Resol DeltaSol DB3-F User Manual

RESOL DeltaSol® DB3-F
Mounting
Connection
Operation
Troubleshooting
Examples
DB3-F
®
Thank your for buying this RESOL product. Read this manual carefully to get the best perfomance from this unit.
*48004710*
48004710
DeltaSol
Manual
www.resol.de
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 2
Safety advice
Please read the following information carefully before installing and opera­ting the controller. In this way damage to the solar system caused by wrong installation will be avoided. Please ob­serve that the mounting is adapted to the characteristics of the building, that the local regulations are respected and is conform with the technical rules
Instructions:
Attention should be paid to
- valid local regulations
Appropriate usage
The controller is to be used in drain­back solar thermal systems in com­pliance with the technical data speci­fied in these instructions.
Improper use excludes all liability claims.
Table of contents
Safety advice ............................................................................................. 2
Technical data and overview of functions .............................................. 3
1. Installation ...........................................................................................5
1.1 Mounting ......................................................................................................5
1.2 Electrical connection .................................................................................5
1.2.1 Data communication / Bus ........................................................................6
1.2.1 Standard solar system ...............................................................................6
1.2.2 Solar system and backup-heating ........................................................... 7
2. Operation and function .....................................................................8
2.1 Buttons for adjustment .............................................................................8
2.2 System Monitoring-Display ......................................................................8
2.2.1 Channel display ...........................................................................................8
2.2.2 Tool bar ........................................................................................................8
2.2.3 System-Screen ............................................................................................ 9
2.3 Flashing codes .............................................................................................9
2.3.1 System-Screen flashing codes .................................................................9
2.3.2 LED flashing .................................................................................................9
3. Commissioning ................................................................................. 10
4. Control parameters and display channels .....................................11
4.1 Overview of channels .............................................................................11
4.1.1-9 Display channels .......................................................................................12
4.1.10-22 Adjustment channels ...............................................................................13
5. Trouble shooting ...............................................................................17
5.1 Various........................................................................................................18
6. Accessory ..........................................................................................20
Imprint .............................................................................................. 20
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
3 |
!
Controller especially developed for solar drainback systems
• System-Monitoring-Display
• Upto4temperaturesensors
Pt1000
• Heatproductionmeasurement
• RESOLVBus
• Functioncontrol
• User-friendlyoperation
• Easy-to-mounthousingwith
outstanding design
• operatinghourscounterand
thermostat function
®
Deliveryscope:
1 x DeltaSol® DB3-F
1 x accessory bag
1 x spare fuse T4A 2 x screw and dowel 4 x strain reflief and screw
Additionnally included in the accesory bag: 1 x sensor FKP6 2 x sensor FRP6
Housing:
plastic, PC-ABS and PMMA
Protection type: IP 20 / DIN 40050
Ambient temp.: 32 ... 104 °F
Dimensions:172 x 110 x 46 mm
Mounting: wall mounting, mounting into patch-panels is possible
Display: System screen for systems visualisation, 16-segment display, 7-seg­ment display, 8 symbols for system status and operating control lamp
Operation: 3 push buttons at the front of the housing
Functions: Differential tempera­ture controller with optional system functions. Function control, operating hours counter for solar pump, pump speed control and heat production measurement.
Inputs:
for 4 temperature sensors Pt1000
Outputs: 2 standard relays
®
Bus: RESOL VBus
Power supply: 115 V~, 50 ... 60 Hz
Total switching capacity: 4 (2) A (115) V~
Mode of operation:
Type 1.b Switching capacity:
electromechanical relay: 2 (1) A (115) V~
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 4
Examples DeltaSol® DB3-F
Standard drain back
systems
Drain back systems with
booster function
Drainback systems with
backup-heating
Forfurtherinformation
on electrical connection, please see chapter 1.
