Resolution RE214 User Manual

I
RE214 Honeywell® Compatible Smoke and Heat Alarm
Smoke Alarm is a fire-protection device
that alarms when it detects smoke or temperatures above 135°F (57°C).
Features
• UL217 and ULC531 listings
• Smoke and heat detection
• 5 year warranty
Quick Start Guide
1. Remove the mounting plate.
2. Pull the battery tab.
3. Restore the mounting plate and twist it fully onto the smoke alarm.
Note: Enrollment is possible only
if the mounting plate is twisted onto the smoke alarm.
4. Enroll Loop 1 of the smoke alarm by placing the panel into wireless enrollment mode and then hold down the smoke’s test button until
Pull Battery Tab
the smoke alarm beeps. Release the test button until the sounder stops beeping, and then press and hold the test button again to enroll.
5. Remove the mounting plate and refer to Sections 2 and 6 for positioning and installation.
12 inches minimum
6. After mounting plate is installed restore the smoke alarm onto the mounting plate and fully test the smoke alarm per Section 7.
Position Smoke Alarm
To replace the battery, detach the
smoke alarm from its mounting plate and replace the batteries.
12 inches minimum
A
T
S
L
L
N
I
G
E
D
I
Test Smoke Alarm
Attention
This manual should be read prior to use and retained for further information.
Verify proper enrollment and operation using your security panel’s installation manual.
Indicator Summary
Normal Operation Action Red LED Yellow LED Sounder
Power Up Insert Battery 1 Flash 1 Flash Off
Standby Off Off Off
Sensing Fire Rapid Flashing Off Full Sound
Fault Mode Action Red LED Yellow LED Sounder
Low Battery Off 1 Flash every 48 sec 1 Beep
Faulty Smoke Sensor Off 2 Flashes every 48 sec 2 Beeps
Faulty Heat Sensor Off 2 Flashes every 48 sec 2 Beeps
End of Life Off 3 Flashes every 48 sec 3 Beeps
Silence Sounding Alarm
Silence “End of Life” indication (up to 30 days)
Test Mode Action Red LED Yellow LED Sounder
Test Smoke Alarm Press Button Rapid Flashing Off Full Sound
Alarm Memory Action Red Led Yellow LED Sounder
24 Hour Memory 2 Flashes every 48
Long Term Memory Press & Hold Button Rapid Flashing Off Rapid Chirping
1.1. Normal Operation
1.1.1. Power Up Twist off the Alarm from the mounting plate
(see Quick Start Guide). Remove the battery tab to power the Alarm, the red LED will flash once followed by one flash of the yellow LED to indicate that the Alarm has been powered successfully and is now in standby mode.
1.1.2. Standby In standby mode there are no active visible or
audible indications which can be intrusive to the householder. To confirm that the Alarm is operational perform a weekly button test.
1.1.3. Weekly button test Press and hold the test button and verify that
the red LED flashes rapidly and the Alarm ramps up to full sound.
1.1.4. Sensing Fire As soon as the Alarm senses smoke it will
go into Alarm. The red LED on the Alarm sensing smoke flashes rapidly to indicate this is the Alarm sensing smoke / fire. Follow the instruction in section 3 and evacuate the building.
1.1.5. Silence False / Nuisance alarm Occasionally Smoke Alarms can be activated
by phenomena other than fire, e.g. dust, insects, cooking fumes. Once you are sure it is a nuisance alarm press the large test button to silence the Alarm for 10 minutes – the red LED will then flash every 8 seconds for 10 minutes.
1.2. Fault Conditions
1.2.1. Low battery
Press & Release Button 1 Flash every 8 sec Off Off for 10 mins
Press & Release Button Off Off for 72 hours Off for 72 hours
Off Off
sec for 24 hours
The Alarm will emit a short beep and flash the Yellow LED when it becomes partially depleted. Check the date when the Alarm should be replaced which is given on the sidewall of the Alarm. When electronic self testing indicates that the battery is becoming low the Alarm will beep and the yellow LED will flash at the same time (about every 48 seconds) to warn the user. This indicates that the battery or batteries must be replaced.
1.2.2. Contaminated chamber If the Alarm sounds without any apparent
smoke being present, press the test button to silence the Alarm for 10 minutes (as described in 1.1.5 above). If the Alarm sounds again it may be contaminated. Pressing the test button again, within 4 minutes of the Alarm re-sounding, will get the Alarm to compensate for chamber contamination. This will normally resolve the problem.
If the Alarm re-sounds for a third time, the Alarm is excessively contaminated and must be replaced. If it is not convenient to replace it immediately, pressing the test button within 4 minutes of it going into alarm (for the third time) will silence the Alarm for 8 hours – however it will give two short beeps (second apart) every 10 minutes to remind the user it has been disabled. If the contamination clears the Alarm will return to normal operation.
(Note: this does not reduce the users fire protection, as a Smoke Alarm in continuous alarm due to a fault, is useless and must be silenced – by taking the Alarm down or as described here. This procedure has the added
2
benefits that the user is reminded every 10 minutes by two short beeps that the Alarm needs to be replaced and that if the problem clears the Alarm will return to detecting fire).
1.2.3. Faulty smoke chamber In the unlikely event of the smoke sensing
chamber becoming defective, the Alarm will give 2 short beeps with 2 yellow LED flashes every 48 seconds. The Alarm must then be replaced.
If it is not convenient to replace it immediately, pressing the test button will silence the beeps and stop the yellow LED flashing for 12 hours. This can be repeated as required.
2. Location and Positioning
Introduction
Congratulations on purchasing a Smoke Alarm. You can easily install these Alarms throughout the property on escape routes, on each storey, in corridors and in closed rooms to give warning of fire.
