Remote Automation Solutions FBxConnect Configuration Software User Manual (for the FB3000 RTU) Manuals & Guides

FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)

FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Remote Automation Solutions
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential system expertise. Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or e-mail us at Education@Emerson.com
.
ii
Contents
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
1.1 Installing and Starting FBxConnect ........................................................................... 1
1.2 User Interface ........................................................................................................... 1
1.2.1 Menu ............................................................................................................ 3
1.2.2 Point Picker .................................................................................................. 4
1.2.3 Forward and Back Buttons ............................................................................ 7
1.2.4 Copy, Paste, and Pause/Resume Buttons ...................................................... 9
1.2.5 Status Bar ................................................................................................... 10
1.3 File Formats ............................................................................................................ 11
1.4 Native Data Types................................................................................................... 11
2.1 Save (Offline Mode) ................................................................................................ 15
2.2 Save As (Offline Mode) ........................................................................................... 16
2.3 Upload Solution ...................................................................................................... 20
2.4 Download Solution ................................................................................................. 27
2.5 Download to Flash .................................................................................................. 34
2.6 Close ...................................................................................................................... 38
3.1 Main ....................................................................................................................... 39
3.2 I/O .......................................................................................................................... 40
3.3 Gas ......................................................................................................................... 41
3.3.1 DP Meter .................................................................................................... 42
3.3.2 Linear Meter ............................................................................................... 43
3.4 Liquid ..................................................................................................................... 44
3.4.1 Liquid Linear Meter ..................................................................................... 45
3.5 History ................................................................................................................... 46
3.6 Alarms .................................................................................................................... 48
3.7 Events .................................................................................................................... 50
3.8 Comm Ports ........................................................................................................... 52
3.8.1 Comm Ports – Overview Tab ....................................................................... 53
iii
3.8.2 Comm Ports – COM Tabs ............................................................................ 55
3.8.3 Comm Ports – ENET Tabs ............................................................................ 56
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Comm Ports – USB Tab ............................................................................... 57
3.8.4
4.1 Home ..................................................................................................................... 60
4.1.1 Configuring the Home Screen .................................................................... 62
4.2 Guided Setup ......................................................................................................... 65
4.2.1 Guided Setup: I\O Configuration ................................................................. 67
4.2.2 Guided Setup: I\O Configuration Details ..................................................... 69
4.2.3 Guided Setup: Communication Settings ..................................................... 72
4.2.4 Guided Setup: 4088 Setup .......................................................................... 74
4.2.5 Guided Setup: Fluid Selection ..................................................................... 76
4.2.6 Guided Setup: Custom Station Layout Configuration .................................. 78
4.2.7 Guided Setup: Station Assignment ............................................................. 80
4.2.8 Guided Setup: Engineering Units ................................................................ 81
4.2.9 Guided Setup: Station ................................................................................ 84
4.2.10 Guided Setup: Gas Composition ................................................................. 89
4.2.11 Guided Setup: DP Meter ............................................................................. 90
4.2.12 Guided Setup: Linear Meter ........................................................................ 95
4.2.13 Guided Setup: Linear Meter Curve Setup ................................................... 102
4.2.14 Guided Setup: Calculation Options ........................................................... 104
4.2.15 Guided Setup: Liquid Density .................................................................... 109
4.2.16 Guided Setup: Liquid Fluid Properties (Sediment and Water) .................... 112
4.2.17 Guided Setup: Liquid Fluid Properties (Additional Factors) ........................ 114
4.2.18 Guided Setup: Liquid Linear Meter ............................................................ 118
4.2.19 Guided Setup: Liquid Meter Curve Setup ................................................... 126
4.2.20 Guided Setup: Default Meter History Setup .............................................. 127
4.3 Engineering Units ................................................................................................. 129
4.4 Point Picker .......................................................................................................... 132
4.5 I/O Setup .............................................................................................................. 135
4.5.1 I/O Configuration ..................................................................................... 136
iv
4.5.1.1 I/O Configuration – General Tab .............................................. 137
4.5.1.2 I/O Configuration – Properties Tab ........................................... 138
4.5.1.3 IO Import Export ...................................................................... 140
4.5.2 4088B Setup ............................................................................................. 185
4.5.3 4088B ...................................................................................................... 187
4.5.3.1 4088B – General Tab ............................................................... 188
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
4.5.3.2
4.5.3.3 Configuring Communications with a 4088B ............................. 194
4.5.4 HART® I/O ............................................................................................... 197
4.5.4.1 HART Device ............................................................................ 205
4.5.4.2 Configuring HART® I/O ........................................................... 211
4.5.5 Differential Pressure ................................................................................. 213
4.5.5.1 Differential Pressure – General Tab .......................................... 214
4.5.5.2 Differential Pressure – Calibration Values Tab .......................... 218
4.5.5.3 Configuring Differential Pressure Inputs................................... 219
4.5.6 Pressure ................................................................................................... 221
4.5.6.1 Pressure – General Tab ............................................................ 222
4.5.6.2 Pressure – Calibration Values Tab ............................................ 225
4.5.6.3 Configuring Static Pressure Inputs ........................................... 227
4088B – User Defines Tab ........................................................ 192
4.5.7 RTD .......................................................................................................... 228
4.5.7.1 RTD – General Tab ................................................................... 229
4.5.7.2 RTD – Calibration Values Tab ................................................... 233
4.5.7.3 Configuring an RTD ................................................................. 235
4.5.8 MV Sensor ................................................................................................ 236
4.5.9 Analog Input ............................................................................................ 238
4.5.9.1 Analog Input – General Tab ...................................................... 239
4.5.9.2 Analog Input – Calibration Values Tab ...................................... 245
4.5.9.3 Configuring Analog Inputs ....................................................... 247
4.5.10 Analog Output ......................................................................................... 249
4.5.10.1 Configuring Analog Outputs .................................................... 254
4.5.11 Digital Input ............................................................................................. 256
4.5.11.1 Configuring Digital Inputs ........................................................ 261
4.5.12 Digital Output .......................................................................................... 262
4.5.12.1 Configuring Digital Outputs ..................................................... 271
4.5.13 Pulse Input ............................................................................................... 273
4.5.13.1 Configuring Pulse Inputs .......................................................... 278
4.5.14 User Data ................................................................................................. 280
4.6 Pass Thru .............................................................................................................. 282
4.7 Summary.............................................................................................................. 284
4.8 Meter Setup ......................................................................................................... 286
4.8.1 Station Assignment .................................................................................. 290
v
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Station Fluid Type ..................................................................................... 291
4.8.2
4.9 DP Meter .............................................................................................................. 293
4.9.1 DP Meter – General Tab ............................................................................ 294
4.9.2 DP Meter – Advanced Tab ......................................................................... 301
4.9.2.1 Discharge Coefficient .............................................................. 306
4.9.3 Gas DP Meter Diagnostics ......................................................................... 308
4.9.3.1 Gas DP Meter Diagnostics – Factors & Values Tab..................... 310
4.9.3.2 Gas DP Meter Diagnostics – Calculation Alarms Tab ................. 314
4.9.4 DP Meter – Rates & Totals ......................................................................... 318
4.9.4.1 Gas DP Meter Rates & Totals – Rates & Totals Tab .................... 320
4.9.4.2 Gas DP Meter Rates & Totals – Fault Totals Tab ........................ 321
4.10 Linear Meter ......................................................................................................... 324
4.10.1 Linear Meter – General Tab ....................................................................... 325
4.10.2 Linear Meter – Auto-Adjust Tab ................................................................ 334
4.10.2.1 Calibration Curve Option (Auto-Adjust) ................................... 338
4.10.3 Linear Meter – Advanced Tab .................................................................... 340
4.10.3.1 Curve Setup (Linear Meter) ...................................................... 344
4.10.4 Linear Meter Diagnostics .......................................................................... 347
4.10.4.1 Gas Linear Meter Diagnostics – Factors & Values Tab ............... 349
4.10.4.2 Gas Linear Meter Diagnostics – Calculation Alarms Tab ............ 353
4.10.5 Linear Meter Rates & Totals ...................................................................... 357
4.10.5.1 Gas Linear Meter Rates & Totals – Rates & Totals Tab ............... 359
4.10.5.2 Gas Linear Meter Rates & Totals – Fault Totals Tab ................... 360
4.11 Fluid Properties .................................................................................................... 364
4.11.1 Fluid Properties – General Tab .................................................................. 364
4.11.2 Fluid Properties – Advanced Tab ............................................................... 370
4.11.3 Fluid Properties – Component Tab ............................................................ 375
4.12 Components ........................................................................................................ 376
4.12.1 Components – General Tab ...................................................................... 377
4.12.2 Components – Component Tab ................................................................ 380
vi
4.12.3 Component Import Export ....................................................................... 382
4.12.3.1 Importing a Gas Composition CSV File ..................................... 384
4.12.3.2 Exporting a Gas Composition CSV File ...................................... 386
4.12.3.3 Creating a Gas Composition CSV File ....................................... 389
4.12.4 Apply Composition Values ........................................................................ 392
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Liquid Linear Meter ............................................................................................... 393
4.13
4.13.1 Liquid Linear Meter Flow Calculations ....................................................... 394
4.13.2 Liquid Linear Meter – General Tab ............................................................. 396
4.13.3 Liquid Linear Meter – Advanced Tab ......................................................... 406
4.13.3.1 Curve Setup (Liquid Linear Meter) ............................................ 409
4.13.4 Liquid Linear Meter – Volume Correction Tab ........................................... 412
4.13.5 Liquid Linear Meter – Water Tab ............................................................... 416
4.13.6 Liquid Linear Meter – Additional Factors Tab ............................................. 419
4.13.7 Liquid Linear Meter – Diagnostics ............................................................. 421
4.13.7.1 Liquid Linear Meter Diagnostics – Factors and Values Tab ........ 423
4.13.7.2 Liquid Linear Meter Diagnostics – Calculation Alarms ............... 425
4.13.8 Liquid Linear Meter – Rates & Totals .......................................................... 429
4.14 Liquid Product ...................................................................................................... 430
4.15 Liquid Density ....................................................................................................... 432
4.16 Station ................................................................................................................. 436
4.16.1 Station – General Tab ............................................................................... 437
4.16.2 Station – Advanced Tab ............................................................................ 454
4.16.2.1 Calculation Failure Options ...................................................... 459
4.16.3 Station – Rates & Totals Tab...................................................................... 461
4.17 Averages .............................................................................................................. 462
4.18 Totals Drop-Down List .......................................................................................... 464
4.18.1 Totals ....................................................................................................... 465
4.18.2 Totals Setup ............................................................................................. 468
4.18.2.1 Totals Setup – Meter Fault Totals ............................................. 470
4.18.2.2 Totals Setup – Meter Fault Triggers .......................................... 471
4.18.2.3 Totals Setup – Summary .......................................................... 474
4.18.2.4 Totals Setup – Finish ................................................................ 475
4.19 Gas Chromatograph ............................................................................................. 476
4.19.1 Gas Chromatograph – Last Poll Tab .......................................................... 477
4.19.2 Gas Chromatograph – Configuration Tab ................................................. 482
4.19.3 Automatically Configured Parameters ...................................................... 486
4.20 Alarms .................................................................................................................. 488
4.21 History ................................................................................................................. 491
4.21.1 History Overview ...................................................................................... 491
4.21.2 Group Configuration ................................................................................ 493
4.21.2.1 Show History Points ................................................................. 496
vii
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Default Meter History Setup ..................................................................... 507
4.21.3
4.21.3.1 Default Hisory Configuration ................................................... 509
4.21.4 History – Advanced Setup ......................................................................... 510
4.21.4.1 History Setup - Advanced – Standard History Sizing Tab ........... 510
4.21.4.2 History Setup - Advanced – Points Assignment Tab .................. 514
4.22 Logs ..................................................................................................................... 516
4.22.1 Event Setup .............................................................................................. 517
4.22.2 Log Properties .......................................................................................... 518
4.22.3 Log Descriptions ....................................................................................... 520
4.23 PID Loops ............................................................................................................. 522
4.23.1 PID Loops – General Tab ........................................................................... 523
4.23.2 PID Loops – Inputs/Outputs Tab ............................................................... 528
4.23.3 PID Loops – Advanced Tab ........................................................................ 531
4.23.4 PID Loops – Tuning Tab ............................................................................ 533
4.24 Action Blocks ........................................................................................................ 535
4.24.1 Action Blocks – General Tab ...................................................................... 535
4.24.2 Action Blocks – Bypass Tab ....................................................................... 542
4.24.3 Action Blocks – Chain Tab ......................................................................... 545
4.25 Math Blocks .......................................................................................................... 547
4.25.1 Supported Operators and Functions ......................................................... 550
4.26 Effects .................................................................................................................. 551
4.27 Control Setup ....................................................................................................... 554
4.28 Communications .................................................................................................. 556
4.28.1 Communications – General Tab ................................................................ 556
4.28.1.1 Port Owners ............................................................................ 561
4.28.2 Communications – Modbus Slave Tab ...................................................... 561
4.28.2.1 Modbus Registers for EFM Application Events .......................... 566
4.28.2.2 Map Table Register .................................................................. 572
4.28.2.3 Remote Data Types ................................................................. 586
4.28.2.4 EFM Archive Mapping .............................................................. 590
4.28.3 Communications – Modbus Master Tab .................................................... 591
viii
4.28.3.1 Poll Table Register ................................................................... 596
4.28.3.2 Map Table Register .................................................................. 608
4.28.3.3 Remote Data Types ................................................................. 621
4.28.4 Communications – DNP3 Tab ................................................................... 625
4.28.4.1 DNP3 Host Information ........................................................... 629
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
4.28.4.2
4.28.5 Configuring Communications Ports .......................................................... 648
4.29 Clock .................................................................................................................... 649
4.30 Power Control ...................................................................................................... 652
4.31 System ................................................................................................................. 654
4.32 I/O Bus ................................................................................................................. 656
4.33 FBxNet ................................................................................................................. 658
5.1 Service Info ........................................................................................................... 663
5.2 Board Info ............................................................................................................. 664
5.3 Firmware Update .................................................................................................. 667
5.4 File Transfer .......................................................................................................... 671
5.4.1 Download a File ........................................................................................ 671
5.4.2 Upload a File ............................................................................................. 673
DNP3 Map Table ...................................................................... 631
5.4.3 Delete a File .............................................................................................. 675
5.5 Warm Start ........................................................................................................... 677
5.6 Cold Start ............................................................................................................. 678
5.7 Calibration ........................................................................................................... 680
5.7.1 BLM Required Information ........................................................................ 682
5.7.2 Calibrating Inputs ..................................................................................... 684
5.7.3 Verifying a Calibration .............................................................................. 693
5.7.4 Setting Zero Shift ..................................................................................... 702
5.7.5 Resetting a Calibration ............................................................................. 709
5.7.6 Viewing a Calibration Report .................................................................... 711
5.7.7 Calibration Errors ...................................................................................... 713
5.7.7.1 Analog Input (AI) Calibration Errors .......................................... 713
5.7.7.2 4088B Calibration Errors .......................................................... 714
5.7.7.3 215 MultiVariable™ Sensor Calibration Errors .......................... 715
5.8 Plate Change ........................................................................................................ 716
5.9 System Power ....................................................................................................... 724
5.10 Time Sync ............................................................................................................. 726
5.11 User Management ................................................................................................ 728
5.11.1 Adding a User ........................................................................................... 730
5.11.2 Modifying a User ...................................................................................... 734
5.11.3 Deleting a User ......................................................................................... 738
5.11.4 Roles ........................................................................................................ 740
ix
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Security Management .......................................................................................... 742
5.12
5.12.1 Permissions .............................................................................................. 743
5.13 Device License ...................................................................................................... 745
5.13.1 Add License File to Device ......................................................................... 748
5.13.2 License Management ............................................................................... 750
5.13.2.1 Add Licensed Product from the Cloud ...................................... 753
5.13.2.2 Restore License from Cloud ..................................................... 758
5.13.2.3 Remove a Licensed Product ..................................................... 761
5.13.2.4 Add License Offline .................................................................. 765
5.13.3 Serial Number Location ............................................................................ 769
6.1 EFM Report ........................................................................................................... 771
6.2 CFX Report ........................................................................................................... 774
6.3 History Report ...................................................................................................... 777
6.4 Alarm Report ........................................................................................................ 781
6.5 Event Report ........................................................................................................ 784
6.6 Configuration Report ............................................................................................ 787
6.7 Configuration Comparison Report ........................................................................ 789
6.8 Gas Composition Report ....................................................................................... 792
6.9 Parameter Status Report ...................................................................................... 794
6.10 Diagnostic Report ................................................................................................. 795
6.11 Calibration Report ................................................................................................ 797
7.1 Management ........................................................................................................ 799
7.1.1 Add FBxDesigner Project .......................................................................... 800
7.1.2 Open FBxDesigner Project ........................................................................ 804
7.1.3 Import Application ................................................................................... 806
7.1.4 Update Application ................................................................................... 808
7.1.5 Export Application .................................................................................... 810
7.1.6 Remove Application ................................................................................. 813
7.2 Application Information ....................................................................................... 815
8.1 FBxVue Overview .................................................................................................. 819
8.1.1 Developer Toolbar .................................................................................... 820
x
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
8.1.1.1
8.1.1.2 Developer Toolbar – Control Buttons ....................................... 822
8.1.2 Display Outline ......................................................................................... 824
8.1.2.1 Control Hierarchy .................................................................... 826
8.1.2.2 OPI .......................................................................................... 826
8.1.2.3 Data Sources ........................................................................... 827
8.1.2.4 Variables ................................................................................. 828
8.1.2.5 Expressions .............................................................................. 829
8.1.2.6 Timers ..................................................................................... 829
8.1.3 Properties ................................................................................................. 830
8.1.3.1 Canvas ..................................................................................... 831
8.1.3.2 Label ....................................................................................... 833
8.1.3.3 TextBox ................................................................................... 835
Developer Toolbar – Layout Buttons ........................................ 821
8.1.3.4 Button ..................................................................................... 839
8.1.3.5 CheckBox ................................................................................ 841
8.1.3.6 RadioButton ............................................................................ 844
8.1.3.7 GroupBox ................................................................................ 846
8.1.3.8 Image ...................................................................................... 848
8.1.3.9 ComboBox .............................................................................. 849
8.1.3.10 NumericUpDown ..................................................................... 852
8.1.3.11 TabControl .............................................................................. 854
8.1.3.12 TabItem ................................................................................... 856
8.1.3.13 Gauge ..................................................................................... 856
8.1.3.14 Chart ....................................................................................... 859
8.1.3.15 Rectangle ................................................................................ 861
8.1.3.16 Ellipse ...................................................................................... 864
8.1.3.17 Line ......................................................................................... 866
8.1.3.18 Accordion ................................................................................ 868
8.1.3.19 AccordionItem......................................................................... 869
8.1.3.20 Grid ......................................................................................... 870
8.1.3.21 GridHeader .............................................................................. 872
8.1.3.22 GridCell ................................................................................... 873
8.1.3.23 Panel ....................................................................................... 873
8.1.3.24 TreeNode ................................................................................ 876
8.1.3.25 TimePicker .............................................................................. 878
xi
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
8.1.3.26
8.2 New Display ......................................................................................................... 882
8.3 Open Display ........................................................................................................ 882
8.4 Save Display ......................................................................................................... 883
8.5 Save Display As ..................................................................................................... 884
8.6 Delete Displays ..................................................................................................... 885
8.7 Download Displays ............................................................................................... 888
8.8 Standalone Displays ............................................................................................. 889
9.1 Online .................................................................................................................. 891
9.2 About ................................................................................................................... 892
DatePicker ............................................................................... 880
xii
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Introduction
FBxConnect™ configuration software enables you to monitor, configure, and calibrate Emerson's FB3000 RTU. Designed for ease of use, FBxConnect™ provides at-a-glance monitoring, quick access to commonly performed tasks, and configuration wizards to quickly get your equipment up and running.

