REMKO KWK 100-4R, KWK 4R, KWK 400-4R, KWK 150-4R, KWK 250-4R Operation,technology,spare Parts

Page 1
REMKO KWK -4R
KWK 100-4R, KWK 150-4R, KWK 250-4R, KWK 400-4R
Wall and ceiling chilled/hot water units for heat pump systems
Operation · Technology · Spare parts
Edition GB – F01
Page 2
Page 3
Contents
Safety notes
Environmental protection and recycling
Transportation and packaging
Guarantee
Unit description
System layout
Operation
Shutdown
Care and maintenance
Troubleshooting and customer service
Installation Instructions for qualified personnel
Installation
Condensate drainage connection
4
4
4
5
5
6
6-7
7
7-8
9
10-11
12-14
14
Electrical wiring
Electrical drawings
Leak testing
Before commissioning
Commissioning
Unit dimensions
Exploded view of the unit
Spare parts list
Technical data
Services
Carefully read this Operating Manual prior to commissioning/using the units. This operating manual is a translation of the German original.
14-15
15
15
16
16
17
17
17
18
19
These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
Page 4
REMKO KWK -4R
Safety notes
Carefully read this Operating Manual before starting the unit for the first time. It contains useful tips and notes as well as hazard warnings to prevent injury to persons or material damage . Failure to follow the directions in this Manual can endanger persons, the environment and the equipment itself and will void any claims for liability.
■
Keep this manual close to the units.
■ The units and components
should not be exposed to any mechanical load or extreme levels of humidity or sunlight.
■ Only qualified personnel may
set up and install the units and components.
■ The unit and its components
must be set-up, connected and operated in accordance with the use and operating conditions stipulated in this manual and comply with all applicable local regulations.
■ Mobile units must be set up
securely on suitable surfaces and in an upright position. Stationary units must be permanently installed for operation.
■ Modification of the units
and components supplied by REMKO is not permitted and can cause malfunctions.
■ Units and components may
not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
■ The operational safety of
the units and components is only assured if they are fully assembled and used as intended. Safety devices may not be modified or bypassed.
■ Do not operate units or
components with obvious defects or signs of damage.
■ All housing parts and unit
openings, e.g. air inlets and outlets, must be free from foreign objects, liquids, or gases.
■ The units and components must
be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
■ Contact with some parts of the
unit or components can result in burns or other injuries. Wearing appropriate protective clothing is necessary to avert risks.
■ Only authorised and trained
persons are permitted to access and operate the units and components.
■ Installation, repair and
maintenance work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the unit is disconnected from the power.
■ To preclude any risks to persons
originating from the units, appropriate precautions must be taken when installing, repairing, maintaining, cleaning or working on the units.
Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
Only recyclable materials are used to manufacture the units and components. Help protect the environment by ensuring that the units or components (for example batteries) are not disposed of in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
Transportation and packaging
The units are shipped in sturdy transport packaging. Immediately check the units on delivery and make a note of any damage or missing parts on the delivery note. Inform the forwarding agent and contractual partner.
Claims under guarantee made at a later date will not be accepted.
■ The electrical power supply is to
be adapted to the requirements of the units.
4
Page 5
Guarantee
In order to make guarantee claims, it is essential that the ordering party or his customer has completed and returned the "guarantee certificate" to REMKO GmbH & Co. KG at the time when the unit was purchased and commissioned. The guarantee conditions are listed in the "General terms and conditions of business and supply". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
Intended use
Unit description
In cooling mode the unit (chilled/ hot water consumer) extracts the heat from the interior room to be cooled into the fin heat exchanger and releases it to the cold operating medium (water or a mix of water and glycol) within a closed medium cycle. As a result of the heat exchange, the medium heats up and the emergent air cools the room down. In heating mode, a warm operating medium warms the room to be heated. The medium cools down as a result of the heat exchange. A valve assembly, which routes the operating medium through the register (energy is given up) or past the resister (energy is not given up), is used to control the cooling or heating capacity.
The unit is designed for use indoors in the lower wall area (vertical installation) and for ceiling installation (horizontal installation). Operation is either individually or in groups using a room temperature controller or via the building management system. The unit consists of a fin heat exchanger, circulation fan, controller and two condensate trays for horizontal and vertical installation.
The available accessories include room temperature controllers for installation in the unit or on the wall, fan modules, air inlet plinth and condensate pumps.
Depending on the model and the equipment, the units are only intended to be used as a chilled/ hot water consumer to cool or warm internal rooms by means of the operating medium water or a water-glycol mixture within a closed medium cycle. Any other use or use in a way that exceeds the definition above is considered non-intended use. The manufacturer/supplier assumes no liability for damages arising from non-intended use. The user bears the sole risk in such cases. Using the equipment as intended also includes working in accordance with the operating manual and installation instructions and complying with the maintenance requirements.
Diagram of a 2-conductor system medium cycle
Recirculating fan
M
Cooling/heating heat exchanger
Connection Medium inlet
M
Valve assembly
(Accessories)
Connection Medium outlet
5
Page 6
REMKO KWK -4R
System layout
The unit is designed for a 2-conductor system. The 2-conductor system has 2 medium pipes (conductors: supply and return flow) for cooling using a cold medium and 2 medium pipes for heating using a warm medium. In cooling mode the combined cooling / heating heat exchanger in the indoor unit extracts the heat from the room air by absorbing it into the operating medium. A circulation pump transports the heated medium to a chiller/warm water generator which extracts heat from the medium or heats the medium in a heat exchanger. The cooled/ heated operating medium is then fed once again to the unit in the medium circuit.
