Remote Automation Solutions ROCLINK 800 Configuration Software User Manual (for ROC800L) Manuals & Guides

Part D301246X012
September 2020

ROCLINK™ 800 Configuration Software User Manual (for ROC800L)

Remote Automation Solutions
ROCLINK 800 Configuration Software User Manual (for ROC800L)
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential system expertise. Our full­time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338­8158 or email us at education@emerson.com
.
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Contents

Chapter 1 – Introduction 1-1
1.1 ROCLINK 800 Software Basics .................................................................................................... 1-1
1.2 Computer Requirements ............................................................................................................... 1-2
1.3 Contacting Technical Support ....................................................................................................... 1-2
1.4 Software Installation ...................................................................................................................... 1-3
1.4.1 Installing ROCLINK 800 under Microsoft Windo ws 1 0, Windows 8 or Windows 7 ........ 1-3
1.4.2 Un-installing ROCLINK 800 .......................................................................................... 1-25
1.5 Starting ROCLINK 800 Software ................................................................................................. 1-25
1.5.1 Logging On.................................................................................................................... 1-25
1.6 User Interface Basics .................................................................................................................. 1-26
1.6.1 The ROC800-Series Dynamic Interface ....................................................................... 1-28
1.6.2 Standard Buttons .......................................................................................................... 1-29
1.6.3 Toolbar Buttons ............................................................................................................. 1-30
1.6.4 Configuration Tree Menu .............................................................................................. 1-31
1.6.5 Keystrokes .................................................................................................................... 1-32
1.6.6 Help System .................................................................................................................. 1-33
1.6.7 Basic Navigation ........................................................................................................... 1-34
1.6.8 Text Boxes .................................................................................................................... 1-35
Chapter 2 – Device Directory and Device Root 2-1
2.1 Device Directory ............................................................................................................................ 2-1
2.1.1 Communication Parameter Setup Screen ...................................................................... 2-2
2.2 Device Root ................................................................................................................................... 2-4
2.2.1 Backing Up ROCLINK Device Definitions ....................................................................... 2-5
2.2.2 Adding a Group ............................................................................................................... 2-5
2.2.3 Deleting a Group ............................................................................................................. 2-6
2.2.4 Adding a Device .............................................................................................................. 2-6
2.2.5 Deleting a Device ............................................................................................................ 2-7
2.2.6 Deleting All Devices ........................................................................................................ 2-7
2.2.7 Renaming a Group or Device ......................................................................................... 2-7
Chapter 3 – Communications and Security 3-1
3.1 Communications............................................................................................................................ 3-1
3.2 ROCLINK 800 Communications ................................................................................................... 3-2
3.2.1 ROCLINK 800 Communications General Tab ................................................................ 3-2
3.2.2 ROCLINK 800 Communications Advanced tab .............................................................. 3-4
3.3 Communication Ports .................................................................................................................... 3-6
3.4 Configuring Communications Ports............................................................................................... 3-7
3.4.1 Configuring TCP/IP Communications on the Ethernet Port ............................................ 3-7
3.4.2 Comm Ports General Tab ............................................................................................... 3-9
3.4.3 Comm Ports Modem Tab .............................................................................................. 3-12
3.4.4 Comm Ports SRBX Tab ................................................................................................ 3-13
3.4.5 Comm Ports Store & Forward Tab................................................................................ 3-15
3.4.6 Comm Ports Diagnostics Tab ....................................................................................... 3-15
3.5 Connecting to a ROC .................................................................................................................. 3-16
3.5.1 Direct Connect .............................................................................................................. 3-17
3.5.2 Local Port (LOI) ............................................................................................................. 3-18
3.5.3 Connect to a ROC ......................................................................................................... 3-18
3.5.4 Successful Login ........................................................................................................... 3-18
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3.5.5 Disconnecting from a ROC ............................................................................................ 3-19
3.6 Troubleshooting Connection Errors ............................................................................................. 3-19
3.6.1 Troubleshooting ROCLINK 800 Communications ......................................................... 3-20
3.6.2 Troubleshooting TCP/IP Connections ........................................................................... 3-20
3.7 Security ........................................................................................................................................ 3-21
3.7.1 ROCLINK 800 Security .................................................................................................. 3-21
3.7.2 Device Security .............................................................................................................. 3-25
Chapter 4 – The File Menu 4-1
4.1 New Configuration .......................................................................................................................... 4-2
4.1.1 Configuration Checklist .................................................................................................... 4-2
4.1.2 Duplicating a Configuration .............................................................................................. 4-3
4.2 Opening a Configuration File ......................................................................................................... 4-3
4.2.1 Configuration Tree Menu ................................................................................................. 4-4
4.2.2 Modifying an Existing Configuration File .......................................................................... 4-6
4.2.3 Adding Modules to an Existing Configurati on F i le ........................................................... 4-6
4.3 Downloading a Configuration ......................................................................................................... 4-8
4.4 Saving a ROC User File ............................................................................................................... 4-10
4.5 Saving a Configuration ................................................................................................................. 4-10
4.6 Printing a Configuration ................................................................................................................ 4-10
4.7 Print .............................................................................................................................................. 4-12
4.8 Print Setup ................................................................................................................................... 4-12
4.9 Recent Files ................................................................................................................................. 4-13
4.10 Close ............................................................................................................................................ 4-13
4.11 Exit ............................................................................................................................................... 4-13
Chapter 5 – The View Menu 5-1
5.1 Directory ......................................................................................................................................... 5-2
5.2 EFM Reports .................................................................................................................................. 5-2
5.2.1 Creating the EFM File ...................................................................................................... 5-2
5.2.2 Viewing EFM Reports ...................................................................................................... 5-3
5.3 Calibration Reports ........................................................................................................................ 5-7
5.3.1 Viewing a Calibration Report ........................................................................................... 5-7
5.4 History Logs ................................................................................................................................... 5-8
5.4.1 Viewing Logs from a Device .......................................................................................... 5-10
5.4.2 Viewing History Logs from a File ................................................................................... 5-11
5.4.3 Plotting History ............................................................................................................... 5-12
5.4.4 Managing Plotted History ............................................................................................... 5-13
5.5 Transaction History ...................................................................................................................... 5-14
5.5.1 Viewing Transaction History Stored in a Device ............................................................ 5-14
5.5.2 Viewing Transaction History Stored in a File ................................................................. 5-16
5.6 Alarm, Event, and Weights & Measurements Event s Logs ......................................................... 5-17
5.6.1 Viewing Alarm Logs ....................................................................................................... 5-18
5.6.2 Viewing Event Logs ....................................................................................................... 5-18
5.6.3 Viewing Weight and Measure Events Logs ................................................................... 5-19
5.7 Display Editor ............................................................................................................................... 5-20
5.8 Display Administrator ................................................................................................................... 5-21
5.8.1 Viewing a Custom Display ............................................................................................. 5-21
5.8.2 Downloading a Custom Display ..................................................................................... 5-21
5.8.3 Deleting a Custom Display ............................................................................................ 5-23
5.9 I/O Monitor ................................................................................................................................... 5-23
5.10 Toolbar ......................................................................................................................................... 5-25
5.11 Refresh User Program Tree ......................................................................................................... 5-25
Chapter 6 – The ROC Menu 6-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)
6.1 Direct Connect............................................................................................................................... 6-1
6.2 Connect/Disconnect ...................................................................................................................... 6-2
6.3 Collect ROC Data .......................................................................................................................... 6-2
6.3.1 Collecting EFM Report Data ........................................................................................... 6-5
6.3.2 Collecting Liquid CFX Flow-Cal Data (ROC800L) .......................................................... 6-7
6.4 Clock ........................................................................................................................................... 6-10
6.4.1 Daylight Savings Time Tab ........................................................................................... 6-11
6.5 ROC Security .............................................................................................................................. 6-11
6.6 ROC Comm Ports ....................................................................................................................... 6-11
6.7 Configuring Device Information ................................................................................................... 6-12
6.7.1 General Tab .................................................................................................................. 6-12
6.7.2 Internet Tab ................................................................................................................... 6-15
6.7.3 Points Tab ..................................................................................................................... 6-17
6.7.4 Other Information Tab ................................................................................................... 6-19
6.7.5 System Configuration Tab ............................................................................................ 6-20
6.7.6 Keypad Display Tab ...................................................................................................... 6-21
6.7.7 Expanded I/O Tab (ROC827) ....................................................................................... 6-22
6.7.8 Module Information Tab ................................................................................................ 6-23
6.7.9 MPU Loading Tab ......................................................................................................... 6-25
6.8 Flags ............................................................................................................................................ 6-26
6.8.1 Flags Tab ...................................................................................................................... 6-26
6.8.2 Returning the Device to Factory Default Settings ......................................................... 6-29
6.8.3 Flags Advanced Tab ..................................................................................................... 6-29
Chapter 7 – 0BThe Configure Menu 7-1
7.1 1BConfiguring I/O .............................................................................................................................. 7-2
7.1.1 8BAnalog Input (AI) Configuration....................................................................................... 7-2
7.1.2 9BAnalog Output (AO) Configuration ................................................................................ 7-18
7.1.3 10BDiscrete Input (DI) Configuration .................................................................................. 7-22
7.1.4 11BDiscrete Output (DO) Configuration .............................................................................. 7-27
7.1.5 12BDiscrete Output Relay (DOR) Configuration ................................................................. 7-36
7.1.6 13BPulse Input (PI) Configuration ....................................................................................... 7-36
7.1.7 14BThermocouple (TC) Input Configuration ....................................................................... 7-43
7.1.8 15BResistance Temperature Detector Input Configurat i on ................................................ 7-49
7.1.9 16BSystem Analog Input (AI) Configuration ....................................................................... 7-63
7.1.10 17BSoft Points ..................................................................................................................... 7-68
7.1.11 18BMulti-Variable Sensor (MVS) Configuration .................................................................. 7-69
7.1.12 19BHART Input Configuration ............................................................................................. 7-88
7.1.13 20BAlternating Current I/O (ACIO) Configuration ............................................................. 7-102
7.1.14 21BAdvanced Pulse Module (APM) Configuration ........................................................... 7-113
7.1.15 22BVirtual Discrete Output (VDO) Configuration .............................................................. 7-132
7.1.16 23BIEC62591 module ....................................................................................................... 7-140
7.2 2BControl Menu ............................................................................................................................. 7-140
7.2.1 24BFST Registers ............................................................................................................. 7-141
7.2.2 25BProportional, Integral, and Derivative (PID) ................................................................ 7-143
7.2.3 26BRadio Power Control ................................................................................................... 7-155
7.2.4 27BSampler/Odorizer ........................................................................................................ 7-158
7.2.5 28BDS800 Development Suite Software .......................................................................... 7-160
7.3 3BHistory Segment Configuration ................................................................................................. 7-162
7.4 4BHistory Point Configuration ....................................................................................................... 7-166
7.4.1 29BHistory ......................................................................................................................... 7-169
7.4.2 30BHistory Wizard ............................................................................................................. 7-173
7.4.3 31BUndefining a Gas History Point ................................................................................... 7-175
7.4.4 32BLiquid Meter History Configuration Wizard ................................................................. 7-175
7.4.5 33BUndefining a Liquid History Point ................................................................................ 7-183
7.4.6 34BConfiguring History for EFM Reporting ....................................................................... 7-185
7.4.7 35BOrifice EFM History Points .......................................................................................... 7-185
ROCLINK 800 Configuration Software User Manual (for ROC800L)
7.4.8 36BTurbine EFM History Points ......................................................................................... 7-186
7.5 5BOpcode Table ............................................................................................................................. 7-187
7.6 6BModbus Communications ........................................................................................................... 7-188
7.6.1 37BModbus Configuration .................................................................................................. 7-189
7.6.2 38BModbus Conversion Codes ......................................................................................... 7-207
7.6.3 39BModbus Events and Alarms ......................................................................................... 7-213
7.7 7BTransaction History .................................................................................................................... 7-218
7.7.1 40BConfiguring Transaction History .................................................................................. 7-220
7.7.2 41BLogging Transaction History ........................................................................................ 7-223
7.7.3 42BClearing Transaction History ....................................................................................... 7-224
Chapter 8 – The Gas Meters Menu 8-1
8.1 Setup .............................................................................................................................................. 8-1
8.1.1 Station Configuration ....................................................................................................... 8-2
8.1.2 Gas Meters Setup Configuration ................................................................................... 8-13
8.2 Gas Meters Calibration Basics ..................................................................................................... 8-26
8.2.1 Verifying an Input ........................................................................................................... 8-28
8.2.2 Calibrating an Input Example ......................................................................................... 8-32
8.2.3 Zero Shift/Offset/RTD Bias ............................................................................................ 8-40
8.3 Gas Meters Values ....................................................................................................................... 8-45
8.3.1 Gas Meters Values: Values Tab .................................................................................... 8-45
8.3.2 Gas Meters Values: Factors Tab ................................................................................... 8-46
8.4 Plate Change ............................................................................................................................... 8-47
Chapter 9 – The Liquid Meters Menu 9-1
9.1 Overview ........................................................................................................................................ 9-2
9.1.1 Software Components ..................................................................................................... 9-4
9.2 Liquids Meters Menu ...................................................................................................................... 9-5
9.2.1 Preferences ...................................................................................................................... 9-5
9.2.2 Product ........................................................................................................................... 9-10
9.2.3 Density Interface ............................................................................................................ 9-16
9.2.4 Station ............................................................................................................................ 9-29
9.2.5 Meter .............................................................................................................................. 9-41
9.3 Batching (Batching_800L) ............................................................................................................ 9-77
9.3.1 Station Batch Configuration ........................................................................................... 9-79
9.3.2 Station Current Batch ..................................................................................................... 9-94
9.3.3 Station Batch History ..................................................................................................... 9-99
9.3.4 Meter Current Batch ..................................................................................................... 9-106
9.3.5 Meter Batch History ..................................................................................................... 9-112
9.4 Batch Queuing (BatchQueue_800L) .......................................................................................... 9-121
9.4.1 Default Batch Queue Configuration ............................................................................. 9-123
9.4.2 Batch Queue Configuration ......................................................................................... 9-124
9.4.3 Batch Queue - Queue Control Tab .............................................................................. 9-133
9.5 Proving (Proving_800L) ............................................................................................................. 9-135
9.5.1 Prover Configuration .................................................................................................... 9-136
9.5.2 Prover Overview .......................................................................................................... 9-158
9.5.3 Trial Details .................................................................................................................. 9-167
9.6 Reporting and Printing (Reporting_800L) .................................................................................. 9-171
9.6.1 Generating Reports ...................................................................................................... 9-173
9.7 Creating a Report (Tutorial) ....................................................................................................... 9-186
9.7.1 Step 1: Create New Display ......................................................................................... 9-186
9.7.2 Step 2: Labels and Captions ........................................................................................ 9-187
9.7.3 Step 3: Aligning Labels ................................................................................................ 9-189
9.7.4 Step 4: Adding the Start and End Time for a Batch ..................................................... 9-190
9.7.5 Step 5: Adding Meter Data to the Report .................................................................... 9-194
9.7.6 Step 6: Adding the Actual Meter Data on the Report .................................................. 9-197
ROCLINK 800 Configuration Software User Manual (for ROC800L)
9.7.7 Step 7: Saving the Report ........................................................................................... 9-200
9.8 Using the Reports User Program .............................................................................................. 9-201
9.8.1 Loading the Report into the Display Administrator ..................................................... 9-201
9.8.2 Configuring the Report ................................................................................................ 9-205
9.8.3 Reading the Report File From Device ........................................................................ 9-212
Chapter 10 – The Utilities Menu 10-1
10.1 Update Firmware ......................................................................................................................... 10-2
10.1.1 CPU Firmware Tab ....................................................................................................... 10-2
10.1.2 Additional Update Firmware Tabs ................................................................................ 10-5
10.2 License Key Administrator .......................................................................................................... 10-6
10.2.1 Managing Licenses ....................................................................................................... 10-7
10.3 Converting EFM Report Files ...................................................................................................... 10-9
10.3.1 Flow-Cal (.CFX) Conversions ..................................................................................... 10-12
10.3.2 PGAS Conversions ..................................................................................................... 10-12
10.4 User Program Administrator ...................................................................................................... 10-21
10.4.1 Downloading a User Program ..................................................................................... 10-23
10.4.2 MPU Loading Threshold ............................................................................................. 10-25
10.5 ROCLINK 800 Security ............................................................................................................. 10-26
10.5.1 Defining Access .......................................................................................................... 10-27
10.6 Analog Input (AI) Calibration Values ......................................................................................... 10-31
10.7 RTD Input Calibration Values .................................................................................................... 10-32
10.8 MVS Input Calibration Values ................................................................................................... 10-34
10.9 FST Editor ................................................................................................................................. 10-35
10.10 Keypad Display Editor ............................................................................................................... 10-35
10.10.1 Creating a Keypad Display File................................................................................... 10-36
10.10.2 Editing a Keypad Display File ..................................................................................... 10-38
10.11 Custom Display Editor ............................................................................................................... 10-42
10.12 Custom EFM Report Editor ....................................................................................................... 10-42
10.12.1 Viewing Custom EFM Reports .................................................................................... 10-44
10.13 Read File from Device ............................................................................................................... 10-47
10.14 W&M Lock/Unlock ..................................................................................................................... 10-49
10.14.1 Creating a Constant Log ............................................................................................. 10-50
10.14.2 Restoring a Current Configuration .............................................................................. 10-51
10.14.3 Restoring a Previous Configuration ............................................................................ 10-51
10.15 Communications Monitor .......................................................................................................... 10-51
Chapter 11 – The Tools Menu 11-1
11.1 Options ........................................................................................................................................ 11-1
Chapter 12 – The Windows Menu 12-1
12.1 Cascade ...................................................................................................................................... 12-1
12.2 Tile ............................................................................................................................................... 12-2
12.3 Active View .................................................................................................................................. 12-3
Chapter 13 – The Help Menu 13-1
13.1 Help Topics ................................................................................................................................. 13-1
13.2 About ROCLINK 800 ................................................................................................................... 13-2
Appendix A – Glossary A-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Appendix B – The Display Editor B-1
B.1 Creating a New Custom Display ................................................................................................... B-2
B.2 Adding Custom Display Objects ................................................................................................... B-6
B.3 Managing Custom Display Objects ............................................................................................. B-20
B.4 Adding an Expression to an Object ............................................................................................. B-23
B.5 Editing a Custom Display from a File .......................................................................................... B-25
Index I-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Chapter 1 – Introduction