1.1 Installing and Starting FBxConnect

FBxConnect™ Configuration Software is installed as a part of Emerson Field Tools. For more information on installation of Field Tools and connecting to a device, refer to Emerson Field Tools Quick Start Guide (D301703X412).

1.2 User Interface

FBxConnect™ is designed for ease of use. At the top of the display, FBxConnect™ utilizes a ribbon­style tabbed menu to navigate the software. Select a menu and submenu option to open the various displays of FBxConnect™.
D301882X012
December 2021
Note
Standard Microsoft® Windows® keyboard shortcuts are supported.
You can right-click your mouse on any field that is associated with an object or parameter in
the FBx product database and select Copy Tag to copy the database tag to your computer's clipboard. You can then paste the information into another application such as FBxDesigner™ or FBxNet.
1
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 1. User Interface
Click on the links below for more information on each user interface element:
1.
2.
3.
4.
5.
2
– Use the Menu to access the displays and wizards used to configure and monitor your
Menu
FB Series product.
Point Picker
the database.
Forward and Back Buttons
forth between displays without losing your spot in the configuration process.
Copy, Paste, and Pause/Resume Buttons
from one instance and paste it into another instance. Use the Pause/Resume button to prevent or restart automatically refreshing the values on the display.
Status Bar – The Status Bar provides general information about the connection to the FB Series
product and contains a slider that controls the zoom level of the display.
– The Point Picker dialog allows you to reference a specific object or parameter in
– The forward and back buttons allow you to quickly jump back and
– Use the Copy and Paste buttons to copy information

1.2.1 Menu

FBxConnect™ contains a ribbon-style tabbed menu at the top of the window. Select a menu tab to view a list of options in a submenu. Select an option from the submenu to open that display or option.
Note
The submenu options are grouped together based on functionality. For example, the Configure menu has a group named Control where you can configure PID Loops, Action Blocks, Math Blocks, and Effects.
Figure 2. Menu and Submenu
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
For more information about each menu, select the name of a menu tab below:
File Menu
device configuration to flash memory, load a saved configuration to the device, or close the current connection to the device.
Monitor Menu – Use the options in this menu to view current conditions including flowing
conditions, history, alarms, events, and communication port status.
Configure Menu – Use the options in this menu to configure device parameters, including meter
runs, I/O, fluid properties, history, customizing the display, and running the Guided Setup.
Services Menu – Use the options in this menu to access utilities and perform maintenance on your
device, such as user management, firmware updates, and calibration.
Reports Menu – Use the options in this menu to collect information and view reports, including
EFM, CFX, fluid composition, history, alarms, events, and diagnostic reports.
Applications Menu – Use the options in this menu to access applications installed on your flow
computer or RTU.
FBxVue Menu – Use the FBxVue menu to create customized displays for the FB Series products.
Help Menu – Use the options in this menu to view information about your installed version of Field
Tools, and to access the online help system.
– Use the options in this menu to save a device configuration file to your PC, save a
3
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Note
If the submenu extends past the end of your screen, use the arrows located on the sides of the submenu to view the available options.

