Reo Elektronik REOTRON MEW Operating Instructions Manual

REOTRON MEW
Single Phase Power Controller
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
REO UK LTD Publication No.: 2022_GBANL.doc
Units 8 -10 Long Lane Industrial Estate 08/99 Craven Arms, Shropshire SY7 8DU Tel: 01588 673411 Fax: 01588 672718 http://www.reo.co.uk eMail: main@reo.co.uk
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Technical Safety Information for the User
This description co nta ins th e nec es s ar y inf ormation for the correct app lication of the product desc r ibe d below. It is intended for use by technically qualified personal.
Qualified personnel are persons who, because of their training, experience and position as well as their knowledge of appropriate standards, regulations, health and safety requirements and working conditions, are authorised to be responsible for the safety of the equipment, at all times, whilst carrying out their normal duties and are therefore aware of, and can report, possible hazards (Definition of specialist according to IEC 364).
Safety Instructions
The following instr uctions are provided for the personal safety of operators and also for the
!
protection of the described product and connected equipment.
Warning! Hazardous Voltage Failure to observe can kill, cause serious injury or damage
Isolate from mains before installation or dismantling work, as well as for fuse changes or post installation modifications.
Observe the prescribed accident prevention and safety rules for the specific application.
Before putting into operation check if the rated voltage for the unit conforms with the local
supply voltage.
Emergency stop devices must be provided for all applications. Operation of the emergency stop must inhibit any further uncontrolled operation.
Prescribed Use The units described herein are electrically powered for use in industrial applications. They are
designed for power adjustment of resistive or inductive loads.
REO UK LTD 2
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Contents Page
1.0 General 4
2.0 Function Description 4
2.1 Effective Current Value 5
2.2 Effective Voltage Value 5
2.3 Current Regulation 5
2.4 Voltage Regulation 5
2.5 Pulse Generation 5
2.6 Temperature Monitoring 5
3.0 Control Inputs and Outputs 5
3.1 Setpoint Input U 6
3.2 Setpoint Input I 6
3.3 Enable (Regulator Inhibit) 6
3.4 Actual Voltage Output (Option) 6
3.5 Actual Current Output (Option) 6
3.6 Fault Indication 6
4.0 Construction 6
5.0 Adjustment Facilities 7
6.0 Adjustment Instructions 7
7.0 Technical Data 9
8.0 Ordering Codes 10
9.0 Adjustment Components 11
10.0 Fuse Change 12
11.0 Installation Guidelines 12
12.0 Guidelines on Electromagnetic Interference 12
13.0 Connection Diagrams 13
14.0 Dimension Drawing 14
14.1 Dimension Drawing MEW 150/XXX 15
REO UK LTD 3
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
1.0 General
The range of REOTRON MEW Thyristor Regulat ors are microprocessor based units for controll ing the power to resisti ve and inductive loads . In essence the units comprise inverse para llel connected power semiconductors (thyristors) and the control and regulation electronics. The units have a regulated, AC output. The inverse parallel connected thyristors operate as contact free, power controllers using the ph ase angle control or the f ull wave principles. In t he phase angle control m ode (symetrical load) the equipment can be used as a voltage or current regulator and also there is an option for power regulation. The set point value for the current and voltage can be provided by an external control vo ltage of 0-10 V, 0-20 mA, DC or a potentiom eter. The lowest set point has priority. The effective value is f ed back internall y from a voltage or curr ent transformer. The m aximum current limit of the unit c annot be exceeded in a ll regulation modes , using phase angle control. Applications with a wide load resistance variation Rcold/Rwarm are possible, and an overloading of the unit is prevented.
Typical Applications Industrial Ovens Steam Generators Lighting Installations
Infra Red Emitters (Dryers) Preheating Plants Air Conditioning Plant Tunnel Heaters Room Heating Equipment Fan Heating Systems Plastic Moulding Equipment Extruders
2.0 Function description
Mains connection
L1 L2 (N)
F1
The MEW thyristor contro l unit was desig ned to oper ate with a symetrical load. Th ey include a voltage and current regu lator. In the voltage regulation m ode the output voltage determ ined by the set point is held constant by an internal circuit, therefore load or mains variations have no influence on the output
PULSE GENERATION
R
C
voltage. The selected maximum current, however, cannot be exceeded in this mode (current limiting). If the unit is used as a current regulator then the output current of the unit is compared with the setpoint and regulated accordingly. The
Fault
output voltage can incr ease to the selected voltage set point. LED's illuminate if the limit Imax or adjustment limits are exceeded. If both set points are adjusted during operation, th e regulator always gives the lower set point priority. During voltage
Actual Current Actual Voltage
Actual Output (Option)
regulation, with underlying current regulation, the voltage regulation is alwa ys in operation providing the a llowed current limit is not exceeded. If the current limit is reached then the current regulator has priority. Should the unit be used as a pure voltage or current r egulator, the other availa ble set point must be linked to the reference voltage (10V DC).
