- safety advice in order to avoid danger and damage to
people and property.
- the valid local standards, regulations and directives!
Description of symbols
WARNING!Warnings are indicated with a
warning triangle!
They contain information on how
to avoid the danger described.
Signal words describe the danger that may occur, when it
is not avoided.
WARNING means that injury, possibly life-threatening
injury, can occur.
ATTENTION means that damage to the appliance can
occur.
Note
Notes are indicated with an information symbol.
Target group
These instructions are exclusively addressed to authorised
skilled personnel.
Only qualified electricians should carry out electrical works.
Initial installation must be effected by qualified personnel
named by the manufacturer.
Information about the product
Proper usage
The solar controller is designed for use in solar thermal
and heating systems in compliance with the technical data
specified in these instructions.
Improper use excludes all liability claims.
CE-Declaration of conformity
The product complies with the relevant
directives and is therefore labelled with the
CE mark. The Declaration of Conformity is
available upon request, please contact RESOL.
Note
Strong electromagnetic fields can impair the
function of the controller.
Î Arrows indicate instruction steps that should be car-
ried out.
Disposal
Dispose of the packaging in an environmentally sound
manner.
Dispose of old appliances in an environmentally sound
manner. Upon request we will take back your old appliances
bought from us and guarantee an environmentally sound
disposal of the devices.
| 2
Î Make sure the controller as well as the
system are not exposed to strong electromagnetic fields.
1 × spare fuse T4A
2 × screws and wall plugs
4 × strain relief and screws
1 × manual
Additionally enclosed in the full kit:
2 × sensor FKP6
2 × sensor FRP6
Technical data
Housing:plastic, PC-ABS and PMMA
Protectiontype:IP 20 / EN 60529
Ambienttemp.:
0 ... 40 °C [32 ... 104 °F]
Size:
172 × 110 × 46 mm
6.8" × 4.3" × 1.9"
Mounting:wall mounting, mounting
into patch-panels is possible
Display: System screen for system
visualisation, 16-segment display, 7-segment display, 8 symbols for system
status and operating control lamp
2.6"
66 mm
1.1"
28 mm
6.8"
172 mm
4.3"
110 mm
Operation:by 3 push buttons at the
front of the housing
Functions:Differential temperature
controller with optional add-on system
functions. Func ti on con trol, operating
hours counter for solar pump, tube
collector function, pump speed control, thermostat function, drainback
and booster option, and heat quantity
measurement.
Inputs: for 4 Pt1000 temperature
sensors
Outputs:2 semiconductor relays
6.1"
155 mm
1.9" / 47 mm
Bus:VBus
®
Powersupply: 100 ... 240 V~
Standbypowerconsumption:
< 1 W
Switchingcapacities:
R1: 1 (1) A 100 ... 240 V~
(semiconductor relay)
R2: 1 (1) A 100 ... 240 V~
(semiconductor relay)
3 |
DeltaSol® BS Plus
104 mm
1. Installation
1.1 Mounting
cover
cable conduits with strain
relief
5.1“
130 mm
lower fastening
display
upper fastening
fuse 4A
4.1“
push button
WARNING! Electric shock!
Opening the housing will expose
live parts!
Î Switch off power supply and discon-
nect the device from power supply
before opening the housing!
The unit must only be installed
• in a dry interior location
• in a non-hazardous location
• away from electromagnetic fields
The controller must additionally be supplied from a doublepole switch with contact gap of at least 3 mm [0.12“].
Route sensor cables and power supply cables separately.
Î Unscrew the cross-head screw from the cover and
remove it along with the cover from the housing
Î Mark the upper fastening point on the wall and drill
Î Fasten the enclosed wall plug and screw leaving the
head protruding
Î Hang the housing from the upper fastening point and
mark the lower fastening point through the hole in the
terminal box (centers 130 mm [5.1“])
Î Drill and insert the lower wall plug
Î Fasten the housing to the wall with lower fastening
screw and tighten
Î Complete wiring connections in accordance with termi-
nal allocations, see chap. 1.2 “Electrical connection”
Î Place the cover back onto the housing
Î Fasten the cover by means of the cross-head screw
1.2 Electrical connection
DE-45527 Hattingen
DeltaSol BS PlusV2
Made in Germany
Temp. Sensor Pt1000
S1S2S3
1 2
| 4
3 4 5 6
S4
VBus
7 8
9 10
®
VBus
ground terminal
CU 72091163 01
R1
IP 20
1 (1) A (1100 ... 240)V~
(1) A (100 ...240) V~
R2
141312
load terminalssensor terminal
power supply terminals
fuse
T4A
100 ... 240V~
50-60 Hz
ATTENTION! ESD damage!
Electrostatic discharge can lead to damage to electronic components!
LNR1NR2N
201918171615
Note:
The minimum pump speed must be set to 100 %
when auxiliary relays or valves are connected.
Î Take care to discharge properly
before touching the inside of the
device. To do so, touch a grounded
surface such as a radiator or tap!
Connecting the device to the mains supply must always be
the last step of the installation!
The power supply to the controller must be carried out via
an external power switch (last step!). The supply voltage
must be 100 ... 240 V~ (50 ... 60 Hz). Flexible cables must
be attached to the housing with the enclosed strain relief
and the corresponding screws.
The controller is equipped with two semiconductor relays, to which loads such as pumps, valves etc. can be
connected:
All Pt1000 temperature sensors are equipped with a
platinum measuring element in their tip. The electrical
resistance of the measuring element changes in relation
to the temperature (see table in chap. 5).
The difference between FKP and FRP type sensors only
lies in the cable insulation material. The insulation material
of FKP type sensor cables resists a higher temperature, so
that FKP type sensors should be used as collector sensors.
FRP type sensors are best used as reference sensors in
stores or pipes.
The controller is equipped with a RESOL VBus® for data
transfer with and energy supply to external modules. The
connection is carried out at the terminals marked “VBus”
(either polarity). One or more RESOL VBus® modules can
be connected via this data bus, such as
• GA3 large display, SD3 smart display
• DL2 datalogger
• VBus
®
/USB or VBus®/LAN interface adapter
• VBus®/PWM interface adapter
• AM1 alarm module
• WMZ calorimeter module
By means of a DL2 datalogger or an interface adapter, the
controller can be connected to a PC or a computer network. With the RESOL ServiceCenter Software (RSC) the
controller measurements can be read out, processed and
visualised. The software allows easy function control of the
system. For the remote parametrisation of the controller, a
special software tool will be available for download, soon.
5 |
DeltaSol® BS Plus
1.4 Terminal allocation in the different system layouts
System layout 1
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as reference
sensor for the store emergency shutdown option (OSEM).
If heat quantity measurement (OHQM) is activated, sensor
S4 has to be connected as return sensor.
If the drainback option (ODB) is activated, relay 2 can be
used to operate a booster pump by activating the booster
function (OBST).
ArrxSystem139
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
nMNxMinimum pump speed30 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
EMx
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
OHQMxOption heat quantity measurementOFF44
FMAXx*Maximum flow6.0 l44
MEDTx*Antifreeze type144
MED%x*Antifreeze concentration (only if MEDT = propylene or ethylene)45 %44
ODBxDrainback optionOFF45
tDTOx*ODB switch-on condition - time period60 s45
tFLLx*ODB filling time5.0 min45
tSTBx*ODB stabilisation time2.0 min45
OBSTs*Option booster functionOFF45
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Emergency temperature collector130 °C [270 °F]40
Emergency temperature collector if ODB is activated:95 °C [200 °F]40
OFF41
110 °C [230 °F]41
20.0 K [40.0 °Ra]
15.0 K [30.0 °Ra]
Version number
41
41
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
s*System-specific channel, only available if the corresponding option is activated
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
Heat exchange from store 1 to store 2 will be operated by
relay 2, if the temperature difference between sensors S3
and S4 is larger than or identical to the adjusted switch-on
temperature difference (DT3O), until the adjusted minimum
(MN3O) and maximum (MX3O) temperature thresholds
of the respective stores are reached. S3 can optionally be
used as reference sensor for the store emergency shutdown
option (OSEM).
Arr 2
R1
S1
Store 1
S2
S3
VBus
10
9
Store 2
S4
R2
Display Channels
ChannelDescriptionTerminalPage
INIT
FLL
STAB
COLxTemperature collectorS137
TST1xTemperature store 1 baseS237
TSTTxTemperature store 1 at the topS337
TST2xTemperature store 2 baseS437
n1 %xPump speed R1R138
n2 %xPump speed R2R238
h P1xOperating hours R1R138
h P2xOperating hours R2R238
TIMExTime-34
ArrxSystem239
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
n1MNxMinimum pump speed R130 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
n2MNsMinimum pump speed R230 %10
EMx
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
DT3OsSwitch-on temperature difference 3
DT3FsSwitch-off temperature difference 3
DT3SsNominal temperature difference 3
RIS3sRise control R2
MX3OsSwitch-on treshold for maximum temperature60.0 °C [140.0 °F]11
MX3FsSwitch-off treshold for maximum temperature58.0 °C [136.0 °F]11
MN3OsSwitch-on treshold for minimum temperature5.0 °C [40.0 °F]11
MN3FsSwitch-off treshold for minimum temperature10.0 °C [50.0 °F]11
ODBxDrainback optionOFF45
tDTOx*ODB switch-on condition - time period60 s45
tFLLx*ODB filling time5.0 min45
tSTBx*ODB stabilisation time2.0 min45
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
1.0 ... 20.0 K [2.0 ... 40.0°Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
6.0 K [12.0°Ra]
DT3F:
Switch-off temperature diff.