1.2.2 Point Picker

In many locations in FBxConnect, you can click browse ( ) to view the Point Picker dialog. The
Point Picker dialog allows you to reference a specific object or parameter in the database. These are used typically when linking two objects together (like a meter to a station) or when dynamically assigning an input or output variable to a source (like an analog input to a meter temperature input).
You can also open the Point Picker dialog to view the database by selecting Configure > Point Picker from the FBxConnect™ main menu.
You can select two different types of references in FBxConnect™ depending on the field: object references and parameter references.
Note
If you open the Point Picker from the FBxConnect™ main menu (Configure > Point Picker), the dialog shows parameter references.
Object References – Sometimes the point picker is used to pick an object reference. In this
case, you are only able to select the object and instance of the object. For example, if you are configuring a meter run and are setting the station assignment, you can only pick which station you wish to assign, not a particular parameter.
4
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 3. Point Picker – Object Reference
Parameter References – Sometimes the point picker is used to pick a parameter reference. In
this case, the Point Picker dialog shows three columns. You select an object and instance of the object in the first column. After clicking on the object type and instance in the first column, the second column displays all appropriate parameters for this particular object reference. Sometimes the parameter you pick in the second column is an object itself, and this object contains additional referenced parameters. You can choose these additional referenced parameters in the third column.
Figure 4. Point Picker – Parameter Reference
5
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
No Filter
Note
only
Parameter
Reference
D301882X012 December 2021
Note
To quickly remove a previously assigned object or parameter reference, right-click the browse
button ( ) and select
Field Description
Filter
Object and Instances
Undefined.
Click ▼ to change which objects and parameters are displayed. Filters may be based on object type, measurement type, or data type.
Select
Object
to view all available Objects.
A group of configuration settings and calculated or measured values related to a specific function. For example, all values associated with the device clock (second, hour, day, etc.) are part of an Object named Clock. From the first column, click on the object type you wish to reference.
Parameter
Instance
One of the configuration settings, calculated values, or measured values that is a part of the object. Each parameter has a value as well as a set of attributes that define it, such as data type, R/W access, measurement type, units, and parameter health. After clicking on the object and instance you wish to reference, the available parameters are displayed. Click on the parameter you wish to reference.
This column appears
There may be one or more occurrences of each type of object with its own set of configuration settings and values. Each occurrence of an object is called an instance. For example, there are multiple instances of the object named Comm, and each instance represents one of the FB Series product’s communication ports. After clicking on the object you wish to reference, the available instances are displayed. Click on the instance you wish to reference.
if you select the Point Picker for a
.
6
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
only
Parameter
Reference
read-only
read-only read-only
read-only
Note
D301882X012
December 2021
Field Description
Referenced Parameter
If the point picker is used to pick a parameter reference, you can pick a parameter directly from the object to which it belongs, or you can pick the parameter through an object reference in a related object. For instance, to pick a parameter to assign to an Average object, you can pick the DP Mtr_1 object and the Station Assignment parameter and then the third column displays all of the parameters that are available from the Station object that is assigned to DP Mtr_1. This is useful because even if the station assignment
later changes, the Average object is always associated with DP Mtr_1.
This column appears
.
Tag
Data
Access
Value
Collect Tag Names
Copy Tag
This
This information, refer to
This
This
Select this button to query the FB Series product and display any unique tag names you have assigned to individual parameters.
You can perform this action at any time to reflect recent configuration changes.
Select this button to copy the currently selected tag to the computer’s clipboard. You can then paste the selected tag into a different application, such as FBxDesigner™.
field shows the name of the selected parameter.
field shows the data type of the selected parameter. For more
field shows the read/write access of the selected parameter.
field shows the value of the selected parameter.

1.2.3 Forward and Back Buttons

if you select the Point Picker for a
Native Data Types.
FBxConnect™ gives you the ability to navigate to a new display to perform additional configuration changes, and quickly navigate to the previous display through the use of forward and back buttons.
These buttons are colored blue to navigate to a new display ( ) and grey return to the previous
display ( ). These buttons allow you to quickly jump back and forth between displays without
losing your spot in the configuration process.
For example:
1.
Configure > Gas > DP Meter from the FBxConnect™ main menu. The DP Meter display
Select opens showing the General tab.
7
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
2.
Select the forward button ( ) located to the right of the Differential Pressure
Differential Pressure I/O display opens and allows you to configure the selected differential pressure input.
Figure 5. Forward Buttons
field. The
3.
After you are done performing changes on the Differential Pressure I/O display, select the back
button ( ) to return to the DP Meter display.
Figure 6. Back Button
8
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)

1.2.4 Copy, Paste, and Pause/Resume Buttons

Use the Copy and Paste buttons to copy information from one instance and paste it into another instance. This make it easy to configure objects that contain similar information, such as meter runs or stations. Use the Pasuse/Resume button to prevent or restart automatically refreshing the values shown on the display.
For example:
1.
2.
3.
Figure 7. Display Showing Copied Information
Configure > Gas > DP Meter. The DP Meter opens showing the General tab.
Select
Select the
Click ▼ from drop-down list at the top of the display and select DP Meter instance 2.
Copy button located at the bottom of the display.
D301882X012
December 2021
4.
Select the second instance. Any information that was changed is highlighted.
Paste button. Configuration information is copied from the first instance into the
9
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
5.
Select the refreshing.
6.
Select the
7.
Review the information and then select
Pause button to prevent the values shown on the display from automatically
Resume button to restart automatically refreshing the values on the display.
Save to save your changes.

1.2.5 Status Bar

The Status Bar is located at the bottom of the display and provides general information about the connection to the FB Series product. Information includes the database build status, your user name, connection status, device type, and type of connection.
Figure 8. Status Bar
1. Database Build Status – Shows the status of the FB Series product database. When the database build is completed, the icon is green. When the database build is not completed, the icon is red.
2. User Name – Shows the user name currently logged into FBxConnect™.
3. Communications Status – Shows the communications status between the FB Series product and FBxConnect™. When the connection to the FB Series product is good, the icon says "Online" and the color is green. When communications have been interrupted, the icon says "Comm Error" and the color is red. When viewing a configuration without being connected to an FB Series product, the icon says "Offline" and the color is grey.
4. Device Type – Shows the FB Series product type currently connected through FBxConnect™.
5. CPU Communications Port and Speed – Shows the communications port being used for communications by FBxConnect™.
6. Zoom – Use the slider to adjust the zoom level of the FBxConnect™ display.
Note
You can also hover your mouse pointer over the slider and move the scroll wheel to adjust the zoom level.
10
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)

1.3 File Formats

The following table describes the file formats used by FBxConnect™ and FBxDesigner™:
Table 1. File Formats
File Extension Software Description
D301882X012
December 2021
.csv FBxConnect™
.mwt FBxDesigner™ Main FBxDesigner™ project file.
.pak FBxConnect™ Individual firmware image (CPU, I/O Modules, etc.).
.pdf FBxConnect™
.ptc FBxConnect™
.v2c FBxConnect™
.xml FBxConnect™ Multiple uses:
.zap FBxConnect™
.zip FBxConnect™
Option for report generation in FBxConnect™ (Alarms, Events, History, etc.).
Option for report generation in FBxConnect™ (Alarms, Events, History, etc.).
Partial configuration file for FB Series products saved via FBxConnect™.
License file generated via the Cloud Licensing Portal, and imported to a device via FBxConnect™.
Configuration file for FB Series flow computers and is
saved via FBxConnect™.
FBxVue display file that is a user interface. The display
file can be edited and viewed via FBxConnect™.
Zipped application package that contains an IEC61131 project and components.
System firmware image that contains all firmware images required for the FB3000 (CPU, I/O Modules, etc.).
.zsl FBxConnect™
.zwt FBxDesigner™