Example of system layout of 2-conductor system (heat pump system)
Indoor area 1
Chilled/heating water Consumer
Condensate collecting drainage
Condensate
Room temperature controller Room temperature controller Room temperature controller
Outdoor area
Inverter heat pump Outdoor unit
Indoor area 2 Indoor area 3
Chilled/heating water Consumer
Condensate
pipe
Refrigerant pipes
pipe
Medium pipes Cooling or heating mode
Chilled/heating water Consumer
Condensate
Buffer tank
pipe
Operation
The unit can be easily operated with the room temperature controller available as an accessory or a controller to be provided by the customer. It is also possible to activate the system using a building management system.
Use the separate operating manuals for this purpose.
The controller is connected to one or more units by a cable. If a group controller is used the maximum current load must be observed.
Not exhaustive
Room temperature controller
Installation in the unit
Inverter heat pump Indoor unit
Precision room temperature controller
Wall mounting
TIP
Help by reducing energy usage in stand-by mode! If the unit, the system or the components are not being used, we recommend disconnecting the power supply. Our recommendation does not apply to safety relevant components.
6
Page 7
Individual control
CBCS
Group activation
Switching relay
Controller
provided by
the customer
Shutdown
Temporary shutdown
1. Let the unit run for 2 to 3 hours in circulation mode, or in cooling mode at maximum temperature, to extract any residual humidity from the unit.
2. Shut down the system using the controller.
3. Switch off the power supply to the unit.
4. Check the unit for visible signs of damage and clean as described in the chapter "Care and maintenance"
Shutdown for an indefinite period
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
Controller
provided by
the customer
CBCS
Care and maintenance
Regular care and maintenance ensure the trouble-free operation and long service life of the unit.
CAUTION
Care and maintenance work may only be carried out if the unit is disconnected from electrical power.
Care
■
Ensure the unit is protected against dirt, mould and other deposits.
■
Clean the unit using a damp cloth. Do not use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
■
Clean the fins on the unit prior to long shutdown periods.
Maintenance
Cleaning the housing
1. Disconnect the power supply to the unit.
2. Clean the grill and cover with a soft, damp cloth.
3. Switch the power supply back on.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.
Filter removal
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
■
We recommend that you take out a maintenance contract with an annual service interval with an appropriate specialist firm.
TIP
A maintenance contract will guarantee that your system always operates reliably!
NOTE
In certain types of use the units and components are subject to a special hygiene maintenance and inspection requirement.
7
Page 8
REMKO KWK -4R
Cleaning the filter
1. Disconnect the power supply to the unit.
2. If necessary remove the unit's cover.
Follow the chapter "Removal of the unit's cover".
3. Fold the filter downwards and pull it out towards the front.
4. Clean the filter with a commercially available vacuum cleaner. To do this, turn the dirty side upwards (Figure 1).
5. Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents. Turn the dirty side downwards to do this (Fig. 2).
6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
7. Carefully insert the filter. Ensure that it fits correctly.
1 Cleaning using a vacuum cleaner
Type of task
Checking / Servicing / Inspection
General Medium cycle bleeding Check medium filling Contamination of fin register Filter contamination Check voltage and current Check function of fan Check condensate drainage Check insulation
8. Switch the power supply and the unit back on.
2
Cleaning with lukewarm water
Commissioning
Monthly
Half-yearly
•
• •
• •
• •
• •
• •
• •
• •
• •
Yearly
Removing the KWK-4R unit's cover
Proceed as follows to clean the filter of units with an air inlet plinth or clean the fin heat exchanger:
1. Disconnect the power supply to the unit.
2. Open the cover of the control panel by pressing the key or removing the screw.
3. Remove the screws under the cover.
4. Pull the unit's cover upwards (Fig. 3).
5. Clean the filer as described above and re-assemble the unit in reverse order.
3
Removing the unit's cover
KWK 100-4R-400-4R
Screw
Screw
Cleaning the condensate pump (accessory)
The indoor unit may contain an integrated or separate condensate pump which pumps any accumulated condensate into outlets at a higher level. Observe the care and maintenance instructions in the separate Operating Manual.
Cleaning the downstream components
1. Disconnect the power supply to the unit.
2. Clean all components such as ducts and grills using suitable cleaning agents including anti-bacterial agents if appropriate.
Unit cover
3. Switch the power supply back on.
8
Page 9
Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly. However, if malfunctions should occur, please check the functions as detailed in the list below. With systems for cooling or heating with indoor units, chillers or heating systems the chapter "Troubleshooting and customer service" in all operating manuals must also be observed. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Possible cause Checks Remedial measures
The unit does not start or switches itself off.
Power failure, low voltage, main fuse defective / main switch turned off.
Power supply cable damaged.
Power surge due to thunderstorm.
External condensate pump malfunction.
Controller not activated
Valve assembly jammed, not working, not yet fully activated.
Does all other electrical equipment function correctly?
Does all other electrical equipment function correctly?
Have there been lightning strikes in the area recently?
Has the pump shut down due to a malfunction?
Has the operating mode/ controller been correctly set?
Is there any electrical power at the valve head or has the time period of 3 minutes after activation passed?