Adjustment range:
0.5 ... 19.5 K [1.0 ... 39.0°Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
4.0 K [8.0°Ra]
Pump speed control
DT3S:
Nominal temperature difference
Adjustment range:
1.5 ... 30.0 K [3.0 ... 60.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
10.0 K [20.0 °Ra]
RIS3:
Rise
Adjustment range:
1 ... 20 K[2 ... 40 °Ra]
in steps of 1 K [2 °Ra]
Factory setting: 2 K [4 °Ra]
The following adjustments are used for the specific function
in system layout 2.
Reference sensors for this function are S3 and S4.
In system layout 2 the controller is equipped with an additional differential control for heat exchange between two
stores. The basic differential function is adjusted using the
switch-on (DT3O) and switch-off (DT3F) temperature
differences.
When the temperature difference exceeds the switch-on
temperature difference, relay 2 switches on. If the temperature difference then falls below the adjusted switch-off
temperature difference, relay 2 switches off.
Note:
The switch-on temperature difference must be
at least 0.5 K [1 °Ra] higher than the switch-off
tempe rature difference.
Note:
For pump speed control of the heat exchange
pump, the operation mode of relay 2 (MAN2)
must be set to Auto.
When the switch-on temperature difference is reached, the
pump is activated at full speed for 10 seconds. Then, the speed
is reduced to the minimum pump speed value (n2MN).
If the temperature difference reaches the adjusted nominal
temperature difference (DT3S), the pump speed increases by
one step (10 %). If the difference increases by the adjustable rise
value, the pump speed increases by 10 % respectively until the
maximum pump speed of 100 % is reached. The response of
the controller can be adapted via the parameter RIS3.
Note:
The nominal temperature difference must be
at least 0.5 K [1 °Ra] higher than the switch-on
tempe rature difference.
Minimum pump speed
n2MN:
Pump speed control
Adjustment range: 30 ... 100
in steps of 5 %
Factory setting: 30
| 10
A relative minimum pump speed can be allocated to the
output R2 via the adjustment channel n2MN.
Note:
When loads which are not speed-controlled (e.g.
valves) are used, the value must be set to 100 % in
order to deactivate pump speed control.
0.0 ... 95.0 °C [30.0 ... 200.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting:
MX3O: 60.0 °C [140.0 °F]
MX3F: 58.0 °C [136.0 °F]
Minimum temperature limitation
MN3O/MN3F:
Minimum temperature limitation
Adjustment range:
0.0 ... 90.0 °C [30.0 ... 190.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting (Arr = 2 only):
MN3O: 5.0 °C [40.0 °F]
MN3F: 10.0 °C [50.0 °F]
Minimum and maximum temperature limits can be set for
the heat exchange function.
The maximum temperature limitation uses sensor 4 as
reference sensor.
The maximum temperature limitation function provides
a maximum tem perature setting, usually to reduce scald
risk in a storage store. If MX3O is exceeded, relay 2 is
switched off until the temperature at sensor 4 falls below
MX3F.
The minimum temperature limitation uses sensor 3 as
reference sensor.
The minimum temperature limitation function provides
a minimum tem perature setting for the heat source in
system layout 2. If the temperature at sensor 3 falls below
MN3O, relay 2 is switched off until the temperature at
sensor 3 exceeds MN3F.
Both switch-on and switch-off temperature differences
DT3O and DT3F are valid for the maximum and minimum
temperature limitation.
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
Sensor S3 is used for a thermostatic function, which operates relay 2 for afterheating or heat dump purposes, when
Arr 3
S1
the adjusted thermostat switch-on temperature (AH O) is
reached. This function can optionally be combined with up
to three adjustable time frames.
Sensor S3 can also be optionally used as a reference sensor
for the thermal disinfection function OTD or the store
emergency shutdown option (OSEM).
Sensor S4 can optionally be connected for measurement
purposes. If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor.
VBus
10
9
R1
S3
S4 / TR
S2
Display Channels
ChannelDescriptionTerminalPage
INIT
FLL
STAB
COLxTemperature collectorS137
TSTBxTemperature store 1 baseS237
TSTTxTemperature store 1 at the topS337
TDIS
S4xTemperature sensor 4S437
TRx*Temperature return sensorS437
n1 %xPump speed R1R138
h P1xOperating hours R1R138
h P2xOperating hours R2R238
kWh
MWh
CDIS
SDIS
DDIS
TIMExTime-34
ArrxSystem339
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
n1MNxMinimum pump speed R130 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
EMx
OCCxOption collector coolingOFF41
CMXx*Maximum collector temperature110 °C [230 °F]41
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference20.0 K [40.0 °Ra]41
DTCFx*Cooling switch-off temperature difference15.0 K [30.0 °Ra]41
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
OHQMxOption heat quantity measurementOFF44
FMAXx*Maximum flow6.0 l44
MEDTx*Antifreeze type144
MED%x*Antifreeze concentration45 %44
AH OsSwitch-on temp. for thermostat 140 °C [110 °F]14
AH FsSwitch-off temp. for thermostat 145 °C [120 °F]14
t1 OsSwitch-on time 1 thermostat00:0014
t1 FsSwitch-off time 1 thermostat00:0014
t2 OsSwitch-on time 2 thermostat00:0014
t2 FsSwitch-off time 2 thermostat00:0014
t3 OsSwitch-on time 3 thermostat00:0014
t3 FsSwitch-off time 3 thermostat00:0014
ODBxDrainback optionOFF45
tDTOx*ODB switch-on condition - time period60 s45
tFLLx*ODB filling time5.0 min45
tSTBx*ODB stabilisation time2.0 min45
OTDsOption thermal disinfectionOFF15
PDISs*Monitoring period01:0015
DDISs*Heating period01:0015
TDISs*Disinfection temperature60 °C [140 °F]15
SDISs*Starting time00:0015
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Emergency temperature collector130 °C [270 °F]40
Emergency temperature collector if ODB is activated:95 °C [200 °F]40
Version number
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
sChannel is specifically available in this system layout
In order to block the thermostat function for a certain
period, there are three time frames t1 ... t3. If the function
should be active between 6:00 and 9:00, set t1 O to 6:00
and t1F to 9:00.
If all time frames are set to 00:00 o’clock, the thermostat
function is continuously activated (factory setting).
Disinfection temperature
Adjustment range:
0 ... 95 °C [30 ... 200 °F]
in steps of 2 °C [2 °F]
Factory setting:
60 °C [140 °F]
This function is used for protecting the upper store zone
against Legionella by activating the afterheating.
Reference sensor for the thermal disinfection is S3!
Î To activate the function, select “On” in the OTD
channel.
For thermal disinfection, the temperature in the upper
DHW store zone has to be monitored. This protection is
ensured when, during the monitoring period (PDIS), the
disinfection temperature (TDIS) is continuously exceeded
for the entire heating period (DDIS). S3 is used as the
reference sensor and displayed as TSTT.
If OTD is activated, PDIS will start as soon as the temperature at S3 falls below TDIS. The display channel CDIS
appears, counting backwards the remaining time of PDIS.
If, during the monitoring period, the temperature at S3
exceeds TDIS continuously for the duration of DDIS,
thermal disinfection is considered complete and a new
monitoring period begins.
If CDIS counts down to 00:00, relay 2 will be operated
in order to use the afterheating for thermal disinfection.
CDIS will then be replaced with a display channel DDIS
showing the adjusted heating period. DDIS will start counting down the heating period as soon as TDIS is exceeded
at S3. As long as DDIS is active, the temperature at S3 will
be displayed as TDIS instead of TSTT.
If, during DDIS, the temperature at S3 exceeds TDIS by
more than 5 K [10 °Ra], relay 2 is switched off until the
temperature falls below TDIS + 2 K [4 °Ra].
If, during DDIS, the temperature at S3 falls below TDIS,
the heating period will restart. DDIS can only be completed when TDIS is exceeded without interruption.
Due to the flexible control logic, the exact time of thermal
disinfection is not predictable. In order to set a fixed time
for the disinfection to be run, the starting delay SDIS must
be employed:
Thermal disinfection with starting delay
SDIS
Starting time
Adjustment range:
00:00 ... 24:00 (o´clock)
in steps of: 00:01
Factory setting: 00:00
When a starting time for thermal disinfection with starting
delay is adjusted in SDIS, the thermal disinfection will be
delayed until that time, even after the CDIS has counted
down to 00:00. If CDIS ends, for example, at 12:00 o‘clock,
and SDIS has been set to 18:30, relay 2 will be operated
with a delay of 6.5 hours at 18:30 instead of 12:00.
During the waiting time, SDIS is displayed with the adjusted
starting time (flashing).
If, during the waiting time, the temperature at S3 exceeds
TDIS for the adjusted heating period DDIS, thermal
disinfection is considered complete and a new monitoring
period begins.
If the starting time is adjusted to 00:00 (factory setting), the
delay function is inactive.
Upon delivery, OTD is deactivated. The adjustment values
PDIS, TDIS, DDIS and SDIS are displayed after the
option has been activated. After the thermal disinfection
function has been completed, the values will be “hidden”
and the monitoring period will be displayed.
15 |
DeltaSol® BS Plus
System layout 4
The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pump will be operated by relay 1, and the respective
store zone will be loaded until the switch-off temperature
differences (DT1F / DT2F) or the maximum store tempera-
Arr 4
S1
tures (S1MX / S2MX) are reached. The priority logic causes
priority loading of the upper zone of the store, if possible.
The 3-way-valve will be operated by relay 2 then.
Sensor S4 can optionally be connected for measurement
purposes.
If heat quantity measurement (OHQM) is activated, sensor
S4 has to be connected as return sensor.
