Reno A&E P-1400 Operations Manual

Page 1
P-1400
Firmware Version 4.02
Operations Manual
Four Channe l Menu Drive Programmable Inductive Loop Vehicle
Detector Designed for Railroad Applications
Four Loop Inputs, Two Vital Outputs, a nd One Vital Input
Built-in Loop Analyzer for Each Channel
This manual contains technical in formation for the
P-1400 Loop Detector
pn 889-1600-04 Revision: April 2020
Page 2
Page 3
THE FOLLOWING PRODUCT WAS DESIGNED, INSPECTED , TESTED AND
MANUFACTURED IN THE USA BY EBERLE DESIGN, INC. IN PHOENIX, ARIZONA.
INFORMATION CONTAINED HEREIN IS PROPR IETARY TECHNICAL INFORMATION OF EBERLE DESIGN, INC. PUBLICATION, REPRODUCTION OR USE IN WHOLE OR PART IS
NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING. ALL
REGISTERED TRADEMARKS OF EBERLE DESIGN INC. ARE UNDER
IT IS AN EBERLE DESIGN, INC. RECOMMENDATION THAT EACH UNIT BE TESTED
AT LEAST ANNUALLY TO ENSURE COMPLIANCE WITH FACTORY
SPECIFICATIONS AND MEETS PROPER OPERATIONAL STANDARDS. THE
RESULTS OF THIS TESTING WILL BE DOCU M EN T ED .
© COPYRIGHT
MAINTENANCE NOTE
Page 4
Page 5
Model P-1400 Operations Manual
Table of Contents
Section 1 General Description ................................................................................................................................ 1
Section 2 General Characteristics .......................................................................................................................... 2
2.1 Loop Frequency .......................................................................................................................................... 2
2.2 Sensitivity ................................................................................................................................................... 2
2.3 Option 1: Loop Inductance Display ............................................................................................................. 2
2.4 Option 2: Loop Inductance -∆L/L Display .................................................................................................. 2
2.5 Option 3: Noise Filter ................................................................................................................................. 2
2.6 Option 4: Detection Zone Tracking ............................................................................................................. 3
2.7 Option 5: Sensitivity Boost ......................................................................................................................... 3
2.8 Option 6: Audible Detect Signal ................................................................................................................. 3
2.9 Loop Check ................................................................................................................................................. 4
2.10 Detector ID ............................................................................................................................................... 4
2.11 Option 7: Synch Feature ............................................................................................................................ 4
2.12 Option 10: Inverted Vital Output............................................................................................................... 4
2.13 Primary Vital Output Delay ...................................................................................................................... 4
2.14 Primary Vital Output Extens io n ................................................................................................................ 4
2.15 Input / Output Mapping ............................................................................................................................. 4
2.16 Full Restore to Factory Default Settings .................................................................................................... 5
2.17 Diagnostic Features Activation ................................................................................................................. 5
2.18 Password Protection .................................................................................................................................. 5
Section 3 Specifications ........................................................................................................................................... 6
3.1 Physical 6
3.2 Electrical ..................................................................................................................................................... 6
3.3 Operational
3.4 Table: Sensitivity, -∆L/L, and Response Time ............................................................................................ 9
3.5 Table: Default Settings ................................................................................................................................ 9
3.6 Table: Terminal Assignments (Labeled on P-1400 Motherboard) ............................................................. 10
3.7 Table : P i n As s i g n ments (DB-9 Communication Interface Connector) ...................................................... 10
Section 4 User Interface ........................................................................................................................................ 11
Section 5 Installatio n and Set-Up ......................................................................................................................... 12
5.1 Initial Installation Start-up Mode Display Screens .................................................................................... 14
5.2 Program Mode Display Screens ................................................................................................................ 15
5.2.1 Primary Vital Output Mapping Screens .......................................................................................... 19
5.2.2 Auxiliary Vital Output Mapping Screens ....................................................................................... 20
5.3 Normal Mode Display Screens .................................................................................................................. 23
5.4 Error Messa ge Display Screens ................................................................................................................. 24
5.5 Loop Check Pass / Fail Indications ........................................................................................................... 25
5.6 Vital Input (VITAL IN) Status / Fail I nd icat ions ....................................................................................... 26
5.7 Primary Vital Output (VIT AL OUT) St a tus / Fail Indic a t io ns ................................................................... 26
5.8 Auxiliary Vital Output (VITAL AUX) Status / Fail Indications ................................................................ 26
5.9 Sync h Fa i l I nd ic a t i o ns ............................................................................................................................... 26
5.9.1 Series Synch Fail Indications ......................................................................................................... 26
5.9.2 Parallel Synch Fail Indications ....................................................................................................... 27
5.10 Loop Fail Indications .............................................................................................................................. 27
5.11 Settin g Sensit ivity Using the Bargrap h .................................................................................................... 27
5.12 Full Restore To Factory Default Settings ................................................................................................ 28
5.13 Diagnostic Features Activation ............................................................................................................... 28
5.14 Display Test ............................................................................................................................................ 28
5.15 Changing Processor Board or Motherboard............................................................................................. 28
Section 6 Block Diagram ...................................................................................................................................... 30
Section 7 Theory of Operation ............................................................................................................................. 31
Section 8 Maintenance and Tr o uble shooting ...................................................................................................... 32
8.1 Basic Troubleshooting Tips ...................................................................................................................... 32
8.2 Things to Know About Loops ................................................................................................................... 33
................................................................................................................................................. 6
Page 6
Page 7

Section 1 General Description

This product manual was written for people installing, operating, and maintaining the Reno A&E Model P-1400 inductive loop vehicle detector. The Mode l P-1400 is a four-channel inductive loop vehicle detector designed as a direct, drop-in replacement for older technology detectors that mount in ground level enclosures. It is designed to be used in applications requiring detection of railway vehicles in large detection areas typically required in classification yard switch and sidesw ipe protection, interlocking and movea ble bridge occupancy detection, or detection of roadway vehicles and/or railway vehicles in at-grade crossing sites.
The Model P-1400 monitors and process es signals from four loop / lead-in circuits, four check loop circuits, and one Vital input. These inputs can be pro grammed to co ntrol two Vital o utputs, one pr imary Vital o utput and one auxiliary Vital output. The primary Vital output ca n be controlled by any combination of t he four loop inputs and/or the Vital input. In addition to the four loop inputs and the Vital input (as described above), the a uxiliary Vital output can be controlled by the four loop Health Status inputs that are continuously monitored by the processor. A loop failure will deactivate the Vital output that the loop status input and/or loop Health Status input is programmed to control. The check loop circuits ca n be programmed to s imulate a vehicle detection (every 1 t o 255 minutes) in the loop area as a means of verifying p roper loop operatio n. T he Vital o utputs a nd Vita l input are monitored to ensure they are in the correct state. If the state of the Vital input is not correct, the front panel LED indicator will turn red and all Vital outp uts will be de act ivated. I f the sta te of e ither V ital o utput is not correct, t he front panel LED corresponding to that output will turn red and both Vital outputs will b e de a ctivated.
A Liquid Crystal Display (LCD ), seve n LEDs, and four f r ont panel pushb uttons a re used t o displa y and program all detector functions. The Model P-1400 also incorporates a series of motherboard and front panel mounted connectors to facilitate set-up and operation. Motherboard mounted Wago type connectors are used for detector input and output connections. A front panel mounted nine pin RS-232 co nnector is used for communication with a laptop computer.
The use of a LCD is one feature that disti nguishes this detector from that of other manufacturers. It a llows for more information, never before a vailable, to be displayed to the user during normal operat ion of the detector. Several diagnostic modes are available to aid the technician in troubleshooting detection problems. It also allows easy viewing and setting of all programmable values in the detector. The detector cont inues to operate normally while being programmed. An eight-se g me nt ba r gr a p h a t t he top of the LCD provides a graphical representation of the relative change of inductance as seen by the detector. This automatically takes into account loop size, loop inductance, number of loops, number of turns, geometry, lead-in length, etc. The firs t bar grap h seg ment repre s e nt s the minimum inductance change necessary for the detector to output a call. Larger inductance changes will be indicated by more segments. Each additio nal segment represents the next sensitivity le vel exceeded. Therefore, the bar grap h indicates if the se nsitivity is se t too high or too low, easily facilita ting the idea l setting of se nsitivity level.
All programmed settings are stored in non-volatile memory and can only be changed by programming new settings. Memory stora ge consists o f an internal EEPROM mounted on the processor board and an EEPROM mounted on the motherboard. Settings programmed on either compone nt must match those programmed on the other for the detector to operate. Loss of power or a detector reset will not change the programmed sett ings. If a loop failure occurs, the LCD will display the type of loop failure as L lo (for -25% change or shorted loop condit ions) or L hi (for +25% change or open loop cond itions). Eac h loop failure is counted ( up to a maximu m of 255 failures) and accumulated in the Loop Failure Memory. Information on the number of failures since t he last detector reset or power interruption is very useful during analysis of problems due to intermittent loop operat ion.
The Model P-1400 detector is a scanning detector. The scanning operation sequentially activates the on and off cycle of each detector channel’s oscillator. Because only one channel’s loop input(s) is (are) active at a given time, crosstalk between adjacent loops connected to the sa me scanning detector is minimized. Several Model P-1400 detectors can be linked together via the Synch In and Synch Out lines. This allows loops connected to different detectors to be scanned in series or parallel. When in Program Mode, t he Model P-1400 detector disp la ys t he re al time loop frequency reading for each channel. The eight frequency levels can be incremented or decremented to provide precise frequency settings. This re moves the guesswork when changing frequency sett ings to eliminate crosstalk. NOTE: Adjacent loops connected to different channels of a non-scanning detec tor or different sca nning detectors should be set to different frequencies with the maximum separatio n possible.
The Reno A&E Model P-1400 utilizes the first major innovat ion in inductive loop detectors since the introduct ion of digital detectors. The programming o f all of the detector’s parameters with four normally ope n pushbutton switches not only simplifies setup by removing binary coded rotary or DIP switches, but also increases the reliability of the detector by removing t he dependence on switch co ntacts during normal operation. T he detailed descriptions displayed on the LCD facilitate the interpretation of operational state conditions to determine the detector status.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 1 of 33
Page 8

Section 2 General Characteristics

2.1 LOOP FREQUENCY

There are eight selectable loop frequency settings ( normally in the range of 20 to 100 kilohertz) per loop input. The actual loop operating frequency is a function of the loop / lead-in network a nd the compo nents o f the lo op oscillator circuit. The digital display of t he actual loop operating frequency for each setting makes it easy to quickly identify and elimina te crosstalk in the most difficult to configure installations. The freque ncy display is typically very stable when the loop is vacant and vehicles are not passing close to the loops. If the reading is varying by more than ±1 in the last digit, this is an indication of possible crosstalk between loops.

2.2 SENSITIVITY

There are ten selectable sensitivit y levels per loop input, plus Continuous-Call a nd Loop-Off. The sensiti vity levels are designed so that a one level increase actually doubles the sensitivity and a one level decrease halves the sensitivity. A unique bargraph displayed on the LCD makes it easy to quickly set sensitivity at the ideal level for any loop / lead-in network situation. (See Section 3.4 for actual detection levels at each sensit ivity level.)
C
ONTINUOUS-CALL: When set to the Co ntinuous-Call state, the Loop Status is continuo usly in the Call state
regardless of the presence or absence of vehicles over the loop. If the Loop Status Input is assigned to a Vital Output , the Cont inuo us-Call state w ill deactivate the V ital Output. The loop oscilla tor is disa bled when in the Continuous-Call State. This state is indicated by Call flashing on the LCD. This option can be selected from the Sensitivity menu in Progra m Mode a nd is useful for checking contro ller response and other t roubleshooting activities.
L
OOP-OFF: When set to the Loop-Off state , the Loo p Stat us is con tinuo usly i n the No -Call state regardless of
the presence or absence of vehicles over the loop. If the Loop Status Input is assigned to a Vital Output, the Loop-Off state will not affect the Vital Output. The loop oscillator is disabled when in the Loop-Off State. This state is indicated by OFF flashing on the LCD. This option can be selected from the Sensitivity menu in Program Mode and is useful for checking controller response and other troubleshooting activit ies.

