed by at the Control Unit.
MAINTENANCE
Your RE5000S Intruder Alarm System requires very little maintenance. However, a few simple tasks will ensure its continued reliability and operation.
CONTROL UNIT
The Control Unit requires no maintenance. If cleaning is required, wipe the outside of the casing with a soft damp cloth. Do not use aerosols or sprays or proprietary cleaners. Do not attempt to clean inside the unit or allow water to enter the unit.
SOLAR SIREN & STROBE
1. At least once a year, preferably in the Autumn, the
solar panel on the top of the siren housing should be cleaned using a soft, damp cloth. This operation will ensure that the solar panel receives all the available light. The cleaning operation can be combined with the general cleaning of the outside of the house, windows etc. to reduce maintenance time.
2. The Solar Siren & Strobe incorporates tamper
protection for system security. Should you, for any reason, have to completely power down the Solar Siren & Strobe (eg. to move the system to a new premises) remove the holding screw at the base of the Siren and hinge off the front cover.
WARNING - THE SIREN WILL SOUND
Disconnect the rechargeable battery and initial power up battery and ensure that the solar panel is covered with a light proof material to prevent it being energised.
3. The Solar Siren & Strobe should not be left for
long periods with the batteries connected, unless the unit is able to receive sufficient light to maintain the battery charging circuit. Failure to maintain charge to the unit will result in the rechargeable battery running unacceptably low. Should this occur, the unit must be recharged from a 240/7.5V dc mains adaptor (Response order code S100TR). When re-powering the Solar
Siren & Strobe fit a new 9V PP3 leak proof alkaline Initial Power-Up battery to ensure that the unit receives sufficient power until the solar panel can recharge the main battery completely.
RECHARGEABLE BATTERIES
The rechargeable batteries in the Control Unit and Solar Siren & Strobe have a typical life of 4 years and need no maintenance during this period providing the batteries are kept charged. The batteries will be damaged if stored in a discharged state.
The rechargeable batteries should be taken to a suitable Recycling Centre at the end of their useful life. DO NOT dispose of with your normal household waste. The rechargeable batteries contain Sulphuric Acid - DO NOT attempt to open the casing.
DETECTORS & REMOTE CONTROL
The Detectors and Remote Control(s) require no maintenance. Simply replace the batteries once a year or when a low battery is indicated. The specifications of the Detector and Remote Control batteries are as follows:
PIR Detectors - 9V PP3 Alkaline or Lithium
Standard Magnetic Contact Detectors - 12V 23A Alkaline
Remote Controls - 12V 23A Alkaline
Please recycle used batteries were Local Authority facilities exist. Keep batteries away from children and do not dispose of in fire.
RE5000S Professional Alarm System 23
Page 26
24 RE5000S Professional Alarm System
TROUBLE SHOOTING
Control Unit will not arm. Control Unit emits 3 bleeps when trying to arm.
1. Magnetic Contact Detector Open - Check Zone LED illuminated and close detector(s) on that Zone. If Detector cannot be closed, enter, then exit Programming mode to clear the indication.
2. Low battery in a Detector. Check Zone indicated, change battery and clear indication at Control Unit.
3. Alarm/low battery indicator not cleared. Enter Main User or Second User Access Code followed by .
Detection Zone has been triggered but no alarm is sounding
1. Entry delay zone triggered - alarm will sound when delay time has expired.
2. Zone omitted when part armed.
3. Silent alarm option selected.
Control Unit ‘Low Battery’ light flashing, Zone LED(s) flashing and control unit bleeping every 60 seconds
1. Check all PIR Detector(s) on the Zone indicated for low battery, indicated by detector LED flashing when movement is detected - change battery(s) as required.
2. Check all Magnetic Detectors on the Zone indicated for low battery indicated by detector LED not illuminating when detector is opened/closed ­change battery(s) as required.
3. Check the battery in all RE5000 Smoke Detectors ­a low battery will also cause the Smoke Detector to bleep every minute - change battery as required.
Full Alarm Occurs when alarm has not been activated by an intruder
1. Ensure mains adaptor is plugged in/connected and switched on.
2. Ensure that the Control Unit is securely fitted to the wall and that the rear battery compartment cover is closed.
3. Check that Personal Attack Button, Medical Alert Pendant or Smoke Detectors have not been operated.
4. Check that battery covers on all detectors are fitted securely.
5. Check for Jamming Detection Alarm operation.
Control Unit not working. Mains light is off.