Heat Alarms can be installed in kitchens and other areas where Smoke Alarms are unsuitable.
NATIONAL FIRE PROTECTION ASSOCIATION REQUIRED PROTECTION
Smoke Detection. Where required by applicable laws, codes, or standards for the specified occupancy, approved single- and multiple-station Smoke Alarms shall be installed as follows:
(1) In all sleeping rooms and guest rooms (2) Outside of each separate dwelling unit sleeping area within 6.4 m (21 ft) of any door to a sleeping room, the distance measured along a path of travel (3) On every level of a dwelling unit, including basements (4) On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics (5) In the living area(s) of a guest suite (6) In the living area(s) of a residential board and care occupancy (small facility)
Are More Smoke Alarms Desirable? The required number of smoke detectors might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke detectors. For this reason, it is recommended that the householder consider the use of additional smoke detectors for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke detectors.
The installation of smoke detectors in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
The equipment should be wired and installed in accordance with National Fire Protection Association’s Standard 72, Chapter 11 and National Electric Code, NFPA 70, Chapter
3. (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
For Canadian installations wiring methods shall be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations. Testing and maintenance procedures shall be in accordance with CAN/ULC-S552, Standard for the Maintenance and Testing of Smoke-Alarms.
IMPORTANT!
Specific requirements for Smoke Alarm installation vary from state to state and from region to region. Check with your local Fire Department for current requirements in your area.
SMOKE ALARMS
Sufficient smoke must enter your Smoke Alarm before it will respond. Your Smoke Alarm needs to be within 6.4 metres (21ft) of the fire to respond quickly. Smoke Alarms also need to be in positions where they can be heard throughout the property, so they can wake you and your family in time for everyone to escape. A single Smoke Alarm will give some protection if it is properly installed, but most homes will require two or more (preferably interconnected) to ensure that a reliable early warning is given. For recommended protection you should put individual Smoke Alarms in all rooms where fire is most likely to break out (apart from the kitchen and bathroom).
Your first Smoke Alarm should be located between the sleeping area and the most likely sources of fire (living room for example), but it should not be more than 6.4 metres (21ft)from the door to any room where a fire may start and block your escape from the house.
Multi-Storey Dwellings
If your home has more than one floor, at least one Alarm should be fitted on each level (see Figure 1). Preferably the Alarms should be interconnected (if feature is present on unit) so as to give sufficient warning throughout the property.
Figure 1 illustrates where Smoke and Heat Alarms should be located in a typical two storey house. Note the spacings in “Protection Levels” which ensure the early detection of fire and that the warning will be heard.
3
PLACE IN CENTRAL
LOCATION AND
NOT WITHIN 305mm (12”)
OF ANY CORNER
SMOKE ALARMS
<610mm (24”) FROM APEX
DEAD AIR
SPACE
Locate Heat Alarms in rooms adjoining escape routes - kitchens, garages, boiler houses etc. where Smoke Alarms are unsuitable.
Figure 1
For minimum protection
- Smoke Alarm on each storey
- in each sleeping area
- every 6.4 metres (21ft) of hallways and rooms
- within 3 metres (10ft) of all bedroom doors
- all units interconnected (where feature is present)
For recommended protection
(in addition to the above):
- Smoke Alarms in every room (except kitchens and bathrooms)
- Heat Alarms located in kitchens, garages etc. within 5.3m (17ft) of potential fire sources
Single Storey Dwelling
If the premises is one storey you should put your first Smoke Alarm in a corridor or hallway between the sleeping and living areas. Place it as near to the living area as possible, but make sure that it can be heard loudly enough in the bedroom to wake someone. See Figure 2 for placement example.
In houses with more than one sleeping area, Smoke Alarms should be placed between each sleeping area and the living area and it is recommended that Heat Alarms should be placed in the kitchen and garage.
Figure 2
room is the most likely place for a fire to start at night, followed by the kitchen (where a Heat Alarm is recommended) and then the dining room. Consideration should be given to installing Smoke Alarms in any bedrooms where fires might occur, for instance, where there is an electrical appliance such as an electric blanket or heater, or where the occupant is a smoker. In addition, consideration should be also given to installing Smoke Alarms in any rooms where the occupant is unable to respond very well to a fire starting in that room, such as an elderly or sick person or a very young child.
Checking Alarms Can Be Heard
With the Alarms sounding in their intended locations check that the alarm can be heard in each bedroom with the door closed, above the sound of any TV/audio systems. The TV/ audio systems should be set to a reasonably loud conversation level. If you cannot hear the alarm over the sound of the TV/audio system, the chances are it would not wake you. Interconnecting the Alarms will help to ensure that the alarm will be heard throughout the property.
Positioning
Ceiling Mounting
Hot smoke rises and spreads out, so a central ceiling position is the recommended location. The air is “dead” and does not move in corners, therefore Smoke Alarms must be mounted away from corners. Keep at least 305mm (12”) from walls and corners (see Figure 3). Additionally, mount the unit at least 305mm (12”) from any light fitting or decorative object which might prevent smoke entering the Smoke Alarm.
Figure 3
Bedroom
Bathroom
Bedroom
Bath
Laundry
Room
Bedroom
Kitchen
Dining Room
Living Room
Recommended Protection
Fire authorities recommend you put individual Smoke Alarms in or near all rooms where fire is most likely to break out (apart from the locations to avoid e.g bathrooms). The living
Wall Mounting
If ceiling mounting is impractical, Smoke Alarms may be mounted on a wall, provided that: a) the top of the detection element is between 150mm (6”) and 305mm (12”) below the ceiling (see; Figure 3a). b) the bottom of the detection element is above the level of any door openings; Wall mounting should only be considered where close spaced beams or similar obstructions may
4
Loading...
+ 8 hidden pages