Reo Elektronik REOTRON MDW 700 Operating Instructions Manual

MDW_700_EN_ANL_34-13.doc
21.08.2013
REOTRON
Electronic Power Controller
3-Phase-Thyristor Power Controller
REOTRON MDW 700 Operating instructions
1
Contents
Technical Information for the User ............................................................................................................... 2
1.0 General ................................................................................................................................................... 3
2.0 Construction ........................................................................................................................................... 3
3.0 Functions ................................................................................................................................................ 4
3.1 Modes ................................................................................................................................................. 4
3.2 Regulation mode ................................................................................................................................. 5
3.3 Set point .............................................................................................................................................. 5
3.4 Feedback ............................................................................................................................................ 6
3.5 Control functions ................................................................................................................................. 6
4.0 Technical Data ........................................................................................................................................ 7
4.1 Limited the output voltage by using line input from 230V or 240V ..................................................... 7
5.0 Declaration of Conformity ....................................................................................................................... 7
6.0 Ordering codes ....................................................................................................................................... 8
7.0 Operation ................................................................................................................................................ 9
7.1 Adjustment .......................................................................................................................................... 9
7.2 Adjustment Procedure ........................................................................................................................ 9
7.3 Indications on display........................................................................................................................ 10
7.4 Error Messages ................................................................................................................................. 10
8.0 Settings ................................................................................................................................................. 11
9.0 Setting up instructions .......................................................................................................................... 12
9.1 Internal set point ............................................................................................................................... 12
9.2 Unit configuration .............................................................................................................................. 12
9.2.1 Service menu ................................................................................................................................. 13
9.2.2 Display effective values measured inside unit ............................................................................... 13
9.3 Setting Up Procedures ...................................................................................................................... 14
9.4 Select Interface ................................................................................................................................. 14
9.5 Save current settings ........................................................................................................................ 15
9.6 Restore parameter settings .............................................................................................................. 15
9.7 Software version ............................................................................................................................... 15
9.8 Hide parameter menus ..................................................................................................................... 15
10.0 Connection diagram ........................................................................................................................... 16
10.1 Connection details .......................................................................................................................... 17
11.0 Dimensions ......................................................................................................................................... 18
12.0 Putting into service ............................................................................................................................. 22
12.1 Preliminaries ................................................................................................................................... 22
12.2 Measurements and Settings ........................................................................................................... 22
12.3 Putting into service without a proper load ....................................................................................... 22
13.0 Installation of Thyristor Control Units ................................................................................................. 23
13.1 Fuses .............................................................................................................................................. 23
13.2 Incoming breaker ............................................................................................................................ 23
13.3 Output Breaker ................................................................................................................................ 23
13.4 Installation and climatic Conditions ................................................................................................. 23
13.5 Signal cables ................................................................................................................................... 23
14.0 Interference prevention....................................................................................................................... 24
14.1 Earthing ........................................................................................................................................... 24
14.2 Control cables ................................................................................................................................. 24
14.3 Interference protection of other external components and equipment ........................................... 24
15.0 Engineering notes ............................................................................................................................... 25
REOTRON MDW 700 Operating instructions
2
Technical Information for the User
This description contains the necessary information for the correct application of the product described below. It is intended for use by technically qualified personal. Qualified personnel are persons who, because of their training, experience and position as well as their knowledge of appropriate standards, regulations, health and safety requirements and working conditions, are authorised to be responsible for the safety of the equipment, at all times, whilst carrying out their nor­mal duties and are therefore aware of, and can report, possible hazards (Definition of specialist according to IEC 364).
Safety Instructions
The following instructions are provided for the personal safety of operators and also for the protection of the described product and connected equipment.
Warning!
Hazardous Voltage Failure to observe can kill, cause serious injury or damage
Isolate from mains before installation or dismantling work, as well as for fuse changes or post installation modifications.
Observe the prescribed accident prevention and safety rules for the specific application.
Before putting into operation check if the rated voltage for the unit conforms with the local
supply voltage.
Emergency stop devices must be provided for all applications. Operation of the emergency stop must inhibit any further uncontrolled operation.
Electrical connections must be covered
Earth bonding must be tested prior to operation
Prescribed Use
The units described herein are electrically powered for use in industrial applications. They are designed for power adjustment of resistive or inductive loads
These units comply with Directive 2004/108/EC
EMC Directive
!
RoHS
COMPLAINT
REOTRON MDW 700 Operating instructions
3
1.0 General
The range of REOTRON MDW Thyristor Regulators are microprocessor based units for controlling the power to resistive and inductive loads. In essence the units comprise inverse parallel connected power semiconductors (thyristors) and the control and regulation electronics. The units have a regulated, AC output. The inverse parallel connected thyristors operate as contact free, power controllers using the phase angle control or the full wave principles. In the phase angle control mode the equipment can be used as a voltage or current regulator and also there is an option for power regulation. The set point value for the current and voltage can be provided by an external control voltage of 0-10 V, 0(4)-20 mA, DC or a potentiometer. The lowest set point has priority. The effective value is fed back internally from a voltage or current transformer. The maximum current limit of the unit cannot be exceeded in all regulation modes, using phase angle control. Applications with a wide load resistance variation Rcold/Rwarm are possible, and an overloading of the unit is prevented.
Typical Applications
Industrial Ovens Steam Generators Lighting Installations Infra Red Emitters (Dryers) Preheating Plants Air Conditioning Plant Tunnel Heaters Room Heating Equipment Fan Heating Systems Plastic Moulding Equipment Extruders
2.0 Construction
The REOTRON -MDW 700 thyristor controller is a completely functional, compact, unit. It has been de­signed for building into an enclosure. All connections for the supply, power output, feedback signals and the supply for the isolator are made through screw terminals. A touch panel with an LED display and set­ting up keys is incorporated in the front panel. There are connectors provided for analogue signals and optional a field bus interface. Inside the unit there is a printed circuit, control card and a power card, com­prising the semiconductors, firing and regulating circuits and the system power supply.