1. Check that mains adaptor is plugged in/connected and switched on.
Control Unit will not function (Sirens are sounding)
1. Disconnect power (including Control Unit back-up battery), for 10 seconds, then re-connect mains power followed by back up battery. (Remember, all programmed functions will be retained if the Memory Link is in the ON position).
Control Unit not accepting access code(s).
1. Pausing too long between pressing keys. Do not pause for more than 5 secs between keys.
2. Incorrect code entered. Allow 5 seconds to elapse before re-entering correct code.
3. Unit has reset to factory default codes/programme. Fit Memory Link in ON position and re-programme all programmable features.
Control Unit emits two-tone chime when detectors are triggered.
1. Door-Chime set to operate on Magnetic Detector Zone(s) - Re-programme Door-Chime Zone(s).
2. Control Unit in Test mode - Reset to normal, disarmed mode.
Control Unit not responding to detectors.
1. Ensure detectors are within radio range of Control Unit. If not, move detector closer.
2. Ensure that the House Code on the Detector is the same as that set in the Control Unit.
3. Replace detector battery.
Solar Siren and Strobe sounding but no alarm at Control Unit.
1. Siren Anti-tamper activated. Check security of Siren/Strobe fixing to wall and that Siren anti-tamper switch is fully depressed.
2. Siren & Strobe has not received Stop signal. Press Disarm on Remote Control to make the Control Unit re-transmit the Stop signal.
Symptom /Recommendation Symptom /Recommendation
Page 27
RE5000S Professional Alarm System 25
Continued
TROUBLE SHOOTING
Solar Siren and Strobe does not operate when system activated.
1. Incorrect Siren Code dip switch settings in Solar Siren and Strobe or Siren code incorrectly programmed into Control Unit.
2. Siren duration time timed-out before Control Unit Autostop time.
3. Disconnect rechargeable and power-up batteries. Cover solar panel and leave unit for 3-5 minutes. Re-connect the batteries and then remove the Solar panel cover.
4. Rechargeable battery low. Power down, fit new initial power up battery and re-power up.
No response from Passive Infra Red Detector
1. Check battery connections are good.
2. Ensure that House Code is same as that set in Control Unit.
Passive Infra Red Detector not detecting a persons movement
1. Allow up to one minute for the Detector to settle down and retry.
2. Ensure that Detector is mounted the correct way up (battery compartment at the bottom except for Pet Alley).
3. Ensure that the Detector is mounted at the correct height 1.8 - 2m from floor, except Pet Alley).
4. Check that the Detector is correctly set-up. (See Setting Up Infra Red Detectors).
5. If Detector is mounted upside down for Pet Alley’, check that the mounting height is not greater than 1m from the floor, depending on the size of pet.
Passive Infra Red Detector flashes when you walk past it
1. Low battery - replace alkaline battery.
Passive Infra Red Detector false alarming
1. Ensure that the Detector is not pointing at a source of heat or a moving object.
2. Ensure that the Detector is not mounted above a radiator or heater.
3. Ensure that the Detector is not facing a window or in direct sunlight.
Remote Control Unit not working
1. Ensure House Code is the same as that set in the Control Unit.
Red light on Remote Control Unit not illuminating
1. Ensure battery is connected with correct polarity.
2. Replace battery with alkaline type.
3. Ensure battery connections are good.
Magnetic Contact Detector not working
1. Ensure House Code is the same as that set in the Control Unit.
Red light on Magnetic Contact Detector not illuminating or is dim when door or window is opened
1. Ensure battery is connected with correct polarity.
2. Replace battery with alkaline type.
3. Ensure battery connections are good.
Magnetic Contact Detector false alarming
1. Ensure that gap between Magnet and Detector is less than 5mm.
2. Tamper switch below battery cover not depressed. Check mounting screw below battery is fitted flush. Check battery cover lugs are not broken.
Symptom /Recommendation Symptom /Recommendation
IF YOU HAVE ANY PROBLEMS RING THE
HELPLINE: 09062 777200
(Lines open 9.00am to 6.00pm, Monday to Friday. Calls charged at 25p per minute)
Page 28
26 RE5000S Professional Alarm System
RE5000S ALARM RECORD
Complete the following information during installation for future reference.
