Thank you for buying this RESOL product. Please read this manual carefully to get the best performance from this unit.
Please keep this manual carefully.
DeltaSol® BS/4
Manual
en
Solar controller
Manual for the specialised craftsman
Installation
Operation
Functions and options
Troubleshooting
(Version 2)
2
en
© 20151016_48005962_DeltaSol_BS4_V2.monen
Safety advice
Please pay attention to the following safety advice in order to avoid danger and damage to people and property.
Instructions
Attention must be paid to the valid local standards, regulations and directives!
Information about the product
Proper usage
The solar controller is designed for electronically controlling standard solar thermal
systems in compliance with the technical data specied in this manual.
Improper use excludes all liability claims.
CE Declaration of Conformity
The product complies with the relevant directives and is therefore labelled with the CE mark. The Declaration of Conformity is available upon request, please contact RESOL.
Note
Strong electromagnetic elds can impair the function of the controller.
Î Make sure the controller as well as the system are not exposed to
strong electromagnetic elds.
Target group
These instructions are exclusively addressed to authorised skilled personnel.
Only qualied electricians should carry out electrical works. Initial installation must be effected by the system owner or qualied personnel
named by the system owner.
Description of symbols
WARNING! Warnings are indicated with a warning triangle!
Î They contain information on how to avoid the dan-
ger described.
Signal words describe the danger that may occur, when it is not avoided.
• WARNING means that injury, possibly life-threatening injury, can occur.
• ATTENTION means that damage to the appliance can occur.
Note
Notes are indicated with an information symbol.
Î Arrows indicate instruction steps that should be carried out.
Disposal
• Dispose of the packaging in an environmentally sound manner.
• Dispose of old appliances in an environmentally sound manner. Upon request we will take back your old appliances bought from us and guarantee an environmen­tally sound disposal of the devices.
Subject to technical change. Errors excepted.
3
en
1 Overview ..............................................................................................4
2 Installation ...........................................................................................5
2.1 Mounting ........................................................................................................................5
2.2 Electrical connection ...................................................................................................6
2.3 Data communication / Bus ..........................................................................................7
2.4 System overview ..........................................................................................................7
2.5 Systems ...........................................................................................................................8
3 Operation and function ....................................................................16
3.1 Buttons .........................................................................................................................16
4 System-Monitoring-Display ..............................................................16
4.1 System screen .............................................................................................................17
4.2 Other indications .......................................................................................................17
5 Commissioning ..................................................................................18
6 Channel overview ..............................................................................20
6.1 Display channels .........................................................................................................20
6.2 Adjustment channels .................................................................................................23
7 Troubleshooting ................................................................................. 31
8 Accessories ........................................................................................34
8.1 Sensors and measuring instruments ......................................................................35
8.2 VBus
®
accessories ......................................................................................................35
8.3 Interface adapters ......................................................................................................35
9 Index ...................................................................................................36
Contents
DeltaSol® BS/4 Solar controller
The RESOL controller for standard solar thermal systems. The DeltaSol® BS controller provides a clear operating concept and is equipped with the illuminated combined display with system-monitoring. Flashing symbols for
sensors, pumps and valves enable an immediate allocation of temperatures, tempera­ture differences and active actuators. Thus, adjusting and monitoring the solar system is quick and easy.
4
en
1 Overview
• 3 basic systems to choose from
• Drainback option
• Heat quantity measurement
• Tube collector function, thermal disinfection function
• Commissioning menu
• Unit °F and °C selectable
• HE pump control via adapter
Technical data
Inputs: 4 Pt1000 temperature sensors Outputs: 2 semiconductor relays Switching capacity: 1 (1) A 240 V~ (semiconductor relay) Total switching capacity: 2 A 240 V~ Power supply: 100 … 240 V~ (50 … 60 Hz) Supply connection: type Y attachment Standby: 0.74 W Temperature controls class: I
Energy efciency contribution: 1 %
Mode of operation: type 1.C.Y action Rated impulse voltage: 2.5 kV Data interface: RESOL VBus
®
VBus® current supply: 35 mA Functions: function control, operating hours counter, tube collector function,
heat quantity measurement and pump speed control
Housing: plastic, PC-ABS and PMMA Mounting: wall mounting, also suitable for mounting into patch panels Indication / Display: System-Monitoring-Display for visualisation of systems,
16-segment and 7-segment display, 8 symbols for indication of system status and operating control lamp
Operation: 3 buttons at the front of the housing Protection type: IP 20 / DIN EN 60529 Protection class: II Ambient temperature: 0 … 40 °C Degree of pollution: 2 Dimensions: 172 x 110 x 49 mm
104 mm
4.1"
130 mm
5.1“
2.6"
66 mm
4.3"
110 mm
6.8"
172 mm
1.1" 28 mm
0.4" / 11 mm
1.9" / 49 mm
0.5" / 13 mm
6.1" / 155 mm
Upper fastening point
Lower fastening point
en
5
InstallationIndications, functions and optionsMessages Commissioning Operation and function
2 Installation
2.1 Mounting
WARNING! Electric shock!
Upon opening the housing, live parts are exposed!
Î Always disconnect the device from power supply
before opening the housing!
Note Strong electromagnetic elds can impair the function of the con­troller.
Î Make sure the controller as well as the system are not exposed to
strong electromagnetic elds.
The unit must only be located in dry interior rooms. The controller must additionally be supplied from a double pole switch with contact
gap of at least 3 mm. Please pay attention to separate routing of sensor cables and mains cables.
In order to mount the device to the wall, carry out the following steps:
Î Unscrew the crosshead screw from the cover and remove it along with the
cover from the housing.
Î Mark the upper fastening point on the wall. Drill and fasten the enclosed wall
plug and screw leaving the head protruding.
Î Hang the housing from the upper fastening point and mark the lower fastening
point (centres 130 mm). Î Insert lower wall plug. Î Fasten the housing to the wall with the lower fastening screw and tighten. Î Carry out the electrical wiring in accordance with the terminal allocation (see
page 6). Î Put the cover on the housing. Î Attach with the fastening screw.
display
button
T4A fuse
cable glands and strain relief
cover
en
6
Installation Indications, functions and options MessagesCommissioningOperation and function
2.2 Electrical connection
WARNING! Electric shock!
Upon opening the housing, live parts are exposed!
Î Always disconnect the device from power supply
before opening the housing!
ATTENTION! ESD damage!
Electrostatic discharge can lead to damage to electronic com­ponents!
Î Take care to discharge properly before touching the
inside of the device!
Note
Connecting the device to the power supply must always be the last step
of the installation!
Note
It must be possible to disconnect the device from the mains at any time.
Î Install the mains plug such that it is accessible at any time. Î If this is not possible, install a switch that can be accessed.
Do not use the device if it is visibly damaged!
The power supply of the device must be 100 … 240 V~ (50 … 60 Hz). Attach exible
cables to the housing with the enclosed strain relief and the corresponding screws. The controller is equipped with 2 semiconductor relays to which a load such as a
pump, a valve, etc. can be connected:
• Relay 1 • Relay 2 18 = Conductor R1 16 = Conductor R2 17 = Neutral conductor N 15 = Neutral conductor N 13 = Grounding terminal 14 = Grounding terminal
Note
The pump speed must be set to 100 % when auxiliary relays or valves are connected.
