Remote Automation Solutions Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107 Flow Managers) Manuals & Guides

Part D301753X012
May 2016
Micro Motion® Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107 Controllers)
Remote Automation Solutions
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Page
Revision
All pages
May-2016
All pages
August-2015
All pages
May-2015
Initial release
February-2014

Revision Tracking Sheet

May 2016
This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):
ii Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)

Contents

Chapter 1 – Introduction 1
1.1 Scope and Organization ................................................................................................................. 1
1.2 Product Overview ........................................................................................................................... 2
1.3 Program Requirements .................................................................................................................. 3
Chapter 2 – Installation 5
2.1 Installing the Module ....................................................................................................................... 5
2.2 Wiring the Module ........................................................................................................................... 5
2.3
MPU Loading Threshold (ROC800) ............................................................................................... 8
Chapter 3 – Configuration 9
3.1 Coriolis Setup and Values Screen ................................................................................................ 10
3.1.1 Coriolis Setup and Values – General Tab ..................................................................... 12
3.1.2 Coriolis Setup and Values – Calibration Tab ................................................................. 15
3.1.3 Coriolis Setup and Values – Diagnostics Tab ................................................................ 17
3.1.4 Coriolis Setup and Values – Smart Meter Verification ................................................... 20
3.1.5 Coriolis Setup and Values – TBR/TMR ......................................................................... 22
3.1.6 Coriolis Setup and Values – Meter Zero ........................................................................ 25
3.1.7 Coriolis Setup and Values – Units Configuration ........................................................... 27
3.1.8 Coriolis Setup and Values – Values .............................................................................. 28
3.1.9 Coriolis Setup and Values – Current Dump Cycle ......................................................... 33
3.1.10 Coriolis Setup and Values – Dump Cycle Min/Max Data .............................................. 35
3.1.11 Coriolis Setup and Values – PVR .................................................................................. 38
3.2 Saving the Configuration .............................................................................................................. 40
Chapter 4 – Reference 43
4.1 Point Type 65/244: Micro Motion Coriolis Interface Module ......................................................... 44
Revised May-2016 iii
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
[This page is intentionally left blank.]
iv Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)

Chapter 1 – Introduction

Caution
When using inputs that are not resident in the flow computer or RTU (that is, are provided by a communication mechanism) for control, ensure that a supervisory system or mechanical safety equipment is in place to provide proper function. While communication errors are noted in the device’s alarm log, be aware that you may need to perform actions to prevent field issues.
This chapter describes the structure of this manual and presents an overview of the Micro Motion® Coriolis Interface module for the FloBoss 107 Flow Manager (FB107) and the ROC800-Series Remote Operations Controller (both the ROC800 and the ROC800L). The Coriolis Interface module provides all of the functions necessary to communicate with the core processor of a Micro Motion Coriolis meter and includes an onboard RS-485 communications port that enables communications between the module and the Coriolis meter without using one of the communications ports of the FB107 or the ROC800/ROC800L.
Additionally, in simple allocation situations which do not require custody transfer, one Coriolis Interface module (which connects with up to six Coriolis meters) can take the place of transmitters. In situations requiring custody transfer and the pulse counts transmitters provide, connecting the Coriolis Interface module to the transmitter provides extensive real-time analysis of flow data.
APP 485 application modules for the ROC800/ROC800L and FB107 (including the Micro Motion Coriolis Interface module) streamline the installation process by automatically installing all point types and screens that are part of the application. APP 485 modules can house a variety of applications; for further information about additional APP 485 modules, contact your sales representative.

1.1 Scope and Organization

This document serves as the user manual for the Micro Motion Coriolis Interface Module, which is intended for use in a FB107 or ROC800/ROC800L. This manual describes how to install and configure the Coriolis Interface module (referred to as the “Coriolis Interface” or “the module” throughout the rest of this manual). You access and
configure this module using ROCLINK 800 configuration software loaded on a personal computer running Microsoft® Windows 2000 (with Service Pack 2), Windows XP, Windows Vista, or Windows 7.
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software, the manual becomes a reference tool.
This manual has the following major sections:
Revised May-2016 Introduction 1
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Chapter 1 – Introduction Chapter 2 – Installation Chapter 3 – Configuration Chapter 4 – Reference
This manual assumes that you are familiar with the FB107 and the ROC800/ROC800L and its configuration. For more information, refer to the following manuals:
FloBoss™ 107 Flow Manager Instruction Manual (part
D301232X012).
ROC800-Series Remote Operations Controller Instruction Manual
(part D301217X012).
ROCLINK™ 800 Configuration Software User Manual (for
FloBoss™ 107) (part D301249X012).
ROCLINK™ 800 Configuration Software User Manual (for
ROC800-Series) (part D301250X012).
ROCLINK™ 800 Configuration Software User Manual (for
ROC800L) (part D301246X012).

1.2 Product Overview

The MMI Coriolis Interface module enables the FB107 or the ROC800/ROC800L to communicate directly with the core processor in up to 6 (4 on the FB107) Micro Motion Coriolis meters on the same EIA-485 (RS-485) communications port. (The module provides its own communications port for this purpose.) The module serves as an interface between Coriolis meters, transmitters, and the FB107 or ROC800/ROC800L, retrieving, validating, and then processing the data.
By supporting multiple core processors or transmitters at one time, the module eliminates the need to have one transmitter for each core processor. Additionally, it removes the need for a water cut probe in a 2­phase separator for liquid output. Finally, it manages transient mist remediation (TMR), transient bubble remediation (TBR), production value reconciliation (PVR), meter zeroing, and Smart Meter Verification (provided these functions are activated on the Coriolis meter’s core processor).
The module operates in either continuous mode (during which flow never ceases) or dump cycle mode (during which, should flow drop below a minimum setpoint, the module stops accumulating flow, counts cycles, and stores cycle-specific data).
Using Modbus, the module continuously requests data from the meters. When it receives new data, the module compares the volume flow rate from the meter to the user-defined volume low flow cutoff value and performs the following actions:
If the value of the volume flow rate register is zero, the
parameters in the module’s point type corresponding to the values
2 Introduction Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
received from the meter are updated, and no further processing of the data is performed.
If the value is greater than zero but less than the volume low
flow cutoff value, the module considers the volume and mass
accumulated to be trickle flow. The accumulated volume and mass values are added to both the daily totals parameters and the separate trickle flow totals.
If the value of volume flow rate is greater than the module’s low
flow cutoff value, the module considers the values received during
the period at which the volume flow rate remains above the volume low flow cutoff value to be part of a dump cycle. The module keeps track of the total volume and mass accumulated during a dump cycle, and updates the volume and mass totals once the dump cycle has ended. The maximum and minimum density and drive gain values that occurred during the dump cycle are also determined.
The module uses the contract hour you define using ROCLINK 800 to determine when a new contract day has begun. The module stores the maximum and minimum density and drive gain values, the number of dump cycles, and the volume and mass accumulators for the current and previous contract days. When a new contract day is reached, the module saves the values for the current contract day as the previous day values, and then resets the current day values. The module also records monthly totals for volume, mass, and the number of dump cycles. The module zeroes totals at the beginning of a new month, which occurs on the contract hour of the first day of a new month.
Note: The totals shown on the Values tab are based on the specified
contract hour. These totals are independent from the Force End of Day selection (ROC > Information), and are not updated when you perform a Force End of Day.
The continuous mode is designed to measure gas or liquid flow when the flow is not coming from a separator monitoring system. In this mode the module continuously requests data from the meters, retrieving and saving values for Total Volume for Today, Yesterday Total Volume, Yesterday's, Monthly and the accumulated value since the last reset. The module retrieves and saves mass values for the same periods.
Note: In case of a communications failure, the module is set to “hold
last value.”

1.3 Program Requirements

The Micro Motion Coriolis Interface module is compatible with version
1.70 (or greater) of the FB107 firmware, with version 3.61 (or greater) of the ROC800 firmware, with version 1.41 (or greater) of the ROC800L firmware, and with version 2.40 (or greater) of the ROCLINK 800 configuration software.
Revised May-2016 Introduction 3
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Device Type
Firmware Version
If used in conjunction with user programs, the Micro Motion Coriolis Interface module works with version 1.02 (or greater) of the Linear Meter Flow Calculation program.
The Coriolis Interface module supports the following firmware versions of these core processors and transmitters:
700 Core Processors V3.42 or greater
800 Enhanced Core Processor V4.14 or greater
1500 Transmitter V6.6 or greater
1700 Transmitter V6.6 or greater
2500 Transmitter V6.6 or greater
2700 Transmitter V6.6 or greater
3000-Series Transmitter V8.40 or greater
Note: The comm settings for the Interface module are fixed at a baud
rate of 19,200, no parity, 8 data bits, and 1 stop bit. You cannot change these values; the meter’s core processor detects this protocol and matches them automatically. However, if you are using transmitters, you must use Micro Motion’s ProLink® software to change the comm settings on those transmitters to match these settings.
4 Introduction Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
General Procedure
Installation requires that you perform a number of steps in a specific

Chapter 2 – Installation

This chapter provides instructions for installing the Coriolis Interface module. Read Section 1.3 of this manual for program requirements. The FB107 and the ROC800/ROC800L each support only one Coriolis Interface module.
Note: The FB107 can support only one APP 485 module. If you
already have an APP 485-based application in your FB107, consider which application is most appropriate for your needs.
sequence:
1. Power down the FB107 or ROC800/ROC800L.
2. Install the application module (refer to Section 2.1).
3. Wire the module (refer to Section 2.2).
4. Power up the FB107 or ROC800/ROC800L.
5. Configure the module (refer to Chapter 3).

2.1 Installing the Module

The application module occupies the standard footprint of an FB107 or ROC800/ROC800L I/O or communications module. Place the module in any empty slot on the ROC800/ROC800L or FB107.
To ensure that the device recognizes the module, you must perform a warm start (ROC > Flags > Warm Start).

2.2 Wiring the Module

Connect the Coriolis meter(s) to the communications port on the module using between 16 and 24 AWG wiring. Figure 1 and Figure 2 show example wiring between the module and several meters.
Note: Coriolis meters must be externally powered.
Revised May-2016 Reference 5
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
A
Micro Motion 700/800 Coriolis Meter with Internal Core Processor
B
Micro Motion MVD Direct Connect™ Safety Barrier
B
A
Figure 1. Module Wiring
6 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
A
Micro Motion 700/800 Coriolis Meter with Internal Core Processor
B
Micro Motion 1700 (single variable), 2700 (multi-variable), or 3000-Series transmitter suited for use in a hazardous area
C
Micro Motion 1500 (single variable), 2500 (multi-variable), or 3000-Series transmitter suited for used in a non-hazardous area.
A
B
C
Figure 2. Module Wiring
For best results, all Micro Motion Coriolis meter and transmitters require 24Vdc power. The following table outlines the typical power draw for standard Coriolis meter configurations. When designing an application, consider these power requirements.
Table 1. Configuration Power Requirements
Configuration 24 VDC Current
Sensor with Core Processor Only 768 mW 32 mA
Sensor with Core Processor & Barrier 1440 mW 60 mA
Sensor with 1500-2500 Transmitter 3432 mW 143 mA
Sensor with 1700-2700 Transmitter 6000 mW 250 mA
Sensor with 3700 Net Oil Transmitter 7420 mW 309 mA
Revised May-2016 Configuration 7
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)

2.3 MPU Loading Threshold (ROC800)

To maximize the performance of your ROC800 device, always verify the performance of specific application combinations before using them in the field to ensure the MPU load typically remains below 85% with peak MPU loading levels below 95%.
To check the current MPU load at any time, select ROC > Information > Other Information and review the value in the MPU loading field.
Figure 3. MPU Loading
8 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)

