Remote Automation Solutions V-Cone Metering Program (For ROC800) Manuals & Guides

Form A6149
Part Number D301193X012 June 2016
V-Cone
Metering Program User Manual
(for ROC800-Series)
Remote Automation Solutions
V-Cone Metering Program User Manual (for ROC800-Series)
Page
Revision
All Pages
June-2016
All Pages
October-2013
All Pages
May-2012
All Pages
October-2011
ii, 1, 5, 6
April-2004
Initial Issue
September-2003

Revision Tracking Sheet

June 2016
This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):
ii Revised June-2016
V-Cone Metering Program User Manual (for ROC800-Series)

Contents

Chapter 1 – Introduction 1
1.1 Scope and Organization ................................................................................................................ 1
1.2 Product Overview .......................................................................................................................... 1
1.3 Program Requirements ................................................................................................................. 2
1.3.1 License Keys .................................................................................................................... 3
Chapter 2 – Installation 5
2.1 Installing the License Key.............................................................................................................. 5
2.1.1 Verifying the License Key Installation .............................................................................. 6
2.2 Downloading the V-Cone Program ............................................................................................... 7
2.3 MPU Loading Threshold .............................................................................................................. 10
Chapter 3 – Configuration 13
3.1 V-Cone Configuration Screen ..................................................................................................... 14
3.2 Station Setup ............................................................................................................................... 16
3.3 Orifice Meter Setup ..................................................................................................................... 16
3.4 Orifice Values .............................................................................................................................. 18
3.5 Saving the Configuration ............................................................................................................. 19
Chapter 4 – Reference 21
4.1 Point Type 61/71: V-Cone Metering Configuration ..................................................................... 22
Revised June-2016 iii
V-Cone Metering Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
iv Revised June-2016
V-Cone Metering Program User Manual (for ROC800-Series)

Chapter 1 – Introduction

This chapter describes the structure of this manual and presents an overview of the V-Cone® Metering program for the ROC800-Series Remote Operations Controller (ROC800).

1.1 Scope and Organization

This document serves as the user manual for the V-Cone Metering user program, which is intended for use in ROC800. This manual describes how to download and configure the V-Cone Metering user program (referred to as the “V-Cone program” or “the program” throughout the rest of this manual). You access and configure the program using ROCLINK 800 Configuration Software (version 2.00 or greater) loaded on a personal computer (PC) running Microsoft® Windows® 2000 (with Service Pack 2), Microsoft Windows XP, Microsoft Windows Vista™, or Microsoft Windows 7 (32-bit or 64-bit).
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software running in a ROC800, the manual becomes a reference tool.
This manual has the following major sections:
Section 1 – Introduction Section 2 – Installation Section 3 – Configuration Section 4 – Reference
This manual assumes that you are familiar with the ROC800 units and their configuration. For more information, refer to the following manuals:
ROC800-Series Remote Operations Controller Instruction Manual
ROCLINK 800 Configuration Software User Manual (for ROC800-

1.2 Product Overview

The V-Cone program allows a ROC800 to calculate a corrected volumetric flow rate at a specified base pressure and temperature for a McCrometer V-Cone or Wafer-Cone flowmeter. The V-Cone or Wafer­Cone flowmeter is very similar to an orifice plate calculation, uses many of the same configuration parameters, and produces many of the same calculated values. For this reason, the user program makes use of existing orifice meter run points already provided by the ROC800 firmware. In addition to the standard orifice point parameters, the ROC800 also calculates an actual volumetric flow rate, a fluid velocity, a thermal expansion factor, and the percent pressure loss in accordance with the
(part D301217X012).
Series) (part D301250X012).
Revised June-2016 Configuration 1
V-Cone Metering Program User Manual (for ROC800-Series)
v. 3.30
v. 2.16
v. 3.30
v. 2.16
McCrometer specification McCrometer Flow Calculations for the V-Cone Flowmeter, October 2002.
As part of the V-Cone program point configuration, you assign the V­Cone or the Wafer-Cone calculation to an orifice meter point. When the calculation is assigned, the standard AGA3 calculation is bypassed and the McCrometer calculation is performed instead. All standard orifice parameters, as well as the additional V-Cone program parameters, are available for assignment to Modbus registers, PID control loops, historical archiving, and FST and DS800 database functions.

