REMKO KWE 440, KWE 370, KWE 150 INOX, KWE 250, KWE 180 INOX Assembly And Operating Instructions Manual

...
Assembly and operating instructions
REMKO KWE 150 - KWE 440 and
REMKO KWE 150 INOX - KWE 440 INOX
Chiller
0183-2018-05 Edition 1, en_GB
Read the instructions prior to performing any task!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety notes for the operator........................................................................................................... 5
1.7 Safety notes for installation, maintenance and inspection.............................................................. 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Warranty........................................................................................................................................ 5
1.11 Transport and packaging............................................................................................................... 6
1.12 Environmental protection and recycling........................................................................................ 6
2 Technical data........................................................................................................................................ 7
2.1 Unit data.......................................................................................................................................... 7
2.2 Unit dimensions............................................................................................................................. 15
2.3 Cooling capacity............................................................................................................................ 16
2.4 Sound pressure level.................................................................................................................... 19
2.5 Characteristic curves..................................................................................................................... 20
3 Design and function............................................................................................................................ 24
3.1 Unit description............................................................................................................................. 24
3.2 System layout................................................................................................................................ 24
3.3 Refrigeration unit construction...................................................................................................... 25
3.4 Hydraulic unit construction............................................................................................................ 25
4 Operation of the controller................................................................................................................. 27
5
Installation instructions for qualified personnel.............................................................................. 31
6 Installation........................................................................................................................................... 36
6.1 Unit installation.............................................................................................................................. 36
7 Condensate drainage connection and safe drainage...................................................................... 44
8 Electrical wiring................................................................................................................................... 45
8.1 General connection and safety instructions.................................................................................. 45
8.2 Unit connection............................................................................................................................. 46
8.3 Electrical components................................................................................................................... 48
9 Leak testing......................................................................................................................................... 48
10 Before commissioning....................................................................................................................... 49
11 Commissioning................................................................................................................................... 51
12 Shutdown............................................................................................................................................. 52
13 Troubleshooting and customer service............................................................................................ 53
14 Care and maintenance........................................................................................................................ 57
15 Index..................................................................................................................................................... 58
3
REMKO KWE
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for
.
liability
Keep this operating manual and the refrigerant data sheet near to the units.

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
1.4

Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4

1.6 Safety notes for the operator

The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grille) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with certain unit parts or components
may lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperature.
n Spaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of suffocation.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign objects, fluids or gases.
n The units must be inspected by a service tech-
nician at least once annually. Visual inspec­tions and cleaning may be performed by the operator when the units are disconnected from the mains.
.

1.7 Safety notes for installation, maintenance and inspection

n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Local regulations and laws such as Water
Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n Mobile units must be set up securely on suit-
able surfaces and in an upright position. Sta­tionary units must be permanently installed for operation.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
, maintenance or
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices must not be altered or
bypassed.
Unauthorised modification
1.8 and changes
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

Depending on the model and the unit, the units are only intended to be used as a chiller for the cooling or warming of the operating medium water or a water-glycol mixture within a closed medium cycle.
Any different or additional use is a non-intended use. The manufacturer / supplier assumes no lia­bility for damages arising from non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
5
REMKO KWE

1.11 Transport and packaging

The devices are supplied in a sturdy shipping con-
. Please check the equipment immediately
tainer upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner cling specialists or at collection points.
, e.g. using certified firms and recy-
6

