Remote Automation Solutions FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide Manuals & Guides

FB1200 Flow Computer 6-Channel I/O Expansion Board Field Replacement Guide
FB1200 Flow Computer 6-Channel I/O Expansion Board Field Replacement Guide
D301819X012
November 2020
400215010-KIT
Remote Automation Solutions
FB1200 Flow Computer 6-Channel I/O Expansion Board Field Replacement Guide
D301819X012 November 2020
Device Safety Considerations
Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety implications. In some situations, improperly using this device may result in damage or injury. Keep this manual in a convenient location for future reference. Note that these instructions may not cover all details or variations in equipment or cover every possible situation regarding installation, operation, or maintenance. Should problems arise that are not covered sufficiently in the text, immediately contact Customer Support for further information.
Protecting Operating Processes
A failure of this device – for whatever reason -- may leave an operating process without appropriate protection and could result in possible damage to property or injury to persons. To protect against this, you should review the need for additional backup equipment or provide alternate means of protection (such as alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.). Contact Remote Automation Solutions for additional information.
Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the equipment has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or local law regulations or codes. You also agree to indemnify Remote Automation Solutions and hold Remote Automation Solutions harmless from any liability or damage which Remote Automation Solutions may incur or suffer due to your failure to ensure device cleanliness.
Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with OSHA rules and regulations as specified in Design Safety Standards for Electrical Systems, 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the National Electrical Code). You must also ground mechanical or pneumatic instruments that include electrically operated devices such as lights, switches, relays, alarms, or chart drives. Important: Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring personnel safety. The guidelines and recommendations in this manual are intended to meet or exceed applicable codes and regulations. If differences occur between this manual and the codes and regulations of authorities having jurisdiction, those codes and regulations must take precedence.
Protecting from Electrostatic Discharge (ESD)
This device contains sensitive electronic components which be damaged by exposure to an ESD voltage. Depending on the magnitude and duration of the ESD, it can result in erratic operation or complete failure of the equipment. Ensure that you correctly care for and handle ESD-sensitive components.
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential system expertise. Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at education@emerson.com.
Ethernet Connectivity
This automation device is intended to be used in an Ethernet network which does not have public access. The inclusion of this device in a publicly accessible Ethernet-based network is
not recommended.
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
Item
Field Replacement Kit Part Number
WARNING
WARNING
D301819X012
November 2020

Replacing the 6-Channel Expansion I/O Board

You can replace the optional 6-channel expansion I/O board provided you replace it with the exact same part.
Restriction
Hazardous area approvals require that any part replaced in the field be the exact same part (“like­for-like”). Upgrading or substituting different parts violates hazardous area certification.
Refer to the table below for the correct field replacement part number.
Board Type UL Field Replacement Kit
Part Number
6-Channel Expansion I/O Board 400215010-KIT
Ambient Temperature Range
May be used up to a maximum ambient temperature of 80°C and a minimum ambient temperature of –40°C; refer to the data plate attached to the device for ambient temperature.
Required Tools
#1 Phillips-head screwdriver
#2 Phillips-head screwdriver
3/32-inch flat head screwdriver (for 3.81 mm pitch terminal block connections and disconnecting the internal connector to the sensor)
Hexagonal torque wrenches with 3mm, #1, and #2 Phillips-head bits. Ranges must include 1 to 2 in-lbs (0.1 to 0.2 N-m), 4 to 6 in-lbs (0.5 to 0.7 N-m), and 10 to 12 in-lbs (1.1 to 1.4 N-m).
Electrical Ratings
Input Voltage: 5.7-30Vdc, 10 Watts Max
I/O Ratings (FB1200 Flow Computer):
o
4 Digital Outputs: 0.5A, 24Vdc
o
2 Analog Outputs: 4-20 mA
EXPLOSION HAZARD – Substitution of any components may impair suitability for Class I, Division 1 or Class I, Division 2.
EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.
1
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
DANGER
1
Screw
2
Retaining Clamp
3
Washer
D301819X012 November 2020
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
EXPLOSION HAZARD: Never remove end cap(s) in a hazardous location. Removing cover(s) in a hazardous location could result in an explosion.