2.3 OPTION 1: LOOP INDUCTANCE DISPLAY

The Loo p I nd uc tance Dis play set t in g c a n be toggled ON or OFF by mome nt a rily pre s s in g e it her the  (UP) or  (DOWN) pus hbu tto n. W hen t his opt io n is enab led ( ON), the LCD dis pla ys t he t ota l lo op inductance (actual loop inductance plus actual lead-in inducta nce) in microhe nries fo r loop ind uctanc e values in the ra nge of 20 to 25 00 microhenries. By recording the inductance of the loop / lead-in circuit when it is first installed, the actual inductance can be compared to the expected inductance to help identify defective loop / lead-in circuits. Loop / lead-in inductance can be easily estimated using the simple formulas included in Section 8.2 of this manual. NOTE: Enabling this option activates it for all loop inputs. This option is automatically disabled 15 minutes after activation or on loss of power.

2.4 OPTION 2: LOOP INDUCTANCE -L/L DISPLAY

The Loop Inductance -ΔL/L Display setting can be toggled ON or OFF by mo mentari ly press ing eit her the (UP) or  (DOWN) pushbutton. When this option is enabled (ON), the LCD displays the percentage of induct ance cha nge (-ΔL/L value) during the Ca ll state. To facilitate the viewing of the maximum amount of change in the -ΔL/L value while traffic is in motion over the detection zone, the channel holds the peak -ΔL/L value for a period of two seconds. NOTE : Enabling this option activates it for all loop inputs. T his option is automatically disabled 15 minutes after activation or on loss of power.

2.5 OPTION 3: NOISE FILTER

Each loop input’s Option 3 has four settings ranging from 3.00 to 3.03. When Optio n 3 is set to 3.00, the option is disab led (OFF), a nd normal noise filtering is used. W hen Option 3 is set to 3.01, 3.02, or 3.03 the option is ON, and increased filtering of the loop signa l is used to eliminate problems assoc iated with particular types of noise. Turning this option ON when not required can degrade the performance of the detector. The default setting o f t his option is 3.00 (OFF). This op tion should only be turned ON at the advice of Reno A&E. NOTE: Each loop can be enabled independently.
3.00 = 250 milliseconds filter.
3.01 = 1 second filter.
3.02 = 2 seconds filter.
3.03 = 10 seconds filter.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 2 of 33
Page 9

2.6 OPTION 4: DETECTION ZONE TRACKING

Each loop input’s Option 4 has nine settings ranging from 4.00 to 4.08. This option allows the user to select a detection zone tracking setting that will maintain detection zone occupancy for an extended period of time. When Option 4 is set to 4.00, the detector will t rack ou t the vehic le (i.e. drop the detection of the vehicle) in four minutes to several hours depending on the amount of inductance chan ge (-ΔL/L) caused by the vehicle when it is detected. The greater the change caused by the vehicle, the longer the time needed to track out the vehicle. When Option 4 is set to 4.01,
4.02, 4.03, 4.04, 4.05, 4.06, 4.07, or 4.08 the option is ON, and the detector wil l provide e xtended detection times.
There are man y fac tors tha t in flu ence t he p roper s ett in g of this op tion. A full expla nat ion of h ow to determine the correct setting is beyond the scope of this manual. Contact a Technical Support representative at Reno A&E regarding proper settin g of this option.
NOTE: Using this option in a long loop application is not recommended. The detector will drop the call prior to the vehicle totally exiting the loop.
4.00 = Tracki ng R ate 0.
4.01 = Tracki ng R ate 1.
4.02 = Tracki ng R ate 2.
4.03 = Tracki ng R ate 3.
4.04 = Tracki ng R ate 4.
4.05 = Tracki ng R ate 5.
4.06 = Tracking Rate 6.
4.07 = Tracki ng R ate 7.
4.08 = Tracki ng R ate 8.

2.7 OPTION 5: SENSITIVITY BOOST

Each loop input’s Option 5 has five settings ranging from 5. 00 to 5.04. W hen Optio n 5 is set to 5. 00, the opt ion is disab led (OFF), a nd no sensitivity boost is added. W hen Option 5 is set to 5.01, 5.02, 5.03, or 5.04 the option is ON, and sensitivity boost is enabled. A fter detect ion, the se nsitivity is boosted to t he currently se lected se nsitivit y level p lus the nu mber of le vel(s ) select ed. The maximu m sens itivit y level that ca n be ob tained w ith or witho ut sensitivity boost is level 10.
5.00 = Off (no sensitivity boost).
5.01 = 1 level of sensitivity boost.
5.02 = 2 levels of sensitivity boost.
5.03 = 3 levels of sensitivity boost.
5.04 = 4 levels of sensitivity boost.

2.8 OPTION 6: AUDIBLE DETECT SIGNAL

Each loop input’s Audible Detect Signa l setting can be toggled ON or OFF by mome nta r ily p re ss i ng e ithe r the (UP) or  (DOWN) pus hbutton. Only one loop input can be turned ON at a t ime. T ur ning this option ON for o ne loop i nput auto matica lly turns it OFF for the other loop inputs. When this option is enabled (ON), an audi ble signal will be activated whenever the detection zone for the selected loop input is occupied. The audible signal indicates actual occupancy of the loop detection zone. This feature allows a technician to watch the detection zone and confirm correct detector operation without having to look at the detector disp lay as well. NOTE: This option is automatically disabled 15 minutes after activation or on loss o f power.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 3 of 33
Page 10

2.9 LOOP CHECK

The Loop Check feature provides a means of auto matically verifying the proper operation of each loop circ uit. The Loop Check Timer can be set for an interval ranging from 0 to 255 minutes in o ne-minute increments. A setting of 000 indicates that the Loop Check feature is off.

2.10 DETECTOR ID

This feature is used in conjunction with the Synch feature (Option 7) and is also used as a means of providing each detector with a unique identification s ignature for communication purposes . Detector ID settings can range from 000 to 255. If, however, t he detec tor is set to an ID value of 255, it is co ns idered to be in an uninitialized state a nd the detector will not save any power down data. When a detector with an ID setting of 255 is powered up, the LCD will alternate betwee n id and 255 until the ID setting is changed to something other than 255 and the new setting is saved in detector memor y. Whe n a ny detecto r is first initialized, its ID setting is, by default, 255.

2.11 OPTION 7: SYNCH FEATURE

This option provides a means o f linking together up to four (4) P-1400 detectors. Each detector’s Option 7 has three settings ranging from 7.00 to 7.02. T here are two modes of Synch, Ser ies Synch and Para llel Synch. W hen set to operate in Series Synch mode, one detector channel in the entire detector system is active at any given time. This has the advantage of minimizing crosstalk between adjacent loops connected to different P-1400 dete ctors. When se t to o perate in Parallel Sync h mode, all detectors scan their respective channel 1, 2, 3, or 4 inputs at the same time. Parallel Synch offers a faster response time than Series Synch, however the potential for crosstalk is greater.
7.00 = Off.
7.01 = Series Synch.
7.02 = Parallel Synch.
NOTE: When operating in either Series or Parallel Synch mode, all linked detectors m ust have Option 7 set to the same setting.

2.12 OPTION 10: INVERTED VITAL OUTPUT

The detector’s Inverted Vital Output option can be toggled ON or OFF by momentarily pressing ei ther the (UP) or  (DOWN) pushbutton. When Option 10 is enabled (ON), the Auxiliary Vita l Output will assu me the state opposite to that of the Primar y Vital Output. When the Primary Vital Output de activates, the Auxiliary Vital Output will activate. When the Primary Vital Output activates, the Auxiliary V ita l Output will deactivate.
Loop failures or loop check test failures w ill deactivate the Primary V ital Output and activate the Auxilia ry Vital Output. If either Vital Output fa ils its self-check, both of the detector’s Vital Outputs will be deactivated and remain deactivated until the problem is corrected and the detector is reset rega rdless of the setting of Option 10.

2.13 PRIMARY VITAL OUTPUT DELAY

The Primary Vital Output ca n be condition ed with a Delay ti me that is adjustable from 0.0 to 25.5 s econds in 0.1­second steps. Primary Vital O utput Delay time sta rts counting dow n when a Call state is received fro m the Loop Status Inp ut o r Vit al I np ut tha t is mapp ed t o the Pr ima ry Vital Output. When the timer reaches zero, the Primary Vital Output is deactivated. Primary V ital Output Delay does not condition the Auxilia ry Vital Output.

2.14 PRIMARY VITAL OUTPUT EXTENSION

The Pr i ma r y V i t a l O u t p ut c an be co ndition e d with an E x t e nsion ti me tha t is adjustab le from 0.0 to 25.5 sec onds in
0.1-second steps. Primary Vital Output Extension time starts counting down when a Call state is cleared from the Loop Status Input or Vital Input that is mapped to t he Primary Vital Output. The Primary Vital Output will remain off until the Extension time reaches zero. Any vehicle enter ing the loop detect ion zone during the E xtension time period causes the Primary Vital Output to remain in the off state, and later, when the last vehicle clears the loop detection zone, the full Primary Vital Output E xtension time starts count ing down again. Primary V ital Output Extension does not co ndition the Auxil iary Vital Output.

2.15 INPUT / OUTPUT MAPPING

The Loop Status Inputs and/or Vital Input can be assigned to either or both of the Pri ma ry Vital and Auxiliary Vital Outputs. Health Status can only be mapped to the Auxiliary Vital Output.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 4 of 33
Page 11

2.16 FULL RESTORE TO FACTORY DEFAULT SETTINGS

Pressi ng a ll fo ur fr o nt pa ne l pus hb ut to n s wit c hes s imu lta ne o us ly a nd co nt inu o us ly f or f ive (5) seconds restores all factory default settings. The countdown of the five se cond period is displayed on the LCD. Releasing any or all of the switches before the countdown ends aborts t he full restore operation. (See Section 3.5 for default settings). Refer to Section 5.0 for details. Caution: Restoring the factory default settings will clear all previously
programmed settings including any mapped output(s).

2.17 DIAGNOSTIC FEATURES ACTIVATION

When the detector is operating in normal mode, pressing either the (UP ) or (DOWN) pushb utton will temporarily activate Option 1 (Loop Inductance Display) and Opt ion 2 (Loop Inductance -ΔL/L Display) for all loop inputs and Option 6 (Audib le Detect S ignal) for the loop input ind icated in the lower port io n of the LCD. All three of these diagnostic options will remain active for 15 minutes.

2.18 PASSWORD PROTECTION

This detector has a password protection feature to gua rd against the accidental change of detector settings. In order to change any detector setting, a va lid password must be entered to disable the password protection feature. Refer to Section 5.0 for details.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 5 of 33
Page 12

Section 3 Specifications

3.1 PHYSICAL

WEIGHT: 2.54 lb (40.6 oz) (2.09 kg). S
IZE: The motherboard is 11 inches (27.94 cm) long x 7.5 inches (19.05 cm) wide. The detector electronics
housing is mounted to the mot herboard and is 6.5 inches ( 16.51 cm) long x 2. 5 inches (6.35 c m) wide x 5 inches (12.7 cm) deep (depth to the motherboard).
O
PERATING TEMPERATURE: -40° F to +180° F (-40° C to +82° C).
C
IRCUIT BOARD: Processor, power supply, LED, and LCD printed circ uit boards are 0.062 inch thick FR4 material
with 2 oz. copper on both sides and plated through holes. Motherboard is 0.125 inch thick FR4 material wit h 2 oz. copper on both sides and plated through holes.
I
NTERFACE CONNECTOR: (Communications, COMM PORT) DB-9, ni ne pi n, right angle, PC Board mount, metal
shell, D subminiature receptacle with gold plated female contacts and nuts for retaining screws. M
OTHERBOARD TERMINALS: Wago cage clamp type 745-831 (gray) and 745-834 (blue).