2 Technical data

2.1 Unit data

Unit data KWE 150 - KWE 250
Series KWE 150 KWE 180 KWE 220 KWE 250
Operating mode Air-cooled compact chiller
Nominal cooling output
Energy efficiency rating EER
1)
1)
SEER 3.84 3.83 3.85 3.85
kW 15.01 17.44 21.58 24.72
3.50
Annual room cooling efficiency ŋ
S,C
Adjustment range - return temperature cooling
% 151 150 151 151
°C +9 to +22
Operating range, cooling °C +15 to +45
Operating range cooling (extension) °C
-7 to +45 2) / -15 to +45
3)
Cooling circuits, number 1
Refrigerant
R410A
4)
GWP value 2088
Refrigerant filling quantity
5)
kg 5.6 6.2 8.1 8.7
CO2 equivalent t 11.69 12.95 16.91 18.17
Compressor, number / type 1 / Scroll
Max. airflow volume
m3/h
10,500 10,000 11,000 20,500
Number of fans 1 2
Sound pressure level
6)
dB (A) 40.4 39.8 41.1 43.3
Sound power level dB (A) 71.9 71.3 72.5 74.9
Power supply V/Ph/Hz 400/3~/50
Enclosure class IP X4
Electrical power consumption, max. kW 6.5 8.7 9.5 12.3
Electrical current consumption, max. A 11.68 15.61 17.07 22.16
Electrical rated power consumption, cooling
Electrical rated current consumption, cooling
kW 4.22 4.99 6.1 6.99
A 7.4 8.7 10.6 12.2
Electrical starting current, max. A 65.6 76.6 102.6 114.2
Operating medium max. 35% ethylene glycol, max. 35% propylene glycol
Operating pressure, medium, max. kPa 600
Nominal flow rate, medium - cooling
Minimum flow volume, medium
m3/h
m3/h
2.59 2.99 3.71 4.25
1.61 1.87 2.32 2.65
7
REMKO KWE
Series KWE 150 KWE 180 KWE 220 KWE 250
Maximum flow volume, medium
m3/h
4.30 4.99 6.18 7.08
Pressure loss, indoor kPa 11 10 11 11
Diaphragm expansion vessel, volume l 6
Diaphragm expansion vessel MAG, pre­liminary pressure
kPa 1.5
Medium connection, inlet Inches 1 1/4 1 1/2
Medium connection, outlet Inches 1 1/4 1 1/2
Medium content, pipe lines l 4.82 5.39 5.95 7.72
Minimum medium volume, per unit l 45 53 65 75
Height mm 1297 1550
Width mm 1590 1990
Depth mm 780 900
Weight kg 217 225 235 331
Operating weight, approx. kg 221.8 230.4 241.0 338.7
Serial number INOX 1790 1791 1792 1793
EDP no. INOX 1656151 1656181 1656221 1656251
Serial number RAL 9018 1742... 1743... 1744... 1745...
EDP no. RAL 9018 1656150 1656180 1656220 1656250
1)
Air intake temperature TK 35, medium inlet 12 , medium outlet 7 ,
2)
Only with compressor crankcase heating accessory
3)
Only with winter pressure regulation accessory, set
4)
Contains greenhouse gas per Kyoto protocol
5)
The refrigerant filling quantity is subject to continuous optimisation. Therefore, the exact filling quantity can
0% glycol concentration
be found on the name plate
6)
Distance 10 m free field
8
Chiller with standard pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Nominal pump pressure, max. kPa 90 87 78 74
System pressure available, cooling kPa 79 77 67 63
Power consumption, pump kW 0.2
Current consumption, pump A 1.3
Weight kg 227 235 245 343
Operating weight, approx. kg 232 240 250 350
Chiller with high-pressure pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Nominal pump pressure, max. kPa 174 166 147 168
System pressure available, cooling kPa 163 156 136 157
Power consumption, pump kW 0.6 1.1
Current consumption, pump A 1.5 2.4
Weight kg 232 240 250 350
Operating weight, approx. kg 237 246 256 358
Chiller with high-performance pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Nominal pump pressure, max. kPa 277 272 256 258
System pressure available, cooling kPa 266 262 245 247
Power consumption, pump kW 1.1 1.5
Current consumption, pump A 2.4 3.2
Weight kg 237 245 255 353
Operating weight, approx. kg 242 250 261 361
Chiller with storage tank and standard pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Medium content, storage tank kPa 60 90
Weight kPa 247 255 265 369
Operating weight, approx. kW 311 320 331 466
9
REMKO KWE
Chiller with storage tank and high-pressure pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Medium content, storage tank kPa 60 90
Weight kPa 252 260 270 376
Operating weight, approx. kW 317 326 336 474
Chiller with storage tank and high-performance pump
Series KWE 150 KWE 180 KWE 220 KWE 250
Medium content, storage tank kPa 60 90
Weight kPa 257 265 275 379