1.4 Native Data Types

Values stored within FB Series devices exist as parameters in an internal database. Each of these parameters has a native data type that best fits the purpose of the data. Many of these data types are industry standard, such as signed integers, unsigned integers, 32-bit floats, and 64-bit doubles. However, more unusual and specialized native data types, such as ENUM16, BIN8, and BYTE4 are also used throughout the device. Data type definitions, their size (in bytes), and typical use or range is defined in the table below.
Understanding the native data types is important for configuration exercises, such as mapping Modbus registers and custom DNP3 maps. External systems do not often have the same native
Zipped Solution that contains the configuration for an FB3000 device and is saved via FBxConnect™.
Zipped FBxDesigner™ project file that contains all files needed for a project.
11
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
data types as an FB Series device. Choosing appropriate remote data type conversions (Modbus) or Tables (DNP3) will depend the size, range, and purpose of the native data types.
Note
ENUM16 – The ENUM16 data type is used extensively throughout the internal database. It is an
integer which represents an enumeration where each value (0, 1, 2, etc.) has a different meaning. This data type is the same as a UINT16 (unsigned 16 bit integer) and should be treated as such for mapping to external systems.
BIN – The BIN data types (BIN8, BIN16, BIN32) are integers where each bit of the value has a
specific meaning. A BIN8 (which is the same as a UINT8) has 8 bits, a BIN16 (same as a UINT16) has up to 16 bits, and a BIN32 (same as a UINT32) has up to 32 bits (note that not all bits may be used). Treat these data types as their associated unsigned integers (UINT8, UINT16, UINT32) when mapping to external systems.
BYTE – The BYTE data types (BYTE4, BYTE6, BYTE32) represent a series of bytes which are all
related, but do not typically form an integer. Use of these data types is rare, and they do not typically have an analogous data type in external systems.
PRMREF and OBJREF – The PRMREF and OBJREF data types are used throughout the system for
linking data and groups of data together. These references can be used to point to other parameters (or objects) sometimes as defined by the user, and other times in a fixed manner. Because of the “tag” based nature of accessing parameters in FB Series devices, a PRMREF is essentially a UC40 (40-character string), and an OBJREF is essentially a UC20 (20-characters string). Treat these data types as their associated strings (UC40 and UC20) when mapping to external systems.
Table 2. FB Series Device Native Data Types
Data Type (Protocol Name)1
UINT8 INTEGER 8 1 Unsigned 8-bit integer.
INT8 INTEGER 8 1 Signed 8-bit integer.
UINT16 INTEGER 16 2 Unsigned 16-bit integer.
INT16 INTEGER 16 2 Signed 16-bit integer.
Data Type (FBxConnect™ Name)2
# of Bytes Definition
Range of 0 to 255.
Range of -128 to 127.
Range of 0 to 65,353.
Range of -32,768 to 32,767.
12
UINT32 INTEGER 32 4 Unsigned 32-bit integer.
Range of 0 to 4,294,967,296.
INT32 INTEGER 32 4 Signed 32-bit integer.
Range of -2,147,483,648 to 2,147,483,647.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
Data Type (Protocol Name)
Data Type (FBxConnect™ Name)
D301882X012
December 2021
Data Type (Protocol Name)1
UINT64 INTEGER 64 8 Unsigned 64-bit integer.
INT64 INTEGER 64 8 Signed 64-bit integer.
FLOAT FLOAT 4 32-bit IEEE floating-point number.
DOUBLE DOUBLE 8 64-bit IEEE floating-point number.
UC10 STRING 10 11 10-character string with null termination.
UC20 STRING 20 21 20-character string with null termination.
UC30 STRING 30 31 30-character string with null termination.
UC40 STRING 40 41 40-character string with null termination.
BYTE4 BYTE 4 4 Byte array with 4 bytes (i.e., an IP address).
Data Type (FBxConnect™ Name)2
# of Bytes Definition
BYTE6 BYTE 6 6
BYTE32 BYTE 32 32 Byte array with 32 bytes.
TIME INTEGER 64 8 Bytes 1 thru 4 – Seconds since Jan 1, 2000.
ENUM16 ENUM 2
BIN8 BIN 8 1 8-bit binary value (bitwise indication).
BIN16 BIN 16 2 16-bit binary value (bitwise indication).
BIN32 BIN 32 4 32-bit binary value (bitwise indication).
PRMREF PRMREF 41 Parameter Reference.
OBJREF OBJREF 21 Object Reference.
1. The
Protocol Specifications Manual (for Emerson FB3000 RTUs) (D310858X012).
2. The
FBxConnect™ Configuration Software.
column lists the data type name shown in the DNP3
column lists the data type name shown in
Byte array with 6 bytes (i.e., a MAC address).
16-bit unsigned integer, which represents an enumeration.
13
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
[This page is intentionally left blank]
14
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
File Menu
Use the options in this menu to save an FB Series product configuration file to your PC, save an FB Series product configuration to flash memory, load a saved configuration to the FB Series product, or close the current connection to the FB Series product.
Figure 9. File Menu (online and offline)
The File menu contains the following options:
– Save changes when modifying a solution's configuration file in offline mode (not connected
Save
to an FB Series product).
Save As – Save changes when modifying a solution's configuration file in offline mode (not
connected to an FB Series product) to a new file on your PC.
Upload Solution – Package application and configuration data from your FB Series product and
save it on your PC.
Download Solution – Load a previously saved configuration file or solution to the connected FB
Series product.
Download to Flash – Save a previously saved configuration file to the flash memory of the
connected FB Series product.
Close – Close the current connection and exit FBxConnect™.

2.1 Save (Offline Mode)

Use the Save option to save changes when modifying a solution's configuration file in offline mode (not connected to an FB Series product). It is good practice to save your configuration whenever you make a change to the file.
When you save a solution's configuration, a file is saved to your PC. This allows you to reload the solution's configuration if something should corrupt your device.
15
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Note
When working in offline mode from a newly created FBxConnect™ configuration file, read-only output parameters are values.
To save a solution's configuration file in offline mode:
1.
Open an FB Series product configuration file in Field Tools, and make the required changes.
2.
Figure 10. Solution Saved Successfully
File > Save from the FBxConnect™ main menu. The Solution Configuration Save dialog
Select opens and shows the progress of saving your solution's configuration.
not included in the configuration file and are instead displayed as default
3.
Close to exit the Solution Configuration Save dialog.
Select

2.2 Save As (Offline Mode)

Use the Save As option to save a copy of the current solution's configuration file and specify a new file name or location. This option is Series product).
Note
When working in offline mode from a newly created FBxConnect™ configuration file, read-only
output parameters are default values.
After you create a backup configuration file, you can load it onto a device using
Solution and save it to the device's flash memory using Download to Flash.
not included in the configuration file and are instead displayed as
only available while in offline mode (not connected to an FB
Download
16
To save a copy of a solution's configuration to a file on your PC:
1.
Open an FB Series product configuration file in Field Tools, and then make the required changes.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
2.
Figure 11. Solution Configuration Save As
3.
File > Save As from the FBxConnect™ main menu. The Configuration Save As dialog
Select displays:
Browse to open a file explorer window.
Select
Figure 12. Save As
4.
Navigate to a location on your PC you wish to save the configuration file, enter a name for the file, and then select
Save. The Configuration Save As screen re-displays.
17
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Note
The default file name includes the connection/device name, report type, and timestamp of
report creation (ConnectionName_ReportType_YYMMDDThhmmss).
The default location for saved configuration files is
C:\Users\Public\Documents\Emerson\FieldTools\FBx\Solutions. This location is in a hidden folder, and you may need to select "show hidden files" on your computer to view this folder.
Figure 13. Partial configuration
5.
If you want to manually select which Objects and Instances are saved in the configuration file, select
Partial Upload. The Select Configuration dialog opens.
Note
The Partial configuration option requires firmware version 2.7 or later.
18
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 14. Select Configuration
6.
Place a check mark next to the specific Objects and Instances you wish to save in the configuration file and click
Note
Select an object in the left most column to show the associated objects/instances in the next
column. Continue this process for the subsequent columns to select which parameters to include in the configuration. For example, select Measurement in the left-hand column and Fluid Properties in the middle column to display the configured Fluid Properties instances in the right-hand column.
An asterisk (*) next to an object indicates that only a partial set of parameters is selected for
that particular object.
Partial configuration files are stored with the file extension
Close. The Configuration Upload dialog re-displays.
.PTC.
19
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 15. Save
7.
Note
Save to save your device configuration to a file on your PC.
Select
A progress bar displays the status of the configuration save process.
8.
When the configuration save process is complete, select FBxConnect™ screen.
Figure 16. Solution Saved Successfully

2.3 Upload Solution

Close to return to the main
20
A Solution contains application and configuration data for an FB Series product. When you Upload a Solution, the system packages application and configuration data from your FB Series product and saves it on your PC.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Note
A Solution consists of two parts: a .ZSL file and a file folder. These two parts must have the same name and be used together when working offline or downloading a saved solution to another unit.
To upload a Solution to your PC:
1.
Figure 17. Solution Upload
File > Upload Solution for the FBxConnect™ main menu. The Solution Upload screen
Select displays.
2.
Select
Browse to open a file explorer window.
21
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 18. Save As
3.
Navigate to a location on your PC you wish to save the Solution, enter a name for the Solution, and then select
Note
The default file name includes the connection/device name, report type, and timestamp of
report creation (ConnectionName_ReportType_YYMMDDThhmmss).
The default location for saved Solutions is
C:\Users\Public\Documents\Emerson\FieldTools\FBx\Solutions. This location is in a hidden folder, and you may need to select "show hidden files" on your computer to view this folder.
Save. The Solution Upload screen re-displays.
22
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 19. Partial Upload
4.
If you want to manually select which Objects and Instances are saved in the configuration file, select
Partial Upload. The Select Configuration dialog opens.
Note
The Partial Upload option requires firmware version 2.7 or later.
23
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 20. Select Configuration
5.
Place a check mark next to the specific Objects and Instances you wish to save in the configuration file and click
Note
Select an object in the left most column to show the associated objects/instances in the next
column. Continue this process for the subsequent columns to select which parameters to include in the configuration. For example, select Measurement in the left-hand column and Fluid Properties in the middle column to display the configured Fluid Properties instances in the right-hand column.
An asterisk (*) next to an object indicates that only a partial set of parameters is selected for
that particular object.
Partial configuration files are stored with the file extension
6.
Note
Upload read only parameters to include all read-only parameters in the configuration
Select file. This option provides a snapshot of the FB Series product, and the resulting configuration file includes flow rates, totals, and diagnostic values. This option is useful when troubleshooting a device.
Close. The Configuration Upload dialog re-displays.
.PTC.
24
This option is not available if you select Partial Upload.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 21. Upload read only parameters
7.
Select
Upload. FBxConnect™ saves the selected Solution to your PC.
25
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 22. Upload
Note
A progress bar displays the status of the Solution save process.
8.
When the Solution upload process is complete, select FBxConnect™ screen.
Close to return to the main
26
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 23. Solution Saved Successfully

2.4 Download Solution

You can download a solution file to your FB Series product after you have saved the solution file to your PC. A Solution contains application and configuration data for an FB Series product. When you Download a Solution, the system transfers application and configuration data from your PC and loads it into your FB Series product.
Note
A Solution consists of two parts: a .ZSL file and a file folder. These two parts must have the same name and be used together when working offline or downloading a saved solution to another unit.
To download a Solution to your FB Series product:
1.
Note
Emerson recommends performing step 1 and step 2 prior to downloading a solution.
File > Download Solution from the FBxConnect™ menu. The Solution Download display
Select opens.
27
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 24. Solution Download
2.
3.
4.
5.
Note
Be sure to select Database is re-initialized with factory defaults.
6.
History to save history data. The History Report display opens. For more information,
Select refer to
Select to
Select to
Select
Select
History Report.
Alarms to save alarm data. The Alarm Report display opens. For more information, refer
Alarm Report.
Events to save event data. The Event Report display opens. For more information, refer
Event Report.
Cold Start. The Cold Start display opens. For more information, refer to Cold Start.
Solution Download. The Solution Download dialog displays:
28
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 25. Solution Download
7.
Figure 26. Open
Browse to open a file explorer window.
Select
29
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
8.
Navigate to a location on your PC of the saved configuration file and select Download screen re-displays.
Note
The default location for saved Solutions is
C:\Users\Public\Documents\Emerson\FieldTools\FBx\Solutions. This location is in a hidden folder, and you may need to select "show hidden files" on your computer to view this folder.
Partial configuration files are stored with the file extension
files, you
must select PTC files in the file type drop-down.
.PTC. To view partial configuration
Open. The Solution
Figure 27. Partial Dowenload
30
9.
If you want to manually select which Objects and Instances are saved in the configuration file, select
Partial Download. The Select Configuration dialog opens.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Note
The Partial Download option requires firmware version 2.7 or later.
Figure 28. Select Configuration
10.
Place a check mark next to the specific Objects and Instances you wish to download to your FB Series product and click
Note
Select an object in the left most column to show the associated objects/instances in the next
column. Continue this process for the subsequent columns to select which parameters to include in the configuration. For example, select Measurement in the left-hand column and Fluid Properties in the middle column to display the configured Fluid Properties instances in the right-hand column.
An asterisk (*) next to an object indicates that only a partial set of parameters is selected for
that particular object.
The system
present in the FB Series product.
does not download objects and instances that require features or licenses not
Close. The Solution Download dialog re-displays.
31
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 29. Selected Components
11.
A solution file may contain multiple items, including the standard FB Series product configuration and various applications. Place a check mark in the Selected column for any item you want to download to the FB Series product.
Note
If you include any applications in the download, use the drop-down menu in the Components column to select either the application and configuration or the only the configuration.
32
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 30. Download
12.
Note
A warning dialog opens if you attempt to download a solution created with a newer firmware
Download to download your Solution to your FB Series product.
Select
A progress bar displays the status of the Solution download process.
A warning dialog opens when you try to download a Solution that includes configured communications parameters. You can potentially lose connection with the FB Series product if you change the parameters on the port to which you are currently connected. Select continue loading the Solution with the new communications configuration. Select to the Solution Download screen.
version to an FB Series product with an older firmware version. Some features and parameters may not be present in older versions of firmware. Downloading the configuration may result in the loss of history records and configuration. Select
Yes to continue or No to cancel the
Yes to
No to return
33
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
download.
13.
When the Solution download is complete, select screen.
Figure 31. Solution Downloaded Successfully
Close to return to the main FBxConnect™