3.2 ELECTRICAL

POWER: 9.5 to 18 VDC, 1.0 Amp maximum. F
USE: 3 amp, ATO / ATC (automotive) type located in a fuse holder mounted on the motherboard.
P
OWER DOWN: When the DC voltage drops be low the low power detection threshold (7.8 VDC ), the detector will
save all needed information to hold calls thro ugh the power down seque nce. Upon power res toration (a minimu m of 9.0 VDC), the detector will use this saved data to determine the correct occupancy state of all loops.
L
OOP FEEDER LENGTH: Up to 1500 feet (450 m) maximum with proper feeder cab le and appropriate loops .
L
OOP INDUCTANCE RANGE: 20 to 2500 micro Henries w ith a Q factor of 5 or greater.
L
OOP INPUTS: Transformer isolated. The minimum capacitance added by the detector is 0.068 microFarad.
L
IGHTNING PROTECTION: The detector can tolerate, without damage, a 10 microFarad capacitor charged to 2,000
volts being discharged directly into the loop input terminals. R
ESET: Application of a 30 millisecond low s tate (relative to input +12 VDC) to the Reset terminal on the
motherboard resets all loops. Each loop can be manually reset b y selecting the loop input then pressing and holding the front pane l CHAN pushbutton for three seconds, or by changing the sens itivity or loop frequency o f the loop input.
S
YNCHRONIZE SCAN CONTROL: The SYNCH IN inp ut a nd SYNCH OUT output allow the loops from different
detectors to be scanned sequentially, either in series or parallel. This feature can be used to eliminate crosstalk between adjacent loops connected to different P-1400 detectors. NOTE: Response times w ill vary depending on the number of detectors (up to a maximum of four) on the Synch Line. (See Section 3.4.)
V
ITAL OUTPUTS: T he P r ima r y and Aux iliary Vital Outputs are transformer isolated and are capable of sourcing 200
mA at 12 VDC. Opto-isolated circ uitry verifies t hat the Vital Ou tput is in the des ired state. If either Vital Outp ut fails its self-check, both of the detector’s Vital Outputs will be deactivated.
V
ITAL INPUTS: 12 volt input isolated from the dete ctor. Opto-isolated c ircuitry verifies that t he Vital Inputs are
operational. C
HECK LOOP RELAYS: Contacts rated for 6.0 Amps maximum, 150 VDC, 300 VAC, a nd 500 VA maximum
switched power.

3.3 OPERATIONAL

LOOP STATUS INDICATORS: Ea c h lo op input has a s uper high intens ity red light emitt ing diode ( LED) to ind icate a Call (vehicle detected over loop) or failed loop.
I
NPUT / OUTPUT INDICATORS: The detector has t hree dual color (green / red) LEDs to indicate the following:
VITAL IN LED Status Meaning
OFF Vital Input is deactivated (low voltage level). ON (GREEN) Vital Input is activated (high volta ge leve l).
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 6 of 33
Page 13
ON (RED) Vital Input has failed its self-check (Vital Input, Primary Vital
VITAL OUT LED Status Meaning
OFF Primary Vital Output is deactivated (low voltage level). ON (GREEN) Primary Vital Output is activated (high voltage level). 2Hz FLASHING (GREEN) Timing Delay activated a nd Primary Vital Output is work ing
5Hz FLASHING (GREEN) Timing Extension activated and Primary Vital Output is
ON (RED) Primary Vital Output has failed its self-check (Vital Input,
VITAL AUX LED Status Meaning
OFF Auxiliary Vital Output is deact ivated ( low voltage level). ON (GREEN) Auxiliary Vital Output is activated ( hig h voltage level). ON (RED) Auxiliary Vital Output has failed its self-check (Vital Input,
R
ESPONSE TIME: See Section 3.4 for response times.
S
ELF-TUNING: Each loop circuit tunes and is operational within two seconds a fter application of power or after
being reset. Full sensitivity and hold time require 30 seconds of operation. E
NVIRONMENTAL & TRACKING: The detector is fully self-compensating for environmental changes a nd loop drift
over t he full te mperature range and the entire loop inductance r ange. G
ROUNDED LOOP OPERATION: The loop is olation transformer allows operation with poor qualit y loops (which may
include one short to ground at a single point). L
OOP (FAIL) MONITOR: If the total inductance o f a channel’s loop input network goes out of the range specified for
the dete ctor , or rap idly c hanges by mo re tha n ±25%, and the Loop a nd/o r Healt h Stat us outp uts a re mappe d, the Loop and/or Health Sta tus outp uts will immediate ly enter Fa il-Safe mode and the LCD will display LOOP FAIL. The type of loop failure will a lso be displayed as L lo (for -25% change or shorted loop conditions) or L hi (for +25% change or open loop conditions). T his will continue as long as t he loop fault exists. At the time of a loop failure, the Loop status LED will begin to flash at a ra te of three flashes per sec ond. The LED will contin ue this display pattern until the loop input channel is manually reset or power is re moved. If the loop self-heals , the LOOP FAIL mess age o n the LC D will e xtin guish a nd the loop input channel will resume operation in a normal manner; except the Loop stat us LED will continue the three flas hes per second display patter n, thus provid ing an alert that a prior Loop Fail condition has occurred. Each loop failure for the loop input c hannel is counted and accumulated into the Loop Fail Memory. The total number of loop failures written into the Loop Fail Memory (since the last power interruption or manual reset) can be seen by stepping through the loop input channel’s detector functions in Program Mod e to the LOOP FAIL mess age. When the status of one or mo re loops is assigned to a Vital Outp ut, a loop failure will deactivate t he Vital Output and the correspo nding VITAL OUT LED will turn from green to OFF to indic ate the failure. When a Health Sta tus is assigned to the Auxiliary Vital Output, a loop failure will deactivate the Auxiliary Vital Output and the VITAL AUX LED w i ll turn off.
L
OOP CHECK: This feature is used as a means of verifying proper operation of each inductive loop connected to a
detector. In a typical installat ion, a separate loop of wire called a check loop will be wound around the perimeter of each inductive loop. The Loop Check T imer can be programmed with a value ranging from 1 to 255 minutes. Once this time interval has elapsed, the detector will automatically short the check loop simulating vehicle detection in the induct ive loop. If this initial loop check test fails, t he detector will enter a verification mode to make certain that the loop failure is indeed due to a loop related problem. W hile operating in this verification mode, the detector will perform a series of ten verification tests and the LCD will flash Pcl. If the te n loo p c hec k verification tests all fail, the Vital Output(s) to which the Loop Status I nput(s) and/or Health Status Input(s ) is (are) mapped will be deactivated. The loop check test w ill be repeated at regular intervals depending on the value programmed into the Loop Check Timer. The Vital Output(s) to which the Loop Status Input(s) and/or Health Status Input(s) is (are) mapped will not be activated until t he problem with the check loop is corrected and the channel reset or until the Loop Check functio n is turned off. During a check loop failure the LCD will flash Lcl. NOTE: If the Loop Check Timer is set to 0 minutes, the Loop Check function is off.
S
YNCH MODE: The Synch feature provides a means of linking up to four P-1400 detectors together. There are two
modes in which the detectors can be configured to operate, Series Synch or Parallel Synch.
Output, and Auxiliary Vital Outp ut reve rt to OFF state).
(high vo lt a ge le vel unt il delay times out).
worki ng (low voltage level until extension t imes out) .
Primary Vital Output, and A uxilia ry Vita l Outp ut reve rt to O FF state).
Primary Vital Output, and A uxilia ry Vita l Outp ut reve rt to O FF state).
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 7 of 33
Page 14
Detector
1
(ID 000)
Synch
Out
Synch
In
Detector
2
Detector
Detector
4
Synch
In
Synch
Out
Synch
In
Synch
Out
Synch
In
Synch
Out
Reset
Reset
Reset
Reset
+ - + - + - +
-
Series Synch Connections
Detector
(ID 000)
Synch
Out
Synch
In
Detector
2
Detector
3
Detector
4
Synch
In
Synch
Out
Synch
In
Synch
Out
Synch
In
Reset
Reset
Reset
Reset
+ - + - + - +
-
Synch
Out
Parallel Synch Connections
Series Synch mode can be used to eliminate the possibility of crosstalk between adjacent loops. Se ries Synch will activate one loop at a time, c ycling through all loops config ured to detect in the Series Synch mode. When the detector system is configured to operate in Series Synch mode, it is necessary for one detector to be identified as the master unit, i.e. the detector that starts the Synch pulse. This master unit must be assigned a Detector ID value of 000. The scanning sequence of detector loop input channels is Detector ID 000 channel 1, Detector ID 000 channel 2, Detector ID 000 channel 3, Detector ID 000 channel 4, second detector channel 1, second detector channel 2, second detector channel 3, second dete ctor channe l 4, a nd so on until the s ynch p ulse returns to the first detector. The Synch-out of the first (master) unit is connected to the Synch-in of the second detector; the S ynch­out of the second detector is connected to the Synch-in of the third detector. This connection scheme is continued until the Synch-out of the last detector is connected to the Synch in of the first (master) detector.
When set to operate in Parallel Synch mode, all detectors configured to operate in Parallel Synch mode start scanning their respective channel 1 loop inputs at the same time and t he n proceed to sequentially scan their respective channel 2, 3, and 4 loop inputs. W hen the detector system is configured to operate in Parallel Synch mode, it is necessary for one detector to be identified as the master unit. This master unit must be assigned a Detector ID value of 000. Connections between detectors differ from those in Series Synch mode in that the Synch-o ut o f first detector is connected to the Synch-in of the othe r d e te c tors and t he S y nc h-in of the first detector is connected to the Synch-out of the other detectors.
Operation in either Synch mode requires that the Reset inputs (on the motherboard) of all detectors be tied together and that the DC - inputs (on the motherboard) of all detectors be tied together. To start operation in either Synch mode, the detectors must be reset using the Reset terminal on the motherboard.
When operating in Series Synch mode, if any detector fails to Synch, all o f the Vital Outputs of e very detector configured to operate in Synch mode will be deactivated. If the detector that has fai led to Synch has the Synch feature turned off, the other detectors confi gured to operate in Synch mode will continue to operate in Series Synch mode.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 8 of 33
Page 15
Response Time (milliseconds)
Two Detectors
Three Detectors
Four Detectors
OFF
-------
-------
-------
-------
-------
-------
-------
-------
1
5.12 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
2
2.56 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
3
1.28 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
4
0.64 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
5
0.32 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
6
0.16 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
7
0.08 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
8
0.04 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
9
0.02 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
10
0.01 %
121 ±25
268 ±52
278 ±58
400 ±80
278 ±58
530 ±110
278 ±58
CALL
-------
-------
-------
-------
-------
-------
-------
-------
Frequency 2 4 6 8
Sensitivity 6 6 6 6
Option 1 - Loop Inductance Display
OFF
OFF
OFF
OFF
Option 2 - Loop Inductance -ΔL/L (%) Display
OFF
OFF
OFF
OFF
Option 3 - Noise Filte r
3.00
3.00
3.00
3.00
Option 4 - Detection Zone Tracking
4.02
4.02
4.02
4.02
Option 5 - Sensitivity B oost
5.00
5.00
5.00
5.00
Option 6 - Audible Detect Signal
OFF
OFF
OFF
OFF
Loop Check Feature
005
005
005
005
Detector ID Setting
255
Option 7 - Synch Fea ture
7.00
Option 10- Inverted Vital Output
OFF
Primary Vital Output Delay Time
00.0
Primar y Vital Output Extension Time
00.0
Primary Vital Output Mapping
00
Auxiliary Vital Output Mapping
000
When operating in Parallel Synch mode, if the master unit fails, all of the Vital Outputs of every detector configured to operate in Synch mode will be deactivated. If one or more of the detectors connecte d to the master unit Fails, only those Vital Outputs o f the d ete c tor(s) that has (have) failed will be deactivated.
When operating in either Series or Parallel mode, FSY w ill be displayed on the LCD screen of the detector(s) associated with the failure. This display state will continue until the problem is corrected and the detectors are powered down and repowered, reset, or until the Synch function is turned off.
In either mode of operation, the Synch feature will co ntinue to function if one or more detectors has (ha ve) be en disabled.

