REMKO KWK 220, KWK 130, KWK 200, KWK 280, KWK 360 Operation,technology,spare Parts

...
Page 1
REMKO KWK / KWK-ZW
KWK 130, KWK 140, KWK 200, KWK 220, KWK 280, KWK 300, KWK 360, KWK 420, KWK 590, KWK 680, KWK 740, KWK 870 KWK 130ZW, KWK 140ZW, KWK 200ZW, KWK 220ZW, KWK 280ZW, KWK 300ZW, KWK 360ZW, KWK 420ZW KWK 590ZW, KWK 680ZW, KWK 740ZW, KWK 870ZW
Cold water wall- and ceiling units Cold water wall- and ceiling units for installation in partition walls and suspended ceilings
Edition GB – N05
Page 2
Page 3
Contents
Safety notes
Environmental protection and recycling
Transportation and packaging
Guarantee
Intended use
Unit description
System layout
Operation
Shutdown
Care and maintenance
Troubleshooting and customer service
Installation Instructions for qualified personnel
Installation
4
4
4
5
5
5
6
7
7
8-9
10
11-14
14-16
Condensate drainage connection
Electrical wiring
Electrical drawings
Leak testing
Before commissioning
Commissioning
Unit dimensions
Exploded view of the unit
Spare parts list
Technical data
Services
Carefully read this operating manual prior to commissioning / using the units!
16-17
17-18
20-21
22-23
22-23
24-27
28-29
18
18
19
19
This manual is an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself. This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
3
Page 4
REMKO KWK / KWK-ZW
Safety notes
Carefully read the operating manual before placing the unit in service for the first time. It contains useful tips and notes as well as hazard warnings to prevent injury to persons or material damage . Failure to follow the directions in this manual can endanger persons, the environment and the equipment itself and will void any claims for liability.
Keep this manual close to the units.
The units and components
should not be exposed to any mechanical load, and extreme levels of humidity or sunlight.
Only qualified personnel may
set up and install the units and components.
The set-up, connection, and
operation of the unit and its components must take place in accordance with the operating conditions stipulated in this manual and comply with all applicable local regulations.
Mobile units must be set up
securely on suitable surfaces and in an upright position. Stationary units must be permanently installed for operation.
Modification of the units
and components supplied by REMKO is not permitted and can cause malfunctions.
Units and components may
not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
The electrical power supply is to
be adapted to the requirements of the units.
The operational safety
of the units and components is only assured if they are fully assembled and used as intended. Safety devices may not be modified or bypassed.
Do not operate units or
components with obvious defects or signs of damage.
All housing parts and unit
openings, e.g. air inlets and outlets, must be free from foreign objects, liquids, or gases.
The units and components must
be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
Contact with some parts
of the unit or components can result in burns or other injuries. Wearing appropriate protective clothing is necessary to avert risks.
Only authorised and trained
persons are permitted to access and operate the units and components.
Installation, repair and
maintenance work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the unit is disconnected from the power.
To preclude any risks to persons
originating from the units, appropriate precautions must be taken when installing, repairing, maintaining, cleaning or working on the units.
Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
Only recyclable materials are used to manufacture the units and components. Help protect the environment by ensuring that the units or components (for example batteries) are not disposed of in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
Transportation and packaging
The units are shipped in sturdy transport packaging. Immediately check the units on delivery and make a note of any damage or missing parts on the delivery note. Inform the forwarding agent and contractual partner.
Claims under guarantee made at a later date will not be accepted.
4
Page 5
Guarantee
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative complete and return the "Certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned. The guarantee conditions are listed in the "General terms and conditions". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
Intended use
Depending on the model and the equipment, the units are only intended to be used as a cold water drain to cool or warm the operating medium water or a water-glycol mixture within a closed medium cycle. Any different or additional use is a non-intended use. The manufacturer / supplier assumes no liability for damages arising from non-intended use. The user bears the sole risk in such cases. Using the equipment as intended also includes working in accordance with the operating manual and installation instructions and complying with the maintenance requirements.
Unit description
In cooling mode the unit (chilled water outlet) extracts the heat from the interior room to be cooled into the fin register and passes it on to the cold operating medium - water or a mix of water and glycol - within a closed medium cycle. As a result of the heat exchange, the medium heats up and the emergent air cools the room down. In heating mode, a warm operating medium warms the room to be heated. The medium cools down as a result of the heat exchange. A valve assembly, which routes the operating medium through the register (energy is given up) or past the resister (energy is not given up), is used to control the cooling or heating capacity.
Diagram of a 2-conductor system medium cycle
Recirculating fan
M
Cooling register
Diagram of a 4-conductor system medium cycle (with heating register)
Recirculating fan
Cooling register
M
Cooling register connection
Medium inlet Medium outlet
The unit is designed for use indoors in the lower wall area (vertical installation) and for ceiling installation (horizontal installation). Operation is either individually or in groups using a room temperature controller or via the building management system. The unit consists of a fin heat exchanger, circulation fan, controller and two condensate trays for horizontal and vertical installation.
The available accessories include room temperature controllers for installation in the unit or on the wall, heating coil for connection to a 4-wire system, valve assembly cooling, fan modules, air inlet plinth, duct parts, grille and condensate pumps.
Medium inlet connection
M
Valve assembly
(accessories)
Medium outlet connection
M
Cooling valve assembly (accessory)
Heating register (accessory)
M M
Medium inlet Medium outlet
Heating register connection
3-way or 2-way valve assembly heating (accessory)
5
Page 6
REMKO KWK / KWK-ZW
System layout
The unit is designed for a 2-conductor system. The unit can easily be upgraded to a 4-conductor system using a heating coil available as an accessory.
The 2-conductor system has 2 medium pipes (conductors: supply and return flow) for cooling using a cold medium and 2 medium pipes for heating using a warm medium. In cooling mode the combined cooling / heating heat exchanger in the indoor unit extracts the heat from the room air by absorbing it into the operating medium. A circulation pump transports the heated medium to a chiller which extracts the heat from the medium in an evaporator and then passes it on to the outside air via a cooling cycle in a condenser. The cooled operating medium is then fed in once again to the unit medium circuit.
Example of system layout of 2-conductor system (heat pump system)
Indoor area 1
Chilled / heating water Consumer
Condensate collecting drainage
Condensate
Room temperature controller Room temperature controller Room temperature controller
Outdoor area
Inverter heat pump Outdoor unit
Not exhaustive
Indoor area 2 Indoor area 3
Chilled / heating water Consumer
Condensate
pipe
Refrigerant pipes
pipe
Medium piping Cooling or heating mode
Inverter heat pump Indoor unit
Chilled / heating water Consumer
Condensate
Buffer tank
pipe
With 2-conductor systems, which are used for cooling or heating, the heating capacity of cold water air-conditioning systems can be generated through a chiller with heat pump function or, in the case of heating systems, through a boiler or heat pump and fed into the circuit. In heating operation, the indoor unit can deliver the heat from the operating medium to the room air.
With 4-conductor systems, which are used for cooling or heating, in one system, both a cooling capacity from a chiller and heating capacity from a separate heating system on the indoor units in an another system are simultaneously present.
Example of system layout of 4-conductor system (cold water air conditioning system)
Indoor area 1
Chilled / heating water Consumer
Condensate collecting drainage
Condensate
Room temperature controller Room temperature controller Room temperature controller
Outdoor area
Chiller
Indoor area 2 Indoor area 3
Chilled / heating water Consumer
Condensate
pipe
Medium piping cooling mode
pipe
Heating room
Chilled / heating water Consumer
Condensate
pipe
Medium piping heating mode
Medium outlet
Boiler
Medium inlet
Not exhaustive
6
Page 7
Operation
The unit can be easily operated with the room temperature controller available as an accessory or a controller to be provided by the customer. It is also possible to activate the system using a building management system.
Use the separate operating manuals for this purpose.
The controller is connected to one or more units by a cable. If a group controller is used the maximum current load must be observed.
Precision room temperature controller
Wall mounting
Room temperature controller
Installation in the unit
Room temperature controller
Wall mounting
TIP
Help by reducing energy usage in stand-by mode! If the unit, the system or the components are not being used, we recommend disconnecting the power supply. Our recommendation does not apply to safety relevant components.