Overview
Display
Output
Control­terminals
Input
* MDW 25 A
27
28
2625
24 23 22 21
DO NOT USE
WITHOUT COVER
REOTRON
MDW
www.reo.de
F I
0P
FOR CONTINUED FIRE
PROTECTION REPLACE
ONLY WITH SPECIFIED
TYPE AND RATED FUSE
DISCONNECT POWER
INPUT BEFORE
REPLACING FUSE
REOTRON MDW 700 Operating instructions
4
3.0 Functions
Features:
Mode:
1. Phase angle control
2. Full wave principle
Regulation mode:
1. Current regulation RMS
2. Voltage regulation RMS
3. Power regulation Real power
Set point inputs:
1. Voltage or Power Potentiometer 10 kR, 0...+10 V, 0(4)...20 mA,
internal Keypad
2. Current
Potentiometer 10 kR, 0...+10 V, 0(4)...20 mA, internal Keypad
Option interface Set point via interface
Feedback monitoring:
1. Voltage or Power Voltage 0...+10 V, DC correspond 0...100% RMS
2. Current Current 0...+10 V, DC correspond 0...100% RMS
Status
Enable (ON/OFF) Contact or 24 V, DC Fault relay Change over contact
Interface: Option
Serial RS 232 Fieldbus Profibus-DP Fieldbus CAN-Bus Fieldbus DeviceNet
3.1 Modes
Phase angle control
In the phase angle control mode the mains voltage half waves are more or less cut in function of the giv­en set point. This mode of operation is suitable for resistive, inductive and resistive-inductive loads. The benefits with this mode of operation are the continuous adjustment, the fine dosing and the high regulating dynamics. A dynamic current limitation is possible only with this mode of operation.
Full wave control
In the full wave principle mode of operation, always full sinus waves are switched in function of the set point. In this operating mode almost no harmonics are produced, however, the dynamic regulation is not possible. This mode of operation is suitable in particular for loads with high thermal inertia.
REOTRON MDW 700 Operating instructions
5
3.2 Regulation mode
The REOTRON MDW Thyristor Regulator range include 3 regulators, ie. voltage, current and power regulator. All the regulators always work in combination, ie. with voltage regulation for example, the cur­rent regulation operates like a cascade control and limits the output current in case of overload on the rated current. In case of current regulation mode, the maximum voltage limit can be prescribed over the voltage set point. With power regulation, the current limit is also effective as cascade. In case both the voltage and current regulation are used, the set point of the power regulator must be set to 100 % (over display, in menu „C 002“, parameter „P“).
Voltage regulation
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using the key­Pad. The units maximum voltage output is factory set to the rated voltage (for 100% set point).
Parameter setting
Parameter Code Setting Output power „P.“ C 020 100% Set point current „I.“ Display or Set point current connection 7 u. 8
C 020
100%, or smaller bridge = 100%
Current regulation
Microprocessor controller with PI Characteristics; the P portion is adjustable externally by using the Key­Pad. The units maximum output current (Rated Current) is factory set.
Parameter setting
Parameter Code Settings Output power „P.“ C 020 100% Set point voltage „U.“ Display or Set point current connection 3 u. 4
C 020
100%, or smaller bridge = 100%
Power regulation
With power regulation, the real power value is controlled. In this case, the input that is normally coordi­nated to the voltage set point is now used as set point input. This set point input corresponds to 0...100 % of the unit output power. The current set point must be set to 100 % or to the required limit value. Set­ting over display or link between terminals 7 and 8.
Parameter setting
Parameter Code Settings Output power „P.“ C 020 0% Set point voltage „U.“ Display C 020 100%, or smaller Set point voltage „I.“ Display or Set point current connection 7 u. 8
C 020
100%, or smaller bridge = 100%
Power regulation „E.F.P.“ C 003 1
3.3 Set point External signals
Two inputs for set points are available
Set point input U, P 0-10V DC, 0(4)…20 mA or Potentiometer 10k Set point input I 0-10V DC, 0(4)…20 mA or Potentiometer 10k
Set point over display
All set points can be set over the internal Key-Panel
REOTRON MDW 700 Operating instructions
6
3.4 Feedback
Current feedback
The current is measured, in one phase, with an internal current transformer. The internal microprocessor determines the effective value of the output current and makes adjustments through a PI loop.
Voltage feedback
The effective voltage is measured with an internal Transformer. It is converted in an analogue input stage and then fed to the internal microprocessor. The effective value is thus determined and applied used for PI regulation using software. Using an external feedback signal of 0..5V is also possible. (See connection diagram)
Output monitor
Effective Voltage 0…10 V, DC correspond 0…100 % output voltage or output power. Effective Current 0…10 V, DC correspond 0…100 % output current
3.5 Control functions
Enable
Run / Stop input. A control voltage (24V DC) must be applied to terminals 32(+) and 31(-), to enable the unit, or a connec­tion made between terminals 32 and 33 by using a switch. A permanent link between terminals 32 and 33 is used for operation without an external enable. The firing pulses are inhibited whilst the enable input is not closed.
Start ramp / Stop ramp
This function reduces surges on the mains supply when the load is switched on and off.
Set point control (min / max) The set-point control characteristics can be adjusted to match the subsequent process controller or automation system, by setting the lower and upper values
Status / Ready relay (clamp 41, 42, 43)
For monitoring the actual status, an internal relay can be used. In case of applied input voltage and ena­bled power output, clamp 42 – 43 closes.
For using this relay as a “READY” signal point “r.b.” in Code “C 003” has to be set to 1. In case of an error like “LO.PO.”, clamp 42 – 43 opens.