VBus
10
9
R1
R2
S4 / TR
Display Channels
ChannelDescriptionTerminalPage
COLxTemperature collectorS137
TSTBxTemperature store 1 baseS237
TSTTxTemperature store 1 at the topS337
S4xTemperature sensor 4S437
TRx*Temperature return sensorS437
n %xPump speed relayR138
hP1xOperating hours R1R138
hP2xOperating hours R2R238
kWh
MWh
TIMExTime-34
ArrxSystem439
nMNxMinimum pump speed30 %
DT1OxSwitch-on temperature difference 16.0 K [12.0 °Ra]39
DT1FxSwitch-off temperature difference 14.0 K [8.0 °Ra]39
DT1SxNominal temperature difference 110.0 K [20.0 °Ra]39
RIS1xRise control R12 K [4 °Ra]
S1 MXxMaximum temperature store 160 °C [140 °F]40
DT2OxSwitch-on temperature difference 26.0 K [12.0 °Ra]39
DT2FxSwitch-off temperature difference 24.0 K [8.0 °Ra]39
DT2SxNominal temperature difference 210.0 K [20.0 °Ra]39
RIS2xRise control R22 K [4 °Ra]
S2MXxMaximum temperature store 260 °C [140 °F]40
EMxEmergency temperature collector130 °C [270 °F]40
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
PRIOxPriority243
tLBxBreak time2 min43
tRUNxCirculation runtime15 min43
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
OHQMxOption heat quantity measurementOFF44
FMAXx*Maximum flow6.0 l44
MEDTx*Antifreeze type144
MED%x*Antifreeze concentration (only if MEDT = propylene or ethylene)45 %44
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Version number
OFF41
110 °C [230 °F]41
20.0 K [40.0 °Ra]
15.0 K [30.0 °Ra]
39
39
39
41
41
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pump will be operated by relay 1, and the respective
store will be loaded until the switch-off temperature differences (DT1F / DT2F) or the maximum store temperatures
Arr 5
S1
(S1MX / S2MX) are reached. The priority logic causes priority loading of store 1, if possible. For loading store 2 the
3-way-valve will be operated by relay 2.
Sensor S4 can optionally be connected for measurement
purposes.
If heat quantity measurement (OHQM) is activated, sensor
S4 has to be connected as return sensor.
VBus
10
9
R2
Store 1
R1
S4 / TR
S2S3
Display Channels
ChannelDescriptionTerminalPage
COLxTemperature collectorS137
TST1xTemperature store 1 baseS237
TST2xTemperature store 2 baseS337
S4xTemperature sensor 4S437
TRx*Temperature return sensorS437
n %xPump speed relayR138
hP1xOperating hours R1R138
hP2xOperating hours R2R238
kWh
MWh
TIME
ArrxSystem539
nMNxMinimum pump speed30 %
DT1OxSwitch-on temperature difference 16.0 K [12.0 °Ra]39
DT1FxSwitch-off temperature difference 14.0 K [8.0 °Ra]39
DT1SxNominal temperature difference 110.0 K [20.0 °Ra]39
RIS1xRise control R12 K [4 °Ra]
S1 MXxMaximum temperature store 160 °C [140 °F]40
DT2OxSwitch-on temperature difference 26.0 K [12.0 °Ra]39
DT2FxSwitch-off temperature difference 24.0 K [8.0 °Ra]39
DT2SxNominal temperature difference 210.0 K [20.0 °Ra]39
RIS2xRise control R22 K [4 °Ra]
S2MXxMaximum temperature store 260 °C [140 °F]40
EMxEmergency temperature collector130 °C [270 °F]40
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
PRIOxPriority143
tLBxBreak time2 min43
tRUNxCirculation runtime15 min43
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
OHQMxOption heat quantity measurementOFF44
FMAXx*Maximum flow6.0 l44
MEDTx*Antifreeze type144
MED%x*Antifreeze concentration (only if MEDT = propylene or ethylene)45 %44
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Version number
OFF41
110 °C [230 °F]41
20.0 K [40.0 °Ra]
15.0 K [30.0 °Ra]
39
39
39
41
41
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pumps will be operated by relay 1 and / or relay 2,
and the respective store will be loaded until the switch-off
temperature differences (DT1F / DT2F) or the maximum
Arr 6
S1
S4
store temperatures (S1MX / S2MX) are reached. The priority logic causes priority loading of the selected store (PRIO),
if possible. Loading both stores simultaneously is possible
as well (PRIO = 0).
Sensor S4 can optionally be connected for measurement
purposes or used as reference sensor for the store emergency shutdown option (OSEM).
VBus
10
9
R1R2
Store 1
S2
Display Channels
ChannelDescriptionTerminalPage
COLxTemperature collectorS137
TST1xTemperature store 1 baseS237
TST2xTemperature store 2 baseS337
S4xTemperature sensor 4S437
TSTTx*Temperature store at the topS437
n1 %xPump speed R1R138
n2 %xPump speed R2R238
h P1xOperating hours R1R138
h P2xOperating hours R2R238
TIMExTime-34
ArrxSystem639
DT1OxSwitch-on temperature difference 16.0 K [12.0 °Ra]39
DT1FxSwitch-off temperature difference 14.0 K [8.0 °Ra]39
DT1SxNominal temperature difference 110.0 K [20.0 °Ra]39
RIS1xRise control R12 K [4 °Ra]39
n1MNxMinimum pump speed R130 %39
S1 MXxMaximum temperature store 160 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
DT2OxSwitch-on temperature difference 26.0 K [12.0 °Ra]39
DT2FxSwitch-off temperature difference 24.0 K [8.0 °Ra]39
DT2SxNominal temperature difference 210.0 K [20.0 °Ra]39
RIS2xRise control R22 K [4 °Ra]39
n2MNxMinimum pump speed R230 %39
S2MXxMaximum temperature store 260 °C [140 °F]40
EMxEmergency temperature collector130 °C [270 °F]40
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
PRIOxPriority143
tLBxBreak time2 min43
tRUNxCirculation runtime15 min43
DTSEx*Spread temperature difference40 K [70 °Ra]43
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
The controller calculates the temperature differences
between the collector sensors S1 and S3 and the store
sensor S2. If the differences are larger than or identical to
the adjusted switch-on temperature difference (DT O), the
respective solar pump will be operated by relay 1 and / or
relay 2, and the store will be loaded until the switch-off
temperature difference (DT F) or the maximum store temperature (S MX) is reached.
Sensor S4 can optionally be connected for measurement
purposes or used as reference sensor for the store emergency shutdown option (OSEM).
ArrxSystem739
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R1 / R22 K [4 °Ra]39
n1MNxMinimum pump speed R130 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
n2MNxMinimum pump speed R230 %39
EM1xEmergency temperature collector130 °C [270 °F]40
EM2xEmergency temperature collector130 °C [270 °F]40
OCC1xOption collector cooling collector 1
CMX1x*Maximum temperature collector 1
OCC2xOption collector cooling collector 2OFF41
CMX2x*Maximum temperature collector 2110 °C [230 °F]41
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCN1xOption minimum limitation collector 1OFF42
CMN1x*Minimum temperature collector 110 °C [50 °F]42
OCN2xOption minimum limitation collector 2OFF42
CMN2x*Minium temperature collector 210 °C [50 °F]42
OCF1xOption antifreeze collector 1OFF42
CFR1x*Antifreeze temperature collector 14.0 °C [40.0 °F]42
OCF2xOption antifreeze collector 2OFF42
CFR2x*Antifreeze temperature collector 24.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
A solid fuel boiler will be operated by relay 2, if the temperature difference between sensors S4 and S3 is larger than or
identical to the adjusted switch-on temperature difference
(DT3O), until the adjusted minimum (MN3O) and maximum
(MX3O) temperature thresholds of the fuel boiler and the
store are reached. S3 can optionally be used as reference
sensor for the store emergency shutdown option (OSEM).
Arr 8
R1
S1
S2
S3
VBus
10
9
S4
R2
Display Channels
ChannelDescriptionTerminalPage
INIT
FLL
STAB
COLxTemperature collectorS137
TSTBxTemperature store 1 baseS237
TSTTxTemperature store 1 at the topS337
TSFBxTemperature solid fuel boilerS437
n1 %xPump speed R1R138
n2 %xPump speed R2R238
h P1xOperating hours R1R138
h P2xOperating hours R2R238
TIMExTime-34
ArrxSystem839
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
n1MNxMinimum pump speed R130 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
n2MNsMinimum pump speed R230 %26
EMx
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
DT3OsSwitch-on temperature difference 3
DT3FsSwitch-off temperature difference 3
DT3SsNominal temperature difference 3
RIS3sRise control R2
MX3OsSwitch-on treshold for maximum temperature60.0 °C [140.0 °F]27
MX3FsSwitch-off treshold for maximum temperature58.0 °C [136.0 °F]27
MN3OsSwitch-on treshold for minimum temperature60.0 °C [140.0 °F]27
MN3FsSwitch-off treshold for minimum temperature65.0 °C [150.0 °F]27
ODBxDrainback optionOFF45
tDTOx*ODB switch-on condition - time period60 s45
tFLLx*ODB filling time5.0 min45
tSTBx*ODB stabilisation time2.0 min45
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
1.0 ... 20.0 K [2.0 ... 40.0°Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
6.0 K [12.0°Ra]
DT3F:
Switch-off temperature diff.
Adjustment range:
0.5 ... 19.5 K [1.0 ... 39.0°Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
4.0 K [8.0°Ra]
Pump speed control
DT3S:
Nominal temperature difference
Adjustment range:
1.5 ... 30.0 K [3.0 ... 60.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
10.0 K [20.0 °Ra]
RIS3:
Rise
Adjustment range:
1 ... 20 K [2 ... 40 °Ra]
in steps of 1 K [2 °Ra]
Factory setting: 2 K [4 °Ra]
The following adjustments are used for the specific functions
in system layout 8.