Operating weight, approx. kW 322 330 341 477
10
Unit data KWE 300 - KWE 440
Series KWE 300 KWE 320 KWE 370 KWE 440
Operating mode Air-cooled compact chiller
Nominal cooling output
1)
Energy efficiency rating EER
1)
kW 29.32 32.00 37.04 43.37
3.50
SEER 3.93 3.91 3.84 3.85
Annual room cooling efficiency ŋ
S,C
Adjustment range - return temperature cooling
% 154 154 150 151
°C +9 to +22
Operating range, cooling °C +15 to +45
Operating range cooling (extension) °C
-7 to +45 2) / -15 to +45
3)
Cooling circuits, number 1
Refrigerant
R410A
4)
GWP value 2088
Refrigerant filling quantity
5)
kg 11.5 12.0 12.6 15.6
CO2 equivalent t 24.01 25.06 26.31 32.57
Compressor, number / type 1 / Scroll
Max. airflow volume
m3/h
20,000 21,000 22,500 22,500
Number of fans 2
Sound pressure level
6)
dB (A) 42.3 43.9 44.5 45.2
Sound power level dB (A) 73.9 75.5 76.1 76.8
Power supply V/Ph/Hz 400/3~/50
Enclosure class IP X4
Electrical power consumption, max. kW 12.7 14.6 18.1 19.9
Electrical current consumption, max. A 22.83 26.36 32.67 35.84
Electrical rated power consumption, cooling
Electrical rated current consumption, cooling
kW 8.1 9.02 10.53 14.22
A 14.1 15.7 18.4 21.3
Electrical starting current, max. A 142.2 121.2 143.2 177.2
Operating medium max. 35% ethylene glycol, max. 35% propylene glycol
Operating pressure, medium, max. kPa 600
Nominal flow rate, medium - cooling
Minimum flow volume, medium
Maximum flow volume, medium
m3/h
m3/h
m3/h
5.04 5.51 6.37 7.45
3.15 3.44 3.98 4.66
8.40 9.16 10.61 12.42
Pressure loss, indoor kPa 12 12 13 14
Diaphragm expansion vessel, volume l 6
11
REMKO KWE
Series KWE 300 KWE 320 KWE 370 KWE 440
Diaphragm expansion vessel MAG, pre­liminary pressure
kPa 1.5
Medium connection, inlet Inches 1 1/2
Medium connection, outlet Inches 1 1/2
Medium content, pipe lines l 8.29 8.85 9.42 10.55
Minimum medium volume, per unit l 88 96 112 131
Height mm 1550
Width mm 1990
Depth mm 900
Weight kg 365 381 391 406
Operating weight, approx. kg 373.3 389.9 400.4 416.6
Serial number INOX 1794 1795 1796 1797
EDP no. INOX 1656301 1656321 1656371 1656441
Serial number RAL 9018 1746... 1747... 1748... 1749...
EDP no. RAL 9018 1656300 1656320 1656370 1656440
1)
Air intake temperature TK 35, medium inlet 12 , medium outlet 7 ,
2)
Only with compressor crankcase heating accessory
3)
Only with winter pressure regulation accessory, set
4)
Contains greenhouse gas per Kyoto protocol
5)
The refrigerant filling quantity is subject to continuous optimisation. Therefore, the exact filling quantity can
0% glycol concentration
be found on the name plate
6)
Distance 10 m free field
12
Chiller with standard pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Nominal pump pressure, max. kPa 95 92 83 70
System pressure available, cooling kPa 83 80 70 56
Power consumption, pump kW 0.3
Current consumption, pump A 1.3
Weight kg 379 395 405 420
Operating weight, approx. kg 387 403 414 430
Chiller with high-pressure pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Nominal pump pressure, max. kPa 155 148 132 110
System pressure available, cooling kPa 143 136 119 96
Power consumption, pump kW 1.1
Current consumption, pump A 2.4
Weight kg 384 400 410 425
Operating weight, approx. kg 392 409 419 436
Chiller with high-performance pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Nominal pump pressure, max. kPa 245 237 220 196
System pressure available, cooling kPa 233 225 207 182
Power consumption, pump kW 1.5
Current consumption, pump A 3.2
Weight kg 387 403 413 428
Operating weight, approx. kg 395 412 423 439
Chiller with storage tank and standard pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Medium content, storage tank kPa 90
Weight kPa 404 420 430 445
Operating weight, approx. kW 502 519 529 546
13
REMKO KWE
Chiller with storage tank and high-pressure pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Medium content, storage tank kPa 90
Weight kPa 410 426 436 451
Operating weight, approx. kW 508 525 535 552
Chiller with storage tank and high-performance pump
Series KWE 300 KWE 320 KWE 370 KWE 440
Medium content, storage tank kPa 90
Weight kPa 413 429 439 454
Operating weight, approx. kW 511 528 539 555
14

2.2 Unit dimensions

Fig. 1: Dimensions KWE 150 - 220 (all measurements in mm)
Fig. 2: Dimensions KWE 250 - 440 (all measurements in mm)
15
REMKO KWE
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
2.3

Cooling capacity

KWE 150 KWE 180
IL Air intake temperature IL Air intake temperature
°C 20 25 30 35 40 °C 20 25 30 35 40
5 16.64 15.70 14.88 13.98 13.02 5 19.39 18.42 17.39 16.31 15.20
6 17.03 16.25 15.41 14.49 13.51 6 20.04 19.03 17.98 16.87 15.72
7 17.61 16.81 15.95 15.01 14.01 7 20.70 19.66 18.58 17.44 16.26
8 18.19 17.39 16.50 15.54 14.52 8 21.37 20.31 19.19 18.03 16.82
9 18.81 17.99 17.08 16.10 15.05 9 22.07 20.98 19.83 18.63 17.39
10 19.43 18.58 17.65 16.65 15.58 10 22.76 21.64 20.46 19.23 17.96
11 20.09 19.21 18.26 17.23 16.14 11 23.49 22.34 21.12 19.86 18.56
12 20.74 19.84 18.86 17.81 16.69 12 24.22 23.03 21.78 20.49 19.16
13 21.43 20.50 19.49 18.42 17.27 13 24.98 23.75 22.47 21.15 19.78
14 22.11 21.15 20.12 19.02 17.85 14 25.73 24.47 23.16 21.80 20.40
15 22.83 21.84 20.78 19.66 18.46 15 26.52 25.22 23.88 22.49 21.05
16 23.55 22.53 21.44 20.29 19.07 16 27.30 25.97 24.60 23.17 21.70
17 24.30 23.26 22.14 20.95 19.71 17 28.12 26.75 25.34 23.88 22.38
18 25.05 23.98 22.83 21.61 20.34 18 28.93 27.53 26.08 24.59 23.05
19 25.84 24.74 23.56 22.31 21.01 19 29.78 28.34 26.86 25.33 23.76
20 26.62 25.49 24.28 23.00 21.67 20 30.62 29.15 27.63 26.06 24.46
KWE 220 KWE 250
IL Air intake temperature IL Air intake temperature
°C 20 25 30 35 40 °C 20 25 30 35 40
5 23.85 22.66 21.44 20.18 18.87 5 27.27 25.93 24.55 23.11 21.61
6 24.66 23.43 22.17 20.87 19.53 6 28.20 26.81 25.38 23.91 22.37
7 25.48 24.21 22.91 21.58 20.20 7 29.14 27.70 26.23 24.72 23.15
8 26.33 25.01 23.67 22.30 20.89 8 30.10 28.62 27.10 25.54 23.93
9 27.20 25.84 24.46 23.05 21.60 9 31.09 29.56 27.99 26.39 24.74
10 28.06 26.66 25.24 23.79 22.30 10 32.08 30.49 28.88 27.24 25.55
11 28.97 27.52 26.06 24.57 23.04 11 33.11 31.47 29.81 28.12 26.39
12 29.88 28.38 26.87 25.34 23.77 12 34.14 32.45 30.74 29.00 27.23
13 30.82 29.28 27.72 26.15 24.54 13 35.21 33.46 31.70 29.91 28.10
16
KWE 220 KWE 250
14 31.76 30.17 28.57 26.95 25.30 14 36.28 34.47 32.66 30.82 28.97
15 32.74 31.10 29.45 27.79 26.10 15 37.39 35.52 33.65 31.77 29.82
16 33.72 32.03 30.33 28.62 26.89 16 38.49 36.57 34.64 32.71 30.67
17 34.74 33.00 31.25 29.49 27.71 17 39.64 37.65 35.67 33.69 31.65
18 35.75 33.96 32.16 30.36 28.53 18 40.78 38.73 36.70 34.66 32.62
19 36.80 34.96 33.11 31.26 29.39 19 41.96 39.85 37.76 35.67 33.58
20 37.84 35.95 34.06 32.15 30.24 20 43.13 40.97 38.82 36.67 34.53
KWE 300 KWE 320
IL Air intake temperature IL Air intake temperature
°C 20 25 30 35 40 °C 20 25 30 35 40
5 32.17 30.62 29.04 27.41 25.71 5 35.58 33.73 31.85 29.91 27.89
6 33.26 31.66 30.04 28.36 26.61 6 36.79 34.87 32.93 30.94 28.88
7 34.35 32.73 31.05 29.32 27.53 7 38.03 36.05 34.05 32.00 29.88
8 35.50 33.82 32.10 30.31 28.47 8 39.30 37.26 35.19 33.08 30.91
9 36.69 34.96 33.18 31.34 29.45 9 40.63 38.51 35.33 34.21 31.98
10 37.88 36.09 34.25 32.36 30.42 10 41.95 39.76 37.56 35.33 33.04
11 39.12 37.28 35.38 33.43 31.44 11 43.34 41.07 37.67 36.50 34.16
12 40.36 38.46 36.50 34.50 32.46 12 44.72 42.38 40.03 37.67 35.27
13 41.66 39.69 37.68 35.62 33.52 13 46.17 43.75 40.13 38.90 36.44
14 42.96 40.92 38.85 36.73 34.58 14 47.62 45.12 42.63 40.13 37.60
15 44.31 42.21 40.07 37.90 35.69 15 49.14 46.55 42.69 41.41 38.82
16 45.66 43.50 41.29 39.06 36.79 16 50.65 47.98 45.34 42.69 40.03
17 47.07 44.84 42.57 40.27 37.95 17 52.23 49.48 46.76 44.03 41.30
18 48.47 46.17 43.84 41.48 39.10 18 53.81 50.97 48.17 45.37 42.57
19 49.93 47.56 45.16 42.74 40.30 19 55.45 52.54 49.65 46.77 43.90
20 51.38 48.94 46.48 44.00 41.50 20 57.09 54.10 51.12 48.17 45.22
17
REMKO KWE
KWE 370 KWE 440
IL Air intake temperature IL Air intake temperature
°C 20 25 30 35 40 °C 20 25 30 35 40
5 40.95 38.97 36.88 34.68 32.38 5 47.81 45.47 43.08 40.61 38.03
6 42.32 40.27 38.11 35.85 33.47 6 49.42 47.00 44.53 41.97 39.32
7 43.72 41.60 39.37 37.04 34.60 7 51.07 48.56 46.00 43.37 40.63
8 45.16 42.97 40.66 38.26 35.74 8 52.76 50.16 47.52 44.80 41.98
9 46.66 44.38 42.00 39.52 36.93 9 54.52 51.83 49.09 46.28 43.37
10 48.15 45.79 43.34 40.78 38.11 10 56.27 53.49 50.66 47.76 44.76
11 49.72 47.27 44.74 42.10 39.35 11 58.12 55.23 52.31 49.31 46.22
12 51.28 48.75 46.13 43.41 40.59 12 59.96 56.97 53.95 50.86 47.68
13 52.91 50.30 47.59 44.79 41.89 13 61.89 58.80 55.67 52.48 49.21
14 54.54 51.84 49.05 46.16 43.18 14 63.81 60.62 57.39 54.10 50.74
15 56.25 53.46 50.57 47.60 44.53 15 65.83 62.53 59.19 55.78 52.34
16 57.96 55.07 52.06 49.03 45.88 16 67.85 64.44 60.99 57.46 53.93
17 59.74 56.75 53.68 50.53 47.29 17 69.96 66.43 62.87 59.25 55.60
18 61.52 58.43 55.27 52.02 48.69 18 72.06 68.42 64.75 61.04 57.27
19 63.37 60.19 56.92 53.58 50.16 19 74.25 70.50 66.72 62.90 59.02
20 65.21 61.94 58.57 55.13 51.62 20 76.44 72.58 68.68 64.75 60.76
18