Zone Detector Type(s) Location(s)
Settings
Instant Part Arm Door­/Delay /Omit Chime
1 2 3 4 5 6 7
Smoke Detector(s)
8
Medical Pendant(s)
In order to comply with the Code of Practice on Noise from Intruder Alarms 1981 you should carry out the following procedures within 48 hours of the Intruder Alarm installation.
1. Notify your local police station in writing that an Intruder Alarm System has been installed, giving details of at least two persons who know the Access Code(s) or are in possession of a Remote Control Unit.
2. Ensure that all users are aware of the operating procedures.
3. Inform the local Environmental Health Authority of the installation and which police station has been informed.
4. Immediately inform your local police station if there is a change to the persons who know your Access Code(s) or have a Remote Control Unit.
IMPORTANT NOTICE FOLLOWING ALARM INSTALLATION
Use the above diagrams to record your House Code and ‘Siren Code, eg.,
Purchase date Installation date
Control Unit serial number
This information is highly confidential and should be kept in a very safe location.
Page 29
RE5000S Professional Alarm System 27
EXTENDING YOUR RE5000S PROFESSIONAL WIRELESS ALARM SYSTEM
You may add additional Remote Controls, Standard Wireless Magnetic Contact Detectors and Wireless PIR Detectors etc, as required, to give additional protection where needed. The following accessories are also available to extend and enhance your system:-
ADDITIONAL SOLAR WIRELESS SIREN & STROBE
RE5000SS
Additional Solar Wireless Siren & Strobes can be added to your RE5000S Professional Solar Wireless Alarm System to give a higher level of security. For example you could have a Siren & Strobe fitted to the front and rear of your premises.
A security coded signal sent from the Control Unit would be received by both Siren & Strobes simultaneously.
DUMMY SIREN & STROBE
RE5000D
Alternatively the Siren & Strobe is available as a Dummy design and acts as an excellent visual deterrent.
MAGNETIC CONTACT DETECTOR WITH HARD-WIRED INPUTS
RE5000MHW
In addition to the features and benefits of the standard RE5000M Magnetic Detector, this unit also incorporates facilities for hard-wiring in optional normally open and normally closed circuits, eg. additional Magnetic Contacts, Panic Buttons, Pressure Mats etc.
MEDICAL ALERT PENDANT
RE5000MP
This small, lightweight transmitter unit is easily operated in the event of a medical emergency and transmits a Medical Alert signal to the Control Unit to trigger a Medical Alert on a dedicated Zone.
The Unit incorporates a neck-chain aerial and comes complete with bracket for wall mounted operation if required.
Page 30
WIRELESS SMOKE DETECTOR
RE5000SD
In the event of fire the battery operated Wireless Smoke Detector will send a security coded signal to your Control Unit which will activate your Alarm System. The Smoke Detector also has its own siren and when used with the RE5000S Wireless Alarm provides an exceptionally high level of safety to your home.
There is no limit to the number of Wireless Smoke Detectors you can use with your system and when used with the RE5000S Control Unit a separate Zone/Alarm output is activated and a Fire Alarm siren tone is sounded to identify that a fire signal has been received by the Control Unit.
SECURITY DIALLER
RE5000AD
Connects directly to your standard telephone line to automatically dial for help upon alarm activation.
Incorporates facilities for storing up to 4 x 24 digit telephone numbers and 3 separate trigger inputs/messages for intruder, fire and medical alert.
Ideal for informing neighbours or relatives of an alarm condition.
Note: Cannot be used for 999 or Police Link.
RESEARCH & DEVELOPMENT
Our R & D Department is constantly developing new products. We practice a policy of continued
improvement and reserve the right to change specifications without prior notice.
28 RE5000S Professional Alarm System
EXTENDING YOUR RE5000S PROFESSIONAL WIRELESS ALARM SYSTEM
Continued.
A
B
C
D
1
4
7
ENT
5
8
0
2
6
9
ESC
3
Page 31
Response RE5000S Professional Alarm System
If you have a problem with your Alarm, or if
you have an item that you feel requires
replacement for whatever reason, please do
not hesitate to call our Helpline on:
09062 777200
(Lines open 9.00am to 6.00pm, Monday to Friday. Calls charged at 25p per minute)
We can solve most problems quickly over the phone.
