Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Page
Revision
All pages
May-2016
All pages
April-2016
Initial release
January-2014
Revision Tracking Sheet
May 2016
This manual may be revised periodically to incorporate new or updated information. The revision date of each
page appears at the bottom of the page opposite the page number. A change in revision date to any page also
changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if
applicable):
ii Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Contents
Chapter 1 – Introduction 1
1.1 Scope and Organization ................................................................................................................... 1
4.2 Best Practices ................................................................................................................................. 42
Chapter 5 – Reference Materials 43
5.1 Point Type 68/247: Modbus Express Setup ................................................................................... 44
5.2 Point Type 69/248: Modbus Master Table ..................................................................................... 58
5.3 Point Type 70/249: Modbus Registers ........................................................................................... 63
5.4 Point Type 71/250: Modbus Expanded Registers .......................................................................... 64
Revised May-2016 iii
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
iv Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Chapter 1 – Introduction
This chapter describes the structure of this manual and presents an
overview of the Modbus Express Module for the ROC800-Series Remote
Operations Controller (ROC800) and the FloBoss 107 Flow Manager
(FB107). The Modbus Express Module provides all of the functions
necessary to communicate with other devices using the Modbus protocol
over RS-485 serial communications.
The Modbus Express Module streamlines the installation process by
automatically installing all point types and screens that are part of the
application.
1.1 Scope and Organization
This document serves as the user manual for the Modbus Express Module,
which is intended for use in a ROC800 and FB107. This manual describes
how to install and configure the Modbus Express Module (referred to as
the “Modbus module” or “the module” throughout the rest of this manual).
You access and configure this module using ROCLINK 800
Configuration Software loaded on a personal computer running Windows
2000 (with Service Pack 2), Windows XP, Windows Vista, or Windows 7.
The chapters in this manual provide information in a sequence appropriate
for first-time users. Once you become familiar with the procedures and the
software, the manual becomes a reference tool.
ROCLINK™ 800 Configuration Software User Manual (for FloBoss
107) (D301249X012).
ROCLINK™ 800 Configuration Software User Manual (for ROC800-
Series) (D301250X012).
Revised May-2016 1
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Capabilities
The Modbus Express Module can simultaneously support up to six
three devices that use many entries. Refer to Table 1 for a list of Master
1.2 Product Overview
The Modbus Express module enables the ROC800 or the FB107 to
communicate directly with devices using the Modbus protocol. The
module has an on-board EIA-485 (RS-485) communications port for this
purpose.
The Modbus Express module provides the following features:
Predetermined register lists for the supported field devices
Easy addition and removal of devices from active service
The ability to poll for user defined registers from a field device
Advanced editing of the Modbus master table
Expanded registers which provide native I/O-like features for certain
registers
The data from the field devices is made available in the host device’s TLP
database for easy access by other system features such as FSTs, meter
runs, and PID loops, as well as a SCADA host system.
The application module communicates with up to six separate devices
over a single multidrop 485 communication. The module also includes
user displays, which are accessible by ROCLINK 800, providing a user
interface to the application’s database.
The module contains two master tables, each with 25 entries. Each entry
corresponds to a separate request to a device. The module uses 200
registers to store the data read from and written to the devices. The
registers support integer and float data entries.
The Modbus Express module allows you to quickly add supported
Modbus devices. The module’s Master Table is pre-populated to poll a list
of pre-selected registers and the module's RS-485 communication port is
pre-configured to match the selected device’s defaults (where possible).
Once you add the device, you enable the Modbus polling, and the module
begins to populate its registers with the data from the device.
Note: Some devices may require settings the module does not natively
support. You may externally configure these devices. Refer to
Section 1.2.1, Supported Devices, for the specific devices
supported at this time and Section 1.2.2, Module Wiring, for its
wiring configurations.
Modbus devices, provided all devices use the same communication
port settings. Since there is a limit to the available number of Master
Table entries (50) and registers (200), the actual number of devices you
can add depends on how the individual devices use the Master Tables
and registers. For example, you may be able to add six devices that
only use a few Master Table or register entries, or to add only two or
2 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Table and register entries required for each supported devices.
Use Express Mode to add multiple instances of the same devices,
which only requires you to change the Modbus RTU address for each
occurrence of the device.
Use Advanced Mode to add different devices, which must be
preconfigured to use the same communication settings (baud rate,
parity, data bits, stop bits, byte order, and RTU/ASCII mode). When
using Advanced Mode, you should disable the module’s automatic
configuration of communication ports and then manually configure the
ports to match the common port settings currently in use.
The User Interface
The Modbus Express Module contains its own central processing unit
(CPU) which handles the Modbus protocol and RS-485
communications. Any data a device sends or receives passes between
the module’s CPU and the flow computer. Due to this architecture, the
user interface has special considerations.
When you change information on a screen (entering a value in a field,
selecting a checkbox, or selecting an item from a pull-down menu), the
module does not “see” that change until you click Apply. Clicking Apply
sends all changes on the screen to the module’s CPU for processing. When
you update items in the module, any changes do not display on the screen
until you click Update. If you click Update before the flow computer has
received updated data from the module, the screen cannot show the
changes.
For example, you select a different baud rate and then click Apply to
apply that change to the module. If you then immediately click Update,
the module’s CPU and the flow computer may not have had sufficient
time to process your change and display it on the screen. You may need to
click Update again. This is particularly evident with status/error
messages.
Additionally, to ensure that the flow of data between the module and flow
computer has sufficient processing and communication time, the module
prevents you from entering data in certain fields on screens (such as "Add
Device" and "Edit/Delete Device" tabs on the Setup configurations
screen). This “locking” feature helps you to select components in the
proper order. A green box around the button or frame indicates that it is
active. For example, in the Add Device tab of the Setup configurations
screen, if you select a device to add and then click Apply, the module
locks the Device section of the screen and activates the Edit and Add Device buttons. At this point, you can only click Add Device to add the
device you select, or click Edit to unlock the Device frame and make any
changes. See Figures 1 and 2.
Revised May-2016 3
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Device
Name
Code
Reg
Reg
Code
Reg
Type
Daniel
Status A
3
2458 1 28
Integer
Status B
3
2459 1 28
Integer
Status C
3
2460 1 28
Integer
Status D
3
2461 1 28
Integer
Status
3
2462 1 28
Integer
Data Qual
3
2300 1 29
Integer
Flow Dir
3
2463 1 28
Integer
Avg Flow
3
2018 2 66
Float
Avg Snd
3
2034 2 66
Float
Figure 1. Setup Screen – Device
Frame highlighted with a green
box
1.2.1 Supported Devices
The Modbus Express module allows devices to communicate using
Modbus protocol over RS-485 serial communication. The following
devices below are pre-mapped so configuration is not required.
Daniel Model 3812 Liquid Ultrasonic Meter
Daniel Mark III Gas Ultrasonic Meter
Fisher Easy-Drive Actuator
Micro Motion Direct Connect (700/800 Core Processor)
Micro Motion Transmitter (1700/2700)
Micro Motion 7826/7828 Density Meter
Micro Motion 7829 Viscosity Meter
Rosemount 3095 MV Transmitter
Rosemount 3300 Guided Wave Radar Level
Platinum BMS-731 Burner Manager
Sick Maihak FlowSic600 Ultrasonic Meter
Krohne Altosonic V12 Ultrasonic Meter
Spectra Sensors SS500/SS2000/SS3000
Figure 2. Setup Screen – Edit and
Add Device Frame highlighted
with a green box
Table 1 shows the Master Table and Register entries for each supported
devices.
