Remote Automation Solutions Manuals & Guides: A6152 ROC300 Protocol Emulation Program (For ROC800-Series)|RAS Manuals & Guides

Form A6152
Part Number D301196X012 January 2009
ROC300 Protocol Emulation Program (for the ROC800-Series Remote Operations Controller) User Manual
Remote Automation Solutions
ROC300 Protocol Emulation Program User Manual
Revision Tracking Sheet
January 2009
This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):
Page Revision
All pages Jan-09 All pages Apr-08 All pages Feb-06 Initial release Jul-04
NOTICE
“Remote Automation Solutions (“RAS”), division of Emerson Process Management shall not be liable for technical or editorial errors in this manual or omissions from this manual. RAS MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THIS MANUAL AND, IN NO EVENT SHALL RAS BE LIABLE FOR ANY INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF PRODUCTION, LOSS OF PROFITS, LOSS OF REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF THIRD PARTIES.
Bristol, Inc., Bristol Canada, BBI SA de CV and Emerson Process Management Ltd, Remote Automation Solutions division (UK), are wholly owned subsidiaries of Emerson Electric Co. doing business as Remote Automation Solutions (“RAS”), a division of Emerson Process Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid are trademarks of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric Co. All other trademarks are property of their respective owners.
The contents of this publication are presented for informational purposes only. While every effort has been made to ensure informational accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or specifications of such products at any time without notice. All sales are governed by RAS’ terms and conditions which are available upon request.
RAS does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any RAS product remains solely with the purchaser and end-user.”
© 2004-2009 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.
ii Rev. Jan-09
ROC300 Protocol Emulation Program User Manual
Contents
Page
Chapter 1 – Introduction 1
1.1 Scope and Organization.......................................................................................................1
1.2 Product Overview.................................................................................................................1
1.2.1 Opcode Mappings by I/O Module Slot.....................................................................2
1.2.2 Events and Alarms Mapping....................................................................................3
1.2.3 Point Type Conversions...........................................................................................3
1.2.4 Unsupported Parameters.........................................................................................4
1.3 Program Requirements........................................................................................................4
Chapter 2 – Installation 7
2.1 Downloading the Program....................................................................................................7
Chapter 3 – Configuration 11
3.1 ROC Protocol Converter Configuration Screen.................................................................12
3.2 History Segment Configuration Screen..............................................................................14
3.3 Saving the Configuration....................................................................................................15
Chapter 4 – Reference 17
4.1 Supported Opcodes...........................................................................................................17
4.2 Point Types 1 to 8, 10, 12 to 17, 19, 40 to 42....................................................................18
4.2.1 Point Type 1: Discrete Input...................................................................................18
4.2.2 Point Type 2: Discrete Output................................................................................21
4.2.3 Point Type 3: Analog Input.....................................................................................23
4.2.4 Point Type 4: Analog Output..................................................................................26
4.2.5 Point Type 5: Pulse Input.......................................................................................28
4.2.6 Point Type 6: PID...................................................................................................30
4.2.7 Point Type 7: AGA Flow Parameters.....................................................................33
4.2.8 Point Type 10: AGA Flow Calculation Values........................................................38
4.2.9 Point Type 12: ROC Clock.....................................................................................40
4.2.10 Point Type 13: System Flags.................................................................................41
4.2.11 Point Type 14: Communication Ports ....................................................................43
4.2.12 Point Type 15: System Variables...........................................................................46
4.2.13 Point Type 16: FST Parameters ............................................................................48
4.2.14 Point Type 17: Soft Point Parameters....................................................................50
4.2.15 Point Type 19: Database Parameters....................................................................51
4.2.16 Point Type 40: Multi-Variable Sensor ....................................................................52
4.2.17 Point Type 41: Run Parameters (#1).....................................................................57
4.2.18 Point Type 42: Run Parameters (#2).....................................................................59
4.3 User Defined Point Type 69/76: Protocol Emulation Program Configuration....................61
Rev. Jan-09 iii
ROC300 Protocol Emulation Program User Manual
[This page is intentionally left blank.]
iv Rev. Jan-09

Chapter 1 – Introduction

This chapter describes the structure of this manual and presents an overview of the ROC300 Protocol Emulation program for the ROC800.

1.1 Scope and Organization

This document serves as the user manual for the ROC300 Protocol Emulation program which is intended for use in a ROC800-Series Remote Operations Controller (“ROC800”). This manual describes how to download, install, and configure the ROC300 Protocol Emulation program (referred to as the “ROC300 Protocol program” or “the program” throughout the rest of this manual). You access and configure this program using ROCLINK 800 Configuration Software loaded on an IBM­compatible personal computer running Windows® 2000 (with Service Pack 2), XP, or Vista.
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software, the manual becomes a reference tool.
ROC300 Protocol Emulation Program User Manual
This manual has the following major sections:
Section 1 – Introduction Section 2 – Installation Section 3 – Configuration Section 4 – Reference
This manual assumes that you are familiar with the ROC800-Series and their configuration. For more information, refer to the following manuals:
ROC809 Remote Operations Controller Instruction Manual (Form
A6116).
ROC827 Remote Operation Controller Instruction Manual (Form
A6175)
ROCLINK 800 Configuration Software User Manual (Form A6121).

1.2 Product Overview

The ROC300 Protocol Emulation program enables a ROC800 to respond to requests from a ROC protocol host driver, used in ROC300-Series Remote Operations Controllers and FloBoss Flow Managers. The program converts ROC Plus protocol point types (used in the ROC800) to ROC Protocol point types and parameters, where applicable. The program also allows you to use specific opcodes to receive and send data from the host to the ROC800.
Rev. Jan-09 1
ROC300 Protocol Emulation Program User Manual
The ROC800 receives requests from a host on a specified communications port. The program converts both ROC Plus protocol point types and parameters to ROC Protocol point types and parameters and ROC Plus protocol Type, Logical, and Parameter (TLPs) to analogous ROC protocol TLPs. The program enables you to use specific opcodes to receive data from the host and to send data from the ROC800. You can access all 200 history points in the ROC800 using opcode 130.
Once you have loaded this program and activated it for a given communications port (see Section 3.1), the ROC Plus Protocol communications are not available on that port. ROCLINK 800 will not connect and allow you to make configuration changes to that selected port. However, one way to have ROC Plus Protocol and the ROC300 Protocol Emulation program available on a given port is to write a supervisory FST program to control which protocol is active. For example, the FST command could be time-related to change the value of point type 69/76, logical 0, parameters 1 and 3 through 6. The parameter number indicates which comm port is active: 0 disables ROC300 Protocol Emulation while 1 enables it (see Section 4.3).
Note: Be careful if you change the baud rate for the comm port used for
ROC Protocol communications. (You define this using the System Configuration tab on the Device Information screen, accessed by selecting ROC > Information > Device Information screen.) If the host computer changes the baud rate of the port on which this program runs, this also changes the baud rate of any other ports on the same Baud Rate Generator.
For further information on the ROC and ROC Plus protocols, refer to ROC Plus Protocol User Manual (Form A6127), part number
D301180X012.
ROC Protocol User Manual (Form A4199), part number
D301053X012.

1.2.1 Opcode Mappings by I/O Module Slot

The host computer uses opcode 130 (see Section 4.1) to poll for values of all 200 history points either by RAM Area 0 to 6 (which corresponds to History Segments 0 to 6) and point numbers 0 to 29 or by RAM Area 0 only and point numbers 0 to 199. When the host computer requests I/O module TLPs, the program assigns logicals based on the module slot in which the I/O module is located:
2 Rev. Jan-09
ROC300 Protocol Emulation Program User Manual
Table 1. Opcode Mappings Based on I/O Module Slot
ROC800 Module Position
1 0 to 15 2 16 to 31 3 32 to 47 4 48 to 63
5 (Unavailable; reserved for System AIs) 64 to 79
6 80 to 95 7 96 to 111 8 112 to 127 9 128 to 143
1
Slots 1 to 4 and slots 6 to 9 (with the exception of slot 5) are available.
2
Logical ranges may change in future releases.
3
Table 1 assumes 16 points for each ROC800 module position.
1, 3
Logical Range2 (Maximum)

1.2.2 Events and Alarms Mapping

Whether the host computer can process certain alarm and event information from the ROC800 depends on how you configure this program and if the point type (or parameter) corresponds to a point type (or parameter) in the ROC Protocol. The ROC Protocol supports 240 alarms and 240 events. ROC800 can store up to 450 alarms and 450 events. During configuration (see Section 3.1) you indicate whether the program retains only the last 240 alarms or events or the full 450 alarms or events.
Note: The program always sends system events (such as warm starts or
cold starts) to the host, since these events have the same format in both the ROC and ROC Plus protocols.

1.2.3 Point Type Conversions

The program converts any ROC800 point type that can be converted to a ROC protocol, as shown in the following table. As appropriate for the point type, the program converts parameter numbers as well.
Table 2. ROC800 Point Type Conversions
ROC800 Point Type Converted to ROC Protocol Point Type
91 – System Variables 15 95 – Communication Ports 14 96 – FST Parameters 16 98 – Soft Point Parameters 17 99 – Configurable Opcode Table 0 101 – Discrete Inputs 1
Rev. Jan-09 3
ROC300 Protocol Emulation Program User Manual
ROC800 Point Type Converted to ROC Protocol Point Type
102 – Discrete Outputs 2 103 – Analog Inputs 3 104 – Analog Outputs 4 105 – Pulse Inputs 5 106 – RTD 3 107 – Thermocouple 3 108 – Multi-Variable Sensor 40 109 – System Analog Inputs 3 110 – PID Control Parameters 6 112 – Station Parameters 7 or 41 113 – Orifice Meter Run Configuration 7 or 41 114 – Orifice Meter Run Values 41 or 42 115 – Turbine Meter Run Configuration 7 116 – Turbine Meter Run Values 41 or 42 136 – ROC Clock 12

1.2.4 Unsupported Parameters

The program cannot support some parameters. If the host tries to access one of these unsupported parameters, the program may or may not send back an error, depending on the circumstances. The program has implemented the following rules to handle these parameters. These rules also apply when the Read-Only and Read-Write statuses don’t match.
Table 3. Unsupported Parameter Handling
If ROC Protocol Parameter is…
Read-Only Not Supported Return 0 or other appropriate Read-Only Read-Only Return actual value Error 105
Read-Only Read-Write Return actual value Error 105 Read-Write Not Supported Return 0 or other appropriate
Read-Write Read-Only Return actual value Error 105 Read-Write Read-Write Return actual value No error
And ROC Plus Parameter is…
Then Action on Read is…
default
default
Then Action on Write is…
Error 105
No error

1.3 Program Requirements

Two versions of the program are provided. The versions use different point types, but are identical in function. Only one program using a specific point type will run on the ROC at any given time. Load the program version which uses a point type set that does not conflict with programs currently running on the ROC.
4 Rev. Jan-09
ROC300 Protocol Emulation Program User Manual
Program specifics include:
User
Defined
Point
(UDP)
69 60,416 130 155,648 1.80 11
76 60,416 130 155,648 1.80 11
Flash
Used
(in bytes)
SRAM
Used (in
bytes)
DRAM
Used (in
bytes)
ROCKLINK
800 Version
Display
Number
File Name
ROCProtocol_69_v124.tar
ROCProtocol_76_v124.tar
Target
Unit/
Version
ROC800
2.10
ROC800
2.10
Note: You must connect a PC to the ROC800’s LOI port before starting the download. Also, display
#11 must be available for this program’s use.
For information on viewing the memory allocation of user programs, refer to the ROCLINK 800 Configuration Software User Manual (Form A6121).
Rev. Jan-09 5
ROC300 Protocol Emulation Program User Manual
[This page is intentionally left blank.]
6 Rev. Jan-09

Chapter 2 – Installation

This section provides instructions for installing the ROC300 Protocol Emulation program into the Flash memory on the ROC800. Read Section
1.3 of this manual for program requirements.

2.1 Downloading the Program

This section provides instructions for installing the program into the Flash memory on the ROC800.
Note: This manual shows the installation of RocProtocol_76_v124.tar.
Choose the program version that uses point types which do not conflict with programs currently installed on the ROC.
To download the program using ROCLINK 800 software:
1. Connect the ROC to your computer using the LOI port.
ROC300 Protocol Emulation Program User Manual
2. Start and logon to ROCLINK 800.
3. Select Utilities > User Program Administrator from the ROCLINK
menu bar. The User Program Administrator screen displays (see
Figure 1):
Figure 1. User Program Administrator
Rev. Jan-09 7
ROC300 Protocol Emulation Program User Manual
4. Select any empty program number into which to download the
program.
5. Click Browse in the Download User Program File frame. The Select
User Program File screen displays (see Figure 2).
6. Select the path and user program file to download from the CD-ROM.
(Program files are typically located in the Program Files folder on the CD-ROM). As Figure 2 shows, the screen lists all valid user program files with the .TAR extension:
Figure 2. Select User Program File
7. Click Open to select the program file. The User Program
Administrator screen displays. As shown in Figure 3, note that the Download User Program File frame identifies the selected program and that the Download & Start button is active:
8 Rev. Jan-09
ROC300 Protocol Emulation Program User Manual
Figure 3. User Program Administrator
8. Click Download & Start to begin loading the selected programs. The
following message displays:
Figure 4. Confirm Download
9. Click Yes to begin the download. When the download completes the
following message displays:
Figure 5. ROCLINK 800 Download Confirmation
10. Click OK. The User Program Administrator screen displays (see
Figure 6). Note that:
The Device User Program Environment frame reflects the use of
system memory.
The User Programs Installed in Device frame identifies the
installed program(s).
Rev. Jan-09 9
ROC300 Protocol Emulation Program User Manual
Figure 6. User Program Administrator
11. Click Close. The ROCLINK 800 screen displays and the download is
complete.
12. Proceed to Section 3 to configure the program.
10 Rev. Jan-09
ROC300 Protocol Emulation Program User Manual

Chapter 3 – Configuration

After you have loaded the ROC300 Protocol Emulation program on the ROC800, you configure the program using one ROCLINK 800 screen (History Segment Configuration) and a program-specific screen (ROC Protocol Converter).
Use the program-specific ROC Protocol Converter screen to enable the
conversion and set the number of events and alarms captured.
Use ROCLINK 800’s History Segment Configuration screen to
configure history segments for the program.
You can access the program-specific screen from the main ROCLINK 800 screen:
Figure 7. ROCLINK 800
Rev. Jan-09 11
ROC300 Protocol Emulation Program User Manual

3.1 ROC Protocol Converter Configuration Screen

Use this screen to enable the conversion and set the number of events and alarms.
Note: Whether the host computer can process certain alarm and event
information from the ROC800 depends on how you configure the program and whether the point type (or parameter) corresponds to a point type (or parameter) in the ROC protocol.
To access this screen:
1. From the Directory Tree, select User Program > Program #1,
RocProtocol.
2. Double-click Display #11, ROC Protocol Converter. The ROC
Protocol Converter configuration screen displays:
Figure 8. ROC Protocol Converter Configuration
3. Review—and change, if necessary—the values in the following fields:
Field Description ROC Protocol On
Existing Ports
Alarm Log Logic
12 Rev. Jan-09
Check one box to select a ROC800 communications port.
Note: Port #2, Ethernet COMM1, is not a valid
choice for this program.
Sets whether the ROC800 logs the most recent 240 alarms the ROC Protocol supports or the full 450 alarms the ROC Plus Protocol (and the ROC800) supports. Selecting Last 240 logs only the most recent 240 alarms.
ROC300 Protocol Emulation Program User Manual
Field Description
Note: If you select All 450, the ROC800 uses a
ROC Plus Protocol TLP for any alarms without a ROC Protocol equivalent.
Event Log Logic
IO Addressing Logic
Sets whether the ROC800 logs the most recent 240 events the ROC Protocol supports or the full 450 events the ROC Plus Protocol (and the ROC800) supports. Selecting Last 240 logs only the most recent 240 events.
Note: If you select All 450, the ROC800 uses a
ROC Plus Protocol TLP for any events without a ROC Protocol equivalent.
Sets whether the ROC800 exclusively uses modules with 16 points or if the program needs verify the number of points used for each module. Valid values are always 16 slots modules or 8 or 16 slots from Sys Param 50.
4. Click Apply to save any changes you have made to this screen.
5. Click OK to return to the ROCLINK 800 screen. Proceed to Section
3.2 to configure ROC800 history segments for use with this program.
Rev. Jan-09 13
ROC300 Protocol Emulation Program User Manual

3.2 History Segment Configuration Screen

Use this screen to configure history segments. The program can access all 200 history points in the ROC800, but you need to configure the ROC800 history segments specifically for the program. To access this screen:
1. Select Configure > History Segments from the ROCLINK menu bar.
The History Segment Configuration screen displays:
Figure 9. ROC Protocol Converter Configuration
2. Allocate history points to segments 01 through 07 (allocating a
maximum of 30 points to segments 01 through 06 and a maximum of 20 points to segment 07). Ensure that the following fields contain the following values:
Field Description Periodic Entries
Periodic Sample Rate
Daily Entries
Enter 840 for each segment used. Enter 60 for each segment used.
Enter 35 for each segment used.
3. Click Apply to save any changes you have made to this screen.
Note: Refer to the ROCLINK 800 Configuration Software User Manual
(Form A6121) for further information on configuring history segments.
4. Click OK to return to the ROCLINK 800 screen. Proceed to Section
3.3 to save the configuration.
14 Rev. Jan-09

3.3 Saving the Configuration

Whenever you modify or change the configuration, it is a good practice to save the final configuration to memory. To save the configuration:
1. Select ROC > Flags. The Flags screen displays:
ROC300 Protocol Emulation Program User Manual
Figure 10. Flags screen
2. Click Save Configuration. A verification message displays:
Figure 11. Perform screen
3. Click Yes to begin the save process. The Status field on the Flags
screen displays In Progress. When the process ends, the Status field on the Flags screen displays Completed.
4. Click Update on the Flags screen. This completes the process of
saving your new configuration.
Rev. Jan-09 15
ROC300 Protocol Emulation Program User Manual
[This page is intentionally left blank.]
16 Rev. Jan-09
ROC300 Protocol Emulation Program User Manual

Chapter 4 – Reference

This section provides tables of information on the point types and parameters the ROC300 Protocol Emulation program uses:
Supported Opcodes. Point Types. User Defined Point Types.

4.1 Supported Opcodes

The ROC300 Protocol Emulation program supports the following opcodes:
Table 4. Summary of Supported Opcodes
Opcode Description
0 Send general update such as I/O update, gas flows, and control loop status. 6 Send ROC configuration 7 Send current time and date.
8 Set new time and date. 10 Send data from configurable opcode tables. 11 Set data in configurable opcode tables.
103
120 Send pointers for alarm, event, and history logs. 121 Send specified number of alarms starting at specified alarm pointer. 122 Send specified number of events starting at specified event pointer. 130
165 Read history point configuration.
167 Send specified contiguous block of parameters. 171 Set parameters for specified point. 180 Send specified parameters. 181 Set specified parameters. 255
Send system information such as on and off times, manual and automatic alarm status, firmware version, and current time and date.
Send archived hourly and daily data for specified history point starting at specified history pointer.
Note: Writing history configuration is not supported.
Error messages transmitted by ROC in response to a request with i nvalid parameters or format.
Rev. Jan-09 17