Check the voltage and if necessary wait for it to come back on.
Repair by certified service centre.
Switch off the mains breaker and switch it back on. Inspection by certified service centre.
Check and clean the pump if necessary.
Check the setting and operation.
Have the valve head replaced or wait for time period to pass.
The unit is running but only provides reduced or no cooling or heating capacity.
Condensate discharge on unit.
Medium outlets on the unit.
Filter is dirty / air inlet / outlet opening is blocked by debris.
Windows and doors open. Heating/cooling output has increased.
Cooling mode is not set.
Medium temperature in cooling mode too high.
Medium temperature in heating mode too low.
Drain pipe of collector reservoir blocked / damaged.
Insulation missing from components carrying the medium.
The condensate drainage line still contains condensate.
Condensate cannot drain / external condensate pump or float defective.
Medium cycle / bleeding valve leaking
Have the filters been cleaned? Clean filters.
Have structural / usage modifications been made?
Is the cooling symbol in the chiller / heat pump display activated?
Is the inlet temperature approx. + 5 ...+ 10 °C and is the circulation pump working?
Is the inlet temperature approx. + 25 ...+ 45 °C and is the circulation pump working?
Can the condensate drain off without any obstruction?
Do all the medium-carrying components outside the drip area have vapour diffusion barrier insulation?
Is there an incline on the condensate drainage line and is it clear?
Are the condensate drainage lines clear and is there an incline? Are the condensate pump and liquid level switch functioning correctly?
Can any leaks be seen on components carrying medium?
Close windows and doors / install additional systems.
Correct the settings for the unit.
Reduce the medium temperature.
Increase the medium temperature.
Clean the drainage pipe and collection container.
Have vapour diffusion barrier insulation properly installed.
Route the condensate drainage line with an incline and clean it.
Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced by a specialist company.
Have leaks sealed by a specialist company.
9
Page 10
REMKO KWK -4R
Installation instructions for qualified personnel
Important notes prior to installation
■
Observe the Operating Manuals for the indoor unit and the chiller or heating system or the heat pump system when installing the entire system.
■
The indoor units and water chillers and heat pump system work independently. A connecting line between the two is not necessary.
■
Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damage by doing so.
■
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
■
Select an installation location which allows air to flow freely through the inlet and outlet. (See section "Minimum clearances").
■
Do not install the unit in the immediate vicinity of devices which generate intensive radiation of heat or cold. Installation in the vicinity of heat or cold radiation reduces the unit output.
■
Lift the unit at the corners and not by the medium or condensate connections.
■
The medium connection lines, valves and connections must have vapour density insulation. If necessary, also insulate the condensate drainage line. In dual systems with cooling and heating modes, the requirements of the current Energy Savings Ordinance (EnEV) must be followed.
10
■
Seal off open lines to prevent dirt getting in and never kink or crimp the lines.
■
Avoid unnecessary bends. This minimises the pressure loss in the lines.
■
Make all electrical connections in accordance with applicable DIN and VDE standards.
■
Always ensure the electrical cables are properly connected to the terminals. Otherwise there is a risk of fire.
■
Adequate clearance must be provided to allow maintenance access to the control box and the valve assembly.
■
Only install the valve assembly or other attachments once the indoor unit has been installed.
Installation material
The indoor unit is attached using 4 bolts to be provided by the customer.
Selecting the installation location
Wall / ceiling unit KWK -4R
The indoor unit is designed for vertical wall installation, for instance underneath windows. However, it can also be used in the upper wall area (max. 1.25 m above floor level).
The unit is also designed for horizontal ceiling installation. In this case particular attention must be paid to the condensate drainage (see the Chapter "Condensate drainage connection").
Connection variants
The following connection variants can be used for the medium and condensate pipes and the control lines.
Connection variants
1
3
1 Outflow through the wall on the left 2 Outflow through the wall on the right 3 Outflow through the floor on the left 4 Outflow through the floor on the right
4
Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work in the suspended ceiling and to facilitate optimum air distribution for the cover.
Minimum clearances
KWK 100-4R to 400-4R Wall installation with ground clearance
1,000
300
300
Min. 100
KWK 100-4R to 400-4R Ceiling installation with air inlet plinth
300
0
1,000
1,000
1,000
300
2
Page 11
Changing medium connection parts
The connection side of the heat exchanger and the condensate drainage line are installed by the works on the left-hand side of the unit. It is possible to change this to the right-hand side.
1. Dismantle the condensate tray by removing the four self-tapping screws.
2. Remove the screws from the heat exchanger mounting on the side cover frame (Fig. 4).
3. Pull the heat exchanger out of the unit's mounting. Be careful as it is easy to be cut by the fins. Do not bend any fins and do not damage the insulation.
4. Cut the insulation of the side stay plate to accommodate the brass connections on the new connection side.
5. Feed the connections through the newly created holes up to the stop (Fig. 5).
6. Place the tear-resistant plastic film on the pipe bend side between the stay plate insulation and the heat exchanger mounting. The film protects the insulation of the stay plate against damage.
7. Let the heat exchanger slide into the retainer (keep the same air duct) and after installing the heat exchanger remove the film and screw the unit back together in reverse order.
Installation variants
Wall / ceiling unit KWK-4R
■ Wall mounting
The unit is secured to the wall by the unit housing. The air inlet is, for example, at floor level or, for example, via an air inlet plinth etc. The air outlet is directly from the housing.