Table 1. Master Table and Register entries for supported devices
Register
Model 3812
Liquid
Ultrasonic
Meter
4 Revised May-2016
Function
Slave
Num
Conv
Value
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Device
Name
Code
Reg
Reg
Code
Reg
Type
Avg Flow
3
2018 2 66
Float
Q Meter
3
2042 2 66
Float
Q Flow
3
2056 2 66
Float
Freq 1 KF
3
2516 2 66
Float
Freq ChA
3
2504 2 66
Float
Freq 1 KF
3
2566 2 66
Float
Freq ChA
3
2554 2 66
Float
CPU FW Ver
3
9006 1 29
Integer
Fwd A Hour
3
4110 1 29
Integer
Rev A Hour
3
4112 1 29
Integer
Fwd A Day
3
4160 1 29
Integer
Rev A Day
3
4162 1 29
Integer
Fwd A Hour
3
4210 1 29
Integer
Rev A Hour
3
4212 1 29
Integer
Fwd A Day
3
4260 1 29
Integer
Rev A Day
3
4262 1 29
Integer
Flow Time
3
2106 2 66
Float
Flow Time
3
2108 2 66
Float
Daniel Mark
Sys Status
3
10953 1 28
Integer
Path A Sta
3
10954 1 28
Integer
Path B Sta
3
10955 1 28
Integer
Path D Sta
3
10957 1 28
Integer
CPU SW Ver
3
11000 1 29
Integer
Data Qual
3
10584 1 29
Integer
Freq 1
3
12468 2 67
Float
Freq 2
3
12518 2 67
Float
K-Factor 1
3
12472 2 67
Float
K-Factor 2
3
12522 2 67
Float
Velocity
3
13574 2 67
Float
Spd of Snd
3
13594 2 67
Float
Ucorr Rate
3
13624 2 67
Float
Corr Rate
3
13638 2 67
Float
Pos Demand
3 0 1
28
Integer
Reset Diag
3 1 1
28
Integer
Recal Dmd
3 2 1
28
Integer
A Cal 0%
3 3 1
28
Integer
A Cal 100%
3 4 1
28
Integer
Actual Pos
3 9 1
28
Integer
Actual Dmd
3
10 1 28
Integer
Num Cycles
3
12 2 63
Integer
Tm Running
3
14 2 63
Integer
Tm Open
3
16 2 63
Integer
Tm Closed
3
18 2 63
Integer
A IP Val
3
24 1 28
Integer
Ctr Src
3
33 1 28
Integer
Loss D Pos
3
34 1 28
Integer
Deadband
3
35 1 28
Integer
LowT Ctoff
3
36 1 28
Integer
III Gas
Ultrasonic
Meter
Register
Path C Sta 3 10956 1 28 Integer
Function
Slave
Num
Conv
Value
Fisher EasyDrive
Actuator
Revised May-2016 5
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Device
Name
Code
Reg
Reg
Code
Reg
Type
Comm Tmout
3
37 1 28
Integer
GO TO POS
6 0 1
28
Integer
SNR 1 AB
4
7025 2 65
Float
SNR 2 AB
4
7027 2 65
Float
SNR 3 AB
4
7029 2 65
Float
SNR 4 AB
4
7031 2 65
Float
SNR 5 AB
4
7033 2 65
Float
SNR 6 AB
4
7035 2 65
Float
SNR 1 BA
4
7037 2 65
Float
SNR 2 BA
4
7039 2 65
Float
SNR 3 BA
4
7041 2 65
Float
SNR 4 BA
4
7043 2 65
Float
SNR 5 BA
4
7045 2 65
Float
SNR 6 BA
4
7047 2 65
Float
Flow Rate
4
7055 2 65
Float
Velocity
4
7057 2 65
Float
Spd of Snd
4
7059 2 65
Float
Vel Path 1
4
7061 2 65
Float
Vel Path 2
4
7063 2 65
Float
Vel Path 3
4
7065 2 65
Float
Vel Path 4
4
7067 2 65
Float
Vel Path 5
4
7069 2 65
Float
Vel Path 6
4
7071 2 65
Float
Spd Snd 1
4
7073 2 65
Float
Spd Snd 2
4
7075 2 65
Float
Spd Snd 3
4
7077 2 65
Float
Spd Snd 4
4
7079 2 65
Float
Spd Snd 5
4
7081 2 65
Float
Spd Snd 6
4
7083 2 65
Float
Micro Motion
Meter Zero
1 4 1
28
Integer
Flow Dir
1
65 1 28
Integer
Status
3
244 2 70
Float
Mass Rate
3
246 2 70
Float
Density
3
248 2 70
Float
Temp
3
250 2 70
Float
Vol Rate
3
252 2 70
Float
Mass Total
3
258 2 70
Float
Vol Total
3
260 2 70
Float
Mass Inv
3
262 2 70
Float
Vol Inv
3
264 2 70
Float
Pr Corr Fl
3
266 2 70
Float
Pr Corr Dn
3
268 2 70
Float
Tube Freq
3
284 2 70
Float
L Pckf Vol
3
288 2 70
Float
Mass Fl Zr
3
292 2 70
Float
Micro Motion
Status
3
256 2 60
Integer
Cor Line D
3
257 2 65
Float
Cor Base D
3
258 2 65
Float
Krohne
Altosonic
V12
Ultrasonic
Meter
Register
Function
Slave
Num
Conv
Value
Direct
Connect
(700/800)
and Micro
Motion
Transmitter
(1700/2700)
Drive Gain 3 290 2 70 Float
7826/7828
Density
6 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Device
Name
Code
Reg
Reg
Code
Reg
Type
Meter
Line Temp
3
259 2 65
Float
Coil Level
3
264 2 65
Float
Timer Per
3
261 2 65
Float
Micro Motion
Status
3
256 2 60
Integer
Line Dens
3
357 2 65
Float
Base Dens
3
258 2 65
Float
Line Temp
3
259 2 65
Float
Coil Level
3
264 2 65
Float
Time Per
3
261 2 65
Float
Kinem Visc
3
290 2 65
Float
Dynam Visc
3
289 2 65
Float
Platinum
Temp Deg C
4 8 1
28
Integer
Temp Deg C
4 9 1
28
Integer
Relights
4
10 1 28
Integer
Input Volt
4
28 2 67
Float
Aux A DegF
4
59 1 28
Integer
Aux B DegF
4
60 1 28
Integer
Curr State
3
23 1 28
Integer
Error Type
3
24 1 28
Integer
Reset Type
3
25 1 28
Integer
Reset Year
3
26 1 28
Integer
Reset Mnth
3
27 1 28
Integer
Reset Day
3
28 1 28
Integer
Reset Hour
3
29 1 28
Integer
Reset Min
3
30 1 28
Integer
Pilot On
3
31 2 57
Integer
Main Pilot On
3
33 2 57
Integer
TC A Temp
3
37 1 28
Integer
TC B Temp
3
38 1 28
Integer
Rem On Off
1
17 1 28
Integer
Rosemount
Status
4
2000 1 28
Integer
PV 4 2002 2 66
Float
SV 4 2004 2 66
Float
TV 4 2006 2 66
Float
FV 4 2008 2 66
Float
Sys Status
3
3002 1 28
Integer
Status 2
3
3004 1 28
Integer
Status 3
3
3005 1 28
Integer
Status 4
3
3006 1 28
Integer
Freq Hz
3
3028 1 28
Integer
Ext Stat 1
3
3057 1 28
Integer
Ext Stat 2
3
3058 1 28
Integer
Ext Stat 3
3
3059 1 28
Integer
Ext Stat 4
3
3059 1 28
Integer
Version
3
5001 2 61
Integer
System Err
3
5039 2 61
Integer
Limit Warn
3
5055 2 61
Integer
7829
Viscosity
Meter
BMS731 Burner
Manager
Register
FlamResist 4 14 1 28 Integer
Function
Slave
Num
Conv
Value
3095 MV
Transmitter
Sick Maihak
FloSci600
Ultrasonic
Meter
Status 1 3 3003 1 28 Integer
Revised May-2016 7
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Device
Name
Code
Reg
Reg
Code
Reg
Type
Uncor Rate
3
7000 2 66
Float
Velocity
3
7003 2 66
Float
Spd of Snd
3
7002 2 66
Float
Meter Fact
3
7026 2 66
Float
Spectra
Concentrat
3
7000 2 65
Float
Temp
3
7002 2 65
Float
Pressure
3
7004 2 65
Float
Spply Volt
3
7006 2 65
Float
PkD1 Mid
3
7008 2 65
Float
FW Version
3
7112 2 65
Float
S Factor
3
7200 2 65
Float
Alm Flags
3
5000 2 64
Integer
FIELD
DEVICE
EXTERNAL
POWER
POWER
EXTERNAL
-
+
DEVICE
FIELD
POWER
EXTERNAL
DEVICE
FIELD
USER SUPPLIED
120 OHM
TERMINATION RESISTOR
++
A
B
A
B
A
B
--
Register
Sensors
SS500 /
SS2000 /
SS3000
Function
1.2.2 Module and Device Wiring
Connect the device(s) to the communications port on the module using 16
to 24 AWG wiring. Figures 3 and 4 show sample wirings between the
module and several sensor types. Figures 5 through 17 show the wiring
diagrams for each supported devices.
