Remote Automation Solutions LineGuard™ 2300 Program User Manual (FloBoss 107) Manuals & Guides

Remote Automation Solutions
Form A6251
Part Number D301346X012 March 2021
LineGuard™ 2300 Program User Manual (FloBoss 107)
LineGuard 2300 Program User Manual
ii Revised March-21
Contents
Chapter 1 – Introduction 1
1.1 Scope and Organization ................................................................................................................... 1
1.2 Product Overview ............................................................................................................................. 1
1.2.1 Basic Program Operation .................................................................................................... 2
1.3 Program Requirements .................................................................................................................... 6
1.3.1 License Key ......................................................................................................................... 6
Chapter 2 – Installation 7
2.1 Installing the License Key ................................................................................................................. 7
2.1.1 Installing a License .............................................................................................................. 7
2.2 Downloading the Program ................................................................................................................ 9
Chapter 3 – Configuration 13
3.1 LineGuard Status Screen ............................................................................................................... 14
3.1.1 LineGuard Status Screen – LineGuard Status tab ............................................................ 15
3.1.2 LineGuard Status – Log/Alarm Setup tab .......................................................................... 18
3.1.3 LineGuard Status – RoD Values tab ................................................................................. 21
3.2 LineGuard Valve Control Screen .................................................................................................... 22
3.2.1 LineGuard Valve Control – LineGuard Valve Control tab ................................................. 23
3.2.2 LineGuard Valve Control – Event Control tab ................................................................... 25
3.2.3 LineGuard Valve Control – Transmitter Fail tab ................................................................ 27
3.2.4 LineGuard Valve Control – Voltage Check tab.................................................................. 29
3.3 Saving the Configuration ................................................................................................................ 31
Chapter 4 – Reference Material 33
4.1 Point Type 22: LineGuard Pressure Log Configuration ................................................................. 34
4.2 Point Type 23: LineGuard Valve Control ........................................................................................ 38
LineGuard 2300 Program User Manual
Revised March-21 1
Chapter 1 – Introduction
This chapter describes the structure of this manual and presents an overview and installation instructions of the LineGuard 2300 Program for the FloBoss 107 (FB107).
1.1 Scope and Organization
This document serves as the user manual for the LineGuard™ user program for use in a FloBoss 107 (FB107). This manual describes how to download, install, and configure the LineGuard user program (referred to as the “LineGuard program” or “the program” throughout the rest of this manual). You access and configure this program using ROCLINK 800 Configuration Software (version 2.60 or greater) loaded on a personal computer (PC) running Windows® 2000 (with Service Pack 2), Windows XP (with Service Pack 3), Windows Vista (32-bit), or Windows 7 (32-bit).
The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software, the manual becomes a reference tool.
This manual has the following major sections:
Chapter 1 – Introduction Chapter 2 – Installation Chapter 3 – Configuration Chapter 4 – Reference
This manual assumes that you are familiar with the FB107 and its configuration. For more information, refer to the following manuals:
FloBoss 107 Flow Manager Instruction Manual (D301232X012) ▪ ROCLINK 800 Configuration Software User Manual (for FB107)
(D301249X012)
1.2 Product Overview
The LineGuard Electronic Linebreak Detection System is a self-contained pipeline monitoring and line break detection device. The device is intended to be installed at a pipeline valve site and is designated to provide data acquisition and supervisory control (both locally and remotely) of a single valve actuator.
The LineGuard product consists of standard FloBoss 107 Flow Manager hardware and firmware while a user program provides the LineGuard functionality. The program is responsible for pressure monitoring, data logging and valve control. Custom user-defined displays are available for configuring and monitoring the operation of the program.
LineGuard 2300 Program User Manual
2 Revised March-21
1.2.1 Basic Program Operation
This section briefly describes the operation of the LineGuard user program, which monitors pipeline pressure, calculates the Rate of Pressure Drop (RoD), maintains minor and major logs, and performs valve control.
Pipeline Pressure
Monitoring
The static pipeline pressure is sampled every 5 seconds and stored as Live Pressure. This value is averaged over a configurable period called the Average Sample Period and is stored as Average Pressure. The Average Sample Period is user-configurable from 5 seconds to 60 seconds in 5 second intervals. The default Average Sample Period is 60 seconds (or 12 samples). The average pressure is averaged over a moving time window and the time window is defined by the average sample period. The average pressure is updated every 5 seconds. The average pressure is used to detect major and minor line-break conditions. The average pressure is archived in both major and minor data logs.