Clamp assignment:
41 normally close (NC) 42 change-over contact (CO) 43 normally open (NO)
run-up
run-down
Output
U,I,P
Time
0
10 20 30 40 50 60 70 80 90 100
[%]
10
20
30
40
50
60
70
80
90
100
[%]
Output-
voltage
Set point
Umin
Umax
adjustment range
Set point
0...100%
REOTRON MDW 700 Operating instructions
7
Failure relay (clamp 44, 45, 46)
In case of an error (for example “Error Hot”) the contact 45 – 46 closes. Clamp assignment:
44 normally close (NC) 45 change-over contact (CO) 46 normally open (NO)
4.0 Technical Data
Type Input voltage [V] Output voltage [V] Output current[A] MDW 700-10/230 - 400
230 – 400 V +/-10% 50/60Hz
Ue – 3 V
0…10 MDW 700-25/230 – 400 0...25 MDW 700-50/230 - 400 0…50 MDW 700-80/230 - 400 0…80 MDW 700-110/230 - 400 0…110 MDW 700-150/230 - 400 0…150 MDW 700-200/230 - 400 0…200 MDW 700-300/230 – 400 0...300 MDW WK 700-115/230 - 400 0…115 MDW WK 700-160/230 - 400 0…160 MDW WK 700-250/230 - 400 0…250 MDW WK 700-350/230 - 400 0…350 MDW WK 700-450/230 - 400 0…450 MDW WK 700-600/230 - 400 0…600 Load R / RL, Transformer Load max. Induction 1,45 Tesla Set point Inputs current voltage or power
0...+10 V 22 kR 0(4)...20 mA 100 R
Potentiometer 10 KR, internal Display External feedback U 0...+/-5 V 22 kR External feedback I 0...+/-5 V 22 kR Feedback monitor / U or P 0...+10 V, DC 5 mA Feedback monitor I 0...+10 V, DC 5 mA Enable Contact 5 mA or 24 V, DC 5 mA Faulty relay Change over contact 250 V, 1 A Protection IP 20 Operating temperature 0... + 45 °C Liquid temperature WK Type 25 °C Input Liquid quantity H2O, 6 ltr/min Storing temperature -20...+75 °C Rel. air humidity 93 % without condensation and surface water coning Contamination level degree 1 (IEC 664) Mounting direction Vertical (Connections below) Mounting height 1000 m, 0,5 % rated current reduction for each additional 100 m
WK = water-cooled
4.1 Limited the output voltage by using line input from 230V or 240V
By using the controller at line input from 230 or 240V you must limited the output voltage under Code 020 – point „u“. At line= 230V to 57% and at line= 240V to 60%.
5.0 Declaration of Conformity
In order to comply with the EMC requirements, when using phase angle controllers it is necessary to build in a suitable filter in the line input, e.g. Book-style filter CNW 207 or CNW 107. (further information in Section 15.0, "Engineering notes")
REOTRON MDW 700 Operating instructions
8
6.0 Ordering codes
Type
ID.-No.:
Input voltage
[V]
Output current
[A]
REOTRON MDW 700-10/230 – 400 6401.01
230 – 400 3x 10
REOTRON MDW 700-10/230 – 400 Profibus DP 6401.10
230 – 400 3x 10
REOTRON MDW 700-10/230 – 400 RS-232 6401.30
230 – 400 3x 10
REOTRON MDW 700-25/230 – 400 6402.01
230 – 400 3x 25
REOTRON MDW 700-25/230 – 400 Profibus DP 6402.10
230 – 400 3x 25
REOTRON MDW 700-25/230 – 400 RS-232 6402.30
230 – 400 3x 25
REOTRON MDW 700-50/230 – 400 6403.01
230 – 400 3x 50
REOTRON MDW 700-50/230 – 400 Profibus DP 6403.10
230 – 400 3x 50
REOTRON MDW 700-50/230 – 400 RS-232 6403.30
230 – 400 3x 50
REOTRON MDW 700-80/230 – 400 6404.01
230 – 400 3x 80
REOTRON MDW 700-80/230 – 400 Profibus DP 6404.10
230 – 400 3x 80
REOTRON MDW 700-80/230 – 400 RS-232 6404.30
230 – 400 3x 80
REOTRON MDW 700-110/230 – 400 6405.01
230 – 400 3x110
REOTRON MDW 700-110/230 – 400 Profibus DP 6405.10
230 – 400 3x110
REOTRON MDW 700-110/230 – 400 RS-232 6405.30
230 – 400 3x110
REOTRON MDW 700-150/230 – 400 6406.01
230 – 400 3x 150
REOTRON MDW 700-150/230 – 400 Profibus DP 6406.10
230 – 400 3x 150
REOTRON MDW 700-150/230 – 400 RS-232 6406.30
230 – 400 3x 150
REOTRON MDW 700-200/230 – 400 6407.01
230 – 400 3x 200
REOTRON MDW 700-200/230 – 400 Profibus DP 6407.10
230 – 400 3x 200
REOTRON MDW 700-200/230 – 400 RS-232 6407.30
230 – 400 3x 200
REOTRON MDW 700-300/230 – 400 6409.01
230 – 400 3x 300
REOTRON MDW 700-300/230 – 400 Profibus DP 6409.10
230 – 400 3x 300
REOTRON MDW 700-300/230 – 400 RS-232 6409.30
230 – 400 3x 300
REOTRON MDW-WK 700-115/230 – 400
6337.01
230 – 400 3x 115
REOTRON MDW-WK 700-115/230 – 400 Profibus DP
6337.10
230 – 400 3x 115
REOTRON MDW-WK 700-115/230 – 400 RS-232
6337.30
230 – 400 3x 115
REOTRON MDW-
WK
700-160/230 – 400
6338.01
230 – 400 3x 160
REOTRON MDW-WK 700-160/230 – 400 Profibus DP
6338.10
230 – 400 3x 160
REOTRON MDW-WK 700-160/230 – 400 RS-232
6338.30
230 – 400 3x 160
REOTRON MDW-WK 700-250/230 – 400
6339.01
230 – 400 3x 250
REOTRON MDW-
W
K
700-250/230 – 400 Profibus DP
6339.10
230 – 400 3x 250
REOTRON MDW-WK 700-250/230 – 400 RS-232
6339.30
230 – 400 3x 250
REOTRON MDW-WK 700-350/230 – 400
6340.01
230 – 400 3x 350
REOTRON MDW-WK 700-350/230 – 400 Profibus DP
6340.10
230 – 400 3x 350
REOTRON MDW-WK 700-350/230 – 400 RS-232
6340.30
230 – 400 3x 350
REOTRON MDW-WK 700-450/230 – 400
6341.01
230 – 400 3x 450
REOTRON MDW-WK 700-450/230 – 400 Profibus DP
6341.10
230 – 400 3x 450
REOTRON MDW-WK 700-450/230 – 400 RS-232
6341.30
230 – 400 3x 450
REOTRON MDW-WK 700-600/230 – 400 Profibus DP
0203.06
230 – 400 3x 600
WK = water-cooled
REOTRON MDW 700 Operating instructions
9
7.0 Operation
The six buttons and a LED display found in the front panel, are used for operating and setting up the unit. All operating methods and adjustable parameters can be set up through this panel.