Order note
• DB3:2standard relay, thermostat or booster function, operating hours counter RESOL DeltaSol® DB/3 115 426 07 RESOL DeltaSol® DB/3 -fullkit incl. 3 temperature sensors Pt1000 (1 x FKP6, 2 x FRP6) 115 426 17
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
5 |
12
S1 S2 S3
3456
Te mp. Sensor
Pt1000
LNR1NR2N
201918171615
S4
78
141312
2 (1) A (115)V~ 2 (1) A (115)V~
R1
R2
VBus
910
1. Installation
1.1 Mounting
front cover
cable gland with strain relief
fastening
fastening
display
fuse 4A
push button
WARNING!
Alwaysswitch-offpower supply and
disconnect the controller from the power supply before opening the housing!
The unit must only be located in dry interior locations. It is not suitable for installation in hazardous locations and should not be placed close to any electromagnetic fields. The controller must additionally be supplied from a double­pole switch with contact gap of at least 3 mm. Please pay attention to separate routing of sensor cables and power supply cables.
1. Unscrew the cross-head screw from the cover and remove it along with the cover from the housing.
2. Mark the upper fastening point on the wall and drill and fasten the enclosed wall plug and screw leaving the head protruding.
3. Hang the housing from the upper fastening point and mark the lower fastening point through the hole in the terminal box (centers on 130 mm). Drill and insert the lower wall plug.
4. Fasten the housing to the wall with lower fastening screw and tighten.
1.2 Electrical connection
sensor terminals
RESOL VBus
®
grounding clamp
fuse
load terminals
power supply terminals
The power supply to the controller must be carried out via an external power switch (last step!) and the supply voltage must be 115 V~ (50 ... 60 Hz). Flexible cables must be attached to the housing with the enclosed strain relief and the corresponding screws.
The controller is equipped with 2 relays to which loads such as pumps, valves, etc. can be connected:
• Relay 1
18 = conductor R1 17 = neutral conductor N 13 = grounding clamp
• Relay 2
16 = conductor R2 15 = neutral conductor N 14 = grounding clamp
Temperature sensors (S1 to S4) have to be connected to the following terminals (either polarity):
1 / 2 = sensor 1 (e.g. sensor collector 1) 3 / 4 = sensor 2 (e.g. sensor tank 1) 5 / 6 = sensor 3 (e.g. tank top sensor)
7 / 8 = sensor 4 (e.g. return temperature sensor) The power supply connection has to be carried out at the following terminals:
19 = neutral conductor N 20 = conductor L 12 = grounding clamp
Electrostatic discharge can lead to damage to elec­tronic components!
Dangerous voltage!
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 6
VBus
10
9
12
S1 S2 S3
3456
Te mp. Sensor
Pt1000
LNR1NR2N
201918171615
S4
78
141312
2 (1) A (115)V~ 2 (1) A (115)V~
R1
R2
VBus
910
1.2.1 Datacommunication/Bus
RESOL VBus®
connection clamps
®
The controller comes with a RESOL VBus
for data com­munication and energy supply of external modules. The connection is effected with optional polarity at the clamps marked with „VBus“. Via this data Bus you can install one or more RESOL VBus® modules, e.g.:
RESOL large display GA3 / SD3
RESOL Data logger, DL2
RESOL Data teleindication
Additionaly, the controller can be connected to the PC with the help of a RESOL RS-COM adapter. With the RESOL ServiceCenter Software (RSC) the controller parameters can be changed, measurements can be read out, processed and visualised. The software enables an easy function control and adjustment of the system. A light Version of the software can be downloaded from www.resol.de for free.
1.2.2 Terminal allocation Arrangement 1 Standard solar system with 1 tank, 1 pump and 3 sen-
sors. The sensor S4 / TRF can be optionally used for heat production measurement.
ARR1
S1
R1
S3
Symbol Description
S1 collector sensor S2 tank sensor bottom
S3 tank sensor top
(optional)
S4 / TRF
S2
S4 / TRL sensor for heat production
measurement
(optional)
solar pump
R1
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
7 |
VBus
10
9
VBus
10
9
ARR1 with booster
S1
Standard solar system with booster function option
with 1 tank, 2 pumps and 3 sensors. The sensor S4 / TRF can be optionally used for heat production measurement.