Shutdown
Temporary shutdown
1. Let the unit run for 2 to 3 hours in circulation mode, or in cooling mode at maximum temperature, to extract any residual humidity from the unit.
2. Shut down the system using the controller.
Individual control
Controller
provided by
the customer
Group activation
CBCS
Switching relay
3. Switch off the power supply to the unit.
4. Check the unit for visible signs of damage and clean it as described in the "Care and maintenance" chapter.
Permanent shutdown
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
Controller
provided by
the customer
CBCS
7
Page 8
REMKO KWK / KWK-ZW
Care and maintenance
Regular care and maintenance ensure the trouble-free operation and long service life of the unit.
CAUTION
Care and maintenance work may only be carried out if the unit is disconnected from electrical power.
Care
Ensure the unit is protected against dirt, mould and other deposits.
Clean the unit using a damp cloth. Do not use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
Clean the fins on the unit prior to long shutdown periods.
Maintenance
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.
Filter removal
Cleaning the filter
1. Disconnect the power supply to the unit.
2. If necessary remove the unit's cover.
Follow the chapter "Removal of the unit's cover".
3. Fold the filter downwards and pull it out towards the front.
4. Clean the filter with a commercially available vacuum cleaner. To do this, turn the dirty side upwards (Figure 1).
5. Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents. Turn the dirty side downwards to do this (Figure 2).
6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
7. Carefully insert the filter. Ensure that it locates correctly.
8. Switch the power supply and the unit back on.
We recommend that you take out a maintenance contract with an annual service from an appropriate specialist firm.
Cleaning the housing
1. Disconnect the power supply to the unit.
2. Clean the grill and cover with a soft, damp cloth.
3. Switch the power supply back on.
TIP
A maintenance contract will guarantee that your system always operates reliably!
1 Cleaning using a vacuum cleaner
Type of task
Checks / Maintenance / Inspection
General Medium cycle bleeding Check medium filling Contamination of fin register Filter contamination Check voltage and current Check function of fan Check condensate drainage Check insulation
2
Cleaning with lukewarm water
Commissioning
Monthly
Half-yearly
Yearly
8
Page 9
Removing the KWK unit cladding
3
Removing the unit's cover
KWK 130-870
Cleaning the condensate pump (accessories)
Proceed as follows to clean the filter of units with an air inlet plinth or clean the fin heat exchanger:
1. Disconnect the power supply to the unit.
2. Open the cover of the control panel by pressing the key or removing the screw.
3. Remove the screws under the cover.
4. Pull the unit's cover upwards (Figure 3).
5. Clean the filter as described above and re-assemble the unit in reverse order.
Removing the KWK-ZW unit cladding
Screw
Screw
Unit cover
KWK 130ZW-870ZW
Housing frame
Screw
The indoor unit may contain an integrated or separate condensate pump which pumps any accumulated condensate into outlets at a higher level.
Observe the care and maintenance instructions in the separate operating manual.
Cleaning the air-side components
1. Disconnect the power supply to the unit.
2. Clean all components such as ducts and grills using suitable cleaning agents including anti­bacterial agents if appropriate.
3. Switch the power supply back on.
The cover can be removed to clean the fan. To do this, proceed as follows:
1. Disconnect the power supply to the unit.
2. Unfasten the screws on the side of the fan cover (Figure 3).
3. Gently remove the cover from the unit.
4. Clean the filter / fan as described above and re­assemble the unit in reverse order.
Fan cover
Screw
NOTE
In certain types of use the units and components are subject to a special hygiene maintenance and inspection requirement.
9
Page 10
REMKO KWK / KWK-ZW
Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly. However, if malfunctions should occur, please check the functions as detailed in the list below. With systems for cooling or heating with indoor units, chillers or heating systems the chapter "Troubleshooting and customer service" in all operating manuals must also be observed. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Malfunction
Malfunction Possible cause Checks Remedial measures
The unit does not start or switches itself off.
Power failure, low voltage, main fuse defective / main switch turned off.
Power supply cable damaged.
Power surge due to thunderstorm.
External condensate pump alarm.
Controller not activated.
Valve assembly jammed, not working, not yet fully activated.
Does all other electrical equipment function correctly?
Does all other electrical equipment function correctly?
Have there been lightning strikes in the area recently?
Has the pump shut down due to a malfunction?
Has the operating mode / controller been correctly set?
Is there any electrical power at the valve head or has the time period of 3 minutes after activation passed?
Check the voltage and if necessary wait for it to come back on.
Repair by specialist firm.
Switch off the mains breaker and switch it back on. Inspection by certified service centre.
Check and clean the pump if necessary.
Check the setting and operation.
Have the valve head replaced or wait for time period to pass.
The unit is running but only provides reduced or no cooling or heating output.
Condensate discharge on unit.
Medium outlets on the unit.
Filter is dirty / air inlet / outlet opening is blocked by debris.
Windows and doors open. Heating / cooling output has increased.
Cooling mode is not set.
Medium temperature in cooling mode too high.
Medium temperature in heating mode too low.
Drain pipe of collector reservoir blocked / damaged.
Insulation missing from components carrying the medium.
The condensate drainage line still contains non-discharged condensate.
Condensate cannot drain / external condensate pump or float defective.
Medium cycle / bleeding valve leaking.
Have the filters been cleaned? Clean filters.
Have structural / usage modifications been made?
Is the cooling symbol in the chiller / heat pump display activated?
Is the inlet temperature approx. + 5 ...+ 10 °C and is the circulation pump working?
Is the inlet temperature approx. + 25 ...+ 45 °C and is the circulation pump working?
Can the condensate drain off without any obstruction?
Do all the medium-carrying components outside the drip area have vapour diffusion barrier insulation?
Is there an incline on the condensate drainage line and is it clear?
Are the condensate drainage lines clear and is there an incline? Are the condensate pump and liquid level switch functioning correctly?
Can any leaks be seen on components carrying medium?
Close windows and doors / install additional systems.
Correct the unit's settings.
Reduce the medium temperature.
Increase the medium temperature.
Clean the drainage pipe and collection container.
Have vapour diffusion barrier insulation properly installed.
Route the condensate drainage line with an incline and clean it.
Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced by a specialist company.
Have leaks sealed by a specialist company.
10
Page 11
Installation instructions for qualified personnel
Important notes prior to installation
Observe the Operating Manuals for the indoor unit and the chiller or heating system or the heat pump system when installing the entire system.
The indoor units and chillers work independently. A connecting line between the two is not necessary.
Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damage by doing so.
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
Select an installation location which allows air to flow freely through the inlet and outlet. (See section "Minimum clearances").
Do not install the unit in the immediate vicinity of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
Lift the unit at the corners and not by the medium or condensate connections.
The medium connection lines, valves and connections must have vapour density insulation. If necessary, also insulate the condensate drainage line. In dual systems with cooling and heating modes, the requirements of the current energy savings ordinance (EnEV) are to be complied with.
Seal off open lines to prevent dirt getting in and never kink or crimp the lines.
Avoid unnecessary bends. This minimises the pressure loss in the lines.
Make all electrical connections in accordance with applicable DIN and VDE standards.
Always ensure the electrical cables are properly connected to the terminals. Otherwise there is a risk of fire.
Service openings should be provided in the suspended ceiling to allow maintenance access to the control box or the valve assembly.
Any ventilation ducts or pipes and connection fittings, which are used to connect a second room or supply fresh air, should be insulated with diffusion-tight material.
Only install the valve assembly or other attachments once the indoor unit has been installed.
Installation material
The indoor unit is attached using 4 bolts to be provided by the customer.
Selecting the installation location
KWK Wall / ceiling unit
The indoor unit is designed for vertical wall installation, for instance underneath windows. However, it can also be used in the upper wall area (max.
1.25 m above floor level).
The unit is also designed for horizontal ceiling installation. In this case particular attention must be paid to the condensate drainage (see the Chapter "Condensate drainage connection").
KWK-ZW wall / ceiling unit for installation between partition walls and ceilings
The indoor unit is designed for vertical installation in partition walls.
The unit is also designed for horizontal installation in ceilings. In this case particular attention must be paid to the condensate drainage (see the Chapter "Condensate drainage connection").
Connection variants
The following connection variants can be used for the medium and condensate pipes and the control lines.
Connection variants
1
3
1 Outflow through the wall on the left 2 Outflow through the wall on the right 3 Outflow through the floor on the left 4 Outflow through the floor on the right
2
4
11
Page 12
REMKO KWK / KWK-ZW
Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work in the suspended ceiling and to facilitate optimum air distribution for the cover.
Minimum clearances
KWK 130 to 870
1,000
300
300
Min. 100
300
0
1,000
KWK 130ZW-870ZW
300
1000 (from air inlet)
4 Removing the condensate tray
1,000
1,000
(from air outlet)
50
Dimensions in mm
300
1000
300
Changing medium connection parts
The connection side of the heat exchanger and the condensate drainage line are installed at the factory on the left-hand side of the unit. It is possible to change this to the right-hand side.
1. Dismantle the condensate tray by removing the four self­tapping screws.
2. Remove the screws from the heat exchanger mounting on the side cover frame (Figure 4).
3. Pull the heat exchanger out of the unit's mounting. Be careful as it is easy to be cut by the fins. Do not bend any fins and do not damage the insulation.
4. Cut the insulation of the side stay plate to accommodate the brass connections on the new connection side.
5. Feed the connections through the newly created holes up to the stop (Figure 5).
6. Place the tear-resistant plastic film on the pipe bend side between the stay plate insulation and the heat exchanger mounting. The film protects the insulation of the stay plate against damage.
7. Let the heat exchanger slide into the retainer (keep the same air duct) and after installing the heat exchanger remove the film and screw the unit back together in reverse order.
5 Removing the heat exchanger
Heat exchanger mounting bolts
Heat exchanger mounting bolts
Installation variants
KWK Wall / ceiling unit
Wall mounting
The unit is secured to the wall by the unit housing. The air inlet is, for example, at floor level or, for example, via an air inlet plinth etc. The air outlet is directly from the housing.
Ceiling mounting
The unit is secured under the ceiling by the unit housing. The air inlet is, for example, at floor level or, for example, via an air inlet plinth etc. The air outlet is directly from the housing.
KWK-ZW wall- / ceiling unit for installation between partition
walls and ceilings
Wall mounting
The unit is secured to the wall by the unit housing. The air inlet is, for example, at floor level or, for example, via a duct elbow etc. The air outlet is guided by a short duct system.
Ceiling mounting
The unit is secured under the ceiling or within the suspended ceiling by the unit housing. The air intake is, for example, freely via a shadow gap on the ceiling or e.g. via a duct angle, etc., the air outlet is guided by a short duct system.
TIP
For KWK 130ZW-870ZW duct components are available as accessories.
Condensate tray bolt
12
NOTE
Duct parts must be insulated so that they are impermeable to vapour diffusion!
Page 13
KWK-ZW inspection openings
Inspection openings must be provided within the partition wall and / or suspended ceiling to ensure maintenance and repair work on or in the unit.
Inspection opening in the area
of the medium connections
with openings of at least 300 cm².
Installation examples
of the electrical wiring with
openings of at least 300 cm².
of the fan unit with openings
in the unit width and a depth of at least 300 cm.
of the heat exchanger with
openings of the unit width and a depth of at least 400 cm².
Installing the feet / air inlet plinth (accessory) only for the KWK
If the feet or plinth available as accessories are be used for units for wall and ceiling mounting (KWK), these must be installed before the unit is installed. Follow the separate Installation Instructions.
KWK 130-870
Basic unit
KWK 130ZW-870ZW
Trim provided by the customer
With plinth
With 90° duct elbow, air inlet
With air inlet plinth
Air inlet via shadow gap
KWK-ZW air duct
If the duct components available as accessories are be used in the units, these must be installed before the unit is installed.
All duct surfaces must be adequately insulated against condensation water on site.
The effective duct cross-section must not be reduced.
The pressure losses on the air side must be kept as low as possible.
Air inlet
The unit can be used with a duct elbow of 90° (accessory). A grille optically hides the opening.
Air inlet and outlet via 90° duct elbow
Installation example in adjoining room
The unit can be used with a customer-supplied duct connection piece with a maximum length of 300 mm.
The air is introduced directly into the unit via a shadow gap.
In order to decouple the vibrations, a flexible ducting connector, e.g. canvas connection piece, should be provided.
Inspection openings must be provided for maintenance and cleaning of the filter in the unit.
13
Page 14
REMKO KWK / KWK-ZW
Installation
Air outlet
The unit can be used with a duct elbow of 90° (accessory). A grille optically hides the opening.
The unit can be used with a customer-supplied duct connection piece with a maximum length of 300 mm.
In order to decouple the vibrations, a flexible duct piece, e.g. canvas connection piece, should be provided.
Duct elbow, 90°, air inlet
Unit installation
Wall installation
The unit is attached by means of mounting holes in the case while also taking account of the air outlet side located in the upper part of the unit.
Mark the mounting points according to the bracket's dimensions on structurally acceptable building components and secure the unit.
Check again that the unit is level.
Connect the medium pipes, electrical cables and condensate drainage line to the unit as described below.
NOTE
Installation should only be performed by authorised specialists.
Ceiling installation
The unit is attached by means of mounting holes in the case while also taking account of the air outlet side directed towards the centre of the room.
Mark the mounting points according to the bracket's dimensions on structurally acceptable building components and secure the unit.
Check again that the unit is level.
Connect the medium pipes, electrical cables and condensate drainage line to the unit as described below.
Duct elbow, 90°, air outlet
NOTE
The air ducting must then be selected in such a way that no short­circuit can occur on the air side.
NOTE
If the unit is not mounted positively, vibration can occur.
Unit suspension
A
B
G
F
E
CD
View from the front
All measurements in mm
A B C D E F G
KWK 100-140 659 415 88 156 65 210 70 KWK 200-220 809 545 88 156 65 210 70 KWK 280-300 959 715 88 156 65 210 70 KWK 360-420 1109 865 88 156 65 210 70 KWK 590-680 1409 1165 88 156 65 210 95 KWK 740-870 1709 1465 88 156 65 210 95
14
Page 15
Selecting the hydraulic connection
2-conductor system for cooling and heating
System components required
2-conductor cooling system
Wall installation without valve assembly: When the fan is switched off the flow of air from the air inlet can be ignored without sacrificing comfort. In this application case, use of a valve assembly is not absolutely essential.
Ceiling installation without valve assembly: A valve assembly must be used in this application case to prevent the flow of cold air from the air outlet when the fan is switched off.
Wall installation with valve assembly: In order to prevent any flow of cold air and severe condensate formation, for reasons of comfort a valve assembly can be used inthis application case.
Ceiling installation with valve assembly: In order to prevent any flow of cold air and permanent flow­generated noise, for reasons of comfort a valve assembly is recommended in this application case.
As the 2-conductor system must cool and heat equally, for reasons of convection during winter operation, a valve assembly is stipulated for all installation methods for this system operation to avoid undesirable heat emission.
4-conductor system for cooling and heating
As the 4-conductor system must cool and heat equally, two valve assemblies are stipulated for this system operation for the cooling and heating register.
Connection of the medium piping
The connection of the piping by the customer is made on the rear side of the units.
For the purpose of servicing, connections must be equipped with shut-off valves and the medium flow rate adjusted using hydronic balancing valves.
Additional automatic bleed valves must be provided in the supply and return flows at the installation's highest point.
The medium piping must not exert any structural load on the unit.
The pipe connections must not impose any thermal or mechanical stresses on the unit. If necessary, cool the piping or support with the second tool.
Valve assembly for 2 or 4-conductor systems (accessory)
In 2 or 4-conductor systems, cold or warm medium is fed through the heat exchangers into the unit and cold or warm air can be discharged. Control is provided by the 3-way valve assembly. It consists of the electrically actuated valve head and the valve body. If the head is electrically activated, it actuates the body, which routes the medium into the register. If the temperature is reached, the head is switched off and the medium is fed past the heat exchanger through the bypass . The bypass serves to ensure the minimum medium flow rate for the chiller.
NOTE
The time between being fully open and fully closed can be approx. three minutes.
Valves for hydronic balancing
The calculated individual pressure losses in the pipeline network layout for each individual unit are adjusted to the entire system with hydronic balancing valves to be provided by the customer. The nominal flow rates for the medium adjust to the values needed as a consequence of the pressure loss.
15
Page 16
REMKO KWK / KWK-ZW
Condensate drainage connection
Anti-freeze protection (accessories)
A water glycol mix is generally used as the medium for a cold water system. Depending on the glycol type and quantity used, the viscosity changes, the pressure loss increases and the unit's cooling or heating output reduces.
All system components must be approved for use with glycol.
NOTE
The product and safety data sheets of the glycol type which is used must be obeyed during use and disposal .
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations because of temperature changes when not operating, diaphragm expansion vessels filled with nitrogen (moisture neutral) must be integrated in the system.
Automatic bleed valves
The unit has one or two manual bleed valves on the collector pipe of the register. The unit can be bled separately after the system has been filled. Automatic bleed valves must also be installed at the highest point in the collector line.
CAUTION
Glycol tolerant bleeding valves are necessary when using media which contain glycol.
Safety valve
Safety valves limit excess operating pressure due to excess warming or overfilling of the operating medium. The valve outlet requires unobstructed draining into a drain line. Applicable local disposal ordinances must be observed if glycol is used.
NOTE
No moisture can condense in the nitrogen filler.
If the temperature falls below the dew point, condensate will form on the cooling fins during cooling mode.
Below the heat exchanger is a collection tray which must be connected to a drain.
The condensate drainage line provided by the customer should be installed with an incline of at least 2 %. If necessary, fit vapour­diffusion-proof insulation.
Route the condensate drainage line of the unit into the drain line without any obstruction. If the condensate runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
When operating the unit at outside temperatures below 0°C, ensure the condensate drainage line is laid in such a manner to protect it against frost. If necessary, fit a pipe heater.
Following installation, check that the condensate run off is unobstructed and ensure that the line is durably leak tight.
Bleeding valve
Outlet
16
Inlet
Manual bleeding valve
Inlet
Outlet
Manual bleeding valve
Vertical mounting
The condensate drainage line can be connected at the funnel nozzle. The position of the nozzle can be selected to be on the left or right. The condensate drainage connection of the condensate tray which is not used must be permanently sealed. If a valve assembly is used, the connection must be made to the additional condensate tray.
Page 17
Electrical wiring
Horizontal mounting
The condensate drainage line can be connected directly to the condensate tray. If a valve assembly is used, the condensate
CAUTION
The condensate drainage connection of the condensate tray which is not used must be permanently sealed (a cap or similar).
is conveyed to the unit's pan and is drained from there.
Condensate drainage connection
Vertical mounting Horizontal mounting
Condensate drainage connection Condensate drainage connection
CAUTION
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
We recommend installing a master / repair switch provided by the customer close to the indoor unit.
The power supply is made at the indoor unit, a control line to the chiller is not necessary.
If a condensate pump, which is available as an accessory, is used in conjunction with the unit, the pump switch-off contact switches off the power supply or the valve if necessary.
The terminal block for making the connections and the plug are located behind the unit's cover on the right side of the unit.
KWK Horizontal mounting
Possible accessories
Room temperature controller
The room temperature controller operates the unit. The controller can be wall­mounted or installed in the unit, as required.
Follow the separate
Installation Instructions.
Switch relay for 4 units, if appropriate
If several units are to be controlled
together in a group, a switch relay is necessary if a room temperature controller is used. Follow the separate Installation Instructions.
Heating element if necessary
The heating element allows
the rooms to be heated electrically via the controller. Follow the separate Installation Instructions.
17
Page 18
REMKO KWK / KWK-ZW
Condensate pump
If the condensate which
forms is to be removed by a condensate pump, this can be placed in the unit. Follow the separate Installation Instructions.
CAUTION
Check all plug and terminal connections to verify that they are tight and make a permanent contact. Tighten as required.
Electrical drawings
KWK 130 (ZW) to 870 (ZW)
Power supply, 230 V/,1~, 50 Hz
Make the connection as follows:
1. Open the unit's cover.
2. Insert the cables into the unit.
3. Connect the unit with a controller and the power supply. See electrical drawings.
4. Install all removed parts.
Electrical wiring
Connection terminals
Phase conductor
Neutral conductor
Earth conductor
Leak testing
The leak test is carried out after the connection has been made.
1. Flush the system twice with tap water.
2. Clean the sieve insert on the dirt trap.
3. Fill the system with water again and bleed the unit at the manual bleed valves.
Level 3
Level 2
Level 1
4. Adjust the test pressure to at least 200 kPa (2.0 bar).
5. Check the connections for leaking water after a period of at least 24 hours . If leaks are visible, the connection has not been properly made. Tighten the connection or establish a new connection.
Black
Blue
Red
White
Green / yellow
M
6. After a successful leak test, remove the excess pressure from the medium piping if a water-glycol mixture is used or adjust the non-circulating pressure to the required system pressure.
18
Page 19
Before commissioning
Anti-freeze protection for the medium
If a water-glycol mixture is used, it is to be pre-mixed before being put in the system. The desired concentration is then to be checked.
Bleeding the system
Air may still be in the pipe lines after the leak test. This is carried during operation of the circulation pump to the automatic bleeding valves or to the cold water drain. It is necessary to bleed again here.
The non-circulating pressure must then be adjusted to the required system pressure.
MAG
Commissioning
Commissioning should only be performed and documented by specially trained personnel.
Observe the manuals for the unit and all other components when commissioning the entire system.
Function test for cooling operating mode
1. Switch the power supply on and if necessary open all shut­off valves.
2. Switch on the chiller and the corresponding circulation pump. The outlet temperature must be between +4 and +18°C.
Function test of heating operating mode
1. Switch the power supply on and if necessary open all shut­off valves.
2. Switch on the heating system and the corresponding circulation pump. The outlet temperature must be between +35 and +70°C.
3. Use the controller to switch on the unit and select the heating mode, maximum fan speed and highest target temperature.
4. Measure and record all the required values in the commissioning report and check the safety functions.
5. Check the unit control system using the functions described in the Chapter "Operation".
The preliminary pressure for
the diaphragm expansion vessel must be adjusted individually to the system layout, the volume of the medium and the installation site.
Valves for hydronic balancing
The calculated excess pressure in the pipe network layout at the individual cold water outlets must be adjusted on the pipe leg regulating valves.
Safety valve
The safety valves and their correct function must be checked.
The drain line for the valves is to be checked for function and leak tightness.
3. Use the controller to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
4. Measure and record all the required values in the commissioning report and check the safety functions.
5. Check the unit control system using the functions described in the Chapter "Operation".
6. Check that the condensate drainage line is functioning correctly by pouring distilled water into the condensate tray.
Final tasks
Reassemble all disassembled parts.
Familiarise the operator with the system.
NOTE
During manual bleeding, any glycol mixtures which escape must be disposed of separately. Do not feed them into the condensate tray!