Reference sensors for this function are S4 and S3.
In system layout 8, the controller is equipped with an additional differential control for heat exchange from a solid
fuel boiler (e.g. woodstove). The basic differential function
is adjusted using the switch-on (DT3O) and switch-off
(DT3F) temperature differences.
When the switch-on difference is reached, relay 2 switches on. When the temperature difference falls below
the adjusted switch-off temperature difference, relay 2
switches off.
Note:
The switch-on temperature difference must be
at least 0.5 K [1 °Ra] higher than the switch-off
tempe rature difference.
Note:
For pump speed control of the solid fuel boiler
pump, the operation mode of relay 2 (MAN2)
must be set to Auto.
When the switch-on temperature difference is reached, the
pump is activated at full speed for 10 seconds. Then, the speed
is reduced to the minimum pump speed value (n2MN).
If the temperature difference reaches the adjusted nominal
temperature difference (DT3S), the pump speed increases by
one step (10 %). If the difference increases by the adjustable rise
value, the pump speed increases by 10 % respectively until the
maximum pump speed of 100 % is reached. The response of
the controller can be adapted via the parameter RIS3.
Note:
The nominal temperature difference must be
at least 0.5 K [1 °Ra] higher than the switch-on
tempe rature difference.
Minimum pump speed
n2MN:
Pump speed control
Adjustment range: 30 ... 100
in steps of 5 %
Factory setting: 30
| 26
A relative minimum pump speed can be allocated to the
output R2 via the adjustment channel n2MN.
Note:
When loads which are not speed-controlled (e.g.
valves) are used, the value must be set to 100 % in
order to deactivate pump speed control.
0.0 ... 95.0 °C [30.0 ... 200.0 °F]
in steps of 0.5 °C [1 °F]
Factory setting:
MX3O: 60.0 °C [140.0 °F]
MX3F: 58.0 °C [136.0 °F]
Minimum temperature limitation
MN3O/MN3F:
Minimum temperature limitation
Adjustment range:
0.0 ... 90.0 °C [30.0 ... 190.0 °F]
in steps of 0.5 °C [1 °F]
Factory setting (Arr = 8 only):
MN3O: 60.0 °C [140.0 °F]
MN3F: 65.0 °C [150.0 °F]
Minimum and maximum temperature limits can be set for
the solid fuel boiler.
The maximum temperature limitation function provides a
maximum tem perature setting, usually to reduce scald risk
in a storage store. If MX3O is exceeded, relay 2 is switched off until the sensor falls below MX3F. TIn Arr 8, this
function uses sensor 3 as reference sensor.
The minimum temperature limitation uses sensor 4 as
reference sensor.
The minimum temperature limitation function provides a
minimum tem perature setting for the solid fuel boiler in
system layout 8. If the temperature at sensor 4 falls below
MN3O, relay 2 is switched off until the temperature exceeds MN3Fagain.
Both switch-on and switch-off temperature differences
DT3O and DT3F are valid for the maximum and minimum
temperature limitation.
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
A heating circuit return preheating will be operated by
relay 2, if the temperature difference between sensors S3
and S4 is larger than or identical to the adjusted switch-on
temperature difference (DT3O). For this purpose, relay 2
will operate the 3-way-valve. S3 can optionally be used as
reference sensor for the store emergency shutdown option
(OSEM).
Arr 9
R1
S1
S2
S3
S4
R2
VBus
9
10
Display Channels
ChannelDescriptionTerminalPage
INIT
FLL
STAB
x*
ODB initialisation active-37
x*
ODB filling time active-37
x*
ODB stabilisation in progress-37
COLxTemperature collectorS137
TSTBxTemperature store 1 baseS237
TSTTxTemperature store 1 at the topS337
TRETxTemperature heating circuitS438
n %xPump speed relayR138
hP1xOperating hours R1R138
hP2xOperating hours R2R238
TIMExTime-34
ArrxSystem939
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
nMNxMinimum pump speed30 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
EMx
OCCxOption collector cooling
CMXx*Maximum collector temperature
OSYCxOption system coolingOFF41
DTCOx*Cooling switch-on temperature difference
DTCFx*Cooling switch-off temperature difference
OSTCxOption store coolingOFF42
OHOLx*Option holiday coolingOFF42
THOLx*Holiday cooling temperature40 °C [110 °F]42
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
DT3OsSwitch-on temperature difference 3
DT3FsSwitch-off temperature difference 3
ODBxDrainback optionOFF45
tDTOx*ODB switch-on condition - time period60 s45
tFLLx*ODB filling time5.0 min45
tSTBx*ODB stabilisation time2.0 min45
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Emergency temperature collector130 °C [270 °F]40
Emergency temperature collector if ODB is activated:95 °C [200 °F]40
OFF41
110 °C [230 °F]41
20.0 K [40.0 °Ra]
15.0 K [30.0 °Ra]
6.0 K [12.0 °Ra]39
4.0 K [8.0 °Ra]39
Version number
41
41
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
sChannel is specifically available in this system layout
The controller calculates the temperature difference
between collector sensor S1 and store sensor S2. If the
difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be
operated by relay 1, and the store will be loaded until the
switch-off temperature difference (DT F) or the maximum
store temperature (S MX) is reached.
If the maximum collector temperature (CMX) is reached, the
solar pump will be operated by relay 1 and the 3-way-valve
Arr 10
S1
will be operated by relay 2 in order to direct the surplus
energy to a heat dump. For security purpose this will be
carried out only if the store temperature is below the nonadjustable emergency shutdown of 95 °C [200 °F].
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as reference
sensor for the store emergency shutdown option (OSEM).
If heat quantity measurement (OHQM) is activated, sensor
S4 has to be connected as return sensor.
VBus
10
9
R2
S3
R1
S4 / TR
Display Channels
ChannelDescriptionTerminalPage
COLxTemperature collectorS137
TSTxTemperature storeS237
S3xTemperature sensor 3S337
TSTTxTemperature store at the topS337
S4xTemperature sensor 4S437
TR
n %xPump speed relayR130
h P1xOperating hours R1R138
h P2xOperating hours R2R238
kWhx*Heat quantity kWh-38
MWhx*Heat quantity MWh-38
TIMExTime-34
ArrxSystem1039
DT OxSwitch-on temperature difference6.0 K [12.0 °Ra]39
DT FxSwitch-off temperature difference4.0 K [8.0 °Ra]39
DT SxNominal temperature difference10.0 K [20.0 °Ra]39
RISxRise control R12 K [4 °Ra]39
nMNxMinimum pump speed30 %39
S MXxMaximum store temperature60 °C [140 °F]40
OSEMxOption store emergency shutdownOFF40
EMxEmergency temperature collector130 °C [270 °F]40
CMXsMaximum collector temperature
OCNxOption minimum limitationOFF42
CMNx*Minimum collector temperature10 °C [50 °F]42
OCFxOption antifreezeOFF42
CFRx*Antifreeze temperature4.0 °C [40.0 °F]42
O TCxOption tube collectorOFF44
TCSTx*OTC starting time07:0044
TCENx*OTC ending time19:0044
TCRUx*OTC runtime30 s44
TCINx*OTC standstill interval30 min44
OHQMxOption heat quantity measurementOFF44
FMAXx*Maximum flow6.0 l44
MEDTx*Antifreeze type144
MED%x*Antifreeze concentration (only if MEDT = propylene or ethylene)45 %44
MAN1xManual operation R1Auto46
MAN2xManual operation R2Auto46
ADA1xHE pump controlOFF46
LANGxLanguageEn46
UNITxTemperature unit°C46
RESExReset - back to factory settings46
####
W005
Version number
110 °C [230 °F]41
Legend:
SymbolSpecification
xChannel is available
x*Channel is available if the corresponding option is activated.
sChannel is specifically available in this system layout
The controller is operated via three push buttons below
the display.
Button1 is used for scrolling forward through the indication menu or to increase the adjustment values. Button2
is used for scrolling backward and reducing values. Button3 is used for selecting channels and confirming adjustments.
During normal operation, only the display channels are
shown.
Î Scroll through the display channels by pressing buttons
1 and 2
Accessingtheadjustmentchannels:
Î Scroll down in the display menu and press button 1 for
approx. two seconds after you have reached the last
display item.
When an adjustment value is shown on the display,
is indicated to the right of the channel name.
Î Press button 3 in order to access the adjustment mode
starts flashing.
Î Adjust the value using buttons 1 and 2Î Briefly press button 3,
permanently appears,the
adjusted value will be saved.
The system monitoring display consists of three blocks:
channel display,tool bar and system screen (active
system layout).
The channel display consists of two lines. The upper line
is an alpha-numeric 16-segment display (text display) for
displaying channel names and menu items. In the lower
7-segment display, the channel values and the adjustment
parameters are displayed.
Temperatures are either indicated in °C or °F, whereas temperature differences are indicated in K or °Ra respectively.
The additional symbols of the tool bar indicate the current
system status.
The system screen (active system layout) shows the system
selected on the controller. It consists of several system
component symbols, which are – depending on the current
status of the system – either flashing, permanently shown
or hidden.
collector 1
valve
pumps
sensors
store heat exchanger
Collectors
with collector sensor
collector 2
store
store sensor base
store sensor
at the top
heating circuit
store 2 or afterheating (with
an additional symbol)
heating circuit
return sensor
valve
sensor
additional symbol for
operation of the burner
afterheating with burner
symbol
Temperature sensor
Heatingcircuit
Stores 1 and 2
with heat exchanger
Pump
3-way valve
the flow direction or the
actual switching position is
shown
• Pumps are flashing when the corresponding relay is switched on
• Sensor symbols are flashing if the corresponding sensor
display channel is selected
• Sensors are flashing quickly in the case of a sensor fault
• Burner symbol is flashing if the afterheating is active
green: everything OK
red/green flashing: initialisation phase
red flashing: manual operation
sensor fault
(sensor symbol is flashing quickly)
33 |
DeltaSol® BS Plus
3. Commissioning
2
3
1
(OK)
The three push buttons of the BS Plus controller
LANG:
Language selection
Selection: dE, En, Fr
Factory setting: En
Î Establish the power supply
During a short initialisation phase, the operating control
lamp flashes red and green.
When the controller is commissioned for the first time or
after a reset, it will run a commissioning menu. The commissioning menu leads the user through the most important adjustment channels needed for operating the system.
Operatingthecommissioningmenu:
Î Enter the channel by pressing button 3
The
The
The commissioning menu consists of the following 6
channels:
1. Language
• dE : German
• En : English
• Fr : French
symbol flashes.
Î Adjust the value by pressing buttons 1 and 2
Î Save the adjustment by pressing button 3 again
symbol stops flashing.
Î Press button 1 or 2 to switch to the next or previous
channel
Î Adjust the desired menu language in this channel
UNIT:
Temperature unit selection
Selection: °C, °F
Factory setting: °C
TIME:
Real time adjustment
2. Unit
Î Adjust the unit in which temperatures and temperature
differences shall be displayed
3. Time
Î Adjust the current time for the real time clock
The hours and minutes have to be adjusted separately, first
the hours, then the minutes.
Î Adjust the desired system layout of your solar thermal
system
For a detailed description of the different system layouts
selectable, see chapter 1.4.
Overviewofsystemlayouts:
Arr 1 : standard solar system layout
Arr 2 : solar system layout with heat exchange
Arr 3 : solar system layout with afterheating
Arr 4 : solar system layout with vertical store charging
Arr 5 : 2-store solar system layout with valve logic
Arr 6 : 2-store solar system layout with pump logic
Arr 7Arr 8
Arr 9Arr 10
Securityenquiry:Î To confirm the security enquiry, press button 3
Arr 7 : solar system layout with 2 collectors and 1 store
Arr 8 : solar system layout with afterheating by solid fuel
boiler
Arr 9 : solar system layout with heating circuit return
preheating
Arr 10: standard solar system layout with heat dump
If the system layout selection is changed later on, any
previous adjustments which have been made in the other
channels will be lost. Therefore, changing the system layout
is always followed by a security enquiry.
Maximum store temp.
Adjustment range:
4 ... 95 °C [40 ... 200 °F]
Arr 10:
4 ... 90 °C [40 ... 190 °F]
in steps of 1 °C [2 °F]
Factory setting: 60 °C [140 °F]
nMN, n1MN, n2MN:
Pump speed control
Adjustment range: 30 ... 100
in steps of 5 %
Factory setting: 30
Conrmationenquiry
5. Maximum store temperature
Î Adjust the desired maximum store temperature
Note:
The controller is also equipped with a nonadjustable emergency shutdown function, which
will shut the system down if the store reaches
95 °C [200 °F].
6. Minimum pump speed
Î Adjust a minimum speed for the pump
Note:
If loads which are not speed-controlled (e.g.
valves) are used, the value must be set to 100 %
for the respective relay.
Completing the commissioning menu
After the last channel of the commissioning menu has been
adjusted and confirmed, the controller asks for confirmation of the adjustments.
Î To confirm the adjustments made in the commissioning
menu, press button 3
Now the controller is ready for operation with typical
settings to suit the selected system layout.
The settings made in the commissioning menu can be
changed later on in the corresponding adjustment channels. Additional functions and options can of course be
individually adjusted as well (see chap. 4.2).
InitialisationIndicates the time adjusted in tDTO, running backwards.
INIT:
ODB initialisation active
FillingtimeIndicates the time adjusted in tFLL, running backwards.
FLL:
ODB filling time active
StabilisationIndicates the time adjusted in tSTB, running backwards.
STAB:
Stabilisation
Note:
The displayed values and adjustment channels
depend on which system layout, which options
and functions have been selected. Only values
and adjustment channels available for the individual settings selected will appear in the menu.
Indication of collector temperaturesIndicates the current collector temperature.
COL,COL1,COL2:
Collector temperature
Display range:
-40 ... +260 °C [-40 ... +500 °F]
Indication of store temperaturesIndicates the current store temperature.
TST,TSTB,TSTT,
TST1,TST2,TDIS:
Store temperatures
Display range:
-40 ... +260 °C [-40 ... +500 °F]
Indication of sensors 3 and 4Indicates the current temperature of the corresponding
S3,S4:
Sensor temperatures
Display range:
-40 ... +260 °C [-40 ... +500 °F]
• COL : collector temperature (1-collector system)
• COL1 : collector temperature 1
• COL2 : collector temperature 2
• TST : store temperature (1-store system)
• TSTB : store temperature base
• TSTT : store temperature top
• TST1 : temperature store 1 (2-store-systems)
• TST2 : temperature store 2 (2-store-systems)
• TDIS : thermal disinfection temperature
(Arr = 3 only; replaces TSTT if, during thermal disinfection, the heating period DDIS is active)
additional sensor (without control function).
• St: temperature sensor 4
Note:
S3 and S4 will only be indicated if the temperature
sensors are connected.
Indication of other temperaturesIndicates the current temperature of the corresponding
kWh/MWh: Heat quantity
in kWh / MWh
Display channel
CDIS
Countdown of monitoring
period
Display range:
0 ... 30:0 ... 24 (dd:hh)
SDIS
Starting time display
Display range:
00:00 ... 24:00 (hh:mm)
DDIS
Heating period display
Display range:
00:00 ... 24:00 (hh:mm)
TIME
Indicates the current pump speed of the corresponding pump.
• n % : current pump speed (1-pump system)
• n1 % : current pump speed pump 1
• n2 % : current pump speed pump 2
Indicates the energy gained in heat quantity – only available if
heat quantity measurement (OHQM) is activated.
The flow rate as well as the reference sensors S1 (flow) and
S4 (return) are used for calculating the heat quantity supplied.
It is shown in kWh in the channel kWh and in MWh in the
channel MWh. The overall heat quantity results from the
sum of both values.
The accumulated heat quantity can be set back to 0. As soon
as one of the display channels of the heat quantity is selected,
the
The display symbol will flash and the heat quantity value
will be set to 0.
In order to interrupt the RESET-process, do not press a
button for about five seconds. The display returns to the
display mode.
If the thermal disinfection option (OTD) is activated and
the monitoring period is in progress, the remaining monitoring time will be displayed as CDIS (in days and hours)
and counted backwards.
If the thermal disinfection option (OTD) is activated and
a starting delay time has been adjusted, the adjusted delay
time is displayed (flashing) in this channel.
If the thermal disinfection option (OTD) is activated and
the heating period is in progress, the remaining time of the
heating period is displayed (in hours and minutes) in this
channel, counting backwards.
Indicates the current time.
symbol is permanently shown on the display.
Î Press button 3 for about two seconds in order to access
the RESET mode of the counter.
Î Confirm the reset with button 3 in order to finish the
reset.
Î Press button 3 for two seconds to adjust the hours
Î Set the hours by pressing buttons 1 and 2
Î Press button 3 again to adjust the minutes
Î Set the minutes by pressing buttons 1 and 2
Î Press button 3 in order to save the adjustments
Operating hours counter
h P / h P1 /hP2:
Operating hours counter
Display channel
| 38
The operating hours counter accumulates the solar operating hours of the respective relay (h P / h P1 / h P2). Full
hours are displayed.
The accumulated operating hours can be set back to zero.
As soon as one operating hours channel is selected, the
symbol
Î In order to access the RESET-mode of the counter,
press button 3 for approx. two seconds.
The display symbol will flash and the operating hours
will be set to 0.
Î Confirm the reset with button 3 in order to finish the
reset.
In order to interrupt the RESET-process, do not press a
button for about five seconds. The display returns to the
display mode.
1.0 ... 20.0 K [2.0 ... 40.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
6.0 K [12.0 °Ra]
DTF/ DT1F/ DT2F/DT3F:
Switch-off temperature diff.
Adjustment range:
0.5 ... 19.5 K [1.0 ... 39.0°Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
4.0 K [8.0°Ra]
In this channel, a pre-defined system layout can be selected.
Each system layout has a set of pre-programmed settings
that can be individually changed.
If the system layout selection is changed later on, all adjustments made in the other channels will be lost. Therefore,
changing the system layout is always followed by a security
enquiry.
The controller works as a standard differential controller. If
the switch-on difference is reached, the pump is activated.
When the temperature difference falls below the adjusted
switch-off temperature difference, the respective relay
switches off.
Note:
The switch-on temperature difference must
be at least 0.5 K [1 °Ra] higher than the switchoff temperature difference.
Note:
When the drainback option ODB is activated,
the temperature differences DT O, DTF and
DT S are set to a fixed adjustment:
DT O = 10 K [20 °Ra]
DT F = 4 K [8 °Ra]
DT S = 15 K [30 °Ra]
Previous adjustments made in these channels will
be overridden and may have to be entered again
if ODB is deactivated later on.