Slave
Num
Conv
Value
Figure 3. Module Wiring FB107 (Generic)
8 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Note: S1, Port B - Half Duplex Set, Term On
FIELD
DEVICE
EXTERNAL
POWER
POWER
EXTERNAL
-
+
DEVICE
FIELD
POWER
EXTERNAL
DEVICE
FIELD
USER SUPPLIED
120 OHM
TERMINATION RESISTOR
++
A
B
A
B
A
B
--
Figure 4. Module Wiring for ROC800 (Generic)
Figure 5. Wiring diagram for Daniel Model
3812 Liquid Ultrasonic Meter
Figure 7. Wiring diagram for Fisher Easy-
Drive Actuator
Figure 6. Wiring diagram for Daniel Mark III
Gas Ultrasonic Meter
Figure 8. Wiring diagram for Micro Motion
Direct Connect 700 Core Processor and 800
Enhanced Core Processor
Revised May-2016 9
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 9. Wiring diagram for 1700 / 2700
Micro Motion Transmitter
Figure 11. Wiring diagram for Micro Motion
7829 Viscosity Meter
Figure 10. Wiring diagram for Micro Motion
7826 / 7828 Density Meter
Figure 12. Wiring diagram for Platinum BMS-
731 Burner Manager
Figure 13. Wiring diagram for Rosemount 3300
Guided Wave Radar Level
10 Revised May-2016
Figure 14. Wiring diagram for Rosemount 3095
MV Transmitter
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
485 to RS-232 converter.
Figure 15. Wiring Diagram for Krohne
Altosonic V12 Ultrasonic Meter
Figure 16. Wiring Diagram for Spectra Sensors
SS500 / SS2000 / SS3000
Note: The Spectra Sensor devices do not
provide an RS-485 port, requiring a RS-
Figure 17. Wiring Diagram for Sick Maihak FlowSic600 Ultrasonic Meter
Note: By default, the RS-485 port on the FLOWSIC600 uses the SICK
Modbus ASCII protocol. You must change this to generic Modbus
RTU protocol using the MEPAFLOW600 configuration software.
1.3 Module Requirements
The Modbus Express module is compatible with version 1.60 (or greater) of
the FB107 firmware, with
firmware, with version 1.30 (or greater) of the ROC800L firmware and
with version 2.10 (or greater) of the ROCLINK 800 software.
Revised May-2016 11
version 3.51 (or greater) of the ROC800 Series 2
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
12 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Chapter 2 – Installation
This chapter provides instructions for installing the Modbus Express
module. Read Section 1.3 of this manual for the module requirements.
Note: You can install only one Modbus Express module in either the
ROC800 or the FB107.
2.1 Installing the Application Module
The application module occupies the standard footprint of an FB107 or
ROC800 I/O or communications module.
To install the module in ROC800, place it in any empty slot on the
ROC800. To install the module in FB107, remove power to the FB107.
Place the module in an empty slot (1 through 7) on the FB107 and reapply
power.
To ensure that the FB107 and ROC800 recognizes the module, you must
perform a warm start (ROC > Flags > Warm Start).
Note: Although the label on the physical module is APP 485, the
Modules (for FB107) or the User Display (for ROC800) from the
Directory Tree verifies that this module contains the Modbus
Express application. See Figures 18 and 19.
Figure 18. Modbus Express Module (FB107)
Revised May-2016 13
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 19. Modbus Express Module (ROC800)
Once you have verified that the ROC800 has recognized the Modbus
Express module, proceed to Chapter 3 to begin configuring the module.
2.2 Updating the Application Module
The ROC800 version of the Modbus Express module is factory-loaded to
use displays 69, 70, 71, and 72. If you have previously installed another
application that already uses one of those displays, you must update the
module’s firmware using the Modbus Express Module 1.01 ALT.BIN file,
which provides the same functionality using displays 73, 74, 75, and 76.
Contact Technical Support for a copy of the ALT.BIN file.
For further information on updating firmware, refer to Section 9.1 Update
Firmware, in Chapter 9 of the ROCLINK 800™ Configuration Software
User Manual (for ROC800 Series), (part D301250X012).
2.3 MPU Loading Threshold (ROC800)
To maximize the performance of your ROC800 device, always verify the
performance of specific application combinations before using them in the
field to ensure the MPU load typically remains below 85% with peak
MPU loading levels below 95%.
14 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
To check the current MPU load at any time, select ROC > Information >
Other Information and review the value in the MPU loading field.
Figure 20. MPU Loading
Revised May-2016 15
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
16 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Chapter 3 – Configuration
After you have successfully installed the Modbus Express module in the
FB107 or ROC800, you configure the module using four module-specific
screens (Setup, Master Table, Registers, and Expanded Registers). Use the
Modbus Master Configuration screen to configure communications with
the device(s).
You must configure the module before you can establish communications
with the device(s). To configure the module (after logging onto
ROCLINK 800 and successfully installing the module) proceed through
the screens as shown in this chapter.
Note: The configurations screens of the Modbus Express module for both
the ROC800 and FB107 platform are identical.
You can access the module-specific screens from the main ROCLINK 800
screen:
Figure 21. ROCLINK 800 (FB107)
Revised May-2016 17
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
3.1 Setup Screen
Figure 22. ROCLINK 800 (ROC800)
Use this screen to configure the communications with Modbus devices and
to add, edit, or delete Modbus devices. The Setup screen has three tabs
(Configure, Add Device, and Edit/Delete Device).
To Access this screen:
1. From the Directory Tree, double-click User Display if you use
ROC800 or Modules > Slot #, Modbus Express Mod if you use
FB107.
Note: For FB107, the Slot # indicates the slot where you install your
Modbus Express module. For example, if you install your
Modbus Express module in slot 2, then you double-click
Module > Slot 2, Modbus Express Mod from the directory
tree.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 23. Modbus Setup screen
Follow Section 3.1.1 through Section 3.1.3 to configure the Configure,
Add Device, and Edit/Delete Device tabs.
3.1.1 Setup – Configure Tab
Use this screen (which displays when you first access the Setup screen) to
configure the comm port settings, Modbus protocol settings, and the
Modbus mode for your Modbus devices.
Revised May-2016 19
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Figure 24. Setup – Configure screen
1. Review the values in the following fields:
Point Number
Baud Rate
Parity
Data Bits
Stop Bits
Selects the Modbus Express screen to
configure. Available option is Setup
configuration screen only.
Sets, in bits per second, the baud rate this
comm port uses when transmitting and
receiving data. The default value is 19.2 kbps.
Indicates whether the communications
controller performs parity checks. The parity
value can be odd, even, or none. The default
value is None.
Sets the number of data bits contained in an
asynchronous byte or character. The default is
8.
Sets the number of stop bits contained in an
asynchronous byte or character. The default is
1.
20 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Byte Order
Sets the order of data bytes in a transmission
or requests, which can be reversed. This only
affects the Data field of a Modbus message
and has no effect on the data bytes for
Function Codes 01, 02, and 05. Valid values
are Least Significant Byte First (places the
Least Significant Byte first; this is the default
value) and Most Significant Byte First (places
the Most Significant Byte first).
Comm Mode
Sets the communications mode for the selected
comm port. The Modbus protocol supports two
modes of transmission, ASCII and RTU. RTU
is the default.
Note: You must configure all devices in the
ASCII
same communications network with the
same mode of transmission. Additionally,
in either ASCII or RTU mode, the
transmitting device places the Modbus
message into a frame that has a known
beginning and ending point.
American Standard Code for
Information Interchange mode
represents each 8-bit byte of data as
two ASCII characters that are the
hexadecimal representation of the
value. This allows the messages to
be read with the use of a dumb
terminal, but uses twice as many
characters as the RTU mode. Each
character sent is composed of a start
bit, 7 or 8 data bits, and one or two
stop bits with Even, Odd, or No
parity. ASCII mode uses Longitudinal
Redundancy Checking (LRC) error
checking.