YOUR GUARANTEE
This product (excluding Alkaline batteries) is guaranteed for one year from the date of purchase against faulty materials or workmanship. We will repair or replace any faulty product. No liability can be accepted for any problems caused by fair wear and tear, buyers negligence, improper fitting or use, local radio interference, wilful or accidental damage, or any consequential loss or damage howsoever caused. This guarantee does
not affect your statutory rights.
If an item develops a fault, the product must be returned to the address
below in adequate
packaging
with:
1. A copy of your original invoice/receipt
2. A full description of the fault
3. All relevant batteries
PLEASE NOTE
If returning a Control Unit, make sure that the rechargeable battery is
disconnected and removed. If returning an External Solar Siren & Strobe,
make sure that the rechargeable battery and initial power up battery
are disconnected and secure and that the unit is packaged to
prevent damage in transit.
For security, Recorded or Registered Post is recommended.
Service Department, Response Electronics Plc
Longmead Business Centre, Blenheim Road
Epsom, Surrey KT19 9QQ
Page 32
Response RE5000S Professional Alarm System
PURCHASED FROM
MODEL
WHERE DID YOU FIRST HEAR OF THIS PRODUCT?
DATE OF PURCHASE
20
Date Month Year
ORDERED BY
Postcode Telephone
OWNERS NAME
(if purchased for business use, please give company name)
ADDRESS
Postcode
Telephone E-mail
TYPE OF USE
(please tick)
Domestic
Business
What further comments would you wish to make about your Wireless Intruder Alarm System?
YOUR PEACE OF MIND AGAINST EXPENSIVE REPAIRS
- FOR AN ADDITIONAL FOUR YEARS
No matter how good the quality of your Wireless Alarm System, we are sure you will agree that as it gets older
the chances of it breaking down must inevitably increase.
This is where the EXTENDED WARRANTY can help.
For just £79.95 you can have peace of mind from expensive repairs to your system AND ANY ACCESSORIES
YOU HAVE PURCHASED for an additional four years. Thats the equivalent of just 39p a week!
This offer is not available after your normal guarantee has expired, so please complete and return the order form
TODAY. If your product cannot be repaired then the EXTENDED WARRANTY will cover your product with a
brand new replacement FREE OF CHARGE.
All we require is your date of purchase, your name and current address along with payment. Full written
confirmation of acceptance will be forwarded to you by return of post.
IMPORTANT - Return your Extended Warranty Application Form (below) with your
Guarantee Registration to give a total of five years cover!
IMPORTANT – PLEASE REGISTER YOUR GUARANTEE
WITHIN 14 DAYS OF PURCHASE
DELIVERY ADDRESS (if different)
Postcode Telephone
RE5000S
Response Electronics Plc are a leading supplier of home security and electrical products, including intruder alarms and residential CCTV. Please tick any of the following boxes for information you wish to be sent to you:
Solar Wirefree Intruder Alarms
Other Wireless Intruder Alarm Systems
Personal Attack Alarm
CCTV Home Surveillance Systems
Wired Alarm Systems
Home Automation
Guarantee Registration
To register your purchase and help us provide you with the latest information on system accessories and give the fastest possible service in the event of a problem, please take a minute to complete this registration and post it back to us,
in
the Freepost envelope provided.
Dont forget to keep your receipt safely, as you will need it in the event of a claim.
PLEASE USE BLOCK CAPITALS THROUGHOUT
METHOD OF PAYMENT (please tick)
1. Please debit my credit card ■Mastercard ■Visa ■Delta ■Switch ■Solo - the sum of £79.95.
//
2. I enclose my ■cheque ■postal order for
£79.95 made payable to Response Electronics Plc.