Current Setpoint Voltage Setpoint Enable
Control Electronics
I
U
Output
REO UK LTD 4
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
2.1 Effective Current Value The effective current value is measured inside the u nit through a current transformer and a burden
resistor. The interna l microprocess or determines the ef fective value of th e output current and adjusts this using a PI regulator.
2.2 Effective Voltage Value The effective vo ltage value is also meas ured internally using a v oltage transformer and the effective
value is controlled by the microprocessor using a PI regulator.
2.3 Current Regulator Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using
trimmer P4. The units m aximum output cur rent (Rated Current) is factor y set. If the thyristor controller is to be adapted for a small load current, then a correction can be made by using trimmer Imax. BEWARE: It is possible t o obtain an outpu t current which is higher than the rat ed current bec ause of component and manuf acturing tolerances, however, for s afety, it is essential that the current lim it is not set higher than the rated current In current regulation mode the LED Imax is permanently illuminated.
2.4 Voltage Regulator Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using
trimmer P3. The units maximum voltage output is factory set to the rated voltage (for 100% set point). Therefore, the setpoint cannot be f ully used during voltage regulation s ince this would not allow for any over voltage. In this oper ating mode ( voltage regulation) ei ther the setpoint m ust be limited or the maximum unit output voltage must be reduced by using the trimmer Umax.
2.5 Pulse Generation The pulses required f or the control of the thyristors are generated by the m icroprocessor and are fed
to amplifiers prior t o the pulse conductors. The sec ondary windings of the pulse cond uctors directly control the thyristors.
2.6 Temperature Monitoring A temperature switc h is fitted into the heat sink to monitor its temperature and this switches off the
thyristor controller , permanently, if the tem perature exceeds a maxim um of 80oC. Fault indication is provided by the general fault relay and displayed by the LED on the front panel.
3.0 Control Inputs and Outputs Control Inputs
Setpoint Input U 0(4)...20 mA, 0-10V DC or Potentiometer 10k Setpoint Input I 0(4)...20 mA, 0-10V DC or Potentiometer 10k Enable 12-24V DC or contacts
Outputs: Effective Current Value 0-10V DC corresponding to 0-100% (Option) Effective Voltage Value 0-10V DC corresponding to 0-100% (Option) Fault Indication Relay Contact 250V/1A (Change over)
REO UK LTD 5
(
)
g
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
3.1 Setpoint Input U
With power regulation here the power setpoint is determined
switch S1/6=ON
The value of the outp ut voltage is determ ined by the s etpoint inp ut U. The setp oint can b e provided in the form of 0-10 V, 0-20mA, DC or with a 10k Potentiometer. A +10V ref erence voltage is prov ided for potentiometer operation.
With setpoint 4...20 mA, put the switch “S1/5” to “ON”.
3.2 Setpoint Input I
The strength of the output current is determined by the set point input "I". The setpoint can be provided in the form of 0-10 V, 0- 20mA, DC or wit h a 10k Potentiom eter. A +10V r eference vo ltage is pro vided for potentiometer operation.
With setpoint 4...20 mA, put the switch “S1/5” to “ON”.
3.3 Enable (Regulator Inhibit)
A control voltage (12-24V DC) must be applied to terminals 9+ and 15-, to enable the unit, or a connection made between terminals 9 and 10 by using a switch. A permanent link between terminals 9 and 10 is used for operation without an external enable. The firing pulses are inhibited whilst the enable input is not closed.
3.4 Actual Voltage Output (Option)
With power regulation the actual power is given instead of the actual volta
e.
A 0-10 V DC output signal is pr ovided and this corresponds to the units m omentary voltage output. This generates 10V for 100% of the units possible output voltage (using the Umax set value).