Chapter 3 – Configuration

After you have successfully installed the MMI Coriolis Interface module and wired the meter to the module, start ROCLINK 800 and configure the module using the Coriolis Setup and Values screen (see Section 3.1). Use the screen – and its component tabs – to configure communications with the Coriolis meter, perform calibration, view flow rates and totals, and view diagnostic information.
To ensure that the device recognizes the module, you must perform a warm start (ROC > Flags > Warm Start).
Note: Once the module is installed, you can identify a ROC800
Coriolis Interface module from the label on the face of the module. On the FB107, the label is on the side of the physical case. Using ROCLINK 800, click the APP 485 module shown in the ROCLINK 800 graphic display. A label appears identifying the module (see Figures 3 and 4).
Figure 4. Micro Motion Coriolis Interface Module (FB107)
Revised May-2016 Configuration 9
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
For the ROC800
1. From the Directory Tree, double-click User Display.
For the FB107
1. From the Directory Tree, double-click Application Module.
Figure 5. Micro Motion Coriolis Interface Module (ROC800)
You must configure the module before you can establish communications with the Coriolis meter. To configure the module (after successfully installing and wiring the module) proceed through the screens as shown in this chapter.

3.1 Coriolis Setup and Values Screen

Note: The Coriolis Setup and Values screen is identical for both the
FB107 and ROC800/ROC800L.
Use this screen to configure communications with the Coriolis meter, perform meter calibration, view flow rates and totals, and view diagnostic information. To access this screen:
2. Double-click Display #66 – Coriolis Setup and Values. The
Coriolis Setup and Values screen displays.
2. Double-click MMI Coriolis Intfc.
3. Double-click Display #66, Coriolis Setup and Values.
4. Double-click 1 – Meter #1. The Coriolis Setup and Values screen
displays.
10 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field
Description
Figure 6. Coriolis Setup and Values
Notes:
The Coriolis Setup and Values screen has a tab format. Sections
3.1.1 through 3.1.11 discuss the requirements for each tab on the
Coriolis Setup and Values screen.
Two fields (Point Number and Meter Tag) at the top of the
screen appear on all tabs (see Figure 5).
For many fields on these screens, bracketed numbers follow the
field labels (see Figure 5). These numbers identify the specific Modbus register in the Coriolis meter’s core processor that provides the value.
1. Review the values in the following fields:
Point Number
Meter Tag
Selects the Coriolis meter to configure. Click to display a drop-down menu of all meters.
Sets a short (10-character) identifier for the selected Coriolis meter.
Revised May-2016 Configuration 11
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Note: The default value for the Point Number field is x – Meter#x,
corresponding to the number of meters your device supports (1 – Meter#1, 2 – Meter#2, and so on). Similarly, Meter Tag is the default value for the Meter Tag field until you provide a value. The values displayed in the examples in this documentation are for illustrative purposes only and do not reflect the factory default.
2. Click Apply to save any changes you have made to this screen.
3. Proceed to Section 3.1.1 to configure the General tab.