R1
S4 / TRF
R2
S3
S2
1.2.3 Terminal allocation Arrangement 2
ARR 2
Symbol Description
S1 collector sensor S2 tank sensor bottom S3 tank sensor top /
thermostat sensor
S4 / TRF sensor for heat production
measurement
(optional)
R1
solar pump
R2 booster pump
Solar system and backup heating with 1 tank, 3 sensors and backup heating. The sensor S4 / TRF can be optionally used for heat production measurement.
S1
Symbol Specification
S1 collector sensor
R1
S3
S2 store sensor bottom S3 store sensor top
S4 / TRF sensor for heat production
measurement (optional)
R2
S4 / TRF
S2
R1 R2
solar pump
pump for backup heating
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 8
!
2. Operation and function
2.1 Buttonsforadjustment
The controller is operated via the 3 push buttons below the display. The forward-button (1) is used for scrolling for­ward through the display menu or to increase the adjustment values. The backward-button (2) is similarly used for scrolling backwards and reducing values.
backwards
2
1
3
(selection / adjustment mode)
SET
2.2 System-MonitoringDisplay
Complete Monitoring-Display
2.2.1 Channel display
forwards
In order to access the adjustment mode, scroll down in the display menu and press the forward button (1) for approx. 2 seconds after you have reached the last display item. If an adjustmentvalueis shown on the display, the „SEt“ icon is displayed. Now, you can access the adjustment mode by using button 3.
• Press buttons 1 and 2 in order to select a channel
• Briey press button 3, „SEt“ will ash
• Adjust the value by pressing buttons 1 and 2
• Briey press buttons 3, so that „SEt“ permanently
appears, the adjusted value will be saved.
The system monitoring display consists of 3 blocks: channel display, tool bar and system screen (active arrange­ment).
channel display
2.2.2 Tool bar
tool bar
The channel display consists of two lines. The upper line is an alpha-numeric 16-segment display (text display) for displaying channel names and menu items. In the lower 7-segment display, the channel values and the adjustment parameters are displayed. Temperatures and temperature differences are indicated in°C or K respectively.
The additional symbols in the tool bar indicate the actual system status.
Symbol standard flashing
relay 1 active
relay 2 active
tank maximum limitation active / maximum tank temperature exceeded
+
+
collector cooling function or recooling function active
collector emergency shutdown or tank emergency shutdown active
sensor defective
manual operation active
SET-mode, change of adjust­ment value is possible
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
9 |
2.2.3 System-Screen
System-Screen
The system screen (active arrangement) shows the scheme which has been selected. The screen consists of several system component symbols, which are - depending on the current status of the system - either flashing, permanently shown or „hidden“.
collector
pumps
sensor
tank heat exchanger
collector with collector sensor
tank top sensor
tank
additional symbol burner operation
backup heating (with addi tional symbol)
temperature sensor
pump
tank 1
with heat exchanger
backup-heating with burner symbol
2.3 Flashingcodes
2.3.1 System screen codes
Pump symbols are flashing during initialization phase
Sensor symbols are flashing if the corresponding sensor
display channel is selected.
Sensor symbols are flashing in the case of a sensor fault.
Burner symbol is flashing if the backup heating is active
2.3.2LEDashingcodes
green: everything OK red/green flashing: initialisation phase manual operation red flashing: sensor fault
(sensor symbol is flashing quickly)
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 10
3. Commissioning
When the controller is commissionend for the first time, the arrangement has to be selected first
1. Switch on power supply. During the initialization phase,
the operating control lamp flashes red and green. The
Operation control lamp
backwards
2
(selection / adjustment mode)
3
SET
1
forwards
version number and the language selection menu are displayed.
During initial commissioning, the language has to be selected.