In This Chapter
1.1 ROCLINK 800 Software Basics ............................................................... 1-1
1.2 Computer Requirements ......................................................................... 1-2
1.3 Contacting Technical Support ................................................................. 1-2
1.4 Software Installation ................................................................................ 1-3
1.4.1 Installing ROCLINK 800 under Microsoft Windows 10,
Windows 8 or Windows 7 ........................................................... 1-3
1.4.2 Un-installing ROCLINK 800 ....................................................... 1-25
1.5 Starting ROCLINK 800 Software ........................................................... 1-25
1.5.1 Logging On ................................................................................. 1-25
1.6 User Interface Basics ............................................................................ 1-26
1.6.1 The ROC800-Series Dynamic Interface .................................... 1-28
1.6.2 Standard Buttons ....................................................................... 1-29
1.6.3 Toolbar Buttons .......................................................................... 1-30
1.6.4 Configuration Tree Menu ........................................................... 1-31
1.6.5 Keystrokes ................................................................................. 1-32
1.6.6 Help System ............................................................................... 1-33
1.6.7 Basic Navigation ........................................................................ 1-34
1.6.8 Text Boxes ................................................................................. 1-35
This chapter describes the ROCLINK™ 800 Configuration software (ROCLINK 800) you use to configure and monitor ROC800L Remote Operations Controllers (ROCs) and the dynamic user interface.

1.1 ROCLINK 800 Software Basics

ROCLINK 800 Configuration software enables you to monitor, configure, and calibrate Remote Operations Controllers (ROCs). Remote Automation Solutions provides the software and user documentation on a CD-ROM.
ROCLINK 800 is designed for ease of use. Drop-down menus simplify accessing the functions provided by the software. Dialog boxes and drop-
down list boxes (▼) help to direct selections and data entry. You can
perform actions with the keyboard or a pointing device, such as a mouse. Refer to User Interface Basics (located in this chapter) for a description of the user interface.
You access help screens either from the Help menu or in a context­sensitive fashion pressing the F1 key when your cursor is in a field. This feature makes it easy to access on-line information for any ROCLINK 800 topic.
You can build custom displays for the ROC that combine both graphic and dynamic data elements, and then use these displays to monitor the operation of the ROC either locally or remotely.
The software also provides multiple levels of security for controlling access to ROCLINK 800 functions, as well as the ROC database.
Revised September-2020 Introduction 1-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)

1.2 Computer Requirements

ROCLINK 800 works on most compatible personal computers (PCs) running Windows® operating systems. The PC can be a desktop or a portable computer, but must meet the following minimum require ment s:
Pentium-class processor (233 MHz or greater recommended). DVD-ROM drive. Windows 7 (32-bit and 64-bit). Windows 8 (32-bit and 64-bit). Windows 10 (32-bit and 64-bit). Windows Server 2012 64 MB of RAM (random access memory). SVGA color monitor, 800 by 600 pixels, small fonts. 105 MB of available hard disk space depending on operating system
and revision level.
EIA-232 (RS-232) serial connection or USB-to-serial adaptor, a
TCP/IP connection, or a dial-up modem connection.

1.3 Contacting Technical Support

For technical support, please contact your local sales representative or contact Remote Automation Solutions directly.
Emerson Automation Solutions
Remote Automation Solutions Marshalltown, IA 50158 USA Houston, TX 77065 USA Pickering, North Yorkshire UK Y018 7JA
Website: http://www.emersonprocess.com/remote/ Technical Support Website:
http://www2.emersonprocess.com/en­US/brands/remote/systems_and_software/supportnet/support_contacts/ Pages/support_contacts.aspx
Toll Free: (US and Canada) 800.537.9313 Hours: 24x5 during normal business days SupportNet Login:
www3.emersonprocess.com/remote/support/v2/login.html
1-2 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)