The mains connection is at the following terminals:
19 = Neutral conductor N 20 = Conductor L 12 = Grounding terminal
VBus
®
DE-45527 Hattingen DeltaSol BS/4V2
12
S1 S2 S3
3456
LNR1NR2N
201918171615
S4
78
141312
1 (1)A 100 ... 240V~ 1 (1)A 100 ... 240V~
R1
R2
T4A
VBus
910
CU 72091163 01
100 ... 240V~
50-60 Hz
Temp. Sensor Pt1000
IP 20
Made in Germany
mains terminals
fuse
load terminalssensor terminals grounding
terminals
Connect the temperature sensors (S1 to S4) to the corresponding terminals with either polarity:
1 / 2 = Sensor 1 (e. g. collector sensor) 3 / 4 = Sensor 2 (e. g. store sensor) 5 / 6 = Sensor 3 (e. g. store sensor top) 7 / 8 = Sensor 4 (e. g. return sensor)
en
7
InstallationIndications, functions and optionsMessages Commissioning Operation and function
2.3 Data communication / Bus
The controller is equipped with the RESOL VBus
®
for data transfer and energy
supply to external modules. The connection is to be carried out at the terminals marked VBus (any polarity).
One or more RESOL VBus
®
modules can be connected via this data bus, such as:
• RESOL DL2 Datalogger
• RESOL DL3 Datalogger
• VBus
®
/ PWM interface adapter
Furthermore, the controller can be connected to a PC or integrated into a net­work via the RESOL VBus
®
/ USB or VBus® / LAN interface adapter (not included). Different solutions for visualisation and remote parameterisation are available on the RESOL website www.resol.com.
Note
More accessories on page 34.
2.4 System overview
1
Standard solar system (page 8)
2
Solar system with afterheating (page 10)
3
Standard solar system with heat dump (page 14)
en
8
Installation Indications, functions and options MessagesCommissioningOperation and function
2.5 Systems
Arrangement 1:
The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switch-on temperature difference (DT O), the solar pump will be activated by the relay, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached.
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as the reference sensor for the store emergency shutdown op­tion (OSEM).
If heat quantity measurement (OHQM) is activated, S4 is to be used as the return sensor.
If the drainback option (ODB) is activated, relay 2 can be used for activating a booster pump. For this purpose, the booster function (OBST) has to be activated.
Mains
3
322
S1
S2
S4 / TR
R1
S3
Example Drainback
system
(with booster pump)
S1
S3
S2
S4/TR
R1 R2
en
9
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description
Connection
terminal
Page
INIT x* ODB initialisation active - 20 FLL x* ODB lling time active - 20 STAB x* ODB stabilisation in progress - 20 COL x Temperature collector S1 20 TST x Temperature store S2 20 S3 x Temperature sensor 3 S3 21 S4 x Temperature sensor 4 S4 21 TR x* Temperature return sensor S4 21 n % x Speed R1 R1 21 hP x Operating hours R1 R1 22 hP1 x* Operating hours R1 (if OBST is activated) R1 22 hP2 x* Operating hours R2 (if OBST is activated) R2 22 kWh x* Heat quantity in kWh - 21 MWh x* Heat quantity in MWh - 21 TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 1 22 DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23 DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23 DT S x Set temperature difference 10.0 K [20.0 °Ra] 23 RIS x Rise R1 2 K [4 °Ra] 24 nMN x Minimum speed 30 % 24 S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM x Store emergency shutdown option OFF 24
EM x
Collector emergency temperature 130 °C [270 °F] 25
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 25
OCC x Collector cooling option OFF 25 CMX x* Maximum collector temperature 110 °C [230 °F] 25 OSYC x System cooling option OFF 25 DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 25 DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 25 OSTC x Store cooling option OFF 25 OHOL x* Holiday cooling option OFF 25 THOL x* Holiday cooling temperature 40 °C [110 °F] 25 OCN x Collector minimum limitation option OFF 26
Adjustment channels
Channel Description Factory setting Page
CMN x* Minimum collector temperature 10 °C [50 °F] 26 OCF x Antifreeze option OFF 26 CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 26 OTC x Tube collector option OFF 27 TCST x* OTC starting time 07:00 27 TCEN x* OTC ending time 19:00 27 TCRU x* OTC runtime 30 s 27 TCIN x* OTC standstill interval 30 min 27 OHQM x Heat quantity measurement option OFF 28 FMAX x* Maximum ow rate 6.0 l 28 MEDT x* Antifreeze type 1 28 MED% x* Antifreeze concentration
(only if MEDT = propylene or ethylene glycol)
45 % 28
ODB x Drainback option OFF 28 tDTO x* ODB switch-on condition - time period 60 s 29 tFLL x* ODB lling time 5.0 min 29 tSTB x* ODB stabilisation time 2.0 min 29 OBST s* Option booster function OFF 29 MAN1 x Manual mode R1 Auto 29 MAN2 x Manual mode R2 Auto 29
ADA1 x HE pump control OFF 29
LANG x Language dE 29 UNIT x Temperature unit °C 29 RESE x Reset - back to factory settings 30
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.
en
10
Installation Indications, functions and options MessagesCommissioningOperation and function
Arrangement 2:
The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switch-on temperature difference (DT O), the solar pump will be activated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached.
Sensor S3 is used for a thermostat function which operates relay 2 for afterheat­ing or heat dump purposes when the adjusted thermostat switch-on temperature (AH O) is reached. This function can optionally be combined with up to three ad­justable time frames.
S3 can optionally be used as the reference sensor for the thermal disinfection func­tion (OTD).
Sensor S4 can optionally be connected for measurement purposes. If heat quantity measurement (OHQM) is activated, S4 is to be used as the return sensor.
Mains
3
3 32 22
S1
S2
S4 / TR
R1
S3
en
11
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description
Connection
terminal
Page
INIT x* ODB initialisation active - 20 FLL x* ODB lling time active - 20 STAB x* ODB stabilisation in progress - 20 COL x Temperature collector S1 20 TSTB x Temperature store 1 base S2 20 TSTT x Temperature store 1 top S3 20 TDIS s* Thermal disinfection temperature (thermal disinfection) S3 20 S4 x Temperature sensor 4 S4 21 TR x* Temperature return sensor S4 21 n1 % x Speed R1 R1 21 h P1 x Operating hours R1 R1 22 h P2 x Operating hours R2 R2 22 kWh x* Heat quantity in kWh - 21 MWh x* Heat quantity in MWh - 21 CDIS s* Countdown of monitoring period (thermal disinfection) - 21 SDIS s* Display of starting time - 22 DDIS s* Heating period display - 22 TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 2 22 DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23 DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23 DT S x Set temperature difference 10.0 K [20.0 °Ra] 23 RIS x Rise R1 2 K [4 °Ra] 24 n1MN x Minimum speed R1 30 % 24 S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM x Store emergency shutdown option OFF 24
EM x
Collector emergency temperature 130 °C [270 °F] 25
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 25
OCC x Collector cooling option OFF 25 CMX x* Maximum collector temperature 110 °C [230 °F] 25 OSYC x System cooling option OFF 25 DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 25 DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 25 OSTC x Store cooling option OFF 25 OHOL x* Holiday cooling option OFF 25 THOL x* Holiday cooling temperature 40 °C [110 °F] 25 OCN x Collector minimum limitation option OFF 26
Adjustment channels
Channel Description Factory setting Page
CMN x* Minimum collector temperature 10 °C [50 °F] 26 OCF x Antifreeze option OFF 26 CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 26 OTC x Tube collector option OFF 27 TCST x* OTC starting time 07:00 27 TCEN x* OTC ending time 19:00 27 TCRU x* OTC runtime 30 s 27 TCIN x* OTC standstill interval 30 min 27 OHQM x Heat quantity measurement option OFF 28 FMAX x* Maximum ow rate 6.0 l 28 MEDT x* Antifreeze type 1 28 MED% x* Antifreeze concentration 45 % 28 AH O s Switch-on temperature for thermostat 1 40 °C [110 °F] 12 AH F s Switch-off temperature for thermostat 1 45 °C [120 °F] 12 t1 O s Thermostat switch-on time 1 00:00 12 t1 F s Thermostat switch-off time 1 00:00 12 t2 O s Thermostat switch-on time 2 00:00 12 t2 F s Thermostat switch-off time 2 00:00 12 t3 O s Thermostat switch-on time 3 00:00 12 t3 F s Thermostat switch-off time 3 00:00 12 ODB x Drainback option OFF 28 tDTO x* ODB switch-on condition - time period 60 s 29 tFLL x* ODB lling time 5.0 min 29 tSTB x* ODB stabilisation time 2.0 min 29 OTD s Thermal disinfection option OFF 13 PDIS s* Monitoring period 01:00 13 DDIS s* Heating period 01:00 13
TDIS s* Disinfection temperature 60 °C [140 °F] 13 SDIS s* Starting time 00:00 13 MAN1 x Manual mode R1 Auto 29 MAN2 x Manual mode R2 Auto 29
ADA1 x HE pump control OFF 29
LANG x Language dE 29 UNIT x Temperature unit °C 29 RESE x Reset - back to factory settings 29
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.