2.5 Download to Flash

Use this option to load a previously saved solution's configuration file to the flash memory of the connected FB Series product. The FB Series product can then load the solution's configuration file saved in flash memory when performing a cold start or rebuilding the FB Series product database after corruption.
34
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Note
You must save a solution's configuration file to your PC before you can download a solution's configuration file to flash memory. For information on saving a solution's configuration file to your PC, refer to
To download a previously saved solution's configuration file to flash memory:
1.
Select configuration to flash dialog displays.
Figure 32. Browse
Upload Solution and Save As.
File > Download to Flash from the FBxConnect™ main menu. The Download solution's
2.
Select
Browse to open a file explorer window.
35
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 33. Open Configuration File
3.
Navigate to the location of your saved configuration file and select
Open.
36
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 34. Download
4.
Note
A progress bar displays the status of the configuration save process.
5.
Download. FBxConnect™ downloads the selected configuration to the FB Series product
Select and saves the configuration to flash memory.
When the configuration download to flash process is complete, select main FBxConnect™ screen.
Close to return to the
37
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 35. Configuration Downloaded Successfully

2.6 Close

Use this option to close the current connection or configuration and exit FBxConnect™.
To close FBxConnect:
1.
Select
Figure 36. Closing Connection
2.
Select
38
File > Close from the FBxConnect™ main menu. A confirmation dialog opens.
Yes to close the connection.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Monitor Menu
Use the options in this menu to view the current flowing conditions, communication port status, FB Series product history, alarms, and events.
Figure 37. Monitor Menu
The Monitor menu contains the following options:
Main (FB3000 RTU)
I/O – View data about the currently installed I/O points and currently configured PID loops.
Gas
DP Meter – View the current flow rates and totals for gas differential pressure meters.
Linear MeterView the current flow rates and totals for gas linear meters.
Liquid
Liquid Linear Meter – View the current flow rates and totals for liquid linear meters.
Note
This option appears only if the FB Series product has a Liquid Calculation license installed.
History – View user periodic, hourly, daily, weekly, and monthly history data stored on the
connected FB Series product.
Alarms – View alarms stored on the connected FB Series product.
Events – View events stored on the connected FB Series product.
Comm Ports – View the status and configuration of the communications ports located on the
connected FB Series product.
– Shows an graphical representation of your RTU.

3.1 Main

The Main display shows a graphical representation of your RTU. The system displays an yellow line around objects that are links when you hover your cursor over them, and a tool-tip description of each object. Click on an object to open the FBxConnect™ configuration display for the selected object.
39
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Note
Click on a personality module to open the online help and view communications and I/O wiring
diagrams.
If a module encounters a communications failure (such as when a previously configured
module has been removed), the graphical representation of that module is dimmed and a red box with an exclamation mark appears under the module. Click the red box to uninstall the module.
To access this display, select Monitor > Main from the FBxConnect™ main menu.
Figure 38. Main

3.2 I/O

Use The I/O display to view data about the currently installed I/O modules. I/O data includes the type of I/O, engineering units to use with the point, and the current value of the point. Channels with an alarm currently raised are highlighted in red.
40
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
To access this display, select Monitor > I/O from the FBxConnect™ main menu. The I/O Overview display opens.
Note
The amount of I/O points shown on this display will vary depending on the type and number of
modules installed.
Fields highlighted in red are an indication of a value in an alarm state.
Figure 39. I/O

3.3 Gas

Use the Gas drop-down in the Monitor menu to view flow rates and totals for gas differential pressure and gas linear meters.
41
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Note
The Gas drop-down items display only if you have previously configured at least one gas differential pressure or linear meter on the
Figure 40. Monitor Gas
The Gas drop-down contains the following options:
Meter Setup display.
DP Meter
differential pressure meters.
Linear Meter – Use the Monitor Gas Linear Meter display to view the current flow rates and totals
for gas linear meters.
– Use the Monitor Gas DP Meter display to view the current flow rates and totals for gas

3.3.1 DP Meter

Use the Monitor Gas DP Meter display to view the current flow rates and totals for gas differential pressure meters. FBxConnect™ provides you with real-time values, as well as values for the current hour, previous hour, current day, and previous day.
To access this display:
1.
2.
Monitor > Gas > DP Meter from the FBxConnect™ main menu. The Monitor Gas DP
Select Meter display opens.
Click ▼ to select a meter to view.
42
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 41. Monitor Gas DP Meter

3.3.2 Linear Meter

Use the Monitor Gas Linear Meter display to view the current flow rates and totals for gas linear meters. FBxConnect™ provides you with real-time values, as well as values for the current hour, previous hour, current day, and previous day.
To access this display:
1.
2.
Monitor >Gas > Linear Meter from the FBxConnect™ main menu. The Monitor Gas Linear
Select Meter display opens.
Click ▼ to select a meter to view.
43
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 42. Monitor Gas Linear Meter

3.4 Liquid

Use the Liquid drop-down in the Monitor menu to view flow rates and totals for liquid linear meters.
Note
This option appears
The Liquid drop-down displays
on the
Figure 43. Monitor Liquid
The Liquid drop-down contains the following options:
Liquid Linear Meter
meters.
only if the FB Series product has a Liquid Calculation license installed.
only if you have previously configured at least one liquid meter
Meter Setup display.
– Use this display to view the current flow rates and totals for liquid linear
44
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)

3.4.1 Liquid Linear Meter

Note
This option appears
The Liquid drop-down displays
on the
Meter Setup display.
Use this display to view the current flow rates and totals for liquid linear meters. FBxConnect™ provides you with the current values, as well as values for the current and previous hour, day, week, and month.
To access this display, select Monitor > Liquid > Liquid Linear Meter. The Monitor Liquid Linear Meter display opens.
Click ▼ in the drop-down list at the top of the display to select an liquid linear meter to view.
Figure 44. Monitor Liquid Linear Meter
only if the FB Series product has a Liquid Calculation license installed.
D301882X012
December 2021
only if you have previously configured at least one liquid meter
45
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021

3.5 History

Use the History option to view user periodic, hourly, daily, weekly, and monthly history data. You can view data from each of the history groups, including User Periodic, General, and Station History.
Note
You
must first configure history points before viewing history data. For more information, refer
to
Configure – History.
The integrity of each history record is checked, and only history records with good integrity are shown.
Each history record has an associated sequence number. A missing history record sequence number indicates a deleted or lost record.
If you change the time zone of your PC, you updated time zone.
must restart your PC before reports reflect the
To view history data stored on an FB Series product:
1.
Figure 45. Collection Criteria
Monitor > History from the FBxConnect™ main menu. The Collection Criteria dialog
Select displays.
46
2.
Click ▼ in the are User Periodic 1, User Periodic 2, General History, Station History 1, or Station History 2.
History Group field to select the history group you want to view. Possible options
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
3.
If you select select a collection interval. Possible options are
4.
In the Collection period field, select oldest/newest history records or select and date range.
Note
Your selection in the Sorting field controls the options presented in this field.
5.
Click the button in the in the Possible options are:
Newest First – Records are sorted from the newest to the oldest.
Oldest First – Records are sorted from the oldest to the newest.
6.
If you select time in the
General History, Station History 1, or Station History 2 in the History Group field,
Hourly, Daily, Weekly, or Monthly.
Oldest 20 records/Newest 20 Records to view the twenty
Time Range to view history records from a specific time
Sorting field to control the order of records in the history report.
Time Range in the Collection period field, enter a beginning and ending date and
From and To fields.
7.
Figure 46. History
View to view the selected history.
Click
Note
Every calculated parameter in meter runs has a health attribute. The status of this attribute is determined by a combination of the inputs used to calculate the parameter and the status of the
47
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
calculation. Values with questionable data integrity are highlighted in pink, and a symbol is placed after the value. Hover your cursor over a highlighted value to view the reason for the highlighting. The symbol definitions are below: ? = In Fault # = In Override X = Unverified Value ! = In Alarm > = Over Range Limit ^ = Stale Value * = Invalid History @ = Undefined History
8.
Click the
9.
Click
10.
Click the your computer. For more information, refer to
Next button to retrieve 20 additional history records.
View All to retrieve all data stored in the flow computer.
Create Report button to open the History Report dialog and save a history report to
History Report.
11.
Click the

3.6 Alarms

Use the Alarms screen to view any currently active alarms on your device.
Note
The integrity of each alarm record is checked, and only alarm records with good integrity are
shown.
Each alarm record has an associated sequence number. A missing alarm record sequence
number indicates a deleted or lost record.
If you change the time zone of your PC, you
updated time zone.
To view alarms stored on the device:
1.
Monitor > Alarms from the FBxConnect™ main menu. The Collection Criteria dialog
Select displays.
Select New button to return to step 1 and select new collection criteria.
must restart your PC before reports reflect the
48
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 47. Collection Criteria
2.
In the Collection period field, select oldest/newest alarm records or select and date range.
Note
Your selection in the Sorting field controls the options presented in this field.
3.
Click the button in the in the Possible options are:
Newest First – Records are sorted from the newest to the oldest.
Oldest First – Records are sorted from the oldest to the newest.
4.
If you select time in the
5.
Click
View to view the selected alarms.
Time Range in the Collection period field, enter a beginning and ending date and
From and To fields.
Oldest 20 records/Newest 20 Records to view the twenty
Time Range to view alarm records from a specific time
Sorting field to control the order of records in the history report.
49
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 48. Alarms
6.
Click the
7.
Note
Double-click on the first column of a row that contains a Flow/Property Calculation Alarm to view information for any raised flow or property calculation alarm codes.
8.
9.
View All to retrieve all data stored in the flow computer.
Click
Click the your computer. For more information, refer to
Click the

