Units 8 -10 Long Lane Industrial Estate 08/99
Craven Arms, Shropshire SY7 8DU
Tel: 01588 673411
Fax: 01588 672718
http://www.reo.co.uk
eMail: main@reo.co.uk
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Technical Safety Information for the User
This description co nta ins th e nec es s ar y inf ormation for the correct app lication of the product desc r ibe d
below. It is intended for use by technically qualified personal.
Qualified personnel are persons who, because of their training, experience and position as well as
their knowledge of appropriate standards, regulations, health and safety requirements and working
conditions, are authorised to be responsible for the safety of the equipment, at all times, whilst carrying
out their normal duties and are therefore aware of, and can report, possible hazards (Definition of
specialist according to IEC 364).
Safety Instructions
The following instr uctions are provided for the personal safety of operators and also for the
!
protection of the described product and connected equipment.
Warning!
Hazardous Voltage
Failure to observe can kill, cause serious injury or damage
• Isolate from mains before installation or dismantling work, as well as for fuse changes or post
installation modifications.
• Observe the prescribed accident prevention and safety rules for the specific application.
• Before putting into operation check if the rated voltage for the unit conforms with the local
supply voltage.
• Emergency stop devices must be provided for all applications. Operation of the emergency
stop must inhibit any further uncontrolled operation.
Prescribed Use
The units described herein are electrically powered for use in industrial applications. They are
designed for power adjustment of resistive or inductive loads.
REO UK LTD2
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Contents Page
1.0 General 4
2.0 Function Description 4
2.1 Effective Current Value 5
2.2 Effective Voltage Value 5
2.3 Current Regulation 5
2.4 Voltage Regulation 5
2.5 Pulse Generation 5
2.6 Temperature Monitoring 5
3.0 Control Inputs and Outputs 5
3.1 Setpoint Input U 6
3.2 Setpoint Input I 6
3.3 Enable (Regulator Inhibit) 6
3.4 Actual Voltage Output (Option) 6
3.5 Actual Current Output (Option) 6
3.6 Fault Indication 6
4.0 Construction 6
5.0 Adjustment Facilities 7
6.0 Adjustment Instructions 7
7.0 Technical Data 9
8.0 Ordering Codes 10
9.0 Adjustment Components 11
10.0 Fuse Change 12
11.0 Installation Guidelines 12
12.0 Guidelines on Electromagnetic Interference 12
13.0 Connection Diagrams 13
14.0 Dimension Drawing 14
14.1 Dimension Drawing MEW 150/XXX 15
REO UK LTD3
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
1.0General
The range of REOTRON MEW Thyristor Regulat ors are microprocessor based units for controll ing
the power to resisti ve and inductive loads . In essence the units comprise inverse para llel connected
power semiconductors (thyristors) and the control and regulation electronics. The units have a
regulated, AC output. The inverse parallel connected thyristors operate as contact free, power
controllers using the ph ase angle control or the f ull wave principles. In t he phase angle control m ode
(symetrical load) the equipment can be used as a voltage or current regulator and also there is an
option for power regulation. The set point value for the current and voltage can be provided by an
external control vo ltage of 0-10 V, 0-20 mA, DC or a potentiom eter. The lowest set point has priority.
The effective value is f ed back internall y from a voltage or curr ent transformer. The m aximum current
limit of the unit c annot be exceeded in a ll regulation modes , using phase angle control. Applications
with a wide load resistance variation Rcold/Rwarm are possible, and an overloading of the unit is
prevented.
Infra Red Emitters (Dryers) Preheating Plants Air Conditioning Plant
Tunnel Heaters Room Heating Equipment Fan Heating Systems
Plastic Moulding Equipment Extruders
2.0 Function description
Mains connection
L1L2 (N)
F1
The MEW thyristor contro l unit was desig ned to oper ate with a
symetrical load. Th ey include a voltage and current regu lator.
In the voltage regulation m ode the output voltage determ ined
by the set point is held constant by an internal circuit, therefore
load or mains variations have no influence on the output
PULSE
GENERATION
R
C
voltage. The selected maximum current, however, cannot be
exceeded in this mode (current limiting). If the unit is used as a
current regulator then the output current of the unit is
compared with the setpoint and regulated accordingly. The
Fault
output voltage can incr ease to the selected voltage set point.
LED's illuminate if the limit Imax or adjustment limits are
exceeded.