3.4 TABLE: SENSITIVITY, -L/L, AND RESPONS E TIME

Sensitivity -ΔL/L
One
Detector
Series Synch
Parallel
Synch
Series Synch
Parallel
Synch
Series Synch
Parallel
Synch

3.5 TABLE: DEFAULT SETTINGS

Channel & Detector Settings
Function Channel 1 Channel 2 Channel 3 Channel 4
Vital Output Settings
Function Setting
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 9 of 33
Page 16
Label
Check Loop 1 (2 Terminals)
Loop 1 (2 Terminals)
Check Loop 2 (2 Terminals)
Loop 2 (2 Terminals)
Check Loop 3 (2 Terminals)
Loop 3 (2 Terminals)
Check Loop 4 (2 Terminals)
Loop 4 (2 Terminals)
Vit al In +
Vit al In -
Reset
Synch In
Synch Ou t
Vital Outputs Out +
Vital Outputs Out -
Vital Outputs Aux +
Vital Outputs Aux -
Power Earth
Power DC -
Power DC +
Pin
Function
1
No Connection
2
RS-232 TX
3
RS-232 RX
4
No Connection
5
RS-232 Common
6
No Connection
7
No Connection
8
No Connection
9
No Connection

3.6 TABLE: TERMINAL ASSIGNMENTS (LABELED ON P-1400 MOTHERBOARD)

3.7 TABLE: PIN ASSIGNMENTS (DB-9 COMMUNICATION INTE RFACE CONNECTOR)

889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 10 of 33
Page 17
P-1400 SERIES
LOOP PROCESSOR
1 2 3 4
CHAN
FUNC
VITALS
OUT
IN
AUX
-L/L =
FREQ KHZ
LOOP FAIL
OPTION
MAX PRESENCE
OFF
EOG
SCANNING
EXTENSION
SENSITIVITY
DELAY
PULSE
SECONDS
3 2 1
4
ON
©
Bargraph
Loop Input LED Indicators
Seven Segment Display
Numbered Loop Symbols
UP Pushbutton
DOWN Pushbutton
Channel Select Pushbutton
Function Select Pushbutton VITAL AUX LED Indicator
VITAL IN LED Indicator
VITAL OUT LED Indicator
Parameter Description DB-9 RS-232 Connector

Section 4 User Interface

Vehicle Signal Strength
Frequency Sett ing
Output Mapping
Parameter Values
Frequency Reading
Inductance Value
• -∆L/L Value
Output Mapping
Type of Loop Failures:
L hi = Open Loop
L lo = Shorted Loop
Change Displayed Loop Input
Channel - Press and Relea s e
Exit Program Mode - Press and
Hold for 1 second
Reset Channel - Press and Hold
for 3 seconds
Change Output Mapping Parameter - Press and Release
Increments Values
Toggles ON and OFF
Activates Detector Diagnostic
Features
LOOPS
Name of Parameter
Timer in Oper ation
Loop Input Channel Displayed
Flashing = Program Mode
Call
Loop Fai lure
Loop Fault has Occurred
Press momentarily to en ter
Progra m M ode and to st e p through param eters
Decrements Va lu es
Toggles ON and OFF
Activates Detector Diagnostic
Features
Output Status - On / Off
Output Failed Self-check
Input Status - On / Off
Input Failed Self-check
NOTES: The LCD backlighting illuminates whenever any pushbutton is pressed. Backlighting will extinguish 15 minutes
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 11 of 33
Output Status - On / Off
Delay Time Activated
Extend Time Activated
Output Failed Self-check
Communications Port
after the last pushbutton press. Pressing any two or three pushbuttons illuminates the LCD backlighting, displays all LCD segments, and
illuminates the VITAL IN, VITAL OUT, and VITAL AU X Output LEDs. The Output LEDs are illuminated in their red phase as a means of confirming proper function of the detector’s Vital Output failure feature.
There are no internal switches or jumpers to set.
Page 18

Section 5 Installation and Set-Up

Mount P-1400 in the enclosure (see diagra ms below). Connect 12 VDC power, Loops, Check Loops, the Vital Input, and the Vital Outputs to the terminals marked on the motherboard as de tailed below and apply power. If a loop is not connected to a loop termina l, the detector w ill see a failed loop and deact ivate the Vita l Output if it is mapped. The Loop Status for loop inputs with no loop connected must be turned off (see Sensitivity) or not assigned (mapped) to a Vital Output (see Vital Output Mapping). If the detector is not new from the factory, it may be advantageous to restore all factory default settings to avoid having to check every setting for e very loop input channel. To restore a ll factory default settings, d isable the pass word protection feature as explained be low. Press a nd hold all four pushbutton switche s simultane ously for fi ve seconds. When all four pushbutt ons are depressed and held, the display will start counting down fro m five (5). When the countdown reaches zero (0), releasing the pushbuttons restores the factory default settings. Releasing any or all of the switches before the countdown ends aborts the full restore operation. Cautio n: Restoring the factory d efault settings will clear all previously programmed settings including any mappe d output(s).
All operating parameters can be adjusted from the front panel. The detector continues to operate norma lly while it is in t he Program Mode . The value cur r ently displayed is alw ays the actua l value being use d. Exa mple: If you are changing the delay time, the time displayed at the instant that a vehicle entered the detection zone for that loop input channel would be the value used fo r the delay timer .
Pressing the FUNC pus hbutton e nters t he Prog ram Mode . The FUNC p ushbutto n has an auto r epeat funct ion. This allows quick navigation to the desired parameter. The FUNC pushbutton only moves forward through all of the parameters. There is no way to move backwards through the parameters.
While viewing any parameter, pressing the CHAN p ushbut ton wil l disp lay the same p aramete r in t he next l oop input channel. The currently selected channel is indicated at the bottom of the LCD display. Pressing and holding the CHAN p ushb utton for one sec ond will exit the Program Mode and return to the Normal Mode.
Pressing and holding either the  (UP) or  (DOWN) pushbutton will ca us e the va lue t o c hange ra p id l y u nt i l the pushbutton is released.
Disabling Password Protection
To change any detector setting, the password protection feature must be disabled. When viewing a setting in the Program Mode, press the (UP) or (DOWN) pushbutton to ente r pa s s word entry mode. The LCD will d is play PSd to provide an indication that a valid password must be entered before any detector sett ing can be changed. NOTE: Pressing the CHAN button for two seconds at an y time will e xit password entry mode . P re ss the (UP) or  (DOWN) pushbutt on. The LC D displa y will cha nge to 000 with the leftmos t 0 flashing. Press the  (DOWN) pushbutton t o change the fl ashing digit t o 9. Press the CHAN pushbutton a second time to ge t the ce nter 0 to flash. Press the (UP) pushbut ton to change the flash i ng digit t o 1. Press the CHAN pushbutton a third t ime to get the rightmost 0 to flash. Press the (UP) p ushbutton to change the flas hing digit to 1. Press the FUNC pushbutton to enter the password. Detector settings can now be c hanged. Press the FUNC pushbut t o n t o e nt e r t he password. Detector settings can now be changed. Password protection can be re-e nabled by pressing and holding the CHAN p ushbutt o n fo r t w o s ec onds followed by pressing the (U P ) pushbut t o n t wic e . If n o a ction is ta ken to re-enable the password protection feature, it will be automatically re-enabled 15 minutes after changing any detector setting.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 12 of 33
Page 19
1.75
4.00
1.50
3.75
1.00
6.55
11.00
7.50
Detector
Electronics
Housing
3.41 Diameter
Hole in Motherboard
.19 Diameter Mounting
Hole (4X)
8.25
4.50
P-1400 Motherboard Dimensions
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 13 of 33
Page 20
ENCLOSURE BOTTOM
MALE / MALE STANDOFF
PCB MOTHERBOARD
#8 FLAT WASHER
#8 LOCK NUT
THREADED HOLE
THROUGH HOLE
©
©
©
P-1400 Mounting Diagram
P-1400 Wire Connection Detail
Strip back the insulation on each wire approximately 0.50 in.
Insert a small flat blade screwdriver into the rectangular slot on the connector and lift to open the terminal contacts.
Insert the stripped wire into the large round hole and remove the screwdriver.
Make certain that the terminal contacts have e nga ged t he w i re c o nduc to r, no t t he wire insulation.

5.1 INITIAL INSTALLAT ION START-UP MODE DISPLAY SCREENS

Upon application of power, the LCD screen will show the detector model letter and firmware version, in this case, Model P-1400 firmware version 3. This screen will be displayed for two seconds.
The ne xt LCD scr ee ns d isp laye d wi ll s how the Detector ID se tting. The display will toggle between the two screens shown with a 50% duty cycle. When shipped from the factory, the Detector ID is set to 255 and the detector is considered to be uninitialized. This will be the case on initial start-up. Before proce eding, the detector ID must be cha nged to something other than 255. To do so, use the  (UP) or  (DOWN) pushbutton to change t he setting to the desired ID number. W hen set to the correct value, press the FUNC pus hbutton to ac cept and s tore the setting. If the detector in question is be ing used as the master unit whe n utilizing the Synch feature, the Detector must be as signed a n ID value o f
000.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 14 of 33
Page 21
1
1
©
1
©
LOOP FAIL
1
©
LOOP FAIL
1
©
©
The detector will next confirm the state of the check loops connected to it. If a ll four check loops are connected and are intact, the LCD screen will display an indication of the successful completion of the check loop verification. This screen will flash twice.
If all four check loops are not connected or one (or more) is (are) damaged in some way, the detector will initiate its check loop verification proce ss. The LCD screen will display an indication of a pending state during the che ck loop verification. This screen will flash for 55 seconds until one of three things happe n; the check loop ver ification fails, the c heck loop(s) causing the check loop verification is (are) connected or restored to a functional state, or the check loop(s) causing the check loop verification is (are) turned off, i.e. the Loop Check Timer of the loop(s) is set to 000.
If the check loop verification process continues for the entire 55 second period and no action has been taken to connect or restore the check loops causing the check loop verification, the LCD screen will toggle between the two screens shown w ith a 50% duty cycle.
If the detector passes its check loop verification process or a pending loop check failure state is resolved in one of the ways mentioned above, the LCD screen will show a normal (idle) condition.