Removing/Replacing the 6-Channel Expansion I/O Board

UL Listed 6-Channel I/O Expansion Board Field Installed Accessory Kit for Use in Class I, Division 1, Groups C, and D; and Class I, Division 2, Groups A, B, C, and D, Part No. 400215010-KIT for use with UL Listed Model Series FB1200.
1. Remove the retaining clamps on the end caps (if present) using a 3 mm hexagonal wrench.
Components of Retaining Clamp Assembly
2
2. Grasp the end cap.
Front End Cap Rear End Cap
3. Unscrew the end cap by turning it counter-clockwise until it comes off. Set the end cap aside in a safe location.
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012
November 2020
Note
If you need more leverage, place a long screwdriver or other appropriate tool across the two notches in the end cap to act as a pry bar.
Front End Cap (unscrewed) Rear End Cap (removed)
4. Unplug terminal block TB1 to disconnect main power. TB1 has eight connectors See the graphic below for detail:
TB1 (Eight connectors)
3
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012 November 2020
5. With a #2 Phillips-head screwdriver, loosen the two captive fastening screws in the recessed areas of the battery pack enclosure.
Note
Not all units include an internal battery but the battery enclosure is always present.
Captive Screws
6. With a #1 Phillips-head screwdriver, loosen the two bottom captive fastening screws on the HMI module. Leave the two top screws on the HMI module connected to the battery pack enclosure.
Captive Screws (loosened)
7. Grasp the HMI module and gently pull it and the battery pack enclosure out of the housing.
4
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012
November 2020
HMI Module (removed)
8. If the battery pack holds an internal battery, disconnect it.
Internal Battery (disconnected)
9. Set the battery pack enclosure and HMI module assembly aside.
5
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012 November 2020
10. With a #2 Phillips-head screwdriver, loosen the two captive fastening screws in the plastic
bezel that hold the CPU module in place.
Bezel Fastening Screws
11. Grasp the plastic bezel and gently pull the CPU module out of the housing.
CPU Module (removed)
12. Use a 3/32-inch flathead screwdriver to separate the internal wire connector plug from the plug on the bottom of the CPU module.
6
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012
November 2020
Internal Wire Connector Plug on CPU Module
13. Use a #1 Phillips-head screwdriver to remove the four screws that attach the I/O expansion board to the CPU module and separate the board from the CPU module. Set the old 6­channel expansion I/O board aside and now use those four screws to attach the (replacement) 6-channel expansion I/O board to your CPU module. Torque screws to 1 to 2 in-lbs (0.1 to 0.2 N-m).
Correct IO Expansion Board Screw Locations
new
7
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012 November 2020
14. Snap the internal wire connector plug (from Step 12) onto the mating plug on the bottom of
the CPU module and gently slide the CPU module with the new 6-channel expansion I/O board into the housing, being careful not to pinch wires. Press firmly into place.
15. Tighten the two captive fastening screws that hold the CPU module in the housing with a
torque value of 4 to 6 in-lbs (0.5 to 0.7 N-m).
16. Slide the HMI module/battery pack enclosure assembly (from Step 7) back into the housing.
With a torque value of 4 to 6 in-lbs (0.5 to 0.7 N-m), tighten the captive fastening screws on the top of the battery pack enclosure and then tighten the bottom screws on the HMI module.
17. Reconnect battery power (if present). (See the connector shown in Step 8).
18. Restore main power at connector TB1.
19. Carefully align the end cap threads with the threads of the enclosure and replace the end
caps. Screw each end cap clockwise (eight full turns) until it is tightly sealed to the enclosure. Endcaps must have at least 8 full threads engaged upon reassembly.
Note
If you need more leverage place a long screwdriver or other appropriate tool across the two notches in the end cap to act as a pry bar.
20. If applicable, tighten the retaining clamp onto the end cap using a 3mm hexagonal wrench.
When tightening, torque to 10 to 12 in-lbs (1.1 to 1.4 N-m).
8
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
D301819X012
November 2020
9
FB1200 Flow Computer 6-Channel Expansion I/O Board Field Replacement Guide
For customer service and technical support,
Global Headquarters, North America, and Latin America:
end-user.
Europe:
Middle East/Africa:
Asia-Pacific:
T +65 6777 8211| F +65 6777 0947
D301819X012 November 2020
visit www.Emerson.com/SupportNet
Emerson Automation Solutions Remote Automation Solutions 6005 Rogerdale Road Houston, TX 77072 U.S.A. T +1 281 879 2699 | F +1 281 988 4445
www.Emerson.com/RemoteAutomation
Emerson Automation Solutions Remote Automation Solutions Unit 1, Waterfront Business Park Dudley Road, Brierley Hill Dudley DY5 1LX UK T +44 1384 487200 | F +44 1384 487258
Emerson Automation Solutions Remote Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone – South 2 Dubai U.A.E. T +971 4 8118100 | F +971 4 8865465
Emerson Automation Solutions Remote Automation Solutions 1 Pandan Crescent Singapore 128461
© 2018-2020 Remote Automation Solutions, a business unit of Emerson Automation Solutions. All rights reserved.
This publication is for informational purposes only. While every effort has been made to ensure accuracy, this publication shall not be read to include any warranty or guarantee, express or implied, including as regards the products or services described or their use or applicability. Remote Automation Solutions (RAS) reserves the right to modify or improve the designs or specifications of its products at any time without notice. All sales are governed by RAS terms and conditions which are available upon request. RAS accepts no responsibility for proper selection, use or maintenance of any product, which remains solely with the purchaser and/or