en
12
Installation Indications, functions and options MessagesCommissioningOperation and function
System-specic functions
The following adjustments are used for the specic functions in system 2. The chan­nels described are not available in any other system.
Thermostat function
Afterheating
Use of surplus energy
The thermostat function works independently from the solar operation and can be used for using surplus energy or for afterheating.
• AH O < AH F
thermostat function for afterheating
• AH O > AH F
thermostat function for using surplus energy
The symbol will be shown on the display if the second relay output is activated.
Reference sensor for the thermostat function is S3.
AH O
Thermostat switch-on temperature Adjustment range: 0.0 … 95.0 °C [30.0 … 200.0 °F] Factory setting: 40.0 °C [110.0°F]
AH F
Thermostat switch-off temperature Adjustment range: 0.0 … 95.0 °C [30.0 … 200.0 °F] Factory setting: 45.0 °C [120.0 °F]
t1 O, t2 O, t3 O
Thermostat switch-on time Adjustment range: 00:00 … 23:45 Factory setting: 00:00
t1 F, t2 F, t3 F
Thermostat switch-off time Adjustment range: 00:00 … 23:45 Factory setting: 00:00
In order to block the thermostat function for a certain period, there are 3 time frames t1 … t3.
If the thermostat function is supposed to run from 06:00 a.m. to 09:00 a.m. only, adjust t1 O to 06:00 a.m. and t1 F to 09:00 a.m.
If the switch-on and switch-off times of a time frame are set to an identical value, the time frame will be inactive. If all time frames are set to 00:00, the thermostat function is solely temperature dependent (factory setting).
en
13
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Thermal disinfection of the upper DHW zone
OTD
Therm. disinfection function Adjustment range: OFF / ON Factory setting: OFF
PDIS
Monitoring period Adjustment range: 0 … 30:0 … 24 h (dd:hh) Factory setting: 01:00
DDIS
Disinfection period Adjustment range:
0:00 … 23:59 (hh:mm) Factory setting: 01:00
TDIS
Disinfection temperature Adjustment range: 0 … 95 °C [30 … 200 °F] Factory setting: 60 °C [140 °F]
This function helps to contain the spread of Legionella in DHW stores by system­atically activating the afterheating.
For thermal disinfection, the temperature at the reference sensor will be moni­tored. Protection is ensured when, during the monitoring period, the disinfection temperature is continuously exceeded for the entire disinfection period.
The monitoring period starts as soon as the temperature at the reference sensor falls below the disinfection temperature. When the monitoring period ends, the allocated reference relay activates the afterheating. The disinfection period starts, if the temperature at the allocated sensor exceeds the disinfection temperature.
Thermal disinfection can only be completed when the disinfection temperature is exceeded for the duration of the disinfection period without any interruption.
Starting time delay
SDIS
Starting time Adjustment range: 0:00 … 24:00 (time) Factory setting: 00:00
If the starting delay option is activated, a starting time for the thermal disinfection with starting delay can be adjusted. The activation of the afterheating is then delayed until that starting time after the monitoring period has ended.
If the monitoring period ends, for example, at 12:00 o'clock, and the starting time has been set to 18:00, the reference relay will be energised with a delay of 6 hours at 18:00 instead of 12:00 o'clock.
Note If the thermal disinfection option is activated, the display channels TDIS,
CDIS, SDIS and DDIS.
en
14
Installation Indications, functions and options MessagesCommissioningOperation and function
Arrangement 3:
The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switch-on temperature difference (DT O), the solar pump will be activated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached.
If the maximum collector temperature (CMX) is reached, the solar pump will be activated by R1 and the 3-port valve by R2 in order to direct the surplus energy to a heat dump. For safety reasons, excess heat dump will only take place as long as the store temperature is below the non-adjustable shutdown temperature of 95 °C [200 °F].
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as the reference sensor for the store emergency shutdown op­tion (OSEM).
If heat quantity measurement (OHQM) is activated, S4 is to be used as the return sensor.
Mains
33
32 22
S1
S2
S4 / TR
R1
S3
R2
en
15
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description
Connection
terminal
Page
COL x Temperature collector S1 20 TST x Temperature store S2 20 S3 x Temperature sensor 3 S3 21 S4 x Temperature sensor 4 S4 21 TR x* Temperature return sensor S4 21 n % x Speed relay R1 21 h P1 x Operating hours R1 R1 22 h P2 x Operating hours R2 R2 22 kWh x* Heat quantity in kWh - 21 MWh x* Heat quantity in MWh - 21 TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 3 23 DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23 DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23 DT S x Set temperature difference 10.0 K [20.0 °Ra] 23 RIS x Rise R1 2 K [4 °Ra] 24 nMN x Minimum speed 30 % 24 S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM x Store emergency shutdown option OFF 24
EM x Collector emergency temperature 130 °C [270 °F] 25 CMX s Maximum collector temperature 110 °C [230 °F] 25 OCN x Collector minimum limitation option OFF 26 CMN x* Minimum collector temperature 10 °C [50 °F] 26 OCF x Antifreeze option OFF 27 CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 27 OTC x Tube collector option OFF 27 TCST x* OTC starting time 07:00 27 TCEN x* OTC ending time 19:00 27 TCRU x* OTC runtime 30 s 27 TCIN x* OTC standstill interval 30 min 27 OHQM x Heat quantity measurement option OFF 28 FMAX x* Maximum ow rate 6.0 l 28 MEDT x* Antifreeze type 1 28 MED% x* Antifreeze concentration
(only if MEDT = propylene or ethylene glycol)
45 % 28
MAN1 x Manual mode R1 Auto 29 MAN2 x Manual mode R2 Auto 29
ADA1 x HE pump control OFF 30
LANG x Language dE 30 UNIT x Temperature unit °C 30 RESE x Reset - back to factory settings 30
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.
en
16
Installation Indications, functions and options MessagesCommissioningOperation and function
3 Operation and function
3.1 Buttons
2 backwards (-)
1 forwards (+)
3 (selection /
conrmation)
Operating control LED
The controller is operated via the 3 push buttons below the display.