19
Page 20
REMKO KWK / KWK-ZW
Unit dimensions
KWK 130 to 870
D
E
Cooling inlet
2-conductor-system
A
B
C
O
N
M
L
J
K
Heating inlet
4-conductor-system (accessory)
Heating outlet
4-conductor-system (accessory)
I
H
G
F
KWK 130 KWK 140 KWK 200 KWK 220 KWK 280 KWK 300 KWK 360
KWK 420
KWK 590
KWK 680
KWK 740 KWK 870
Electrical wiring
S
R
Q
P
A B C D E F G H I J K L M N O P Q R S
659 478 219 65 85 251 322 383 395 110 185 42 112 141 155 415 65 275 345
659 478 219 65 85 251 322 383 395 110 185 42 112 141 155 415 65 275 345
809 478 219 65 85 251 322 383 395 110 185 42 112 141 155 565 65 275 345
809 478 219 65 85 251 322 383 395 110 185 42 112 141 155 565 65 275 345
959 478 219 65 85 251 322 383 395 110 185 42 112 141 155 715 65 275 345
959 478 219 65 85 251 322 383 395 110 185 42 112 141 155 715 65 275 345
1109 478 219 65 85 251 322 383 395 110 185 42 112 141 155 865 65 275 345
1109 478 219 65 85 251 322 383 395 110 185 42 112 141 155 865 65 275 345
1409 525 230 65 85 251 319 428 445 114 195 42 112 155 174 1165 65 290 385
1409 525 230 65 85 251 319 428 445 114 195 42 112 155 174 1165 65 290 385
1709 525 230 65 85 251 319 428 445 114 195 42 112 155 174 1465 65 290 385
1709 525 230 65 85 251 319 428 445 114 195 42 112 155 174 1465 65 290 385
All measurements in mm
20
Page 21
Unit dimensions
KWK 130ZW to 870ZW
D
E
Air inlet Air outlet
W
Cooling inlet
2-conductor-system
O
A
N
M
L
B
Heating inlet
4-conductor-system (accessory)
Heating outlet
4-conductor-system (accessory)
I
H
G
F
J
K
U
C
U
V
KWK 130 KWK 140 KWK 200 KWK 220 KWK 280 KWK 300 KWK 360
KWK 420
KWK 590
KWK 680
KWK 740 KWK 870
Electrical wiring
S
R
Q
P
A B C D E F G H I J K L M N O P Q R S U V W
415 446 216 65 85 251 322 383 395 110 185 42 112 141 155 415 65 275 345 390 100 206
415 446 216 65 85 251 322 383 395 110 185 42 112 141 155 415 65 275 345 390 100 206
545 446 216 65 85 251 322 383 395 110 185 42 112 141 155 565 65 275 345 540 100 206
545 446 216 65 85 251 322 383 395 110 185 42 112 141 155 565 65 275 345 540 100 206
715 446 216 65 85 251 322 383 395 110 185 42 112 141 155 715 65 275 345 690 100 206
715 446 216 65 85 251 322 383 395 110 185 42 112 141 155 715 65 275 345 690 100 206
865 446 216 65 85 251 322 383 395 110 185 42 112 141 155 865 65 275 345 840 100 206
865 446 216 65 85 251 322 383 395 110 185 42 112 141 155 865 65 275 345 840 100 206
1165 493 227 65 85 251 319 428 445 114 195 42 112 155 174 1165 65 290 385 1140 120 217
1165 493 227 65 85 251 319 428 445 114 195 42 112 155 174 1165 65 290 385 1140 120 217
1465 493 227 65 85 251 319 428 445 114 195 42 112 155 174 1465 65 290 385 1440 120 217
1465 493 227 65 85 251 319 428 445 114 195 42 112 155 174 1465 65 290 385 1440 120 217
All measurements in mm
21
Page 22
REMKO KWK / KWK-ZW
Exploded view KWK 130 to 870
2
9
12
10
11
6
8
4
3
5
7
1
We reserve the right to modify the dimensions and design
as part of the ongoing technical development process.
Spare parts list
No. Designation
1 Unit cover 1111750 1111750 1111751 1111751 1111752 1111752 2 Fin exchanger 1111758 1111758 1111759 1111759 1111760 1111760 3 Outlet grill 1111764 1111764 1111764 1111764 1111764 1111764 4 Control panel, right 1111765 1111765 1111765 1111765 1111765 1111765 5 Control panel, left 1111766 1111766 1111766 1111766 1111766 1111766 6 Fan unit, complete 1112394 1112394 1112395 1112395 1112396 1112396 7 Air filter 1111773 1111773 1111774 1111774 1111775 1111775 8 Condensate tray 1111779 1111779 1111780 1111780 1111781 1111781
9 Condensate tray, valve assembly, vertical 1111785 1111785 1111785 1111785 1111785 1111785 10 Transformer, speed step 1112400 1112400 1112400 1112400 1112400 1112400 11 Condenser fan 1112402 1112402 1112403 1112403 1112404 1112404 12 Condensate connection 1111790 1111790 1111790 1111790 1111790 1111790
No. Designation
1 Unit cover 1111753 1111753 1111755 1111755 1111757 1111757
2 Fin exchanger 1111761 1111761 1111762 1111762 1111763 1111763
3 Outlet grill 1111764 1111764 1111764 1111764 1111764 1111764
4 Control panel, right 1111765 1111765 1111765 1111765 1111765 1111765
5 Control panel, left 1111766 1111766 1111766 1111766 1111766 1111766
6 Fan unit, complete 1112397 1112397 1112398 1112398 1112399 1112399
7 Air filter 1111776 1111776 1111777 1111777 1111778 1111778
8 Condensate tray 1111782 1111782 1111783 1111783 1111784 1111784
9 Condensate tray, valve assembly, vertical 1111785 1111785 1111785 1111785 1111785 1111785 10 Transformer, speed step 1112400 1112400 1112401 1112401 1112401 1112401 11 Condenser fan 1112403 1112403 1112405 1112405 1112404 1112404 12 Condensate connection 1111790 1111790 1111790 1111790 1111790 1111790
When ordering spare parts, please state the EDP and unit number (see name plate)!
KWK 130 KWK 140 KWK 200 KWK 220 KWK 280 KWK 300
KWK 360 KWK 420 KWK 590 KWK 680 KWK 740 KWK 870
22
Page 23
Exploded view KWK 130ZW to 870ZW
5
3
Spare parts list
No. Designation
1 Fin exchanger 1111758 1111758 1111759 1111759 1111760 1111760 2 Fan unit, complete 1112394 1112394 1112395 1112395 1112396 1112396 3 Air filter 1111773 1111773 1111774 1111774 1111775 1111775 4 Condensate tray 1111779 1111779 1111780 1111780 1111781 1111781 5 Condensate tray, valve assembly, horizontal 1111791 1111791 1111791 1111791 1111791 1111791 6 Transformer, speed step 1112400 1112400 1112400 1112400 1112400 1112400 7 Condenser fan 1112402 1112402 1112403 1112403 1112404 1112404 8 Condensate connection 1111790 1111790 1111790 1111790 1111790 1111790
8
2
7
6
4
We reserve the right to modify the dimensions and design
as part of the ongoing technical development process.
KWK 130 ZWKWK 140 ZWKWK 200 ZWKWK 220 ZWKWK 280 ZWKWK 300
1
ZW
No. Designation
1 Fin exchanger 1111761 1111761 1111762 1111762 1111763 1111763 2 Fan unit, complete 1112397 1112397 1112398 1112398 1112399 1112399 3 Air filter 1117736 1111776 1111777 1111777 1111778 1111778 4 Condensate tray 1111782 1111782 1111783 1111783 1111784 1111784 5 Condensate tray, valve assembly, horizontal 1111791 1111791 1111791 1111791 1111791 1111791 6 Transformer, speed step 1112400 1112400 1112401 1112401 1112401 1112401 7 Condenser fan 1112403 1112403 1112405 1112405 1112404 1112404 8 Condensate connection 1111790 1111790 1111790 1111790 1111790 1111790
When ordering spare parts, please state the EDP and unit number (see name plate)!