If both set points are adjusted during operation, th e regulator
always gives the lower set point priority. During voltage
Actual
Current
Actual
Voltage
Actual
Output
(Option)
regulation, with underlying current regulation, the voltage
regulation is alwa ys in operation providing the a llowed current
limit is not exceeded. If the current limit is reached then the
current regulator has priority. Should the unit be used as a
pure voltage or current r egulator, the other availa ble set point
must be linked to the reference voltage (10V DC).
Current
Setpoint
Voltage
Setpoint
Enable
Control
Electronics
I
U
Output
REO UK LTD 4
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
2.1 Effective Current Value
The effective current value is measured inside the u nit through a current transformer and a burden
resistor. The interna l microprocess or determines the ef fective value of th e output current and adjusts
this using a PI regulator.
2.2 Effective Voltage Value
The effective vo ltage value is also meas ured internally using a v oltage transformer and the effective
value is controlled by the microprocessor using a PI regulator.
2.3 Current Regulator
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using
trimmer P4. The units m aximum output cur rent (Rated Current) is factor y set. If the thyristor controller
is to be adapted for a small load current, then a correction can be made by using trimmer Imax.
BEWARE: It is possible t o obtain an outpu t current which is higher than the rat ed current bec ause of
component and manuf acturing tolerances, however, for s afety, it is essential that the current lim it is
not set higher than the rated current
In current regulation mode the LED Imax is permanently illuminated.
2.4 Voltage Regulator
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using
trimmer P3. The units maximum voltage output is factory set to the rated voltage (for 100% set point).
Therefore, the setpoint cannot be f ully used during voltage regulation s ince this would not allow for
any over voltage. In this oper ating mode ( voltage regulation) ei ther the setpoint m ust be limited or the
maximum unit output voltage must be reduced by using the trimmer Umax.
2.5 Pulse Generation
The pulses required f or the control of the thyristors are generated by the m icroprocessor and are fed
to amplifiers prior t o the pulse conductors. The sec ondary windings of the pulse cond uctors directly
control the thyristors.
2.6 Temperature Monitoring
A temperature switc h is fitted into the heat sink to monitor its temperature and this switches off the
thyristor controller , permanently, if the tem perature exceeds a maxim um of 80oC. Fault indication is
provided by the general fault relay and displayed by the LED on the front panel.
3.0 Control Inputs and Outputs
Control Inputs
Setpoint Input U 0(4)...20 mA, 0-10V DC or Potentiometer 10kΩ
Setpoint Input I 0(4)...20 mA, 0-10V DC or Potentiometer 10kΩ
Enable 12-24V DC or contacts
Outputs:
Effective Current Value 0-10V DC corresponding to 0-100% (Option)
Effective Voltage Value 0-10V DC corresponding to 0-100% (Option)
Fault Indication Relay Contact 250V/1A (Change over)
REO UK LTD 5
(
)
g
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
3.1 Setpoint Input U
With power regulation here the power setpoint is determined
switch S1/6=ON
The value of the outp ut voltage is determ ined by the s etpoint inp ut U. The setp oint can b e provided in
the form of 0-10 V, 0-20mA, DC or with a 10kΩ Potentiometer. A +10V ref erence voltage is prov ided
for potentiometer operation.
With setpoint 4...20 mA, put the switch “S1/5” to “ON”.
3.2 Setpoint Input I
The strength of the output current is determined by the set point input "I". The setpoint can be provided
in the form of 0-10 V, 0- 20mA, DC or wit h a 10k Potentiom eter. A +10V r eference vo ltage is pro vided
for potentiometer operation.
With setpoint 4...20 mA, put the switch “S1/5” to “ON”.
3.3 Enable (Regulator Inhibit)
A control voltage (12-24V DC) must be applied to terminals 9+ and 15-, to enable the unit, or a
connection made between terminals 9 and 10 by using a switch. A permanent link between terminals 9
and 10 is used for operation without an external enable. The firing pulses are inhibited whilst the
enable input is not closed.
3.4 Actual Voltage Output (Option)
With power regulation the actual power is given
instead of the actual volta
e.
A 0-10 V DC output signal is pr ovided and this corresponds to the units m omentary voltage output.
This generates 10V for 100% of the units possible output voltage (using the Umax set value).
3.5 Actual Current Output (Option)
A 0-10 V DC output signal is provided and this cor responds to the units mom entary current output.
This generates 10V for 100% of the units possible output current (using the Imax set value).