The “I“ and “O“ buttons are used for switching the unit ON and OFF, however, these do not provide mains isola­tion, they simply inhibit the power semiconductors
The “P“, “F“ and “Cursor Buttons“ are used for parameter adjustment. Parameters are set by using menu controls which are called up by entering operator codes. A capital letter is used to indicate the selected function. The display value can be increased or decreased by units, or tenths of units, by a short press of the cursor buttons. Holding the buttons down will cause the display to change in units of ten.
7.1 Adjustment
To prevent accidental or unauthorized adjustment the adjustment parameters, in the user menus, are protected. A code must be entered to open the user menus. There are different pass codes for each func­tion group.
Setting adjustments are automatically saved upon leaving the programming mode or if no button is pressed for a period of 100 seconds.
7.2 Adjustment Procedure
All setting routines are commenced by pressing the programming button “P“. The following diagram should clarify the sequence in which keys are pressed:
1. Press the “P“ key.
2. Select the code number with the cursor keys.
3. Press the “P“ key. This displays the first menu point. The required menu point can be found by re-
peatedly pressing the “P“ key (scrolling).
4. The value in the menu point can be changed with the cursor keys.
5. Scroll to the next menu point or to the end of the menu, which returns the display to the set point val-
ue, by pressing the “P“ key. To exit the menu and return back to the normal display quickly, depress the “P“ key for 5 seconds.
6. To return back to the previous position in the menu, press the “F“ key
I
0
P
F
ON
OFF
DISPLAY
PROGRAMMING MODE / ENTER
UP
DOWN
BACK
P
Example
F
P
P
P
P
P
P
P
REOTRON MDW 700 Operating instructions
10
7.3 Indications on display
During normal running mode ‘run’ is shown in the LED display. In the programming mode an abbreviation for the corresponding parameter (see setting up instructions) and the setting values, are displayed. Setting changes are stored upon leaving the programming mode or after a pause of 100 seconds.
Initialisation Phase. When the supply voltage is connected (Left decimal point blinks)
Normal Operation
Unit is not enabled
Left decimal point is present. Current regulation is active. The maximum current of the unit or the regulated current set point value has been reached.
The two upper vertical segments of the first digit illuminate. Peak value limiter. This is caused by a fault condition on either the load or by the externally generat­ed effective value, feedback signal. The load impedance is too low, for example, or the effective value is too high. The upper horizontal segment of the first digit illuminates. Maximum control limit of the controller has been reached. The unit has no more regulation range available and so the output voltage is near to the supply voltage.
Lower horizontal of the first digit illuminates. Maximum power limit has been reached
Under Voltage, input voltage to too low.
7.4 Error Messages
Over temperature of the power semi-conductors, output is inhibited. Use `C009` to reset
Overvoltage, input voltage too high, output is inhibited. Use `C009` to reset
Error messages must be reset in menu `C009`
REOTRON MDW 700 Operating instructions
11
8.0 Settings
The following table contains all the available key settable parameters. The unit is supplied with factory settings that can be recalled from access code “C210” under FAC. User codes can be saved under code “C143” and then recalled with code “C210” under USPA.
Parameter: Code
Factory
Default
Menu Code
Set point
when internal
set point
is selected only!
Voltage set point
0...100 % U. 0 % 002
Current set point
0...100 % I. 0 % 002
Power set point
0…100 % P. 100 % 002
Configuration
External set point OFF
0 / I E.S.O 0 003
4...20 mA (only when E.S.O. = 0)
0 / I 4.20 0 003
Enable Inverse
0 / I -En. 0 003
External Voltage set point
0 / I E.F.U. 0 003
External Current set point
0 / I E.F.I. 0 003
Power regulation
0 / I E.F.P 0 003
Full wave control
0 / I F.S.P 0 003
Ready relay
0 / I r.b 0 003
Parameter
Minimum Output Voltage (without set point)
0...100 % U. 0 % 020
Minimum Output Current (without set point)
0...100 % I. 0 % 020
Minimum Output Power (without set point)
0...100 % P. 100 % 020
Maximum Output Voltage (Limit)
25...100 % u 100 % 020
Maximum Output Current (Limit)
25...100 % i 100 % 020
Maximum Output Power (Limit)
25...100 % p 100 % 020
Voltage Regulator – P Characteristic
1...100 P.U. 20 020
Current Regulator - P Characteristic
1...100 P.I. 15 020
Power Regulator - P Characteristic
1...100 P.P. 15 020
Soft Start (ramp)
0...60 Sec. /. 0,1 020
Soft Stop (ramp)
0...60 Sec. \ 0,1 020
Interface
Interface ON
0 / I S.I.F. 0 017
Service
Save User Parameter
PUSH 143
Restore Factory Default Settings
FAC. 210
Enable advanced Service mode
0 / I En.S. 0 127
Display software version
001
REOTRON MDW 700 Operating instructions
12
9.0 Setting up instructions
9.1 Internal set point
Code C 002
9.2 Unit configuration
Code 003
P
P
P
P
P
P
P P
P P
P P
P
P
P
P
P P
P P
U.P.A. = 0 = Regulation mode U.P.A. = I = control mode
Only in Service Mode C 127 En.S. = I
E.S.O. = 0 = External Set point E.S.O. = I = Internal Set point (Keys)
4.20 = 0 = External Set point 0...20 mA / 0...10V
4.20 = I = External Set point 4...20 mA
E.F.U.= 0 = internal feedback voltage E.F.U. = I = external feedback voltage
Running mode
E.F.P. = 0 = Voltage- / Current regulation E.F.P. = I = Power regulation set point
F.S.P. = 0 = Phase angle control F.S.P. = I = Full wave control
r.b. = 0 = Relay = Status function r.b. = I = Relay = Fault function
-E.n. = 0 = Invert Enable Off
-E.n. = I = Invert Enable On
E.F.I. = 0 = internal feedback current E.F.I. = I = external feedback current
P
Set point 1, Voltage [%]
Set point 2, Current [%]
F
P
P
P
P
P
Running mode
Set point 3, Power [%]
P
P
REOTRON MDW 700 Operating instructions
13
9.2.1 Service menu Display set-points sent to the unit.
9.2.2 Display effective values measured inside unit
P
Code 050
Display set point voltage [%]
Display set point power [%]
F
P
P
P
Running mode
Display set point current [%]
P
P
Code 051
Display feedback voltage [%]
Display feedback power [%]
F
P
P
P
Running mode
Display feedback current [%]
P
REOTRON MDW 700 Operating instructions
14
9.3 Setting Up Procedures
9.4 Select Interface
Code C 017 Interface (Option)
Communication using the interface is activated by setting parameter “S.I.F.” to “I”. Should there be a need to run under manual control e.g. for testing, then this parameter should be set to “0”.
P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Code 020
P
P
P P
P P
Min ouptput voltage [%] (without external set point)
Min output current [%] (without external set point)
Output voltage limit [%] Umax
Start ramp time [Sec.]
Running mode
Output current limit [%] Imax
P-Char current regulation
Stop ramp time [Sec.]
Min output power [%] (without external set point)
P-Char power regulation
Output power limit [%] Pmax
P-Char voltage regulation
0 = Interface OFF I = Interface ON
Running mode
P
P P
P
REOTRON MDW 700 Operating instructions
15
9.5 Save current settings
Code C 143
9.6 Restore parameter settings
Code C 210
9.7 Software version
9.8 Hide parameter menus
Code C 117
If Hd.C. = I all parameter menus are hide. Set Hd.C to "0" again for change parameters.
Save current parameter settings
Running mode
P P
P
P
Restore factory settings
Running mode
Restore user settings (previously saved in "C 143"
P
P
P
P
P
P
Hd.C. = 1= Hide menus
Running mode
P P
P
P
Code 001
Version
Date
Running mode
P P
P
P
P
P
REOTRON MDW 700 Operating instructions
16
10.0 Connection diagram
0(4)...20 mA
0...+10 V
Pot. 10 KR
SETPOINTS
VOLTAGE CURRENT
-
+
+10V
+10V
-
+
-
+
-
+
24 V
ENABLE
EXTERNAL
FILTER
EXTERNAL
FEEDBACK
0...5V
AC/DC
0...10V
DC
0...10V
DC
U U I
ACTUAL VALUE
OUTPUT
RELAY
STATUS
LOAD
I
U
PE
L1 L2
L3L2
W
1
2 3
4
5
6 7 8 3332
31
15 16 17 18 11 12 13
14
41 42 43
+
-
+
-
V
PE
PE
L1
U
L3
FAILURE
44
45 46
3 AC 230/400 V 50/60 Hz
I
INTERFACE
OPTION
Interface
24 V
DC
+
-
CONTROL LOGIC
3635
34
RELAY
Fan
(MDW 50-300)
U
MDW 700
0...5V
AC/DC
I
(21)
(22) (23)
(26)
(27)
(28)
(24)
(25)
230/240V AC
50/60Hz
(T=Fan test
connector)
NTL
REOTRON MDW 700 Operating instructions
17
10.1 Connection details
0...+10 V
0(4)...20 mA
Set point
voltage
Set point
current
Pot. 10 K
1
2
3 456
7 8
+10V
+10V
1
2 3 456 7 8
1
2
3 4 5 6
7 8
0...+10 V0(4)...20 mA
Set point
voltage
Pot. 10 K
1
2
3 456
7 8
+10V
+10V
1
2
3 456
7 8
1
2 3 456 7 8
0...+10 V0(4)...20 mA
Set point
current
Pot. 10 K
1
2
3 456
7 8
+10V
+10V
1
2
3 456
7 8
1
2
3 456
7 8
+10V
+10V
+10V
+10V
+10V
+10V
+10V +10V
Voltage and current regulation
Voltage regulation
Current regulation
0...+10 V0(4)...20 mA
Set point
power
Pot. 10 K
1
2
3 456
7 8
+10V
+10V
1
2
3 456
7 8
1
2
3 456
7 8
+10V
+10V
+10V
+10V
Power regulation
If using 4...20 mA signal, set parameter 4.20 = I in Menu " C003"
If using 4...20 mA signal, set parameter 4.20 = I in Menu " C003"
If using 4...20 mA signal, set parameter 4.20 = I in Menu " C003"
If using 4...20 mA signal, set parameter 4.20 = I in Menu " C003"
Actual
output
value
Current 0...10 V, DC
Voltage 0...10 V, DC
power
RESERVE
11 13 14 15 16 17 1812
RESERVE
44 45
46
Fault
Relay
Internal Relay
41 42
43
Internal Relay
Relay
Reserve
REOTRON MDW 700 Operating instructions
18
255
L1 L2 L3 PE
U V W PE
REOTRON
MDW
PROFIBUS
DP
24V DC
Us
BA
1
ADR.