KWK 360 ZWKWK 420 ZWKWK 590 ZWKWK 680 ZWKWK 740 ZWKWK 870
ZW
23
Page 24
REMKO KWK / KWK-ZW
Technical data
Series KWK 130 KWK 140 KWK 200 KWK 220 KWK 280 KWK 300
Operating mode
2.2 rated cooling output
1)
Rated cooling output, sensitive
Rated heating output
2)
kW 1.31 1.48 1.96 2.2 2.77 3.11
1)
kW 1.11 1.28 1.56 1.81 2.25 2.57
kW 1.61 1.86 2.22 2.58 3.23 3.69
Chilled water units for wall and ceiling mounting, 2-conductor version
Application area (room volume), approx. 40 50 60 70 90 100
Operating range - indoor unit °C +15 to +35
Air flow volume per stage m³/h
Sound pressure level per stage
3)
dB(A)
Sound power level per stage dB(A)
120/199/263 147/228/314 173/264/349 199/313/416
262/392/518 294/451/610
22/31/38 24/34/42 23/32/39 25/36/43 28/35/42 28/38/45
30/39/46 32/42/50 31/40/47 33/44/51 34/43/50 36/46/53
Power supply V/Hz 230/1~/50
Enclosure class IP X0
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW 35 44 39 49 51 65
A 0.15 0.19 0.17 0.22 0.24 0.31
Operating medium Water; max. 35% ethylene glycol, max. 35% propylene glycol
Operating limits, medium - cooling °C +4 to +18
Operating limits, medium - heating °C +35 to +80
Max. operating pressure, medium kPa 600
Nominal flow rate, medium - cooling 1)m³/h 0.23 0.26 0.34 0.38 0.47 0.53
Nominal flow rate, medium - heating 2)m³/h 0.28 0.32 0.39 0.45 0.55 0.63
Rated pressure drop, internal - cooling 1)kPa 4.3 5.3 11.3 14.2 7.8 9.5
Rated pressure drop, internal - heating 2)kPa 5.3 6.8 11.8 15.3 8.9 11.2
Medium connection, inlet Inches 1/2 female
Medium connection, outlet Inches 1/2 female
Medium volume l 0.6 0.6 0.9 0.9 1.1 1.1
Condensate drainage connection mm 19
Dimensions - Height mm 478 478 478 478 478 478
Width mm 659 659 809 809 959 959
Depth mm 219 219 219 219 219 219
Weight kg 14 14 17 17 20 20
Operating weight, approx. kg 14.6 14.6 17.9 17.9 21.1 21.1
Standard colour Similar to RAL 9016
Serial number 1698... 1699... 1700... 1701... 1702... 1703...
EDP 1662210 1662220 1662230 1662240 1662250 1662260
1) Air inlet temperature TK 27 °C / FK 19 °C, medium inlet 7 °C, medium outlet 12 °C, 0% glycol concentration, max. air flow volume
2) Air inlet temperature TK 20 °C, medium inlet 45 °C, medium outlet 40 °C, 0% glycol concentration, max. air flow volume
3) Distance of 1.0 m in a 100 m3 space with a reverberation time of 0.3 s
24
Page 25
Technical data
Series KWK 360 KWK 420 KWK 590 KWK 680 KWK 740 KWK 870
Operating mode
2.2 rated cooling output
1)
Rated cooling output, sensitive
Rated heating output
2)
kW 3.61 4.19 5.93 6.8 7.4 8.66
1)
kW 2.8 3.31 4.61 5.36 5.65 6.72
kW 3.95 4.69 6.46 7.54 7.9 9.45
Chilled water units for wall and ceiling mounting, 2-conductor version
Application area (room volume), approx. 120 150 190 220 240 280
Operating range - indoor unit °C +15 to +35
Air flow volume per stage m³/h
Sound pressure level per stage
3)
dB(A)
Sound power level per stage dB(A)
282/462/611 328/524/751 468/724/1001 538/843/1203
524/873/1195 612/1037/1489
22/32/39 24/36/44 29/40/47 32/43/51 29/38/45 31/41/49
30/40/47 32/44/52 37/48/55 40/51/59 37/46/53 39/49/57
Power supply V/Hz 230/1~/50
Enclosure class IP X0
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW 72 92 121 145 145 179
A 0.29 0.38 0.56 0.69 0.69 0.78
Operating medium Water; max. 35% ethylene glycol, max. 35% propylene glycol
Operating limits, medium - cooling °C +4 to +18
Operating limits, medium - heating °C +35 to +80
Max. operating pressure, medium kPa 600
Nominal flow rate, medium - cooling 1)m³/h 0.62 0.72 1.02 1.17 1.27 1.49
Nominal flow rate, medium - heating 2)m³/h 0.68 0.81 1.11 1.3 1.36 1.62
Rated pressure drop, internal - cooling 1)kPa 14 22 16 18 10 15.5
Rated pressure drop, internal - heating 2)kPa 14.8 20.1 25.5 33.5 14.6 19.9
Medium connection, inlet Inches 1/2 female
Medium connection, outlet Inches 1/2 female
Medium volume l 1.4 1.4 2.4 2.4 3 3
Condensate drainage connection mm 19
Dimensions - Height mm 478 478 525 525 525 525
Width mm 1109 1109 1409 409 1709 1709
Depth mm 219 219 230 230 230 230
Weight kg 23 23 35 35 47 47
Operating weight, approx. kg 24.4 24.4 37.4 37.4 50 50
Standard colour Similar to RAL 9016
Serial number 1704... 1705... 1706... 1707... 1708... 1709...
EDP 1662270 1662280 1662290 1662300 1662310 1662320
1) Air inlet temperature TK 27 °C / FK 19 °C, medium inlet 7 °C, medium outlet 12 °C, 0% glycol concentration, max. air flow volume
2) Air inlet temperature TK 20 °C, medium inlet 45 °C, medium outlet 40 °C, 0% glycol concentration, max. air flow volume
3) Distance of 1.0 m in a 100 m3 space with a reverberation time of 0.3 s
25
Page 26
REMKO KWK / KWK-ZW
Technical data
Series
Operating mode
Rated cooling output
1)
Rated cooling output, sensitive
Rated heating output
2)
KWK
130ZW
Chilled water units for partition wall and suspended ceiling installation, 2-conductor version
kW 1.31 1.48 1.96 2.2 2.77 3.11
1)
kW 1.11 1.28 1.56 1.81 2.25 2.57
kW 1.61 1.86 2.22 2.58 3.23 3.69
KWK
140ZW
KWK
200ZW
KWK
220ZW
KWK
280ZW
KWK
300ZW
Application area (room volume), approx. 40 50 60 70 90 100
Operating range - indoor unit °C +15 to +35
Air flow volume per stage m³/h
Sound pressure level per stage
3)
dB(A)
Sound power level per stage dB(A)
120/199/263 147/228/314 173/264/349 199/313/416
262/392/518 294/451/610
22/31/38 24/34/42 23/32/39 25/36/43 28/35/42 28/38/45
30/40/47 32/44/52 37/48/55 40/51/59 37/46/53 39/49/57
Static pressure, max. Pa 30 30 20 30 20 40
Power supply V/Hz 230/1~/50
Enclosure class IP X0
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW 35 44 39 49 51 65
A 0.15 0.19 0.17 0.22 0.24 0.31
Operating medium Water; max. 35% ethylene glycol, max. 35% propylene glycol
Operating limits, medium - cooling °C +4 to +18
Operating limits, medium - heating °C +35 to +80
Max. operating pressure, medium kPa 600
Nominal flow rate, medium - cooling 1)m³/h 0.23 0.26 0.34 0.38 0.47 0.53
Nominal flow rate, medium - heating 2)m³/h 0.28 0.32 0.39 0.45 0.55 0.63
Rated pressure drop, internal - cooling 1)kPa 4.3 5.3 11.3 14.2 7.8 9.5
Rated pressure drop, internal - heating 2)kPa 5.3 6.8 11.8 15.3 8.9 11.2
Medium connection, inlet Inches 1/2 female
Medium connection, outlet Inches 1/2 female
Medium volume l 0.6 0.6 0.9 0.9 1.1 1.1
Condensate drainage connection mm 19
Dimensions - Height mm 216 216 216 216 216 216
Width mm 460 460 610 610 760 760
Depth mm 446 446 446 446 446 446
Weight kg 9 9 11 11 13 13
Operating weight, approx. kg 9.6 9.6 11.9 11.9 14.1 14.1
Serial number 1710... 1711... 1712... 1713... 1714... 1715...
EDP 1662215 1662225 1662235 1662245 1662255 1662265
1) Air inlet temperature TK 27 °C / FK 19 °C, medium inlet 7 °C, medium outlet 12 °C, 0% glycol concentration, max. air flow volume
2) Air inlet temperature TK 20 °C, medium inlet 45 °C, medium outlet 40 °C, 0% glycol concentration, max. air flow volume
3) Distance of 1.0 m in a 100 m3 space with a reverberation time of 0.3 s
26
Page 27
Technical data
Series
Operating mode
Rated cooling output
1)
Rated cooling output, sensitive
Rated heating output
2)
KWK
360ZW
Chilled water units for partition wall and suspended ceiling installation, 2-conductor version
kW 3.61 4.19 5.93 6.8 7.4 8.66
1)
kW 2.8 3.31 4.61 5.36 5.65 6.72
kW 3.95 4.69 6.46 7.54 7.9 9.45
KWK
420ZW
KWK
590ZW
KWK
680ZW
KWK
740ZW
KWK
870ZW
Application area (room volume), approx. 120 150 190 220 240 280
Operating range - indoor unit °C +15 to +35
Air flow volume per stage m³/h
Sound pressure level per stage
3)
dB(A)
Sound power level per stage dB(A)
282/462/611 328/524/751 468/724/1001 538/843/1203
524/873/1195 612/1037/1489
22/32/39 24/36/44 29/40/47 32/43/51 29/38/45 31/41/49
30/40/47 32/44/52 37/48/55 40/51/59 37/46/53 39/49/57
Static pressure, max. Pa 30 40 70 70 50 60
Power supply V/Hz 230/1~/50
Enclosure class IP X0
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW 72 92 121 145 145 179
A 0.29 0.38 0.56 0.69 0.69 0.78
Operating medium Water; max. 35% ethylene glycol, max. 35% propylene glycol
Operating limits, medium - cooling °C +4 to +18
Operating limits, medium - heating °C +35 to +80
Max. operating pressure, medium kPa 600
Nominal flow rate, medium - cooling 1)m³/h 0.62 0.72 1.02 1.17 1.27 1.49
Nominal flow rate, medium - heating 2)m³/h 0.68 0.81 1.11 1.3 1.36 1.62
Rated pressure drop, internal - cooling 1)kPa 14 22 16 18 10 15.5
Rated pressure drop, internal - heating
2)
kPa 14.8 20.1 25.5 33.5 14.6 19.9
Medium connection, inlet Inches 1/2 female
Medium connection, outlet Inches 1/2 female
Medium volume l 1.4 1.4 2.4 2.4 3 3
Condensate drainage connection mm 19
Dimensions - Height mm 216 216 226 226 226 226
Width mm 910 910 1210 1210 1510 1510
Depth mm 446 446 493 493 493 493
Weight kg 15 15 25 25 35 35
Operating weight, approx. kg 16.4 16.4 27.4 27.4 38 38
Serial number 1716... 1717... 1718... 1719... 1720... 1721...
EDP 1662275 1662285 1662295 1662305 1662315 1662325
1) Air inlet temperature TK 27 °C / FK 19 °C, medium inlet 7 ℃, medium outlet 12 °C, 0% glycol concentration, max. air flow volume
2) Air inlet temperature TK 20 °C, medium inlet 45 °C, medium outlet 40 °C, 0% glycol concentration, max. air flow volume
3) Distance of 1.0 m in a 100 m3 space with a reverberation time of 0.3 s
27
Page 28
REMKO KWK / KWK-ZW
Services
Cooling capacity
Air inlet
5 °C 7 °C 9 °C 11 °C 13 °C 15 °C
TK 27°C,
Q
K
Q
FK19°C
KWK 130
KWK 140
KWK 200
KWK 220
KWK 280
KWK 300
KWK 360
KWK 420
KWK 590
KWK 680
KWK 740
KWK 870
Air inlet temperature TK 27°C / FK 19°C, 0% Glycol concentration, Spread t = 5K QK = Cooling capacity, overall QS = Cooling capacity, sensitive V = Medium flow rate
Fan stage
[kW]
max 1.64 1.24 282 1.31 1.11 226 1.05 1 180 0.86 0.86 147 0.71 0.71 122 0.57 0.57 97 med 1.34 0.99 230 1.08 0.88 185 0.85 0.8 146 0.68 0.68 118 0.57 0.57 98 0.45 0.45 78 min 0.9 0.64 155 0.73 0.57 126 0.57 50 98 0.45 0.45 77 0.37 0.37 64 0.3 0.3 51 max 1.85 1.43 319 1.48 1.28 255 1.2 1.15 205 0.99 0.99 169 0.82 0.82 140 0.65 0.65 111 med 1.84 1.1 254 1.19 0.99 204 0.94 0.89 162 0.77 0.77 131 0.64 0.64 109 0.51 0.51 87 min 1.06 0.77 182 0.86 0.68 147 0.66 0.6 114 0.53 0.53 91 0.44 0.44 76 0.35 0.35 61 max 2.41 1.75 414 1.96 1.56 337 1.52 1.38 260 1.22 1.22 210 1.02 1.02 176 0.82 0.82 141 med 1.94 1.39 334 1.59 1.24 273 1.25 1.09 213 0.97 0.97 166 0.81 0.81 139 0.65 0.65 112 min 1.38 0.96 236 1.13 0.86 194 0.87 0.75 150 0.69 0.67 118 0.57 0.57 97 0.46 0.46 79 max 2.74 2.02 471 2.23 1.81 383 1.75 1.64 300 1.41 1.41 242 1.18 1.18 203 0.95 0.95 163 med 2.22 1.6 381 1.81 1.43 311 1.42 1.26 242 1.12 1.12 192 0.94 0.94 161 0.75 0.75 129 min 1.55 1.09 266 1.27 0.97 218 0.97 0.85 167 0.76 0.76 130 0.64 0.64 109 0.51 0.51 88 max 3.42 2.52 588 2.77 2.25 476 2.18 2.05 373 1.76 1.76 302 1.47 1.47 252 1.18 1.18 202 med 2.77 2.01 477 2.26 1.79 388 1.75 1.57 298 1.4 1.4 240 1.17 1.17 201 0.94 0.94 161 min 2.01 1.42 3.46 max 3.84 2.87 660 med 3.09 2.25 530 2.51 2.01 431 1.96 1.77 335 1.57 1.57 270 1.31 1.31 225 1.05 1.05 181 min 2.21 1.57 380 1.81 1.4 311 1.4 1.23 240 1.1 1.1 188 0.92 0.92 158 0.74 0.74 127 max 4.38 3.13 752 3.61 2.8 620 2.82 2.47 485 2.25 2.2 385 1.85 1.85 318 1.5 1.5 257 med 3.52 2.48 605 2.91 2.21 500 2.28 1.95 392 1.78 1.74 304 1.46 1.46 251 1.18 1.18 203 min 2.33 1.61 401 max 5.1 3.7 877 med 3.89 2.76 668 3.21 2.46 551 2.52 2.17 432 1.98 1.93 340 1.63 1.63 279 1.32 1.32 226 min 2.65 1.84 456 2.2 1.64 378 1.72 1.44 295 1.35 1.29 232 1.08 1.08 186 0.88 0.88 151 max 7.21 5.16 1239 5.96 4.61 1022 4.6 4.06 788 3.68 3.62 632 3.04 3.04 522 2.46 2.46 422 med 5.58 3.93 959 4.61 3.5 791 3.6 3.08 617 2.8 2.72 480 2.31 2.31 396 1.87 1.87 321 min 3.87 2.68 665 max 8.28 5.99 1422 med 6.3 4.47 1084 5.19 3.99 893 4.01 2.51 689 3.13 3.13 537 2.63 2.63 452 2.13 2.13 365 min 4.36 3.03 749 3.61 2.7 620 2.81 2.37 483 2.16 2.11 371 1.78 1.78 306 1.44 1.44 248 max 8.94 6.32 1537 7.4 5.65 1271 5.78 4.98 990 4.48 4.4 768 3.73 3.73 642 3.03 3.03 520 med 6.94 4.83 1192 5.76 4.32 989 4.49 3.8 771 3.48 3.32 596 2.85 2.85 490 2.31 2.31 398 min 4.47 3.07 769 max 10.5 751 1805 med 7.99 5.6 1373 6.62 5.01 1137 5.24 4.41 986 4.08 3.86 700 3.31 3.31 568 2.69 2.69 461 min 5.13 3.53 881 4.27 3.15 734 3.35 2.77 575 2.62 2.42 450 2.09 2.09 358 1.7 1.7 292