Button 1 (+) - Scrolling forwards, increasing adjustment values. Button 2 (-) - Scrolling backwards, reducing adjustment values. Button 3 (OK) - conrming / selecting.
During normal operation, display channels will be displayed.
Î In order to scroll between display channels, press buttons 1 and 2.
Access to adjustment channels:
Î Use button 1 in order to scroll to the last display channel, then press and hold
down button 1 for approx. 2 s.
If an adjustment channel is shown on the screen,
will be displayed on the
right-hand side next to the channel name.
Î Press button 3 in order to select an adjustment channel.
starts ashing.
Î Adjust the desired value with buttons 1 and 2. Î Briey press button 3.
permanently appears, the adjusted value has been saved.
4 System-Monitoring-Display
System-Monitoring-Display
The System-Monitoring-Display consists of 3 blocks: channel display, tool bar and system screen.
Channel display
The channel display consists of 2 lines. The upper display line is an alphanumeric 16-segment display. In this line, mainly channel names and menu items are displayed. In the lower 16-segment display, values are displayed.
Tool bar
The additional symbols in the tool bar indicate the current system state.
en
17
InstallationIndications, functions and optionsMessages Commissioning Operation and function
4.1 System screen
The system selected is indicated in the System-Monitoring-Display. It consists of several system component symbols which are – depending on the current status of
the system – either ashing, permanently shown or not indicated.
Collector
with collector sensor
Temperature sensor
Store
with heat exchanger
Pump
3-port valve
Only the ow direction or
current switching position is indicated.
Afterheating
with burner symbol
4.2 Other indications
System screen
Pumps are ashing when the corresponding relay is switched on.
Sensor symbols are ashing, if the corresponding sensor display channel is selected.
Sensors are ashing quickly in the case of a sensor fault.
Burner symbol is ashing if the afterheating is active.
Operating control LED
Green: Everything OK
Red / green ashing: Initialisation active Red ashing: Manual mode
Sensor fault (sensor symbol is ashing quickly)
Permanently
shown
Flashing Status indications:
Relay 1 active
Relay 2 active
Maximum store temperature exceeded
+
Store emergency shutdown active
Collector emergency shutdown active
Collector cooling active
System cooling active
+
Store cooling active
Holiday cooling option activated
+
Holiday cooling active
Collector minimum limitation active
Antifreeze function activated
Antifreeze function active
+
Manual mode relay 1 ON
+
Manual mode relay 2 ON
Manual mode relay 1 / 2 OFF
Sensor fault
en
18
Installation Indications, functions and options MessagesCommissioningOperation and function
5 Commissioning
2 backwards (-)
1 forwards (+)
3 (selection /
conrmation)
Î Connect the device to the mains.
The controller runs an initialisation phase in which the operating control LED ashes
red / green. When the controller is commissioned or when it is reset, it will run a commission-
ing menu. The commissioning menu leads the user through the most important adjustment channels needed for operating the system.
Adjustment mode ashing
Operation
Changing a value ashing
Conrming a value not ashing
to the next
parameter
1
1
3
3
2
2
1. Language
Î Adjust the desired menu language.
LANG
Language selection Selection: dE, En, Fr Factory setting: dE
2. Temperature unit
Î Adjust the desired unit.
UNIT
Temperature unit Selection: °F, °C Factory setting: °C
3. Time
Î Adjust the clock time.
First of all adjust the hours, then the minutes.
TIME
Real time clock
4. Arrangement
Î Adjust the desired system.
For a detailed description of the systems to choose from, see page 8.
Arr
System selection Adjustment range: 1 … 3 Factory setting: 1
If the system selection is changed later on, any previ­ous adjustments which have been made in the other channels will be lost. Therefore, changing the system is always followed by a security enquiry.
Commissioning
en
19
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Only con rm the security enquiry if you are
sure that you wish to change the system selec­tion.
Security enquiry
Î In order to con rm the security enquiry, press
button 3.
5. Maximum store temperature
Î Adjust the maximum store temperature.
S MX
Adjustment range: 4 … 95 °C [40 … 200 °F] Factory setting: 60 °C [140 °F]
Note
The controller is also equipped with a non-adjustable emergency shutdown, deacti­vating the system if the store reaches 95 °C [200 °F].
6. Minimum speed
Î Adjust the minimum speed for the corresponding
pump.
nMN
Speed control Adjustment range: 30 … 100 % Factory setting: 30
Note
The pump speed must be set to 100 % when auxiliary relays or valves are connected.
Commissioning
Con rmation
Completing the commissioning menu.
After the last channel of the commissioning menu has
been adjusted and con rmed, the controller asks for con rmation of the adjustments.
Î In order to con rm the adjustments made in the
commissioning menu, press button 3.
The controller is then ready for operation and nor­mally the factory settings will give close to optimum operation.
Note
The adjustments carried out during commis­sioning can be changed anytime in the cor­responding adjustment channel. Additional functions and options can also be activated or deactivated (see page 23).
en
20
Installation Indications, functions and options MessagesCommissioningOperation and function
Display of collector temperatures
COL
Collector temperature Display range: -40 … +260 °C [-40 … +500 °F] Indicates the collector temperature.
Display of store temperatures
TST, TSTB, TSTT, TDIS
Store temperatures
Display range: -40 … +260 °C [-40 … +500 °F] Indicates the store temperatures.
• TST : Store temperature
• TSTB : Store temperature base
• TSTT : Store temperature top
• TDIS : Thermal disinfection temperature (replaces TSTT if, during thermal disinfection, the heating period DDIS is active)
TSTB, TSTT and TDIS are only available if Arr = 2
6 Channel overview
6.1 Display channels
Note
The display and adjustment channels as well as the adjustment ranges de­pend on the system selected, the functions and options as well as on the system components connected to the controller.
Display of drainback time periods
Initialisation
INIT
ODB initialisation active Indicates the time adjusted in tDTO, running backwards.
Filling time
FLL
ODB lling time active
Indicates the time adjusted in tFLL, running backwards.
Stabilisation
STAB
ODB stabilisation in progress Indicates the time adjusted in tSTB, running backwards.
en
21
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Indication of sensors 3 and 4
S3, S4
Sensor temperatures
Display range: -40 … +260 °C [-40 … +500 °F] Indicates the current temperature at the corresponding additional sensor (without control function).
• S3: Temperature at sensor 3 (only if Arr = 1 or 3)
• S4: Temperature at sensor 4
Note
S3 and S4 will only be indicated if the temperature sensors are connected to the corresponding terminals.
Indication of return temperature
TR
Return temperature Display range: -40 … +260 °C [-40 … +500 °F] If the heat quantity measurement is activated, the temperature at sensor S4 will be indicated as TR.
Indication of current pump speed
n %
Current pump speed Display range: 30 … 100 % Indicates the current pump speed of the corresponding pump.