3.5 Actual Current Output (Option)
A 0-10 V DC output signal is provided and this cor responds to the units mom entary current output. This generates 10V for 100% of the units possible output current (using the Imax set value).
3.6 Fault Indication
Relay changeover contacts are provided for indicating that there has been a unit fault. The following fault conditions energise the relay and cause the unit to switch off: Over temperature of the power unit Mains synchronisation not possible A fault condition must be cancelled with the RESET push button.
4.0 Construction The thyristor regulator un it is a completely wired, function tes ted, compact unit. The unit is des igned
for panel mounting. T he co nnections for th e m ains s uppl y and l oad ar e bro ught out t o scr ew term inals and the control signals to plug-in screw terminals. The unit front panel incorporates the adjustment components (trimmers, switch and light diodes) to display and control the operating conditions. The fuses for protecting th e sem iconductors is built into the f ront panel are ac cessed b y removin g the front panel.
REO UK LTD 6
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
5.0 Adjustment Facilities The following parameters can be adjusted on the unit:­ Umax - Maximum Output Voltage Umin - Minimum Output Voltage Imax - Maximum Output Current Imin - Minimum Output Current P - Characteristic of the Voltage Regulator P - Characteristic of the Current Regulator Ramp up time Ramp down time The trimmers are adjustable through the front panel.
6.0 Adjustment Instructions Preparatory Steps
Connect unit according to connection drawing, disconnect the enable and adjust set point to zero. The unit will now operate with the basic factory settings: output curr ent = rated current,
output voltage = rated in put voltage1), Umin = 0, phase angle control, regulation mode. The setpoint control c urve can be det ermined by using trimmers Umin/Umax and Imin/Imax ie the setpoint control range. At this stage, it is also possible, to make permanent adjustments, without external setpoints. The range minimum always ex tends from zero to the adjusted range maximum. The maximum value must be set first.
Adjustment of the MAX - Values Umax Hint: If the output voltage is to be regulated at the maximum set point, then the maximum output
voltage must be limited at a value which reduces the regulation range. Switch on the m ains voltag e and enab le the uni t. Set the cur rent set po int to m axim um. Now increase the voltage set point unti l the required output voltage level is reached (obs erve current lim it indicator) . If the set point source is no t yet at m aximum , then the output volt age must be reduced ag ain by using trimmer Umax and then t he voltage s et point can be further incr eased until the maximum value of the voltage set point is ac hieved. If there is no risk of dam aging the load with an over voltage th en the output voltage can be set by using trimmer Umax with the set point turned fully up. Anticlockwise adjustment increases the output voltage.
Imax Remove the unit enable. Adjust voltage set point to maximum and current setpoint to zero. Turn trimmer Imax fully clockwise (10 turn pot). Next enable the unit and adjust the current setpoint to maximum. Set the maximum current value by turning trimmer Imax anti-clockwise.
REO UK LTD 7
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Adjustment of the MIN - Values: Umin
Trimmers P1 and P2 ar e used to adjust the MIN va lue, however these trim mers are used for vari ous other functions. Below is the recommended adjustment procedure.
Set rotary switch 'S2' on the f ront panel to pos ition '1' and press the RES ET butto n. Next adjust the trimmers P1 (coarse) and P2 (fine) to the required minimum voltage and afterwards press th e SETUP button. T o return to normal operat ion put the r otary switch 'S2' back to '0' and press the RESET button.
Imin This adjustment is only meaningful for pure current contro l, if a current f ree condition of the loa d is to be avoided. This adjustment is als o carried out by using trimm ers P1 and P2. Set rotary switch 'S2' o n the front
panel to position '2' and pres s the RESET button. Next adjust the trimmers P1 (c oarse) and P2 (fine) to the requir ed minimum current and af terwards press the S ETUP button. To return to normal op eration put th e rotar y switch 'S2' bac k to '0' and pres s the RES ET button.
Ramp up /down times The ramp up time f or when the unit is switched o n, using the enable input ( set point 100%) or when the set point sudden ly rises, giving 0 to 1 00% of the maximum output value, and also t he run down time to reach an output value for a set point change in the direction of zero. This adjustment is similarly achieved using the trimmer P1 for Ramp up and P2 for Ramp down times. With the voltage set point at zero and the current set point at maximum. Set rotary switch 'S2' on the front panel to position '3' and press the RESET button. Next set the
required ram p time (0.1-10s) using trimmer P1 and test for a set point change from zero to 100%; afterwards set the ramp down time with trimmer P2 and again test by changing the set point. W hen the required val ues have been chosen, once again press the "SETUP" button, return rotary switch 'S2' back to '0' and press the RESET button.