Revised May-2016 21
RTU
Poll Master Table
Once
Controls whether the system begins a Modbus
Master polling sequence. Click to perform an
on-demand poll of the Modbus master table.
Remote Terminal Unit mode allows
for greater character density and
better data throughput than ASCII for
the same baud rate. Each message
is transmitted in a continuous stream.
Data is sent in 8-bit binary
characters. RTU mode uses Cyclic
Redundancy Check (CRC) error
checking. This is the default.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Indicates whether the system continually
Starting Request
Number of Requests
Timeout
Sets a beginning value from which the Modbus
Master polling sequence begins. This number
corresponds to a line number on the Modbus
Master Table associated with this comm port
(Point Number 1, 1–25 and Point Number 2,
26–50).
Sets the total number of requests the Modbus
Master makes for this polling sequence. This
value specifies the total number of lines in the
Master tables on which to execute the polls.
The default value 0 prevents the polling from
occurring.
Note: The tables are contiguous. If you
indicate requests that are more than a
single table, the system accesses the
second table to complete the request.
Sets the amount of time, in seconds, that the
Master (Host) waits to receive a valid message
after the FB107 or ROC800 sends a request to
a device.
Note: A value less than 1 may not give
enough time for a response and may
fail.
Retries
Continuous Polling
Request Delay
Good Messages
Bad Messages
Sets the number of times (after the initial try)
that the Master, FB107 or ROC800, attempts to
establish communications with the specified
device before reporting a timeout error. Valid
values are between 0 and 255; the default is 2.
executes the Modbus Master polling sequence.
Valid values are Enabled (polling occurs
continually) or Disabled (polling occurs only as
requested).
Note: Use the Request Delay field to
schedule the continual polling.
Sets a delay time, in seconds, between polling
sequences. A polling sequence includes all
requests defined in the Number of Requests
field.
Note: This field is valid only when you enable
Continuous Polling.
Indicates the number of valid responses the
module has received.
Indicates the number of invalid responses the
module has received.
22 Revised May-2016
2. Click Apply to save any changes you have made to this screen.
3. Proceed to Section 3.1.2 to configure the Setup – Add Device Tab.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
3.1.2 Setup – Add Device Tab
Use this screen to select and configure Modbus device. To access the
screen:
1. Select the Add Device tab on the Setup Screen. The Add Device
screen displays:
Note: The green box around the section indicates that the section is
active and configurable.
Figure 25. Setup – Add Device screen
Revised May-2016 23
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Sets the RTU address for the slave device to
be queried.
Sets a custom tag up to 10 characters in length
you can define for the device.
Enables the advanced options for adding a
device.
Allows master table adjustments. This
parameter activates only when you select the
Advanced option.
Allows communication settings adjustments
This parameter activates only when you select
the Advanced option.
Sets the location in master table to where the
device is added. This parameter shows only
when you select the Advanced option.
24 Revised May-2016
Register Start
Sets the location in registers table to where the
device is added. This parameter shows only
when you select the Advanced option.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Description (1-8)Sets the description for additional registers.
This parameter shows only when you select
the Advanced option.
Function Code (1-8) Sets the function code to be used for the added
registers. This parameter shows only when you
select the Advanced option.
Slave Register (1-8) Configures the slave register to be polled.
Shows only when you select the Advanced
option and activates only when the function
code is not disabled.
Number of Registers
(1-8)
Conversion Code
Add Device –
Automatic Mode
Add Device –
Advanced Mode
Sets the number of slave registers to be polled.
Shows only when you select the Advanced
option and activates only when the function code is not set to disabled.
Sets the conversion code to be used for the
additional registers. Shows only when you
select the Advanced option and activates only
when the function code is not set to disabled.
Shows the status or error for devices added
automatically. This shows by default or when
you uncheck the Advanced option.
Shows the status or error for devices added
manually. Shows only when you select the
Advanced option
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.1.3 to configure the Setup – Edit/Delete Device
Tab.
3.1.3 Setup – Edit/Delete Device Tab
Use this screen to edit and delete Modbus devices. To access the screen:
Revised May-2016 25
1. Select the Edit/Delete Device tab on the Setup Screen. The
Edit/Delete Device screen displays:
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Figure 27. Setup – Edit/Delete Device screen
2. Review the values in the following fields:
Device Type (1-6)Sets the device type.
RTU Address (1-6)Sets the RTU address for the device to be
queried.
Custom Name (1-6) Shows the custom name entered from Add
device tab.
Master Table Start
(1-6)
Master Table End
(1-6)
Register Start (1-6) Shows where in the Registers Table this
Register End (1-6) Shows where in the Registers Table this
Shows where in the Master Table this device's
entries begin.
Shows where in the Master Table that this
device's entries end.
device's entries begin. A value of 0 indicates
the device is not configured.
device's entries end. A value of 0 indicates the
device is not configured.
26 Revised May-2016
Pack Master Table
Pack Registers
Status/Error
Deletes empty Master Table fields and makes
the entries contiguous.
Deletes empty Registers Table fields and
makes the entries contiguous.
Show the status error of the added devices
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
3. Click Apply to save any changes you have made to this screen.
4. Click Close to return to the main ROCLINK 800 screen. Proceed to
Section 3.2 to configure the Master Table Screen.
3.2 Master Table Screen
Use this screen to configure the Modbus Express master table. The module
uses 50 Master Table entries (25 for each logical). To access this screen:
1. From the Directory Tree, double-click User Display if you use
ROC800 or Modules > Slot #, Modbus Express Mod if you use
FB107.
Note: For FB107, the Slot # indicates the slot where you install your
Modbus Express module. For example, if you install your
Modbus Express module in slot 2, then you double-click
Module > Slot 2, Modbus Express Mod from the directory
tree.
Figure 28. Master Table screen
3. Review the values in the following fields:
Revised May-2016 27
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Point Number
RTU Address (1-25), (26-50)
Function Code
(1-25), (26-50)
Slave Register
(1-25), (26-50)
Selects the Modbus master table to configure.
Click
Sets the RTU address for the device to be
queried.
Note: The Master Table screen has two
Sets the Modbus function code to be sent to
the device. Click
codes.
Note: The Master Table screen has two
Sets the starting register number from which
data is drawn from the device. Valid values are
1 to 65535.
Note: The Master Table screen has two
to display all available master tables.
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point Number field to access rows 26-50.
to display all valid function
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point Number field to access rows 26-50.
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point
Number field to access rows 26-50.
Master Register
(1-25), (26-50)
Number of Registers
(1-25), (26-50)
Sets the starting register number into which
data is stored on the device. Valid values are 1
to 65535.
Notes:
This number corresponds to the Value field
on the Register screen.
The Master Table screen has two
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point Number field to access rows 26-50.
Sets the total number of registers to poll.
Note: The Master Table screen has two
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point Number field to access rows 26-50.
28 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
0
Inactive
1
Timeout Error
2
Addr Check
3
Function Code Error.
4
Num of Exp Bytes
5
RCV Slave Resp
6
CRC/LRC Check
7
CRC/LRC Check
8
Valid Response Received
128
Write Data Error
129
Acc Dev Data
130
Master Table Error
131
Trans Timeout
144
Tx/Rx Buff Ovr
145
Invalid Func #
Conversion Code
(1-25), (26-50)
Sets the type of conversion performed (if any)
on data before it is either sent to the host or
written to the FB107 or ROC800. The
conversions accommodate differences in data
types between the devices. Conversion codes
affect Function Codes 3, 4, 6, and 15. Click
to display all valid conversion codes:
0 = No Conversion
25 = Any type to FLOAT
26 = Any type to signed short
27 = Any type to signed long
28 = Any type to unsigned short
29 = Any type to unsigned long
30 = Any type to unsigned byte
57 = Any type to signed long 0,1,2,3
58 = Any type to signed long 1,0,3,2
59 = Any type to signed long 2,3,0,1
60 = Any type to signed long 3,2,1,0
61 = Any type to unsigned long 0,1,2,3
62 = Any type to unsigned long 1,0,3,2
63 = Any type to unsigned long 2,3,0,1
64 = Any type to unsigned long 3,2,1,0
65-72 = IEEE Floating Point Number
Note: The Master Table screen has two
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point
Number field to access rows 26-50.