2. - Select the adjustment channel LANG
- Change to the -mode (see. 2.1)
- Select your language
- Save the adjustment by pressing the button
After initialization, the controller is in the automatic mode with typical settings. The pre-programmed system scheme is Arr 1.
3. - select adjustment channel Arr
ARR 1
ARR 1 with booster
ARR 2
- change to the -mode (see 2.1)
- select the arrangement via the Arr-index number
- save the adjustment by pressing the button
Now the controller is ready for operation with typical settings to suit that system and normally the factory settings will give close to optimum operation.
Overview of arrangements:
ARR 1 : standard solar sytem (with booster function option) ARR 2 : solar system with backup heating
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
11 |
4. Control parameters and display channels
4.1 Overview of channels
Legend:
x
Corresponding channel is available.
x*
Corresponding channel is available when the corresponding option is enabled
Please note: Only if temperature sensors are connected, will S3 and S4 be displayed.
channel
INIT x x time period - switch-on conditions
FLL x x time period - filling time active 12
STAB** x x time period - stabilisation active 12
COL x x temperature collector 12
TST x Temperature tank 12
TSTL x temperature tank base 12
TSTU x temperature tank top 12
S3 x temperature sensor 3 12
TRF
S4
n % x speed relay 1 12
n1 % x speed relay 1 12
h P x operating hours relay 1 13
h P1 x operating hours relay 1 13
h P2 x operating hours relay 2 13
kWh
MWh
ARR 1-2 Arrangement
DT O x x Switch-on temperature difference 13
DT F x x Switch-off temperature difference 13
DT S x x Sset temperature difference 13
RIS x x Rise 13
tDTO x x time period - switch-on conditions 13
tFLL x x filling time 13
tSTB x x time period - stabilisation 14
OBST*** x booster function option 14
S MX x x maximum temperature tank 1 14
EM x x emergency shutdown collector 1 15
ARR description page
1 2*
active
temperature return sensor 12
temperature sensor 4 12
heat quantity kWh 15
heat quantity MWh 15
12

Only if the option heat production measurement is activa­ted (OHQM), will the corresponding channel be available.

Only if the option heat production measurement is deactiva­ted (OHQM), will the corresponding channel be available.
MEDT
Only if an antifreeze (MEDT) other than water or Tyfocor LS/G-LS(MEDT0or3) is used, will the channel anti­freeze concentration (MED%) be displayed.
channel
OCN x x option collector minimum
CMN x x minimum collector temperature 15
TH O x switch-on temp. thermostat 16
TH F x switch-off temp. thermostat 16
OHQM x HQM option 14
FMAX
MEDT
MED% MEDT MEDT antifreeze concentration 14
n1MN x minimum speed relay 1 16
HND x x manual mode relay 1 16
HND1 x x manual mode relay 1 16
HND2 x x manual mode relay 2 16
LANG x x language 16
Db x XX.XX
ARR description page
1 2
limitation
maximum flow rate 14
antifreeze type 14
15
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 12
4.1.1 Initialization
INIT:
Initialization active
4.1.2 Fillingtime
FLL:
Filling time active
4.1.3 Stabilization
STAB:
Stabilization
4.1.4 Collector temperature
COL:
Collector temperature Display range: -40 ... +480 °C
Indicates the time adjusted in tDTE, running backwards.
INIT : Initialization
Indicates the time adjusted in tFLL, running backwards.
FLL : filling time
Indicates the time adjusted in tSTB, running backwards.
STAB : Stabilization
Indicates the collector temperature.
COL : Collector temperature
4.1.5 Tank temperatures
TSTTSTL,TSTU:
Tank temperatures Display range: -40 ... +480 °F
4.1.6 Sensor 3 and Sensor 4
S3, S4:
Sensor temperatures Display range: -40 ... +480 °F
4.1.7 Other temperatures
TRF:
Other measured temperatures Display range: -40 ... +480 °F
Indicates the tank temperature.