Proportional Characteristic Voltage Regulation The speed of regulation (sensitivity) of the voltage regulator. Adjust, using the actual load, using trimmer P3.
Proportional Characteristic Current Regulation The speed of regulation (sensitivity) of the current regulator. Adjust, using the actual load, using trimmer P4.
Hint To return the unit to the factory settings, the procedure is as follows:­Rotate selector switch "S2" to position "F" an d press the RESET butto n. After wards press the SETUP button and return select or switch "S2" to position "0" and press the RE SET button once more. The factory settings are now reinstated.
Selector Switch S1 (Operating Mode)
S1/1 OFF = Phase angle control ON = Full wave control
1 2
3 4 5 6 7 8
OFF
S1/2 not active S1/3 not active S1/4 not active S1/5 OFF = 0...20 mA ON = 4...20 mA (Setpoint) S1/6 OFF = U/I - Regulation ON = Power Regulation S1/7 OFF = Without data interface ON = with data interface S1/8 OFF = Reserved
ON
The RESET button must be pressed before a change of the switch settings.
REO UK LTD 8
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
7.0 Technical Data
TYPE Rated Voltage Output Voltage2) Output Current 50/60 Hz MAX.
MEW 10/230 230 V +6% -10% 0-230 V 10 A MEW 10/400 400 V +6% -10% 0-400 V 10 A MEW 20/230 230 V +6% -10% 0-230 V 20 A MEW 20/400 400 V +6% -10% 0-400 V 20 A MEW 50/230 230 V +6% -10% 0-230 V 50 A MEW 50/400 400 V +6% -10% 0-400 V 50 A MEW 80/230 230 V +6% -10% 0-230 V 80 A MEW 80/400 400 V +6% -10% 0-400 V 80 A MEW 110/230 230 V +6% -10% 0-230 V 110 A MEW 110/400 400 V +6% -10% 0-400 V 110 A MEW 150/400 400 V +6% -10% 0-400 V 150 A
Load Types resistive / resistive - inductive; for transformers max. induction 1,45 Tesla Setpoint source 5 / 10 k Potentiometer
0-10V, DC 0-20 mA
Ramp up/down time 0,1 - 10 sec. Enable Switch 12-24 V, DC Actual value output I 0-10 V, DC
Actual value output U 0-10 V, DC Fault relay 1 change over contacts 250 V, 1 A Ambient temp. 0-45 °C Dimensions approx. (HxBxD) MEW 10/XXX MEW 20/XXX MEW 50/XXX MEW 80/XXX MEW110/XXX MEW150/XXX 290x70x205 290x110x205 290x110x205 320x150x205 320x180x205 320x180x205
2)
The output voltage is subject to a voltage loss across the semiconductors.
REO UK LTD 9
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
8.0 Ordering Codes
Type ID-Number Description
REOTRON MEW 10/230 6311 10 A/230 V Standard unit REOTRON MEW 10/400 6312 10 A/400 V Standard unit REOTRON MEW 10/230 DA 6316 10 A/400 V with D/A-Module REOTRON MEW 10/400 DA 6317 10 A/400 V with D/A-Module REOTRON MEW 10/230 RS 6315 10 A/400 V with RS 232 Interface REOTRON MEW 10/400 RS 6318 10 A/400 V with RS 232 Interface REOTRON MEW 10/230 IS 6313 10 A/400 V with INTERBUS-S Interface REOTRON MEW 10/400 IS 6314 10 A/400 V with INTERBUS-S Interface REOTRON MEW 20/230 6321 20 A/230 V Standard unit REOTRON MEW 20/400 6322 20 A/400 V Standard unit REOTRON MEW 20/230 DA 6328 20 A/230 V with D/A-Module REOTRON MEW 20/400 DA 6327 20 A/400 V with D/A-Module REOTRON MEW 20/230 RS 6329 20 A/230 V with RS 232 Interface REOTRON MEW 20/400 RS 63210 20 A/400 V with RS 232 Interface REOTRON MEW 20/230 IS 6324 20 A/230 V with INTERBUS-S Interface REOTRON MEW 20/400 IS 6325 20 A/400V with INTERBUS-S Interface REOTRON MEW 50/230 6331 50 A/230 V Standard unit REOTRON MEW 