Signature Date
Issue Number
(Switch Only)
Expiry DateStart Date
Page 33
TO WIN A FANTASTIC PRIZE
FOR
FREE ENTRY
INTO
OUR
PRIZE DRAW
FOR
FREE ENTRY
INTO
OUR
PRIZE DRAW
TO WIN A FANTASTIC PRIZE
(See the enclosed Prize Draw Offer Sheet for the
current offer, plus Prize Draw Rules)
Either fill in your details overleaf and return the
GUARANTEE REGISTRATION FORM WITH the
ENCLOSED PRIZE DRAW OFFER SHEET
within 14 days to:
Response Electronics Plc Guarantee Registration Department FREEPOST KT4437 Epsom, Surrey KT19 9BR
ALTERNATIVELY
you can register your Guarantee online via
www.responseplc.com
where you will automatically be entered
into our current Prize Draw
Page 34
Solar Wireless Siren
& Strobe
Order Code: RE5000SS
Case material 3mm ABS
Dual front and rear Anti-Tamper
Internal Receiver and Aerial UK frequency 418MHz
Sealed Lead Acid Battery 6V 1.2AHr
Solar Panel 7.5V - Charge Rate typically 60mA
Time out - Switchable 3 or 15 mins
Xenon Strobe current 125mA (1watt)
Quiescent current 850µA (typical)
Piezo Sounder 105dB current 150mA
Operation time in complete darkness - 40 days
Anti-Foam
Also available as Visual Deterrent Dummy Unit (order code RE5000D)
Control Unit
6 Fully Programmable Zones
Separate Medical Alert & Fire Alarm Zones
Integral 105db Siren
3 Siren Tones - Intruder, Fire, Medical Alert
Zones programmable for:-
Entry delay Part Arm/Zone omit Door-Chime
Entry delay - variable 10-180 secs
Exit delay variable - 10-180 secs
Alarm duration - variable 30 secs to 15 minutes
Silent Alarm facility
Self learn House Code
4 digit User Access Code
4 digit Guest Code
Quick Arm facility
Test mode facility
Combined fixing cover/ cover Anti-Tamper
N.O./N.C. latching change-over contacts
Sophisticated Jamming Detection Facility
Individual Zone Alarm activation LED’s
Zone indication for Detector low battery
Communicator/Dialler interface wiring
Integral Solar Siren & Strobe transmitter
Non volatile memory
Integral Back-up battery
Hard-wired Zone input facility
Hard-wired Siren connection facility
12 Volt DC Axillary output facilities
Wireless Magnetic
Contact Detector
Order Code: RE5000M
LED Battery confirmation
Anti-Tamper
Operating gap up to 10mm
Door or window mounting
Low Battery Indicator
Alkaline Battery supplied
Wireless Passive
Infra Red Detector
Order Code: RE5000P
Detection range:- up to 5m at 180° and 14m at 110°
Walk test facility
RF Immunity
Temperature Compensation
Low Battery Indication
Anti-Tamper
Wall Bracket corner or flat surface mount
Alkaline Battery supplied
Remote Control
Order Code: RE5000R
Disarm
Part Arm
Full Arm
Personal Attack
Alkaline Battery supplied
Key Ring fixing
Security Dialler
Order Code: RE5000AD
Input Voltage 11.5-14V dc
Current consumption 35mA standby 70mA active
Trigger inputs A, B, C, D +ve or -ve applied, max 24V
Phrase length (A, B, C, D, O) max 40 seconds
REN value - 0
Exchange compatibility - LD and DTMF (auto switching)
Non Volatile Memory
4 x 24 digit phone number storage
BABT/RTTE Approved
Magnetic Contact
Detector
(with hard-wired inputs)
Order Code: RE5000MHW
Door or window mounting
Anti-Tamper
Operating gap up to 10mm
Low Battery Indication
N.O. and N.C. Hard-wired input options
LED Battery confirmation
Alkaline battery supplied
Wireless Medical
Pendant
Order Code: RE5000MP
Hand held; neck pendant or wall mounting options
Wall bracket supplied
Integral aerial
Latching operation
Reset facility
Batteries supplied
Wireless Smoke
Detector
Order Code: RE5000SD
Optical Sensor element
Security coded signal to Control Unit
Battery test button
Low Battery audio confirmation
Integral Siren
Requires alkaline battery
RE5000S PROFESSIONAL SOLAR WIRELESS
ALARM SYSTEM - SPECIFICATION
A
B
C
D
1
4
7
ENT
5
8
0
2
6
9
ESC
3
HELPLINE:
09062 777200
(Lines open 9.00am to 6.00pm, Monday to
Friday. Calls charged at 25p per minute)
If you need
help, just dial
the Helpline
for expert
technical
support
Response Electronics Plc
are Quality Assurance
Registered to
BS EN ISO9002 1994,
by SGS Yarsley ICS.
Response Electronics Plc. Longmead Business Centre, Epsom, Surrey KT19 9QQ.
visit our website:
www.responseplc.com
03.01
0359
RADIO DEVICES FOR
USE IN THE UK
Loading...