5.2 PROGRAM MODE DISPLAY SCREENS

PARAMETER Password Protection Screen. S
ETTING 911 disables the Password Protection.
S
ETTING DISPLAYED PSd.
7-
SEGMENT DISPLAY Press the (UP) o r (DOW N) pushbut ton to d isplay
000 to access password entry mode.
D
EFAULT SETTINGS Password Protection feature is active.
E
XAMPLE Password entry mode is available for access.
N
OTES Pressing the CHAN b utton for two seconds at any time
will exit password entry mode.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 15 of 33
Page 22
FREQ KHZ
1
©
SENSITIVITY
1
©
OPTION
1
ON © OPTION
OFF
1
©
OPTION
1
ON © OPTION
1
ON
©
PARAMETER ...................Frequency.
S
ETTINGS ........................E ight selections - 1 to 8.
S
ETTING DISPLAYED ......Bargraph indicates settings from 1 (left) to 8 (rig ht).
7
SEGMENT DISPLAY ......Actual frequency of the loop circuit. T ypically 20.0 to 99.9
D
EFAULT SETTING..........Loop Input 1 = 2, Loop Input 2 = 4, Loop Input 3 = 6, and Loop
E
XAMPLE ........................Frequency setting 4 is selected for loop input. The loop
N
OTES .............................Changi ng t he fr eque nc y wi ll re set the Loo p Inp ut. A n unsta ble
P
ARAMETER ...................Sensitivity.
S
ETTINGS ........................12 selections - 1 to 10, OFF, or CALL.
S
ETTING DISPLAYED ......7-segment display will show currently selected setting.
7
SEGMENT DISPLAY ......Currently selected Sensiti vity.
D
EFAULT SETTING..........6 for all loop inputs.
E
XAMPLE ........................Sensitivity 6 is selected for loop input 1.
N
OTES .............................Changing the sensitivity will reset the loop input. The bargraph
P
ARAMETER ...................Option 1 (Loop / Lead-In Induc tance Display).
S
ETTINGS ........................ON or OFF.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........OFF fo r all loop inputs.
E
XAMPLE ........................Option 1 is turned ON for all loop inp uts.
N
OTES .............................This option is a detector-wide setting. Changing it for one loop
P
ARAMETER ...................Option 2 (Perce nt age of Inducta nce change, -L/L).
S
ETTINGS ........................ON or OFF.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........OFF fo r all loop inputs.
E
XAMPLE ........................Option 2 is turned OFF for all loop inputs.
N
OTES .............................This option is a detector-wide setting. Changing it for one loop
P
ARAMETER ...................Option 3 (Noise Filter).
S
ETTINGS ........................Four selections - 3.00 to 3.03.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........3.00 (OFF) for all loop inputs.
E
XAMPLE ........................Option 3.02 is turned ON for loop inp ut 1.
N
OTES .............................This option is a channel specific setting. Changing it for one
ARAMETER ...................Option 4 (Detection Zone Tracking).
P S
ETTINGS ........................Nine selections - 4.00 to 4.08.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........4.02 (ON) for all loop inputs.
E
XAMPLE ........................Option 4.03 is turned ON for loop inp ut 1.
N
OTES .............................This option is a loop input spec ific setting. Changing it for o ne
kiloHertz.
Input 4 = 8.
frequency is 34.9 kHz.
frequency display varying more than ±0.2 kiloHertz may indicate loop crosstalk or other interference.
will show strength of ve hicle calls so that correct sensitivity can be verified from this screen.
input changes it for all loop inputs. This option will automatically turn off in 15 minutes.
input changes it for all loop inputs. This option will automatically turn off in 15 minutes.
loop input changes it for that loop input only. It is strongly
recommended that this option be set to 3.00 (OFF) for normal operation.
loop input changes it for that loop input only.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 16 of 33
Page 23
OPTION
1
ON
©
OPTION
1
ON © LOOP FAIL
SCANNING
1
© © ©
OPTION
OFF
©
P
ARAMETER ...................Option 5 (Sensitivity Boost).
S
ETTINGS ........................Five selections - 5.00 to 5.04.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........5.00 (OFF) for all loop inputs.
E
XAMPLE ........................Option 5.04 is turned ON for loop inp ut 1
N
OTES .............................This option is a loop input spec ific setting. Changing it for one
The max i mum sensitivity leve l ob t ainable with or without sensitivity bo os t is level 10. If
P
ARAMETER ...................Option 6 (Audible Detect).
S
ETTINGS ........................ON or OFF.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........OFF fo r all loop inputs.
E
XAMPLE ........................Option 6 is turned ON for loop inp ut 1.
N
OTES .............................This op tion is mutua lly excl usive w ith the same op tion in a ny
P
ARAMETER ...................Loop Check Timer setting.
S
ETTINGS ........................256 selections - 000 to 255 minutes in 1 minute steps.
S
ETTING DISPLAYED ......7-segment display will show currently se lec te d s e tting.
7-
SEGMENT DISPLAY ......Currently selected time in minutes.
D
EFAULT SETTING..........Five minutes (005) for all loop inputs.
E
XAMPLE ........................The Loop Check Timer for Loop 1 is set for 25 minutes.
N
OTES .............................This option is a loop input spec ific setting. Changing it for o ne
ARAMETER ...................Option 7 (Synch Feature ) .
P S
ETTINGS ........................Three selections - 7.00 to 7.02.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7-
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........7.00 (OFF) for all loop inputs.
E
XAMPLE ........................Option 7 is turned OFF.
NOTES .............................This option is a detector-wide setting. Setting Opt ion 7 to 7.01
P
ARAMETER ........................Detector ID setting.
S
ETTINGS .............................256 selections - 000 to 255.
S
ETTING DISPLAYED ...........7-segment display will show currently
7-
SEGMENT DISPLAY ...........Current Detector ID setting. The displa y
D
EFAULT SETTING...............255.
E
XAMPLE .............................Detector ID is set as 158.
N
OTES ..................................When set to Detector ID number 255, the
loop input changes it for that loop input o nly.
the setting of either sensitivity or s ensitivity boost is such that the resu lta nt sens itiv ity le vel is g reat er tha n 10 (e. g. Se nsit ivit y Level 7, Sensitivity Boost setting of 5.4), the audible detect signal (buzzer) will sound to provide an indication that the combination being selected is invalid. (See Section 2.2 ­Sensitivity for more details.)
other loop inp ut. Turning it on for one loop input turns it off for all other loop inpu ts . T h is option will automatically turn off after 15 minutes.
loop input changes it for that loop input o nly.
selected setting.
will toggle between the two screens w ith a 50% duty cycle.
detector is considered uninitialized.
activates Series Synch (SYS), setting Option 7 to 7.02 activates Parallel Synch (SY P ).
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 17 of 33
Page 24
EXTENSION
SECONDS
©
DELAY
SECONDS
©
LOOP FAIL
1
©
© 1 ©
OPTION
OFF
1
©
PARAMETER ...................Option 10 (Inverted Vital Output).
S
ETTINGS ........................ON or OFF.
S
ETTING DISPLAYED ......The word ON or OFF will be displayed.
7-
SEGMENT DISPLAY ......The number of this option.
D
EFAULT SETTING..........OFF fo r all loop inputs.
E
XAMPLE ........................Option 10 is turned OFF.
N
OTES .............................This option is a detector-wide setting. Changing it for one loop
P
ARAMETER ...................Primar y Vital Output D elay.
S
ETTINGS ........................256 selections - 00.0 to 25.5 Seco nds in 0.1 s e cond steps.
S
ETTING DISPLAYED ......7-segment display will show currently se lec te d s e tting.
7
SEGMENT DISPLAY ......Currently selected Delay time in seconds.
D
EFAULT SETTING..........00.0 seconds.
E
XAMPLE ........................Delay of 10 seconds selected for the Primary Vital Output.
N
OTES .............................If the loop input’s detection zone is occupied when this
P
ARAMETER ...................Primary Vital Output Extension.
S
ETTINGS ........................256 selections - 00.0 to 25.5 Seco nds in 0.1 s e cond steps.
S
ETTING DISPLAYED ......7-segment display will show currently se lec te d s e tting.
7
SEGMENT DISPLAY ......Currently selected Extension time in seconds.
D
EFAULT SETTING..........00.0 seconds.
E
XAMPLE ........................E xtensio n of 2.5 se conds s elected fo r the Pr imary Vit al Output.
N
OTES .............................If the loop input’s detection zone is occupied when this
P
ARAMETER ...................Loop Fail.
S
ETTINGS ........................Pressing the (UP) o r (DOWN) pushbutton will clear the
S
ETTING DISPLAYED ......View only.
7
SEGMENT DISPLAY ......Loop Failures since the last time it was cle ared manually or due
D
EFAULT SETTING..........000.
E
XAMPLE ........................There are 8 Loop Failures in the accumulat or for channe l 1.
N
OTES .............................Count will be reset to 0 after loss of power, pressing the
P
ARAMETER ........................Firmwar e Vers ion and R evision.
S
ETTINGS .............................View Only.
S
ETTING DISPLAYED ...........View Only.
7
SEGMENT DISPLAY ...........Model letter and firmware version on one
D
EFAULT SETTING...............Not Applicable.
E
XAMPLE .............................Model P-1400 firmware version 3,
input changes it for all loop inputs.
parameter is changed, it will not take effect until the detect ion zone is empty or the loop input is reset.
parameter is changed, it will not take effect until the detection zone is empty or the loop input is reset.
Loop Fail memory.
to power failure.
(UP) or (DOWN) p ushb utton, or a res et inp ut to t he Res et terminal on the motherboard.
screen and firmware revision on the other screen. The display will toggle between the two screens with a 50% duty cycle.
revision .00.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 18 of 33
Page 25
©
Any Input on Loops 3, 2, or 1 will be mapped to the Primary Vital Output.
Any Input on Loops 3 or 2 will be m apped to the Vital Output.
Any Input on Loops 3 or 1 will be m apped to the Primary Vital Output.
Any Input on Loop 3 will be mapped to t he Primary Vital Output.
Any Input on Loops 2 or 1 will be m apped to the Primary Vital Output.
Any Input on Loop 2 will be mapped to the Primary Vital Output.
Any Input on Loop 1 will be mapped to the Primary Vital Output.
No Loop Inputs will be mapped to the Primary Vital Output.
Display Setting
Loop Status Inputs Selected
Any Input on Loops 4, 3, 2, or 1 will be mapped to the Primary Vital Output.
Any Input on Loops 4, 3, or 2 will be mapped to the Primary Vital Output.
Any Input on Loops 4, 3, or 1 will be mapped to the Primary Vital Output.
Any Input on Loops 4 or 3 will be m apped to the Primary Vital Output.
Any Input on Loops 4, 2, or 1 will be mapped to the Primary Vital Output.
Any Input on Loops 4 or 2 will be m apped to the Primary Vital Output.
Any Input on Loops 4 or 1 will be m apped to the Primary Vital
Any Input on Loop 4 will be mapped to the Primary Vital Output.
3 4 1
2

5.2.1 PRIMARY VITAL OUTPUT MAPPING SCREENS

PARAMETER ...................Primary Vital Output Mapping.
S
ETTINGS ........................32 selections - any and a ll combinations of the four Loop Status
S
ETTING DISPLAYED ......Bargraph indicates Loop Status Inputs and/or Vital Input
7
SEGMENT DISPLAY ......7-segment display will show currently selected setting. The
D
EFAULT SETTING..........00. No Loop Status Inputs mapped to the Primary Vital Output.
E
XAMPLE ........................Loop Status Inputs 1, 2, & 3 mapped to the Primary Vital
N
OTES .............................The first character is displayed in Hexadecimal notation (Base
To set the mapping status of the Loop Status Inputs, repeatedly press the FUNC pushbutton to enter Pro gram Mode and toggle through the set-up pa ram eter s unti l the disp lay sc ree n show s the bar grap h and tw o o f the se ven segment display characters. The left character will flash indicating the current setting and the four leftmost bargraph segments will show the correspond ing Loop Status Input mapping. Use the (UP) or (DOWN) pushbutton to change the setting to the des ired configurat ion. The various co mbinations of disp lay characters and bargra ph disp lay are s hown belo w.
Inputs and the V ital Inp ut.
mapped to the Primary Vital Output. In Loop Status Input mode, the leftmost segment = Loop Status Input 4, next segment = Loop Status Input 3, next segment = Loop Status Input 2, next segment = Loop Status I nput 1. In V ital Input mode, the sixth segment from left = Vital I nput.
first character corresponds to the Loop Status Inp uts mapped to the Pri mary Vita l Outp ut, the se cond character corresponds to the Vital Input mapped to the Primar y V ital O utput.
Vital Input not mapped to the Primary V ita l Outp ut.
Output. Vital Input not mapped to the Prima ry Vital Output.
16).
Output.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 19 of 33
Page 26
Display Setting
Vital Input Mapping Status
Vital Input not mapped to the Primary Vital Output.
Vital Input m apped to the Primary Vit al Output.
©
To set the ma pp ing s tat us o f the Vita l I nput whe n in the Pr imar y V ital O ut put M app ing Pro gra m Mo de, pres s t he CHAN p ushbutton once. The right char acter will flash indicating the current setting and the sixth bargrap h segment from the left will show the corresponding Vital Input mapping. Use the  (UP) or  (DOWN) pushbutton to change the setting to the desired configuration. The two combinations of display characters and bargra ph disp lay are s hown belo w.
When in Normal Mode, repeatedly press the FUNC pushbutto n to e nt e r Pr o g ram Mode and toggle through the set­up para mete rs unt il t he dis pla y scre en sho ws t he bar grap h and t wo of t he se ven s egme nt d ispla y char acte rs. T he left character will flash indicating the current setting and the four leftmost bargraph segments will show the corresponding Loop Status Input ma pping. Press the CHAN pushbutton once. The right character will flash indica ti ng t he c ur re nt se tt ing a nd the s ixt h b ar gra p h se gme nt fr om t he le ft w i ll s how the co rr es po nd in g Vi ta l I npu t mapping. Use the  (UP) or  (DOWN) pus hb ut to n to cha n ge t he s et t ing t o t he d e sire d c o nfi gur a tio n. The tw o combinations of display characters and bargraph display are shown below.