8
PE
FOR CONTINUED FIRE
PROTECTION REPLACE
ONLY WITH SPECIFIED
TYPE AND RATED FUSE
DISCONNECT POWER
INPUT BEFORE
REPLACING FUSE
REOTRON
MDW
230V
AC
I
0
P
F
210
320
37,5
217,5
8
312
6,5 mm
14,5 mm
6,5 mm
Option
11.0 Dimensions
MDW 700 10 A / 25 A
MDW 700 50A / 80A
Attention connect the fan!
REOTRON
MDW
PROFIBUS
DP
24V DC
Us
BA
1
ADR.
8
PE
41 42 43 44 45 46 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 831 32 33 34 35 36
FOR CONTINUED FIRE
PROTECTION REPLACE
ONLY WITH SPECIFIED
TYPE AND RATED FUSE
DISCONNECT POWER
INPUT BEFORE
REPLACING FUSE
I
0
P
F
Option
PE L1
L2 L3
PE U
V W
290
B
5
285
A
210
5 mm
5 mm 9 mm
15
Type
MDW 25
MDW 10 with Interface
130
110
MDW 10
A
MDW 25 with Interface
160 160
B
70 90 90 90
REOTRON MDW 700 Operating instructions
19
MDW 700 110A / 150A / 200A Attention connect the fan!
7,5
4
1
5
4
3
0
255
210
231 12
Ø6
Ø6
Ø8,5
Ø8,5
1
6
2
7
3
8
4
9
5
L1 L2 L3
U V W
DO NOT USE
WITHOUT COVER
PROFIBUS
DP
24V DC
Us
BA
1
ADR.
8
PE
REOTRON
MDW
www.reo.de
FOR CONTINUED FIRE PROTECTION REPLACE ONLY WITH SPECIFIED TYPE AND RATED FUSE
DISCONNECT POWER
INPUT BEFORE
REPLACING FUSE
P
F
I
0
PE
230V
AC
REOTRON MDW 700 Operating instructions
20
MDW 700 300A
Attention connect the fan!
Ø5,0
6
2
5
9
320
362
300
33414301
312
Schraube
M10x40 / 933
Input 230V
50/60Hz
REOTRON
MDW
L1L2L3
U V W
www.reo.de
P
F
I
0
1 2 3
U
L1
VL2W
L3
Ø8,5
Ø8,5
Input air cooling
Input air cooling
Output air cooling
2
7
3
8
4
9
5
1
6
DP 24
PROFIBUS
DP
24V DC
ADR.
1
8
U
BA
RESET
PE
PROFIBUS-DP
PE
REOTRON MDW 700 Operating instructions
21
MDW 700 WK (water-cooled)
Type A B MDW - WK 115, 160, 250, 350 400 380 MDW - WK 450, 600 550 530
REOTRON
MDW
L1L2L3
U
www.reo.de
P
F
I
0
UL1VL2W
L3
Ø 9,0
Ø 19,0
2
0
2
2
1
2
A
B
8
180
300
330
2
7
3
8
4
9
5 1
6
DP 24
PROFIBUS
DP
24V DC
ADR.
1
8
U
BA
RESET
PE
PROFIBUS-DP
PE
Ø 9,0
REOTRON MDW 700 Operating instructions
22
12.0 Putting into service
Safety Instruction
Qualified personnel only, are permitted to install electronic equipment
Because attenuation capacitors (Y-capacitors) are used, leakage current flows through the case to pro­tective earth (PE). Therefore, units must be earthed.
12.1 Preliminaries
Check if the local supply voltage is the same as the rated voltage for the unit (rating plate) and that the load is within the permitted power range.
Connect the control unit in accordance with the connection diagram.
Adjust set-points to zero.
Switch off enable (if used)
Check if cables are connected correctly.
The control unit is now ready for operation and can be switched on (power supply, enable). The unit is factory set according to the rating plate i.e. 100% set point equals 100% voltage, cur­rent or power.
Set-point control only can be used, in which case no other settings are necessary.
12.2 Measurements and Settings
Because of the phase-angle-control, the shapes of the supply voltage and current sine curves are changed. The output voltage and current must be measured with effective value meter (true-RMS).
12.3 Putting into service without a proper load
A thyristor can only be switched ("fired") into a conducting state, if the current level is sufficiently high enough. It will only switch-off, if the current is lower than the threshold current (every time the current goes through the zero-crossing point). When the thyristor controller is put into service, without a proper load, realistic measurements such as the voltage, for example, cannot be obtained. Even the setting of the output current i.e. limit, can only be done with a proper load and not by short circuiting the output of the thyristor controller. This is because the thyristor, once “fired”, cannot be turned off. The current has to pass through "zero" for the thyristor to switch off. Using a low impedance load it is not possible to evalu­ate the current level from the internal current flow. If a proper load is not available or not possible to carry out the correct commissioning procedure then a makeshift test can be carried by connecting a resistive load, such as incandescent lamps to the output of the thyristor controller.
!
REOTRON MDW 700 Operating instructions
23
13.0 Installation of Thyristor Control Units
13.1 Fuses
The REOTRON MDW... series of thyristor controllers are fitted with semiconductor fuses, which protect the power semiconductors (thyristors) from damage when there is a short-circuit on the output. These fuses are selected for the permitted peak current of the semiconductors and are not provided for protec­tion against overload or line faults! Fuses are provided only in the current-carrying circuits with thyristors.
Fuses for overload, line and earth fault protections should be fitted to the incoming power side.