Rate of Drop (RoD)
Pressure Calculation
The LineGuard device reacts to a drop in pipeline pressure. The current Rate of Pressure Drop (RoD) is calculated as the change in average pressure over the last minute and is available every sample cycle (5 seconds) in units of pressure/minutes. The current RoD is rolled over to an average RoD based on the average sample period. The average sample period for RoD calculations is equal to the sample period used in calculating average pressure. The average RoD is used to detect major and minor line-break conditions. The average RoD is archived in both major and minor data logs.
Data Logging
The LineGuard program maintains four data logs, major data logs, event logs, and alarm logs.
Minor Data Logs
A Minor Log is initiated when a minor alarm is enabled and becomes active. Alarm conditions include when the average pressure is less than the minor low pressure setpoint, average pressure greater than the minor high setpoint, and average RoD greater than the minor RoD setpoint. Each minor log setpoint and alarm is user configurable.
A complete minor log consists of a beginning time stamp (MM/DD/YY HH:MM:SS), 60 average pressure values and 60 average RoD values. Values are stored in the log at a user configurable Minor Log Period. Valid log periods for a minor log include 30 seconds, 1 minute, 2 minutes, 3 minutes, 4 minutes, and 5 minutes. At each log period the current average pressure and average RoD is written to the minor log.
A minor log archives 60 (complete log) values for average pressure and average RoD values regardless of whether the initiating alarm condition persists. A log is archived to memory once the log is complete. Another minor log is initiated if the minor log alarm condition remains active.
A total of 100 minor logs can be stored in the unit. Minor logs are circular logs with the earliest log overwritten with the newest log once all 100 logs are full. Minor log data archival will also stop 50 logs (60 values each) after a major log alarm condition becomes active and will not resume until
LineGuard 2300 Program User Manual
Revised March-21 3
after the user has manually cleared the major log alarm state.
Major Data Logs
A Major Log is initiated when a major alarm becomes active, the alarm is enabled, and the event duration period has been satisfied. Alarm conditions include Average Pressure less than the Major Low SetPoint, Average
Pressure greater than Major High SetPoint, and Average RoD greater than Major RoD SetPoint. Major Log SetPoints, alarms, and event durations are
user configurable. A complete Major Log consists of a time stamp (MM/DD/YY
HH:MM:SS), 30 average pressure values, and 30 average RoD values prior to the major alarm becoming active and 30 average pressure values and 30 average RoD values after the major alarm became active. The time stamp indicates the actual time of the line break.
Only one major log is saved in the LineGuard unit. A major log will be retained and not overwritten until you manually clear the major alarm state by pressing Clear Logs on the LineGuard Status screen. Values are stored in the log at a user configurable major log period. Valid log periods for a major log include 5 seconds, 10 seconds, 15 seconds, and 30 seconds. The current average pressure and average RoD is written to the major log at each log period.
Event Logs
The program adds an entry to the Event log when changes in setpoints or parameters occur that affect program operation. Changes can include remote and local commands to change valve position, change setpoints, and change in parameters that affect any aspect of the LineGuard operation. The standard FloBoss firmware performs event logging. Event data may be used to establish a history of LineGuard status and pipeline valve activity. The circular event log maintains a maximum of 240 records and overwrites old data as new events occur.
Alarm Logs
Alarm Logs are triggered by exceeding operating limits and setpoints. The alarm log function is performed by the standard FloBoss firmware. The alarm log collects, and stores data not directly related to operator change requests. Alarm entries include battery low voltage condition and any other input point high and low condition. The alarm log can store up to 240 alarms and overwrites old entries as new alarms are encountered. An alarm entry is also created when a minor or major alarm becomes active, a Minor or Major Alarm becomes inactive, and when automatic valve closure is initiated, and a transmitter fail condition becomes active or clears. The following user text type alarm is created by the calculation program.
LineGuard 2300 Program User Manual
4 Revised March-21
Alarm Entry
Description
Auto Close Init
Indicates the time at which automatic valve closure was initiated.
Major Low
Indicates the value and time at which the major low alarm became active or inactive.
Major RoD
Indicates the value and time at which the major RoD alarm became active or inactive.
Major High
Indicates the value and time at which the major high alarm became active or inactive.
Minor Low
Indicates the value and time at which the minor low alarm became active or inactive.
Minor RoD
Indicates the value and time at which the minor RoD alarm became active or inactive
Minor High
Indicates the value and time at which the minor high alarm became active or inactive.