1.4 Software Installation

Note: The device requires version 1.88 or later of ROCLINK 800. When
To install ROCLINK 800:
1. Extract the .zip file to the local hard drive (for example, in the
2. Double-click the setup.exe file if the installation Wizard does not
3. Click Next in the ROCLINK 800 Welcome screen. Read the License
using the Microsoft Windows 8 or Windows 7 operating system, refer to Installing ROCLINK 800 under Microsoft Windows 10, Windows 8 or Windows 7 (located in this chapter).
C:\TEMP\directory) or place the DVD-ROM into the drive.
automatically launch. The installation Wizard screen appears.
Agreement and click YES to accept it. Enter your Name and Company name, and click Next.
The program installs the software in the default recommended directory C:\Program Files\ROCLINK800 or C:\Program Files (x86) \ROCLINK800. Select an alternative destination folder if you want to install the software in a folder other than the default.
4. Follow the setup installation directions.
5. Click the Finish button in the Wizard Complete screen. Note: You may need to restart your PC to complete the installation.
1.4.1 Installing ROCLINK 800 under Microsoft Windows 10, Windows 8 or Windows 7
To install or upgrade ROCLINK 800 on the Microsoft Windows 10, Windows 8 or Windows 7 platform, you must temporarily disable User Account Control before performing the installation and change your PC’s Regional Settings.
Disabling User Account Control ensures that all files copy and are not limited by Windows’ security enhancements. Refer to Disabling User
Account Control (Windows 10), Disabling User Account Control (Windows 8) and Disabling User Account Control (Windows7) (located in
this chapter). Changing your PC’s Region Settings prevents you from potentially
encountering configuration file errors. Refer to Changing Region Settings
(Windows 10), Changing Region Settings (Windows 8) and Changing Region Settings (Windows 7) (located in this chapter).
Revised September-2020 Introduction 1-3
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Disabling User Account Control (Windows 10)
Note: User Account Control must remain disabled in order to run
ROCLINK 800.
To disable User Account Control:
1. Right-click the Start menu and select Search from the pop-up menu.
Figure 1-1. Pop-Up Menu
2. Type UAC into the Search field.
1-4 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-2. Search
3. Click Change User Account Control settings in the results list.
4. Move the User Account Control slider to Never Notify.
Revised September-2020 Introduction 1-5
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-3. User Account Control Settings (Windows 10)
5. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change.
Click Yes (and enter Administrator password if necessary) if Windows asks if you want to allow the changes.
6. Reboot the computer for your changes to take effect.
7. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
Disabling User Account Control (Windows 8)
Note: User Account Control must remain disabled in order to run
ROCLINK 800.
To disable User Account Control:
1. Select Search and type UAC into the Search field.
1-6 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
.
Figure 1-4. Search
2. Select Settings and click Change User Account Control settings.
Figure 1-5. Settings – Results for “uac
3. Move the User Account Control slider to Never Notify.
Revised September-2020 Introduction 1-7
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-6. User Account Control Settings (Windows 8)
4. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change.
Click Yes (and enter Administrator password if necessary) if Windows asks if you want to allow the changes.
5. Reboot the computer for your changes to take effect.
6. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
1-8 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Disabling User Account Control (Windows 7)
Note: User Account Control must remain disabled in order to run
ROCLINK 800.
To disable User Account Control:
1. Select Start and type MSCONFIG in the Search field.
2. Click the program file msconfig.exe. The System Configuration
screen displays.
Figure 1-7. System Configuration
3. Click the Tools tab.
Figure 1-8. Change UAC Settings
4. Select Change UAC Settings.
Revised September-2020 Introduction 1-9
ROCLINK 800 Configuration Software User Manual (for ROC800L)
5. Click Launch. The User Account Control Settings window displays.
Figure 1-9. User Account Control Settings (Windows 7)
6. Move the User Account Control slider to Never Notify.
7. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change. Click
Yes (and enter the Administrator password if necessary) if Windows asks if you want to allow the changes.
.
8. Reboot the computer to apply the changes.
9. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
Changing Region Settings (Windows 10)
To avoid potential error when opening configuration files, we recommend that you change your PC’s location to United States.
To change your PC’s location:
1-10 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
1. Right-click the Start menu and select Search from the pop-up menu.
Figure 1-10. Pop-Up Menu
Revised September-2020 Introduction 1-11
ROCLINK 800 Configuration Software User Manual (for ROC800L)
2. Type region into the search field.
Figure 1-11. Search
3. Click Region in the results list.
4. Select the Location tab.
5. Change or verify that the current location is set to United States.
1-12 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-12. Home Location
6. Click OK button to save changes and close the Region window.
Changing Region Settings (Windows 8)
To avoid potential error when opening configuration files, we recommend that you change your PC’s location to United States.
To change your PC’s location:
1. Select Search and type region into search field.
Revised September-2020 Introduction 1-13
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-13. Search
2. Select Settings and click Region in the results list.
Figure 1-14. Search Results
3. Set the Location tab.
4. Change or verify that the current location is set to United States.
1-14 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-15. Home Location
5. Click OK to save changes and close the Region window.
Changing Region Settings (Windows 7)
To avoid potential errors when opening configuration files, we recommend that you change your PC’s location to United States.
To change your PC’s location:
1. Select Start > Control Panel. The Control Panel displays:
Revised September-2020 Introduction 1-15
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-16. Control Panel
2. Select Clock, Language, and Region. The Clock, Language, and
Region screen displays:
Figure 1-17. Clock, Language, and Region
1-16 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3. Click Change location. The Region and Language screen displays
showing the Location tab.
Figure 1-18. Region and Language
4. Change or verify that the current location is set to United States.
5. Click OK to save your changes and close the Region and Language
window.
Enabling User Account Control (Windows 10)
Note: User Account Control must remain disabled in order to run
ROCLINK800.
To enable User Account Control:
Revised September-2020 Introduction 1-17
ROCLINK 800 Configuration Software User Manual (for ROC800L)
1. Right-click the Start menu and select Search and from the pop-menu.
Figure 1-19. Pop-Up Menu
2. Type UAC into the search field.
1-18 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-20. Search
3. Click Change User Account Control settings in the results list.
4. Move the User Account Control slider to the default position.
Revised September-2020 Introduction 1-19
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 1-21. User Account Control Settings
5. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change.
Click Yes (and enter Administrator password if necessary) if Windows asks if you want to allow the changes.
6. Reboot the computer for your changes to take effect.
7. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
Enabling User Account Control (Windows 8)
Note: User Account Control must remain disabled in order to run
ROCLINK800.
To enable User Account Control:
1-20 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
1. Select Search and type UAC into the search field.
Figure 1-22. Search
2. Select Settings and click Change User Account Control settings.
Figure 1-23. Settings, Results for “uac”
Revised September-2020 Introduction 1-21
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3. Move the User Account Control slider to the default position.
Figure 1-24. User Account Control Settings
4. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change. Click
Yes (and enter the Administrator password if necessary) if Windows asks if you want to allow the changes.
5. Reboot the computer for your changes to take effect.
6. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
1-22 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Enabling User Account Control (Windows 7)
Note: User Account Control must remain disabled in order to run
ROCLINK 800.
To enable User Account Control:
1. Select Start and type MSCONFIG in the Search field.
2. Click the program msconfig.exe. The System Configuration screen
displays:
Figure 1-25. System Configuration
3. Click the Tools tabs.
Figure 1-26. Change UAC Settings
Revised September-2020 Introduction 1-23
ROCLINK 800 Configuration Software User Manual (for ROC800L)
4. Select Change UAC Settings.
5. Click Launch. The User Account Control Settings screen displays.
Figure 1-27. User Account Control Settings
6. Move the User Account Control slider to the default position.
7. Click OK to save your changes and close the User Account Control
Settings window.
Note: You must have Administrator rights to make this change. Click
Yes (and enter the Administrator password if necessary) if Windows asks if you want to allow the changes.
.
8. Reboot the computer to apply your changes.
9. Start ROCLINK 800. Refer to Starting ROCLINK 800 Software
(located in this chapter).
1-24 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
1.4.2 Un-installing ROCLINK 800
To remove ROCLINK 800 from your PC:
1. Click the Windows Start button.
2. Select Settings > Control Panel.
3. Double-click the Add/Remove Programs icon.
4. Select ROCLINK 800.
5. Click Add/Remove.
6. Follow the instructions.

1.5 Starting ROCLINK 800 Software

To use ROCLINK 800 to configure a hardware device, you must have the ROC or properly connected to power. Refer to the appropriate hardware instruction manual. You must also connect the PC to the devices Local Operator Interface (LOI), Ethernet, serial, or modem port.
To run ROCLINK 800, perform one of the following:
Double-click the Desktop Shortcut. Select Start > Programs > ROCLINK 800 > ROCLINK 800.
The software loads and initializes.
Note: You can only run one version of ROCLINK 800 at a time.
1.5.1 Logging On
To log on to ROCLINK 800:
1. Connect the ROC to the Local Operator Interface (LOI – Local Port)
and launch ROCLINK 800.
Figure 1-28. Logon
Revised September-2020 Introduction 1-25
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Typically, your initials are your User ID. If User IDs have not yet been assigned, try using the default User ID of LOI. You assign User IDs using the ROC > Security features of ROCLINK 800.
1. Type your assigned 4-digit Password and click OK.
For added security, the software displays an asterisk for each number that you type. If passwords have not yet been assigned, use the default password of 1000 (valid with default User ID of LOI).
2. ROCLINK 800 validates the User ID and Password you enter against
a predefined list.
If the log on is not valid, a dialog box appears. Click OK and re-enter
the User ID and Password. You can repeat the procedure as many times as needed until you successfully enter a valid User ID and Password. If the log on is valid, ROCLINK 800 displays the Device Directory screen.
To exit from the log on screen, press Esc or click Cancel. This closes ROCLINK 800 and returns you to the point where you started ROCLINK
800.

1.6 User Interface Basics

You interact with ROCLINK 800 using various displays on the computer monitor, keyboard, and pointing device.
The major components of ROCLINK 800 user interface are:
Graphical interface.Menu bar and menus. Toolbar. Function screens. Dialog boxes. Help system, including the Status bar and message boxes. Device Directory or Configuration Tree menu.
ROCLINK 800 employs a Graphical User Interface (GUI) with a standard Windows menu structure. After logging on to ROCLINK 800, available functions display in a menu bar with drop-down menus:
1-26 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Menu
Options
File
New, Open, Download, Close, Save Configuratio n, Print Configuration, Print, Print Setup, [List of recent files], Exit
View
Directory, EFM Report, Cal i b ration Report, History, Alarms, Toolbar, Refresh User Program Tree
ROC
Direct Connect, Connect, Disconnect, Collect Data, Clock,
available when you select a connection option (COM1,
specific communications connection.
Configure
I/O, Control, History Segments, History Points, Opcode Table, MODBUS
Meter
Setup, Calibration, Values, Plate Change
Figure 1-29. ROCLINK 800 Menu
A Status Line at the bottom left of the display contains pertinent information about the highlighted item, such as a menu option or a parameter.
Buttons display dialog boxes for further configuration details or perform a desired action, such as the Update button. To activate the button:
1. Click the button with a left click of the mouse.
2. When a button is active, press Enter or a function key.
Dialog boxes are areas that "pop up" inside the current screen to allow further selections or enter values. Dialog boxes also provide messages or more detailed information.
The menu structure lists choices from which you can set the desired function. Once a function is selected, the screen or dialog box for that function displays. This screen or dialog box provides the requested information and lets you enter the applicable configuration data.
Table 1-1. Menu Listing for ROCLINK 800 (ROC800L)
Events, Weights & Measure Events, Display, I/O Monitor,
Security, Comm Ports, Information, Flags Note: The Direct Connect menu option is the default; it
directs ROCLINK 800 to connect with any available valid connection. The Connect menu option becomes
Revised September-2020 Introduction 1-27
COM2, Ethernet, etc.) from the Device Root. By clicking Connect, you tell ROCLINK 800 to use that
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Menu
Options
Utilities
Update Firmware, License Key Administrator, Con vert EFM
Lock/Unlock, Communications Monitor
User
(Located under the Configuration Tree) Liquid Ca lcs_800L, Reporting_800L
Tools
Options
Window
Cascade, Tile, Device Directory, [List of open windows]
Help
Help Topics, About ROCLINK 800
File, User Program Administrator, ROCLINK 800 Security, AI Calibration Values, RTD Calibration Values, MVS Calibration Values, FST Editor, Keypad Display Editor, Custom Display Editor, Custom EFM Report Editor, Read File From Device,
Programs
Batching_800L, BatchQueue_800L, Prov i ng_800L,
1.6.1 The ROC800-Series Dynamic Interface
You can navigate the ROC options either by using the ROCLINK menu structure or by clicking on the ROC graphical dynamic interface and selecting a tab or button. The dynamic interface display shows the current settings of the point including alarms and integrity.
The system displays a white line around objects that are links when you hover your cursor over them. A link descriptor displays indicating the links definition.
1-28 Introduction Revised September-2020
Figure 1-30. ROC800L User Interface
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Button
Description
Minimizes and hides windows.
Maximizes the size of the windows to fit in the screen
Restore window to original size.
Closes a window.
Expands options listed in the Device Directory or
Hides options listed in the Device Directory or
Prints the active display.
Click to Browse for a selection.
Updates contents of the active window from the device.
Copies the contents of window to Clipboard.
Pastes the contents of the Clipboard to the active
Applies changes on the active window to the device box appears if there are unsaved changes.
Cancels without saving changes and closes the act i ve
Applies changes on the active window to the device. Saves the contents of the active window to the
Closes the active window. A Confirm Save dialog bo x appears if there are unsaved changes.
Deletes the current selection.
Starts automatic device polling.
Stops automatic device polling.
1.6.2 Standard Buttons
Several buttons appear on the majority of ROCLINK 800 screens.
area.
Configuration Tree Menu.
Configuration Tree Menu.
window.
and close the active window. A Confirm Save dial og
window.
Clicking Apply does not close the active window.
Revised September-2020 Introduction 1-29
configuration file.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Note
1.6.3 Toolbar Buttons
The following buttons appear in the ROCLINK 800 toolbar.
Figure 1-31. ROCLINK 800 Toolbar
ROCLINK 800 grays out a button if it is not applicable to the current screen.
Button Description
Creates a new configuration file. You specify available configuration parameters using menu selection s. Configure the file as if you were connected to the device. Functions requiring a live connection are unavailable in this mode.
Opens an existing configuration file. You create confi gurat ion files using the New Device or Save Configuration functions.
Saves the current configuration of the connect ed device to a disk file.
Deletes currently selected text and place it in the Clipboard. Note: Currently not available.
Copies currently selected text and places it in the Clipboard. Note: Currently not available.
Pastes text currently in the Clipboard at the cursor’s current location.
: Currently not available.
Prints the configuration file. Note: Currently not available.
Connects to a device locally using the (LOI) Local Operator Interface port.
Disconnects from a device.
Displays the first of two .DSP files loaded on the device.
Note: Not currently functional on the ROC800L platform.
Displays the second of two .DSP files loaded on the device.
Note: Not currently functional on the ROC800L platform.
Displays the Analog Input (AI) screen.
Displays the Discrete Input (DI) screen.
Displays the Pulse Input (PI) screen.
1-30 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Button Description
Displays the Analog Output (AO) screen.
Displays the Discrete Output (DO) screen.
Displays the Comm Port screen.
Displays the Flags screen.
Displays the Clock screen.
Displays the Meter Setup screen.
Displays the Plate Change screen.
Displays the PID Loop screen.
Opens the Function Sequence Table (FST) Editor.
Displays an About ROCLINK 800 screen providing program information, version, creation date, and copyright for ROCLINK
800. Launches the ROCLINK 800 on-line help system.
1.6.4 Configuration Tree Menu
When you open a configuration file or go on-line with a ROC, the Configuration Tree appears on the left-hand side of the screen. The tree hierarchically displays the parts of a configuration (such as I/O, Meter Runs, and History) that you can change.
Revised September-2020 Introduction 1-31
ROCLINK 800 Configuration Software User Manual (for ROC800L)
From the Configuration Tree, you may change the configuration or monitor current operations. Once you are in the Configuration Tree menu, you can use the + and – symbols to display or hide various options.
Double-click the desired function in the Configuration Tree to display the associated screen. Double-clicking an icon is the same as selecting the option in the menu bar or clicking a Toolbar button.
If this is the first time that you have connected to the ROC, refer to Setting the Clock (located in Chapter 6).
1.6.5 Keystrokes
If you are using the keyboard, you may use the Alt key plus one or more letters to access menus. Windows underlines the appropriate letter in the menus. For example, to access the Open File dialog box, press Alt + F and press O. You may also use the Left Arrow () and Right Arrow () keys to highlight a menu bar item (the help Status Line at the bottom of the screen provides a description of the menu) and press the letter.
With a menu displayed, you can highlight the desired item by using the Down Arrow () and Up Arrow () keys or the mouse. Once you have highlighted an item, press Enter to activate the function.
Figure 1-32. Configuration Tree Menu
To leave a menu or submenu, press Esc. You can then select another menu. You can also access another menu using and .
The text scrolling keys are Page Up and Page Down.
1-32 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Option
Description
Contents
Presents a list of Help Topics that display based on task-
Configuration > Scale Values tab.
Index
Locates specific Help Topics. The Index lists each f i el d by the tab or screen in which the field appears.
To use the keyboard in configuration screens and dialog boxes, press Tab to move in a predetermined sequence from one parameter field or button to the next. The selected field or button becomes highlighted. Fields unavailable for changes are automatically skipped.
When you Tab to the last field or button in the screen or dialog box, pressing Tab again jumps back to the first field or button. To go back to a previous field or button, press Shift + Tab.
In an option field, the currently selected option is highlighted. To select one of the other options, use or to highlight the desired option and then press Enter.
In a field that requires a text or numerical entry, type in the required characters or numbers from the keyboard. Use Backspace or Delete to erase unwanted characters. Use  and  to move the cursor one character at a time and Home and End to place the cursor at the beginning and end of the field, respectively.
Other keys or key combinations include:
F1 – Launches ROCLINK 800 on-line help. Esc – Cancels the current activity, closes the screen, and returns you
to the last-used place in the menu structure, screen, or other place from which the dialog box originated. If a menu is active, Esc closes the last-opened menu, taking you up one level in the menu structure. If the menu bar is active, Esc de-selects all menu options. Press Alt or click with the mouse to reactivate the menu bar.
Ctrl + N – Creates a new configuration file. Ctrl + O – Opens a configuration file.
Ctrl + S – Saves the current configuration file.
1.6.6 Help System
The Help menu provides detailed on-screen information about getting started with ROCLINK 800 and performing keyboard operations, a list of the Help topics, and the ROCLINK 800 version.
To display context sensitive help on a field, a parameter, or a button, press F1 while the field, parameter, or button is highlighted. A help window appears on the screen.
To view detailed help, select Help > Help Topics from the menu bar.
Revised September-2020 Introduction 1-33
Table 1-2. Help System
oriented situations. Each screen, tab, and field has a help topic associated with it. For example: the MODBUS Scale Values tab is located under Modbus > Modbus
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Search
Activates a search function on a specific word.
Back
Returns to the last topic that you viewed.
Print
Sends the currently displayed topic to the PC’s default printer.
See Also
Displays topics related to the currently selected topic.
<< / >>
Navigates forward (>>) or backwards (<<) through the help the order of the topics as displayed in the Contents t ab.
system on a per topic basis. The Browse Sequence follows
1.6.7 Basic Navigation
When you start the ROCLINK 800, the Device Directory displays. After you connect to a ROC, the Configuration Tree View displays.
Use the + and – symbols to display or hide various options. Double-click a point to display the associated parameter configuration screen. You can also use the menu options and buttons to display the associated parameter configuration screen.
The Status Line at the bottom of the Device Directory and Configuration Tree provides critical information. The left side displays brief information about the device being connected. The right side displays the device status (on-line or off-line) and system time.
TLP Selections
In many locations in ROCLINK 800, you can click the TLP Browse button (a button with three dots) to view the Select TLP dialog. The Select TLP dialog allows you to assign specific inputs and outputs to parameters. ROCLINK 800 uses Point Type (T), Logical Number (L), and Parameter (P) to define point locations.
Figure 1-33. Select TLP Dialog
To use the Select TLP dialog box:
1. Select the Point Type from the list. This opens a list of logical
numbers and parameters that belong to that Point Type.
1-34 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
2. Select the Logical Number. In the configuration screens, the Logical
Number is generally referred to as Point Number or Number.
3. Select the specific Parameter. These are usually called by the same
term as the Tag on the configuration screen. The field at the bottom of the Select TLP dialog displays the numeric
point location of the TLP point or a text abbreviation, depending on the setting in the Tools > Options window.
4. Select the Show All Point Types and Parameters checkbox to view
all points and parameters regardless of their validity. By default, ROCLINK only displays points and parameters that are valid for the current configuration you are performing.
5. Click OK.
Display TLP
Auto Scan Update
Interval
1.6.8 Text Boxes
Displays values on the Select TLP screen as either text or numbers. For example, the TLP for Register 2 of FST 1 could display as either "FST 1,R2" or "96, 0, 3".
Select Tools > Options to set the time interval, in seconds, at which the Auto Scan feature on various screens in ROCLINK 800 polls the ROC. Clicking Auto Scan causes ROCLINK 800 to poll the device automatically, until you click Stop Scan.
Text boxes appear in various places throughout ROCLINK 800. You can enter alphanumeric character (A through Z and 0-9) into text boxes. For example, you can enter name (tag) for a device or a short description for an I/O point.
Revised September-2020 Introduction 1-35
ROCLINK 800 Configuration Software User Manual (for ROC800L)
[This page is intentionally left blank.]
1-36 Introduction Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Chapter 2 – Device Directory and Device Root