50/400 6332 50 A/400 V Standard unit REOTRON MEW 50/230 DA 6338 50 A/230 V with D/A-Module REOTRON MEW 50/400 DA 6337 50 A/400 V with D/A-Module REOTRON MEW 50/230 RS 6339 50 A/230 V with RS 232 Interface REOTRON MEW 50/400 RS 63310 50 A/400 V with RS 232 Interface REOTRON MEW 50/230 IS 6333 50 A/400 V with INTERBUS-S Interface REOTRON MEW 50/400 IS 6334 50 A/400 V with INTERBUS-S Interface REOTRON MEW 80/230 6341 80 A/230 V Standard unit REOTRON MEW 80/400 6342 80 A/400 V Standard unit REOTRON MEW 80/230 DA 6348 80 A/230 V with D/A-Module REOTRON MEW 80/400 DA 6347 80 A/400 V with D/A-Module REOTRON MEW 80/230 RS 63410 80 A/400 V with RS 232 Interface REOTRON MEW 80/400 RS 6349 80 A/400 V with RS 232 Interface REOTRON MEW 80/230 IS 6343 80 A/400 V with INTERBUS-S Interface REOTRON MEW 80/400 IS 6344 80 A/400 V with INTERBUS-S Interface REOTRON MEW 110/230 6351 110 A/230 V Standard unit REOTRON MEW 110/400 6352 110 A/400 V Standard unit REOTRON MEW 110/230 DA 6358 110 A/4 00 V with D/A- M od ule REOTRON MEW 110/400 DA 6357 110 A/4 00 V with D/A- M od ule REOTRON MEW 110/230 RS 6355 110 A/4 00 V with RS 232 I nterf ac e REOTRON MEW 110/400 RS 6356 110 A/4 00 V with RS 232 I nterf ac e REOTRON MEW 110/230 IS 6353 110 A/400 V with INTERBUS-S Interface REOTRON MEW 110/400 IS 6354 110 A/400 V with INTERBUS-S Interface REOTRON MEW 150/400 DA 2057 150 A/4 00 V with D/A- M od ule
REO UK LTD 10
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
9.0 Adjustment Components
LED Indicator Functions
ERROR System fault TEMP Over temperature SYNC Mains synchronisation fault I-Max Current limit reached ie current regulator active
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
LOAD Impedance fault / peak current reached MAX Max. a djustment limit reached INIT Initialisation phase READY Ready to operate ENABLE Enable IN1 External Input 1 (Reserved) IN2 External Input 2 (Reserved)
S2 S2 = 1 S2 = 2 S2=3 P1 =Umin/coarse
P2 = Umin/fine
Imin/coarse Imin/fine
Ramp up Ramp down times
P3 = P-Characteristic voltage regulator P4 = P-Characteristic current regualtor
Selector Switch S1 S1/1 - OFF = Phase angle control ON = Full wave control
S1/2 - S1/3 - Reserved for curent controller S1/4 - S1/5 – OFF = 0...20 mA ON = 4...20 mA (Setpoint) S1/6 - OFF = I/U-Regulation ON = Power regulation S1/7 - OFF = without data interface ON = with data interface S1/8 - OFF = Reserved
Selector Switch S2 0 = Normal operation (Regulator)
1 = Adjus tment Umin 2 = Adjustment Imin 3 = Adjustment ramp up/down times 4 = Reserved 5 = Uncontrolled operation (no regulation / no current limiting) 6-E = Reserved F = Reinstate factory settings
ERROR TEMP
SYNC I-max LOAD MAX INIT READY ENABLE IN1 IN2
P1
P2
P3
P4
1 2 3 4
S1
5 6 7 8
ONOFF
U-max
I-max
4
5
3
6
2
7
1
8
0
S2
9
F
A
E
B
D
C
RESET
SETUP
RESET = System reset-Button SETUP = Enter new parameters
REOTR ON
MEW
REO UK LTD 11
Operating Instructions REOTRON MEW
10.0 Fuse change
Switch unit off before changing fuse!
!
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
The semiconductor f use can be found in the left han d section of the f ront panel. T o change the fuse the two screws marked "x" must be loosened. The cover can then be removed by sliding it to the right. For MEW/xxx type units the fuse can be found in the front panel.