3.7 Events

Use the Events screen to view events stored in device memory.
Note
The integrity of each event record is checked, and only event records with good integrity are
shown.
Next button to retrieve 20 additional alarm records.
Create Report button to open the Alarm Report dialog and save an alarm report to
Alarm Report.
Select New button to return to step 1 and select new collection criteria.
50
Each event record has an associated sequence number. A missing event record sequence
number indicates a deleted or lost record.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
If you change the time zone of your PC, you
updated time zone.
To access this screen:
1.
Figure 49. Collection Criteria
Monitor > Events from the FBxConnect™ main menu. The Collection Criteria dialog
Select displays.
must restart your PC before reports reflect the
2.
Note
You must configure your flow computer to keep separate legal and non-legal event logs on the
Configure – System screen to view this field.
3.
Note
Your selection in the Sorting field controls the options presented in this field.
4.
Sub-type field, select if you want to view legal or non-legal events.
In the
Collection period field, select Oldest 20 records/Newest 20 Records to view the twenty
In the oldest/newest event records or select and date range.
Click the button in the in the Possible options are:
Newest First – Records are sorted from the newest to the oldest.
Sorting field to control the order of records in the history report.
Time Range to view event records from a specific time
51
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Oldest First – Records are sorted from the oldest to the newest.
5.
If you select time in the
6.
Figure 50. Events
View to view the selected events.
Click
Time Range in the Collection period field, enter a beginning and ending date and
From and To fields.
7.
8.
9.
10.
View All to retrieve all data stored in the flow computer.
Click
Next to retrieve 20 additional event records.
Click
Create Report to open the Event Report dialog and save an event report to your
Click computer. For more information, refer to
Select New to return to step 1 and select new collection criteria.
Click

3.8 Comm Ports

Use the Comm Ports display to view the read-only status and configuration of each communications port on the FB Series product.
To access this display, select Monitor > Comm Ports from the FBxConnect™ main menu.
52
Event Report.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 51. Comm Ports
The Comm Ports display has the following tabs:
Overview
Series product, each port's user-defined name, a color-coded status for each port, and port statistics.
COM – Use these tabs to view read-only information about the current configuration of each serial
port.
ENET – Use this tab to view read-only information about the current configuration of the Ethernet
port.
USB – Use this tab to view read-only information about the current configuration of the USB port.
– Use this tab to view a read-only list of communications ports on the connected FB

3.8.1 Comm Ports – Overview Tab

Use this tab to view a read-only list of available communications ports on the connected FB Series product, a color-coded status for each port, and port statistics.
To access this tab:
1.
Monitor > Comm Ports. The Communication Ports display opens showing the Overview
Select tab.
53
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 52. Comm Ports – Overview Tab
54
2.
Review the status of each port (Enabled or Disabled).
3.
Note
Statistics to open a Communication statistics pop-up display and view the number of
Click messages sent and received on the selected communications port.
For serial ports, a separate tab shows statistics for each configured Port Owner (DNP3, Modbus Slave, and Modbus Master). For more information, refer to Communications – General Tab
For Ethernet ports, use the IP Connections drop-down to view statistics for each IP connection. For more information, refer to Communications – General Tab
.
.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 53. Communication statistics
4.
Note
For Ethernet ports, you must reset statistics for each IP Connection individually.
Reset statistics to reset the message counters for the selected communications port.
Click

3.8.2 Comm Ports – COM Tabs

Use these tabs to view read-only information about the current configuration of each serial port.
To access these tabs, select Monitor > Comm Ports > COM tab.
Note
To configure the information shown on this tab, refer to Communications.
55
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 54. Comm Ports – COM1 Tab

3.8.3 Comm Ports – ENET Tabs

Use this tab to view read-only information about the current configuration of the Ethernet port.
To access this tab, select Monitor > Comm Ports > ENET1/2 tab.
Note
The Ethernet port supports seven sessions. One session is dedicated to Modbus Master, and six
sessions are configurable as DNP3, Modbus Slave, or ROC communications.
To configure the information shown on this tab, refer to Communications
56
.
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 55. Comm Ports – Ethernet Tab

3.8.4 Comm Ports – USB Tab

Use this tab to view read-only information about the current configuration of the USB port of the FB3000 RTU.
To access this tab, select Monitor > Comm Ports > USB tab.
Note
To configure the information shown on this tab, refer to Communications.
57
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 56. Comm Ports – USB Tab
58
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Configure Menu
Use the options in this menu to configure FB Series product parameters, including meter runs, I/O, fluid properties, and history.
Figure 57. Configure Menu
The Configure menu contains the following options:
– Set a site name, set your home screen, and view general product information about your
Home
device.
Guided Setup – Configure the FB3000 using a guide that directs you through the configuration
process.
Engr UnitsConfigure the engineering units used in calculations.
Point Picker –View internal database parameters in the FB Series product.
I/O Setup – Configure the inputs and outputs of the flow computer.
Pass Thru – Configure parameters used when communicating with other Ethernet enabled FB
Series products and remote I/O racks.
Summary – Shows an overview of all configured stations and assigned meters.
Meter Setup – Configure general meter run settings, including the number of DP and linear meter
runs.
Gas
DP Meter – Configure differential pressure meters in your device.
Linear Meter – Configure linear meters in your device.
Fluid PropertiesDefine the physical properties of the fluid flowing through each meter.
ComponentsConfigure how the system calculates fluid composition and the different
components of the fluid flowing through the meter.
Liquid
Liquid Linear Meter – Configure liquid linear meters in your FB Series product.
Liquid Product – Define liquid products and their fluid properties.
Liquid DensityConfigure liquid density inputs.
Station – Configure parameters for stations.
Averages – Configure which inputs the system uses to calculate averages, and view the results of
those calculations.
59
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
– Configure which inputs the system totalizes, and to view the results of those calculations.
Totals
GC – Configure gas chromatograph options for each meter, and to view the data from each
configured gas chromatograph.
AlarmsConfigure which parameters need to be monitored, and which alarms need to be raised
when limits are reached.
History – Configure history points, to enable and disable history logging for the history groups, to
configure user period for user periodic history group types and to configure contract time for standard history group types.
Logs – Configure the options for history, alarm, and event logs.
PID Loops – Configure Proportional, Integral, and Derivative (PID) controls.
Action BlocksConfigure Action Blocks.
Math Blocks – Configure up to 10 instances of Math Blocks.
Effects – Configure custom logic components that drive a selected device parameter to a user
defined value.
Control Setup – Configure the number of Action Blocks, Math Blocks, Effects, and PID Loops
instances available.
CommunicationsConfigure the communications ports on your device.
Clock – Set the device clock and configure daylight savings time options.
Power Control – Conserve battery power to a radio or any other communicating device.
System – Configure your event log type and database recovery options.
I/O Bus – Configure the polling interval and view statistics for each I/O module installed in an
FB3000 RTU.
FBxNet – Configure the FB Series product to communicate over FBxNet.

4.1 Home

Use this display to enter a site name, modify which display opens when you first connect to the FB Series product, and view general product information.
To access this display:
1.
Select
Configure > Home. The Configure Home display opens.
60
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Product Type
read-only
Product Description
read-only
Site Name
Current Time
read-only
Note
only
Online
D301882X012
December 2021
Figure 58. Configure – Home
2.
Review – and change as necessary – the values in the following fields:
Field Description
This connected (online) or the configuration you are viewing (offline).
This
Enter a unique site name for the FB Series product.
This clock.
This field appears
.
field shows the type of FB Series product to which you are
field shows information about the FB Series product type.
field shows the current time and date of the FB Series product's
for FB Series products with a communication status of
61
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Firmware Version
read-only
Note
only
Offline
Home Screen
Browse
D301882X012 December 2021
Field Description
This configuration you are currently viewing.
This field appears
.
field shows firmware version for the FB Series product
for FB Series products with a communication status of
3.
Select
Select the connect to the FB Series product. For more information, refer to
Home Screen.
Save to save any changes you make to this tab.
button a choose a specific display to open when you first

4.1.1 Configuring the Home Screen

You can configure a specific display to open when you first connect to the FB Series product. The default is the Main standalone display, or factory display located in the C:\Users\Public\Documents\Emerson\FieldTools\FBx\CommonDisplays folder.
To set the home screen display:
1.
Figure 59. Configure – Home
Configure > Home. The Home display opens.
Select
display in the Monitor Menu, but you can configure any application display,
Configuring the
62
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
2.
Select the
Figure 60. Select Home Screen display
Browse button. The Select Home Screen display opens.
3.
From the list on the left-side of the display, select what type of display (factory, standalone, or application) you want to open when you first connect to the FB Series product. A list of possible displays shows on the right-side of the display.
63
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Figure 61. Select Home Screen display – Select Button
4.
Navigate to your desired display, highlight the display, and select the Home Screen display closes showing the Configure Home display.
Select button. The Select
64
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 62. Select Home Screen display – Select Button
5.
Note
You can also configure the display to show a specific instance when it opens. To do this, add a colon (:) after the display name followed by the instance. For example, the third instance of the Logs display opens if you enter
Save to save your changes. The next time you connect to the FB Series product, the
Select display you selected will be the first display that opens.

4.2 Guided Setup

Use Guided Setup to configure an FB3000 for the first time. Guided Setup directs you through the process of configuring your FB3000's measurement and I/O functionality, and automatically configures history points needed by API 21.1.
Note
The steps available in the Guided Setup differ based on your FB Series product type and
purchased options. This document shows all possible steps.
If you need help on a specific display of Guided Setup, press
for that particular display.
Configure_Logs_Logs:Log_3.
F1 to open the online help system
65
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
read-only
read-only
read-only
D301882X012 December 2021
CAUTION
Guided Setup may change your history configuration. If you have previously configured your FB3000, collect history data before proceeding.
To access Guided Setup:
1.
Figure 63. Guided Setup
Configure > Guided Setup. The first page of Guided Setup opens.
Select
2.
Review – and change as necessary – the values in the following fields:
Field Description
Site Name
Product Description
Product Type
Sets the name of the active connection in Field Tools.
This currently configuring.
This currently configuring.
field shows the description of the FB Series product you are
field shows the product type of the FB Series product you are
66
Current Time
Synchronize Time
This clock.
Select this button to synchronize the FB Series product clock with your PC clock.
field shows current time and date of the FB Series product
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
read-only
D301882X012
December 2021
Field Description
Serial Number
This configuring.
field shows the serial number of the FB Series product you are
Configuration Steps
3.
Next to advance to the next step in the Guided Setup.
Select
Shows the steps involved in the Guided Setup process.

4.2.1 Guided Setup: I\O Configuration

Use this display to configure the input and output types available on your FB3000 RTU. You can configure an input to operate as an analog input (AI), digital input (DI), or pulse input (PI).
Note
A separate
The amount of I/O points shown on this display varies depending on the device type and
installed options.
You can
add or remove an I/O module and copy or paste the configuration of one I/O module to another.
I/O Configuration display is available for each installed module.
right-click on the I/O Setup node or individual I/O modules in the navigation tree to
67
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
read-only
Note
All AI, All DI
All PI
D301882X012 December 2021
Figure 64. Guided Setup: I/O Configuration
1.
Review – and change as necessary – the values in the following fields:
Field Description
Module Type
8AIDIPI 2AO 2DO Module
This The fields available for each module type are described below:
The 8AIDIPI 2AO 2DO (3MIX12) module provides eight input channels and four output channels. You can configure each input channel as either an analog input (AI), digital input (DI), or pulse input (PI). The output channels are comprised of two analog outputs (AO) and two digital outputs (DO).
Inputs
Outputs
IO Loop Power Control
field shows the I/O module type installed in the selected slot.
Sets each input channel as either an analog input, digital input, or pulse input.
Select either channels as either analog inputs, digital inputs, or pulse inputs, respectively.
Shows the available output channels on the selected I/O module.
Enables or disables the 24-Volt loop power feature.
, or
to configure all input
68
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
All AO
All DO
D301882X012
December 2021
Field Description
8AODO Module
The 8AODO module provides eight output channels. You can configure each output channel as either an analog output (AO) or digital output (DO).
HART 4 Module
I/O Import Export
Outputs
IO Loop Power Control
The HART 4 (HRT04) module provides four input/output channels used to communicate with HART devices using the HART protocol. You can configure each channel as either an analog input (AI) or analog output (AO). A channel set as an input can be configured for use in point-to-point or multi-drop mode. A channel set as an output can be configured for use in point-to-point mode only.
Analog
Select this button to import a CSV file containing a new I/O configuration or export you current I/O configuration to a CSV file. For more information, refer to Importing I/O Configuration CSV Files,
CSV Files, and Creating I/O Configuration CSV Files.
Sets each output channel as either an analog putput, digital input, or pulse input.
Select either as either analog outputs or digital outputs, respectively.
Enables or disables the 24-Volt loop power feature.
Sets each channel as either and analog input (AI) or analog output (AO).
or
to configure all output channels
Exporting I/O Configuration
2.
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.