5.2.2 AUXILIARY VITAL O UTPUT MAPPING SCREENS

PARAMETER ...................Auxiliary Vital Output Mapping.
S
ETTINGS ........................512 selections - any and all combinations of the four Loop
S
ETTING DISPLAYED ......Bargraph indicates Loop Status Inputs, Vital Input, and/or
7
SEGMENT DISPLAY ......7-segment display will show currently selected setting. The
D
EFAULT SETTING..........000. No Loop Status Inputs mapped to the Auxiliary Vital
E
XAMPLE ........................Loop Status Inputs 1, 2, & 3 mapped to the Auxiliary Vital
N
OTES .............................The first and third characters are displayed in Hexadecimal
To set the mapping status of the Loop Status Inputs, repeatedly press the FUNC pushbutton to enter Pro gram Mode and toggle through the set-up parameters until the display screen shows the bargraph and t hree o f t he s e ve n segment display characters. The left character will flash indicating the current setting and the four leftmost bargraph segments will show the corresponding Loop Status Input mapping. Use the  (UP) or  (DOWN) pushbu tt on to c ha n ge the setting to the desired configuration. The various combinations of display characters and bargra ph disp lay are s hown on the next page.
Status Inputs, the Vit al Input, and the four Health Status Input s.
Health Status Inputs mapped to the Auxiliary Vital Output. In Loop Status Input mode, the leftmost segment = Loop Status Input 4, next segment = Loop Status Input 3, next segment = Loop Status Input 2, next segment = Loop Status Input 1. In Vital Input mode, the sixth segment from left = Vital Input. In Health Status Input mode, the rightmost segment = Health Status Input 1, next segment = Loop Status Input 2, next segment = Loop Status Input 3, next segment = Loop Status Input 4.
first character corresponds to the Loop Status Inp uts mapped to the Auxiliary Vital Outp ut, the se cond cha racter corres ponds to the Vital Input mapped to Auxiliar y Vital Output, and t he third character corresponds to the Health Status Inputs mapped to the Auxiliary Vital Output.
Output. Vital Input not mapped to the Auxiliar y Vital Output. No Hea lth Stat us Inputs mapped t o the Auxiliar y V ital O utput.
Output. Vital Input not mapped to the Auxiliar y Vital Output. Health Status Inputs 1, 2, 3, & 4 mapped t o the Auxiliar y Vital Output.
notation (Base 16).
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 20 of 33
Page 27
Display Setting
Loop Status Inputs Selected
Any Input on Loops 4, 3, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 4, 3, or 2 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 4, 3, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 4 or 3 will be mapped to the
Any Input on Loops 4, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 4 or 2 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 4 or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loop 4 will be mapped to the Auxiliary Vital Output.
3 4 1
2
Any Input on Loops 3, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 3 or 2 will be mapped to the Auxiliary Vital Output.
Any Input on Loops 3 or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loop 3 will be mapped to the Auxili
Any Input on Loops 2 or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Loop 2 will be mapped to the Auxiliary Vital Output.
Any Input on Loop 1 will be mapped to the Auxiliary Vital Output.
No Loop Inputs will be mapped t o the Auxiliary Vital Output.
Display Setting
Vital Input Mapping Status
Vital Input will not be m apped to the Auxiliary Vital Output.
Vital Input will be mapped to the Auxi liary Vital Output.
Auxiliary Vital Output.
ary Vital Output.
To set the mapping status o f the Vita l Inpu t whe n in the Auxilia r y Vital O utput Map p ing Pro gram Mo de, press the CHAN pushbutto n once. The center character w ill flash indicating the current s etting and the sixth bargraph segment from the left will show the corresponding Vital Input mapping. Use the  (UP) or  (DOWN) pushbutton to change t he setting to the desired configuration. The two combinations of display characters and bargra ph disp lay are s hown belo w.
When in Normal Mode, repeatedly press the FUNC pushbutton to enter Program Mode and toggle through the set­up parameters until the d isplay screen shows the ba r grap h a nd th re e o f t he s e ve n se gme nt d isp la y c ha rac te rs. T he left character will flash indicating the current setting and the four leftmost bargraph segments will show the corresponding Vital Input mapping. Press the CHAN pushbutton once. The center character will flash indicating the cur rent set ti ng and the sixt h ba rgra ph s eg men t fro m the lef t wil l sho w t he co rre sp ond ing V ita l Inp ut ma pp ing. Use the  (UP) or  (DOWN) pushbutton to change the setting to the desired configuration. The two combinations of display characters and bargraph display are shown below.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 21 of 33
Page 28
Display Setting
Health Status Inputs Selected
Any Input on Health Status 4, 3, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health St atus 4, 3, or 2 will be mapped to Auxiliary Vital Output.
Any Input on Health St atus 4, 3, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 4 or 3 will be map
Any Input on Health St atus 4, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 4 or 2 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 4 or 1 will be mapped
Any Input on Health Status 4 will be mapped to the Auxiliary Vital Output.
3 4 1
2
Any Input on Health Status 3, 2, or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 3 or 2 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 3 or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 3 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 2 or 1 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 2 will be mapped to the Auxiliary Vital Output.
Any Input on Health Status 1 will be mapped to the Auxiliary Vital Output.
No Health Status Inputs will be m apped t o the Auxiliary Vital Output.
To set the mapping status of the Health Status Inputs when in the Auxiliary Vital Output M apping Pr ogram M ode, press the CHAN pus hbutton once again. The right character will flash indicating t he current setting a nd the four right most bar graph s egment s will s how t he corre spond ing Hea lth Sta tus Inp ut mapp ing. Us e the  (UP ) or  (DOWN) pushbutton to c hange the setting to the desired configuration. The various combinations o f d isplay characters and bargraph display are shown below.
When in Normal Mode, repeatedly press the FUNC pushbutton to enter Program Mode and toggle through the set­up para met ers unt il t he dis play screen shows the bargraph and three of the seven segment display characters. The left character will flash indicating the current setting and the four leftmost bargraph segments will show the corresponding Vital Input mapping. Press the CHAN pushbutton twice. The r ight character w ill flash ind icating the current setting and the fo ur rightmost bargraph segments will show the corres ponding Health Status Input mapping. Use the  (UP) or  (DOWN) p ushbutton to change the setting to the desired co nfiguration. T he various combinations of display characters and bargraph display are shown below.
ped to the Auxiliary Vital Output.
to the Auxiliary Vital Output.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 22 of 33
Page 29
1 © 1
©
L =
1
©
-L/L =
1
©
-L/L =
LOOP FAIL
OPTION
MAX PRESENCE
OFF
EOG
SCANNING
EXTENSION
SENSITIVITY
DELAY
PULSE
SECONDS
3 2 1
4
ON
©

5.3 NORMAL MODE DISPLAY SCREENS

STATE .............................Idle.
B
ARGRAPH DISPLAY .......Off.
7
SEGMENT DISPLAY ......Three Dashes.
L
OOP INPUT LED ...........OFF.
E
XAMPLE ........................C hannel 1 is idle.
N
OTES .............................This is the normal state for a loop input channel when the loop
S
TATE .............................Call.
B
ARGRAPH DISPLAY .......Number of sensit ivity levels inducta nce change from vehicle
7
SEGMENT DISPLAY ......Call.
L
OOP INPUT LED ...........Solid ON.
E
XAMPLE ........................Channel 1 detection zone is occupied by a vehicle that exceeds
S
TATE .............................Loop Inductance D ispla y (Optio n 1 ON).
B
ARGRAPH DISPLAY .......Off if no vehicle is detected, number of sensitivity levels
7
SEGMENT DISPLAY ......Loop / Lead-In circuit ind uctance in micro Henr ies. I f the value
T
EXT ...............................L=.
L
OOP INPUT LED ...........The loop input LED operates as normal, indicating call as
E
XAMPLE ........................Channel 1 Loop / Lead-In circuit inductance is 98 microHenries
N
OTES .............................If Option 2 (-ΔL/L Display) is ON, this display is only shown
S
TATE .............................Loop Inductance -ΔL/L Display (% Change) (Option 2 ON).
B
ARGRAPH DISPLAY .......OFF if no vehicle is d e t e ct e d . Number o f s e nsitivi t y levels that
7-
SEGMENT DISPLAY ......Percentage of change in inductance of the Loop / Lead-In
T
EXT ...............................-L/L.
L
OOP INPUT LED ...........The loop input LED operates as normal, indicating call as
E
XAMPLE ........................Loop Input Channel 1 detection zone is occupied by a vehicle
N
OTES .............................This display is only visible while the channel is detecting a
S
TATE .............................LCD Disp lay Test.
B
ARGRAPH DISPLAY .......All segments on.
7
SEGMENT DISPLAY ......All segments on.
T
EXT ...............................All segme nts on.
L
OOP INPUT LED ...........The loop input LED operates as normal, indicating call as
E
XAMPLE ........................All segments on.
N
OTES .............................This display is visible whenever a ny two or three pushbutton
detection zone is unoccupied.
exceeds (first dot = current sensitivity level, second dot = next lower sensit ivity level, e t c.).
the detection threshold by four sensitivity leve ls.
inductance change from vehicle exceeds (first dot = current sensitiv ity level, seco nd dot = ne xt lower sensiti vity level, etc.).
exceeds 999, the display will alternate between t he thousands place (1 or 2) and the lower three digits of the induct a nc e va l ue .
expected.
and it is not detecting a vehicle.
when the channel is not detect i ng a vehicle.
the inductance change caused by the vehicle exceeds the detection threshold (firs t dot = current se nsitivity level, seco nd dot = next lower sensitivity level, etc.) if a vehicle is detected.
circuit.
expected.
that exceeds the detection threshold by three (3) sensitivity levels and Channel 1 percentage change of inductance is
0.087%.
vehicle.
expected.
switches are pressed at the same time.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 23 of 33
Page 30
1
©
©
1
©
1
1
©
©
1
1
©