■ Ceiling mounting
The unit is secured under the ceiling by the unit housing. The air inlet is, for example, at floor level or, for example, via an air inlet plinth etc. The air outlet is directly from the housing.
Installation examples
KWK 100-4R - 400-4R
Basic unit With foot
Installing the feet /air inlet plinth (accessory) only for the KWK-4R
If the feet or plinth available as accessories are be used for units for wall and ceiling mounting, these must be installed before the unit is installed. Follow the separate Installation Instructions.
With air inlet plinth
4 Removing the condensate tray
Condensate tray bolt
5 Removing the heat exchanger
Heat exchanger mounting bolts
Heat exchanger mounting bolts
11
Page 12
REMKO KWK -4R
Installation
Unit installation
Selecting the hydraulic connection
Wall installation
The unit is attached by means of mounting holes in the case while also taking account of the air outlet side located in the upper part of the unit.
■
Mark the mounting points according to the bracket's dimensions on structurally acceptable building components and secure the unit.
■
Check again that the unit is level.
■
Connect the medium pipes, electrical cables and condensate drainage line to the unit as described below.
NOTE
Installation should only be performed by authorised specialists.
Unit suspension
Ceiling installation
The unit is attached by means of mounting holes in the case while also taking account of the air outlet side directed towards the centre of the room.
■
Mark the mounting points according to the bracket's dimensions on structurally acceptable building components and secure the unit.
■
Check again that the unit is level.
■
Connect the medium pipes, electrical cables and condensate drainage line to the unit as described below.
A
B
2-conductor cooling system
■
Wall installation without valve assembly: When the fan is switched off the flow of air from the air inlet can be ignored without sacrificing comfort. In this application case, use of a valve assembly is not absolutely essential.
■
Ceiling installation without valve assembly: A valve assembly must be used in this application case to prevent the flow of cold air from the air outlet when the fan is switched off.
■
Wall installation with valve assembly: In order to prevent any flow of cold air and severe condensate formation, for reasons of comfort a valve assembly can be used in this application case.
■
Ceiling installation with valve assembly: In order to prevent any flow of cold air and permanent flow-generated noise, for reasons of comfort a valve assembly is recommended in this application case.
G
CD
All information in mm.View from the front
A B C D E F G
KWK 100 660 415 88 158 70 205 70 KWK 150 810 565 88 158 70 205 70 KWK 250 960 715 88 158 70 205 70 KWK 400 1110 865 88 158 70 205 70
12
F
2-conductor system for
E
cooling and heating
■
As the 2-conductor system must cool and heat equally, for reasons of convection during winter operation a valve assembly is specified for all installation methods for this system operation to avoid undesirable heat emission.
Page 13
Connection for medium piping
■
The connection of the piping by the customer is made on the rear side of the units.
■
For the purpose of servicing, connections must be equipped with shut-off valves and the medium flow rate adjusted using hydronic balancing valves.
■
Additional automatic bleed valves must be provided in the supply and return flows at the installation's highest point.
■
The medium piping must not exert any structural load on the unit.
■
The pipe connections must not impose any thermal or mechanical stresses on the unit. If necessary cool the piping or support with the second tool.
System components required
Valve assembly for 2-conductor systems (accessory)
In 2-conductor systems, cold or warm medium is fed through the heat exchanger into the unit and cold or warm air can be discharged. Control is provided by the 3-way valve assembly. It consists of the electrically actuated valve head and the valve body. If the head is electrically activated, it actuates the body, which routes the medium into the register. If the temperature is reached, the head is switched off and the medium is fed past the heat exchanger through the bypass . The bypass serves to ensure the minimum medium flow rate for the chiller or the heat pump.
NOTE
The time between being fully open and fully closed can be approx. three minutes.
Valves for hydronic balancing
The calculated individual pressure losses in the pipeline network layout for each individual unit are adjusted to the entire system with hydronic balancing valves to be provided by the customer. The nominal flow rates for the medium adjust to the values needed as a consequence of the pressure loss.
Anti-freeze protection (accessories)
A water glycol mix is generally used as the medium for a cold water system. Depending on the glycol type and quantity used, the viscosity changes, the pressure loss increases and the unit's cooling or heating capacity reduces.
All system components must be approved for use with glycol.
Bleeding valve
Manual bleeding valve
Inlet
Outlet
NOTE
The product and safety data sheets of the glycol type which is used must be obeyed during use and disposal.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations because of temperature changes when not operating, diaphragm expansion vessels filled with nitrogen (moisture neutral) must be integrated in the system.
Automatic bleed valves
The unit has one or two manual bleed valves on the collector pipe of the register. The unit can be bled separately after the system has been filled. Automatic bleed valves must also be installed at the highest point in the collector line.
CAUTION
Glycol tolerant bleeding valves are necessary when using media which contain glycol.
Manual bleeding valve
Inlet
Outlet
13
Page 14
REMKO KWK -4R
Safety valve
Safety valves limit excess operating pressure due to excess warming or overfilling of the operating medium. The valve outlet requires unobstructed draining into a drain line. Applicable local disposal ordinances must be observed if glycol is used.
NOTE
No moisture can condense in the nitrogen filler.
Condensate drainage connection
As the temperature on the heat exchanger is below the dew point, condensate is formed during cooling mode.