In This Chapter
2.1 Device Directory ................................................................................... 2-1
2.1.1 Communication Parameter Setup Screen ................................. 2-2
2.2 Device Root .......................................................................................... 2-4
2.2.1 Backing Up ROCLINK Device D efinitions ................................. 2-5
2.2.2 Adding a Group ......................................................................... 2-5
2.2.3 Deleting a Group ....................................................................... 2-6
2.2.4 Adding a Device ........................................................................ 2-6
2.2.5 Deleting a Device ...................................................................... 2-7
2.2.6 Deleting All Devices .................................................................. 2-7
2.2.7 Renaming a Group or Device .................................................... 2-7
This chapter describes the Device Directory screen and the Device Root, the graphical representation of all devices, which appears on that screen.

2.1 Device Directory

The Device Directory is the first screen that displays after you successfully log onto ROCLINK 800 but before you connect to a device.
Figure 2-1. Device Directory and Device Root
Note: Once you connect to a device, ROCLINK 800 replaces the
Device Directory screen with a device-specific configuration tree screen (see Figure 2-2).
Revised September-2020 Device Directory and Device Root 2-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 2-2. Configuration Tree
You use the Device Directory screen to create and maintain communications setup configurations for a PC running ROCLINK 800. You can uniquely configure the communication ports on the PC to send data to a specified ROC. You may add, delete, or modify these communications setups and establish a tree of groups and devices.
Use the + and – symbols to display or hide various options.
Note: You can only configure a PC’s communications ports from the
Device Directory screen. To re-display the Device Directory screen at any time, select Window > Device Directory or View > Directory.
2.1.1 Communication Parameter Setup Screen
The ROCLINK 800 Communication Parameter Setup screen allows you to change your PC communications port, time-out settings, and other variables ROCLINK 800 uses when establishing a connection to a device.
2-2 Device Directory and Device Root Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
In order for ROCLINK 800 to communicate with a device, ROCLINK 800 must know to which device it is communicating. Each device within a group is given a unique device address.
To set the PC communication parameters:
1. Right-click the label in the Device Directory that corresponds to the
PC port you want to use.
Figure 2-3. Device Pop-up Menu Tree
2. Select Properties. The ROCLINK 800 Communications Parameters
screen displays.
Revised September-2020 Device Directory and Device Root 2-3
ROCLINK 800 Configuration Software User Manual (for ROC800L)

2.2 Device Root

Figure 2-4. Communication Parameters
3. Configure the ROCLINK 800 communications parameters (refer to
Chapter 3, Communications and Security for a complete discussion of this screen).
4. Click Apply. You are ready to connect to the ROC.
The device root graphically represents the devices and their organizational structure on the Device Directory screen. When you open ROCLINK 800, the device root displays the default device labels. Using the Communication Parameters screen, you can modify the communications setup configurations for these devices or add new devices with new configurations. Each icon on the device root represents a different type of communications connection.
2-4 Device Directory and Device Root Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 2-5. Device Root
The default device labels, which correspond to available communication ports, include:
 COM1 Device.  COM2 Device.  Modem Device.  Ethernet Device.  New Group1 > New Device1.  New Group1 > New Device2.
You may add, delete, or modify the communication configurations for each of these devices. You can also define device groups.
2.2.1 Backing Up ROCLINK Device Definitions
After you configure your device settings, we strongly recommend that you create a back-up file of those settings. ROCLINK 800 stores these values in the file ROC_USER.mdb. Use Windows Explorer to find the ROC_USER.mdb file, then copy the file and store it in a safe place. This backup file enables you to restore your settings in case they ever become corrupted.
You can configure devices on-line communications using the Local Operator Interface (LOI) Port (also known as the "local port") or a communication port, such as a modem.
For differentiation, each ROC has a Tag and a unique Device Address which you define on the ROCLINK 800 Communications Parameters screen (see Figure 2-4). The Device Address must be different from any other host system that may access the network.
2.2.2 Adding a Group
You can organize devices into groups. Typically, groups contain devices in the same geographical area or with another common feature. When
Revised September-2020 Device Directory and Device Root 2-5
ROCLINK 800 Configuration Software User Manual (for ROC800L)
you double-click a group icon, ROCLINK 800 displays all devices or subgroups associated with that group.
To add a new group to the device root directory:
1. Right-click the Device Root icon. A pop-up menu displays.
2. Select Add a Group. ROCLINK 800 adds the new group icon to the
device root graphic.
To add a subgroup to an existing group:
1. Right-click the Group icon. A pop-up menu displays.
2. Select Add a Group. ROCLINK 800 adds the new group icon to the
selected group.
2.2.3 Deleting a Group
To delete a group:
1. Right-click a group icon. A pop-up menu displays.
2. Select Delete Group. A Confirm Delete dialog box displays.
3. Click Yes to delete the group and all subordinate groups and devices
in that group.
2.2.4 Adding a Device
To add a new device to the device root:
1. Right-click the device root icon. A pop-up menu displays.
2. Select Add a Device. ROCLINK 800 adds a device icon to the
device root.
3. Configure the new device’s communication parameters (see Chapter
3, Communications and Security).
To add a device to an existing group:
1. Right-click the group icon. A pop-up menu displays.
2. Select Add a Device. ROCLINK 800 adds a device icon in the
selected group.
Figure 2-6. Delete Group
2-6 Device Directory and Device Root Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3. Configure the new device’s communication parameters (see Chapter
3, Communications and Security).
2.2.5 Deleting a Device
To delete a device:
1. Right-click a device icon. A pop-up menu displays.
2. Select Delete Device. A Confirm Delete dialog displays.
3. Click Yes to delete the device.
Figure 2-7. Delete Device
2.2.6 Deleting All Devices
To delete all device communication parameter configurations in the device root directory:
Note: This deletes all ROC units that you currently have configured.
1. Right-click the device root icon. A pop-up menu displays.
2. Select Delete All Devices. A Confirm Delete dialog displays.
Figure 2-8. Delete All Devices
3. Click Yes. ROCLINK 800 deletes all devices in the device root.
2.2.7 Renaming a Group or Device
You can easily replace the ROCLINK 800-provided default group or device names with names you choose. To rename a group or device in the Device directory:
1. Right-click the device or group icon. A pop-up menu displays.
2. Select Rename. Enter a name.
Revised September-2020 Device Directory and Device Root 2-7
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Note: Although your label can be up to 72 characters in length, keep
the label short for easy recognition.
3. Press Enter when finished. ROCLINK 800 adds the new label to the
device or group.
2-8 Device Directory and Device Root Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Chapter 3 – Communications and Security

In This Chapter
3.1 Communications ................................................................................... 3-1
3.2 ROCLINK 800 Communications ........................................................... 3-2
3.2.1 ROCLINK 800 Communicati ons General Tab .......................... 3-2
3.2.2 ROCLINK 800 Communicati ons A dvanced tab ........................ 3-4
3.3 Communication Ports ........................................................................... 3-6
3.4 Configuring Communications Ports ...................................................... 3-7
3.4.1 Configuring TCP/IP Communications on the
Ethernet Port ............................................................................. 3-7
3.4.2 Comm Ports General Tab ......................................................... 3-9
3.4.3 Comm Ports Modem Tab ........................................................ 3-12
3.4.4 Comm Ports SRBX Tab .......................................................... 3-13
3.4.5 Comm Ports Store & Forward Tab .......................................... 3-15
3.4.6 Comm Ports Diagnostics Tab .................................................. 3-15
3.5 Connecting to a ROC .......................................................................... 3-16
3.5.1 Direct Connect ......................................................................... 3-17
3.5.2 Local Port (LOI) ....................................................................... 3-18
3.5.3 Connect to a ROC ................................................................... 3-18
3.5.4 Successful Login ..................................................................... 3-18
3.5.5 Disconnecting from a ROC ...................................................... 3-19
3.6 Troubleshooting Connection Errors .................................................... 3-19
3.6.1 Troubleshooting ROCLINK 800 Communications ................... 3-20
3.6.2 Troubleshooting TCP/IP C onnections ..................................... 3-20
3.7 Security ............................................................................................... 3-21
3.7.1 ROCLINK 800 Security ........................................................... 3-21
3.7.2 Device Security ....................................................................... 3-25