5.4 ERROR MESSAGE DISPL AY SCREENS

The Model P-1400 stores operating parameters and detection reference settings in two places. The detector hardware includes an internal EEPROM mounted on the processor board and an EEPROM mounted on the motherboard.
Logic programmed into the detector operating firmware continua lly checks the data stored on the two compone nts listed above. This check function provides a means of verifying several key factors that ensure that the detector is functioning properly. Thes e includ e:
Detector power up status - Has the detector powered up correctly and is it operating in the correct state? Detector Failure status - Are failure conditions be ing identified and is the detector res ponding to these failures
correctly? Stored data status - Is the data stored on each o f the two data storage components consistent with each other?
If the information obtained via the check function ind icates that there is a problem with some phase of the detector operation, the LCD screen will display one or more of the error messages listed below.
Uninitialized Motherboard Mounted EEPROM . The display will toggle between the two screens shown with a 50% duty cycle. This is an indication that the motherboard mounted EEPROM is uninitialized. To correct this problem, press the FUNC pus hbutto n. If the e rror mess age does not clear, the motherboard mounted EEPROM is defective. Return the detector to the factory for servicing.
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector setti ngs are correct for the installation in questio n.
Uninitialized Interna l E EPROM. The display will toggle between the two screens shown with a 50% duty cycle. This is an indication that the internal EEPROM is uninitialized. To correct this problem, press the FUNC pushbutton. If the error message does not clear, the internal EEPROM is defective. Return the detector to the factory for servicing.
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector settings are correct for the installation in questio n.
Uninitialized Internal and Motherboard M ounted EEPROMs. The display will toggle bet ween the two scr eens sho wn with a 50% dut y cycle. This is an indic ation that t he interna l EEPROM and the motherbo ard mounte d EEPROM are uninitialized. To correct this problem, press the FUNC pushbutton. If the error message does no t clear, the internal EEPROM and the motherboard mounted EEPROM are defective. Return the detector to the factory for servicing. NOTE: Clearing this error message will reset the detector to factory default settings and will clear any previously mapped output(s).
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector setti ngs are correct for the installation in questio n.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 24 of 33
Page 31
©
1
1
©
1
©
©
1
1
©
©
1
©
1
1
©
Loop Check Pass
Motherboard Mounted EEPROM Error. T he display will toggle between the two s cree ns s hown w ith a 50% d uty cyc le. This is an i ndicat io n that the data stored on the motherboard mounted EEPROM is corrupt. Press the FUNC pushbutton to copy the reference data stored on the internal EEPROM to the motherboard mounted EEPROM. If the error message does not clear, the motherboard mounted EEPROM is defective. Return the detector to the factory for servicing.
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector setti ngs are correct for the installation in questio n.
Internal EEPR OM Erro r . The display will toggle between the two screens shown with a 50% duty cycle. This is an indication that the data stored on the inte rnal EEPR O M is c o rr upt. Pres s t he FUNC pushbutt o n t o co p y the reference data stored on the motherboard mounted EEPROM to the internal EEPROM. If the error message does not clear, the internal EEPROM is defective. Return the detector to the factory for servicing.
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector settings are correct for the installation in questio n.
Interna l and Extern al EEP ROM Err or. The disp lay will toggle between the two s cree ns s hown w ith a 50% d uty cyc le. This is an i ndicat io n that the data stored on the internal EEPROM and the motherboard mounted EEPROM is corrupt. Press the FUNC p ushbut ton to copy the re fere nce data stored on the microprocessor to the internal EEPROM and the motherboard mounted EEPROM. If the error message does no t clear, the internal EEPROM and the mot herboard mounted EE PROM a re defective . Return the detector to the factory for servicing. NOTE: Clearing this error message will reset t he detector to factory default s ettings and will clear any previously mapped output(s).
Warning: If the error message clears after pressing the FUNC pushbutton, the us er must confirm that t he stored detector setti ngs are correct for the installation in question.
Detection Reference Error. This is an indication that the internal EEPROM and the motherboard mounted EEPROM detection reference values do not match. Press the FUNC pushbutton to clear the error message.
Warning: If the error message clears after pressing the FUNC pushbutton, the user must confirm that the stored detector s e ttings ar e c or r e ct for the ins tallation in question.
Warning: Clearing this error will reset all internal and external detection reference values. If a vehicle (or vehicles) is (are) present over any or all loops at this time, the inductance change caused by the vehicle(s) will be incorporated into the new baseline detection reference and the vehicle(s) will no longer be detected.

5.5 LOOP CHECK PASS / FAIL INDICATIONS

The Loop Check feature is enabled whenever the Loop Check Timer for a specific loop input is set to a value between 1 and 255 minutes. When the Loop Check T imer has timed out, the detector will automatically short the check loop to simulate vehicle detection. If the percentage of inductance change is greater than or equal to -0.04% L/ L, and the channel on which the current loop check test is selected and being viewed on the LCD, the display will show PAS.
Indication
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 25 of 33
Page 32
LOOP FAIL
1
©
LOOP FAIL
1
©
Loop Check
1 Loop Check
If the percentage of inductance change caused by activating the check loop is less than -0.04% L/L, the detector will initiate its check loop verification process. The LCD screen will displa y a n ind icat io n of a pe ndi ng st ate (Pcl) during the check loop verification. This scree n will flash for 55 seconds until one o f three things happen; the check loop verificat ion fails (indic ati on s how n be low - Lcl), the check loop(s) causing t he check loop verificat ion is (are) connected or restored to a functional state (indication shown above, PAS), or the check loop(s) causing the check loop verificat ion is (are) turned off, i.e. the Loop C heck Timer of the loop(s) is set to 000.
Pending Indication
If the check loop verification fails, the LED corresponding to t hat loop channel will begin flashing at a three Hz rate. If the channel corresponding to the check loop failure is selected and being viewed on the LCD, the display will toggle between a screen showing L and LOOP FAIL and a scree n showing Lcl and LOOP FAIL wit h a 50% dut y cyc le to indicate a that Loop Check failure has occurred. In addition, the loop status will enter the Ca ll state and the Health Stat us will enter the Fail condition. A Loop Check failure w ill dea ctiva te a ny Prima ry Vita l O utput to which any loop input or Health Sta tus is mapp ed. When t he Health Status of one or more loop inp uts is (are) mapped to an Auxiliary V ital Output, a loop check failure will deact ivate the Auxiliary Vital Output.
Disabling the Loop Check feature (setting the Loop Check Timer to zero), powering down the detector, or res etting the channel that failed t he loop
Failure Indication
The Loop Check feature is suppressed if the loop has an open, a shorted, or a relative (±25% L/L) failu re. The detector will perform a loop check test on all programmed channels two seconds after start-up or two seconds
after a reset.
NOTE: If the Loop Check Timer is set to 000, the Loop Check function is off.
check test will clear the Loop C heck fa ilur e. Howe ver, if the pro blem tha t caused the Loop Check failure is not corrected, the channel will fail the next loop check test.

5.6 VITAL INPUT (VITAL IN) STATUS / FAIL I NDICATIONS

The Vital Input has a dual color (gree n / red) LED t hat illu minates in various wa ys to ind icate the sta te of the Vita l Input. Whe n the L ED is off, the V ita l Inp ut is de act ivat ed (l ow vo ltage leve l). W hen t he LE D dis pla ys as solid green, the Vi tal In put is acti vated ( high v olta ge leve l). W hen the LED d ispla ys as s olid re d, the Vital Input has failed its self-check.

5.7 PRIMARY VITAL OUTPUT (VI TAL OUT) STATUS / FAIL INDICATIONS

The Primary Vital Output has a d ual color (green / red) LED that illuminates in various ways to indicate the state of the Primary Vital O utput. When the LED is o ff, the Primary Vita l Output is deactivated (low voltage level). When the LED d isp la ys as so lid gr ee n, the Pr i mar y V ita l O ut p ut is ac t iva te d ( hig h volt a ge le ve l). W he n the LE D displays as a two Hz flashing green, t iming delay is activated and the Primar y Vital Output is functioning (low volta ge level unt il delay t imes out). When the LED displays as a five Hz flashing green, timing extension is activated and the Primary Vital Output is funct ioning (low voltage leve l un t il extension times out). When the LED displays as solid red, the Primary Vital Output has failed its self-check.

5.8 AUXILIARY VITAL OUTP UT (VITAL AUX) STATUS / FAIL INDICATIONS

The Auxiliary Vital Output has a d ual colo r (green / re d) LED that illu mina tes in various wa ys to in dicate t he state of the Auxiliary Vital Output. When the LED is off, t he Auxiliary V ital Output is dea ctivated (low voltage level). When the LED displays as s olid green, the Auxiliary Vital Output is activated (hig h voltage level). When t he LED displays as solid red, the Auxiliar y Vita l Out put has failed its self-check.

5.9 SYNCH FAIL INDICATI O NS

5.9.1 SERIES SYNCH F AIL I NDI CATIONS

889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 26 of 33
Page 33
©
Series
Indication
Parallel
Indication
+25% change or
-25% change or
LOOP FAIL
1
©
LOOP FAIL
1
©
When the Synch feature is set to operate in Ser ies Synch mode (Option 7 is set to 7. 01), the LCD wi ll display SYS. If, after completing the sampling routine, the detector determines there is a failure on one or more loop inputs, the LCD will display FSY and continue sampling. If the Synch failure is cleared, the fail indicat ion (FSY) will no lo n ger be dis p layed on the LC D .
Synch Mode
Failure

5.9.2 PARALLEL SYNCH FAIL INDICATIONS

When the Synch feature is set to operate in Para llel Synch mode (Option 7 is set to 7. 02), the LCD will display SYP If, after completing the sampling routine, the detector d ete rmines there is a failure on one or more loop inputs, the LCD will display FSY and continue sampling. If the Synch failure is cleared, the fa il indication (FSY) will no longer be displayed on the LCD.
Synch Mode
Failure

5.10 LOOP FAIL INDICATIONS

If the to tal induc tanc e of a c han nel’s loop inp ut net work goes out o f the range specified for the detector, or rapidly c hanges by more than ±25%, the loop input channel will ente r the Fail-Safe mode a nd d ispla y LOOP FAIL on the LCD. The type of loop failure will also be displayed as L lo (for -25% change or shorted loop cond itions) or L hi (for +25% change or open loop conditions). This w ill continue as long as the loop fault exists. Fail-Safe mode generates a continuous call. At the time of a loop failure, t he loop input c hannel’s LED will begin to flas h at a rate o f t hree flashes per second. The LED will co ntinue this display pattern until the channel is manually reset or power is removed.
If the loop self-heals, the LOOP FAIL message on the LCD will extinguish and the loop input channel will resume operation in a normal manner; except, the LED will continue the three flashes per second
open loop
condition.
shorted loop
condition.
channel (since the last power interruption or manual reset) is written into the Loop Fail M emory and can be seen by stepping through the channel’s functions in Program Mode to the LOOP F A IL display.
This is a useful tool to identify intermittent loop prob lems. If the count is extremely high for the pe riod of time observed, the problem is very likely a loose connection (check for loose connections at the termina l strip and bad splices in the field). The Loop Fail Count is reset when power is removed from the detector. This prevents the Loop Failure Count from moving to another loop if the detector is moved to a new location.
To view the Loop Fail Count, se lect the desired loop input channel using the CHAN p ushb utto n the n rep eate dly press the FUNC pushbu tton unt il the LOOP F AIL disp lay is sho wn. The Loop Fa il Count displa y is afte r the Optio n disp lays. Press ing the  (UP) or  (DOWN) pus hbutton while the Loop Fail Co unt is displayed, will reset the count to zero.
display pattern, thus, providing an a lert that a prior Loop Fail condition has occurred. Each loop failure is counted and accumulated into the Loop Fail Memory. The total number of loop failures for the loop input

5.11 SETTING SENSITIVITY USING THE BARGRAPH

The bargraph is a graphical representation of the relative change of inductance as seen by the detector loop input channel; automatically taking into account sensitivity setting, loop geometry, configuration, lead-in length, etc. The firs t ba rgrap h se gment repr ese nts t he mini mum induc tance cha nge (s et b y the s ensit ivit y leve l) ne ces sary for the loo p i np ut c ha nne l to ou tp ut a ca l l. Ea ch add itional segment represents the inductance change in excess of the
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 27 of 33
Page 34
SENSITIVITY 10 9 8 7 6 5 4 3 2 1
% of Inductance 0.01 0.02 0.04 0.08 0.16 0.32 0.64 1.28 2.56 5.12
.
1
©
SENSITIVITY 10 9 8 7 6 5 4 3 2 1
%
.
©
next se ns itiv ity t hres ho ld. U sua lly, the lar ger t he ve hic le de tec ted , the mo re ba rgra ph seg ments dis pla yed , i.e . the greater the -L/L. The bargraph can be used to select the proper sensitivity le ve l.
The bargraph below shows the deflection (3 segments) o f a vehicle with Sensitivity set to Level 5. The vehicle in the loop zone is causing a change of inductance greater than 1.28% -ΔL/Lor Sensiti vity Level 3.
The Bargraph is a window that adjusts to the sensitivity setting
of Inductance 0.01 0.02 0.04 0.08 0.16 0.32 0.64 1.28 2.56 5.12
The bargraph below has the same vehicle in the loop zone causing the same inductance change as above. Because the sensitivity setting was increased to Level 8, six segments are now displayed. If the bargraph displays 5 or 6 segments for a vehicle in the loop, the sensitivity has been set to the proper range.
The Bargraph is a window that adjusts to the sensitivity setting

5.12 FULL RESTORE TO FACTORY DEFAULT SETTINGS

Pressi ng a ll fo ur fr o nt pa ne l pus hb ut to n s wit c hes s imu lta ne o us ly a nd co nt inu o us ly f or f ive (5 ) se co nd s re st o res a ll factory default settings. The countdown of the five se cond period is displayed on the LCD. Releasing any or all of the sw itches before the countdown ends aborts t he full restore operation. (See Section 3.5 for default settings). Refer to Section 5.0 for details. Caution: Restoring the factory default settings will clear all previously
programmed settings including any mapped output(s).