TSP : tank temperature
TSPU : tank temperature bottom
• TSPO : tank temperature top
Display of the current temperature at the corresponding additional sensor (without control function).
S3 : temperature - sensor 3
S4 : temperature - sensor 4
Please note: Only if the temperature sensors are connected (displa­yed), will S3 and S4 be displayed.
Display of the current temperature at the sensor.
TRF : temperature - return
4.1.8 Pump speed
n %, n1 %:
Pump speed Display range: 30 ... 100 %
Display of the current pump speed of the corresponding pump (on DB2 and DB4 only).
n % : current pump speed (1-pump system)
n1 % : current pump speed pump 1
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
13 |
4.1.9 Operating hours counter
h P / h P1 / h P2:
Operating hours counter Display channel
4.1.10 ∆T-regulation
DTO:
Switch-on temperature diff. Adjustment range: 2...40 Factory setting: 20.0
The operating hours counter accumulates the solar opera­ting hours of the respective relay (h P / h P1 / hP2). Full hours are displayed.
The accumulated operating hours can be set back to zero. As soon as one operating hours channel is selected, the sym-
bol is displayed. Press the SET (3) button for approx. 3 seconds in order to access the RESET-mode of the counter. The display symbol will flash and the operating hours will be set to 0. Confirm the reset with the button in order to finish the reset.
In order to interrupt the RESET-process, do not press a button for about 5 seconds. The display returns to the display mode.
When the switch-on difference (DTO) is continuously ex­ceeded during the tDTO period, the pump is switched on. When the temperature difference falls below the adjusted switch-off difference (DTF), the controller switches off.
DTF: Switch-off temperature diff. Adjustment range: 1 ... 38 Factory setting 8
4.1.11Timeperiod-switch-onconditions
tDTO:
Time periode - switch-on conditions Adjustment range: 1 ... 100 s Factory setting: 60 s
4.1.12Fillingtime
tFLL:
Filling time Adjustment range: 1 ... 30 min Factory setting: 5 min
Please note: The switch-on temperature difference must be at least 0,5 K higher than the switch-off tempe rature difference.
The parameter tDTO is used for adjusting the time period during which the switch-on condition must be permanentely fulfilled.
The filling time can be adjusted using the parameter tFLL. During this period, the pump runs at 100% speed and the booster pump is additionally switched-on.
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 14
4.1.13 Stabilization
tSTB: Stabilization Adjustment range: 1 ... 15 min Factory setting: 2 min
The parameter tSTB is used for adjusting the time period during which the switch-off condition will be ignored after the filling time has ended.
4.1.14Boosterfunctionoption
OBST:
Booster function Adjustment range: ON, OFF Factory setting: OFF
4.1.15 Maximum tank temperature
S MX:
Maximum tank temperature Adjustment range: +40 ... 480
4.1.16Heatproductionmeasurement
OHQM:Heat quantity mea-
surement Adjustment range: OFF ... ON Factory setting: OFF
FMAX: Flow rate in l/min Adjustment range: 0 ... 20 in 0,1-steps Factory setting: 6,0
MEDT: Antifreeze type Adjustment range: 0 ... 3 Factory setting: 1
This function is used for switching on a second pump during filling the solar system. When solar loading starts, R2 is ener­gized in parallel to R1. After the filling time (tFLL) has ended, R2 is switched off.
If the adjusted maximum temperature is exceeded, the tank will no longer be loaded in order to avoid damage caused by overheating. If the maximum tank temperature is exceeded,
will be shown.
Please note: The controller is equipped with a tank emer­gency shutdown function, which prevents the tank from being loaded when the tank temperature exceeds 295 °F.
Heat production measurement is possible if a flowmeter is used. For this purpose, the heat quantity measurement option (OHQM)has to be enabled.
The flow rate should be read from the flowmeter (l/min) and has to be adjusted in the channel FMAX. Antifreeze type and concentration of the heat transfer medium have to be adjusted in the channels MEDTandMED%.