3.1 Communications

This chapter describes how to configure the communication ports on a PC and on a ROC. It also describes how to use the Connect and Direct Connect features in ROCLINK 800 and how to define security to control access to the ROC and ROCLINK 800.
Before you attempt to connect to a ROC, you must configure communication parameters in two places:
 ROCLINK 800 Communications
Configure device communications on the Device Directory screen (Device Directory and Device Root). This sets the PC’s comm ports to communicate with a specific device.
Communication Ports on the ROC
Select ROC > Comm Ports to access the Comm Port screen and configure the ROC communication ports for incoming or outgoing communications. Refer to Section 3.3, Communication Ports.
ROCLINK 800 Configuration Software User Manual (for ROC800L)

3.2 ROCLINK 800 Communications

The Device Directory communication configurations allow ROCLINK 800 to communicate to an individual ROC.
To set the PC communication parameters:
1. Right-click the label in the Device Directory that corresponds to the
PC port you want to use.
2. Select Properties. The ROCLINK 800 Communication Parameters
screen displays.
3. Configure the ROCLINK 800 communications parameters. Refer to
Section 3.3, Communications and Security.
4. Click Apply. You are ready to connect to the ROC.
3.2.1 ROCLINK 800 Communications Gener al Tab
The Device Directory is the first screen that displays after you successfully log onto ROCLINK 800 but before you connect to a device.
To display the ROCLINK 800 Communication Parameters screen, right­click on a device icon in the device root and select Properties. The ROCLINK 800 Communication Parameters screen displays, showing the General tab.
Use the General tab to configure basic communications for the PC running ROCLINK 800.
Figure 3-1. ROCLINK 800 Communications – General tab
3-2 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Note: The default device address is 240.
Device Group
Tag Sets a unique nam e for the ROC. Enter up to 50
alphanumeric characters to identify the ROC.
Connect Click to communicate with the PC using the
parameters configured for this PC’s communications port.
Device Address Sets the address of the specific ROC with which
you desire to communicate. If you are connected to a multi-drop series of devices, enter the Device Address (default is 240) and Device Group of the specific device. The defaul t values for the Device Address and Device Group are 240.
Associates the ROC with a specific group. The default Device Group is 240.
Note: If you connect a PC running ROCLINK 800
directly to the device’s LOI (Local Port), ROCLINK 800 makes a request to Device Group of 240 and Device Address of 240. The Local Port of a device always responds to a request for Address 240 and Group 240, no matter what Device Address and Device Group is configured in the device if the LOI Security is valid.
Host Address Identifies the PC’s host address, which by default is
Address 3. If more than one computer running ROCLINK 800 communicates with a group of devices (either by radio or by other multi-drop communications), you must define unique host address for each device to avoid multiple responses. The host address must also be different from any other host system that may access the communications link.
Use the following host group and host address conventions: 0 and 240 are reserved
Host Group Identifies the PC’s host group, which by default i s
1. When using ROC Protocol, the group address
must match the address defined at the destination
ice in order for communications to properly
dev transmit.
Use the following host group and host address convention: 0 and 240 are reserve
Use Sets the type of connection. Valid values are
Comm Port, Modem, or TCP/IP. Note: If you select TCP/IP, ROCLINK 800 applies
only the Time Out parameter you define on
the Advanced tab. No other parameters defined on that tab apply.
d
Revised September-2020 Communications and Security 3-3
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
PC.
PC Baud Rate
Modem
Phone Number
TCP/IP
Refresh Comm Port
PC Comm Port Sets the comm port on the PC ROCLINK 800 uses
for this setup. The ROC can communicate t hrough any of the PC’s configured comm ports. The default comm port is 1.
Note: This field is available only if you set the
Comm Port option. Before you select this
parameter, check to see which communications ports are assigned in the
Sets the baud rate ROCLINK 800 uses to communicate with the device through a serial port (COM port). For successful communications, t he baud rate you set here must match the baud rate on the PC. The default value is 19200. If you have difficulties communicating to your device, set the baud rate in both the device and the computer to the default baud rate.
Note: This field is available only if you selected
the Comm Port option.
Modem Indicates the modem ROCLINK 800 uses. Click
to list all available modems. Only the modems defined in the Windows Control Panel display. Ensure that the modem you select is properly set up.
Note: This field is available only if you selected
the
Sets the telephone number for the device ROCLINK 800 dials.
Note: This field is available only if you selected
the Modem option.
Override Default TAPI Init String
IP Address Indicates the IP address for the TCP/IP connection.
Port Number Indicates the port for the TCP/IP connection.
List
Indicates that ROCLINK 800 should use an override initialization string configuration. When you select this option, you must provide an override initialization string.
Note: This field is available only if you selected
the Modem option.
Note: This field is available only if you selected
the TCP/IP option.
Note: This field is available only if you selected
the
Click to enable ROCLINK 800 to refresh the listing of displayed comm ports.
Note: This field is available only if you selected
the Comm Port option.
option.
option.
3-4 Communications and Security Revised September-2020
3.2.2 ROCLINK 800 Communications Advanc ed tab
Use the Advanced tab on the ROCLINK 800 Communications Parameters screen to configure advanced communications features.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Figure 3-2. ROCLINK 800 Communications – Advanced tab
Number of Retries Sets the number of times (after the initial attempt)
ROCLINK 800 tries to request data from the specified device before reporting a timeout error. Valid values are between 0 and 25. The default is
3. Use the Time Out parameter to adjust the amount of time between retries.
Note: This parameter does not apply to the dial-
up modem, which only tries to establish a connection once.
Tx Delay Sets, in seconds, the amount of time ROCLINK
800 waits before transmitting data. This delay enables the request-to-send (RTS) line for the amount of delay specified before transmitting dat a. The default is 0.05.
Typically, this value allows a radio to fully stabilize before the system applies data for transmission.
For EIA-232 (RS-232) and dial-up modem
communications, set this value (and the value in the Key Off Delay field) to 0 (zero) or the default of 0.05 seconds.
For EIA-485 (RS-485) and radio
communications, set this value to 0.1.
Note: These variables may change, based on
your situation. These are general values that you need to assess for each circumstance.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Key Off Delay
Time Out Sets, in seconds, the actual amount of time that
ROCLINK 800 waits to receive a valid message after it sends a request to a device. The default is
3. Modem users typically accept the default value. Do not set this field to 0 (zero). This prevents
ROCLINK 800 from timing out, and quickly exhausts the Retries.
Note: If you select TCP/IP as the communications
method on the General tab, ROCLINK 800 applies only the Time Out parameter. No other parameters defined on that tab apply.
Sets, in seconds, the amount of time ROCLINK 800 waits after transmitting a message before turning off the ready to send (RTS) signal. The default is 0. You can change this value to optimize communications.
The default value should be sufficient for dial-up modems and EIA-232 (RS-232) connections. For radios, a value of 0.01 may be appropriate.
Host CRC Check Indicates whether ROCLINK 800 uses cyclical
redundancy checking. The default value is
Enabled.

3.3 Communication Ports

In addition to configuring the communications ports on the PC, you also configure the device-specific communication parameters.
While in a configuration and on-line with an ROC, select ROC > Comm Ports to display the Comm Port screen. Each communications port has a unique set of parameters on the screen.
Use the Comm Ports screen to set up the communications ports that are available for incoming and outgoing communications with the ROC.
Note: Use the Device Directory to define PC communication ports.
The communication ports located on the ROC provide a data link to ROCLINK 800, other devices, and host systems. The type of module enables the following communications:
EIA-232 (RS-232) serial communications. EIA-422 (RS-422) serial communications. EIA-485 (RS-485) multi-point serial communications. Dial-up modem communications. TCP/IP communications.
3-6 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Port
Port Location
Default Tag
Function/Type
1
CPU RJ-45 (top)
Local Port
LOI / RS-232D
2
CPU RJ-45 (middle)
COMM1
Ethernet
3
CPU 5-pin (bottom)
COMM2
Serial / EIA-232 (RS-232)
4
Module Slot 1
COMM3
EIA-232 (RS-232), EIA-485 (RS-485), or Modem
5
Module Slot 2
COMM4
EIA-232 (RS-232), EIA-485 (RS-485), or Modem
6
Module Slot 3
COMM5
EIA-232 (RS-232), EIA-485 (RS-485), or Modem
Note: You also access the Comm Port screen by selecting ROC >
Table 3-1. Communication Ports for the ROC800-Series

