Remote Automation Solutions FB2200 Flow Computer 8-Channel Expansion I/O Board Field Replacement Guide Manuals & Guides

FB2200 Flow Computer 8-Channel Expansion I/O Board Field Replacement Guide
FB2200 Flow Computer 8-Channel Expansion I/O Board Field Replacement Guide
D301804X012
November 2020
400217010-KIT
Remote Automation Solutions
FB2200 Flow Computer 8-Channel Expansion I/O Board Field Replacement Guide
D301804X012 November 2020
Device Safety Considerations
Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety implications. In some situations, improperly using this device may result in damage or injury. Keep this manual in a convenient location for future reference. Note that these instructions may not cover all details or variations in equipment or cover every possible situation regarding installation, operation, or maintenance. Should problems arise that are not covered sufficiently in the text, immediately contact Customer Support for further information.
Protecting Operating Processes
A failure of this device – for whatever reason -- may leave an operating process without appropriate protection and could result in possible damage to property or injury to persons. To protect against this, you should review the need for additional backup equipment or provide alternate means of protection (such as alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.). Contact Remote Automation Solutions for additional information.
Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the equipment has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or local law regulations or codes. You also agree to indemnify Remote Automation Solutions and hold Remote Automation Solutions harmless from any liability or damage which Remote Automation Solutions may incur or suffer due to your failure to ensure device cleanliness.
Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with OSHA rules and regulations as specified in Design Safety Standards for Electrical Systems, 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the National Electrical Code). You must also ground mechanical or pneumatic instruments that include electrically operated devices such as lights, switches, relays, alarms, or chart drives. Important: Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring personnel safety. The guidelines and recommendations in this manual are intended to meet or exceed applicable codes and regulations. If differences occur between this manual and the codes and regulations of authorities having jurisdiction, those codes and regulations must take precedence.
Protecting from Electrostatic Discharge (ESD)
This device contains sensitive electronic components which be damaged by exposure to an ESD voltage. Depending on the magnitude and duration of the ESD, it can result in erratic operation or complete failure of the equipment. Ensure that you correctly care for and handle ESD-sensitive components.
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential system expertise. Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at education@emerson.com.
Ethernet Connectivity
This automation device is intended to be used in an Ethernet network which does not have public access. The inclusion of this device in a publicly accessible Ethernet-based network is not recommended.
FB2200 Flow Computer 8-Channel Expansion I/O Board Field Replacement Guide
Item
Field Replacement Kit Part Number
WARNING
WARNING
D301804X012
November 2020

Replacing the 8-Channel Expansion I/O Board

You can replace the 8-channel expansion I/O board in the field provided that the replacement is the same part and version.
Refer to the table below for the correct field replacement kit part number.
8-Channel Expansion I/O Board
Ambient Temperature Range
May be used up to a maximum ambient temperature of 80°C and a minimum ambient temperature of –40°C; refer to the data plate attached to the device for ambient temperature.
Required Tools
#2 Phillips-head screwdriver
Hexagonal torque wrenches Ranges must include 1 to 2 in-lbs (0.1 to 0.2 N-m) and 7 to 9 in­lbs (0.8 to 1.0 N-m)
Electrical Ratings
Input Voltage: 10.5 Vdc to 30 Vdc external supply (Max power at 10 watts)
Restriction
Hazardous area approvals require that any part replaced in the field be the exact same part (like for like). Upgrading or substituting different parts violates hazardous area certification.
400217010-KIT
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
EXPLOSION HAZARD – Substitution of any components may impair suitability for Class I, Division
2.
Tip
Because some of these procedures involve removing small parts such as screws, we recommend you provide a container to hold small parts.
1
Loading...
+ 5 hidden pages