3.1.1 Coriolis Setup and Values – General Tab

Use this tab (which displays when you access the Coriolis Setup and Values screen) to configure communications with one or more Coriolis meters, configure and enable polling, and set communications parameters.
Figure 7. Coriolis Setup and Values – General Tab
12 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field
Description
1. Review the values in the following fields:
Communications
Modbus Address
Poll Timeout
Number of Retries
Actual Poll Period
Enter the Modbus address of the target Coriolis device. Valid values are 1–15, 32–47, 64–79, and 96–110. The default is 255.
Note: The Modbus address you select must be
unique and not assigned to any other meter connected to this module. That is, you cannot select Address 2 for meter 2 if that address is already assigned to meter 1.
Sets the amount of time, in seconds, the program waits to receive a response from a Coriolis meter. If a response is not received within the specified time period, the message is retried or the meter is marked with a response timeout status in the Comm Status field.
Sets the number of times the program attempts to successfully communicate with the selected Coriolis meter before issuing a response timeout status in the Comm Status field. If a meter does not respond within the specified number of retries, the program attempts to restore communications with the meter every 10 seconds.
This read-only field shows the period of time, in seconds, between meter polls.
Comm Status
This read-only field shows the current communication status with the selected meter. Valid values are Communication Disabled, Communicating, Configuring Slot Registers, Retrying, Response Timeout, Invalid CRC, Invalid Response Format, and Slot Register Configuration Failed, Slow Poll Mode, Reset Totals Failed, and Incompatible Target Device.
Note: “Slow poll mode” occurs when the
module’s poll request fails, all retries are exhausted, and the device is not responding (which might occur if the connecting wire has been cut). In this case, the device automatically slows polling, shifting from a once-per-second poll sequence to a once-every-10­seconds poll sequence. Once the communication problem is resolved, normal polling resumes within 10 seconds.
Revised May-2016 Configuration 13
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field
Description
using the Continuous Flow meter mode.
Poll Mode
Meter Mode
Flow Direction Mode
Enables polling between the module and the selected Coriolis meter. Valid values are
Enabled and Disabled. The default is Disabled.
Note: When you select Enabled, the module
re-synchronizes with the current value of the Coriolis device’s mass and volume accumulators. If any flow occurs during Disabled, it will not be recorded by the module accumulations. To avoid accumulation issues, you must assure the Coriolis device is in a state of no­flow when disabling polling.
Defines how the module handles flow. Valid values are Continuous Flow and Dump Cycle. The default is Continuous Flow.
For liquid flow measurement, use Dump Cycle mode. For gas flow measurement, use Continuous mode.
Sets the Flow Direction configured for the meter. The default is Forward Only.
Note: Bi-Directional is available only when
Live Coriolis Values
Volume Flow Rate
Mass Flow Rate
Sensor Temperature
This read-only field shows the current volume flow rate, as reported by the meter. Configure display units using the Units Configuration tab.
The Flow Direction Mode you select controls the values shown in this frame. Values in the Forward column display only if you select Forward Only or Bi-Directional. Values in the Reverse column display only if you select Reverse Only or Bi-Directional.
This read-only field shows the current mass flow rate, as reported by the meter. Configure display units using the Units Configuration tab.
The Flow Direction Mode you select controls the values shown in this frame. Values in the Forward column display only if you select Forward Only or Bi-Directional. Values in the Reverse column display only if you select Reverse Only or Bi-Directional.
This read-only field shows the current temperature value retrieved from the meter. You configure the display units using the Units Configuration tab.
14 Configuration Revised May-2016
Flowing Density
This read-only field shows the current density value retrieved from the meter. Configure display units using the Units Configuration tab.
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field
Description
Drive Gain
Micro Motion Coriolis Licensed Features
This read-only field shows, as a percentage, the current drive gain value.
This read-only field shows the specific licensed features of the Coriolis meter which are currently active.
2. Click Apply to save any changes you have made to this screen.
3. Proceed to Section 3.1.2 to configure the Calibration tab.