3.4 Configuring Communications Ports

The ROC comm. ports provide a link to computers, such as one running ROCLINK 800 or a host computer.
Select ROC > Comm Ports to set up communication ports available for the ROC.
The SRBX or RBX (Spontaneous Report-by-Exception) alarming feature is available for serial communication ports. It is not supported on the Ethernet port. This feature allows the device to call in to a host computer when a configured alarm occurs. To prevent "nuisance" alarms from being reported to the host, configure the parameters correctly. If you wish to configure dial-up RBX, a modem must be present and appropriately configured.
When using RBX Alarming, you must ensure that the alarms are enabled and configured for each point you desire to monitor. Configure the alarm parameters so that an alarm occurs only when desired. Configure the parameters on the Alarms tabs of the I/O configuration screens.
Once configured, save the configuration of all communications ports to programmable ROM using ROC > Flags > Flash Memory Save
Configuration.
Comm Ports from the ROCLINK 800 menu bar and then
selecting the appropriate comm port from the drop-down menu or by selecting the Comm Ports icon from the menu bar.
3.4.1 Configuring TCP/IP Communications on t he Ethernet Port
Use TCP/IP connections through the Ethernet port for DS800, Modbus® RTU encapsulated in TCP/IP, Modbus TCP/IP, or ROC Plus Protocol communications.
To configure TCP/IP communications:
1. Connect to the ROC.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
2. If using ROC Plus, Modbus RTU Encapsulated in TCP/IP, or
Modbus TCP/IP, set the parameters on the ROC > Information > Internet tab.
3. If using DS800, set the parameters and enable the DS800
communications on the Configure > Control > DS800 screen.
4. If using Modbus RTU Encapsulated using TCP/IP or Modbus
TCP/IP, sets the communications port and configure the parameters on the Configure > Modbus > Configuration screen.
Note: The parameters on the General, Modem, SRBX, and Store and
Forward Tabs of the ROC > Comm Ports screen do not apply to the Ethernet port.
The ROC > Comm Ports Diagnostics tab displays the communication statistics available for all Modbus and ROC Plus Protocol communications transmitted using TCP/IP connections. Refer to the discussion of the Comm Ports Diagnostics Tab.
The Ethernet port supports up to six ROC Plus connections, six Modbus slave connections, and one Modbus Master connection all at the same time. The number of active TCP/IP connections displays on the Active Connections field on the ROC > Information > Internet tab.
SRBX messaging or firmware updates cannot be transmitted over a TCP/IP connection.
Once a ROC Plus Protocol, Modbus RTU encapsulated in TCP/IP, or Modbus TCP/IP connection is made, the communication session can be closed by a timeout. Three timeouts that can close a connection are executed as follows:
A security timeout is started after a valid login. If a valid ROC Plus
Protocol message is not received within 60 minutes, the connection closes. The timeout is reset after each valid message.
An inactivity timer for each TCP/IP connection has been added in
addition to the security timeout. The ROC Information > Internet > Inactivity Time field sets this parameter in seconds. A value of 0 disables the timer. If a valid ROC Plus Protocol message is not received within the Inactivity Time, the connection closes.
Each connection will be kept alive by periodic transmissions of
messages (probes). If the other side of the connection fails to respond to ten repetitive probes, the connection will be considered broken and the connection closes. The amount of idle time (in seconds) before the first probe is configurable is set in the ROC > Information > Internet > Keep Alive Time field. The other ni n e probes will be 64 seconds apart. The total time will be: (9*64) + the value of the Keep Alive Time parameter.
3-8 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
DS800
Use the DS800 Development Suite Software to develop programs,
ROC Plus
ROC > Security for the Ethernet port enables or disables security for
Modbus
The ROC800-Series (firmware version 1.30 or greater) allows both
independently of ROCLINK 800. You can download these programs over the Ethernet port to a ROC800-Series that has the optional license key installed.
Once DS800 is enabled on the Configure > Control > DS800 screen, the Ethernet port for DS800 is always available to accept DS800 connections.
The ROC800-Series is capable of distinguishing TCP/IP messages received from DS800, in Modbus, or in ROC Protocol. The ROC800­Series firmware routes the DS800 messages to the correct communications task.
Protocol
all ROC Plus Protocol based Ethernet connections.
The Ethernet port is always available to accept ROC Plus Protocol connections.
Modbus RTU encapsulated in TCP/IP and Modbus TCP/IP communications on the Ethernet port. Modbus RTU encapsulated in TCP/IP is the form of Modbus protocol traditionally supported on serial connections in the ROC800-Series, which is encapsulated in a TCP/IP message. Modbus TCP/IP is the protocol developed for use over TCP/IP
connections. The Ethernet port is always available to accept Modbus connections. The ROC800-Series supports Modbus communications on any of the
serial ports, at the same time as Modbus RTU encapsulated over TCP/IP or Modbus TCP/IP connections.
3.4.2 Comm Ports General Tab
Select ROC > Comm Ports to configure the communications ports on the ROC. The Comm Port screen displays, showing the General tab.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Indicates the specific comm port to be configured. Click ▼ to display all valid selections.
Sets a 10-character name (“tag”) to help identify the comm port.
This read-only field displays the type of
present in slots 1, 2, or 3 of the base unit.
Baud Rate
Sets, in bits per second, the transmit and receive data baud rate for the comm port.
Indicates whether the communications cont roll er value (odd or even).
Data Bits
Sets the number of data bits contained in an asynchronous byte, or character. The default is 8.
Sets the number of stop bits contained in an asynchronous byte, or character. The default is 1.
Sets, in seconds, the amount of time the ROC
be sufficient.
Comm Ports
Tag
Comm Type
Parity
Stop Bits
Key On Delay
Figure 3-3. Comm Port - General tab
communications port, such as EIA-232 (RS-232) or Ethernet.
Note: The message “No Module” appears in this
field when no communication module is
performs parity checks and, if selected, the parit y
waits after turning on the ready to send (RTS) signal before beginning transmission. The default is 0. You can change this value to optimize communications.
The default value should be sufficient for dial-up modems and EIA-232 (RS-232) connections. For older radios, you may need to set this value to 0.2 seconds. For newer radios, 0.02 seconds should
3-10 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Sets, in seconds, the amount of time the ROC
circumstance.
Sets the communication protocol this port uses
and cannot be used for communications.
Key Off Delay
Port Owner
waits after transmitting a message before turning off the ready to send (RTS) signal. The default is
0. You can change this value to optimize communications.
The default value should be sufficient for dial-up modems and EIA-232 (RS-232) connections. For radios, a value of 0.01 may be appropriate.
Note: These variables may change, based on
your situation. These are general values that you need to assess for each
ROC Plus Protocol/Modbus Slave
configures the port to automatically switch between Modbus and ROC Plus Protocol messages.
ROC Plus Protocol Only configures the port
to only accept ROC Plus protocol messages (Modbus Slave is disabled).
Modbus Slave Only configures the port to
allow the ROC to act only as a Modbus slave device (ROC Plus Protocol is disabled).
Note: Use the "Only" options only if the
messages received use this specific protocol. Otherwise, select ROC Plus Protocol/Modbus Slave if this comm port is going to have both protocols communicate on it.
Modbus Master configures the port to allow
the ROC to poll Modbus devices.
DS800 configures the port to download and
debug Development Suite 800 projects only. You will not be able to connect two ROC units together with this option. It is exclusively configured for DS800/PC communications.
Note: Modems are not supported for the
DS800 communication type.
LCD configures the port for communications
with a ROC Keypad Display.
I/O Module configures this port to use the
communications protocol residing in the I/ O module.
User Program configures this port to use the
communications protocol residing in the loaded user program. The user program number here matches the user program number in the Configuration Tree menu and the User Program Administrator screen.
Reserved indicates that this port is reser ved
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Modem Type
Sets the modem type. Valid values are None
modem). The default is None.
Sets, in seconds, the amount of time that the
connection is made, the Disconnect Time begins.
Sets, in seconds, the amount of time that the
each valid receive signal.
Sets, in seconds, how long the ROC waits without
received.
3.4.3 Comm Ports Modem Tab
Use the Modem tab on the Comm Ports screen to configure the device’s modem communication ports.
Connect Time
Disconnect Time
Inactivity Time
Figure 3-4. Comm Port - Modem tab
(using a serial link to the host), External (using an external modem), and Internal (using an internal
ROC waits after initiating a call to receive a connect message from a device (typically the modem) before it terminates the call. The default is 60 seconds.
The Connect Time varies from system to system and can take up to 60 seconds to make and complete a dial up connection. If a successful
ROC waits for further activity on the line before it hangs up. ROCLINK 800 resets this timer after
receiving a signal before resetting the modem. The inactivity timer looks at the valid receive counter to determine if the signal has been
3-12 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Sets the string of characters the device requires
Command characters.
Sets the Hayes-style connect command the unit
operations, such as for SRBX Alarming.
Sets the Hayes-style disconnect command Typically, this is the command ATH0.
This read-only field shows the modem’s current status result code. Valid values are:
Result Code
Definition
0 = OK
Successfully executed command line
1 = CONNECT
Connection established
2 = RING
Ring signal detected
3 = NO CARRIER
Carrier not detected/lost
4 = ERROR
Error in command line
6 = NO DIAL TONE
No dial tone detected 7 = BUSY
Busy signal detected
8 = NO ANSWER
Line not picked up on the called end
Config Command
to initialize the modem. For external modems, refer to the manufacturer’s literature. For an internal modem, use the default value or the modem card may not operate correctly. Refer to your modem’s documentation for default Config
Connect Command
requires to contact the host. Typically, this is the command ATDT followed by the telephone number (for example, ATDT5155551212). T he unit requires this parameter for dial-out
Disconnect
Command
Modem Status
required to disconnect the contact to the host.
3.4.4 Comm Ports SRBX Tab
Use the SRBX tab to configure the Spontaneous-Report-by-Exception alarming features.
The SRBX (Spontaneous Report-by-Exception) alarming feature is available for serial communication ports. This feature allows the device to call in to a host computer when a configured alarm occurs. If you wish to configure dial-up RBX, then a modem must be present and appropriately configured.
When you use RBX alarming, ensure that you enable and configure alarms for each point you desire to monitor. Configure the alarm parameters so that an alarm occurs only when desired. This prevents "nuisance" alarms. You configure RBX alarm parameters on the Alarms tab on the I/O, MVS, and Meter Setup configuration screens.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Sets the SRBX Mode for Spontaneous-Report-by­is Disabled.
Sets the address of the host to which the SRBX feature communicates.
Sets the group of the host to which the SRBX feature communicates.
Sets, in seconds, the time the device waits
45 seconds.
Sets the number of times the device attempts to
acknowledges the SRBX alarm.
SRBX Mode
SRBX Host Address
SRBX Host Group
Delay
SRBX Attempts
Figure 3-5. Comm Port - SRBX tab
Exception alarming on this comm port. The default
between attempts to transmit an SRBX or RBX message. Each SRBX or RBX Attempts parameter has an associated delay parameter. The default for Delay #1 is 20 seconds, the default for Delay #2 is 30 seconds, and the default for Delay #3 is
resend a message if it does not obtain a valid response on the first try. "Attempt" refers to the initial message plus any retries.
ROCLINK 800 provides three parameters. The default for all parameters is Fixed Number. The default value for SRBX Attempt #1 is 1. The default value for SRBX Attempt #2 is 2. The default value for SRBX Attempt #3 is 3.
Select Fixed Number to set how many times ROCLINK 800 retries sending a message after the first unsuccessful attempt. If you enter 0, no retries occur. Select Continuous (255) to start continuous retries that stop only when the host
3-14 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
This read-only field shows the current SRBX alarm.
This read-only field shows the status of SRBX is processing) or Inactive.
Field
Description
Indicates whether the port transmit s messages
(do not transmit messages).
Sets the path and group numbers of the devices
host from by the previous parameter.
SRBX Alarm Index
SRBX Status
messaging. Valid values are Active (SRBX alarm
3.4.5 Comm Ports Store & Forward Tab
Select ROC > Comm Ports > Store & Forward tab to configure the Store & Forward features on the ROC.
Store & Forward
Store & Forward
Path
3.4.6 Comm Ports Diagnostics Tab
Select ROC > Comm Ports > Diagnostics tab to view the
communications diagnostic features on the ROC.
Figure 3-6. Comm Port - Store & Forward tab
(Store & Forward). Valid values are Enabled (transmit messages out of the port) and Disabled
that need to receive this SRBX message and forward it on to the next device to extend the communications path. You may also specify addresses for other devices that support the ROC Protocol. The device you specify by the last non­zero Address or then sends the message to the
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Indicates the number of valid ROC Plus protocol
you can zero them out if necessary.
This read-only field Indicates the time and date of protocol message received.
Indicates the number of messages sent by the
zero out if necessary.
Indicates the number of ROC Plus protocol or
necessary.
Byte Time
This read-only field shows the time and date of
Valid Receive Counters
Successful Message Time
Transmit Counter
Invalid Message Bytes
Invalid Message

3.5 Connecting to a ROC

To connect the computer to a remotely located ROC a serial, dial-up modem, radio, satellite, or other communications line should be installed. This connection may be made through the LOI (Local Port) or other Communications Port on the ROC.
Figure 3-7. Comm Port – Diagnostics tab
or Modbus protocol messages the ROC800 has received. Although these are incrementing values,
the last valid ROC Plus protocol or Modbus
ROC. This is an incrementing value that you can
Modbus protocol bytes lost. This is an incrementing value that you can zero out if
the last invalid message.
Use the Connect command to connect to a serial or dial-up modem. To use Connect:
1. Physically connect the ROC.
3-16 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Click the Direct Connect icon to establish a connection with a ROC.
2. Launch and log in to ROCLINK 800.
3. Perform one of the following:
Select a device from the Device Directory and press the EnterDouble-click a device in the Device Directory.
Select a device from the Device Directory and click the ConnectSelect ROC > Connect to connect to the device currently
3.5.1 Direct Connect
ROCLINK 800 attempts to establish communications through all PC
comm ports at various baud rates, until it receives a valid reply. By default, ROCLINK 800 tags the LOI Port as the local port (comm 1),
as shown on the Comm Port screen (ROC > Comm Ports). For the Direct Connect option to work, security conditions must be met,
and the PC must be connected to the Local Operator (LOI) port of the device with communication settings of:
key.
button on the toolbar.
selected in the Device Directory.
8 Data Bits.1 Stop Bit. No Parity.
When you click Direct Connect, ROCLINK tries to initiate communications with the device by performing a search of the PC communication ports at various baud rates. ROCLINK then "locks on" to the first comm port and baud rate that are successful in communicating with a device.
To use Direct Connect:
1. Physically connect a cable to the ROC.
2. Launch and log into ROCLINK 800.
3. Do one of the following:
Click on the Direct Connect icon in the Device Directory. Click the Direct Connect button on the toolbar. Select ROC > Direct Connect.
4. If this is the first time that you have connected to the ROC, continue
to the steps for Setting the Clock.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3.5.2 Local Port (LOI)
The PC running ROCLINK 800 physically connects to the device through a cable. For a local connection, this cable is typically a prefabricated local operator interface (LOI) cable (available from Remote Automation Solutions). One end of the cable (a 9-pin, D-shell, female connector) plugs into a serial communications port on the PC running ROCLINK 800. The other end of the cable plugs into the ROC operator interface connector called the Local Port.
Note: If your PC does not have a serial port, you may use a USB-to-
serial connector for the LOI connection.
3.5.3 Connect to a ROC
To connect the computer to a remotely located ROC, install a serial, dial-up modem, radio, satellite, or other communications line. This connection may be made through the LOI (Local Port) or other communications port on the ROC.
Use the Connect command to connect to a serial or dial-up modem. To use Connect:
1. Physically connect the ROC.
2. Launch and log in to ROCLINK 800.
3. Perform one of the following:
Select a device from the Device Directory and press the Enter
key.
Double-click a device in the Device Directory. Select a device from the Device Directory and click the Connect
button on the toolbar.
Select ROC > Connect to connect to the device currently
selected in the Device Directory.
3.5.4 Successful Login
A successful login produces an on-line connection and displays a tree representing the configuration in the ROC. Refer to Configuration Tree Menu.
3-18 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Close the screen by clicking the lower of the two Close buttons
located in the upper-right corner of the device screen.
Click the Disconnect button located on the Toolbar.
Select File > Close. This automatically closes the connection.
Figure 3-8. Successful Logon
3.5.5 Disconnecting from a ROC
To disconnect an online connection:

3.6 Troubleshooting Connection Errors

Several events can cause a connection problem: If the parameters ROCLINK 800 uses when establishing a
communications link to your PC are incorrect, it cannot make a direct connection. Refer to Troubleshooting ROCLINK 800 Communications.
If ROCLINK 800 stands idle for too long and exceeds the timeout
value for a device, a communications failure can also occur. In this case, simply log back into ROCLINK 800 and use the Direct Connect or Connect features.
If you do not have security access to the ROC, you cannot make a
connection. You must configure a valid User ID and Password (using the ROC > Security option) for each user who can connect to a ROC.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
If the PC cannot establish a connection to the ROC by "pinging" the
Device Address (ROC Address), ROCLINK 800 cannot make a TCP/IP connection. Refer to Troubleshooting TCP/IP Connections.
3.6.1 Troubleshooting ROCLINK 800 Communications
Occasionally, you may need to alter your PC communications options when you are having problems communicating with your ROC.
1. Select the desired Device in the Device Directory. Right-click and
select Properties.
2. Make sure you have specified the correct Device Address and
Device Group of the ROC or with which you are trying to communicate. If you are communicating through the LOI port of the device, the universal address is Device Address is 240 and Group Address is 240.
3. Click the Advanced tab. Try increasing the Time Out and/or Tx
Delay.
4. Click Apply. Return to the General tab, and click Connect.
5. If you are still having trouble communicating, try increasing the
Number of Retries field in the Advanced tab. Click Apply. Return to the General tab, and click Connect.
6. If you are still having trouble communicating, try increasing or
decreasing the Key Off Delay field in the Advanced tab. Click Apply. Return to the General tab, and click Connect.
7. Check the security settings of ROCLINK 800.
3.6.2 Troubleshooting TCP/IP Connections
If you are unable to establish a connection between ROCLINK 800 and the ROC on the Ethernet port, verify that the PC is able to "ping" the ROC.
1. Launch the DOS command prompt and write a command to "ping"
the ROC at its IP address (for example, C:\>ping 155.177.78.111).
2. If the Ping Statistics Reply is similar to "Packets: Sent = 4, Received
= 4, Lost = 0 <0% loss>", then the PC and ROC are connecting. You may need to alter the Internet communications setting in ROCLINK 800 software. Verify all parameters on the pertinent screens. Refer to Configuring TCP/IP Communications on the Ethernet Port (ROC800-Series).
3. If the Ping Statistics Reply is similar to "Packets: Sent = 4, Received
= 0, Lost = 4 <100% loss>", then the PC and ROC are not connecting. Review your network, your physical connection, your router, and your PC.
3-20 Communications and Security Revised September-2020

3.7 Security

3.7.1 ROCLINK 800 Security
ROCLINK 800 Configuration Software User Manual (for ROC800L)
You control security in two ways: ROCLINK 800 Security: Enables who can access (log on)
ROCLINK 800 software and the Access Level assigned to a user.
Device Security: Enables who has access to the ROC Comm Ports
and the LCD.
Note: Security Access Levels enable you to control which users have
access to specific ROCLINK 800 functions.
Use the ROCLINK 800 Security screen to set access to ROCLINK 800.
Note: Refer to Device Security for instructions on securing the ROC.
To access this screen, select Utilities > ROCLINK 800 Security. The ROCLINK 800 Security screen displays. Its table format enables you to define, by operator ID, password, and security level, who can log on to ROCLINK 800 and the screens which those IDs can access. You may define up to 32 different users.
Note: Utilities > ROCLINK 800 Security must match ROC >
Security (Device Security) in order for users to log into
ROCLINK 800.
Figure 3-9. ROCLINK 800 Security
Note: The default Operator ID is LOI. The default Password is 1000.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Security Access
Table 3-2 lists the system screens and their system-assigned security
1. Select Utilities > ROCLINK 800 Security.
2. Enter the three alphanumeric characters for the Operator ID, which
are typically the initials of the person who operates the device. Each Operator ID must be unique and is case-sensitive.
3. Enter the four numeric characters (between 0000 and 9999) to define
the operator Password. More than one user can have the same password.
4. Enter the desired Access Level for the user. 0 is the lowest (least
inclusive) access level and allows access to the fewest number of screens. 5 is the highest (most inclusive) access level and allow access to all screens. Each access level permits access to screens at that level and any inherited from lower access levels. For example, an operator ID with Access Level 3 can access screens with levels 0, 1, 2, and 3. Refer to Security Access Levels.
Note: Click the User Access Levels button to globally all access
levels.
5. Click the Save button.
Levels
access levels. The Menu Options focus on the activity while you use the Access Levels to increase or decrease responsibility levels within the Menu Options.
To access this screen, select Utilities > ROCLINK 800 Security > User Access Levels.
Notes:
If you enable security on any port, at least one operator ID must
have the highest level of security (level 5).
ROCLINK 800 rejects login requests if access levels are greater
than device security.
Table 3-2. Security Access Levels
Menu Menu Option Access Level
1 Configure Transaction History 5 15 View Display New 5 24 ROC Security 5 71 Utilities License Key Admin 107 5 72 Utilities License Key Administrator 800 5 80 Utilities Custom Display Editor 5 81 Utilities Custom EFM Report Editor 4 20 ROC Display Administrator 4 69 Utilities Update Firmware 4
3-22 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Menu Menu Option Access Level 70 Utilities Upgrade Hardware 4 74 Utilities User Program Administrator 3
2 File New 3 4 File Download 3
5 File Save Configuration 3 18 View Display From File 3 19 View Display From Device 3 23 ROC Clock 3 25 ROC Comm Ports 3 27 ROC Information 3 28 ROC Flags 3 29 Configure IO AI Points 3 30 Configure IO AO Points 3 31 Configure IO DI Points 3 32 Configure IO DO Points 3 33 Configure IO PI Points 3 34 Configure IO TC Points 3 35 Configure IO RTD Points 3 36 Configure IO System AI Points 3 37 Configure IO Soft Points 3 38 Configure IO Extended Soft Point 3 39 Configure IO MVS Sensor 3 40 Configure IO HART Points 3 41 Configure IO Setup 3 42 Configure IO Advanced Pulse Module 3 43 Configure IO ACIO Module 3 44 Configure IO Virtual Discrete Output 3 45 Configure Control FST Registers 3 46 Configure Control PID Loop 3 47 Configure Control Radio Power Control 3 48 Configure Control Sampler/Odorizer 3 49 Configure Control DS800 3 50 Configure History Segments 3 51 Configure HistoryPoints 3 52 Configure Opcode Table 3
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Menu Menu Option Access Level 53 Configure Modbus 3 54 Configure Rtu Network 3 55 Configure LCD User List 3 56 Configure User Data UD1 3 73 Utilities Convert EFM File 3 75 Utilities AI Calibration Values 3 76 Utilities MVS Calibration Values 3 77 Utilities FST Editor 3 78 Utilities Keypad Display Editor 3 79 Utilities Read File From Device 3 82 Utilities Options 3 84 Tools Data Logger 3
7 View EFM Report 2
8 View Calibration Report 2 22 ROC Collect Data 2 57 Meter Setup 2 58 Meter Setup 800 Station 2 59 Meter Setup 800 Orifice meter 2 60 Meter Setup 800 Linear meter 2 61 Meter Calibration 2 62 Meter Calibration 800 Orifice meter 2 63 Meter Calibration 800 Linear Meter 2 64 Meter Values 2 65 Meter Values 800 Orifice meter 2 66 Meter Values 800 Linear Meter 2 67 Meter Plate Change 2 68 Meter History 2
3 File open 1
6 File Print Configuration 1
9 View History From Device 1 10 View History From File 1 11 View Alarms From Device 1 12 View Alarms From File 1 13 View Events From Device 1 14 View Events From File 1
3-24 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Menu Menu Option Access Level 21 View I/O Monitor 1 26 ROC Memory 1 16 View Display Display 1 0 17 View Display Display 2 0 83 Utilities Communications Monitor 0
3.7.2 Device Security
Use the Device Security screen to control who has access to the Comm Ports on a specific device. When you enable this feature, you must log in to ROCLINK 800 to use the communications port. You can enable this feature on each communications port separately.
To access the Device Security screen, select ROC > Security. The Device Security screen displays. Refer to Adding and Deleting Users in Device Security.
Note: Any operator ID you define in ROC >Security (which defines
access to a device) must match an operator ID you also must define in Utilities > ROCLINK 800 Security (which defines access to the software). Without both components, an ID cannot log onto ROCLINK 800 and gain access to a ROC.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Adding a User
To add an operator ID:
3-26 Communications and Security Revised September-2020
Figure 3-10. Device Security
The default Operator ID is LOI; the default Password is 1000.
1. Select ROC > Security.
2. Click an Operator ID field to add, edit, or remove a user. Refer to
Security Access Levels for a full list of the access levels.
3.7.2.1. Adding and Deleting Users
This section details how to add and delete users in Device Security.
1. Select ROC > Security.
2. Click on an empty cell in the table. The Device Security dialog
displays.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Field
Description
Indicates the unique three alphanumeric
ID must be unique and is case-sensitive.
Sets the numeric characters (between 1 and 9999)
password.
Confirm Password
Validates the password you entered in the Password field.
Sets the access level for this operator ID. 0 is the
Table 3-2.
Sets the groups to which this user belongs. This Display uses for secur i ty.
Figure 3-11. Device Security – User Table
3. Complete the dialog as described.
Operator ID
characters for the operator ID. This ID is typically the initials of the person who operates the device through that communications port. Each Operator
Password
for the password. More than one operator ID can have the same password.
Note: If you define a password with fewer than
four numbers (such as 123), do not place leading zeroes (such as 0123) before a
Access Levels
lowest access level and allows access to the fewest number of screens. 5 is the highest access level and permits access to all screens. Each access level permits access to screens at that level and any inherited from lower access levels.
For example, the IDs with access level 3 can access screens with levels 0, 1, 2, and 3. Refer to
Member of Groups
field corresponds to the groups the Keypad
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Deleting a User
To delete an operator ID:
4. Click OK to add the user and close the dialog. The Device Security
screen displays, showing the user you have just added.
1. Select ROC > Security.
2. Click an Operator ID to delete.
3. Click Remove.
4. Click Yes to the confirmation dialog. The Device Security screen
displays, showing that the operator ID has been removed.
3.7.2.2. Groups Tab
Select ROC > Security > Groups tab to establish up to 20 unique groups that Keypad Display security uses.
Note: If your application does not require a keypad display, you do not
need to create groups.
To create a group:
1. Select ROC > Security.
2. Select the Groups tab. The Groups screen displays.
3-28 Communications and Security Revised September-2020
Figure 3-12. Device Security – Groups tab
ROCLINK 800 Configuration Software User Manual (for ROC800L)
3. Enter a group name (such as Operators, Technicians, or
Supervisors) in each line.
4. Click Apply to save your groups. Note: You then use the Keypad Display Editor (Utilities > Keypad
Display Editor) to indicate which displays those particular groups may access. Your application does not require a keypad display; you do not need to create groups.
3.7.2.3. Comm Ports Tab
When you select the Comm Ports tab, the Comm Ports screen displays:
Figure 3-13. Device Security – Comm Ports tab
For each communications port, select one of the following Security options:
Disabled – All login requests are accepted.User ID Enabled – Login requests are accepted if the Operator ID
and password are valid. Upon successful login, full access is allowed.
Revised September-2020 Communications and Security 3-29
ROCLINK 800 Configuration Software User Manual (for ROC800L)
User Access Level Enabled – Login requests are accepted if the
Operator ID and password are valid. Upon successful login, the user is restricted by access level. See Security Access Levels.
Note: If you enable security on any port, at least one user must have the
highest level of security (level 5).
3.7.2.4. User/Group Summary Tab
The Device Security > User/Group Summary tab displays a table that summarizes the defined associations between users and groups. It reflects the users you defined on the Users tab and the groups you defined on the Groups tab.
You can also use this table to modify those associations. Click in a box to add (or remove) a user ID from a group. Click Apply to save any changes.
Figure 3-14. Device Security – User/Group Summary tab
3-30 Communications and Security Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Chapter 4 – The File Menu

In This Chapter
4.1 New Configuration ................................................................................ 4-2
4.1.1 Configuration Checklist ............................................................. 4-2
4.1.2 Duplicating a Configuration ....................................................... 4-3
4.2 Opening a Configuration File ................................................................ 4-3
4.2.1 Configuration Tree Menu ........................................................... 4-4
4.2.2 Modifying an Existing Configuration File ................................... 4-6
4.2.3 Adding Modules to an Exist ing Configuration File ..................... 4-6
4.3 Downloading a Configuration ................................................................ 4-8
4.4 Saving a ROC User File ..................................................................... 4-10
4.5 Saving a Configuration ....................................................................... 4-10
4.6 Printing a Configuration ...................................................................... 4-10
4.7 Print ..................................................................................................... 4-12
4.8 Print Setup .......................................................................................... 4-12
4.9 Recent Files ........................................................................................ 4-13
4.10 Close ................................................................................................... 4-13
4.11 Exit ...................................................................................................... 4-13
Use the File Menu to print, open, close, and save configuration files. Configuration files contain all hardware and software settings for your ROC800L.
Figure 4-1. File Menu
Note: Because of the complex relationship of point types and user
programs in the ROC800L, you cannot currently use File > New to create a new ROC800L configuration file. However, you can save the configuration file resident in a working ROC800L and subsequently edit it.
Revised September-2020 File Menu 4-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)

4.1 New Configuration

The New option on the File menu allows you to create a configuration file when you are not physically connected to a ROC. However, because of the complex relationship of point types and user programs in the ROC800L, it is not currently possible to create a ROC800L configuration file while you are off-line. However, you can save the configuration file resident in a working ROC800L and subsequently edit it. See the section Saving a ROC User File
In addition to keeping backup copies of the configuration file, it is also good practice to keep a backup copy of the ROC_USER.mdb file. This file contains the communications, security, and password settings for the device.
To create a backup copy of the file: Open Windows Explorer and navigate to the folder where ROCLINK
800 software is located. Typically, this folder is C:\Program Files\ROCLINK800.
Create a copy of the ROC_USER.mdb file. Paste the copy into another folder on the PC or a disk. Saving a Configuration (located in this chapter) for further information.
4.1.1 Configuration Checklist
For a ROC800-Series:
ROC menu > ROCLINK 800 Security (logon) Device Directory > Comm Port > Properties (PC communication
configurations)
ROC menu > Security (User List and Comm Port Security) ROC menu > ClockROC menu > Information (system variables) ROC menu > Comm Ports (FloBoss device communication
configurations)
Configure menu > I/O menu > AI, AO, DI, DO, DOR, PI, TC, RTD,
MVS, HART, APM, ACIO, VDO and IEC62591
Meter > Setup > StationMeter > Setup > Orifice MeterMeter > Setup > Linear MeterConfigure menu > Control menu > PID Loop Configure menu > Control menu > FST Registers Configure menu > History Segments Utilities menu > FST EditorView menu > Display > New or from File (for custom PC displays)
ROCLINK 800 Configuration Software User Manual (for ROC800L)
ROC menu > Flags (for saving and system variables to Flash
memory)
4.1.2 Duplicating a Configuration
You can duplicate the configuration for another ROC800-Series by using these menu functions in the following order:
1. File > Save Configuration to save a device’s configuration to a
specified file.
2. ROC > Direct Connect (Local Port) or Connect (modem) to
connect physically to the second unit, and then communicate.
3. File > Download loads the configuration into the unit.
After you have loaded configuration data into the second device (Step 3) and changed it as needed, you can save the configuration to its own disk file by using Step 1.

4.2 Opening a Configuration File

Use the Open option to open a configuration file stored on a PC’s hard drive. Once you open the configuration file, it automatically becomes the active configuration file and you may edit the file offline. You can also load the configuration file into the device using the Download function.
To open a configuration file:
1. Start ROCLINK 800.
2. Select File > Open. The Open dialog box displays.
3. Select a configuration file name and click Open. The configuration
file displays.
Notes:
ROCLINK 800 files have the .800 extension. If you receive an error when opening a configuration file, ensure
that your PC’s Regional Settings are configured correctly. Refer to Installing ROCKLINK 800 under Microsoft Windows 10, 8 or Windows 7 (located in Chapter 1).
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 4-2. Open File Configuration
4.2.1 Configuration Tree Me nu
When you open a configuration file, the Configuration Tree appears on the left-hand side of the screen. The tree hierarchically displays the parts of a configuration (such as I/O, Meter Runs, and History) that you can change.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Option
Description
I/O
Lists all available inputs and outputs by type.
Control
Displays the FST, Radio Control, Sampler/Odo rizer,
Information screen.
Meter
Lists all available gas meters and all stations.
System
Displays Comm Port, Device Flags, and Opcode Table information.
History
Displays all available History Segments and History Points.
User Program
Displays all user programs.
User Display
Accesses custom displays stored in the configuration custom user displays and user program displays).
Figure 4-3. Configuration Tree Menu
DS800, and PID options enabled on the ROC >
file. The file can store a maximum of 246 displays (both
From the Configuration Tree, you may change the configuration or monitor current operations. Once you are in the Configuration Tree menu, you can use the + and – symbols to display or hide various options.
Double-click the desired function in the Configuration Tree to display the associated screen. Double-clicking an icon is the same as selecting the option in the menu bar or clicking a Toolbar button.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
4.2.2 Modifying an Existing Configuration File
You can make modifications to an existing configuration file offline. This allows you to share configuration files between multiple devices and customize each configuration file to account for device differences.
To modify an existing configuration file:
1. Start ROCLINK 800.
2. Select File > Open. The Open dialog box displays.
3. Select a configuration file name and click Open. The configuration
file displays.
Note: ROCLINK 800 files have the .800 extension.
Figure 4-4. Modifying Configuration File
4.2.3 Adding Modules to an Existing Configuration File
You can add modules to an existing device configuration file. To modify an existing configuration file:
1. Start ROCLINK 800.
2. Select File > Open. The Open dialog box displays.
3. Select a configuration file name and click Open. The configuration
file displays.
Note: ROCLINK 800 files have the .800 extension.
4. Right-click an empty slot to display a pop-up menu of available
modules.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
5. Select the appropriate module from the pop-up menu. An Add New
Module dialog displays.
Figure 4-5. Add New Module
6. Click Start to add the new module TLPs to the configuration file.
Figure 4-6. Add New Module Success
ROCLINK 800 Configuration Software User Manual (for ROC800L)
7. Click Finish. A dialog displays warning you that all offline and
online connections must be closed to complete the operation.
Caution
Any unsaved changes to other configuration files are lost when the connections are closed.
Figure 4-7. Connection Must Be Closed
8. Click OK to close all online and offline connections and the new
module to the configuration.
Figure 4-8. New Module Added

4.3 Downloading a Configuration

Use the Download option to download a saved configuration to a ROC.
1. Connect to the ROC.
2. Select File > Download. The Select Configuration File to Download
dialog displays.
3. Select a configuration file. ROCLINK 800 configuration files have
the extension .800.
4. Click Open. The Download Configuration screen displays.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 4-9. Download Configuration-Base Firmware Tab
5. Select only the configuration points you desire to download.
ROCLINK 800 grays out any items not configured in your configuration.
6. Select the User Defined Points tab. The User Defined Points screen
displays.
Figure 4-10. Download Configuration-User Defined Points Tab
7. Select only the User Defined Points you desire to download.
8. Click Download. ROCLINK 800 begins to download the
configuration points you have chosen, and displays the status, point type, and point number information as the download progresses.
9. Click OK when the download completes.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
10. Select ROC > Flags and click the Save Configuration for Flash
Memory button.

4.4 Saving a ROC User File

In addition to keeping backup copies of the configuration file, it is also good practice to keep a backup copy of the ROC_USER.mdb file. This file contains the communications, security, and password settings for the device.
To create a backup copy of the file: Open Windows Explorer and navigate to the folder where ROCLINK
800 software is located. Typically, this folder is C:\Program Files\ROCLINK800.
Create a copy of the ROC_USER.mdb file. Paste the copy into another folder on the PC or a disk.

4.5 Saving a Configuration

The Save Configuration option saves the current configuration of a connected device to a disk file. This feature is useful when creating a backup, when configuring similar ROC for the first time, or when making configuration changes off-line. Once a backup configuration file is created, it can be loaded into a device using File > Download.
1. Select File > Save Configuration. The Save As dialog box appears.
2. Type the desired File name of the backup file.
3. Click Save.
ROCLINK 800 configuration files have the extension .800.

4.6 Printing a Configuration

Use the Print Configuration option to specify the point types that you want to print.
1. Select File > Print Configuration. The Print Configuration Setup
screen displays.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 4-11. Print Configuration
2. Select the specific Point Types to print. Note: Click Select All or Deselect All to select multiple point
types, point numbers, or parameters. Use your mouse to select/deselect individual point types, point numbers, or parameters.
3. Select the Point Numbers to print.
4. Select the Parameters to print. Note: Click the Certified Print button to automatically print all
point types, point numbers, and parameters in the device. This option does not allow you to deselect any point types, point numbers, or parameters.
5. Click OK. ROCLINK 800 reads the configuration from the device
and displays the Print Preview screen.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
HTML
Converts the file to the format of a hypertext mark up
Figure 4-12. Print Preview-Certified Print

4.7 Print

6. Use screen option buttons (located on the toolbar) to either directly
print the preview or export the preview (with a file name you specify) to your PC’s hard drive in one of the following formats:
Button Result
Print Sends file to a local printer PDF Converts the content to the format of an Adobe® Acrobat®
file
Excel Converts the content to the format of a Micr osoft® Excel™
spreadsheet file
RTF Converts the content to the format of a Microsoft Rich Text
Format (RTF
TXT Converts the file to the format of an ASCII-compatible text
file
language file.
®
) file
Click Print or select Print from the File menu to print ROCLINK 800­generated historical, event, and alarm log reports.

4.8 Print Setup

Use Print Setup to change the default printer for ROCLINK 800 information.
To change printers: Select File > Print Setup.

4.9 Recent Files

ROCLINK 800 Configuration Software User Manual (for ROC800L)
Select the printer you desire to print to from the Name drop-down list.
The File menu displays the configuration files that you have recently opened or saved.

4.10 Close

4.11 Exit

Figure 4-13. Recent Files
Select File > Close to close the active screen.
Note: Because the graphic display is an active screen, selecting Close
can terminate the online connection.
Select File > Exit to exit the ROCLINK 800 program. The following may occur:
If you are currently editing a configuration file, ROCLINK 800
closes the file.
If you are currently connected to a dial-up ROC, ROCLINK 800
issues the hang-up command to the modem.
If you are currently online with a ROC, the connection automatically
terminates.
ROCLINK 800 Configuration Software User Manual (for ROC800L)
[This page is intentionally left blank.]
ROCLINK 800 Configuration Software User Manual (for ROC800L)

Chapter 5 – The View Menu

In This Chapter
5.1 Directory ................................................................................................ 5-2
5.2 EFM Reports ......................................................................................... 5-2
5.2.1 Creating the EFM File ............................................................... 5-2
5.2.2 Viewing EFM Reports ................................................................ 5-3
5.3 Calibration Reports ............................................................................... 5-7
5.3.1 Viewing a Calibration Report ..................................................... 5-7
5.4 History Logs .......................................................................................... 5-8
5.4.1 Viewing Logs from a Device .................................................... 5-10
5.4.2 Viewing History Logs from a Fi l e ............................................. 5-11
5.4.3 Plotting History ........................................................................ 5-12
5.4.4 Managing Plotted History ........................................................ 5-13
5.5 Transaction History ............................................................................. 5-14
5.5.1 Viewing Transaction History Stored in a Device ..................... 5-14
5.5.2 Viewing Transaction History Stored in a File .......................... 5-16
5.6 Alarm, Event, and Weights & Measurements Event s Logs ................ 5-17
5.6.1 Viewing Alarm Logs ................................................................. 5-18
5.6.2 Viewing Event Logs ................................................................. 5-18
5.6.3 Viewing Weight and Measure Events Logs ............................. 5-19
5.7 Display Editor ...................................................................................... 5-20
5.8 Display Administrator .......................................................................... 5-21
5.8.1 Viewing a Custom Display ....................................................... 5-21
5.8.2 Downloading a Custom Display .............................................. 5-21
5.8.3 Deleting a Custom Display ...................................................... 5-23
5.9 I/O Monitor .......................................................................................... 5-23
5.10 Toolbar ................................................................................................ 5-25
5.11 Refresh User Program Tree ............................................................... 5-25
Use the View menu options to view the Device Directory; electronic flow measurement (EFM) reports; calibration logs; history, alarms, weights and measures, and events logs; create, view, and manage custom displays, monitor I/O; view the toolbar; and update point tags on the User Program configuration tree.
Revised September-2020 View Menu 5-1
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 5-1. View Menu

5.1 Directory

5.2 EFM Reports

Select View > Directory to replace the ROC800-Series graphic image or Configuration Tree with the Device Directory. The Device Directory displays the root level of all devices and groups configured in ROCLINK 800.
Note: You can also switch displays between the Device Directory and
the online device using the Windows option on the ROCLINK 800 menu bar.
Select View > EFM Report to generate printed and on-screen reports of the configuration, alarms, events, and historical flow data for a gas meter point and to the EFM reports to other formats. ROCLINK 800 uses EFM (Electronic Flow Measurement) reports in conjunction with the ROC's AGA flow calculation capabilities to display or print previously collected flow data. An EFM report file contains all flow data, which includes the operational characteristics (configuration parameters, history, events, and alarms) of each measured meter run configured in the ROC.
Note: If a communication failure occurs during the EFM Report
process, the initial data collected before the comm failure remains in the report.
5.2.1 Creating the EFM File
Before you can view the EFM report data, you must first create the report file. Refer to Chapter 6, Section 6.3, Collect ROC Data, for this process.
5-2 View Menu Revised September-2020
ROCLINK 800 Configuration Software User Manual (for ROC800L)
5.2.2 Viewing EFM Reports
“Viewing” an EFM report requires you to identify the EFM data you want to use, selecting a report format file, and then indicating the kinds of data to include in the report. To view the EFM report:
1. Select View > EFM Report. An Open dialog displays, listing all the
.EFM files.
2. Select an .EFM file and click Open. The View EFM Report screen
displays.
Figure 5-2. View EFM Report
3. Select Custom as the Report Type. This activates the Browse
button.
4. Click Browse to display a Select Custom Report screen.
Revised September-2020 View Menu 5-3
ROCLINK 800 Configuration Software User Manual (for ROC800L)
Figure 5-3. Select Custom Report
5. Select a report file and click Open. The View EFM Report screen
displays, indicating the selected report file.
Figure 5-4. Selected Custom Report File
6. Define the report content:
5-4 View Menu Revised September-2020
Loading...