Comm Status (1-25),
(26-50)
This read-only field shows the status of the
query.
Note: The Master Table screen has two
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point Number field to access rows 26-50.
Revised May-2016 29
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field
Description
Device (1-25), (26-50) Shows the custom name of the device.
Note: The Master Table screen has two
continuous sections; rows 1-25 and rows
26- 50. Rows 1-25 are shown by default.
Select 2 - MTbl 26-50 using the Point
Number field to access rows 26-50.
4. Click Apply to save any changes you have made to this screen.
5. Click Close to return to the ROCLINK 800 screen. Proceed to Section
3.3 to configure the Register screen.
3.3 Registers Screen
The module uses 200 registers (50 for each logical) to store data read from
or written to the devices. All register values are in float or register data
types that depend on the conversion codes you use. To access this screen:
1. From the Directory Tree, double-click User Display if you use
ROC800 or Modules > Slot #, Modbus Express Mod if you use
FB107.
Note: For FB107, the Slot # indicates the slot where you install your
Modbus Express module. For example, if you install your
Modbus Express module in slot 2, then you double-click
Module > Slot 2, Modbus Express Mod from the directory
tree.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 29. Registers screen
3. Review—and change as necessary—the values in the following fields:
Field Description
Point Number
Tag
Register Value
Integer (1-50), (51-
100), (101-150), and
(151-200)
Register Value Float
(1-50), (51-100), (101-
150), and (151-200)
Selects one of the four register logicals. Click
to display all available Registers tables.
Sets a unique identifier for the selected table.
Shows or sets the integer value for each register.
Note: The Registers table screen has four
continuous sections; rows 1-50, rows 51100, rows 101-150, and rows 151-200.
Rows 1-50 are shown by default. Select 2
- Reg 51-100 using the Point Number
field to access rows 51-100. Use the other
Point Number options to access the rest
of the rows.
Shows or sets the floating value for each
register.
Note: The Registers table screen has four
continuous sections; rows 1-50, rows 51100, rows 101-150, and rows 151-200.
Rows 1-50 are shown by default. Select 2
- Reg 51-100 using the Point Number
field to access rows 51-100. Use the other
Point Number options to access the rest
of the rows.
Revised May-2016 31
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field Description
Register Tag (1-50),
(51-100), (101-150),
and (151-200)
Device (1-50), (51-
100), (101-150), and
(151-200)
4. Click Close to return to the ROCLINK 800 screen. Proceed to Section
3.4 to configure the Expanded Registers screen.
3.4 Expanded Regs Screen
Shows or sets a unique identifier for each
register.
Note: The Registers table screen has four
continuous sections; rows 1-50, rows 51100, rows 101-150, and rows 151-200.
Rows 1-50 are shown by default. Select 2
- Reg 51-100 using the Point Number
field to access rows 51-100. Use the other
Point Number options to access the rest
of the rows.
Shows the device’s custom name.
Note: The Registers table screen has four
continuous sections; rows 1-50, rows 51100, rows 101-150, and rows 151-200.
Rows 1-50 are shown by default. Select 2
- Reg 51-100 using the Point Number
field to access rows 51-100. Use the other
Point Number options to access the rest
of the rows.
Use this screen to configure the Expanded Registers. To access this
screen:
1. From the Directory Tree, double-click User Display if you use
ROC800 or Modules > Slot #, Modbus Express Mod if you use
FB107.
Note: For FB107, the Slot # indicates the slot where you install your
Modbus Express module. For example, if you install your
Modbus Express module in slot 2, then you double-click
Module > Slot 2, Modbus Express Mod from the directory
tree.
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 30. Expanded Registers screen, Register Type – Disabled
Figure 31. Expanded Registers screen, Register Type – Floating Point
Revised May-2016 33
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Figure 32. Expanded Registers screen, Register Type – Integer
Figure 33. Expanded Registers screen, Register Type – Digital
3. Review—and change as necessary—the values in the following fields:
34 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field Description
Point Number
Selects one of the twenty-five expanded register
logicals.
Tag
Sets a unique identifier for the selected expanded
register table.
Link to Register
Register Type
Set which register the expanded register maps to.
Sets the register type.
Float Value
Float Manual
Value
Units
Floating Point
Alarm
Shows the live floating value
for the register. This
parameter shows only when
Register Type is set to
Floating Point.
Sets the manual float value
for the register. This
parameter shows only when
Register Type is set to
Floating Point.
Configures the units for the
register. This parameter
shows only when Register
Type is set to Floating
Point or Integer.
Sets the floating alarm. This
parameter shows only when
Register Type is set to
Floating Point.
Low Alarm Value
High Alarm Value
Alarm Deadband
Val.
Use Manual Float
Override
Clip Float Value to
Alarm Range
Sets the low alarm value.
This parameter shows only
when Register Type is set
to Floating Point.
Sets the high alarm value.
This parameter shows only
when Register Type is set
to Floating Point or Integer.
Sets the alarm deadband
value. This parameter shows
only when Register Type is
set to Floating Point or
Integer.
Configures float override.
This parameter shows only
when Register Type is set
to Floating Point or Integer.
Sets float value clipping.
This parameter shows only
when Register Type is set
to Floating Point.
Revised May-2016 35
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field Description
Integer Value
Integer Manual
Value
Integer Alarm
Use Manual Int
Override
Clip Int Value to
Alarm Range
Show Integer Bits
Shows the live integer value
for the register. This
parameter shows only when
Register Type is set to
Integer.
Sets the manual integer
value for the register. This
parameter shows only when
Register Type is set to
Integer.
Sets the integer alarm. This
parameter shows only when
Register Type is set to
Integer.
Configures float override.
This parameter shows only
when Register Type is set
to Integer.
Sets integer clipping to
alarm range. This parameter
shows only when Register Type is set to Integer.
Shows integers as bits. This
parameter shows only when
Register Type is set to
Integer.
Digital Status
Digital Manual
Status
Digital Alarm
Use Manual
Digital Status
Override
Enables or disables the
digital register type. This
parameter shows only when
Register Type is set to
Digital.
Sets the manual digital
status for the register. This
parameter shows only when
Register Type is set to
Digital.
Sets the digital alarm mode.
The digital alarm selections
include: disable alarms,
enable on set alarms, enable
on clear alarms, and enable
on change alarms. This
parameter shows only when
Register Type is set to
Digital.
Enables manual digital
status override. This
parameter shows only when
Register Type is set to
Digital.
36 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Field Description
Invert Status
Active Alarms
4. Click Close to return to the ROCLINK 800 screen. Proceed to Section
3.5 to save the configuration.
3.5 Saving the Configuration
Whenever you modify or change the configuration, it is a good practice to
save the final configuration to memory. To save the configuration:
1. Select ROC > Flags. The Flags screen displays:
Sets user interface options.
This parameter displays
only when you select Digital
as the Register Type.
Shows the active alarms.
Figure 34. Flags
2. Click Save Configuration. A verification message displays:
Figure 35. Save Verification
3. Click Yes to begin the save process. The Flash Write Status field on
the Flags screen displays In Progress. When the process ends, the
Flash Write Status field on the Flags screen displays Completed.
Revised May-2016 37
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
4. Click Update on the Flags screen. This completes the process of
saving your new configuration.
Note: For archive purposes, you should also save this configuration to
your PC’s hard drive or a removable media (such as a flash drive)
using the File > Save Configuration option on the ROCLINK 800
menu bar.
38 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Adding a Device using
From the Setup (Display #69) Configuration Screen, select the Add
Chapter 4 – Usage
This chapter describes quick start procedures and best practices for the
Modbus Express module.
4.1 Quick Start Procedures
Defaults Settings
Device tab. A green box around the Device area indicates the portion of
the display that is active.
1. Select a device from the Device Type pull-down menu and click the
Apply button. (If the device is not using the factory default RTU
address, you may optionally enter a custom address and a short custom
name for the device. When you leave those fields empty, the Modbus
Express module uses the program defaults.)
2. Click Update. The Status/Error box shows a Ready to Add message
and the green box highlights the Edit and Add Device buttons.
Note: It takes time before the changes to propagate.
3. Click the Add Device button. After a moment, click Update. The
Status/Error box displays Device Added message.
To verify if you successfully added the device, select the Edit/Delete
Device tab from the Setup configuration screen. The screen shows all the
devices you added with the default RTU Address and Custom Name.
Other entries will show where in the Master Table the device is (start to
end) and where in the Registers table the device registers are (start to end).
To begin polling, select the Configure tab of the Setup configuration
screen, select Enabled from the Continuous Polling section and click
Apply. Click Auto Scan to enable auto refresh of the display (remember to
turn it off later), or click Update periodically to verify if the Good
Messages count is increasing. If Bad Messages count increases, the device
is either incorrectly wired or the comm port settings do not match the
default communication settings the Modbus Express module uses.
The Modbus Express Module - Master Table (Display #70) screen also
displays the entries of the device you add for further verification. The
Comm Status and Comm Status Description columns indicate the statuses
of each Master Table entry.
To check if the data are being polled from the device, view the Modbus Express Module - Registers (Display #71) screen and check if the
Register entry of the device you add (either in the Integer column or
Floating column) contains a value other than 0 or 0.0.
Revised May-2016 39
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Deleting a Device
Packing the Master
Table/Registers
To delete a device:
1. Open the Edit/Delete Device tab of the Setup (Display #69)
configuration screen.
2. Check the box(es) of the device(s) you wanted to delete then click
Apply.
3. Click Update. The Status/Error field should show Ready to
Delete/Pack.
4. Click the Delete/Pack then wait a moment before you click
Update. The Status/Error shows Device Deleted. This resets the
device entries to empty or zero values.
Note:
If desired, you can reset the Starting Request and Number of
Request Values using the Configure tab of the Setup (Display #69)
configuration screen.
The Modbus Express module ignores empty Master Table entries.
If you delete a device, you may leave gaps in the Master Table or
Registers table. For example, if you add three devices and the first
device takes Master Table entries 1-3, the second takes entries 4-9, and
the third takes entries 10-15, the deletion of the second device leaves
entries 4-9 empty.
Disabling Automatic
Comm Port or Master
Mode Configuration
(Advanced Mode)
If this is undesirable, you can check the Pack Master Table the
Edit/Delete Device tab of the Modbus Express Module – Setup
(Display #69) configuration screen to remove the empty entries. So, If
you select Pack Master Table the first device still occupies entries 13, the former third device (originally entries 10-15) moves down to 510 and so on. The same thing applies to the Registers. This is to make
more contiguous empty entries in the tables for adding new devices.
You can access the Advanced mode using the Add Device tab on the
Modbus Express Module – Setup (Display #69) configuration screen.
When you enable the Advanced mode, you can override the automatic
setting of the Master Mode and the comm port settings.
When you uncheck the Set Master Mode Start/Num Reqs, the
module prevents the automatic setting of the Master Mode such as
setting the starting entry and the number of requests. When you
uncheck the Set Comm Port to Defaults, the module prevents
automatic configuration of the RS485.
If you add a device with different comm port settings than factory
defaults, enable the Advanced mode and uncheck Set Comm Port Device Defaults.
40 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
manual entries made by the user.
Overriding Custom
Table Index Entries
(Advanced Mode)
Adding Extra Modbus
Registers
(Advanced Mode)
When in Advanced mode, you can specify the location of your
device’s entries in the Master Table and Registers table. If you specify
Master Table Start to be 10, the device's Master Table entries start at
10. If a device is already present or if table spaces are not enough to
accommodate the entries, the module returns an error. The same thing
applies for device registers if you specify the Registers Start value.
This feature is applicable if you are sectioning your device’s entries in
the Registers table. Since each Registers table is made up of four
columns with 25 registers each (1-25, 26-75, etc.), you can add a
device with less than 25 registers at entry 1, then the second device at
entry 26, the third device at entry 76, and so on. This places the device
entries in each column of the Registers table. This feature does not
affect any process.
You can add up to eight additional Master Table entries for the device
to enable polling of additional custom device registers. You can add
any device registers. After you add the device, these registers appear in
the Master Table and Registers entry for the device. If you delete the
device, the module deletes these additional entries along with the
default entries. The entries also move along with default entries if you
pack the Master Table or Registers.
Manually Adding
Master Table and
Registers
You can set a custom Register tag name for each extra modbus register.
If you add and entry that polls multiple registers and only entered the
description of first entry, the first Register uses the description name
you enter plus a generated name of "+RegXXX" where "XXX" is an
offset from the Register value. For example, if you enter “Volume” in
the first register at register 3000, you first register name is “Volume”
plus “+Reg3002”, “+Reg3004”, etc. You can change these generated
names in the Modbus Express Modules - Registers (Display #71)
configuration screen.
You can configure the Modbus Express module manually to add
devices that are not natively supported by the module.
You must manually configure the Master Table start and end request
entries to include any manual Master Table entries you add. You must
enable Continuous Polling using the Configure tab of the Setup
configuration screen.
Note: Any devices added by Express Mode will not overwrite any
Revised May-2016 41
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Monitor the Good
When you enable Continuous Polling, the Good Messages counter
4.2 Best Practices
Messages Counter
Check the Master Table
Comm Status field
increments for each line in the Master Table that is successfully polled.
Any FST or other application that monitors Modbus Express Registers
should verify that the Good Messages count is incrementing. If not, the
Registers data may not be accurate. If you detect this situation, check
the Master Table status.
Note: The baud rate of the comm port, the number of slave registers
being polled in the Master Table, and the Request Delay value
all impact how often the Good Messages counter increments.
Reading the Register values may happen faster than the Modbus
Express module can retrieve data from the device(s).
If you configure a device is with ten Master Table entries, each entry
has a Comm Status value of 8 indicating that the last poll was
successful. If Good Messages value appears to stop incrementing, an
FST can scan through the Master Table Comm Status parameters for
the device and look for error indicators.
Note: Both Good Messages and Comm Status should be checked to
verify an error. In the event of some failure of the Modbus
Express module, such as the disconnected cable, the Comm
Status values remain in the last successful polling but do not
indicate any error.
To verify errors:
1. Check if the Good Messages has incremented since the last check.
2. If Good Messages does not increment, check Master Table –
Comm Status fields for the device being polled and check for nonsuccessful status codes.
3. Handle this potential error as needed.
42 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Chapter 5 – Reference Materials
This section provides tables of information on the point types the Modbus
Express module uses.
For the FB107:
Point Type 68 (Modbus Express Setup)
Point Type 69 (Modbus Master Table)
Point Type 70 (Modbus Registers)
Point Type 71 (Modbus Expanded Registers)
For the ROC800:
Point Type 247 (Modbus Express Setup)
Point Type 248 (Modbus Master Table)
Point Type 249 (Modbus Registers)
Point Type 250 (Modbus Expanded Registers)
Revised May-2016 43
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
5.1 Point Type 68/247: Modbus Express Setup
Point type 68 (for FB107) or 247 (for ROC800) contains configuration parameters for the Modbus Express App Module as a whole. There is a
single logical for this point type.
Point Type 68/247: Modbus Express Setup
Parm
#
0 Point Tag ID R/W User AC 10
1 Baud Rate R/W User UINT8 1 0-3 3 1.00 Sets the baud rate for the RS-
2 Data Bits R/W User UINT8 1 0-1 8 1.00 Sets the data bits.
3 Stop Bits R/W User UINT8 1 0-1 1 1.00 Sets the stop bits.
4 Parity R/W User UINT8 1 0-2 0 1.00 Sets the parity.
5 Transmission Mode R/W User UINT8 1 0-1 0 1.00 Controls the type of
6 Byte Order R/W User UINT8 1 0-1 0 1.00 Controls which byte is sent out
Name Access
System or
User Update
Data Type Length Range Default Version
0x20 → 0x7E for
each ASCII
character
"EasyMB Cfg" 1.00 Sets point type description
Description of functionality
and meaning of values
485 communication port
0 = 2400
1 = 4800
2 = 9600
3 = 19200
7 = 7 bits
8 = 8 bits
1 = 1 bit
2 = 2 bits
0 = None
1 = Odd
2 = Even
transmission mode desired.
0 = RTU Mode
1 = ASCII Mode
first for floats, short integers,
and long integers.
