Product Codes: FP4057T: Flexi Panels, 320 x 240 QVGA, 5.7” Color
TFT, with no expansion slot.
FP4057T-E: Flexi Panels, 320 x 240 QVGA, 5.7” Color
TFT, with 5 expansion slots.
FP4057TN: Flexi Panels, 320 x 240 QVGA, 5.7” Color
TFT, Ethernet with no expansion slots.
FP4057TN-E: Flexi Panels, 320 x 240 QVGA, 5.7” Color
FP4057Tx-x Specifications
FP4057Txx is Flexi Panel series product. Flexi Panel Series operator interfaces provide human-machine interface for PLCs / Inverters. It communicates with PLCs / Inverters over serial communication port to fetch the information. Information can be displayed over LCD or can be used to build a logic.
Specifications of FP4057Tx-x: Power Supply: For FP4057T: 24VDC; 7W
Display: 5.7”TFT (320 x 240 Pixels)
Color Graphical Display Bezel: IP 65 rated Keypad LEDs: 7 Memory: 6 MB Max. Application Memory Communication: 2 COM Ports: COM1 & COM2: RS232/RS485/RS422 USB Device: For Upload and Download USB Host: For mass storage interface
Operating Temp.: 0 to 50 C Humidity: 10% to 90% (Non condensing) Panel cutout: 184.00 mm x 131.00 mm Weight: For FP4057TX: Approx. 695gm
For FP4057TX-E: 715gm
For FP4057TN: 24VDC; 8W
For FP4057TX-E: 24VDC; 10W
Ethernet: For connecting to a PLC, programming of
HMI, a third party device or drive
(10/100Mbps)
o
Panel Mounting and Panel cut-out:
Tighten the mounting screws evenly to a torque between 0.6 and
0.7 Nm to maintain water and dust resistance. Make sure the panel is not dirty and warped and that it is strong enough to hold the unit.
Note: Maximum Panel thickness (On which unit is to be mounted) should be 6.0mm (Tolerance: +0.00mm and -0.50mm).
Procedure to mount the unit:
FIGURE - 1 There are four (4) slots provided on the unit case to
mount the unit. Also a set of four (4) mounting hardware is provided with each FP5 unit. (It is consist of single cap nut, screw and clamp)
FIGURE - 2 Insert the clamp into the slot provided on the unit
case. hold the unit straight. Tighten the mounting screws evenly to a torque between 0.6 and 0.7 Nm.
FIGURE - 3 Thus this mounting hardware will hold the unit with
the surface.
F1
F2
F3
F4
F5
F6
184.00
195.00
142.00
131.00
Gasket
Front Case
Mounting Hardware
Back Case
Quick Start Manual Doc. No.: QS\FP5\0310; Ver.: 1.00C Renu Electronics Pvt. Ltd.; Pub.: 06/2011
System Components:
- FP4057Txx unit with LCD, Touch Screen and RTC
- Power Supply Connector
- Installation Kit: Gasket, Four Mounting hardware (each mounting hardware set consists of single cap nut, screw and clamp).
- *FlexiSoft Software Installer CD
*FlexiSoft: Please check the latest version each time. Note: User should order PLC / programming cable separately.
WARNING:
WARNING: DO NOT REMOVE OR REPLACE WHILE CIRCUIT IS LIVE UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITIBLE CONCENTRATIONS OF FLAMMABLE SUBSTANCES.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - Substitution of components may impair suitability for Class I, Division 2.
WARNING - CAUTION, Battery May Explode If Mistreated. Do Not Recharge, Disassemble Or Dispose Of In Fire.
WARNING - Replace Battery With type CR1225FH-LF, manufactured by Renata SA, only. Use of Another Battery May Present A Risk Of Fire Or Explosion. See Owner's Manual For Safety Instructions”
A recommendation for the user to periodically inspect the sealed devices used, for any degradation of properties and replace if degradation is found.
Figure - 1
Figure - 2
Figure - 3
RAM 256MB Hard Disk 800MB (including 200MB for the .NET Space Framework Redistributable) Display 1024 x 768 High Color 16-bit Mouse/ Required Keyboard
(i) Insert the CD in the PC drive and follow the instructions given.
(ii) In case the software does not autoexecute, please run the \DISK1\SETUP.EXE file from CD.
(iii) In case software has been downloaded from the Web site, first Extract the software installation files, then run the Setup.exe file.
Getting Started:
User should follow the given sequence to configure and use any Flexi Panel series unit:
1. Install FlexiSoft Software.
2. Create a PZM application using FlexiSoft software.
3. Connect programming cable.
4. Download Firmware i.e. driver for the PLC if PLC is being used. FP unit cannot communicate with PLC till the required driver is downloaded to the unit.
5. Download application.
6. Now FP unit is ready to use in the system.
Install the software:
The minimum system requirements for running the FlexiSoft software are: Processor 800MHz Pentium processor OR euivalent
processor Operating Microsoft Windows 2000 System Microsoft Windows XP Professional / Home
Edition with SP2 / Vista
Technical Support
For Technical support please contact factory along with the unit serial number and revision number written on the address sticker of the unit. Also provide information of the PLC if used in application.
Renu Electronics Pvt. Ltd. Survey No. 2/6, Baner Road, Pune – 411 045. Maharashtra, INDIA Tel: +91 20 27292840 Fax: +91 20 27292839 E-mail: support@renuelectronics.com Website: www.renuelectronics.com
MANUAL REVISIONS: Rev. No. Doc. No. Date Description
1.00A QS\FP5\0310 21/12/10 Rated input voltage is mentioned.
1.00B QS\FP5\0310 17/01/11 Wattage & weight of the unit is updated.
1.00C QS\FP5\0310 28/06/11 Ethernet models added.
Cable Diagrams: 4 Wire RS422/RS485 Cable connections:
Cable Diagrams: PC to unit programming cable:
Cable Diagrams: 2 Wire RS485 Cable connections:
Quick Start Manual Doc. No.: QS\FP5\0310; Ver.: 1.00C Renu Electronics Pvt. Ltd.; Pub.: 06/2011
Grounding:
The optimum method for grounding electronic equipment is to ground it separately from other high-power systems, and to ground more than one unit of electronic equipment with a single­point ground. The grounding marked terminal (see below) is provided on the unit.
Note: Do not use a ground that has an unstable impedance, such as painted screws, or ground subject to vibration.
Port Details (COM1 and COM2): Pin description of communication port for FP models is as follows: