Remote Automation Solutions Bristol Lower Power Transmitter Interface Board Manuals & Guides

Product Information Package
PIP-TIBS3530
Mar., 2007
TeleFlow Plus & TeleRTU Plus
Low Power Transmitter Interface Board Part No. 392950-01-4
For The Following Bristol Instruction Manuals: CI-3530-20B & CI-3530-25B
www.EmersonProcess.com/Bristol
IMPORTANT! READ INSTRUCTIONS BEFORE STARTING!
Be sure that these instructions are carefully read and understood before any operation is attempted. Improper use of this device in some applications may result in damage or injury. The user is urged to keep this book filed in a convenient location for future reference.
These instructions may not cover all details or variations in equipment or cover every possible situation to be met in connection with installation, operation or main­tenance. Should problems arise that are not covered sufficiently in the text, the pur­chaser is advised to contact Bristol for further information.
EQUIPMENT APPLICATION WARNING
The customer should note that a failure of this instrument or system, for whatever reason, may leave an operating process without protection. Depending upon the application, this could result in possible damage to property or injury to persons. It is suggested that the purchaser review the need for additional backup equipment or provide alternate means of protection such as alarm devices, output limiting, fail­safe valves, relief valves, emergency shutoffs, emergency switches, etc. If additional in-formation is required, the purchaser is advised to contact Bristol .
RETURNED EQUIPMENT WARNING
When returning any equipment to Bristol for repairs or evaluation, please note the following: The party sending such materials is responsible to ensure that the materials returned to Bristol are clean to safe levels, as such levels are defined and/or determined by applicable federal, state and/or local law regulations or codes. Such party agrees to indemnify Bristol and save Bristol harmless from any liability or damage which Bristol may incur or suffer due to such party's failure to so act.
ELECTRICAL GROUNDING
Metal enclosures and exposed metal parts of electrical instruments must be grounded in accordance with OSHA rules and regulations pertaining to "Design Safety Standards for Electrical Systems," 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the National Electrical Code).
The grounding requirement is also applicable to mechanical or pneumatic in­struments that include electrically-operated devices such as lights, switches, relays, alarms, or chart drives.
EQUIPMENT DAMAGE FROM ELECTROSTATIC DISCHARGE VOLTAGE
This product contains sensitive electronic components that can be damaged by exposure to an electrostatic discharge (ESD) voltage. Depending on the magnitude and duration of the ESD, this can result in erratic operation or complete failure of the equipment. Read supplemental document S14006 at the back of this manual for proper care and handling of ESD-sensitive components.
Bristol 1100 Buckingham Street, Watertown, CT 06795
Telephone (860) 945-2200
WARRANTY
A. Bristol warrants that goods described herein and manufactured by Bristol are free
from defects in material and workmanship for one year from the date of shipment unless otherwise agreed to by Bristol in writing.
B. Bristol warrants that goods repaired by it pursuant to the warranty are free from
defects in material and workmanship for a period to the end of the original warranty or ninety (90) days from the date of delivery of repaired goods, whichever is longer.
C. Warranties on goods sold by, but not manufactured by Bristol, are expressly limited
to the terms of the warranties given by the manufacturer of such goods.
D. All warranties are terminated in the event that the goods or systems or any part
thereof are (i) misused, abused or otherwise damaged, (ii) repaired, altered or modified without Bristol's consent, (iii) not installed, maintained and operated in strict compliance with instructions furnished by Bristol, or (iv) worn, injured or damaged from abnormal or abusive use in service time.
E. THESE WARRANTIES ARE EXPRESSLY IN LIEU OF ALL OTHER
WARRANTIES EXPRESS OR IMPLIED (INCLUDING WITHOUT LIMITATION WARRANTIES AS TO MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE), AND NO WARRANTIES, EXPRESS OR IMPLIED, NOR ANY REPRESENTATIONS, PROMISES, OR STATEMENTS HAVE BEEN MADE BY BRISTOL UNLESS ENDORSED HEREIN IN WRITING. FURTHER, THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION OF THE FACE HEREOF.
F. No agent of Bristol is authorized to assume any liability for it or to make any written
or oral warranties beyond those set forth herein.
A. Buyer's sole remedy for breach of any warranty is limited exclusively to repair or
replacement without cost to Buyer of any goods or parts found by Seller to be defective if Buyer notifies Bristol in writing of the alleged defect within ten (10) days of discovery of the alleged defect and within the warranty period stated above, and if the Buyer returns such goods to Bristol's Watertown office, unless Bristol's Water­town office designates a different location, transportation prepaid, within thirty (30) days of the sending of such notification and which upon examination by Bristol proves to be defective in material and workmanship. Bristol is not responsible for any costs of removal, dismantling or reinstallation of allegedly defective or defective goods. If a Buyer does not wish to ship the product back to Bristol, the Buyer can arrange to have a Bristol service person come to the site. The Service person's transportation time and expenses will be for the account of the Buyer. However, labor for warranty work during normal working hours is not chargeable.
B. Under no circumstances will Bristol be liable for incidental or consequential
damages resulting from breach of any agreement relating to items included in this quotation, from use of the information herein or from the purchase or use by Buyer, its em-ployees or other parties of goods sold under said agreement.
REMEDIES
How to return material for Repair or Exchange
Before a product can be returned to Bristol for repair, upgrade, exchange, or to verify proper operation, form (GBU 13.01) must be completed in order to obtain a RA (Return Authorization) number and thus ensure an optimal lead time. Completing the form is very important since the information permits the Bristol Repair Dept. to effectively and efficiently process the repair order.
You can easily obtain a RA number by:
A. FAX Completing the form (GBU 13.01) and faxing it to (860) 945-3875. A Bristol Repair
Dept. representative will return call (or other requested method) with a RA number.
B. E-MAIL Accessing the form (GBU 13.01) via the Bristol Web site (www.bristolbabcock.com)
and sending it via E-Mail to brepair@bristolbabcock.com representative will return E-Mail (or other requested method) with a RA number.
C. Mail Mail the form (GBU 13.01) to
Bristol Inc. Repair Dept. 1100 Buckingham Street Watertown, CT 06795
A Bristol Repair Dept. representative will return call (or other requested method)
with a RA number.
D. Phone
Calling the Bristol Repair Department at (860) 945-2442. A Bristol Repair Depart-
ment representative will record a RA number on the form and complete Part I, then send the form to the Customer via fax (or other requested method) for Customer completion of Parts II & III.
A copy of the completed Repair Authorization Form with issued RA number should be in­cluded with the product being returned. This will allow us to quickly track, repair, and return your product to you.
. A Bristol Repair Dept.
Bristol Repair Authorization Form (off-line completion)
(Providing this information will permit Bristol to effectively and efficiently process your retu rn. Completion is required to
receive optimal lead time. Lack of information may result in increased lead times.)
Date___________________ RA #___________________SH Line No.____________ Standard Repair Practice is as follows: Variations to this is
practice may be requested in the “Special Requests” section.
Evaluate / Test / Verify Discrepancy
Repair / Replace / etc. in accordance with this form
Return to Customer
Part I Please complete the following information for single unit or multiple unit returns
Address No. (office use only) Address No. (office use only) Bill to : Ship to:
Purchase Order: Contact Name:____________________________________ Phone: Fax: E-Mail:
Part II Please complete Parts II & III for each unit returned
Model No./Part No. Description
Please be aware of the Non warranty standard charge:
There is a $100 minimum evaluation charge, which is
applied to the repair if applicable ( in “returned” B,C, or D of part III below)
Range/Calibration S/N Reason for return
: Failure Upgrade Verify Operation Other
1. Describe the conditions of the failure (Frequency/Intermittent, Physical Damage, Environmental Conditions,
Communication, CPU watchdog, etc.)
(Attach a separate sheet if necessary)
2. Comm. interface used: Standalone RS-485 Ethernet Modem (PLM (2W or 4W) or SNW) Other:______________
3. What is the Firmware revision? _____________________ What is the Software & version?
Part III If checking “replaced” for any question below, check an alternate option if replacement is not available
A. If product is within the warranty time period but is excluded due
to Bristol’s warranty clause, would you like the product:
repaired returned replaced scrapped?
B. If product were found to exceed the warranty period, would you like the product:
C. If product is deemed not repairable would you like your product: D. If Bristol is unable to verify the discrepancy, would you like the product:
repaired returned replaced scrapped?
returned replaced scrapped? returned replaced *see below?
* Continue investigating by contacting the customer to learn more about the problem experienced? The person to contact
that has the most knowledge of the problem is: ______________________________ phone_____________________
If we are unable to contact this person the backup person is: _________________________ Special Requests: ____________________________________________________________________________________
phone_____________________
____________________________________________________________________________________________________
Ship prepaid to: Bristol Inc., Repair Dept., 1100 Buckingham Street, Watertown, CT 06795
Phone: 860-945-2442 Fax: 860-945-2220 Form GBU 13.01 Rev. C 04/27/06
Bristol
Training
GET THE MOST FROM YOUR BRISTOL
BABCOCK INSTRUMENT OR SYSTEM
Avoid Delays and problems in getting your system on-line
Minimize installation, start-up and maintenance costs.
Make the most effective use of our hardware and software.
Know your system.
As you know, a well-trained staff is essential to your operation. Bristol Inc. offers a full schedule of classes conducted by full-time, professional instructors. Classes are offered throughout the year at three locations: Houston, Orlando and our Watertown, CT headquarters. By participating in our training, your personnel can learn how to install, calibrate, configure, program and maintain any and all Bristol products and realize the full potential of your system.
For information or to enroll in any class, contact our training department in Watertown at (860) 945-2343. For Houston classes, you can also contact our Houston office, at (713) 685-
6200.
A Few Words About Bristol Inc.
For over 100 years, Bristol® has been providing innovative solutions for the measurement and control industry. Our product lines range from simple analog chart recorders, to sophisticated digital remote process controllers and flow computers, all the way to turnkey SCADA systems. Over the years, we have become a leading supplier to the electronic gas measurement, water purification, and wastewater treatment industries.
On off-shore oil platforms, on natural gas pipelines, and maybe even at your local water company, there are Bristol Inc. instruments, controllers, and systems running year-in and year-out to provide accurate and timely data to our customers.
Getting Additional Information
In addition to the information contained in this manual, you may receive additional assis­tance in using this product from the following sources:
Help Files / Release Notes
Many Bristol software products incorporate help screens. In addition, the software typically includes a ‘read me’ release notes file detailing new features in the product, as well as other information which was available too late for inclusion in the manual.
Contacting Bristol Inc. Directly
Bristol's world headquarters is located at 1100 Buckingham Street, Watertown, Connecticut 06795, U.S.A.
Our main phone numbers are:
(860) 945-2200 (860) 945-2213 (FAX)
Regular office hours are Monday through Friday, 8:00AM to 4:30PM Eastern Time, excluding holidays and scheduled factory shutdowns. During other hours, callers may leave messages using Bristol's voice mail system.
Telephone Support - Technical Questions
During regular business hours, Bristol's Application Support Group can provide telephone support for your technical questions.
For technical questions about TeleFlow products call (860) 945-8604.
For technical questions about ControlWave call (860) 945-2394 or (860) 945-2286.
For technical questions regarding Bristol’s OpenEnterprise product, call (860) 945-3865 or e-mail: scada@bristolbabcock.com
For technical questions regarding ACCOL products, OpenBSI Utilities, UOI and all other software except for ControlWave and OpenEnterprise products, call (860) 945-2286.
For technical questions about Network 3000 hardware, call (860) 945-2502.
You can e-mail the Application Support Group at: bsupport@bristolbabcock.com
The Application Support Group maintains an area on our web site for software updates and technical information. Go to: www.bristolbabcock.com/services/techsupport/
For assistance in interfacing Bristol hardware to radios, contact Bristol’s Communication Technology Group in Orlando, FL at (407) 629-9463 or (407) 629-9464.
You can e-mail the Communication Technology Group at:
orlandoRFgroup@bristolbabcock.com
Telephone Support - Non-Technical Questions, Product Orders, etc.
Questions of a non-technical nature (product orders, literature requests, price and delivery information, etc.) should be directed to the nearest sales office (listed on the rear cover of this manual) or to your Bristol-authorized sales representative.
Please call the main Bristol Inc. number (860-945-2200) if you are unsure which office covers your particular area.
Visit our Site on the World Wide Web
For general information about Bristol Inc. and its products, please visit our site on the World Wide Web at: www.bristolbabcock.com
Training Courses
Bristol’s Training Department offers a wide variety of courses in Bristol hardware and software at our Watertown, Connecticut headquarters, and at selected Bristol regional offices, throughout the year. Contact our Training Department at (860) 945-2343 for course information, enrollment, pricing, and scheduling.
PIP-TIBS3530
LOW POWER TRANSMITTER INTERFACE BOARD
PT. NO. 392950-01-4
TABLE OF CONTENTS
SECTION TITLE
Section 1 - INTRODUCTION
1.1 DESCRIPTION...................................................................................................................1
1.1.1 Transmitter Operation.........................................................................................................1
1.2 LED INDICATORS............................................................................................................2
1.3 JUMPER JP1.......................................................................................................................2
Section 2 - INSTALLATION & SERVICE
2.1 REMOVAL/REPLACEMENT & INSTALLATION OF THE LPTIB..............................3
2.1.1 Removal/Replacement of the Low Power Transmitter Interface Bd..................................3
2.1.2 Installation of the Low Power Transmitter Interface Board Option...................................4
2.2 FIELD WIIRING.................................................................................................................5
2.2.1 Terminal Connections.........................................................................................................5
Section 3 - SPECIFICATIONS
3.1 GENERAL SPECIFICATIONS..........................................................................................8
3.2 ENVIRONMENTAL SPECIFICATIONS..........................................................................8
SUPPLEMENTS
Special Instructions for Class I, Division 2 Hazardous Locations.............................................. Appendix A
PIP-TIBS3530 Page 0-1 Table Of Contents
Section 1
INTRODUCTION
1.1 DESCRIPTION
Low Power Transmitter Interface Boards allow up to two (2) Bristol, Series 3508 or Series 3808 Transmitters to communicate with an ACCOL loaded host TeleFlow 3530-20B Electronic Gas Measurement Computer (EGMC) or 3530-25B TeleRTU. The EGMC/RTU polls and stores data from each transmitter and communicates with the network. Two LEDS on the LPTI Board [CD (DS1) & RTS (DS2)] indicate the communication status.
The LPTI Board is housed in the TeleFlow Plus or TeleRTU Plus enclosure and is interfaced to a TeleFlow I/O Expansion Board. LPTI Boards are powered by a 12V power supply or battery. LPTI Boards contain one jumper (JP1) for configuration purposes.
The LPTI Board (Figure 1) is wired to the TeleFlow I/O Expansion Board connector (TB5) and is mounted with Snap Track (holder) and Mounting Bracket as illustrated in Figure 2.
1.1.1 Transmitter Operation
3508 Series
Each Transmitter must be assigned a unique address via the SMARTKIT program as described in Section 4.2 PROGRAM LOADING AND STARTUP Transmitter manual. Additionally, all Transmitters wired to the TI Board must be operated in the minimum current mode (3.8 mA). This mode is selected via the SMARTKIT program as described in Section 4.7 TRANSMITTER OPERATING MODES Transmitter manual, i.e., CI-3508-10C, CI-3508-30C or CI-3508-99C.
of the appropriate 3508
of the appropriate 3508
Figure 1 - Transmitter Interface Board P/N 392950-01-4
PIP-TIBS3530 Page 1 Transmitter Interface Bds.
3808 MVT Series
Each Model 3808 MVT Transmitter must be assigned a unique address via the WebBSI
On/Off Menu (see Section 3 of Customer Instruction Manual CI-3808). Additionally,
Sign only analog versions of the 3808 MVT can be interfaced to a Transmitter Interface Board.
1.2 LED INDICATORS
The LPTIB contains two LEDs which have the following functions: Carrier Detect (CD) and Request to Send (RTS). When the board is sending a Request To Send, LED DS2 (RTS) will be ON and LED DS1 (CD) will be OFF. Conversely, when the LPTIB is receiving data from a 3508/3808 Transmitter, LED DS2 (RTS) will be OFF and LED DS1 - Carrier Detect (CD) will be ON.
1.3 JUMPER JP1
Jumper JP1 is used to configure the LPTIB for operation with one or two 3508/3808 Transmitters. If only one 3508/3808 Transmitter is to be connected to the LPTIB, Jumper JP1 must be installed across JP1-1 and JP1-2. Additionally, when only one 3508/3808 Transmitter is to be connected to the LPTIB, it must be connected to connector TB1. When two 3508/3808 Transmitters are connected to the LPTIB, Jumper JP1 must be removed and stored in either JP1-1 or JP1-2.
PIP-TIBS3530 Page 2 Transmitter Interface Bds.
Section 2
INSTALLATION & SERVICE
2.1 REMOVAL/REPLACEMENT & INSTALLATION OF THE LPTIB
2.1.1 Removal/Replacement of the Low Power Transmitter Interface Bd.
An installed LPTI Board option will contain the following parts:
1. LPTI Board (with removable Terminal Blocks
2. Dual PCB Mounting Bracket
3. Snap Track
4. LPTI Board Cables (Power & RS-232 Intf.)
5. Two #8-32 x ¼” SEM Screws
6. Two #8-32 x 3/8” Pan Head Screws and Two #7-32 Elastic Locking Nuts
Figure 2 - Low Power Transmitter Interface Board Mounting Diagram
TeleFlow Plus or TeleRTU with Power Distribution Board, 21V Power Supply
Board & Digital To Relay I/O Board
PIP-TIBS3530 Page 3 Transmitter Interface Bds.
To remove the optional Low Power Transmitter Interface Board follow steps 1 through 4 below. To replace the Low Power Transmitter Interface Board follow steps 2 and 3 below in reverse order, installing rather than removing the item in question and then perform step
4.
1. Open the Instrument Front Cover (Door).
2. Unplug the removable Terminal Blocks (with wiring harnesses installed) from the
optional Low Power Transmitter Interface Board.
3. Slide the Low Power Transmitter Interface Board toward the front of the unit and out of
the Snap Track.
Note: If a replacement Low Power Transmitter Interface Board is available
follow steps 2 through 3 in reverse order (after configuring Jumper JP1 (see Section 1.3), installing rather than removing the item in question.
4. Close and Secure the Door.
Figure 3 - Bottom View of TeleRTU Plus (Similar to TeleFlow Plus)
2.1.2 Installation of the Low Power Transmitter Interface Board Option
1. Open the Instrument Front Cover.
2. If the unit in question already contains a Power Distribution Board, but only has one Snap Track, the other Snap Track will have to be installed. This will require removal of the two (2) #8-32x3/8” Pan Head Screws and the two (2) #8-32 Elastic locking Nuts which secure the Power Distribution Board’s Snap Track to the Dual PCB Mounting Bracket. Secure the second Snap Track to the Dual PCB Mounting Bracket as shown in Figure 2 using two (2) #8-32 x 3/8” Pan Head Screws and two (2) #8-32 Elastic Locking
PIP-TIBS3530 Page 4 Transmitter Interface Bds.
Nuts. Configure the LPTIB for operation with one or two 3508/3808 Transmitters. If only one 3508/3808 Transmitter is to be connected to the LPTIB, Jumper JP1 must be installed across JP1-1 and JP1-2. Additionally, when only one 3508/3808 Transmitter is to be connected to the LPTIB, it must be connected to connector TB1. When two 3508/3808 Transmitters are connected to the LPTIB, Jumper JP1 must be removed and installed in JP1-1 or JP1-2. Slide the LPTI Board into the Snap Track (see Figure 2).
3. Connect power wiring (14 AWG) and RS-232 Interface wiring (20 to 14 AWG) to LPTIB. Route field wiring cable(s) (20 to 14 AWG) associated with the LPTI Board into the TeleFlow Plus or TeleRTU Plus through a ¾” conduit fitting (user installed) on the bottom of the enclosure (see Figure 3). Connect Transmitter wiring to the appropriate LPTI Board Terminal Connectors (TB1 and TB2) (see Section 2.2.1, Table 1 & Figure 4).
5. Close and Secure the Instrument Front Cover.
2.2 FIELD WIRING
The device uses compression-type terminals that accommodate up to #14 AWG wire. A connection is made by inserting the bared end (1/4 inch Max.) into the clamp beneath the screw and then securing the screw. Insert the bared end fully to prevent short circuits.
Allow some slack in the wires when making terminal connections. The slack makes the connections more manageable and minimizes mechanical strain on the printed circuit boards and harnesses.
2.2.1 Terminal Connections
LPTI Boards contain four terminal blocks that accommodate interface connections to the 3530-20B or 3530-25B, power and field wiring connections. TB1 & TB2 are two-position Terminal Blocks, which connect to the signal/power inputs of the transmitters. Three­position Terminal Block (TB3) connects to the 3530-20B or 3530-25B power source. Five­position Terminal Block TB4 provides an RS-232 interface with the host 3530-20B/25B.
TABLE 1 - LPTI BOARD TERMINAL DESIGNATIONS
LPTIB
TB#
TB1-1 XMTR1- 3508/3808- 3508/3808- 3508/3808­TB1-2 XMTR1+ 3508/3808+ 3508/3808+ 3508/3808+ TB2-1 XMTR2- 3508/3808- 3508/3808- 3508/3808­TB2-2 XMTR2+ 3508/3808+ 3508/3808+ 3508/3808+ TB3-1 SHUTDOWN N/A N/A N/A TB3-2 +12VIN TB5-1 of PDB. CPUB J8-1 or J6-1 CPUB J2-1 or J4-1 TB3-3 +12VRET TB5-2 of PDB. CPUB J8-2 or J6-2 CPUB J2-2 or J4-2 TB4-1 GND GND of LPI/OB TB5-1 LPI/OB TB5-1 LPI/OB TB5-1 TB4-2 CTS RTS of LPI/OB TB5-5 LPI/OB TB5-5 LPI/OB TB5-5 TB4-3 RTS CTS of LPI/OB TB5-4 LPI/OB TB5-4 LPI/OB TB5-4 TB4-4 RXD TXD of LPI/OB TB5-7 LPI/OB TB5-7 LPI/OB TB5-7 TB4-5 TXD RXD of LPI/OB TB5-6 LPI/OB TB5-6 LPI/OB TB5-6
LPTIB
TB NAME
CONNECTION
if PDB.
Is Present
Note: PDB = Power Distribution Board
3530-20B
CONNECTION
If no PDB.
3530-25B
CONNECTION
If no PDB.
PIP-TIBS3530 Page 5 Transmitter Interface Bds.
LPTI Boards may be connected to internally powered transmitters (see Figure 4). In the case of an Internally Powered Transmitter (powered from LPTIB’s on-board +12V Sup­ply/Regulator) an external +12 Vdc power supply is wired to LPTI Board connector TB3 as shown in Figure 4. The supply is wired across the +12VIN and +12VRET terminals. The input voltage range is +10.8Vdcc to +16Vdc.
LPTIB’s are typically powered from the 3530’s power source (battery). Because of power distribution restrictions (CPU Board connector wiring capacity), power is typically routed through a Power Distribution Board (see Figures 5 & 6). Power Distribution Boards are mounted to the 3530 in question using a Snap Track and Dual PCB Mounting Bracket identical to the ones used for the LPTI Board and the Digital to Relay I/O Board options.
Figure 4 - Internally Powered Transmitter Field Wiring
PIP-TIBS3530 Page 6 Transmitter Interface Bds.
Figure 5 - Mounted Power Distribution Board
Figure 6 - Power Distribution Board Schematic/Wiring Diagram
PIP-TIBS3530 Page 7 Transmitter Interface Bds.
Section 3
SPECIFICATIONS
3.1 GENERAL SPECIFICATIONS
Communication Interface: RS-232 (± 3V minimum)
3508/3808 Interface: FSK Modem - Bell 202 Compatible (1200 Hz/2200 Hz modulation) Baud Rate is 1200
ESD Susceptibility: Field connected circuits are designed to meet the requirements of IEC 801-2 for ESD withstand capability up to 10KV.
EMI Compatibility: Designed to coexist within a shielded enclosure with the TeleFlow (3530-20B) or the TeleRTU (3530-25B) electronics. EMI radiation is insignificant and susceptibility is
comparable or superior to associated
electronics.
Transient Susceptibility: Field connected circuits are designed to meet the requirements of ANSI/­ IEEEC37.90-1998 (Formerly IEEE 472) for surge withstand capability.
3.2 ENVIRONMENTAL SPECIFICATIONS
Operating Temperature: -40°C to +60°C (-40°F to +140°F)
Storage Temperature: -40°C to +85°C (-40°F to +185°C)
Relative Humidity: 15% - 95% Non-condensing
Vibration: 1G for 10Hz to 500Hz
per PMC-31-1 (without damage or impairment)
PIP-TIBS3530 Page 8 Transmitter Interface Bds.
Low Power Transmitter Interface Board
Special Instructions for Class I, Division 2 Hazardous Locations
1. The Bristol Low Power Transmitter Interface Board (LPTIB) is listed by Underwriters
Laboratories (UL) as nonincendive and is suitable for use in Class I, Division 2, Groups A, B, C and D hazardous locations or non-hazardous locations only. Read this document carefully before installing a nonincendive Bristol LPTIB Board. In the event of a conflict between the LPTIB Board User Manual (PIP-TIBS3530) and this document, always follow the instructions in this document.
2. Wiring must be performed in accordance with Class I, Division 2 wiring methods as
defined in Article 501-4 (b) of the National Electrical Code, NFPA 70 for installations within the United States, or as specified in Section 18-152 of the Canadian Electrical Code for installation in Canada.
3. WARNING: EXPLOSION HAZARD - Substitution of components may impair
suitability for use in Class I, Division 2 environments.
4. WARNING: EXPLOSION HAZARD - When situated in a hazardous location,
turn off power before servicing/replacing the unit and before installing or removing I/O wiring.
5. WARNING: EXPLOSION HAZARD - Do Not disconnect equipment unless the
power has been switched off or the area is known to be nonhazardous.
03/24/2007 Appendix A of PIP-TIBS3530 - LPTIB Board Page 1 of 1
Product Information Package
PIP-TIBS3530
Low Power Transmitter Interface Board Part No. 392950-01-4
Mar., 2007
Emerson Process Management Bristol, Inc.
1100 Buckingham Street Watertown, CT 06795 Phone: +1 (860) 945-2262 Fax: +1 (860) 945-2525 www.EmersonProcess.com/Bristol
Emerson Electric Canada, Ltd. Bristol Canada
6338 Viscount Rd. Mississauga, Ont. L4V 1H3 Canada Phone: 905-362-0880 Fax: 905-362-0882 www.EmersonProcess.com/Bristol
Emerson Process Management BBI, S.A. de C.V.
Homero No. 1343, 3er Piso Col. Morales Polanco 11540 Mexico, D.F. Mexico Phone: (52-55)-52-81-81-12 Fax: (52-55)-52-81-81-09 www.EmersonProcess.com/Bristol
Emerson Process Management Bristol Babcock, Ltd.
Blackpole Road Worcester, WR3 8YB United Kingdom Phone: +44 1905 856950 Fax: +44 1905 856969
www.EmersonProcess.com/Bristol Emerson Process Management
Bristol, Inc.
22 Portofino Crescent, Grand Canals Bunbury, Western Australia 6230 Mail to: PO Box 1987 (zip 6231) Phone: +61 (8) 9725-2355 Fax: +61 (8) 8 9725-2955 www.EmersonProcess.com/Bristol
The information in this document is subject to change without notice. Every effort has been made to supply complete and accurate information. However, Bristol, Inc. assumes no responsibility for any errors that may appear in this document.
If you have comments or questions regarding this manual, please direct them to your local Bristol sales representative, or direct them to one of the addresses listed at left.
Bristol, Inc. does not guarantee the accuracy, sufficiency or suitability of the software delivered herewith. The Customer shall inspect and test such software and other materials to his/her satisfaction before using them with important data.
There are no warranties, expressed or implied, including those of merchantability and fitness for a particular purpose, concerning the software and other materials delivered herewith.
TeleFlow is a trademark of Bristol, Inc. The Emerson logo is a trade mark and service mark of Emerson Electric Co. Other trademarks or copyrighted products mentioned in this document are for information only, and belong to their respective companies, or trademark holders.
Copyright (c) 2007, Bristol, Inc., 1100 Buckingham St., Watertown, CT 06795. No part of this manual may be reproduced in any form without the express written permission of Bristol, Inc.