Display of heat quantity
kWh / MWh
Heat quantity in kWh / MWh Display channel
Indicates the heat quantity produced in the system. For this purpose, the heat quan-
tity measurement option has to be enabled. The ow rate as well as the values of the reference sensors ow and return are used for calculating the heat quantity
supplied. It is shown in kWh in the kWh channel and in MWh in the MWh chan­nel. The overall heat quantity results from the sum of both values.
The accumulated heat quantity can be set back to zero. As soon as one of the dis­play channels of the heat quantity is selected, the symbol is displayed.
Î In order to access the reset mode of the counter, press button 3 for approx. 2 s.
starts ashing and the heat quantity value will be set back to zero.
Î In order to nish the reset process, press button 3.
In order to interrupt the reset process, do not press any button for about 5 s. The display returns to the display mode.
Indication of thermal disinfection
CDIS
Countdown monitoring period Display range: 0 … 30:0 … 24 (dd:hh)
If the thermal disinfection option (OTD ) is activated and the monitoring period is in progress, the remaining time is displayed as CDIS (in hours and minutes), counting backwards.
en
22
Installation Indications, functions and options MessagesCommissioningOperation and function
SDIS
Display of starting time Display range: 00:00 … 24:00 (hh:mm)
If the thermal disinfection option (OTD) is activated and a starting delay time has been adjusted, the adjusted starting time is displayed as SDIS (ashing).
DDIS
Indication of heating period Display range: 00:00 … 24:00 (hh:mm)
If the thermal disinfection option (OTD ) is activated and the heating period is in progress, the remaining time is displayed as CDIS (in hours and minutes), counting backwards.
TIME
Indicates the current clock time.
Î In order to adjust the hours, press button 3 for approx. 2 s. Î Set the hours by pressing buttons 1 and 2. Î In order to adjust the minutes, press button 3. Î Set the minutes by pressing buttons 1 and 2. Î In order to save the adjustments, press button 3.
Operating hours counter
h P / h P1 / h P2
Operating hours counter Display channel
The operating hours counter accumulates the operating hours of the correspond­ing relays (h P / h P1 / h P2).
Full hours are displayed. The accumulated operating hours can be set back to zero. As soon as the operating
hours channel is selected, the symbol is displayed.
Î In order to access the reset mode of the counter, press button 3 for approx. 2 s.
starts ashing and the operating hours value will be set back to zero.
Î In order to nish the reset process, press button 3.
In order to interrupt the reset process, do not press any button for about 5 s. The display returns to the display mode.
en
23
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
6.2 Adjustment channels
System selection
Arr
System selection Adjustment range: 1 … 3 Factory setting: 1
In this channel, a pre-dened system can be selected. Each system has a set of
pre-programmed settings that can be individually changed. If the system selection is changed later on, any previous adjustments which have
been made in the other channels will be lost. Therefore, changing the system is always followed by a security enquiry.
Only conrm the security enquiry if you are sure that you wish to change
the system selection.
Security enquiry
Î In order to conrm the security enquiry, press button 3.
T control
DT O
Switch-on temperature difference Adjustment range: 1.0 … 20.0 K [2.0 … 40.0 °Ra] Factory setting: 6.0 K [12.0 °Ra]
The controller works as a standard differential controller. If the temperature reach­es or exceeds the switch-on temperature difference, the pump switches on. When the temperature difference reaches or falls below the adjusted switch-off tempera­ture difference, the respective relay switches off.
Note
The switch-on temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-off temperature difference.
DT F
Switch-off temperature difference Adjustment range: 0.5 … 19.5 K [1.0 … 39.0 °Ra] Factory setting: 4.0 K [8.0 °Ra]
Note
When the drainback option ODB is activated, the values of the param­eters DT O, DT F and DT S will be adapted to values suiting drainback systems: DT O = 10 K [20 °Ra] DT F = 4 K [8 °Ra] DT S = 15 K [30 °Ra] Adjustments previously made in these channels will be overridden and have to be entered again if ODB is deactivated later on.
Speed control
DT S
Set temperature difference Adjustment range: 1.5 … 30.0 K [3.0 … 60.0 °Ra] Factory setting: 10.0 K [20.0 °Ra]
Note
For pump speed control, the operating mode of the relay 1 must be set to Auto (adjustment channel MAN1).
en
24
Installation Indications, functions and options MessagesCommissioningOperation and function
RIS
Rise Adjustment range: 1 … 20 K [2 … 40 °Ra] Factory setting: 2 K [4 °Ra]
If the temperature difference reaches or exceeds the switch-on temperature differ­ence, the pump switches on at 100% speed for 10 s. Then, the speed is reduced to the minimum pump speed value.
If the temperature difference reaches the adjusted set value, the pump speed in­creases by one step (10 %). The response of the controller can be adapted via the parameter Rise. Each time the difference increases by the adjustable rise value, the pump speed increases by 10 % until the maximum pump speed of 100% is reached. If the temperature difference decreases by the adjustable rise value, pump speed will be decreased by one step.
Note
The set temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-on temperature difference.
Minimum speed
nMN
Minimum speed Adjustment range: 30 … 100 % Factory setting: 30 % If ODB is activated: 50 %
A relative minimum pump speed can be allocated to the output R1 via the adjust­ment channel nMN.
Note
When loads which are not speed-controlled (e. g. valves) are used, the value nMN must be set to 100 % to deactivate pump speed control.
Maximum store temperature
S MX
Maximum store temperature Adjustment range: 4 … 95 °C [40 … 200 °F] Arr 3: 4 … 90 °C [40 … 190 °F] Factory setting: 60 °C [140 °F]
If the store temperature reaches the adjusted maximum temperature, the store will no longer be loaded in order to avoid damage caused by overheating. A hysteresis of 2 K [4 °Ra] is set for the maximum store temperature.
If the maximum store temperature is exceeded, is displayed.
Note
If the collector cooling or the system cooling function is activated, the ad­justed maximum store temperature may be exceeded. In order to prevent system damage, the controller is also equipped with an integrated store emergency shutdown, deactivating the system if the store reaches 95 °C [200 °F].
Store emergency shutdown
OSEM
Store emergency shutdown option Adjustment range: ON, OFF Factory setting: OFF
This option is used for activating the internal store emergency shutdown for an up­per store sensor. If the temperature at the reference sensor exceeds 95 °C [200 °F], the store will be blocked and loading will be stopped until the temperature falls below 90 °C [190 °F].
Note
S3 is used as the reference sensor.
en
25
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Collector emergency shutdown
EM
Collector limit temperature Adjustment range: 80 … 200 °C [170 … 390 °F] Factory setting: 130 °C [270 °F]
When the collector temperature exceeds the adjusted collector limit tempera­ture, the solar pump (R1) switches off in order to protect the system components against overheating (collector emergency shutdown). If the collector limit temper­ature is exceeded, is displayed (ashing).
Note
If the drainback option ODB is activated, the adjustment range of EM is changed to 80 … 120 °C [170 … 250 °F]. The factory setting in that case is 95 °C [200 °F].
Cooling functions
In the following the 3 cooling functions – collector cooling, system cooling and store cooling – are described in detail. The following note is valid for all 3 cooling functions:
Note
The cooling functions will not become active as long as solar loading is possible.
Collector cooling
OCC
Collector cooling option Adjustment range: OFF / ON Factory setting: OFF
CMX
Maximum collector temperature Adjustment range: 70 … 160 °C [150 … 320 °F] Factory setting: 110 °C [230 °F]
The collector cooling function keeps the collector temperature within the operat­ing range by heating the store. If the store temperature reaches 95 °C [200 °F] the function will switch off for safety reasons.