Below the heat exchanger is a collection tray which must be connected to a drain.
■
The condensate drainage line provided by the customer should be installed with an incline of at least 2 %. If necessary, fit vapour-diffusion­proof insulation.
■
Route the condensate drainage line of the unit into the drain line without any obstruction. If the condensate runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
Condensate drainage connection
■
When operating the unit at outside temperatures below 0°C, ensure the condensate drainage line is laid in such a manner to protect it against frost. If necessary, fit a pipe heater.
■
Following installation, check that the condensate drain is unobstructed and ensure that the line is permanently leak tight.
Vertical mounting
The condensate drainage line can be connected at the funnel nozzle. The position of the nozzle can be selected to be on the left or right. The condensate drainage connection of the condensate tray which is not used must be permanently sealed. If a valve assembly is used, the connection must be made to the additional condensate tray.
Horizontal mounting
The condensate drainage line can be connected directly to the condensate tray. If a valve assembly is used, the condensate is conveyed to the unit's pan and is drained from there.
Electrical wiring
CAUTION
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
■
We recommend installing a master / repair switch provided by the customer close to the indoor unit.
■
The power supply is made to the indoor unit; a control line to the chiller/heat pump is not necessary.
■
If a condensate pump, which is available as an accessory, is used in conjunction with the unit, the pump switching-off contact switches off the power supply or the valve if necessary.
■
The terminal block for making the connections and the plug are located behind the unit's cover on the right side of the unit.
Possible accessories
Room temperature controller
■ The room temperature controller
operates the unit. The controller can be wall-mounted or installed in the unit, as required. Follow the separate Installation Instructions.
Vertical mounting Horizontal mounting Horizontal mounting
Drain duct
Condensate drainage connection Condensate drainage connection
14
Switch relay for 4 units, if appropriate
■ If several units are to be
controlled together in a group, a switch relay is necessary if a room temperature controller is used. Follow the separate Installation Instructions.
CAUTION
The condensate drainage connection of the condensate tray which is not used must be permanently sealed (a cap or similar).
Page 15
Condensate pump
■ If the condensate which forms is
to be removed by a condensate pump, this can be placed in the unit. Follow the separate Installation Instructions.
CAUTION
Check all plug and terminal connections to verify that they are tight and make a permanent contact. Tighten as required.
Electrical drawings
KWK 100-4R to 400-4R
Power supply
230V, 1~, 50Hz
Phase conductor
Neutral conductor
Earth conductor
Make the connection as follows:
1. Open the unit's cover.
2. Insert the cables into the unit.
3. Connect the unit with a controller and the power supply. See electrical drawings.
4. Install all removed parts.
Level 3 Level 2 Level 1
Electrical wiring
Connection terminals
Legend
Wt = white Gn = green Ye = yellow Pk = pink Gn/Ye = green/yellow Bl = blue Bn = brown Bk = black Gr = grey Vi = violet Or = orange Rd = red
KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Conden-
sor
m³/h dB(A) dB(A)
Item 1
333 40.5 49 63 1 338 43.5 52 44 1 584 47.5 56 85 1 716 47.5 56 90 1
Item 2
296 39.5 48 56 2 348 41.5 50 38 2 505 44.5 53 75 2 570 42.5 51 69 2
Item 3
252 38.5 47 49 3 304 38.5 47 32 3 430 41.5 50 65 3 490 37.5 46 58 3
Item 4
200 34.5 43 40 4 bk 1 254 36.5 45 29 4 bk 1 353 36.5 45 54 4 bk 1 432 34.5 43 47 4 bk 1
Item 5
147 28.5 37 29 5 bl 2 194 32.5 41 21 5 bl 2 254 27.5 36 40 5 bl 2 300 26.5 35 35 5 bl 2
min max
Item 6
128 25.5 34 27 6 rd 3 184 25.5 34 17 6 rd 3 232 26.5 35 36 6 rd 3 283 25.5 34 30 6 rd 3
Air flow
1.0 µF 2.0 µF 1.5 µF 2.5 µF
level
Sound power
Sound pressure
Power
consumption
W
colour
terminal
Conductor
Transformer
Connection
Leak testing
The leak test is carried out after the connection has been made.
1. Flush the system twice with tap water.
2. Clean the sieve insert on the dirt trap.
3. Fill the system with water again and vent the unit at the manual
Air flow
Sound power
Sound pressure
m³/h dB(A) dB(A)
level
Power
W
consumption
colour
terminal
Conductor
Transformer
Connection
m³/h dB(A) dB(A)
bleed valves.
4. Adjust the test pressure to at least 200 kPa (2.0 bar).
5. Check the connections for leaking water after a period of at least 24 hours . If leaks are visible, the connection has not been properly made. Tighten
Air flow
level
Sound power
Sound pressure
Power
Transformer
consumption
W
terminal
Conductor
colour
Connection
m³/h dB(A) dB(A)
Air flow
level
Sound power
Sound pressure
the threaded connection or
make a new connection.
6. After a successful leak test, remove the excess pressure from the medium piping if a water-glycol mixture is used or adjust the non-circulating pressure to the required system pressure.
Power
Transformer
consumption
W
colour
terminal
Conductor
Connection
15
Page 16
REMKO KWK -4R
Before commissioning
Anti-freeze protection for the medium
If a water-glycol mixture is used, it is to be pre-mixed before being put in the system. The desired concentration must then be checked.