3.1.2 Coriolis Setup and Values – Calibration Tab

Use this screen to perform and view meter calibration factors. To access this screen:
1. Select the Calibration tab. The Calibration screen displays:
Figure 8. Coriolis Setup and Values – Calibration Tab
2. Review—and change as necessary—the values in the following
fields:
Field Description
Revised May-2016 Configuration 15
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field Description
Volume Flow Cutoff
Mass Flow Cutoff
Volume Flow Meter Factor
Mass Flow Meter Factor
Density Meter Factor
Flow Calibration Factor
Temperature Calibration Factor
Density Temp Correction (DT)
Sets the Volume Flow Cutoff value for the target Coriolis meter. The default is 0.
Sets the Mass Flow Cutoff value for the target Coriolis meter. The default is 0.
Sets the Volume Flow Meter Factor value for the target Coriolis meter. Valid values are from
0.8 to 1.2. The default is 0.
Sets the Mass Flow Meter value for the target Coriolis meter. Valid values are from 0.8 to 1.2. The default is 0.
Sets the Density Meter Factor value for the selected Coriolis meter. Enter any decimal value greater than zero. The system multiplies this value by the live density reading to produce the published density value.
Sets the Flow Calibration Factor value for the selected Coriolis meter. The default is 0.
Sets the Temperature Calibration Factor value for the selected Coriolis meter. The default is 0.
Sets the Density Temperature Correction value for the selected Coriolis meter. Valid values are from -20 to 20. The default is 0.0.
Density Flow Correction (FD)
Flow Calibration Pressure
Flow Damping
Density Calibration Points
Tube Periods
Slug Flow
Sets the Density Flow Correction value for the selected Coriolis meter. The default is 0.0.
Sets the Flow Calibration Pressure value of the selected Coriolis meter. Enter any decimal value greater than zero. The default is 0.0.
Sets the flow rate internal damping in seconds. Valid values are from 0 to 60 seconds. The default is 0.0.
Sets the values for Density Calibration Point 1 (D1) and Density Calibration Point 2 (D2). Valid values are from 0 to 5 g/cc. The default is 0.0.
Sets the values for Tube Period D1 (K1) and Tube Period D2 (K2) from the physical Coriolis sensor plates. K1 is the tube period when the sensor is filled with a fluid of Density D1. K2 is the tube period when the sensor is filled with a fluid of Density D1. Both of these values are in units of microseconds. Valid values are from 1000 to 50000. The default is 0.0.
Sets, in g/cc, the high and low density values for slug flow. The high density limit should be greater than the low value. Valid values are from 0 to 5 g/cc. The default is 0.0.
16 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field Description
Pressure Correction Factor
External Input Values
Load Optimization
Correction of Mass and Density for Pressure
Sets the values for Pressure Correction Factor for flow and density. Valid values are from -0.1 to 0.1. The default is 0.0.
Sets the values for External Input Values for temperature and pressure. Valid temperature values range from –240 °C to 450 °C. Valid pressure values range from –.5 to 10000 BAR. The default for both is 0.0.
Enables Load Optimization. Valid values are Enabled and Disabled. Default is Disabled.
Enables the module to calculate compensation for the effect of high pressure on the measurement accuracy of the Coriolis mass flow and density.
This calculation requires that you first provide flow and density values for the Pressure Correction Factors, and you must provide a pressure value for the External Input Value. Valid values are Enabled and Disabled. The default is Disabled.
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.1.3 to configure the Diagnostics tab.