If the store temperature exceeds the adjusted maximum store temperature, the solar system is switched off. If the collector temperature increases to the adjusted maximum collector temperature, the solar pump is activated until the collector temperature falls below the maximum collector temperature. The store temper­ature may then exceed the maximum temperature, but only up to 95 °C [200 °F] (emergency shutdown of the store).
If the collector cooling function is active, and are displayed (ashing).
Note
This function will only be available if the system cooling function (OSYC) is deactivated.
Note
In system 3, the parameter CMX is available without the OCC function. In system 3, CMX is used for setting the activation temperature for the heat dump function. No other switch-on condition is needed in that case.
System cooling
OSYC
System cooling option Adjustment range: OFF / ON Factory setting: OFF
DTCO
Switch-on temperature difference Adjustment range:
1.0 … 30.0 K [2.0 … 60.0 °Ra] Factory setting: 20.0 K [40.0 °Ra]
DTCF
Switch-off temperature difference Adjustment range:
0.5 … 29.5 K [1.0 … 59.0 °Ra] Factory setting: 15.0 K [30.0 °Ra]
en
26
Installation Indications, functions and options MessagesCommissioningOperation and function
The system cooling function aims to keep the solar system operational for a longer time. The function overrides the maximum store temperature to provide thermal
relief of the collector eld and the heat transfer uid on hot days.
If the store temperature is higher than the adjusted maximum store temperature and the switch-on temperature difference DTCO is reached, the solar pump re­mains switched on or will be switched on. Solar loading is continued until either the temperature difference falls below the adjusted value DTCF or the collector limit temperature is reached. If the system cooling function is active, and are displayed (ashing).
Note
This function will only be available, if the collector cooling function (OCC) is deactivated.
Store cooling
OSTC
Store cooling option Adjustment range: OFF / ON Factory setting: OFF
OHOL
Holiday cooling option Adjustment range: OFF / ON Factory setting: OFF
THOL
Holiday cooling temperature Adjustment range: 20 … 80 °C [70 … 175 °F] Factory setting: 40 °C [110 °F]
When the store cooling function is activated, the controller aims to cool down the store during the night in order to prepare it for solar loading on the following day. If the adjusted maximum store temperature S MX is exceeded and the collector temperature falls below the store temperature, the system will be reactivated in order to cool down the store. Cooling will continue until the store temperature has fallen below the adjusted maximum store temperature (S MX) again. A hysteresis of 2 K [4 °Ra] is set for the store cooling function.
Reference threshold temperature differences for the store cooling function are DT O and DT F. If no DHW consumption is expected for a longer period of time, the additional holiday cooling option OHOL can be activated in order to extend the store cool­ing function. The adjustable temperature THOL then replaces the maximum store temperature (S MX) as the switch-off temperature for the store cooling function.
When the holiday cooling function is activated, and (ashing) are shown on the display.
If the holiday cooling function is active, , and are displayed (ashing).
Collector minimum limitation
OCN
Collector minimum limitation option Adjustment range: OFF / ON Factory setting: OFF
CMN
Minimum collector temperature Adjustment range:
10.0 … 90.0 °C [50.0 … 190.0 °F] Factory setting: 10 .0 °C [50.0 °F]
If the collector minimum limitation option is activated, the pump (R1) will only be switched on if the adjustable minimum collector temperature is exceeded. The minimum temperature prevents the pump from being switched on too often at low collector temperatures. A hysteresis of 5 K [10 °Ra] is set for this function.
If the collector minimum limitation is active, is displayed (ashing).
Note
If OSTC or OCF is active, the collector minimum limitation will be over­ridden. In that case, the collector temperature may fall below CMN.
en
27
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Antifreeze function
OCF
Antifreeze option Adjustment range: OFF / ON Factory setting: OFF
CFR
Antifreeze temperature Adjustment range:
-40.0 … +10.0 °C [-40.0 … +50.0 °F]
Factory setting: + 4.0 °C [+ 40.0 °F]
The antifreeze function activates the loading circuit between the collector and the store when the temperature falls below the adjusted antifreeze temperature. This will protect the uid against freezing or coagulating. If the adjusted antifreeze tem­perature is exceeded by 1 K [2 °Ra], the loading circuit will be deactivated.
If the antifreeze function is activated, is displayed. If the antifreeze function is active, and are displayed (ashing).
Note
Since this function uses the limited heat quantity of the store, the anti­freeze function should only be used in regions with few days of tempera­tures around the freezing point. The antifreeze function will be suppressed if the store temperature falls below +5 °C [+40 °F] in order to protect the store from frost damage.
Tube collector function
OTC
Tube collector option Adjustment range: OFF / ON Factory setting: OFF
TCST
Tube collector function starting time Adjustment range: 00:00 … 23:45 Factory setting: 07:00
TCEN
Tube collector function ending time Adjustment range: 00:00 … 23:45 Factory setting: 19:00
TCRU
Tube collector function runtime Adjustment range: 5 … 500 s Factory setting: 30 s
TCIN
Tube collector function standstill interval Adjustment range: 1 … 60 min Factory setting: 30 min
This function is used for improving the switch-on behaviour in systems with non-ideal sensor positions (e. g. with some tube collectors). This function operates within an adjusted time frame. It activates the collector circuit pump for an adjust­able runtime between adjustable standstill intervals in order to compensate for the delayed temperature measurement.
If the runtime is set to more than 10 seconds, the pump will be run at 100 % for
the rst 10 s of the runtime. For the remaining runtime, the pump will be run at
the adjusted minimum speed. If the collector sensor is defective or the collector is blocked, this function is suppressed or switched off.
Note
If the drainback option ODB is activated, TRCU will not be available. In that case, the runtime will be determined by the parameters tFLL and tSTB.
en
28
Installation Indications, functions and options MessagesCommissioningOperation and function
Heat quantity measurement
OHQM
Heat quantity measurement Adjustment range: OFF / ON Factory setting: OFF
FMAX
Flow rate in l/min Adjustment range: 0.5 … 100.0 Factory setting: 6.0
Heat transfer uid:
0: Water 1: Propylene glycol 2: Ethylene glycol 3: Tyfocor
®
LS / G-LS
MEDT
Heat transfer uid
Adjustment range: 0 … 3 Factory setting: 1
MED%
Antifreeze concentration in Vol-% (MED% is not indicated when MEDT 0 or 3 is used.) Adjustment range: 20 … 70 % Factory setting: 45 %
If OHQM is activated, the heat quantity gained can be calculated and displayed. Heat
quantity measurement is possible if a owmeter is used. The heat quantity balancing (estimation) uses the difference between the ow and
return temperatures and the entered ow rate (at 100 % pump speed).
Î Read the ow rate (l/min) and adjust it in the FMAX channel. Î Adjust the antifreeze type and concentration of the heat transfer uid in the
channels MEDT and MED%.
Note
If the system 3 has been selected and OHQM is activated, heat quantity measurement will be interrupted when the 3-port valve switches to the heat dump.
Drainback option
Note
A drainback system requires additional components such as a holding tank. The drainback option should only be activated if all components re­quired are properly installed.
Note
The drainback option is only available in systems 1 and 2.
In a drainback system, the heat transfer uid will ow into a holding tank if solar loading does not take place. The drainback option initiates the lling process if solar
loading is about to start. If the drainback option is activated, the following adjust­ment can be made.