3.6 Fault Indication
Relay changeover contacts are provided for indicating that there has been a unit fault.
The following fault conditions energise the relay and cause the unit to switch off:
Over temperature of the power unit
Mains synchronisation not possible
A fault condition must be cancelled with the RESET push button.
4.0 Construction
The thyristor regulator un it is a completely wired, function tes ted, compact unit. The unit is des igned
for panel mounting. T he co nnections for th e m ains s uppl y and l oad ar e bro ught out t o scr ew term inals
and the control signals to plug-in screw terminals. The unit front panel incorporates the adjustment
components (trimmers, switch and light diodes) to display and control the operating conditions.
The fuses for protecting th e sem iconductors is built into the f ront panel are ac cessed b y removin g the
front panel.
REO UK LTD 6
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
5.0 Adjustment Facilities
The following parameters can be adjusted on the unit: Umax - Maximum Output Voltage Umin - Minimum Output Voltage
Imax - Maximum Output Current Imin - Minimum Output Current
P - Characteristic of the Voltage Regulator P - Characteristic of the Current Regulator
Ramp up time Ramp down time
The trimmers are adjustable through the front panel.
6.0 Adjustment Instructions
Preparatory Steps
Connect unit according to connection
drawing, disconnect the enable and
adjust set point to zero. The unit will
now operate with the basic factory
settings: output curr ent = rated current,
output voltage = rated in put voltage1), Umin = 0,
phase angle control, regulation mode.
The setpoint control c urve can be det ermined by
using trimmers Umin/Umax and Imin/Imax ie the
setpoint control range. At this stage, it is also
possible, to make permanent adjustments,
without external setpoints.
The range minimum always ex tends from zero to
the adjusted range maximum. The maximum
value must be set first.
Adjustment of the MAX - Values
Umax
Hint: If the output voltage is to be regulated at the maximum set point, then the maximum output
voltage must be limited at a value which reduces the regulation range.
Switch on the m ains voltag e and enab le the uni t. Set the cur rent set po int to m axim um. Now increase
the voltage set point unti l the required output voltage level is reached (obs erve current lim it indicator) .
If the set point source is no t yet at m aximum , then the output volt age must be reduced ag ain by using
trimmer Umax and then t he voltage s et point can be further incr eased until the maximum value of the
voltage set point is ac hieved. If there is no risk of dam aging the load with an over voltage th en the
output voltage can be set by using trimmer Umax with the set point turned fully up. Anticlockwise
adjustment increases the output voltage.
Imax
Remove the unit enable. Adjust voltage set point to maximum and current setpoint to zero. Turn
trimmer Imax fully clockwise (10 turn pot). Next enable the unit and adjust the current setpoint to
maximum. Set the maximum current value by turning trimmer Imax anti-clockwise.
REO UK LTD 7
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
Adjustment of the MIN - Values:
Umin
Trimmers P1 and P2 ar e used to adjust the MIN va lue, however these trim mers are used for vari ous
other functions. Below is the recommended adjustment procedure.
Set rotary switch 'S2' on the f ront panel to pos ition '1' and press the RES ET butto n. Next
adjust the trimmers P1 (coarse) and P2 (fine) to the required minimum voltage and
afterwards press th e SETUP button. T o return to normal operat ion put the r otary switch
'S2' back to '0' and press the RESET button.
Imin
This adjustment is only meaningful for pure current contro l, if a current f ree condition of the loa d is to
be avoided.
This adjustment is als o carried out by using trimm ers P1 and P2. Set rotary switch 'S2' o n the front
panel to position '2' and pres s the RESET button. Next adjust the trimmers P1 (c oarse)
and P2 (fine) to the requir ed minimum current and af terwards press the S ETUP button.
To return to normal op eration put th e rotar y switch 'S2' bac k to '0' and pres s the RES ET
button.
Ramp up /down times
The ramp up time f or when the unit is switched o n, using the enable input ( set point 100%) or when
the set point sudden ly rises, giving 0 to 1 00% of the maximum output value, and also t he run down
time to reach an output value for a set point change in the direction of zero.
This adjustment is similarly achieved using the trimmer P1 for Ramp up and P2 for Ramp down times.
With the voltage set point at zero and the current set point at maximum.