5.13 DIAGNOSTIC FEATURES ACTIVATION

When the detector is operating in normal mode, pressing either the  (UP) or  (DOWN) p ushbutton w ill temporarily activate Option 1 (Loop Inductance Display) and Opt ion 2 (Loop Inductance -ΔL/L Display) for all loop i np uts and Optio n 6 (Audib le Detect S ignal) for the loop input ind icated in the lower port io n of the LCD. A ll three of these diagnostic options will remain active for 15 minutes.

5.14 DISPLAY TEST

Pressing any two or three of the front panel pushb utton switches simultaneo usly will turn on a ll possible s ymbols and messages on the LCD screen.

5.15 CHANGING PROCESSOR BOARD OR MOTHERBOARD

The P-1400 dete ctor stores use r-progra mmed para meters o n an internal EEPROM mounted o n the p rocessor boa rd and on an EEPROM mounted on the motherboard. This allows the user to change the processor assembly or motherboard and reset the parameters that were programmed for that particular site. When a new processor assembly or motherboard is installed, an Error message will appear on the LCD. The LCD will alternate between Cpy and In. This message means that the parameters stored on the motherboard mounted EEPROM do not match the parameters stored on the EEPROM on the processor board. If the motherboard was replaced, pressing the FUNC pushbutton will accept the para mete rs s tored on the EEPROM on the processor board and store them on the motherboard mounted EEPROM. If the processor board was replaced, pressing either the  (UP) or  (DOWN) pushbu tt on w ill cha n ge t he a l te rna ti ng mes s age o n t he LCD to Cpy and Out. Pre ss in g t he FUNC pushbutton will
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 28 of 33
Page 35
1 © 1 © 1 © 1
©
accept the parameters stored on the motherboard mounted EEPROM and copy t hem to the EEPROM on t he processor board.
Parameters stored on the motherboard mounted EEPROM do not match those s tored on t he interna l EEPROM. Pressin g the FUNC pushbutton will accept the parameters stored on the internal EEPROM and store them on the motherboard mounted EEPROM, i.e. copy the internal EEPROM parameters to the motherboard mounted EEPROM.
Parameters stored on the motherboard mounted EEPROM do not match those s tored on t he interna l EEPROM. Pressin g the FUNC pushbutton will accept the parameters stored on the motherboard mounted EEPROM and store them on the internal EEPROM, i.e. copy the motherboard mounted EEPROM parameters to the internal EEPROM.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 29 of 33
Page 36
Loop
Loop
Loop
Non-
Loop
Loop
Loop
Loop
Loop
Loop
Squaring Circuit
DETECT
LCD
+9 to
DC Com
Vs
+12 VDC
GND
Front
Pushbutton
32 MHz
Audible
Loop
Loop
Loop
RS-232
RS-232
Check
Check
Check
Check
Check
+10 VDC
+5 VDC
Synch In
Synch Out
Loop 1
Check
Loop 2
Check
Loop 3
Check
Loop 4
Internal
EEPROM
Motherboard
EEPROM
Auxiliary
Vital
Vital I nput
Primary
Vital

Section 6 Block Diagram

Inputs
Loop 1
Inputs
Inputs
Loop 2
Inputs
Inputs
Loop 3
Inputs
Isolation
Loop
Activation
Relay
Isolation
Loop
Activation
Relay
Isolation
Loop
Activation
Relay
Oscillator
Oscillator
Oscillator
Capacitors
Capacitors
Capacitors
Micro Controller
volatile
LEDs
Panel
Switches
Oscillator
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 30 of 33
Inputs
Loop 4
Inputs
+18 VDC
Isolation
Loop
Activation
Relay
Power
Supply
Oscillator
Capacitors
Communication
Input
Buzzer
Communication
Output
Mounted
Page 37

Section 7 Theory of Operation

The Re no A&E M od el P -1400 detector digitally meas ures changes in the resonant frequency of four independent loop circuits to determine if a vehicle has entered the detection zone. The Model P-1400 detector applies an excitation voltage to each loop circuit resulting in the loops oscillating at their reso nant frequencies. The current flow in the loop wire creates magnetic fields around the loop wire. When a vehicle passes over the loop area, the conduc tive meta l o f the vehicle causes a loading of the loop’s magnetic fields. The loading decreases the loop inductance, which causes the resonant frequency to increase. By continuously sampling the loop’s resonant freque ncy, the magnitude and rate o f change c an be determined. If the frequency change exceeds a selectable threshold (set by the sensitivity settings), the detector will deactivate a Vital output if one is mapped. If the rate of change is slow, typical of environ mental drift, the detecto r will cont inuously track and compensate for the change. The Model P-1400 detector also monitors the loop frequency for out of range conditions such as an open or shorted loop circuit.
The Model P-1400 detector is a scanning detector. The scanning method sequentially turns on and off eac h channel’s loop oscillator. Each channel’s osc illator circuit supplies t he excitation voltage that is coupled to the loop circuit by a loop isolation transformer. The tra nsformer provides high common mode isolation between the loop and detector electronics, which allows the detector to opera te on poor qualit y loops including a single s hort to ground. The transformer also limits the amount of static energy (lightning) that can transfer to the detector electronics. A spark gap transient suppression device is connected across the loop inp uts co nne cted to the isolation transformer. This device dissipates static charges prior to the transformer. A network of four capacitors is connected to the detector side of the isolation transformer. Three of the capacitors can be switched in or out of the oscillator circuit to shift the frequency of the loop osc illator circuit thus providing frequency separation be tween adjacent loops. The three switchable capacitors are electronically switched using FETs and are selected when programming parameter value s with the front p anel pushbutton switches.
The outputs from the four loop oscillators are tied together and fed into a co mmon squaring circuit. This is possible since the detector is a scanning detector allowing only a single loop oscillator to be operating at a ny given time. The sine wave from each loop oscillator circuit is squared to provide a prec ise zero crossing signal for the input to the microcontroller. This signa l is called the loop sample. The loop sample is an integral number of complete oscillations from the loop oscillator circuit. The number of loop oscillatio ns counted is a function of the selected sensitivity setting for the detector channel. The required number of loop oscillations needed for a loop sample increases as the sensitivity setting is increased. The microcontroller uses the period of the loop sample for accumulating high-speed (32 MHz) crystal clock p ulses generated by the microcontroller’s internal high-speed crystal oscillator. The number of crystal clock pulses accumulated during consecutive loop samples is compared to the internal reference number of crystal clock pulses stored in the microcontroller’s memory.
When a vehic le ente rs t he loop zone t he l oop ind ucta nce de creases. This decrease in loop inductance causes an increase in the loop oscillato r frequency. In turn, an increase in loop oscillator frequency results in a decrease of the time period for the loop sample. Hence, when a vehicle enters the loop zone, the number of cr ystal clock pulses accumulated during a loop sample period decreases. By comparing the new count with the reference count, a percentage change can be calculated that indirectly relates to the inductance change. If the magnitude of the change exceeds a selectable threshold (sensitivity setting), the detector deactivates a Vital output if one is mapped. The rate of change is also monitored. Slow rates of c hange caused by environmental fluctuations are tracked and automatically compensated for. This process is conducted independently for each of the four loop oscillator circuits.
The microcontroller uses the high-speed crystal clock count to calculate the loop inductance, frequency and percentage of change. If selected, the values are displayed on the seve n-segment LCD. The microcontroller also processes the pushbutton switch selections for the LCD display and stores the operating parameters in non-volatile memory. Stored parameters are changed with the front panel switches or via the front panel RS-232 communications port and are unaffected by loss o f power or detector reset. The microcontroller continuously processes the loop samples and detector operation is not affected during the operation of the switches or the LCD. NOTE: When eit her the sensitivity or frequency of a loop input channel is changed, the loop input cha nnel is reset.
In addition, the microcontroller conditions the outputs based on Loop Status Inputs, Vital Inputs, Health Status Inputs , and the p rogramme d settings of the va rious ti mers (Prima ry Vita l Output De lay, Pri mary Vital O utput Extension, and Loop Check) and options (Option 1, Option 2, Option 3, Option 4, Opt ion 5, Option 6 and Option
7).
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 31 of 33
Page 38

Section 8 Maintenance and Troubleshooting

The Reno A&E Model P-1400 Detector requires no maintenance. If you are having problems with your Mode l P­1400 detector, use the troubleshooting tips below to help determine the cause of the prob lem.

8.1 BASIC TROUBLESHOOTING TIPS

Detector Enclosure Checks:
Verify correct input voltage to the detector. Check the detector diagnostics. If there is a current loop failure or the loop fail memory shows a loop failure has
occurred, the problem is probably not related to the detector module. Check the loop / lead-in cable resistance of the detect loops and the check loops. A value greater t han five
Ohms is an indication of a splice or connection problem or a broken loop wire. Disconnect the detect loop or check loop from the detector. Use a 500 VDC Megger to measure the resistance
from one of the loop wires to earth ground. It should be greater than 50 megOhms. If lower, separate the splice at the pull box and isolate the problem to the loop or lead-in cable.
Verify all terminal screws are tight. Inspect all loop connections in the detector enclosure, especially crimped lug connections. If suspect, solder the
lugs to the wire. If the lightening or surge suppression devices on the loop inputs in the detector e nclosure are s uspect, remove or
replace them. Check for places in the detector enclosure where the harness wires or lead-in cable may be pinched or chaffed. Make sure that each pair of interconnect (lead-in) wires for the loop(s) are individually twisted together.
Field Checks:
Inspect the loop. Look for exposed wires, debris pressed into the loop wires, paveme nt s hifts , e tc . Check splices in the pull box. They must be soldered and waterproofed. DO NOT USE WIRE NUTS. Check that each set of loop lead-in wires in each pull box is twisted to gether [six (6) twists per foot, minimu m]
and that lead-in lengths are not excessi ve.
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 32 of 33
Page 39

8.2 THINGS TO KNOW ABOUT LOOPS

Always use a wire with cross-linked Polyet hylene insu lation (insulation type XLPE) for loo p wire. Typical sensing height is ⅔ of the shortest leg of a loop. Therefore, a 6΄ x 6΄ loop will have a detection height of 4΄. The inductance of a conventional four-sided loop can be estimated using the formula: L = P x (T2 + T) / 4 Where: L = Loop Inductance in microhenries
P = Loop Perimeter in feet T = Number of Turns of Wire.
Therefo re, a 6΄ by 6 ΄ loop with 3 turns would have an inductance of:
L = (6 + 6 + 6 + 6) x (32 + 3) / 4 L = 24 x (9 + 3) / 4 L = 24 x 12 / 4 L = 24 x 3
L = 72 microhenries. The inductance of a QuadrupoleTM loop can be estimated using the formula: L = [P x (T
P = Loop Perimeter in feet TOL = Number of Turns of Wire (Outer Legs) T CL = Length of Center Leg in feet.
2
+ TOL) / 4] + [CL x (T
OL
2
+ TCL) / 4] Where: L = Loop Inductance in microhenries
CL
= Number of Turns of Wire (Center Legs)
CL
Therefo re, a 6΄ by 50΄ loop with a 2-4-2 config uration w ould have an inductance of:
L = [(6 + 50 + 6 + 50) x (22 + 2) / 4] + [50 x (42 + 4) / 4]
L = [112 x (4 + 2) / 4] + [50 x (16 + 4) / 4]
L = (112 x 6 / 4) + (50 x 20 / 4)
L = (112 x 1.5) + (50 x 5)
L = 168 + 250
L = 418 micr ohenries. Loop Feeder cable typically adds 0.22 microhenrie s of inductance per foot of cable. Total inductance of loops connected in series: L Total inductance of loops connected in parallel: L
= L1 + L2 + L3 + . . . + LN.
TOTAL
= 1 / [ (1 / L1) + (1 / L2) + (1 / L3) + . . . + (1 / LN) ].
TOTAL
889-1600-04 Model P-1400 Operations Manual Rev Apr 2020 Page 33 of 33
Loading...