ODB
Drainback option Adjustment range: OFF / ON Factory setting: OFF
Note
If the drainback option is activated, the cooling functions and the antifreeze function will not be available. If one or more than one of these functions have been activated before, they will be deactivated again as soon as ODB is activated. They will remain deactivated, even if ODB is deactivated later on.
Note
If the drainback option ODB is activated, the factory settings of the pa­rameters nMN, DT O, DT F and DT S will be adapted to values suiting drainback systems. Additionally, the adjustment range and the factory setting of the collector emergency shutdown will change. Adjustments previously made in these channels will be overridden and have to be entered again if the drainback option is deactivated later on.
en
29
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Time period – switch-on condition
tDTO
Time period – switch-on condition Adjustment range: 1 … 100 s Factory setting: 60 s
The parameter tDTO is used for adjusting the time period during which the
switch-on condition must be permanently fullled.
Filling time
tFLL
Filling time Adjustment range: 1.0 … 30.0 min Factory setting: 5.0 min
The lling time can be adjusted using the parameter tFLL. During this period, the pump runs at 100 % speed.
Stabilisation
tSTB
Stabilisation Adjustment range: 1.0 … 15.0 min Factory setting: 2.0 min
The parameter tSTB is used for adjusting the time period during which the switch-
off condition will be ignored after the lling time has ended.
Booster function
OBST
Booster function Adjustment range: ON / OFF Factory setting: OFF
This function is used for switching on a second pump when lling the solar system. When solar loading starts, R2 is energised in parallel to R1. After the lling time has
elapsed, R2 switches off.
Note
The booster function is available in system 1 only. The booster function will only be available if the drainback option has been activated.
Operating mode
MAN1 / MAN2
Operating mode Adjustment range: OFF, Auto, On Factory setting: Auto
For control and service work, the operating mode of the relays can be manually adjusted. For this purpose, select the adjustment value MAN1 (for R1) or MAN2 (for R2) in which the following adjustments can be made:
• MAN1 / MAN2
Operating mode OFF : Relay off (ashing) + Auto : Relay in automatic operation ON : Relay on (ashing) + + /
Note
Always adjust the operating mode back to Auto when the control and service work is completed. Normal operation is not possible in manual mode.
en
30
Installation Indications, functions and options MessagesCommissioningOperation and function
HE pump control
ADA1
HE pump control via adapter Adjustment range: ON, OFF Factory setting: OFF
This option is used for controlling a high-efciency pump via a VBus
®
/ PWM adapter. The power supply of the pump is carried out via the semiconductor relay R1. For pump speed control with activated ADA1 option, the relay is switched on or off (no burst control). Temperature dependent speed information is transmitted via the VBus®. The relay will remain deactivated for 1 hour after its switch-off conditions
have been fullled (pump protection).
Language
LANG
Language selection Selection: dE, En, Fr Factory setting: dE
In this adjustment channel the menu language can be selected.
• dE : Deutsch
• En : English
• Fr : French
Unit
UNIT
Temperature unit selection Selection: °F, °C Factory setting: °C
In this adjustment channel, the display unit for temperatures and temperature differ­ences can be selected. The unit can be switched between °C / K and °F / °Ra during operation.
Temperatures and temperature differences in °F and °Ra are displayed without units. If the indication is set to °C, the units are displayed with the values.
Reset
RESE
Reset function By means of the reset function, all adjustments can be set back to their factory
settings.
Î In order to carry out a reset, press button 3. All adjustments that have previously been made will be lost! For this reason, a secu­rity enquiry will appear after the reset function has been selected. Only conrm the security enquiry if you are sure you want to set back all adjust­ment to the factory setting.
Security enquiry
Î In order to conrm the security enquiry, press button 3.
Note
After a reset, the commissioning menu will start again (see page18).
en
31
InstallationIndications, functions and optionsMessages Commissioning Operation and function
If a malfunction occurs, the display symbols will indicate an error code:
T4A fuse
°C °F Ω °C °F Ω
-10 14 961 55 131 1213
-5 23 980 60 140 1232
0 32 1000 65 149 1252
5 41 1019 70 158 1271
10 50 1039 75 167 1290
15 59 1058 80 176 1309
20 68 1078 85 185 1328
25 77 1097 90 194 1347
30 86 1117 95 203 1366
35 95 1136 100 212 1385
40 104 1155 105 221 1404
45 113 1175 110 230 1423
50 122 1194 115 239 1442
Resistance values of Pt1000 sensors
The symbol is indicated on the display and the symbol ashes.
Sensor fault. An error code instead of a temperature is shown on the sensor
display channel.
Disconnected Pt1000 temperature sensors can be checked with an ohmmeter.
Please check the resistance values correspond with the table.
Cable is broken. Check the cable.
Short circuit. Check the cable.
- 88.8888.8
Operating control LED is permanently off.
Check the power supply of the controller. Is it disconnected?
no
The fuse of the controller could be blown. The fuse holder (which holds the spare fuse) becomes accessible when the cover is removed.The fuse can then be replaced.
yes
Check the supply line and recon-
nect it.
Note
For answers to frequently asked questions (FAQ) see www.resol.com.
7 Troubleshooting
en
32
Installation Indications, functions and options MessagesCommissioningOperation and function
Pump starts for a short moment, switches off, switches on again, etc.
Temperature difference at the
controller too small?
no yes
Wrong position of collector
sensors?
yes
Change Ton and Toff corre-
spondingly.
Mount the collector sensor at
solar ow (warmest collector
output); use immersion sleeve of the respective collector.
no
Plausibility control of the option
tube collector function
o.k.no
Pump is overheated, but no heat transfer from the collector to the store, ow
and return have the same temperature; perhaps also bubbling in the lines.
Vent the system; increase the system pressure to a static primary pressure of at least plus 0.5 bar [7.25 psi]; if necessary continue to increase the pressure; switch the
pump on and off for a short time.
Air or gas bubbles in the system?
no yes
Are the valves or the non-return
valves defective or is the dirt trap
blocked?
yes
Clean the dirt trap or replace defective component
Pump starts up very late.
The temperature difference between store and collector increases enormously
during operation; the collector circuit cannot dissipate the heat.
Collector circuit pump / zone valve
defective?
no yes
Heat exchanger calcied?
yes
Check or replace, if necessary
Decalcify it
no
Heat exchanger blocked?
yesno
Clean it
Heat exchanger too small?
yes
Replace with correctly sized one.
Change Ton and Toff corre-
spondingly.
Switch-on temperature difference
Ton too large?
no yes
Non-ideal position of the collector
sensor (e. g. atscrew sensor instead
of sensor in immersion sleeves)?
Put the solar pump (R1) into the manual mode On for a short time during irradiation. Check whether the collector temperature signi­cantly increases.
yes
o.k.
no
Minimum limitation active
en
33
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Stores cool down at night.
Collector circuit pump runs during
the night?
no yes
Check the controller.
Collector temperature at night is
higher than the outdoor temperature.
no yes
Check the non-return valves in
the ow and the return pipe for functional efciency.
Sufcient store insulation?
yes no
Increase insulation.
Insulation close enough to the
store?
yes no
Replace insulation or increase it.
Are the store connections insulated?
yes no
Insulate the connections.
Warm water outow upwards?
no yes
Change connection and let the
water ow sidewards or through
a siphon (downwards); less store losses now?
Does the DHW circulation run for
a very long time?
no yes
Use the circulation pump with
timer and switch-off thermostat
(energy-efcient circulation).
Circulation pump and blocking valve should be switched off for 1 night; less store losses?
yes no
Check whether the pumps of the after-heating circuit run at night; check whether the non-return valve is defective; problem solved?
no
no yes
o.k.
Check the non-return valve in warm
water circulation - o.k.
yes no
Further pumps which are connect­ed to the solar store must also be checked.
The gravitation circulation in the circulation line is too strong; insert a stronger valve in the non-return valve or an electrical 2-port valve behind the circulation pump; the 2-port valve is open when the pump
Clean or replace it.
is activated, otherwise it is closed; connect pump and 2-port valve electrically in parallel; activate the circulation again. Deactivate pump speed control!
The solar circuit pump does not work, although the collector is considerably
warmer than the store.
Is the display working?
yes no
Does the pump start up in manual
operation?
yes
There is no current; check fuses /
replace them and check power
supply.
The adjusted temperature differ-
ence for starting the pump is to high; choose a value which makes more sense.
no
Is the pump current enabled by the
controller?
yes
Is the pump stuck?
Turn the pump shaft using a screw-
driver; now passable?
Pump is defective - replace it.
Controller fuse ok?
Controller might be defective -
replace it.
no
yes
no
no yes
Replace fuse
a
a
b
b
34
en
8 Accessories
Sensors
Overvoltage protection
device
SD3 Smart Display /
GA3 Large Display
AM1 Alarm Module
DL3 Datalogger
DL2 Datalogger
RESOL VBus® / USB & VBus® / LAN
interface adapters
35
en
8.1 Sensors and measuring instruments
Temperature sensors
The product range includes high-precision platinum temperature sensors, atscrew
sensors, outdoor temperature sensors, indoor temperature sensors, cylindrical clip­on sensors, also as complete sensors with immersion sleeve.
Order information can be fount in our catalogue and on our website.
Overvoltage protection device
In order to avoid overvoltage damage at collector sensors (e. g. caused by local lightning storms), we recommend installing the overvoltage protection RESOL SP10.
8.2 VBus
®
accessories
SD3 Smart Display
The RESOL Smart Display is designed for simple connection to RESOL controllers with RESOL VBus
®
. It is used for visualising data issued by the controller: collector temperature, store temperature and energy yield of the solar thermal system. The use of high-efciency LEDs and lter glass assures a high optical brilliance. An addi­tional power supply is not required.
GA3 Large Display module
The GA3 is a completely mounted large display module for visualisation of collec­tor- and store temperatures as well as the heat quantity yield of the solar system via one 6-digit and two 4-digit 7-segment-displays. An easy connection to all controllers with RESOL VBus
®
is possible. The front plate is made of antireective lterglass and
is printed with a light-resistant UV-lacquering. The universal RESOL VBus® allows the parallel connection of 8 large displays as well as additional VBus® modules.
AM1 Alarm Module
The AM1 Alarm Module is designed to signal system failures. It is to be connected to the VBus
®
of the controller and issues an optical signal via the red LED if a failure has occurred. The AM1 also has a relay output, which can e. g. be connected to a building management system (BMS). Thus, a collective error message can be issued in the case of a system failure.
The AM1 Alarm module ensures that occurring failures can be immediately recog-
nised and repaired, even if the system and the controller are difcult to access or
located in a remote place. Thus, the reliability and the stable yield of the system are ensured.
DL2 Datalogger
This additional module enables the acquisition and storage of large amounts of data (such as measuring and balance values of the solar system) over a long period of time. System access is possible with just a few clicks via the VBus.net Internet portal. For transmission of the data stored in the internal memory of the DL2 to a PC, an SD card can be used.
The DL2 is appropriate for all controllers with RESOL VBus
®
. It can be connected directly to a PC or router for remote access and thus enables comfortable system monitoring for yield monitoring or for diagnostics of faults.
DL3 Datalogger
Be it solar thermal, heating or DHW heat exchange controllers – with the DL3 you can easily and conveniently log system data. Get a comprehensive overview of all controllers connected with the large full graphic display.
Transfer data with an SD memory card, or use the LAN interface to view and pro­cess data on your PC. System access is possible with just a few clicks via the VBus. net Internet portal.
8.3 Interface adapters
VBus
®
/ USB interface adapter
The VBus
®
/ USB interface adapter is the interface between the controller and a personal computer. With its standard mini USB port it enables a fast transmission of system data for processing, visualising and archiving as well as the parametrisation of the controller via the VBus®. The RESOL ServiceCenter software is included.
VBus
®
/ LAN interface adapter
The VBus
®
/ LAN interface adapter is designed for the direct connection of the controller to a PC or router. It enables easy access to the controller via the local network of the owner. Thus, controller access, system parameterisation and data charting can be effected from every workstation of the network. The VBus® / LAN interface adapter is suitable for all controllers equipped with a RESOL VBus®. The RESOL ServiceCenter software is included.
36
en
9 Index
A
Accessories.................................................................................................................... 34
, 35
Afterheating ......................................................................................................................... 12
Antifreeze function ............................................................................................................ 27
B
Booster function ................................................................................................................ 29
C
Code ..................................................................................................................................... 31
Collector cooling ............................................................................................................... 25
Collector emergency shutdown ..................................................................................... 25
Commissioning ................................................................................................................... 18
Cooling functions ............................................................................................................... 25
D
T control ........................................................................................................................... 23
Data communication / Bus ................................................................................................... 7
Diaplays ................................................................................................................................ 17
Drainback option ............................................................................................................... 28
E
Electrical connection ............................................................................................................ 6
H
Heat quantity measurement ............................................................................................ 28
HE pump control ............................................................................................................... 30
Holiday cooling option ...................................................................................................... 26
L
Language ............................................................................................................................... 30
M
Manual mode ....................................................................................................................... 29
Minimum and maximum temperatures ......................................................................... 26
Minimum collector limitation .......................................................................................... 26
Minimum collector temperature .................................................................................... 26
Monitoring-Display ............................................................................................................ 16
Mounting ................................................................................................................................. 5
O
Operating mode ................................................................................................................. 29
S
Sensor type .......................................................................................................................... 21
Speed control ...................................................................................................................... 23
Store cooling ....................................................................................................................... 26
System overview ................................................................................................................... 7
T
Technical data ......................................................................................................................... 4
Thermal disinfection .......................................................................................................... 13
Thermostat function ......................................................................................................... 12
Time ...................................................................................................................................... 18
Troubleshooting .................................................................................................................. 31
Tube collector function..................................................................................................... 27
U
Unit........................................................................................................................................ 30
37
en
38
en
39
en
Distributed by: RESOL – Elektronische Regelungen GmbH
Heiskampstraße 10 45527 Hattingen / Germany
Tel.: +49 (0) 23 24 / 96 48 - 0 Fax: +49 (0) 23 24 / 96 48 - 755
www.resol.com info@resol.com
Important note
The texts and drawings in this manual are correct to the best of our knowledge. As faults can never be excluded, please note:
Your own calculations and plans, under consideration of the current standards and directions should only be basis for your projects. We do not offer a guarantee for the completeness of the drawings and texts of this manual - they only represent some examples. They can only be used at your own risk. No liability is assumed for incorrect, incomplete or false information and / or the resulting damages.
Note
The design and the specications can be changed without notice.
The illustrations may differ from the original product.