Bleeding the system
■
Air may still be in the pipe lines after the leak test. This is carried to the automatic bleeding valves or the consumer by the operation of the circulation pump. In this case it is necessary to bleed the system again.
■
The non-circulating pressure must then be adjusted to the required system pressure.
MAG
■ The preliminary pressure for the
diaphragm expansion vessel must be adjusted individually to the system layout, the volume of the medium and the installation site.
Valves for hydronic balancing
■
The calculated excess pressure in the pipe network layout at the individual cold water consumers must be adjusted at the hydronic balancing valves.
Safety valve
■
The safety valves and their correct function must be checked.
Commissioning
■
Commissioning should only be performed and documented by specially trained personnel.
■
Observe the manuals for the unit and all other components when commissioning the entire system.
Function test for cooling operating mode
1. Switch the power supply on and if necessary open all shut­off valves.
2. Switch on the chiller, the heat pump and the corresponding circulation pump. The outlet temperature must be between +4 and +18°C.
3. Use the controller to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
4. Measure and record all the required values in the commissioning report and check the safety functions.
5. Check the unit control system using the functions described in the Chapter "Operation".
6. Check that the condensate drainage line is functioning correctly by pouring distilled water into the condensate tray.
Function test of heating operating mode
1. Switch the power supply on and if necessary open all shut-off valves.
2. Switch on the chiller, the heat pump and the corresponding circulation pump. The outlet temperature must be between +35 and +70°C.
3. Use the controller to switch on the unit and select the heating mode, maximum fan speed and highest target temperature.
4. Measure and record all the required values in the commissioning report and check the safety functions.
5. Check the unit control system using the functions described in the Chapter "Operation".
Final tasks
■
Reassemble all disassembled parts.
■
Familiarise the operator with the system.
NOTE
During manual bleeding, any glycol mixtures which escape must be disposed of separately. Do not feed them into the condensate tray!
■
The drain line for the valves is to be checked for function and leak tightness.
16
Page 17
Unit dimensions
KWK 100-4R to 400-4R
A
K
J
Cooling / heating inlet
Cooling / heating outlet
D
E
L
Exploded view of the units KWK 100-4R to 400-4R
B
H
I
C
O
N
M
All information in mm
KWK
G
F
100-
4R
A 660 810 960 1110 B 480 480 480 480 C 220 220 220 220 D 70 70 70 70 E 95 95 95 95 F 249 249 249 249 G 393 393 393 393 H 96 96 96 96 I 185 185 185 185 J 42 42 42 42 K 156 156 156 156 L 415 565 715 865 M 70 70 70 70 N 275 275 275 275 O 345 345 345 345
KWK 150-
4R
KWK 250-
4R
KWK 400-
4R
2
8
4
9
12
10
11
3
6
7
5
1
Spare parts list
No. Designation
1 Unit cover 1111750 1111751 1111752 1111753 2 Finned heat exchanger 4 rows of tubes 1111746 1111747 1111748 1111749 3 Outlet grill 1111764 1111764 1111764 1111764 4 Control panel, right 1111765 1111765 1111765 1111765 5 Control panel, left 1111766 1111766 1111766 1111766 6 Fan unit, complete. 1111767 1111768 1111769 1111770 7 Air filter 1111773 1111774 1111775 1111776 8 Condensate tray 1111779 1111780 1111781 1111782
9 Condensate tray, valve assembly, vertical 1111785 1111785 1111785 1111785 10 Transformer, speed step 1111786 1111778 1111788 1111789 11 Condenser fan 1111794 1111795 1111796 1111797 12 Condensate connection 1111790 1111790 1111790 1111790
When ordering spare parts, please state the EDP and unit number (see name plate)!
KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
17
Page 18
REMKO KWK -4R
Technical data
Series KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Operating mode
Nominal cooling output
Nominal cooling output, sensitive
Nominal heating capacity 2) /
1)
1)
3)
Application area (room volume), approx.
Operating range - indoor unit
Air flow volume per stage
Sound pressure level per stage
4)
Sound power level per stage
Power supply
Enclosure class
Electr. rated power consumption
Electr. rated current consumption
1)
1)
Operating medium
Operating limits, medium - cooling
Operating limits, medium - heating
Chilled/hot water units for wall and ceiling mounting, 2-conductor version
kW
kW
kW
1.18 1.59 2.21 2.73
0.93 1.23 1.70 2.08
1.35 / 0.66 1.80 / 0.97 2.53 / 1.40 3.05 / 1.68
m³ 45 60 80 100
°C +15 to +35
m³/h 128/147/200 184/194/254 232/254/353 283/300/423
dB(A) 25.5/28.5/34.5 25.5/32.5/36.5 26.5/27.5/36.5 25.5/26.5/34.5
dB(A) 34/37/43 34/41/45 35/36/45 34/35/43
V/Hz 230/1~/50
IP X0
kW 0.04 0.03 0.05 0.05
A 0.19 0.15 0.26 0.31
Water; max. 35 % ethylene-glycol, max. propylene-glycol max. 35 %
°C +4 to +18
°C +35 to +80
Max. operating pressure, medium
kPa 600
Nominal flow rate, medium - cooling 1)/ 3)m³/h 0.20 0.27 0.38 0.47
Nominal flow rate, medium - heating
Rated pressure drop, internal - cooling
Rated pressure drop, internal - heating
Medium connection, inlet
Medium connection, outlet
Medium volume
Condensate drainage connection
2)
m³/h 0.24 / 0.11 0.31 / 0.17 0.44 / 0.24 0.53 / 0.29
1)
kPa 1.2 3.3 6.7 5.5
2)
kPa 2.1 / 0.6 4.6 / 1.6 10.7 / 4.0 7.8 / 2.9
Inches 1/2 female
Inches 1/2 female
l 0.9 1.2 1.5 2.2
mm 19
Dimensions - Height mm 480 480 480 480
Width mm 660 810 960 1110
Depth mm 220 220 220 220
Weight
Operating weight, approx.