2.4 Sound pressure level

KWE 150 - KWE 250
KWE 150 KWE 180 KWE 220 KWE 250
Hz Sound pressure level Lp in dB(A), distance 10 m
63 11.60 11.60 11.60 14.50
125 24.60 24.60 24.60 27.50
250 24.20 23.70 24.40 27.10
500 32.50 31.40 33.60 36.50
1000 36.50 33.70 36.50 37.60
2000 33.50 33.60 34.80 37.90
4000 31.50 33.10 32.90 35.30
8000 27.90 30.30 26.00 27.90
Complete 40.4 41.10 43.30 42.30
KWE 300 - KWE 440
KWE 300 KWE 320 KWE 370 KWE 440
Hz Sound pressure level Lp in dB(A), distance 10 m
63 14.50 14.50 14.50 14.50
125 27.50 27.50 27.50 27.50
250 28.90 26.70 27.00 27.00
500 34.40 35.50 36.80 36.40
1000 36.80 38.80 39.30 39.90
2000 36.00 38.70 39.40 40.80
4000 35.20 35.70 36.50 36.90
8000 28.70 29.70 29.00 29.80
Complete 43.90 44.50 45.20 76.80
19
50 45 40 35 30 25 20 15 10 5 0
0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
50 45 40 35 30 25 20 15 10 5 0
1,30,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
50 45 40 35 30 25 20 15 10 5 0
0,3 0,5 0,6 0,8 0,9 1,1 1,2 1,4 1,5 1,7 1,8
50 45 40 35 30 25 20 15 10 5 0
0,4 0,6 0,7 0,9 1,0 1,2 1,3 1,5 1,6 1,8 1,9
50 45 40 35 30 25 20 15 10 5 0
0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4
50 45 40 35 30 25 20 15 10 5 0
0,5 0,7 0,9 1,1 1,3 1,5 1,7 1,9 2,1 2,3 2,5
50 45 40 35 30 25 20 15 10 5 0
0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4 2,6 2,8
5
0 45 40 35 30 25 20 15 10 5 0
1,1 1,3 1,5 1,7 1,9 2,1 2,3 2,5 2,7 2,8 3,1
KWE 150 KWE 180
KWE 220 KWE 250
KWE 300 KWE 320
KWE 370 KWE 440
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
REMKO KWE