Trans Low
Indicates the value and time at which the pressure value reported from the transmitter dropped below the low limit.
Trans High
Indicates the value and time at which the pressure value reported from the transmitter rose above the high limit.
Trans OK
Indicates the value and time at which the pressure value reported from the transmitter are within alarm limits.
Shutdown Control
The LineGuard program automatically closes the valve when a major line break is detected.
Line Break Detection
The Average Pressure and Average RoD are used to detect line-break conditions every sample cycle (5 seconds). Valve closure is activated when the four following conditions are met: a major log alarm becomes active, it remains active for the configured Event Duration, auto-closure is enabled for the event, and the Close Output field is defined. The major log will continue to record data until it becomes full. The event duration can be configured from 0 seconds to 1800 seconds (30 minutes).
If the average pressure or average RoD returns to an allowable level during the event duration period, then valve closure is not initiated and normal pressure monitoring resumes.
Once a line-break situation has been detected, valve closure is completed, a major log is filled, and then all log recording and valve control stops. The user must select Clear Logs on the LineGuard Status screen before normal pressure monitoring, logging, and control is resumed. If the Open Output field is defined, the user can open the valve by selecting Force Open on the LineGuard Valve Control screen or remotely. If the Open Output field on the LineGuard Valve Control screen is not defined, the user must manually open the valve on site.
LineGuard 2300 Program User Manual
Revised March-21 5
Valve Control
The control valve can be opened and closed both remotely and on-site by
setting the “Manual Close Flag” or “Manual Open Flag.” When the “Manual Open Flag” is set the configured “Open Output” is energized for the “Open Duration.” When the “Manual Close Flag” is set the configured “Close Output” is energized for the “Close Duration.” “Open Duration” and “Close Duration” values can be configured from 5 seconds to 1800
seconds (30 minutes). Automatic valve closure can be initiated by a high-pressure condition, low
pressure condition or a high rate of drop of pressure condition. After auto­closure has been initiated, even a favorable pressure change will not de-
energize the “Close Output” and the valve will stroke to completion. Any
or all of these closure controls may be individually disabled if desired by setting the “Auto-closure” for the alarm type to disabled. If auto-closure is disabled, the program will still perform all other functions unless “Close Output” is activated.
Limit switch inputs may be configured for both the open and close operations. During valve closure the program will monitor the “Close Limit Switch” status (if configured) and de-activate the “Close Output” when the limit switch status becomes active. If the close limit switch input is not defined, the close output will remain energized for the full close duration period. During valve opening the program will monitor the “Open Limit Switch” status (if configured) and de-activate the “Open Output” when the limit switch status becomes active. If the open limit switch input is not defined, the open output will remain energized for the full open duration period.
Data Log Collection
Minor and major data logs are collected from the LineGuard unit using the LineGuard Log Utility (refer to LineGuard Logs Utility User Manual D301577X012). This software and associated documentation may be purchased from Remote Automation Solutions. The interface software allows the user to log-on into the LineGuard unit remotely or on-site and retrieve logs. The utility is intended only for collection of minor and major data logs from the LineGuard device. All other operations, including program monitoring, program configuration, and event and alarm log collection, are accomplished with the ROCLINK 800 configuration software.
Input Error Detection
The program provides error detection for failed transmitters and input power limits.
The user may enable a check for pressure transmitter fail detection (see tab on the LineGuard Valve Control screen). The user enters low and high pressure set points. When the transmitter fail check is enabled and the input pressure is outside of one of the set points for more than a user defined delay period, the program begins a transmitter reset sequence.
The program first cycles power to the pressure transmitter. If the pressure value returns to within the set points, normal LineGuard operations are continued. If the input pressure remains out of limits, the program initiates
LineGuard 2300 Program User Manual
6 Revised March-21
a restart (warm-start) of the FloBoss 107. If the pressure value returns to within the set points, normal LineGuard operations are continued. If the input pressure remains out of limits, line break detection software and value closure algorithm are disabled until the pressure input value returns to within the expected range.
The user may enable a check for input voltage error (see tab on the LineGuard Valve Control screen). The user enters low and high input voltage alarm limits. When the voltage check is enabled and the input voltage to the FloBoss 107 is outside of one of the alarm limits, the program first checks to see if a valve closure is already in progress. If a closure is in progress, the program will wait for the closure to complete before taking action. When the input voltage is out of limits and no closure in is progress, line break detection software and value closure algorithm are disabled until the input voltage returns to within limits.