Antifreeze type:
0 : water 1 : propylene glycol 2 : ethylene glycol
®
3 : Tyfocor
LS / G-LS
MED%: Antifreeze concen­tration (Vol-) % When MEDT 0 or 3 is used, the parameter MED% is ‚hidden‘. Adjustment range: 20 ... 70 Factory setting: 45
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
15 |
kWh/MWh: Heat quantity in kWh / MWh Display channel
4.1.17 Collector emergency temperature Collector emergency shutdown
EM:
Collector emergeny shutdown temperature Adjustment range: 230 ... 400°F Factory setting: 285°F
°F
The flow rate as well as the reference sensors S1 (flow) and S4 (return) are used for calculating the heat quantity sup­plied. It is shown in kWh in the channel kWh and in MWh in the channel MWh. The overall heat quantity results from the sum of both values (please pay attention to the units!).
Example: 123 kWh + 123 MWh = 123.123 kWh
The accumulated heat quantity can be reset. As soon as one of the display channels of the heat quantity is selected,
the symbol is permanently shown on the display. Press button SET (3) for about 2 seconds in order to access the RESET mode of the counter. The display symbol will flash and the heat quantity value will be set to 0. In order to finish this process, press the button to confirm.
In order to interrupt the RESET process, no button should be pressed for about 5 seconds. The controller automatically returns to the display mode.
If the adjusted collector emergency shutdown temperature (EM) is exceeded, the controller will switch off the solar pump (R1) in order to protect the system against overheating (collector emergency shutdown). The factoring setting is 285 °F but it can be changed within the adjustment range of 230 ... 400 °F.
(flashing) is displayed.
4.1.18 Collector minimum limitation option
OCN:
Collector minimum limitation Adjustment range: OFF / ON Factory setting: OFF
CMN: Collector minimum temperature Adjustment range: 210 ... 380°F Factory setting: 40°F
4.1.19 Thermostat function (ARR = 2)
backup heating use of surplus energy
The minimum collector temperature is the minimum temperature which must be exceeded for the solar pump (R1) to switch on. The minimum temperature prevents the pump from being switched on too often at low collector temperatures. If the temperature falls below the minimum temperature,
The thermostat function works independently from the solar operation and can be used for using surplus energy or for backup heating.
THO < THF thermostat function for backup heating
THO > THF thermostat function for using surplus energy
When the 2nd relay output is active, is displayed.
(flashing) is shown on the display.
THO:
Thermostat switch-on tem perature Adjustment range:
30 ... 205 °F Factory setting: 100°F
THF:
Thermostat switch-off tem pe rature Adjustment range:
30 ... 205 °F Factory setting: 110°F
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 16
t1 O, t2 O, t3 O:
Thermostat switch-on time Adjustment range: 00:00 ... 23:45 Factory setting: 00:00
4.1.20 Operating mode
t1F,t2F,t3F:
Thermostat switch-off time Adjustment range: 00:00 ... 23:45 Factory setting: 00:00
In order to block the thermostat function for a certain period of time, there are 3 time frames t1 ... t3. If the func­tion should be activated only between e.g. 6:00 and 9:00, set t1 O to 6:00 and t1Fto 09:00. The thermostat function is continuously activated (factory setting). If all time frames are set to 00:00, the thermostat function is continuously activated (factory setting).
MAN/MAN1/MAN2:
Operating mode Adjustment range: OFF, AUTO, ON Factory setting: AUTO
4.1.21Language(LANG)
LANG:
Language choice Adjustment range: dE, En, It, Fr Factory setting: En
For control and service work, the operating mode of the controller can be manually adjusted. For this purpose, select the adjustment value MAN. The following adjustments can be carried out:
• MAN
Operating mode OFF : relay off AUTO : relay in automatic operation ON : relay on
In this channel, different languages are available.