Pump speed control
DT S / DT1S / DT2S / DT3S:
Nominal temperature difference
Adjustment range:
1.5 ... 30.0 K [3.0 ... 60.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
10.0 K [20.0 °Ra]
RIS / RIS1 / RIS2 / RIS3:
Rise
Adjustment range:
1 ... 20 K [2 ... 40 °Ra]
in steps of 1 K [2 °Ra]
Factory setting: 2 K [4 °Ra]
Minimum pump speed
nMN, n1MN, n2MN:
Pump speed control
Adjustment range: 30 ... 100 %
in steps of 5 %
Factory setting: 30 %
When the switch-on temperature difference is reached,
the pump is activated at full speed for 10 seconds. Then, the
speed is reduced to the minimum pump speed value (factory
setting = 30 %).
If the temperature difference reaches the adjusted nominal
temperature difference, the pump speed increases by one
step (10 %). If the difference increases by the adjustable rise
value, the pump speed increases by 10 % respectively until the
maximum pump speed of 100 % is reached. The response of
the controller can be adapted via the parameter “Rise”.
A relative minimum pump speed can be allocated to the
outputs R1 and R2 via the adjustment channels nMN, n1MN and n2MN.
Note:
For pump speed control, the operation mode
of the corresponding relay must be set to Auto
(adjustment channel MAN1 / MAN2)
Note:
The nominal temperature difference must be
at least 0.5 K [1 °Ra] higher than the switch-on
tempe rature difference.
Note:
When loads which are not speed-controlled (e.g.
valves) are used, the value must be set to 100 % in
order to deactivate pump speed control.
39 |
DeltaSol® BS Plus
Maximum store temperature
S MX / S1MX / S2MX:
Maximum store temp.
Adjustment range:
4 ... 95 °C [40 ... 200 °F]
Arr 10:
4 ... 90 °C [40 ... 190 °F]
in steps of 1 °C [2 °F]
Factory setting: 60 °C [140 °F]
Store emergency shutdown option
OSEM
Store emergency shutdown
option
Adjustment range: OFF / ON
Factory setting: OFF
Once the adjusted maximum temperature is exceeded,
the solar pump is switched off and further loading of the
store is prevented to reduce scald risk or system damage.
A fixed hysteresis of 2 K [4 °Ra] is set for the maximum
store temperature.
When the temperature at the corresponding sensor exceeds
the adjusted maximum store temperature, the
shown on the display.
Note:
If the collector cooling or the system cooling
function is activated, the adjusted store temperature may be overridden. In order to prevent
system damage, the controller is also equipped
with an integrated store emergency shutdown
if the store reaches 95 °C [200 °F].
This option is used for activating the integrated store
emergency shutdown for an upper store sensor. If the
temperature at the reference sensor exceeds 95 °C, store
1 will be blocked and loading will be stopped until the
temperature falls below 90 °C.
Note:
Sensor S3 ist used as the reference sensor in
the system layouts 1, 2, 3, 8, 9 and 10. In the
system layouts 6 and 7, sensor S4 is used as the
reference sensor.
This option is not available in system layouts
4 and 5.
symbol is
Collector temperature limitation
Emergency shutdown of the collector
EM / EM1 / EM2:
Collector temperature limitation
Adjustment range:
80 ... 200 °C
[170 ... 390 °F]
in steps of 1 °C [2 °F]
Factory setting:
130 °C [270 °F]
If the adjusted collector emergency shutdown temperature
(EM / EM1 / EM2) is exceeded, the controller switches off
the solar pump (R1 / R2) in order to protect the system
against overheating (collector emergency shutdown).
A hysteresis of 10 K [20 °Ra] is set for the collector
temperature limitation. While the collector is in emergency
shutdown,
WARNING!Danger of injury and system da-
(flashing) is shown on the display.
Note:
If the drainback option ODB is activated, the ad-
justment range of EM is changed to 80 ... 120 °C
[170 ... 250 °F]. The factory setting in that case is
95 °C [200 °F].
mage through pressure surges!
If water is used as a heat transfer medium in a pressure-less system, the water will start boiling at 100 °C [212 °F].
Î If a pressure-less drainback
system is used with water as a
heat transfer medium, do not
adjust the collector temperature limitation EM to more
Cooling functionsIn the following the three cooling functions – collector
cooling, system cooling and store cooling – are described
in detail. The following notes are valid for all three cooling
functions:
Note:
The cooling functions will not become active as
long as solar loading is possible.
Note:
In 2-store-systems, the cooling functions will only
affect store 1, respectively the base area of the
store (such as in Arr = 4).
Collector cooling functionWhen the collector cooling function is activated, the controller
OCC / OCC1 / OCC2:
Option collector cooling
Adjustment range: OFF / ON
Factory setting: OFF
CMX / CMX1 /CMX2:
Maximum collector temp.
Adjustment range:
70 ... 160 °C
[150 ... 320 °F]
in steps of 1 °C [1 °F]
Factory setting:
110 °C [230 °F]
aims to keep the collector at an operational temperature.
When the adjusted maximum store temperature is reached,
solar loading stops. If the collector temperature increases
to the adjusted maximum collector temperature, the solar
pump is activated until the collector temperature falls at least
5 K [10 °Ra] below the maximum collector temperature. The
store temperature may increase (subordinate active maximum
store temperature), but only up to 95 °C [200°F] (emergency
shutdown of the store).
If the collector cooling function is active,
is shown on the display.
Note:
This function will only be available if the system
cooling function (OSYC) is deactivated.
and (flashing)
System cooling function
OSYC:
Option system cooling
Adjustment range: OFF / ON
Factory setting: OFF
DTCO:
Switch-on temperature diff.
Adjustment range:
1.0 ... 30.0 K [2.0 ... 60.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
20.0 K [40.0°Ra]
DTCF:
Switch-off temperature diff.
Adjustment range:
0.5 ... 29.5 K [1.0 ... 59.0 °Ra]
in steps of 0.5 K [1 °Ra]
Factory setting:
15.0 K [30.0 °Ra]
Note:
In system layout 10, the parameter CMX is
available without the OCC function. In system
layout 10, CMX is used to set the activation
temperature for the heat dump function. No
other switch-on condition is needed in that case.
When the system cooling function is activated, the controller aims to keep the solar system operational for a longer
time. The function overrides the maximum store temperature to provide thermal relief of the collector field and the
heat transfer fluid on hot days.
If the store temperature is higher than the maximum store
temperature (S MX / S1MX) and the switch-on tempera-
ture difference DTCO is reached, the solar system remains
activated. Solar loading is continued until either the store
temperature reaches 95 °C [200 °F] (emergency shutdown
of the store), the temperature difference falls below the
adjusted value DTCFor the collector emergency shutdown
temperature EM is reached.
If the system cooling function is active,
is shown on the display.
Note:
This function will only be available if the collector
cooling function (OCC) is deactivated.
Store cooling option
Adjustment range: OFF / ON
Factory setting: OFF
OHOL:
Holiday cooling option
Adjustment range: OFF / ON
Factory setting: OFF
THOL:
Holiday cooling temperature
Adjustment range:
20 ... 80 °C [70 ... 175 °F]
in steps of 1 °C [1 °F]
Factory setting:
40 °C [110 °F]
Collector minimum limitation option
OCN / OCN1 /OCN2:
Collector minimum limitation
Adjustment range: OFF / ON
Factory setting: OFF
CMN / CMN1 /CMN2:
Collector minimum temp.
Adjustment range:
10.0 ... 90.0 °C [50.0 ... 190.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting:
10.0 °C [50.0 °F]
When the store cooling function is activated, the controller
aims to cool down the store during the night in order to
prepare it for solar loading on the following day.
If the adjusted maximum store temperature (S MX / S1MX)
is exceeded and the collector temperature falls below the
store temperature, the system will be reactivated in order
to cool down the store. Cooling will continue until the store
temperature has fallen below the adjusted maximum store
temperature (S MX / S1MX) again. A fixed hysteresis of 2 K
[4 °Ra] is set for this function.
Reference threshold temperature differences for the store
cooling function are DT O and DTF.
If no DHW consumption is expected for a longer period
of time, the additional holiday cooling option OHOLcan
be activated in order to extend the store cooling function.
The adjustable temperature THOL then replaces the
maximum store temperature (S MX / S1MX) as a switch-off
temperature for the store cooling function.
When the holiday cooling function is activated
(flashing) are shown on the display.
While the holiday cooling function is active, , and
(flashing) are shown on the display.
If the collector minimum limitation option is activated,
the pump (R1 / R2) is only switched on if the adjustable
collector minimum temperature is exceeded. The minimum
temperature prevents the pump from being switched on
too often at low collector temperatures. A fixed hysteresis
of 5 °K [10 °Ra] is set for this function
If the collector minimum limitation is active,
shown on the display.
Note:
If OSTC or OCF is active, the collector minimum
function will be overridden. In that case, the
collector temperature may fall below CMN.
, and
(flashing) is
Antifreeze option
OCF/ OCF1/OCF2:
Antifreeze function
Adjustment range: OFF / ON
Factory setting: OFF
CFR/CFR1/CFR2:
Antifreeze temperature
Adjustment range:
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps of 0.5 °C [1 °F]
Factory setting:
4.0 °C [40.0 °F]
| 42
The antifreeze function activates the loading circuit between
the collector and the store when the temperature falls below
the adjusted antifreeze temperature. This will protect the
fluid against freezing or coagulating. If the adjusted antifreeze
temperature is exceeded by 1 K [2 °Ra], the loading circuit
will be deactivated.
When the antifreeze function is activated, is shown on
the display. If the antifreeze function is active, and
(flashing) are shown on the display.
Note:
Since this function uses the limited heat quantity
of the store, the antifreeze function should be
used in regions with few days of temperatures
around the freezing point.
The antifreeze function will be suppressed if the
store temperature falls below 5 °C [40 °F] in
order to protect the store from frost damage.