1.3 Program Requirements
The LineGuard program is compatible with version 1.85 (or greater) of the FB107 firmware and with version 2. 60 (or greater) of the ROCLINK 800 software.
Program specifics include:
File Name
Target Unit/
Version
User Defined
Point (UDP)
Flash Used
(in bytes)
DRAM Used
(in bytes)
ROCLINK
800
Version
Display
Number
LineGuard_1-
1_13.bin
FB107 1.85
22, 23
16,338
16,282
2.60
21, 22
Note: You must connect a PC to the FB107’s LOI port before starting the
download.
For information on viewing the memory allocation of user programs, refer to the ROCLINK 800 Configuration Software User Manual (for FB107) (D301249X012).
1.3.1 License Key
Some applications require that you install a license in the CPU to run the application. This license software is specific to these applications and is the property of the individual vendor (shown in the Vendor Name field on the License Key Administrator screens). RAS (and other authorized vendors) distribute software licenses on security-enhanced universal serial bus (USB) drives.
You must install the following license keys to use the LineGuard program.
LineGuard License Key.
LineGuard 2300 Program User Manual
Revised March-21 7
Chapter 2 – Installation
This section provides instructions for installing the LineGuard program. Read Section 1.3 of this manual for program requirements.
Note: The program and license key can be installed in any order. The
manual shows the installation of the license key first.
2.1 Installing the License Key
A USB key-based license is required to use the LineGuard program.
2.1.1 Installing a License
To install a USB key-based license on the FB107:
1. Insert the USB license key in a USB port on your PC.
2. Select Utilities > License Key Administrator > Transfer Between
DEVICE and KEY from the ROCLINK 800 menu bar. The Transfer Licenses Between a Device and a Key screen displays.
Figure 1. Transfer Licenses Between a Device and a Key
LineGuard 2300 Program User Manual
8 Revised March-21
Note: This screen has three sections. The upper portion (Licenses on
Device) shows any software licenses installed on the FB107. The middle portion (Licenses on Key) shows software licenses on the license key. The lower portion of the screen (License Key Event Log) provides a rolling log of the last eight events related to this license key.
3. Select the key-based license you want to transfer to the FB107
(LineGuard 2300, as shown in Figure 1).
4. Click Move to Device. ROCLINK moves the license from the key to
the FB107 and updates the screen.
Figure 2. License Installed
Note: An FB107 can hold up to six different licenses, although you can
install only one instance of each license on the FB107. When you click Move to Device, ROCLINK 800 moves only one instance of the license onto the FB107 and automatically decreases the license quantity on the USB key by one.
5. Verify the license name displays in the Licenses on Device section of
the screen. Proceed to Section 2.2 to download the user program.
LineGuard 2300 Program User Manual
Revised March-21 9
2.2 Downloading the Program
This section provides instructions for installing the program into the Flash memory on the FB107.
To download the program using ROCLINK 800 software:
1. Connect the FB107 to your computer using the LOI port.
2. Start and logon to ROCLINK 800.
3. Select Utilities > User Program Administrator from the ROCLINK
menu bar. The User Program Administrator screen displays (see
Figure 3):
Figure 3. User Program Administrator
4. Click Browse in the Download User Program File frame. The Select
User Program File screen displays (see Figure 4).
5. Select the path and user program file to download from the CD-ROM.
(Program files are typically located in the Program Files folder on the CD-ROM). As Figure 4 shows, the screen lists all valid user program files with the .BIN extension:
LineGuard 2300 Program User Manual
10 Revised March-21
Figure 4. Select User Program File
6. Click Open to select the program file. The User Program
Administrator screen displays. As shown in Figure 5, note that the Download User Program File frame identifies the selected program and that the Download & Start button is active:
Figure 5. User Program Administrator
LineGuard 2300 Program User Manual
Revised March-21 11
7. Click Download & Start to begin loading the selected programs. The
following message displays:
Figure 6. Confirm Download
8. Click Yes to begin the download. When the download completes the
following message displays:
Figure 7. ROCLINK 800 Download Confirmation
9. Click OK. The User Program Administrator screen displays (see
Figure 8). Note that:
The User Programs Installed in Device frame identifies the
installed program(s).
The Status field indicates that the program is running.
LineGuard 2300 Program User Manual
12 Revised March-21
Figure 8. User Program Administrator
Note: If you install the program before you install the license key, the
Status field reads License Not Found. Install the license key to change the status of the program.
10. Click Close. The ROCLINK 800 screen displays and the download is
complete. Proceed to Chapter 3, Configuration.
Loading...
+ 31 hidden pages