Fuse Types: MEW 10/xxx FF 16
MEW 20/xxx ET 35 MEW 50/xxx ET 80 MEW 80/xxx EET 140 MEW 110/xxx EET 160 MEW 150/xxx 6.6 URB 000 BS88/250
When ordering spare fuses use capital letters for fuse types.
11.0 Installation Guidelines The unit is desi gned for p anel m ounting. It sho uld be i nstalled ver tically wit h the t erminals at
the bottom. Ensure that there is sufficient air space in unventilated cabinets. The units can be place d side by side with a minimum clearanc e of 30mm. If the units are mounted one over the other, then there must be a clearance of approximately 250mm.
The control cables should be shielded and the shield should be connected to earth.
12.0 Guidelines on Electromagnetic Interference
INTERBUS-S is a serial data transfer system which was conceived for app lications in an industrial environment. When correctly installed, INTERBUS-S complies with all the requirements specified in the standard IEC 801 for data trans fer system s in a harsh in dustrial enviro nment. W hen the interface module is used in an electromagnetic, interference prone, area, then the possible sources of interference should be suppressed. Interference can be due, in particu lar, to:
Protection devices
Switching of inductive loads
Solenoid valves
RC networks and var istors suppress interference. Ma nufacturers supply correctly si zed components for suppressing solenoid coils. Electrical spikes, which can affect bus cables in an industrial environment, can be suppressed by a correctly fitted screen. The following measures provide the best screening results:
Cover fixing screws of bus cable plugs and conductors at equal potentials.
Only use connectors with a metal or metalised housing.
Spread out the screen in connectors.
REO UK LTD 12
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
13.0 Connection Diagrams
Control Terminals
00 1 2 34 5 6 7 8 910
Voltage setpoint Current setpoint Enable (Power setpoint)
+10V +10V
10k 10k
Potentiometer setpoint source
12 345678910
00+++
0 - 20mA 0 - 20mA Setpoint Voltage Setpoint Current
(Power setpoint)
Enable 24V, DC
(to terminal 15)
12 345678910
00++
0 - 10V, DC 0 - 10V, DC Setpoint Voltage Setpoint Current
(Setpoint power)
Setpoint source using 0-10 V, DC control voltage
11 12
0 - 10V 0 - 10V
Actual value Voltage
(Actual value power)
13
14 15 16 17 18 19 20
00++
Actual value Current
(Optional)
NC C NO
Enable
Setpoint source using 0-20 mA control current
Power terminals
230V, 50/60Hz 400V, 50/60Hz
L1 (L) L2 (N)
PE
21 22 23 24 25 26
L1 L2 PE PE V U(N)(L) (N) (U)
Load
REO UK LTD 13
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
14.0 Dimensions
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
P1
ERROR TEMP
SYNC I-max LOAD MAX INIT READY ENABLE IN1
e
IN2
P2
P3
P4
1 2 3 4
S1
5 6 7 8
ONOFF
U-max
I-max
4
5
3
6
2
7
1
8
0
S2
9
F
A
E
B
D
C
RESET
SETUP
d
REOTRON
MEW
a
b
c
x
205
Dimension MEW10 MEW20 MEW50 MEW80 MEW110
a - 70 70 60 90 b 35 15 15 30 30 c 70 110 110 150 180 d 290 290 290 320 320 e 280 280 280 304 304 x - 5 5 5 10
REO UK LTD 14
Operating Instructions REOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
14.1 Dimensions MEW 150/XXX
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
P1
P2
P3
P4
1 2 3 4
S1
5 6 7 8
ONOFF
U-max
I-max
4
7
1
8
S2
F
RESET
SETUP
320
290
FOR CONTINUED FIRE PROTECTION REPLACE ONLY WITH SPECIFIED TYPE AND RATED FUSE
DISCONNEC T POWER INPUT BEFORE REPLACING F USE
ERROR TEMP SYNC I-max LOAD
MAX INIT READY
ENABLE IN1 IN2
REOTRON
MEW
90
180
2
21
22
5
11 12 13 14 15 16 17 18 19 20
26
25
23
12 345678910
3
1 Control terminals 2 Power terminal Input L1 3 Power terminal Input L2 (N)
8
4 Power terminal Output V (N ) 5 Power terminal Output U (U) 6 PE 7 PE 8 Plexiglass cover
6
24
1
4
7
REO UK LTD 15
Loading...