S
[kW]V [l/h]
Q
K
Q
[kW]
[kW]V [l/h]
1.65 1.27
3.11 2.57
1.94 1.44
4.19 3.31
3.21 2.38
6.79 5.36
3.73 2.74
8.66 6.72
S
Q
K
[kW]
283 1.29 1.11 222 1 0.99 1.72 0.83 0.83 143 0.67 0.67 115 534 2.44 2.31 417 2 2 344 1.67 1.67 287 1.34 1.34 230
333 1.51 1.26 260 1.18 1.13 204 0.95 0.95 163 0.77 0.77 133 720 3.24 3.02 554 2.6 2.6 447 2.19 2.19 376 1.77 1.77 304
552 2.54 2.09 436 1.96 1.87 338 1.58 1.58 271 1.28 1.28 220
1166 5.28 4.73 903 4.21 4.21 723 3.53 3.53 607 2.85 2.85 490
641 2.93 2.4 503 2.28 2.1 390 1.81 1.81 311 1.47 1.47 253
1489 6.78 5.94 1162 5.36 5.28 918 4.5 4.45 768 3.6 3.6 619
Medium inlet
Cooling capacity
Q
S
[kW]V [l/h]
Q
K
[kW]
[kW]V [l/h]
Q
S
Q
K
[kW]
Q
S
[kW]V [l/h]
Q
K
[kW]
Q
S
[kW]V [l/h]
28
Page 29
Heating output
Air inlet
TK 20°C
KWK 130
KWK 140
KWK 200
KWK 220
KWK 280
KWK 300
KWK 360
KWK 420
KWK 590
KWK 680
KWK 740
KWK 870
Fan stage
max 0.83 143 1.73 1.22 209 3.33 1.61 276 5.31 2 343 7.63 2.09 179 2.41 2.48 213 3.22 med 0.66 114 1.16 0.97 166 2.21 1.27 219 3.52 1.58 271 5.04 1.66 142 1.6 1.97 169 2.13 min 0.43 74 0.54 0.62 107 1.02 0.82 140 1.61 1.01 174 2.3 1.07 92 0.74 1.26 108 0.98 max 0.96 164 2.21 1.41 242 4.27 1.86 319 6.84 2.31 397 9.86 2.41 207 3.1 2.87 246 4.14 med 0.74 127 1.41 1.08 186 2.7 1.43 245 4.31 1.77 304 6.19 1.86 160 1.96 2.2 189 2.61 min 0.51 88 0.74 0.75 128 1.4 0.98 168 2.22 1.21 208 3.17 1.28 110 1.02 1.51 130 1.35 max 1.17 201 4 1.7 292 7.51 2.22 382 11.8 2.75 472 16.9 2.91 250 5.45 3.44 295 7.2 med 0.93 159 2.64 1.34 230 4.94 1.75 300 7.75 2.16 371 11 2.29 197 3.58 2.71 232 4.72 min 0.64 111 1.39 0.92 158 2.56 1.2 206 4 1.48 254 5.67 1.58 136 1.86 1.86 160 2.44 max 1.35 232 5.15 1.96 337 9.7 2.58 442 15.3 3.19 547 21.9 3.36 289 7.04 3.98 341 9.31 med 1.07 184 3.41 1.55 266 6.39 2.03 348 10 2.5 430 14.3 2.65 228 4.63 3.13 269 6.12 min 0.73 125 1.72 1.04 179 3.19 1.36 234 4.99 1.68 288 7.09 1.79 154 2.31 2.11 181 3.04 max 1.69 290 2.96 2.46 422 5.6 3.23 554 8.85 4 686 12.7 4.21 361 4.06 4.99 428 5.38 med 1.34 230 1.97 1.95 334 3.71 2.55 438 5.84 3.15 541 8.34 3.33 286 2.69 3.94 338 3.56 min 1.69 290 2.96 2.46 422 5.6 3.23 554 8.85 4 686 12.7 4.21 361 4.06 4.99 428 5.38 max 1.93 331 3.73 2.81 482 7.08 3.69 634 11.2 4.57 785 16.1 4.81 413 5.13 5.7 489 6.81 med 1.51 259 2.42 2.19 376 4.57 2.87 493 7.21 3.56 610 10.3 3.75 322 3.31 4.44 381 4.39 min 1.05 180 1.28 1.52 260 2.39 1.98 340 3.75 2.45 420 5.34 2.6 223 1.73 3.07 263 2.29 max 2.09 359 5.04 3.02 518 9.42 3.95 677 14.8 4.87 837 21.1 5.17 443 6.84 6.1 524 9.02 med 1.65 283 3.32 2.37 407 6.17 3.1 532 9.66 3.82 656 13.7 4.06 349 4.48 4.79 411 5.89 min 1.07 184 1.55 1.53 263 2.86 1.99 342 4.45 2.45 421 6.3 2.62 225 2.07 3.09 265 2.72 max 2.48 425 6.8 3.59 615 12.8 4.69 806 20.1 5.8 996 28.6 6.14 527 9.25 7.26 623 12.2 med 1.84 315 4.01 2.65 454 7.48 3.46 594 11.7 4.27 733 16.7 4.53 389 5.43 5.35 459 7.15 min 1.22 209 1.96 1.75 301 3.61 2.28 392 5.64 2.81 482 7.99 3 257 2.62 3.53 303 3.44 max 3.45 592 8.81 4.96 851 16.3 6.46 1110 25.5 7.97 1368 36.2 8.49 728 11.8 10 859 15.6 med 2.61 449 5.41 3.75 644 9.98 4.88 838 15.6 6.01 1032 22 6.42 551 7.24 7.56 648 9.5 min 1.78 306 2.76 2.55 437 5.05 3.31 568 7.84 4.07 698 11.1 4.36 374 3.66 5.12 440 4.79 max 4.01 689 11.5 5.78 992 21.4 7.54 1,295 33.5 9.3 1597 47.6 9.89 849 15.5 11.7 1002 20.4 med 2.98 512 6.82 4.28 735 12.6 5.58 957 19.7 6.87 1179 27.9 7.33 629 9.14 8.63 741 12 min 2.01 345 3.41 2.88 494 6.27 3.74 642 9.74 4.6 790 13.8 4.93 423 4.54 5.8 497 5.95 max 4.21 722 5.01 6.06 1040 9.3 7.9 1356 14.6 9.75 1673 20.7 10.4 892 6.75 12.2 1049 8.88 med 3.21 550 3.1 4.6 790 5.73 5.99 1028 8.94 7.38 1267 12.7 7.87 676 4.16 9.27 796 5.46 min 2.03 348 1.39 2.9 498 2.54 3.76 646 3.95 4.63 794 5.57 4.96 426 1.84 5.83 500 2.41 max 5.02 861 6.82 7.23 1242 12.7 9.45 1622 19.9 11.7 2002 28.4 12.4 1063 9.22 14.6 1254 12.2 med 3.73 640 4.04 5.35 919 7.49 6.98 1198 11.7 8.6 1477 16.6 9.17 787 5.43 10.8 927 7.14 min 2.34 402 1.79 3.35 575 3.28 4.35 747 5.09 5.35 919 7.2 5.73 492 2.38 6.74 578 3.11
Medium inlet / medium outlet
35/30 °C 40/35 °C 45/40 °C 50 /45 °C 55/45 °C 60/50 °C
Heating output
Q
H
[kW]V [m³/h]p [kPa]
Q
H
[kW]V [m³/h]p [kPa]
Q
H
[kW]V [m³/h]p [kPa]
Q
H
[kW]V [m³/h]p [kPa]
Q
H
[kW]V [m³/h]p [kPa]
Q
H
[kW]V [m³/h]p [kPa]
Air inlet temperature TK 20°C, 0% Glycol concentration, Spread t = 5K QK = Heating output, overall V = Medium flow rate p = Pressure loss
29
Page 30
REMKO KWK / KWK-ZW
30
Page 31
Page 32
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail info@remko.de Internet www.remko.de
Hotline
Air conditioning and heating technology
+49 5232 606-0
Export
+49 5232 606-130
Consultation
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation
of being more than just
an excellent, reliable supplier:
REMKO, a partner who helps
to solve problems.
Sales
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO employees in the field
are more than just sales
people: above all, they must
be advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely
and reliably. However, in the event
of a malfunction REMKO
customer service is quickly
on the scene. Our comprehensive
network of experienced dealers
guarantees quick and reliable
service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...