Priority logic can be used in multi-store system
layouts only (Arr = 4, 5, 6).
PRIO:
Loading priority
Adjustment range:
SE 1, SE 2, Su 1, Su 2, 0, 1, 2
Factory setting:
Arr 4: 2
Arr 5, 6: 1
Note:
If the priority is set to Su 1 or Su 2, solar
loading of the subordinate store will be aborted
at once if the temperature in the priority store
(store 1 for Su 1, store 2 for Su 2) falls below
the adjusted maximum temperature. If, in that
case, the temperature difference between
the priority store and the collector is not
sufficiently high, solar loading will be stopped
completely.
Spreaded loading temperature difference
(only available if PRIO is set to SE 1 or SE 2)
DTSE:
Spread temperature difference
Adjustment range:
20 ... 90 K [40 ... 160 °Ra]
in steps of 1 K [1 °Ra]
Factory setting: 40 K [70 °Ra]
If a multi-store system layout has been chosen, the priority logic determines how the heat is divided between
the stores. Different types of priority logic are adjustable:
• spreaded loading (SE 1 and SE 2)
• successive loading (Su 1 and Su 2)
• parallel loading (0)
• store sequence control (1 and 2)
If priority SE 1 or SE 2 (only available in Arr 6) is
adjusted, the subordinate store will be loaded in parallel if
the temperature difference between the collector and the
priority store (store 1 for SE 1, store 2 for SE 2) exceeds
the adjusted value DTSE and the subordinate store has not
reached its maximum temperature.
Parallel loading will stop as soon as the temperature
difference between the collector and the priority store falls
2 K [4 °Ra] below DTSE or the subordinate store reaches
its maximum temperature.
If priority Su 1 or Su 2 is adjusted, the stores are loaded
successively. The subordinate store will only be loaded if the
priority store (store 1 for Su 1, store 2 for Su 2) has reached
its adjusted maximum temperature (S1MX or S2MX).
If priority 0 is adjusted and the switch-on conditions are
fulfilled for both stores, the stores are loaded in parallel
(Arr 6), resp. in an oscillating loading (Arr 4, 5) beginning
with the store with the lowest temperature. In an oscillating
loading, solar loading will switch from one store to the other
in steps of 5 K [10 °Ra] temperature difference between
the stores.
If priority 1 / 2 is adjusted, store sequence control will
be activated (see below) with the corresponding store as
priority store.
Storesequencecontrol
(only available if priority is set to SE 1, SE 2, 1 or 2)
tLB:
Loading break time
Adjustment range: 1 ... 30 min
Factory setting: 2 min
tRUN:
Loading runtime
Adjustment range: 1 ... 30 min
Factory setting: 15 min
Store sequence control will be activated when PRIO is set
to SE 1, SE 2, 1 or 2.
If the priority store cannot be loaded, the subordinate
store is checked. If useful heat can be added, it will be
loaded for the “loading runtime time” (tRUN - factory
setting 15 min.) After this, the loading process stops and
the controller monitors the increase in collector temperature during the loading break time tLB. If it increases by
2 K [4° Ra], the break time timer starts again to allow the
collector to gain more heat. If the collector temperature
does not increase sufficiently, the subordinate store will
be loaded again for the tRUN time as before.
As soon as the switch-on condition of the priority store is
fulfilled, it will be loaded. If the switch-on condition of the
priority store is not fulfilled, loading of the second store will
be continued. If the priority store reaches its maximum temperature, sequence controlled loading will not be carried out.
If store sequence control is active and the system switches
to load the priority store, the parameter tLBalso acts as a
stabilisation timer, during which the switch-off condition DTF
is ignored while the system operation stabilises.
Tube collector function
Adjustment range: OFF / ON
Factory setting: OFF
TCST:
Tube collector function
starting time
Adjustment range:
00:00 ... 23:45
in steps of 00:15
Factory setting: 07:00
TCEN:
Tube collector function
ending time
Adjustment range:
00:00 ... 23:45
in steps of 00:15
Factory setting: 19:00
TCRU:
Tube collector function
runtime
Adjustment range: 5 ... 500 s
in steps of 5 s
Factory setting: 30 s
TCIN:
Tube collector function
standstill interval
Adjustment range: 1 ... 60 min
in steps of 1 min
Factory setting: 30 min
This function helps overcome the disadvantages caused by
the non-ideal sensor position with some tube collectors.
This function operates within an adjusted time frame (beginning at TCST and ending at TCEN). It activates the
collector circuit pump for an adjustable runtime (TCRU)
between adjustable standstill intervals (TCIN) in order to
compensate for the delayed temperature measurement.
If the runtime TCRU is set to more than ten seconds, the
pump will be run at 100 % for the first ten seconds of the
runtime. For the remaining runtime, the pump will be run
at the adjusted minimum speed nMN.
If the collector sensor is defective or the collector is blocked,
this function is suppressed or switched off.
In system layout 7 (Arr = 7) both collectors are operated
independently from each other by means of this function.
If the store is being loaded by one collector, the other one
is nevertheless operated after the adjusted standstill time.
Note:
If the drainback option ODB is activated, TCRU
will not be available. In that case, the runtime is
determined by the parameters tFLL and tSTB.
WARNING!Danger of injury and system da-
mage through pressure surges!
If a drainback system is filled due to
the tube collector function and the
heat transfer medium enters very hot
collectors, pressure surges can occur.
Î If a pressure-less drainback
sy ste m is u sed, TC ST and
TCEN must be adjusted such
that the system will not be
filled during times of potentially strong irradiation!
Heatquantitymeasurement
OHQM: Heat quantity measurement
Adjustment range: OFF / ON
Factory setting: OFF
FMAX: Flow rate in l/min
Adjustment range: 0.5 ... 100.0
in steps of 0.5
Factory setting: 6.0
MED%: Antifreeze ratio
in Vol-% (MED% is hidden
when MEDT 0 or 3 is used.)
Adjustment range: 20 ... 70 %
in steps of 1 %
Factory setting: 45 %
| 44
If OHQM is activated, the heat quantity gained can be calculated and displayed. Heat quantity measurement is possible
on Arr. 1, 3, 4, 5 and 10 if a flowmeter is used. To enable heat
quantity measurement, proceed as follows:
Î Read the flow rate (l/min) from the flowmeter at maxi-
mum pump speed and adjust it in the FMAX channel
Î Adjust the heat transfer fluid and the concentration of
If the system layout 10 has been selected and
OHQM is activated, heat quantity measurement
will be interrupted when the 3-way-valve
switches to the heat dump.
Drainback optionA drainback system permits the heat transfer fluid to drain
Note:
A drainback system layout requires additional
components such as a hold ing tank. The
drainback option should only be activated if
all components required are properly installed.
Note:
The drainback option is only available in system
layouts with one store and one collector (Arr
1, 2, 3, 8 and 9).
ODB:
Drainback option
Adjustment range: OFF / ON
Factory setting: OFF
back into the holding tank when solar energy is not collected. The drainback option will initiate the filling of the
system when solar loading begins.
If the drainback option ODBis activated, the pump will
operate at 100 % speed for the adjusted filling time tFLL
in order to fill the system with fluid from the holding tank.
After tFLL, pump speed will go down to the adjusted
minimum pump speed nMn. The switch-off conditions will
then be ignored for the stabilisation time tSTB in order to
avoid the system from shutting down prematurely.
If the function is activated, the menu items described in the
following (tDTO, tFLL and tSTB) have to be adjusted:
Note:
When the drainback option ODB is activated,
the cooling functions OCC, OSYC and OSTC
as well as the antifreeze function OCF are not
available.
If OCC, OSYC, OSTC orOCFhave already
been activated before, they will be deactivated
again as soon as ODB is activated. They will
remain deactivated, even if ODB is deactivated
later on.
Time period - switch-on conditions
tDTO:
Time period -
switch-on conditions
Adjustment range: 1 ... 100 s
in steps of 1 s
Factory setting: 60 s
Fillingtime
tFLL:
Filling time
Adjustment range:
1.0 ... 30.0 min
in steps of 0.5 min
Factory setting: 5.0 min
Note:
When the drainback option ODB is activated,
the temperature differences DT O, DTF and
DT S as well as the minimum speed values
nMN / n1MN are set to a fixed adjustment.
Additionally, the adjustment range and the
factory setting of the collector emergency
shutdown temperature EM changes (see the
corresponding channel descriptions for further
information).
Previous adjustments made in these channels will
be overridden and have to be entered again if
ODB is deactivated later on.
The parameter tDTO is used for adjusting the time period
during which the switch-on condition DT O must be permanentely fulfilled.
The filling time can be adjusted using the parameter tFLL.
During this period, the pump runs at 100 % speed.
Stabilisation
tSTB:
Stabilisation
Adjustment range:
1.0 ... 15.0 min
in steps of 0.5 min
Factory setting: 2.0 min
Boosterfunctionoption
OBST:
Booster function
Adjustment range: ON / OFF
Factory setting: OFF
The parameter tSTB is used for adjusting the time period
during which the switch-off condition DTF will be ignored
after the filling time has ended.
This function is used for switching on a second pump when
filling the solar system. When solar loading starts, R2 is energised in parallel to R1. After the filling time (tFLL) has ended,
R2 is switched off.
Note:
The booster function is available in system layout 1
(Arr = 1) only.
The booster function will only be available if the
drainback option has been activated.