13.2 Incoming breaker
An isolator must be connected in front of a thyristor-controller, mounted inside a control panel (VDE 0160/6.3.1) because of the leakage-current from a high-impedance thyristor and hence the current flow through the protection circuit. This can be used to disconnect the unit from mains supply before a routine shut-down. Because all REOTRON thyristor-controllers have an enable input, it is possible to inhibit the input pulses, and hence firing of the thyristors, until the main contactors have securely closed or before the contactors open again when shutting down. When enable inputs are used in this way, the contactors can be rated for current-free switching, in which case AC1 would be suitable. If direct-on-line switching is used i.e. by switching the thyristor controller, without using the enable, the rating of the contactors must be in accordance with AC3.
13.3 Output Breaker
A circuit-breaker on the output of the thyristor controller should be avoided, because it cannot operate without a load. Current or voltage monitoring in the output of the thyristor controller must be used to con­trol the circuit-breaker at the input side. Current-free switching of the thyristor controllers’ output (e.g. load switching) is possible, however, by using the enable input.
13.4 Installation and climatic Conditions
The mounting base should be free of vibration, if possible. Note that the temperature of the heat-sink rises when a power controller is operating. The heat-sink must be mounted vertically to ensure efficient cooling. The ambient temperature range allowed below the heat-sink is 0°...+45°C. The relative air hu­midity is < 75% without dew. The clearance below the unit should be at least100mm and above at least 150mm. There must be a clearance of 50mm between units mounted next to each other. For altitudes above 1000m the power must be derated by 0,5% per 100m additional height.
13.5 Signal cables
Set Points If external voltage (0...10V) or current (0(4)...20mA) set-points are used; care should be taken to ensure that all equipment is connected through equal-potential bonding. If the bonding is earthed, then this should be at a single point, thus avoiding earthing loops and possible coupled interference.
REOTRON MDW 700 Operating instructions
24
14.0 Interference prevention
14.1 Earthing
Correct earthing of electronic controls is highly important for two reasons: First it ensures the safety of operators and service personnel, and secondly it provides a fail-safe opera­tion of the equipment. Therefore, in addition to providing protective earthing, in accordance to DIN stand­ards, it also provides an earth path for pulse interference produced during operation. For the latter, con­trollers that are mounted onto a chassis–plate in a control panel should be bonded to earth with the shortest possible connection and the largest possible earth contact area and also, for example, onto the centrally bonded chassis-plate. The reason for this is to ground high-frequency interferences produced by switching on the mains (contactors, relays, switches) before they cause fault conditions. If the earth con­ductors are too long and if they run together with other cables, in one cable duct, then they are unsuitable for grounding high-frequency noise. The more complex the unit and the more "intelligent" the functions - especially serial bus connections – then the more important it is to use correct earthing techniques.
14.2 Control cables
Control cables also are "antennas" that receive interference produced by other loads. Signal cables that are run alongside power cables can generate voltage spikes through inductive and capacitive cross­coupling. Therefore control conductors should not be mixed with power cables in the same cable ducting. If this cannot be avoided then shielded cables should be used. In particular cables from inverters to mo­tors are very critical because of the presence of high-speed switching. There should be maximum dis­tance between control cables output cables from frequency inverters. The shielding around the control conductors should be grounded onto a large contact area (earthed mounting plate) at the equipment end.
14.3 Interference protection of other external components and equipment
Contactors produce extreme Burst-interferences on switching. Contactor coils must be connected with
RC-snubbers. Suitable RC-snubbers can be obtained from switch manufacturers. Magnets / magnetic valves are also interference sources in the same way as contactors. RC- snubbers
and varistors can be components and varistors can be connected across these components
Frequency inverters are to connect to a mains filter recommended by the manufacturer. Motor wires should be shielded and routed away from control cables.
REOTRON MDW 700 Operating instructions
25
15.0 Engineering notes
Type
connection terminal
(power)
connection terminal
(control)