2.5 Characteristic curves

Pressure loss
1: Pressure loss [kPa] 2: Medium flow rate [l/sec]
20
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
1,21,11,00,90,80,70,60,50,40,30,2
140 120 100
80 60 40 20
0
1,31,21,11,00,90,80,70,60,50,40,3
140
120
100
80 60 40 20
0
1,51,41,31,21,11,00,90,80,70,60,5
140 120 100
80 60 40 20
0
1,71,61,51,41,31,21,11,00,90,80,7
140
120
100
80 60 40 20
0
2,22,11,91,81,61,51,31,21,00,90,7
140 120 100
80 60 40 20
0
2,22,01,91,71,61,41,31,11,00,8
140
120
100
80 60 40 20
0
2,42,22,01,81,61,41,21,0
140 120 100
80 60
40 20
0
2,82,72,52,42,22,11,91,81,61,51,3
140
120
100
80 60 40 20
0
2,3
KWE 180KWE 150
KWE 220 KWE 250
KWE 300
KWE 320
KWE 370 KWE 440
System pressure available - standard pump
1: System pressure available [kPa] 2: Medium flow rate [l/sec]
21
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
200
160
120
80
40
0
0,1 0,2 0,4 0,5 0,6 0,8 0,9 1,0 1,1 1,3 1,4
200
160
120
80
40
0
0,1 0,3 0,4 0,6 0,7 0,9 1,0 1,2 1,3 1,5 1,6
200
160
120
80
40
0
0,3 0,5 0,6 0,8 0,9 1,1 1,2 1,4 1,5 1,7
1,8
200
160
120
80
40
0
0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2
200
160
120
80
40
0
0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4
200
160
120
80
40
0
0,4 0,6 0,9 1,1 1,3 1,6 1,8 2,0 2,2 2,5 2,7
200
160
120
80
40
0
0,6 0,8 1,1 1,3 1,5 1,8 2,0 2,2 2,4 2,7 2,9
200
160
120
80
40
0
0,9 1,1 1,4 1,6 1,8 2,1 2,3 2,5 2,7 3,0 3,2
KWE 150 KWE 180
KWE 220 KWE
250
KWE 300
KWE 320
KWE 370 KWE 440
REMKO KWE
System pressure available - high-pressure pump
1: System pressure available [kPa] 2: Medium flow rate [l/sec]
22
System pressure available - high-performance pump
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
350 300 250 200 150 100
50
0
0,1 0,2 0,4 0,5 0,6 0,8 0,9 1,0 1,1 1,3 1,4
KWE 150 KWE 180
KWE 220 KWE 250
KWE 300
KWE 320
KWE 370 KWE 440
350 300 250 200 150
100
50
0
0,1 0,3 0,4 0,6 0,7 0,9 1,0 1,2 1,3 1,5 1,6
350 300 250 200 150 100
50
0
350 300 250 200 150
100
50
0
350 300 250 200 150 100
50
0
350 300 250 200 150
100
50
0
350 300 250 200 150 100
50
0
350 300 250 200 150
100
50
0
0,3 0,5 0,6 0,8 0,9 1,1 1,2 1,4 1,5 1,7 1,8 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2
0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4 0,4 0,6 0,9 1,
1 1,3 1,6 1,8 2,0 2,2 2,5 2,7
0,6 0,8 1,1 1,3 1,5 1,8 2,0 2,2 2,4 2,7 2,9 0,9 1,1 1,4 1,6 1,8 2,1 2,3 2,5 2,7 3,0 3,2
1: System pressure available [kPa] 2: Medium flow rate [l/sec]
23
B1
A
4
1a
3
1
2
1 1
1c1b
3
3
B3B2
5
6
3a
REMKO KWE