45 |
DeltaSol® BS Plus
Operating mode
MAN1/MAN2:
Operating mode
Adjustment range:
OFF, Auto, ON
Factory setting: Auto
HEpumpcontrol
ADA1/ADA2:
HE pump control
Adjustment range: ON / OFF
Factory setting: OFF
For control and service work, the operating mode of the
controller can be manually adjusted. For this purpose, select
the adjustment value MAN1, MAN2 in which the following
adjustments can be made:
• MAN1/MAN2
Operating mode
OFF : relay off
(flashing) +
Auto : relay in automatic operation
ON : relay on
(flashing) + + /
Note:
Always adjust the operating mode back to
“Auto” when the control and service work is
completed. Normal operation is not possible in
manual mode.
This option is used for controlling high-efficiency pumps via
®
a VBus
/ PWM adapter. The power supply of the pump(s)
takes place via the semiconductor relay(s). For pump speed
control with activated ADA1 / ADA2 option, the relay is switched on or off (no pulse packets). Temperature dependent
®
speed information is transmitted via the VBus
. The relay will
remain deactivated for 1 hour after its switch-off conditions
have been fulfilled (pump protection).
Language
LANG:
Language selection
Selection: dE, En, Fr
Factory setting: En
Unit
UNIT:
Temperature unit selection
Selection: °C, °F
Factory setting: °C
Reset
RESE
Reset function
Note:
The parameter ADA1 refers to relay 1 and is
available in all system layouts. The parameter
ADA2 refers to relay 2 and is available in the
system layouts 2, 6, 7, 8.
The menu language can be adjusted in this channel.
• dE : German
• En : English
• Fr : French
In this adjustment channel, the display unit for temperatures
and temperature differences can be chosen. The unit can be
switched between °C / K and °F / °Ra during operation.
Temperatures and temperature differences in °F and °Ra
are displayed without units. If the indication is set to °C, the
units are displayed with the values.
By using the reset function, all adjustments will be set back
to the factory settings.
Î To initiate a reset, press button 3
Any previous adjustments will be lost. Therefore, initiating the reset function is always followed by a security
enquiry.
Operating control lamp flashes red. On the display the
symbols and appear.
Sensor defect. An error code instead of
a temperature is displayed in the sensor
display channel.
T4A
100 ... 240V~
CU 72091163 01
R1
1 (1) A (1100 ... 240)V~
(1) A (100 ...240) V~
R2
141312
load terminalssensor terminals
- 88.8888.8
50-60 Hz
201918171615
power supply
terminals
In the case of an error, a message is shown on the display
of the controller:
Warning symbols
LNR1NR2N
Operating control lamp
Operating control lamp off.
Check the power supply. Is it disconnected?
no
yes
Cable broken.
Check cable.
Short circuit.
Check cable.
Disconnected Pt1000 temperature sensors can be checked with an ohmmeter. In
the following table, the resistance values
with the corresponding temperatures are
shown.
Pump is overheated, but no heat transfer from the
collector to the store, flow and return have the same
temperature; perhaps also air / gas bubbles in the lines.
Air in the system?
Air in the system; in crease
the system pressure to at
noyes
least static primary pressure plus 7. 25 psi (0.5 bar);
if necessary continue to
increase pressure; switch
the pump off and on for a
Is the collector circuit
short time.
blocked at the dirt trap?
yes
Clean the dirt trap
Pump starts up very late
Pump starts for a short moment, switches off, switches
on again, etc.
Temperature difference
at the controller too
small?
Change ∆Ton and ∆Toff
noyes
correspondingly. Problem
solved?
no
yes
Wrong position of collector sensors?
no
yes
Mount the collector sen-
o.k.
sor at solar flow (warmest
collector output); use sen-
Plausibility control of
the option tube collec-
sor well of the respective
collector.
tor special function
The temperature difference between store and collector
increases enormously during operation; the collector circuit cannot dissipate the heat.
Switch-on temperature
difference ∆Ton to large?
noyes
Non-ideal position of the collector sensor (e.g. flatscrew
sensor instead of sensor in
sensor wells)?
Control the non-return
valve in warm water circulation - o.k.
Further pumps which are
connected to the solar
store must also be checked.
Collector circuit pump
runs during the night?
Check controller:
yesno
Manual operation active?
noyes
Collector temperature is
at night higher than the
outdoor temperature
noyes
Sufficient store insulation?
Tube collector function
active? Store cooling
or antifreeze function
active?
Check the check valve in
the flow and the return
pipe with regard to the
functional efficiency.
The thermosiphoning in
the circulation line is too
strong; insert a stronger
valve in the non-return valve or an electrical 2-port
valve behind the circulation pump; the 2-port valve
is open when the pump is
activated, otherwise it is
closed; connect pump and
2-port valve electrically in
Clean or replace it
parallel; activate the circu-
yesno
Increase insulation.
lation again
The solar circuit pump does not work, although the coll-
Insulation close enough
ector is considerably warmer than the store.
to the store?
yesno
Are the store connec-
Replace insulation or increase it.
Is the control lamp (LED)
illuminated?
There is no current; check
fuses / replace them and
check power supply.
tions insulated?
yesno
Does the pump start up
in manual operation?
no
yes
Is the pump current
enabled by the controller?
no
yes
The adjusted temperature
difference for starting the
pump is to high; choose a
value which makes more
sense.
Is the pump stuck?
yes
Turn the pump shaft using
yesno
Warm water outflow
upwards?
noyes
Does the warm water
circulation run for a very
long time?
noyes
Insulate the connections.
Change connection and
let the water flow horizontally or through a siphon (downwards); less
store losses now ?
noyes
o.k.
Use the circulation pump
with timer and switch-off
thermostat (energy efficient circulation).
a screwdriver; now pas-
Circul atio n p ump and
sable?
blocking valve should be
switched off for one night;
less store losses?
yesno
C h e c k w h e t h e r t h e
pumps of the afterheating
circuit run at night; check
whether the non-return
valve is defective; problem
solved ?
Controller might be defective - replace it or contact
the distributor.
49 |
DeltaSol® BS Plus
6. Accessories
Sensors
Our product range includes high-precision platinum temperature sensors, flatscrew sensors,
outdoor temperature sensors, indoor temperature sensors, cylindrical clip-on sensors, also
as complete sensors with immersion sleeve.
For more information, see our catalogue and price list.
Overvoltage protection device
In order to avoid overvoltage damage at collector sensors (e.g. caused by local lightning
storms), we recommend the overvoltage protection RESOL SP10.
RESOL SP10 Article no.: 180 110 70
Smart Display SD3
The RESOL Smart Display is designed for simple connection to RESOL controllers with
RESOL VBus
®
. It is used for visualizing data issued by the controller: collector temperature,
storage temperature and energy yield of the solar thermal system. The use of high-efficient
LEDs and filter glass assures a high optical brilliance and good readability even in poor visibility conditions and from a larger distance. An additional power supply is not required.
The RESOL Large Display GA3 is designed for simple connection to RESOL controllers via
the RESOL VBus
®
. It is used for visualizing the data issued by the controller: collector and
store temperature as well as heat quantity produced in the solar system.
The use of high-efficient LEDs and antireflective filter glass assures a high optical brilliance
and good readability - even in poor lighting conditions and at a larger distance.
This additional module enables the acquisition and storage of large amounts of data (such
as measuring and balance values of the solar system) over a long period of time. The DL2
can be configured and read-out with a standard internet browser via its integrated web
interface. For transmission of the data stored in the internal memory of the DL2 to a PC,
an SD card can be used.
The DL2 is appropriate for all controllers with RESOL VBus
to a PC or router for remote access and thus enables comfortable system monitoring for
yield monitoring or for diagnostics of faults.
RESOL DL2Article no.: 180 007 10
VBus®/USBinterfaceadapter
®
The new VBus
/ USB interface adapter is the interface between the controller and a
personal computer. With its standard mini-USB port it enables a fast transmission of system
data via the VBus® for processing, visualizing and archiving. A full version of the RESOL
ServiceCenter software is included.
®
RESOLVBus
/USBinterfaceadapter Article no.: 180 008 50
®
. It can be connected directly
VBus® / LAN interface adapter
The VBus® / LAN interface adapter is designed for the direct connection of the controller
to a PC network or router. It enables easy access to the controller via the local network of
the owner. Thus, controller access and data charting can be effected from every workstation
of the network. A full version of the RESOL ServiceCenter software is included.
RESOLVBus
®
/ LAN interface adapter Article no.: 180 008 80
VBus® / PWM interface adapter
The VBus® / PWM interface adapter is used for the speed control of a pump via a PWM or
0-10 V signal. Via the VBus®, the adapter receives information from the controller about the
necessary pump speed. The speed is converted into a PWM or direct voltage signal and put
out to the corresponding terminals.
RESOLVBus
®
/ PWM interface adapter Article no.: 180 008 60
AM1 Alarm module
The AM1 alarm module is designed to signal system failures. It is to be connected to the
VBus® of the controller and issues an optical signal via a red LED if a failure has occurred.
The AM1 also has a potential-free relay output, which can e. g. be connected to a building
management system (BMS). Thus, a collective error message can be issued in the case of a
system failure.
Important notice:
The texts and drawings in this manual are correct to the
best of our knowledge. As faults can never be excluded,
please note: Your own calculations and plans, under con sideration of the current standards should only be basis for your
projects. We do not offer a guarantee for the completeness of
the drawings and texts of this manual - they only represent
some examples. They can only be used at your own risk.
No liability is assumed for incorrect, incomplete or false
information and / or any resulting damages.
Pleasenote:
The design and the specifications can be changed without prior notice.
The illustrations may differ from the original product.
This mounting- and operation manual including all parts
is copyrighted. Another use outside the copyright requires
the approval of RESOL - Elektronische Regelungen GmbH.
This especially applies for copies, translations, microfilms and the storage into electronic systems.
Editor: RESOL - Elektronische Regelungen GmbH