0 = LSB first (Associated with
little-endian processors)
1 = MSB first (Associated with
big-endian processors)
44 Revised May-2016
Point Type 68/247: Modbus Express Setup
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Parm
#
7 Master Poll Trigger R/W User UINT8 1 0-1 0 1.00 Controls the initiation of a
8 Master Start Reg
Num
9 Master Num
Requests
10 Master Cont Poll
Enable
11 Master Poll Delay R/W User UINT32 4 0-86400 (24 hrs) 1 1.00 Contains the delay time in
12 Master Poll Timeout R/W User UINT16 4 0-3600 (1 hr) 1 1.00 Contains the amount of time in
13 Master Poll Retries R/W User UINT8 1 0-255 3 1.00 Sets the number of times a
14 Number of Good
Msgs
Name Access
R/W User UINT8 1 0-255 0 1.00 Sets on which row the scanning
R/W User UINT8 1 0-255 0 1.00 Sets the number of rows to be
R/W User UINT8 1 0-1 0 1.00 Controls whether the Modbus
R/W System UINT32 4 0-4294967295 0 1.00 Indicates the number of good
System or
User Update
Data Type Length Range Default Version
Description of functionality
and meaning of values
Modbus master polling
sequence.
0 = Idle
1 = Enable a one-time pass
through the Master Table.
begins.
polled. The polling starts on
what is set in Master Start Reg
Num.
master poll request sequence.
0 = Disabled
1 = Continuously poll the
configured Master Table, with a
Master Poll Delay between
each scan.
seconds between continuous
master poll requests (Continous
poll mode only).
seconds the module will wait for
a response from a device
before marking it as timeout
error.
Master Table row will be retried
in the event of a timeout.
Modbus responses received
from all devices.
Revised May-2016 45
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Point Type 68/247: Modbus Express Setup
Parm
#
15 Number of Bad Msgs R/W System UINT32 4 0-4294967295 0 1.00 Indicates the number of bad
16 Device 1 Type R/W User UINT8 1 0-15 0 1.00 Selects the type of device.
17 Device 1 Address R/W User UINT8 1 0-255 0 1.00 Sets the Modbus slave address
18 Device 1 Name R/W User/System AC10 10
19 Device 1 Table Start R/W User UINT1 1 0-50 0 1.00 Sets the starting row for this
20 Device 1 Table End R/W User UINT8 1 0-50 0 1.00 Sets the last row for this device
250 = Bad Conversion Code
251 = Invalid Device Type
selected
252 = Unable to Delete/Pack
253 = Master Table Full
255 = Registers Full
255 = Device Table Full
Revised May-2016 57
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
5.2 Point Type 69/248: Modbus Master Table
Point type 69 (for FB107) or 248 (for ROC800) contains configuration parameters for the Modbus Master Table. There are two logicals for
this point type.
Point Type 69/248: Modbus Master Table
Parm
#
0 Point Tag ID R/W User AC10 10
1 Slave Address 1 R/W User UINT8 1 0-255 0 1.00 Sets the device RTU address
2 Function Code 1 R/W User UINT8 1 0-6, 15-16 0 1.00 Sets the Modbus function code:
3 Slave Register 1 R/W User UINT16 2 0-65535 0 1.00 Sets the device register
4 Master Register 1 R/W User UINT8 1 0-200 0 1.00 Sets the App module register
5 Number of Registers 1 R/W User UINT8 1 0-255 0 1.00 Sets the number of registers to
Name Access
System or
User Update
Data
Type
Length Range Default Version
0x20 → 0x7E for
each ASCII
character
"Master
Tbl X"
where X
is the
logical
1.00 Sets the point type description.
Description of functionality and
meaning of values
0 = Disabled
1 = Read logic coil status
2 = Read discrete input status
3 = Read output registers
(holding)
4 = Read input registers
5 = Force single logic coil
6 = Preset single holding register
15 = Force multiple logic coils
16 = Preset multiple holding
registers
request from device
58 Revised May-2016
Point Type 69/248: Modbus Master Table
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Parm
#
6 Conversion Code 1 R/W User UINT8 1 0, 25-30, 57-74 0 1.00 Sets the conversion code:
Name Access
System or
User Update
Data
Type
Length Range Default Version
Description of functionality and
meaning of values
0 = No Conversion
25 = Any type to FLOAT
26 = Any type to signed short
27 = Any type to signed long
28 = Any type to unsigned short
29 = Any type to unsigned long
30 = Any type to unsigned byte
57 = Any type to signed long
0,1,2,3
58 = Any type to signed long
1,0,3,2
59 = Any type to signed long
2,3,0,1
60 = Any type to signed long
3,2,1,0
61 = Any type to unsigned long
0,1,2,3
62 = Any type to unsigned long
1,0,3,2
63 = Any type to unsigned long
2,3,0,1
64 = Any type to unsigned long
3,2,1,0
65-72 = IEEE FLOATing Point
Number
Revised May-2016 59
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Point Type 69/248: Modbus Master Table
Parm
#
7 Comm Status 1 R System UINT8 1 0-9, 128-131,
…
Name Access
System or
User Update
Data
Type
Length Range Default Version
0 1.00 Shows the last poll status.
144-145
Description of functionality and
meaning of values
0 = Inactive
1 = Timeout Error
2 = Addr Check
3 = Function Code Error
4 = Num of Exp Bytes
5 = Rcv Slave Resp
6 = CRC/LRC Check
7 = CRC/LRC Check
8 = Valid Slave Resp
128 = Write Data Err
129 = Acc Dev Data
130 = Master Table Error
131 = Trans Timeout
144 = Tx/Rx Buff Ovr
145 = Invalid Func #
Note: Parameters 1-7 repeat up to 25 times, once for each Master Table entry.
169 Slave Address 25 R/W User UINT8 1 0-255 0 1.00 Sets the slave RTU address
170 Function Code 25 R/W User UINT8 1 0-6, 15-16 0 1.00 Sets the Modbus function code:
0 = Disabled
1 = Read logic coil status
2 = Read discrete input status
3 = Read output registers
(holding)
4 = Read input registers
5 = Force single logic coil
6 = Preset single holding register
15 = Force multiple logic coils
16 = Preset multiple holding
registers
171 Slave Register 25 R/W User UINT16 2 0-65535 0 1.00 Sets the device register
172 Master Register 25 R/W User UINT8 1 0-200 0 1.00 Sets the App module register
60 Revised May-2016
Point Type 69/248: Modbus Master Table
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Parm
#
173 Number of Registers 25 R/W User UINT8 1 0-255 0 1.00 Sets the number of registers to
174 Conversion Code 25 R/W User UINT8 1 0, 25-30, 57-74 0 1.00 Sets the conversion code:
Name Access
System or
User Update
Data
Type
Length Range Default Version
Description of functionality and
meaning of values
request from the device
0 = No Conversion
25 = Any type to FLOAT
26 = Any type to signed short
27 = Any type to signed long
28 = Any type to unsigned short
29 = Any type to unsigned long
30 = Any type to unsigned byte
57 = Any type to signed long
0,1,2,3
58 = Any type to signed long
1,0,3,2
59 = Any type to signed long
2,3,0,1
60 = Any type to signed long
3,2,1,0
61 = Any type to unsigned long
0,1,2,3
62 = Any type to unsigned long
1,0,3,2
63 = Any type to unsigned long
2,3,0,1
64 = Any type to unsigned long
3,2,1,0
65-72 = IEEE FLOATing Point
Number
Revised May-2016 61
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Point Type 69/248: Modbus Master Table
Parm
#
175 Comm Status 25 R System UINT8 1 0-8, 128-131,
Name Access
System or
User Update
Data
Type
Length Range Default Version
144-145
Description of functionality and
meaning of values
0 1.00 Shows the last poll status.
0 = Inactive
1 = Timeout Error
2 = Addr Check
3 = Function Code Error
4 = Num of Exp Bytes
5 = Rcv Slave Resp
6 = CRC/LRC Check
7 = CRC/LRC Check
8 = Valid Slave Resp
128 = Write Data Err
129 = Acc Dev Data
130 = Master Table Error
131 = Trans Timeout
144 = Tx/Rx Buff Ovr
145 = Invalid Func #
62 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
5.3 Point Type 70/249: Modbus Registers
Point type 70 (for FB107) or 249 (for ROC800) contains the registers (50 per logical) that the module uses to store data it reads from and
writes to slave devices. This point type has four logicals.