3 Design and function

3.1 Unit description

In cooling mode, the unit (an air-cooled chiller) takes heat out of the operating medium to be cooled, water or a mixture of water and glycol, within a closed medium cycle in the evaporator (plate heat exchanger) and passes it on to the closed cooling cycle.
As a consequence of the heat exchange, the medium cools and the refrigerant in the cooling cycle vaporises under low pressure. The gaseous refrigerant enters an electric compressor (scroll construction) which increases the pressure and the temperature of the refrigerant.
The gaseous refrigerant is led into a finned con­denser exchange, condenses the refrigerant under high pressure to a liquid.
The air emerging at the condenser heats the envi­ronment. The liquid refrigerant is fed by means of a variable injector valve back to the evaporator where the circuit begins again. In heating mode, a chiller with heat pump functions (HP-function) can take up heat from the ambient air in the finned con­denser and pass it on to the operating medium. A reversing valve switches the cooling cycle function.
A return temperature dependent, adaptive con­troller, which ensures the unit's operation and all of the safety functions, is used to control the cooling or heating capacity. A potential-free contact pro­vides for remote enabling.
The unit is designed for outdoor installation. Under certain circumstances, it can also be used in indoor areas.
The unit cooling cycle comprises an evaporator, compressor, thermal injection valve, condenser, condenser fan, fan control system and high and low pressure switches. Units with heat pump func­tion also have a reversing valve and a collecting flask.
The medium cycle comprises a circulation pump, expansion vessel, safety valve and differential pressure switch.
A storage tank is not mandatory.
Winter pressure controls, cabled remote control, crankcase heating, vibration dampers, heaters for anti-freeze protection, external medium storage tanks, glycol concentrate and a technical assis­tance commissioning are available as accessories.
, which, as a consequence of the heat

3.2 System layout

The unit is designed for a 2-conductor system.
The system has 2 medium pipes (conductors: Supply and return flow) for cooling using a cold medium. In combination with a corresponding system, the output can be transmitted to the room to be cooled via the floor, the building structure or by means of ceiling cooling. For each of the dif­ferent systems, a minimum flow volume and a min­imum medium volume must be ensured for the plant.
Fig. 3: System layout
A: Outdoor area B1-3: Indoor area 1,2,3 1: Cold water drain 1a: Infrared remote control 1b: Room temperature controller 1c: Cabled remote control 2: Chiller 3: Condensate drainage line 3a: Condensate drainage line
(only units with HP-function) 4: Condensate collecting drainage 5: Medium outlet 6: Medium inlet
24
NOTICE!
PZH PSH
PZL
TC
KWE 150-220
KWE 250-440
PZH PSH
PZL
TC
P
KWE 150-220
KWE 250-440
P
KWE 150-220
P
KWE 250-440
P
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This device contains refrigerant with a greenhouse potential of 2088. That means the escape of 1 kg of this refrig­erant has an ef
fect on global warming that is 2088 times greater than 1 kg CO2, based on 100 years. Do not conduct any work on the refrigerant circuit or dismantle the device ­always enlist the help of qualified experts.