Standard colour
Serial number
EDP no.
kg 14.0 17.0 20.0 23.0
kg 14.9 18.2 21.5 25.2
similar to RAL 9016
1382... 1383... 1384... 1385...
1663100 1663150 1663250 1663400
1) Air inlet temperature TK 27°C / FK 19 °C, medium inlet12 °C, medium outlet 7 °C, 0% glycol concentration, max. air flow volume
2) Air inlet temperature TK 20°C, medium inlet 45 °C, medium outlet 40 °C, 0% glycol concentration, max. air flow volume
3) Air inlet temperature TK 20°C, medium inlet 35 °C, medium outlet 30 °C, 0% glycol concentration, max. air flow volume
4) Distance 1.5 m in a 100m2 room with a reverberation time of 0.3 seconds
18
Page 19
Services
Cooling capacity
Air inlet
TK 27°C,
FK19°C
KWK
100-4R
KWK
150-4R
KWK
250-4R
KWK
400-4R
Air inlet temperature TK 27°C / FK 19°C, 0% glycol concentration, spread∆t = 5K QK = cooling capacity, total QS = cooling capacity, sensible V = medium flow rate
Fan Unit
Flow Noise
volume
Level
min 128 25.5 34 0.83 0.63 141.8 0.53 0.53 14.6 0.37 0.37 18.3 0.26 0.19 22.6
5 147 28.5 37 0.93 0.71 158.8 0.6 0.6 14.7 0.42 0.42 18.5 0.29 0.18 23.3 4 200 34.5 43 1.18 0.93 202.5 0.78 0.78 15.3 0.54 0.54 18.9 0.38 0.14 24.9 3 252 38.5 47 1.40 1.13 240.2 0.95 0.95 15.7 0.66 0.66 19.2 0.43 0.12 25.6 2 296 39.5 48 1.57 1.29 269.5 1.07 1.07 16.1 0.75 0.75 19.4 0.48 0.09 26.1
max 333 40.5 49 1.71 1.41 293.5 1.19 1.19 16.2 0.82 0.82 19.6 0.52 0.03 26.7
min 184 25.5 34 1.22 0.92 209.5 0.78 0.78 14.3 0.54 0.54 18.2 0.37 0.29 22.3
5 194 32.5 41 1.27 0.97 218 0.81 0.81 14.4 0.57 0.57 18.2 0.37 0.33 22.0 4 254 36.5 45 1.59 1.23 273 1.04 0.98 15.4 0.72 0.72 18.5 0.43 0.39 22.3 3 304 38.5 47 1.83 1.43 314.1 1.22 1.22 14.9 0.84 0.84 18.7 0.47 0.43 22.7 2 348 41.5 50 2.03 1.61 348.4 1.37 1.37 15.2 0.94 0.94 18.9 0.51 0.47 23.0
max 388 43.5 52 2.20 1.76 377.6 1.50 1.43 15.9 1.09 1.09 18.6 0.54 0.49 23.2
min 232 26.5 35 1.57 1.17 269.3 1.10 1.10 12.8 0.69 0.69 18.0 0.40 0.40 21.8
5 254 27.5 36 1.69 1.27 290 1.18 1.18 13.0 0.75 0.75 18.1 0.43 0.43 21.9 4 353 36.5 45 2.21 1.70 379.3 1.54 1.54 13.9 1.03 1.03 18.2 0.54 0.54 22.4 3 430 41.5 50 2.57 2.01 441.1 1.81 1.81 14.4 1.20 1.20 18.6 0.61 0.61 22.7 2 505 44.5 53 2.90 2.30 497.6 2.03 2.03 14.9 1.37 1.37 18.9 0.67 0.67 23.0
max 584 47.5 56 3.23 2.59 554.3 2.26 2.26 15.3 1.53 1.53 19.1 0.80 0.80 22.9
min 283 25.5 34 1.95 1.45 334.5 1.32 1.22 14.0 0.86 0.86 17.8 0.50 0.50 86.4
5 300 26.5 35 2.10 1.53 351.9 1.54 1.30 14.0 1.02 0.90 17.9 0.55 0.52 90.2 4 423 34.5 43 2.73 2.08 468.6 1.86 1.86 13.8 1.27 1.27 17.9 0.66 0.66 114.3 3 490 37.5 46 3.08 2.37 528.8 2.13 2.10 14.1 1.45 1.45 18.1 0.73 0.73 125.3 2 570 42.5 51 3.67 2.69 595.4 2.55 2.37 14.5 1.75 1.61 18.5 0.79 0.79 137.1
max 716 47.5 56 4.12 3.26 707.1 2.82 2.82 15.1 1.94 1.94 18.9 0.90 0.90 155.5
V
[l/h]
pressure
power
dB(A) dB(A)
7 /12°C 10 /15°C 14/19°C 18/21°C
Q
K
Q
S
[kW]
[kW]V [l/h]
Q
K
[kW]
Q
S
[kW]V [l/h]
Q
K
[kW]
Q
S
[kW]V [l/h]
Q
K
Q
S
[kW]
[kW]V [l/h]
Works level 1 and 2 Rated capacity, level 3
Heating capacity
Fan Unit
Air inlet
TK 20°C,
FK14°C
Level
KWK
100-4R
KWK
150-4R
KWK
250-4R
KWK
400-4R
Air inlet temperature TK 20°C, 0% glycol concentration, spread ∆t = 5K QK = heating capacity, total