Set rotary switch 'S2' on the front panel to position '3' and press the RESET button. Next set the
required ram p time (0.1-10s) using trimmer P1 and test for a set point change from
zero to 100%; afterwards set the ramp down time with trimmer P2 and again test by
changing the set point. W hen the required val ues have been chosen, once again press
the "SETUP" button, return rotary switch 'S2' back to '0' and press the RESET button.
Proportional Characteristic Voltage Regulation
The speed of regulation (sensitivity) of the voltage regulator. Adjust, using the actual load, using
trimmer P3.
Proportional Characteristic Current Regulation
The speed of regulation (sensitivity) of the current regulator. Adjust, using the actual load, using
trimmer P4.
Hint
To return the unit to the factory settings, the procedure is as follows:Rotate selector switch "S2" to position "F" an d press the RESET butto n. After wards press the SETUP
button and return select or switch "S2" to position "0" and press the RE SET button once more. The
factory settings are now reinstated.
Selector Switch S1 (Operating Mode)
S1/1 OFF = Phase angle control ON = Full wave control
1
2
3
4
5
6
7
8
OFF
S1/2 not active
S1/3 not active
S1/4 not active
S1/5 OFF = 0...20 mA ON = 4...20 mA (Setpoint)
S1/6 OFF = U/I - Regulation ON = Power Regulation
S1/7 OFF = Without data interface ON = with data interface
S1/8 OFF = Reserved
ON
The RESET button must be pressed before a change of the switch settings.
REO UK LTD 8
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
7.0 Technical Data
TYPE Rated Voltage Output Voltage2) Output Current
50/60 Hz MAX.
MEW 10/230 230 V +6% -10% 0-230 V 10 A
MEW 10/400 400 V +6% -10% 0-400 V 10 A
MEW 20/230 230 V +6% -10% 0-230 V 20 A
MEW 20/400 400 V +6% -10% 0-400 V 20 A
MEW 50/230 230 V +6% -10% 0-230 V 50 A
MEW 50/400 400 V +6% -10% 0-400 V 50 A
MEW 80/230 230 V +6% -10% 0-230 V 80 A
MEW 80/400 400 V +6% -10% 0-400 V 80 A
MEW 110/230 230 V +6% -10% 0-230 V 110 A
MEW 110/400 400 V +6% -10% 0-400 V 110 A
MEW 150/400 400 V +6% -10% 0-400 V 150 A
Load Types resistive / resistive - inductive; for transformers max. induction 1,45 Tesla
Setpoint source 5 / 10 kΩ Potentiometer
0-10V, DC
0-20 mA
Ramp up/down time 0,1 - 10 sec.
Enable Switch 12-24 V, DC
Actual value output I 0-10 V, DC
Actual value output U 0-10 V, DC
Fault relay 1 change over contacts 250 V, 1 A
Ambient temp. 0-45 °C
Dimensions approx. (HxBxD)
MEW 10/XXX MEW 20/XXX MEW 50/XXX MEW 80/XXX MEW110/XXX MEW150/XXX
290x70x205 290x110x205 290x110x205 320x150x205 320x180x205 320x180x205
2)
The output voltage is subject to a voltage loss across the semiconductors.
REO UK LTD 9
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
8.0 Ordering Codes
Type ID-Number Description
REOTRON MEW 10/230 6311 10 A/230 V Standard unit
REOTRON MEW 10/400 6312 10 A/400 V Standard unit
REOTRON MEW 10/230 DA 6316 10 A/400 V with D/A-Module
REOTRON MEW 10/400 DA 6317 10 A/400 V with D/A-Module
REOTRON MEW 10/230 RS 6315 10 A/400 V with RS 232 Interface
REOTRON MEW 10/400 RS 6318 10 A/400 V with RS 232 Interface
REOTRON MEW 10/230 IS 6313 10 A/400 V with INTERBUS-S Interface
REOTRON MEW 10/400 IS 6314 10 A/400 V with INTERBUS-S Interface
REOTRON MEW 20/230 6321 20 A/230 V Standard unit
REOTRON MEW 20/400 6322 20 A/400 V Standard unit
REOTRON MEW 20/230 DA 6328 20 A/230 V with D/A-Module
REOTRON MEW 20/400 DA 6327 20 A/400 V with D/A-Module
REOTRON MEW 20/230 RS 6329 20 A/230 V with RS 232 Interface