Point Type 70/249: Modbus Registers
Parm
#
0 Point Tag ID R/W User AC10 10
1 Register Value U32 1 R/W User UINT32 4 0-4294967295 0.0 1.00 Shows or sets the integer value
2 Register Value Float 1 R/W User FLOAT 4 Any valid IEEE
3 Register Tag 1 R/W User AC10 10
...
Name Access
System or
User Update
Data
Type
Length Range Default
0x20 → 0x7E for
each ASCII
character
floating point
0x20 → 0x7E for
each ASCII
character
"Registers
X", where X
is the logical
0.0 1.00 Shows or sets the floating value
“” 1.00 Sets the description for register 1.
Version Description of functionality and
meaning of values
1.00 Sets the point type description.
for register number 1.
for register number 1.
Note: Parameters 1-3 repeat up to 50 times, once for each Master Table entry.
148 Register Value U32
50
149 Register Value
FLOAT 50
150 Register Tag 50 R/W User AC10 10
R/W User UINT32 4 0-4294967295 0.0 1.00 Sets the holding parameter for the
value of register 50 if register is
an integer (else 0).
R/W User FLOAT 4 Any valid IEEE
floating point
0x20 → 0x7E for
each ASCII
character
0.0 1.00 Sets the holding parameter for the
value of register 50 if register is
floating point (else 0.0).
“” 1.00 Sets the description for register
50.
Revised May-2016 63
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
5.4 Point Type 71/250: Modbus Expanded Registers
Point type 71 (for FB107) or 250 (for ROC800) contains the expanded registers. This point type has twenty-five logicals.
Point Type 71/250: Modbus Expanded Registers
Parm
#
0 Point Tag ID R/W User AC10 10
1 Expanded Register
2 Parent Register R/W User UINT8 1 1-200 0 1.00 Shows or sets which register this
3 Float Value R System FLOAT 4 Any valid IEEE
4 Float Manual Value R/W User FLOAT 4 Any valid IEEE
5 Float Alarm Low
6 Float Alarm High
7 Float Alarm
8 Integer Value R/W User UINT32 4 0-4294967295 0 1.00 Shows the live value read from
9 Integer Manual Value R/W User UINT32 4 0-4294967295 0 1.00 Shows or sets the value for the
10 Integer Alarm Low
11 Integer Alarm High
Name Access
R/W User UINT8 1 0-3 0 1.00 Shows or sets the I/O type for the
Type
R/W User FLOAT 4 Any valid IEEE
Value
R/W User FLOAT 4 Any valid IEEE
Value
R/W User FLOAT 4 Any valid IEEE
Deadband Value
R/W User UINT32 4 0-4294967295 0 1.00 Shows or sets the integer alarm
Value
R/W User UINT32 4 0-4294967295 110 1.00 Sets the integer alarm high value.
Value
System or
User Update
Data
Type
Length Range Default
0x20 → 0x7E for
each ASCII
character
floating point
floating point
floating point
floating point
floating point
"Exp Reg X",
where X is
the logical
0.0 1.00 Shows the live value read from
0.0 1.00 Shows or sets the value for the
-10.0 1.00 Shows or sets the float alarm low
110.0 1.00 Shows or sets the float alarm high
2.0 1.00 Shows or sets the float alarm
Version Description of functionality and
meaning of values
1.00 Shows or sets the Point Type
description.
expanded register:
0 = Disabled
1 = Floating Point
2 = Integer
3 = Digital
expanded register maps to.
the register, in floating point form.
register in floating point form.
value.
value.
deadband value.
the register, in integer form.
register in integer form.
low value.
64 Revised May-2016
Point Type 71/250: Modbus Expanded Registers
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Parm
#
12 Integer Alarm
13 Units R/W User AC10 10 0x20 – 0x7E for
14 Digital Status R System UINT8 1 0-1 0 1.00 Shows if the digital status is active
15 Digital Manual Status R/W User UINT8 1 0-1 0 1.00 Sets status for the register in
16 Alarm Mode R/W User UINT8 1 0-15 0 1.00 Configures the alarm mode:
17 Alarm Status R System U8 1 0-255 0 1.00 Shows the alarm status:
0 = All alarms disabled
Bit 0 = Floating point alarm
enabled
Bit 1 = Integer alarm enabled
Bit 2-3 = Digital alarm bits
Bit 2 (4) = Digital alarm on set
Bit 3 (8) = Digital alarm on clear
Bit 2 & 3 (12) = Digital alarm on
change
0 = No alarm
Bit 0 = Low Alarm
Bit 1 = Low Low Alarm (unused)
Bit 2 = High Alarm
Bit 3 = High High Alarm (unused)
Bit 4 = Rate Alarm (unused)
Bit 5 = Digital Alarm
Bit 6 = Point Fail Alarm (unused)
Bit 7 = Scanning Disabled
(unused)
Revised May-2016 65
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
Point Type 71/250: Modbus Expanded Registers
Parm
#
18 Exp Reg UI Flags R/W User UINT8 1 0-255 0 1.00 Configures the user interface
Name Access
System or
User Update
Data
Type
Length Range Default
Version Description of functionality and
meaning of values
flags:
Bit 0 = Float manual override
Bit 1 = Float clipping
Bit 2 = Int manual override
Bit 3 = Int clipping
Bit 4 = Digital override
Bit 5 = Digital invert
Bit 6 = unused
Bit 7 = Show Int as bits
66 Revised May-2016
Modbus Express Module Instruction Manual (ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
Revised May-2016 67
Modbus Express Instruction Manual (ROC800-Series and FloBoss 107)
For customer service and technical support,
Global Headquarters,
North America, and Latin America:
are marks owned by one of the companies in the Emerson Process Management
business unit of Emerson Electric Co. Emerson Process Management, Emerson and the Emerson
Europe:
Middle East/Africa:
Asia-Pacific:
T +65 6777 8211| F +65 6777 0947
visit www.EmersonProcess.com/Remote/Support.
Emerson Process Management
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445
www.EmersonProcess.com/Remote
Emerson Process Management
Remote Automation Solutions
Unit 8, Waterfront Business Park
Dudley Road, Brierley Hill
Dudley UK DY5 1LX
T +44 1384 487200 | F +44 1384 487258
Emerson Process Management
Remote Automation Solutions
Emerson FZE
P.O. Box 17033
Jebel Ali Free Zone – South 2
Dubai U.A.E.
T +971 4 8118100 | F +971 4 8865465
Remote Automation Solutions, a business unit of Emerson Process Management, shall not be
liable for technical or editorial errors in this manual or omissions from this manual. REMOTE
AUTOMATION SOLUTIONS MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WITH
RESPECT TO THIS MANUAL AND, IN NO EVENT SHALL REMOTE AUTOMATION SOLUTIONS BE
LIABLE FOR ANY INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING,
BUT NOT LIMITED TO, LOSS OF PRODUCTION, LOSS OF PROFITS, LOSS OF REVENUE OR USE
AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER,
AND CLAIMS OF THIRD PARTIES.
Emerson Process Management Ltd, Remote Automation Solutions (UK), is a wholly owned
subsidiary of Emerson Electric Co. doing business as Remote Automation Solutions, a business
unit of Emerson Process Management. FloBoss, ROCLINK, ControlWave, Helicoid, FBxConnect,
and OpenEnterprise are trademarks of Remote Automation Solutions. AMS, PlantWeb, and the
PlantWeb logo
logo are trademarks and service marks of the Emerson Electric Co. All other marks are property
of their respective owners.
The contents of this publication are presented for informational purposes only. While every
effort has been made to ensure informational accuracy, they are not to be construed as
warranties or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. Remote Automation Solutions reserves the right to modify
or improve the designs or specifications of such products at any time without notice. All sales
are governed by Remote Automation Solutions’ terms and conditions which are available upon
request. Remote Automation Solutions does not assume responsibility for the selection, use or
maintenance of any product. Responsibility for proper selection, use and maintenance of any
Remote Automation Solutions product remains solely with the purchaser and end-user.
Remote Automation Solutions
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.