4.2.2 Guided Setup: I\O Configuration Details

Use this display to select what input and output types are available on your device. You can configure inputs to operate as an analog input (AI), digital input (DI), or pulse input (PI).
Note
A separate
The amount of I/O points shown on this display varies depending on the device type and
installed options.
I/O Configuration display is available for each installed module.
69
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
read-only
Note
only
Note
only
Note
only
must
D301882X012 December 2021
Figure 65. Guided Setup: I/O Config
70
1.
Review – and change as necessary – the values in the following fields:
Field Description
Channel
Tag
Units Type
Units
Type
This on the previous page.
Sets an identifier (up to 20-alphanumeric characters) for the selected channel.
Select ▼ to set the measurement type used for the selected channel.
This field appears outputs, or pulse inputs.
Select ▼ to set the engineering units used for the selected channel.
This field appears outputs, or pulse inputs.
Select ▼ to set if the channel measures either current input or voltage input.
This field appears
The default selection is Disabled. You
Voltage before the AI will scan a field device.
When Current Input is selected, an on-board software switchable 250-
ohm resistor is enabled for the selected channel.
column shows the type of I/O you selected for each channel
for channels configured as analog inputs, analog
for channels configured as analog inputs, analog
for channels configured as analog inputs.
select either Current or
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
only
Note
Note Note
must
Note
must
Note
only
HART I/O
read-only
D301882X012
December 2021
Field Description
EU Scaling Mode
Select ▼ to set how the EU scaling parameters are determined.
Low Reading EU
This field appears
Multi-Point Calibration
EU Scaling
Sets the minimum value (in A/D counts) that the analog input can measure.
for channels configured as analog inputs.
EU scaling parameters are determined by the calibration. You cannot modify the EU scaling parameters (Low Reading EU, High Reading EU, Adjusted A/D 0 Percent, Adjusted A/D 100 Percent) directly. You must use the calibration wizard to adjust the scaling of the AI.
If you download a configuration file that has Multi-Point Calibration selected, the calibration on your device remains unchanged.
EU scaling parameters are determined by the values you enter in the Low Reading EU, High Reading EU, Adjusted A/D 0 Percent, Adjusted A/D 100 Percent fields.
If you download a configuration file that has EU Scaling selected, the existing calibration on your device is overwritten using the EU scaling parameters.
High Reading EU
Details
HART Channel Configuration
You this field.
Sets the maximum value (in A/D counts) that the analog input can measure.
You this field.
Select this button to open the selected I/O channel configuration display.
Select to return to Guided Setup.
Use these fields to configure the HART I/O module.
These fields show
HART Channel
HART Comm Mode
select EU Scaling in the EU Scaling Mode field to enable entry in
select EU Scaling in the EU Scaling Mode field to enable entry in
if your configuration cantains a
This HART module.
Sets the communication mode for the selected channel. Possible options are:
Disabled
field displays the name of the channel on the
Stop all HART communication.
module.
71
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
only
analog inputs
Note
only
MultiDrop
D301882X012 December 2021
Field Description
Point to Point
Enables the channel to communication with one HART device per channel.
2.
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.
Number of Devices
Details
MultiDrop
Sets the number of HART devices connected in parallel.
This field appears Comm Mode field.
Select to open the HART I/O selected HART channel.
Enables the channel to communicate with up to five HART devices connected in parallel.
This option is available configured as
if you select

4.2.3 Guided Setup: Communication Settings

Use this display to enable communications with 4088B multivariable transmitters and configure gas chromatographs.
for channels
(AI).
in the HART
display and configure the
72
Figure 66. Guided Setup: Communication Settings
1.
Review – and change as necessary – the values in the following fields:
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
only
Note
only
Note
only
read-only
D301882X012
December 2021
Field Description
Enable/Disable 4088 Communications on COM3/4
Comm Port to GC
Select to enable or disable 4088 communication on communication port 3 and/or communications port 4 of the FB Series product.
Select to open a Point Picker
port on the FB Series product is connected to the gas chromatograph.
dialog and define which communications
GC Device Address
Baud Rate
GC Server IP Address
GC Server Port Number
Polling Interval
Polling
GC Polling Alarm
Sets the Modbus address the FB Series product uses to communicate with the gas chromatograph. You must set this value before the program can poll data and write it to the meter run.
Sets the baud rate of communications over the selected port.
This field applies
Specifies the IP address of the GC.
This field applies
Specifies port number used by the GC.
This field applies
Sets the delay (in seconds) the system waits before asking the gas chromatograph for the next set of results.
Select ▼ to enable or disable polling of the gas chromatograph.
This are:
Normal
Poll Failed
Comp Code Match Error
Poll Disabled
Auto config Failed
field shows the status of the poll result. Possible statuses
to GC connections using a serial port.
to GC connections using an Ethernet port.
to GC connections using an Ethernet port.
Chromat Type
Specifies either the American or European version of the SIM-2251 Modbus map and polling sequences.
73
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Note
only
Before
Comm Port to GC
GC Modbus Address
Disabled
Polling
Save
Note
must
Comm Port to GC
D301882X012 December 2021
Field Description
Auto Configure
Select this button to automatically configure the selected communications port and Modbus parameters necessary to poll the gas chromatograph. The port owner is automatically changed to Modubus Master for selected communications port.
This field is
selecting the Auto Configure button, you must first specify a communications port in the the then click
To view which parameters are automatically configured when you select Auto Configure, refer to Automatically Configured Parameters
available if you are connected to an FB Series product.
field, select
to write these settings to the FB Series product.
field and an address in
in the
field, and
.
Details
2.
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.
Select this button to open the Communications configuration display for the communications port configured in the Comm Port to GC field. Select
to return to Guided Setup.
You
configure the

4.2.4 Guided Setup: 4088 Setup

Use this display to enable communications with a 4088B multivariable transmitter on either COM3 or COM4.
Note
If you enabled 4088B communications on multiple communications ports, there is a separate
tab for each port at the top of the display.
When communicating with more than six 4088Bs at 9600 baud, update times exceed once per
second.
field before this button is active.
74
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
to return to Guided Setup.
1
240
read-only
D301882X012
December 2021
Figure 67. Guided Setup: 4088 Setup
1.
Review – and change as necessary – the values in the following fields:
Baud Rate
COM3/4 Details
Transmitter Scanning
Tag
Description
4088B Modbus Address
Sets the baud rate for 4088B communications using the selected port.
Select this button to open the Communications configuration display for the communications port configured in the Comm Port to GC field. Select
Place a check mark to enable the system to scan the selected 4088B for data.
Enable All
Sets a name (up to 8-alphanumeric characters) for the selected 4088B.
Sets a description (up to 16-alphanumeric characters) for the selected 4088B.
Sets the unique Modbus address for the selected 4088B multivariable transmitter. The default address is mode, each 4088B must have a unique address. Use Address sensor to determine the address of the connected sensor. This is similar to polling a device using Address and Group 240. When Address 240 is used, the sensor responds with its address by updating the Address field.
Select to enable communications for all transmitters.
. If the 4088B is used in the multi-drop
to poll the
Input Health Status
This 4088B.
field shows the current operating status of the selected
75
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Note
Baud Rate
must
Enable
Transmitter Scanning
Note
must
Enable
Transmitter Scanning
D301882X012 December 2021
Auto Scan
Details
Wiring Diagram
2.
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.
Select to have the system automatically scan the baud rates for the 4088B with the indicated Modbus address.
The baud rate of the transmitter is changed to the baud rate
configured in the
You
to activate this button.
Select this button to open the 4088B configuration display for the selected
transmitter. Select to return to Guided Setup.
You activate this button.
Click to open a 4088B wiring diagram for the selected communications port.
select the
select the
field.
checkbox in the
checkbox in the
field
field to

4.2.5 Guided Setup: Fluid Selection

Use this display to select the station layout, and to assign number and types of meters for each fluid type.
76
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Custom
Apply
Note
read-only
Custom
any
D301882X012
December 2021
Figure 68. Guided Setup: Fluid Selection
1.
Station Layout
Fluid Type
DP Meters
Review – and change as necessary – the values in the following fields:
Select how meters are assigned to stations.
One per each meter
One per fluid type
Custom
This field is
meter in your FB Series product.
Select the type of fluids being measured.
Set the number of differential pressure meters for each fluid type.
Each meter is assigned to a separate station.
Each fluid type is assigned to a separate station.
Select
Station Layout Configuration display. This display allows
you to specify the number of stations, assign the fluid type for each station, and configure the number and types of meters assigned to each station.
and set to
and select
if you have previously configured
to open the Custom
77
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
read-only
read-only
D301882X012 December 2021
Linear Meters
Maximum Meters
Used/Allocated Meters
2.
Complete the following step based on your selections:
If you select either
select
Apply to save your selections to the FB Series product. A confirmation dialog opens.
Select
OK to advance to Engineering Units.
Figure 69. Confirmation
Set the number of linear meters for each fluid type.
This
This FB3000.
One per each meter or One per each fluid type in the Station Layout field,
field shows the number of meters available in your FB3000.
field shows the number of meters currently assigned in your
If you select
assigned to a station, select display.
If you select
to a station, select
Custom in the Station Layout field and you do not have any meters currently
Next to open the Custom Station Layout Configuration pop-up
Custom in the Station Layout field and you do have any meters currently assigned
Next to open the Station Assignment display.