• dE : German
En : English
• It : Italiano
• Fr : French
(flashing) +
(flashing) +
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
17 |
12
S1 S2 S3
3456
Te mp. Sensor
Pt1000
LNR1NR2N
201918171615
S4
78
141312
2 (1) A (115)V~ 2 (1) A (115)V~
R1
R2
VBus
910
5. Troubleshooting
fuse T4A
Operating control lamp flashes red. The symbol and the are shown.
Sensor fault. An error code instead of a temperature is shown on the sensor display channel.
-88.8888.8
If a malfunction occurs, a message is displayed in the display of the controller:
Warning symbol
Operating control lamp
Operating control lamp off
Check the power supply
o.k.
Cable is broken. Check the cable.
Short-circuit. Check the cable.
Disconnected Pt1000 temperature sen sors can be checked with an ohmmeter. In the following table, the resistance values corresponding to different temperatures are listed.
°F Ω °F Ω
14 961 131 1213 23 980 140 1232 32 1000 149 1252 41 1019 158 1271 50 1039 167 1290 59 1058 176 1309 68 1078 185 1328 77 1097 194 1347 86 1117 203 1366
95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442
Resistance values of the
Pt1000-sensors
The fuse of the controller could be blown. It can be replaced after the front cover has been removed (spare fuse is enclosed in the accessory bag).
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
| 18
5.1Various:
The temperature difference between the tank and the coll­ector increases enormously during operation; the collector circuit cannot divert the heat.
Collector circuit pump defective ?
no yes
Check / replace it
Heat exchanger calcified?
no
yes
Decalify it
Heat exchanger blocked?
yesno
Clean it
The solar circuit pump does not run although the collector is significantly warmer than the tank.
Does the control LED flash?
No current; check fuses / replace them and check
yes no
Does the pump start up in manual operation?
no
yes
power supply.
The adjusted temperature difference for starting the pump is to high; choose a value which makes more sense.
Is the pump current re­leased by the controller?
Is the pump stuck?
no
yes
yes
Turn the pump shaft using a screwdriver; now passable?
Heat exchanger too small?
yes
Repalce with correctly sized one
Are the controller fuses o.k.?
no yes
Replace the fuses.
no
Pump is defective ­replace it
Controller might be de­fective - replace it.
DeltaSol® DB3-F
© RESOL 09098 deltasol_db3-f.monus.indd
19 |
Notes
DeltaSol® DB3-F
6. Accessories
Sensors
Our product range includes high-precision platinum tem­perature sensors, flatscrew sensors, outdoor temperature sensors, indoor temperature sensors, cylindrical clip-on sensors and irradiation sensors, also as complete sensors with immersion sleeves.
Overvoltage protection device
In order to avoid overvoltage damage at collector sensors (e.g. caused by local lightning storms), we recommend in­stalling the overvoltage protection RESOL SP1.
Flowmeter
If you wish to carry out a heat production measurement, you need a flowmeter for measuring the flow rate in your system.
Distributedby:
RESOL-ElektronischeRegelungenGmbH
Heiskampstraße 10
45527 Hattingen / Germany
Tel.: +49 (0) 23 24 / 96 48 - 0 Fax: +49 (0) 23 24 / 96 48 - 755
www.resol.de info@resol.de
Important notice: The text and drawings in this manual are correct to the best of our knowledge. As faults can never be excluded, please note: Your own calculations and plans, under con­sideration of the current standards and directives should only be basis for your projects. We do not offer a guaran­tee for the completeness of the drawings and texts of this manual - they only represent some examples. They can only be used at your own risk. No liability is assumed for incor­rect, incomplete or false information and / or any resulting damages.
Please note:
The design and the specifications can be changed without prior notice. The illustrations may differ from the original product.
| 20
Reprinting/copying
This mounting- and operation manual including all parts is copyrighted. Another use outside the copyright re­quires the approval of RESOL - Elektronische Regelungen
GmbH. This especially applies for copies, translations,
micro films and the storage into electronic systems.
Editor: RESOL - Elektronische Regelungen GmbH
© RESOL 09098 deltasol_db3-f.monus.indd