Example: if 15 liters of water and 20 liters of glycol are used in the solar circuit,
then follows:
Vol % = (20 : (15 + 20)) x 100 = 57
Determining the ratio for unknown volumes:
RESOL refractomter:
In order to analyze the system, a small amount of uid has to be withdrawn from
the solar circuit and applied to the prism surface of the refractometer. Hold the
pointy end against the light and turn the ocular until the borderlines become visible. The borderlines indicate the freezing temperature. In a table on the receptacle
of the heat transfer uid, the value for the vol.-% corresponding to the temperature value, is shown.
4 Commissioning
When the RESOL WMZ calorimeter is commissioned for the rst time or after a
reset, it will run a commissioning menu. The commissioning menu leads the user
through the most important adjustment channels needed.
Commissioning:
Version x.xx
Language English
Temp. unit °C
Commissioning menu
The commissioning menu consists of the
channels described in the following.
At the top of the commissioning menu,
the version number of the device is indicated.
Commissioning:
Language English
Temp. unit °C
Flow unit Litres/hour
Language
Selection: Deutsch, English, Francais, Italiano, Espanol
Factory setting: Deutsch
Î Adjust the desired menu language.
Commissioning:
Temp. unit °C
Flow unit Litres/hour
Energy unit kWh
Temp. unit
Selection: °C, °F
Factory setting:°C
Î Adjust the desired temeprature unit.
Commissioning:
Flow unit Litres/hour
Energy unit kWh
Antifr. type Water
Flow unit
Selection: Litres/hour, Gal./minute
Factory setting: Litres/hour
Î Adjust the desired ow rate unit.
Commissioning:
Energy unit kWh
Antifr. type Water
Antifreeze 40 %
Energy unit
Selection: kWh, BTU
Factory setting: kWh
Î Adjust the desired energy unit.
Commissioning:
Energy unit kWh
Antifr. type Water
Antifreeze 40 %
Antifr. type
Selection: Water, Propylene, Ethylene,
Tyfo LS
Factory setting: Water
Î Adjust the heat transfer uid used in
the system.
Commissioning:
Antifr. type Propylene
Antifreeze 40 %
Volume/Imp. 1.0 L/I
Antifreeze
Adjustment range: 20 … 70 %
Factory setting: 40 %
Available only if Antifr. type is set to Pro-
pylene or Ethylene.
Î Adjust the antifreeze ratio of the
heat transfer uid used in the
system.
Commissioning:
Antifr. type Propylene
Antifreeze 40 %
Volume/Imp. 1.0 L/I
Volume/Imp.
Adjustment range: 0.1 … 99.9 L/I
Factory setting: 1.0 L/I
Î Adjust the impulse rate of the
owmeter or ow rate sensor
respectively.