4.2.6 Guided Setup: Custom Station Layout Configuration

Use this display to manually customize your station layout. You can select the type of fluid being measured by the station, and the number and type of meters belonging to each station.
Note
This display opens only if you select Custom in the Station Layout field on the Fluid Selection display and you
do not have any meters currently assigned to a station.
78
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Note
must
Natural Gas
Note
must
Natural Gas
D301882X012
December 2021
Figure 70. Guided Setup: Custom Station Layout Configuration
1.
2.
Station
Fluid
Gas DP Meter
Gas Linear Meter
Add Station to add a station and configure its properties.
Select
Review – and change as necessary – the values in the following fields:
Select  to select a station iteration to configure.
Select  to set the type of fluids being measured by the selected station.
Select to set the number of gas differential pressure meters being
measured by the selected station.
You
Select to set the number of gas linear meters being measured by the
selected station.
You
select
select
in the Fluid field to enable this field.
in the Fluid field to enable this field.
79
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Note
must
read-only
D301882X012 December 2021
Liquid Linear Meter
Totals
3.
Note
Stations without at least one meter type assigned are automatically removed from the list.
Figure 71. Confirmation
Apply to save any changes you make to this display. A confirmation dialog opens.
Select
Select to set the number of liquid linear meters being measured by the
selected station.
You
These assigned to station.
select Liquid in the Fluid field to enable this field.
fields show the total number of each meter type currently
4.
Yes to advance to the next step in the Guided Setup.
Select

4.2.7 Guided Setup: Station Assignment

Use this display to manually customize your station layout. You can select the type of fluid being measured by the station, and the number and type of meters belonging to each station.
Note
This display opens only if you select Custom in the Station Layout field on the Fluid Selection display and you
do have any meters currently assigned to a station.
80
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012
December 2021
Figure 72. Guided Setup: Station Assignment
1.
Tabs appear at the top of the display. Each tab consists of up to 12 meters. Select the tab that contains the meters you want to assign to a specific station.
2.
Select to open a
Note
Gas meters and liquid meters cannot belong to the same station. If you assign a gas meter to a liquid station or a liquid meter to a gas station, a Flow Calculation alarm is raised.
3.
Note
You cannot change the fluid type of a station if a meter is already assigned to that station. In this case, you change the Fluid Type field.
4.
Station Fluid Type to configure the fluid type measured by each station.
Select
must first remove any meters assigned to the selected station before you are able to
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.
Point Picker dialog and assign each meter to a specific station.

4.2.8 Guided Setup: Engineering Units

Use this display to configure the engineering units used by the station for measurements. You can select Set all to US/Imperial, Set all to Metric, Set all to Canadian, or configure each measurement type individually. You can also configure how many decimal places are used for each measurement value.
81
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
D301882X012 December 2021
Conversion factors for the different engineering units are taken from the following standards:
IEEE/ASTM SI 10-2002 - IEEE/ASTM Standard for Use of the International System of Units (SI):
The Modern Metric System
Manual of Petroleum Measurement Standards Chapter 15—Guidelines for the Use of the
International System of Units (SI) in the Petroleum and Allied Industries
ANSI/API MPMS Ch. 14.3.3/AGA Report No. 3
Note
FB Series products use full-resolution data for all calculations. The Decimal Places fields on this
display are used
Fields on this display differ based on what fluid type the selected station is measuring (Natural
Gas or Liquid).
Changes to engineering units are applied to the station and all meters assigned to the selected
station, even if a meter has previously been configured. Additionally, any I/O associated with the station or its meters is also updated. Refer to Configure – Summary are assigned to each station.
only for viewing data in FBxConnect Configuration Software.
to view which meters
Molar mass units are dependent upon the density units:
Density Unit Molar Mass Unit
lb/ft³ lb/lb-mol
lb/MMCF lb/lb-mol
lb/US gal lb/lb-mol
lb/bbl lb/lb-mol
RD lb/lb-mol
°API lb/lb-mol
kg/m³ kg/kmol
kg/L kg/kmol
g/cc g/mol
Joule Thomson units are dependent upon the pressure units:
Pressure Unit Joule Thompson Unit
psi °F/psi
kPa K/kPa
82
bar °C/bar
MPa K/MPa
kg/cm² K/MPa
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Set all to US/Imperial
Set all to Metric
Set all to Canadian
D301882X012
December 2021
Acceleration units are dependent upon the linear long units:
Linear Long Unit Acceleration Unit
ft ft/s²
m m/s²
Note
The 4088 does not support temperature units of Kelvin.
Figure 73. Guided Setup: Engineering Units (Liquid Station shown)
1.
Review – and change as necessary – the values in the following fields:
Select to automatically configure the selected station to use US/Imperial units for all measurements and calculations.
Select to automatically configure the selected station to use metric units for all measurements and calculations.
Select to automatically configure the selected station to use Canadian units for all measurements and calculations.
83
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
D301882X012 December 2021
Meter Inputs
Totals
Rates
Fluid
Length
K-Factor
Select ▼ to choose the measurement units used with each meter input and the number of decimal places shown in FBxConnect. Meter Inputs include differential pressure units, static pressure units, and temperature units.
Select ▼ to choose the measurement units used when calculating totals and the number of decimal places shown in FBxConnect. Totals include gas volume units, energy units, mass units, liquid volume units, water volume units, and flow time units.
Select ▼ to choose the measurement units used when displaying rate and the number of decimal places shown in FBxConnect. Rates include gas volume units, energy units, mass units, liquid volume units, and water volume units.
Select ▼ to choose the measurement units used when performing fluid calculations and the number of decimal places shown in FBxConnect. Fluid properties include dynamic viscosity, density, volume-based heating value, mass-based heating value, water density, and oil density.
Select ▼ to choose the measurement units used for distance and the number of decimal places shown in FBxConnect. Length includes linear short and linear long.
Select ▼ to choose the measurement units used when calculating the K­factor and the number of decimal places shown in FBxConnect. K-factor includes volumetric and mass.
Other
Reset Decimal Places
2.
Apply to save your selections to the FB Series product and advance to the next step in
Select the Guided Setup.
Select ▼ to choose the measurement units used for other calculations, including water content, and the number of decimal places shown in FBxConnect.
Select to revert all measurement units to show the default number of decimal places in FBxConnect.

4.2.9 Guided Setup: Station

Use this display to configure parameters for the selected station.
Note
Available station parameters are slightly different based on the measured fluid type. All
possible fields are described below.
84
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
D301882X012
December 2021
You can
configuration of one station to another.
Figure 74. Guided Setup: Station (Natural Gas shown)
right-click on the Station node in the navigation tree to copy or paste the
1.
Review – and change as necessary – the values in the following fields:
General Tag
Description
Sets an identifier (up to 20-alphanumeric characters) for the selected station.
Sets a description (up to 20-alphanumeric characters) for the selected station.
85
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
read-only
to return to Guided Setup.
Note
User
Note
User
only
Fluid Type
Natural Gas
Note
only
Fluid Type
Natural Gas
D301882X012 December 2021
Details
Atmospheric Pressure
Base Temperature Selection
Base Pressure Selection
Fluid Type
Select this button to open the standard Station configuration display. Select
Atm Pressure Mode
Override Atm Pressure
Sets the flow measurement Base Temperature specified in the gas contract. The temperature units are in degrees Fahrenheit or degrees Celsius.
Select
Sets the flow measurement Base Pressure specified in the gas contract. The pressure units are in psi(a) or kPa.
This selected station.
Click ▼ to set how the system acquires the atmospheric pressure value used in calculations. Possible options are:
Override
Calculated
Sets a value to use for the atmospheric pressure in calculations when Override is selected in the Atm Pressure Mode field.
to enter a custom temperature value.
field shows the type of fluid measured by the
The system uses a value you define in the Override Atm Pressure field.
The system calculates the atmospheric pressure value.
Contract Properties
Component Configuration
Select
This field appears
Contract Hour
Contract Day of Week
Contract Day of Month
These fields appears
Components Object
Operation Mode
to enter a custom pressure value.
Sets the hour at which daily, weekly, and totals rollover and history records are logged (for daily-based, weekly-based, or monthly-based reports).
Sets the day of the week at which totals rollover and history records are logged (for weekly-based reports).
Sets the day of the month at which totals rollover and history records are logged (for monthly-based reports).
Click to open a Point Picker
Components object from the database that the station uses to calculate fluid composition.
Sets how the system acquires the component information. Possible options are:
for stations with a
for stations with a
of
of
dialog and select a
.
.
86
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Note
only
Measured
Operation Mode
Note
only
Measured
Operation Mode
Note
only
Fluid Type
Natural Gas
D301882X012
December 2021
GC Data Object
Stream Number
Measured
Override
Remote Download
Select to open a Point Picker
GC Data instance is associated with each Components instance.
This field appears
Sets the Stream number associated with each GC Data instance configured in the GC Data Object field.
Selected composition is obtained from the LIVE parameters updated from a gas chromatograph.
Selected composition is obtained from the OVRD parameters entered by a user. Changes to OVRD parameters are logged to the event log.
Selected composition is obtained from the OVRD parameters downloaded from a SCADA host or other remote master. Changes to OVRD parameters are not logged to the event log.
dialog and define which
if you select
field.
in the
Calculation Methods
Heating Value Calc Standard
Calculation Failure Option
This field appears
Sets the calculation standard used in heating value calculations. Options are GPA 2172 (2009) and ISO 6976 (1995).
Selection of ISO 6976 will use the base compressibility
(Zb) value calculated per ISO 6976 in the heating value calculation. Selection of GPA 2172 will use the Selected Base Compressibility value in the heating value calculation.
This field appears
Sets how the FB Series product responds if a calculation failure occurs. Possible options are:
Alarm Disabled
Alarm and Continue
if you select
field.
for stations with a
.
No alarm is logged if a calculation failure occurs.
An alarm is logged and the calculation continues if a calculation failure occurs.
in the
of
87
FBxConnect™ Configuration Software User Manual (for the FB3000 RTU)
Field
Description
Note
only
Fluid Type
Natural Gas
AGA8 2017 Part 2 / GERG 2008
AGA8 2017 Gross 1
Gross 2, AGA8 1994 Gross 1
Gross
2
SGERG
ISO 12213-3
NX-19
Heating Value Calc Standard
AGA8
ISO 12213-2
SGERG 1991 Std, CV/RD/N2/H2 or CV/N2/CO2/H2
ISO 12213-3 2006 Pref, Set B or Set D
SGERG 1991 RD/N2/CO2/H2 or ISO 12213-3 2006 Set C
NX-19 1962
NX-19 Mod or NX-19 VDE/VDI
D301882X012 December 2021
Compressibility / Density Calculation
Sets the desired compressibility/density calculation for the selected station. Select a standard from the list on the left, and then select a version/method to use from the list on the right.
Alarm and Halt Calculation
This field appears
pure gas measurement. For more information about pure gas measurement, refer to
If you select
, any
value and real relative density base compressibility are calculated using your selection in the
Some compressibility/density standards are based on a specific set of reference conditions. For the most accurate results, ensure the following reference conditions are configured based on the Compressibility/Density Calculation you select:
, any
An alarm is logged and the calculation stops if a calculation failure occurs.
for stations with a
can be used for both natural gas and
Measuring Pure Gas.
or
, or any
of
option, the real heating
field.
or
.
 Any reference conditions.
 Any reference conditions.
The Base Temperature Selection field is set to 0°C. The Base Pressure Selection field is set to 1.01325 bar. The Heating Value Combustion Temperature field is set to 25°C.
The Base Temperature Selection field is set to 0°C. The Base Pressure Selection field is set to 1.01325 bar. The Heating Value Combustion Temperature field is set to 25°C.
The Base Temperature Selection field is set to 0°C. The Base Pressure Selection field is set to 1.01325 bar.
The Base Temperature Selection field is set to 60°F. The Base Pressure Selection field is set to 14.73 psi(a).
The Base Temperature Selection field is set to 0°C. The Base Pressure Selection field is set to 1.01325 bar.
88
Loading...