V = medium flow rate
Flow Noise
volume
min 128 25.5 34 0.48 31 83 0.69 35.9 119.9 0.91 41.1 159.3 1.13 46 196.8
5 147 28.5 37 0.53 30.6 92 0.78 35.7 136 1.03 40.7 180 1.27 45.6 222.3 4 200 34.5 43 0.66 29.7 114.8 1.02 35.1 178 1.35 39.9 234.7 1.66 44.5 290 3 252 38.5 47 0.82 29.6 142.7 1.24 34.6 216.2 1.63 39.1 284.7 2.02 43.6 352 2 296 39.5 48 0.94 29.4 164 1.42 34.1 246.5 1.86 38.6 324.4 2.30 42.9 401.5
max 333 40.5 49 1.04 29.2 180.8 1.56 33.8 270.8 2.05 38.1 356.8 2.53 42.4 441.5
min 184 25.5 34 0.73 31.7 126.1 1.05 36.9 183 1.36 41.8 236.8 1.66 46.6 289.7
5 194 32.5 41 0.76 31.6 132.5 1.10 36.8 191.8 1.42 41.7 248.2 1.74 46.5 303.7 4 254 36.5 45 0.97 31.3 168.6 1.40 36.2 242.6 1.80 40.9 314.1 2.21 45.6 384.8 3 304 38.5 47 1.13 31 196.8 1.63 35.8 282.7 2.10 40.4 366.3 2.57 45 449.1 2 348 41.5 50 1.27 30.8 220.3 1.82 35.4 316.4 2.36 40 410.3 2.89 44.5 503.5
max 388 43.5 52 1.39 30.6 241 1.99 35.1 346 2.58 39.6 449.1 3.16 44 551.1
min 232 26.5 35 0.97 32.4 169.1 1.37 37.4 237.8 1.75 42.3 304.9 2.13 47.1 371.4
5 254 27.5 36 1.06 32.3 183.2 1.48 37.2 257.7 1.90 42 330.5 2.31 46.8 402.9 4 353 36.5 45 1.40 31.7 243.6 1.97 36.5 343.2 2.53 41.2 441.1 3.09 45.8 538.5 3 430 41.5 50 1.66 31.4 287.6 2.33 36 405.7 3.00 40.6 522.1 3.66 45.1 638 2 505 44.5 53 1.89 31.1 328.3 2.67 35.6 463.7 3.43 40 597.4 4.19 44.5 730.3
max 584 47.5 56 2.13 30.7 369.2 3.00 35.2 521.9 3.87 39.5 673 4.72 43.8 823.8
min 283 25.5 34 1.18 32.3 205.3 1.67 37.4 290 2.14 42.3 372.2 2.60 47.1 453.6
5 300 26.5 35 1.25 32.3 216.3 1.76 37.3 305.5 2.25 42.1 392.2 2.74 46.9 478.1 4 423 34.5 43 1.68 31.7 292.1 2.37 36.6 412.6 3.05 41.2 530.7 3.71 45.9 648.1 3 490 37.5 46 1.91 31.5 330.9 2.69 36.2 467.8 3.46 40.8 602.3 4.22 45.4 736 2 570 42.5 51 2.16 31.2 375.3 3.06 35.8 531.1 3.93 40.3 684.5 4.80 44.8 837.3
max 716 47.5 56 2.60 30.7 452 3.69 35.2 640.4 4.75 39.6 826.6 5.80 43.9 1012.3
V
[l/h]
pressure
power
dB(A) dB(A)
30 /35°C 40 /35°C 45/40°C 50/45°C
Q
[kW]
LA
H
LA
[°C]
= temperature air outlet, theor.
V
[l/h]
Q
H
[kW]
LA
[°C]
V
[l/h]
Q
H
[kW]
LA
[°C]
V
Q
H
[l/h]
[kW]
Works level 1 and 2 Rated capacity, level 3
[°C]
V
LA
[l/h]
19
Page 20
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Consultation
Thanks to intensive training,
our consultants are always
completely up-to-date when it
comes to technical expertise.
This has given us the reputation
of being more than just an
excellent, reliable supplier:
REMKO, a partner who helps to
solve problems.
Sales
REMKO offers not just a well-
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO employees in the
field are more than just sales
people: above all, they must
be advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely and
reliably. However, in the event of
a malfunction REMKO customer
service is quickly on the scene.
Our comprehensive network of
experienced dealers guarantees
quick and reliable service.
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail [email protected] Internet www.remko.de
Hotline
Air conditioning and heating technology
+49 5232 606-0
Export
+49 5232 606-130
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...