Wireless
Security
RE213 Honeywell-Compatible Carbon Monoxide Alarm
Features
• Senses and alarms to Carbon Monoxide per UL2034
• Sleek design
• Cover tamper.
• Strong, reliable RF signal.
• 3-5 year battery life on 3 Panasonic LR6-AA batteries.
• Low Battery indication.
Key Instructions
1. Attach the mounting plate
Locate on ceiling, or wall in or near sleeping areas.
Some local codes have specifications on CO detectors.
Mounting plate removes counter-clockwise
2. Insert batteries making sure of polarity. Close battery door.
3. Enroll sensor in panel:
a) Enter Zone Programming Mode (e.g. *56)
b) Zone Type = 14
c) Input type = Supervised RF Transmitter.
d) When asked for a serial number, press Tamper button
e) Select Loop 1 for CO
4. Testing:
a) Place panel in Sensor Test mode.
b) Press & hold TEST button until you the sounder beep.
c) Panel will indicate the sensor is open, and alarm will sound.
NOTE: Using CO-in-a-Can will cause an actual CO alarm.
Operation
Specifications
CO Sensitivity: (UL2034)
70ppm 60-120 minutes
150ppm 10-50 minutes
400ppm 4-15 minutes
(EN50291)
50ppm 60-90 minutes
100ppm 10-40 minutes
150ppm 3 minutes or less
CO Sensing Technology: Electrochemical
Heat Alarm Point: 135 – 149 F (UL 521)
Alarm Sound: Temporal Three
Replacement Battery: 3 Panasonic LR6-AA
Temperature Range: 40 to 100 F (Long Term)
Humidity: 0 – 95% Relative Humidity
Housing dimensions: 4.9 inch diameter, 1.4 inch high
Specifications subject to change without notice.
Tabs
Button
from Mount
Needed
RE213_Honeywell-Compat_CO_Instructions Page 1 of 4 15-May-14
(Loud) every 8
seconds
Beeps
(Loud)
(Loud)
every 60 seconds
minute
minute
minute
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
(pulsing)
& Yellow
(pulsing)
(steady)
(pulsing)
every minute
twice a
minute
4 times a
minute
Alarm Signal
sent to panel
signal to panel
signal to be sent
Not Sent
Not Sent
Not Sent
present.
TEST button will silence
Panel: Clear alarm
condition.
Pictures
Element
RED GREEN YELLOW
TEST Button
Bucket
Door
Release
Button
RE213_Honeywell-Compat_CO_Instructions Page 2 of 4 15-May-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com

Opening Cover
Battery
Door
Down
On
Release
Button
Battery
Polarity
Notices
Verify proper enrollment and operation, per control panel installation instructions, at installation.
CARBON MONOXIDE ALARM M330 USER’S MANUAL, which is included in device box, is an integral part
of the operating information of the RE213 device.
Approved as a self-contained carbon monoxide alarm per UL2034. This represents the ability of each
individual sensor to sound locally upon sensed carbon monoxide conditions.
“GE”, “Interlogix”, “Honeywell”, “2GIG”, “DSC”, “Napco” are trademarks owned by General Electric
Company, UTC Fire & Security Americas Corporation, Inc., Honeywell International Inc., 2GIG
Technologies Inc., Tyco Safety Products Canada LTD, Napco Security Systems respectively.
Resolution Products, Inc. products will function with one of either GE/Interlogix, Honeywell and
2GIG, DSC or Napco. However, no Resolution product is produced by, endorsed by, nor is officially
associated with any of these other manufacturers. Resolution recommends verifying proper
enrollment and operation, per control panel installation instructions, at installation.
Warranty
Resolution Products, Inc. will replace products that are defective in their first five (5) years.
FCC Notice
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
(1)This device may not cause harmful interference.
(2)This device must accept any interference that may be received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by the Resolution Products, Inc. could void
the user's authority to operate this equipment.
FCC ID: U5X-RE213
IC Notice
This device complies with Industry Canada license-exempt RSS standard(s). Operation is
subject to the following two conditions:
(1)This device may not cause interference, and
(2)This device must accept any interference, including interference that may
cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils
radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
(1)l'appareil ne doit pas produire de brouillage, et
(2)l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d'en compromettre le fonctionnement.
IC: 8310A-RE213
RE213_Honeywell-Compat_CO_Instructions Page 3 of 4 15-May-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
RE213_Honeywell-Compat_CO_Instructions Page 4 of 4 15-May-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com