REOTRON MDW 700-10 4 mm2 1,5 mm2 REOTRON MDW 700-25 4 mm2 1,5 mm2 REOTRON MDW 700-50 16 mm2 1,5 mm2 REOTRON MDW 700-80 35 mm2 1,5 mm2 REOTRON MDW 700-110 50 mm2 1,5 mm2 REOTRON MDW 700-150 70 mm2 1,5 mm2 REOTRON MDW 700-200 95 mm2 1,5 mm2 REOTRON MDW-WK 700-115 copper bar 10,5 mm hole 1,5 mm2 REOTRON MDW-WK 700-160 copper bar 10,5 mm hole 1,5 mm2 REOTRON MDW-WK 700-250 copper bar 10,5 mm hole 1,5 mm2 REOTRON MDW-WK 700-350 copper bar 10,5 mm hole 1,5 mm2 REOTRON MDW-WK 700-450 copper bar 10,5 mm hole 1,5 mm2
Type
recommended line filter in the mains input
REOTRON MDW 700-10 CNW 207 / 10 REOTRON MDW 700-25 CNW 207 / 35 REOTRON MDW 700-50 CNW 207 / 50 REOTRON MDW 700-80 CNW 207 / 80 REOTRON MDW 700-110 CNW 207 / 150 REOTRON MDW 700-150 CNW 207 / 200 REOTRON MDW 700-200 CNW 207 / 200 REOTRON MDW-WK 700-115 CNW 207 / 150 REOTRON MDW-WK 700-160 CNW 207 / 200 REOTRON MDW-WK 700-250 CNW 107 / 280 REOTRON MDW-WK 700-350 CNW 107 / 500 REOTRON MDW-WK 700-450 CNW 107 / 500
Type
weight in kg
min. cable cross
-
section
Power loss
REOTRON MDW 700-10 4 1,5 mm2 40 W REOTRON MDW 700-25 5 4 mm
2
100 W
REOTRON MDW 700-50 8,5 16 mm
2
180 W
REOTRON MDW 700-80 9,5 35 mm
2
310 W REOTRON MDW 700-110 11 50 mm2 480 W REOTRON MDW 700-150 14,5 70 mm
2
540 W REOTRON MDW 700-200 16 95 mm2 660 W REOTRON MDW-WK 700-115 7 70 mm2 500 W REOTRON MDW-WK 700-160 8 95 mm
2
580 W
REOTRON MDW-WK 700-250 10,5 120 mm
2
900 W REOTRON MDW-WK 700-350 13 185 mm2 1260 W REOTRON MDW-WK 700-450 16 300 mm2 1620 W
Type
recommended input
fuse: Type: gl / gG
internal semiconductor fuse
REOTRON MDW 700-10 16 A SI 16 FF ordering number: 0900 10 REOTRON MDW 700-25 25 A SI 35 ET ordering number: 0900 17 REOTRON MDW 700-50 63 A SI 80 ET ordering number: 0900 19 REOTRON MDW 700-80 100 A SI 140 EET ordering number: 0900 20 REOTRON MDW 700-110 125 A SI 160 EET ordering number: 0900 21 REOTRON MDW 700-150 160 A SI 250 EET ordering number: 0900 22 REOTRON MDW 700-200 200 A SI 315 EET ordering number: 0900 23 REOTRON MDW-WK 700-115 125 A non-existent REOTRON MDW-WK 700-160 200 A non-existent REOTRON MDW-WK 700-250 250 A non-existent REOTRON MDW-WK 700-350 400 A non-existent REOTRON MDW-WK 700-450 500 A non-existent
REOTRON MDW 700 Operating instructions
26
Headquarters
- Germany
REO ELEKTRONIK AG
Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188
REO INDUCTIVE COMPONENTS AG
Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188
E-Mail: info@reo.de
Internet:
www.reo.de
China
REO Shanghai Inductive Components Co., Ltd No. 536 ShangFeng Road · Pudong, 201201 Shanghai · China Tel.: +86 (0)21 5858 0686 · Fax: +86 (0)21 5858 0289 E-Mail: info@reo.cn · Internet: www.reo.cn
France
REO VARIAC S.A.R.L. ZAC Du Clos aux Pois 1 · 6/8 rue de la Closerie-LISSES· F-91048 Evry Cédex Tel.: +33 (0)1 6911 1898 · Fax: +33 (0)1 6911 0918 E-Mail: reovariac@reo.fr · Internet: www.reo.fr
Great Britain
REO (UK) Ltd. Units 2-4 Callow Hill Road · Craven Arms · Shropshire SY7 8NT · UK Tel.: +44 (0)1588 673 411 · Fax: +44 (0)1588 672 718 E-Mail: main@reo.co.uk · Internet: www.reo.co.uk
India
REO GPD INDUCTIVE COMPONENTS PVT. LTD 2/202 Luna Road · Village Luna · Taluka Padra Vadodara - 391440 · India Tel.: +91 (2662) 221723 E-Mail: info@reogpd.com · Internet: www.reo-ag.in
Italy
REO ITALIA S.r.l. Via Treponti, 29 · I-25086 Rezzato (BS) Tel.: +39 030 279 3883 · Fax: +39 030 279 0600 E-Mail: info@reoitalia.it · Internet: www.reoitalia.it
Poland REO CROMA Sp.zo.o ul. Pozaryskiego 28, bud 20 · PL-04-703 Warszawa Tel.: +48 (0)22 812 3066 · Fax: +48 (0)22 815 6906 E-Mail: croma@croma.com.pl · Internet: www.croma.com.pl
Spain
REO ESPAÑA 2002 S.A. C/Manuel Ventura i Campeny 21B · local 9 · E-08339 Vilassar de Dalt (Barcelona) Tel.: +34 937 509 994 · Fax: +34 937 509 995 E-Mail: info@reospain.com · Internet: www.reospain.com
Switzerland
REO ELEKTRONIK AG Im Halbiacker 5a · CH-8352 Elsau Tel.: +41 (0)52 363 2820 · Fax: +41 (0)52 363 1241 E-Mail: info@reo.ch · Internet: www.reo.ch
Turkey
REOTURKEY ELEKTRONİK San. ve Tic. Ltd. Şti.
Halil Rıfatpasa Mah. · Darülceze CD Perpa Tic Merkezi B Blok Kat 8 No:1095 · TR-34384 Sisli – Istanbul Tel.: +90 (0)212 2215 118 · Fax: +90 (0)212 2215 119 E-Mail: info@reo-turkey.com · Internet: www.reo-turkey.com
USA
REO-USA, Inc. 8450 E. 47th St · USA-Indianapolis, IN 46226 Tel.: +1 317 8991 395 · Fax: +1 317 8991 396 E-Mail: info@reo-usa.com · Internet: www.reo-usa.com
Divisions
- Germany
REO INDUCTIVE COMPONENTS AG
TrainTechnologies Division Centre of Competence Berlin Erasmusstraße 14 · D-10553 Berlin Tel.: +49 (0)30 3670236t 0 · Fax: +49 (0)30 3670236 10 E-Mail: zentrale.berlin@reo.de · Internet: www.reo.de
Fertigung /Production TrainTechnologies Division Eduard-Maurer-Straße 13 · D-16761 Hennigsdorf
IBK Drives Division Holzhausener Straße 52 · D-16866 Kyritz Tel.: +49 (0)33971 485 0 · Fax: +49 (0)33971 485 90 E-Mail: ibk@reo.de · Internet: www.reo.de
Setzermann Medical Division Schuldholzinger Weg 7 · D-84347 Pfarrkirchen Tel.: +49 (0)8561 9886 0 · Fax: +49 (0)8561 9886 40 E-Mail: setzermann@reo.de · Internet: www.reo.de
Test and PowerQuality Division Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: main@reo.de · Internet: www.reo.de
Loading...