REOTRON MEW 20/400 RS 63210 20 A/400 V with RS 232 Interface
REOTRON MEW 20/230 IS 6324 20 A/230 V with INTERBUS-S Interface
REOTRON MEW 20/400 IS 6325 20 A/400V with INTERBUS-S Interface
REOTRON MEW 50/230 6331 50 A/230 V Standard unit
REOTRON MEW 50/400 6332 50 A/400 V Standard unit
REOTRON MEW 50/230 DA 6338 50 A/230 V with D/A-Module
REOTRON MEW 50/400 DA 6337 50 A/400 V with D/A-Module
REOTRON MEW 50/230 RS 6339 50 A/230 V with RS 232 Interface
REOTRON MEW 50/400 RS 63310 50 A/400 V with RS 232 Interface
REOTRON MEW 50/230 IS 6333 50 A/400 V with INTERBUS-S Interface
REOTRON MEW 50/400 IS 6334 50 A/400 V with INTERBUS-S Interface
REOTRON MEW 80/230 6341 80 A/230 V Standard unit
REOTRON MEW 80/400 6342 80 A/400 V Standard unit
REOTRON MEW 80/230 DA 6348 80 A/230 V with D/A-Module
REOTRON MEW 80/400 DA 6347 80 A/400 V with D/A-Module
REOTRON MEW 80/230 RS 63410 80 A/400 V with RS 232 Interface
REOTRON MEW 80/400 RS 6349 80 A/400 V with RS 232 Interface
REOTRON MEW 80/230 IS 6343 80 A/400 V with INTERBUS-S Interface
REOTRON MEW 80/400 IS 6344 80 A/400 V with INTERBUS-S Interface
REOTRON MEW 110/230 6351 110 A/230 V Standard unit
REOTRON MEW 110/400 6352 110 A/400 V Standard unit
REOTRON MEW 110/230 DA 6358 110 A/4 00 V with D/A- M od ule
REOTRON MEW 110/400 DA 6357 110 A/4 00 V with D/A- M od ule
REOTRON MEW 110/230 RS 6355 110 A/4 00 V with RS 232 I nterf ac e
REOTRON MEW 110/400 RS 6356 110 A/4 00 V with RS 232 I nterf ac e
REOTRON MEW 110/230 IS 6353 110 A/400 V with INTERBUS-S Interface
REOTRON MEW 110/400 IS 6354 110 A/400 V with INTERBUS-S Interface
REOTRON MEW 150/400 DA 2057 150 A/4 00 V with D/A- M od ule
REO UK LTD 10
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
9.0 Adjustment Components
LED Indicator Functions
ERROR System fault
TEMP Over temperature
SYNC Mains synchronisation fault
I-Max Current limit reached ie current regulator active
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
LOAD Impedance fault / peak current reached
MAX Max. a djustment limit reached
INIT Initialisation phase
READY Ready to operate
ENABLE Enable
IN1 External Input 1 (Reserved)
IN2 External Input 2 (Reserved)
S2 S2 = 1 S2 = 2 S2=3
P1 =Umin/coarse
P2 = Umin/fine
Imin/coarse
Imin/fine
Ramp up
Ramp down
times
P3 = P-Characteristic voltage regulator
P4 = P-Characteristic current regualtor
Selector Switch S1
S1/1 - OFF = Phase angle control ON = Full wave control
S1/2 -
S1/3 - Reserved for curent controller
S1/4 -
S1/5 – OFF = 0...20 mA ON = 4...20 mA (Setpoint)
S1/6 - OFF = I/U-Regulation ON = Power regulation
S1/7 - OFF = without data interface ON = with data interface
S1/8 - OFF = Reserved
Selector Switch S2
0 = Normal operation (Regulator)
1 = Adjus tment Umin
2 = Adjustment Imin
3 = Adjustment ramp up/down times
4 = Reserved
5 = Uncontrolled operation (no regulation / no current limiting)
6-E = Reserved
F = Reinstate factory settings
ERROR
TEMP
SYNC
I-max
LOAD
MAX
INIT
READY
ENABLE
IN1
IN2
P1
P2
P3
P4
1
2
3
4
S1
5
6
7
8
ONOFF
U-max
I-max
4
5
3
6
2
7
1
8
0
S2
9
F
A
E
B
D
C
RESET
SETUP
RESET = System reset-Button
SETUP = Enter new parameters
REOTR ON
MEW
REO UK LTD 11
Operating InstructionsREOTRON MEW
10.0 Fuse change
Switch unit off before changing fuse!
!
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
The semiconductor f use can be found in the left han d section of the f ront panel. T o change the fuse
the two screws marked "x" must be loosened. The cover can then be removed by sliding it to the right.