1.3 Program Requirements

The V-Cone program version 1.11 is compatible with ROC800-Series 2 firmware version 3.30 (or greater), ROC800-Series 1 firmware version
2.16 (or greater), ROC800L firmware version 1.20 (or greater), and with version 2.00 (or greater) of ROCLINK 800 configuration software. The program requires you to install an AGA 3/7/8 hardware-based license key to enable the calculations, and a V-Cone license key to enable the user program.
File Name
V-Cone.61.tar
V-Cone.71.tar
Target
Unit/
Version
ROC800-
Series 2
ROC800-
Series 1
ROC800-
Series 2
Notes:
Two versions of the program are included. Installation and operation
are identical between the two programs, but they use different point type locations, different display numbers. V-Cone.61.tar uses point types 61 and uses display 61. V-Cone.71.tar uses point types 71 and uses display 71. Install the program version that avoids point type conflicts with currently installed programs.
The installation process and functionality is the same for all versions
of the V-Cone program.
Program specifics include:
User Defined
Point (UDP)
61 16151 408 73728 2.00 61
71 16151 408 73728 2.00 71
Flash Used
(in bytes)
SRAM Used
(in bytes)
DRAM
Used (in
bytes)
ROCLINK
800
Version
Display
Number
ROC800-
Series 1
For information on viewing the memory allocation of user programs, refer to Section 7.7 of the ROCLINK 800 Configuration Software User Manual (for ROC800-Series) (part D301250X012).
Revised June-2016 Configuration 2
V-Cone Metering Program User Manual (for ROC800-Series)
DOC0422A
J1
U1

1.3.1 License Keys

License keys, when matched with valid license codes, grant access to applications such as the V-Cone program. An AGA3/7/8 license key must be present to provide the required number of meter runs, and a separate license key is also required to enable the V-Cone user program.
The term “license key” refers to the physical piece of hardware that can contain up to seven different licenses (refer to Figure 1–1). Each ROC800 can have none, one, or two license keys installed. If you remove a license key after enabling an application, the firmware disables the task from running. This prevents unauthorized execution of protected applications in a ROC800.
Figure 1-1. License Key
Revised June-2016 Configuration 3
V-Cone Metering Program User Manual (for ROC800-Series)
[This page is intentionally left blank.]
Revised June-2016 Configuration 4
V-Cone Metering Program User Manual (for ROC800-Series)
DOC0423A

Chapter 2 – Installation

This section provides instructions for installing the V-Cone program into the ROC800. Read Section 1.3 of this manual for program requirements.
Notes:
The computer running ROCLINK 800 must be connected to the Local
Operator Interface (LOI) port before you begin the download.
The program and license key can be installed in any order. The manual
shows the installation of the license key first.
The installation process and functionality is the same for all versions
of the V-Cone program.

2.1 Installing the License Key

If you order the V-Cone program for a new ROC800, your ROC800 is delivered with the license key installed. Go to Section 2.2. If you order the program for an existing ROC800, you must install the license key yourself.
Caution
Failure to exercise proper electrostatic discharge precautions, such as wearing a grounded wrist strap may reset the processor or damage electronic components, resulting in interrupted operations.
When working on units located in a hazardous area (where explosive gases may be present), make sure the area is in a non-hazardous state before performing these procedures. Performing these procedures in a hazardous area could result in personal injury or property damage.
To install a license key:
1. Remove power from the ROC800.
2. Remove the wire channel cover.
3. Unscrew the screws from the Central Processing Unit (CPU) faceplate.
4. Remove the CPU faceplate.
5. Place the license key in the appropriate terminal slot (P4 or P6) in the
CPU.
Figure 2-1. License Key Installation
Note: When using a single license key, install it in slot P4.
Revised June-2016 Configuration 5