3.1.3 Coriolis Setup and Values – Diagnostics Tab

Use this screen to view the meter status and diagnostic messages for the selected Coriolis meter. To access this screen:
1. Select the Diagnostics tab. The Diagnostic screen displays:
Revised May-2016 Configuration 17
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Figure 9. Coriolis Setup and Values – Diagnostics Tab
2. Review the values in the following fields:
Field Description
Meter Status
Sensor Failure
Data Loss Possible
Flow Direction
Meter RTD Temp Out of Range
Line RTD Temp Out of Range
This read-only field shows the current status of the selected meter based on the value in the primary Coriolis status register. Valid values are Yes and No.
This read-only field shows the meter’s possibility of data loss. Valid values are Yes and No.
This read-only field shows the meter’s flow direction. Valid values are Forward or Reverse.
This read-only field shows whether the temperature for the meter’s RTD is out of range. Valid values are Yes and No.
This read-only field shows whether the temperature for the line’s RTD is out of range. Valid values are Yes and No.
18 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field Description
Density Outside Standard Range
Temp. Outside Standard Range
RAM Diagnostic Failure
EEPROM Checksum Failure
Drive Overrange
Density Outside of Limits
Communication Statistics
Number Requests Sent to Meter
This read-only field shows whether the meter’s reported density is outside of standard API ranges. Valid values are Yes and No.
This read-only field shows whether the meter’s temperature is outside of standard API ranges. Valid values are Yes and No.
This read-only field shows whether the RAM diagnostic procedure (initiated during a power reset) has failed. Valid values are Yes and No.
This read-only field shows whether the EEPROM Checksum procedure (initiated during a power reset) has failed. Valid values are Yes and No.
This read-only field shows whether the drive is outside of its proscribed range. Valid values are Yes and No.
This read-only field shows whether the density is outside of standard limits. Valid values are Yes and No.
This read-only field shows the total number of Modbus requests the module has sent to the selected meter.
Number of Good Responses
Number of Response Timeouts
Number of Error Reponses
Reset Comm Stats
Meter Information
Meter Model Type
Manufacturer ID
Device Type
This read-only field shows the total number of valid Modbus responses the module has received from the selected meter.
This read-only field shows the total number of instances when the program has not received a response within the timeout period from the selected meter.
This read-only field shows the total number of erroneous Modbus responses the module has received from the selected meter.
Click to reset all communication statistics values displayed in the Communication Statistics frame.
This read-only field shows the type of sensor for the selected meter. Valid values are Curved Tube and Straight Tube.
This read-only field shows the manufacturer’s ID for the selected meter.
This read-only field shows the specific type of meter or transmitter connected to the module.
Revised May-2016 Configuration 19
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Field Description
Current Pressure Compensation Effect on Flow
Current Pressure Compensation Effect on Density
Board Temperature
Input Voltage
Live Zero
Zero Standard Deviation
Raw Tube Frequency
Left Pickoff Voltage
This read-only field shows the current pressure compensation effect on flow of the Coriolis meter. Default value is 0.
This read-only field shows the current pressure compensation effect on density of the Coriolis meter. Default value is 0.
This read-only field shows the board temperature of the selected meter. Default value is 0.
This read-only field shows the input voltage of the selected meter. Default value is 0.
This read-only field shows the live zero in mass flow of the selected meter. Default value is 0.
This read-only field shows the zero standard deviation value of the selected meter. Default value is 0.
This read-only field shows the raw tube frequency in Hz of the selected meter. Default value is 0.
This read-only field shows the left pickoff voltage of the selected meter. Default value is
0.
Left Pickoff Amplitude
Right Pickoff Voltage
Right Pickoff Amplitude
This read-only field shows the left pickoff amplitude in volts of the selected meter. Default value is 0.
This read-only field shows the right pickoff voltage of the selected meter. Default value is
0.
This read-only field shows the right pickoff amplitude of the selected meter. Default value is 0.
3. Proceed to Section 3.1.4 to configure the Smart Meter Verification
tab.

3.1.4 Coriolis Setup and Values – Smart Meter Verification

Use this screen to view the Smart Meter Verification status for the selected Coriolis meter. This screen displays only if Smart Meter Verification is available for that sensor and only if that sensor is connected to a Coriolis meter using the 800 enhanced core processor.
Note: The message Feature not supported on this Micro Motion meter
displays if this meter does not support Smart Meter Verification.
To access this screen:
20 Configuration Revised May-2016
Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107)
Sets the value the meter uses when initiating the
with Output Fixed.
1. Select the Smart Meter Verification tab. The Smart Meter
Verification screen displays:
Figure 10. Coriolis Setup and Values – Smart Meter Verification Tab
2. Review—and change as necessary—the values in the following
fields:
Field Description
Output State
Stiffness Setpoint
Start Action
Current State
Percent Complete
Sets the output state of the Smart Meter during the verification procedure. Default is Last Value.
Sets the stiffness setpoint for the Smart Meter verification. Valid values range from 0.0025 to
0.4.
Smart Meter verification process. Default is Start
This read-only field shows the current state of the verification. Valid values are Stopped and Running.
This read-only field shows the completion percentage of the current verification procedure.
Revised May-2016 Configuration 21
Loading...
+ 57 hidden pages