For MEW/xxx type units the fuse can be found in the front panel.
When ordering spare fuses use capital letters for fuse types.
11.0 Installation Guidelines
The unit is desi gned for p anel m ounting. It sho uld be i nstalled ver tically wit h the t erminals at
the bottom. Ensure that there is sufficient air space in unventilated cabinets.
The units can be place d side by side with a minimum clearanc e of 30mm. If the units are
mounted one over the other, then there must be a clearance of approximately 250mm.
The control cables should be shielded and the shield should be connected to earth.
12.0 Guidelines on Electromagnetic Interference
INTERBUS-S is a serial data transfer system which was conceived for app lications in an industrial
environment. When correctly installed, INTERBUS-S complies with all the requirements specified in
the standard IEC 801 for data trans fer system s in a harsh in dustrial enviro nment. W hen the interface
module is used in an electromagnetic, interference prone, area, then the possible sources of
interference should be suppressed.
Interference can be due, in particu lar, to:
• Protection devices
• Switching of inductive loads
• Solenoid valves
RC networks and var istors suppress interference. Ma nufacturers supply correctly si zed components
for suppressing solenoid coils.
Electrical spikes, which can affect bus cables in an industrial environment, can be suppressed by a
correctly fitted screen. The following measures provide the best screening results:
• Cover fixing screws of bus cable plugs and conductors at equal potentials.
• Only use connectors with a metal or metalised housing.
• Spread out the screen in connectors.
REO UK LTD 12
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
13.0 Connection Diagrams
Control Terminals
00
1 2 34 5 6 7 8 910
Voltage setpointCurrent setpointEnable
(Power setpoint)
+10V+10V
10k10k
Potentiometer setpoint source
12 345678910
00+++
0 - 20mA0 - 20mA
Setpoint VoltageSetpoint Current
(Power setpoint)
Enable
24V, DC
(to terminal 15)
12 345678910
00++
0 - 10V, DC0 - 10V, DC
Setpoint VoltageSetpoint Current
(Setpoint power)
Setpoint source using
0-10 V, DC control voltage
1112
0 - 10V0 - 10V
Actual value
Voltage
(Actual value power)
13
141516171819 20
00++
Actual value
Current
(Optional)
NC CNO
Enable
Setpoint source using
0-20 mA control current
Power terminals
230V, 50/60Hz
400V, 50/60Hz
L1 (L)
L2 (N)
PE
212223242526
L1L2PEPEVU(N)(L)(N)(U)
Load
REO UK LTD 13
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
14.0 Dimensions
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
P1
ERROR
TEMP
SYNC
I-max
LOAD
MAX
INIT
READY
ENABLE
IN1
e
IN2
P2
P3
P4
1
2
3
4
S1
5
6
7
8
ONOFF
U-max
I-max
4
5
3
6
2
7
1
8
0
S2
9
F
A
E
B
D
C
RESET
SETUP
d
REOTRON
MEW
a
b
c
x
205
Dimension MEW10 MEW20 MEW50 MEW80 MEW110
a - 70 70 60 90
b 35 15 15 30 30
c 70 110 110 150 180
d 290 290 290 320 320
e 280 280 280 304 304
x - 5 5 5 10
REO UK LTD 14
Operating InstructionsREOTRON MEW
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
14.1 Dimensions MEW 150/XXX
ELEKTRONIK
ELEKTRONIK
ELEKTRONIKELEKTRONIK
P1
P2
P3
P4
1
2
3
4
S1
5
6
7
8
ONOFF
U-max
I-max
4
7
1
8
S2
F
RESET
SETUP
320
290
FOR CONTINUED FIRE
PROTECTION REPLACE
ONLY WITH SPECIFIED
TYPE AND RATED FUSE
DISCONNEC T POWER
INPUT BEFORE
REPLACING F USE
ERROR
TEMP
SYNC
I-max
LOAD
MAX
INIT
READY
ENABLE
IN1
IN2
REOTRON
MEW
90
180
2
21
22
5
11 12 13 14 15 16 17 18 19 20
26
25
23
12 345678910
3
1 Control terminals
2 Power terminal Input L1
3 Power terminal Input L2 (N)
8
4 Power terminal Output V (N )
5 Power terminal Output U (U)
6 PE
7 PE
8 Plexiglass cover
6
24
1
4
7
REO UK LTD 15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.