3.3 Refrigeration unit construction

3.4 Hydraulic unit construction

Fig. 4: Standard
Fig. 5: Standard
Fig. 6: With pump
Fig. 7: With pump
25
KWE 150-220
P
KWE 250-440
P
KWE 150-220
P
KWE 250-440
P
KWE 150-220
P
KWE 250-440
P
REMKO KWE
Fig. 8: With storage tank and pump
Fig. 9: With storage tank and pump
Fig. 12: With storage tank and high-pressure or high-performance pump
Fig. 13: With storage tank and high-pressure or high-performance pump
Fig. 10: With high-pressure or high-performance pump
Fig. 11: With high-pressure or high-performance pump
26
2
1
4
3
5
6
4
7
8 9
10
11 12
1
2
3
4
5
6
7
8
9
10
11
12
4 Operation of the
controller
Explanation of the keys
“Alarm” key
By pressing this key selected. Pressing the key again acknowledges that a malfunction has been rectified. The error memory can be called up by subsequently pressing the “Enter” key.
“Main menu” key
This key takes you to the main menu in which the 8 submenus are located. T arrow keys and the “Enter” key to select a sub­menu.
“Back” key
Press this key to cancel an entry or to return to the previous menu.
, a current malfunction can be
o navigate, press the
“Compressor” display
When this symbol appears, the compressor is acti­vated and in operation.
“Operating mode” display
This symbol indicates the current operating mode. If e.g. cooling capacity is requested, a snowflake appears here and the system is in cooling mode.
“Pump” display
If the circulation pump is activated, this symbol appears and the pump is in operation.
“Operating status” display
Displays the current operating status of the system, e.g. the “On” operating status is displayed while the system is running.
“System temperature” display
Displays the system temperature measured at the return flow
.
Main menu
Access to the main menu is possible by pressing the “Main menu” key. The main menu provides access to the 8 submenus. To navigate, press the arrow keys and then the “Enter” key to select a submenu.
A. On / Off Unit
“Arrow up / down” key
Use the arrow keys to navigate within the menus
The operating status can be selected here. OFF, Auto, Energy Save and ON are available.
and set the parameter values
B. Setpoint
In the “Setpoint” submenu, the return flow temper-
“Enter” key
The “Enter” key can be used to select a parameter
ature can be set in nominal mode and in Energy save mode.
or setpoint or to confirm the setting of a setpoint.
C. Clock / Scheduler
Meanings of the displays
T
ime and date display
The current time and date are displayed here.
In this menu it is possible to set the time and date. In addition, a time program can be stored in which it can be determined when the system is to be On,
Off or operated in Energy Save mode. Under the “C. Clock / Scheduler” submenu, the time and date can be adjusted manually.
“Identification number” display
Displays the system identification number for a building management system. It can be adjusted under the “F
. Board switch” submenu.
D. Input / Output
Under “Input / Output” current probe values and
information about the current operating status of
various components can be read.
27
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Off
1 x
!
Main menu 1/8
B.Setpoint
C.Clock/Scheduler
A.On/Off Unit
1 x
REMKO KWE
E. Data Logger
This is the error memory of the system, in which up to 50 malfunctions can be stored. If all 50 spaces are occupied, the oldest malfunction is deleted and overwritten.
F
. Board switch
This menu allows the addressing of the system for a building management system.
G. Service
In this menu you can configure the settings on the system. Access is password protected. If you have any questions, please contact our service depart­ment.
H. Manufacturer
This menu level is only accessible to the manufac­turer. If you have any questions, please contact our service department.
The desired operating status can be set as follows:
To enter the main menu, press the “Menu” key on the start screen.
Operating states
The unit has four adjustable operating states:
Off: The unit is in standby mode. The safety equip­ment is still active.
Auto: Automatic switching between heating and cooling. This operating state is intended for units with heat pump function.
Energy Save: In the Energy Save operating state, the system runs the stored Energy Save setpoints and time program.
On: The unit is activated and complies with the normal setpoints.
In the main menu, use the arrow keys to select the “A. On / Of “Enter” key
f Unit” submenu and confirm with the
28
!
On/Off Unit A01
Unit
Off
Cooling only
In the “On / Off Unit” window, press the “Enter” key.
1 x
!
On/Off Unit A01
Unit
Off
Cooling only
!
On/Off Unit A01
Unit
On
Cooling only
1 x
!
On/Off Unit A01
Unit
On
Cooling only
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Off
1 x
!
Main menu 2/8
C.Clock/Scheduler
A.On/Off Unit
B.Setpoint
1 x
!
Thermoreg. Unit B01
Heat pump temperature Nominal setpoint (ON)
Cooling: 23.0 C° Heating: 0.0 C°
Setpoint return temperature sensor
Two different values can be set for the return flow temperature:
Nominal setpoint: The setpoint for normal opera­tion
Energy Save setpoint: The setpoint for the energy-saving mode
The respective “heating” setting is intended for units with heat pump function and therefore has no function.
The setpoints can be set as follows:
The value can now be changed using the two arrow keys.
Press the “Enter” key to confirm your selection.
To enter the main menu, press the “Menu” key on the start screen.
In the main menu, use the arrow keys to select the “B. Setpoint” submenu and confirm with the “Enter” key
The setting is now made and saved.
29
1 x
!
Thermoreg. Unit B01
Heat pump temperature Nominal setpoint (ON)
Cooling: 23.0 C° Heating: 0.0 C°
!
Thermoreg. Unit B01
Heat pump temperature Nominal setpoint (ON)
Cooling: 9.0 C° Heating: 0.0 C°
1 x
!
Thermoreg. Unit B01
Heat pump temperature Nominal setpoint (ON)
Cooling: 9.0 C° Heating: 0.0 C°
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Alarm-Off
1 x
!
!
Alarms ALF01
Position: ID1
Fan overload
2 x
!
!
Thermoreg. Unit B01
Heat pump temperature Nominal setpoint (ON)
Cooling: 23.0 C° Heating: 0.0 C°
Unit
Alarms ALF01
No active alarm Press ENTER
to DATA LOGGER
REMKO KWE
In the “Thermoreg. Unit” field, use the arrow keys to select the window for the setpoint in nominal or energy-saving mode and press the “Enter” key
The value can now be changed using the two arrow keys.
.
Display and acknowledge malfunctions
In order to protect the unit from damage, the con­troller checks the components that are relevant for the safety of the unit by means of sensors for tem­perature, pressure, configuration, etc.
An error code and a brief description of the mal­function are displayed in the error view of the con­troller
. A rectified error can be acknowledged in the
error view:
To enter the error view, press the “Alarm” key on the start screen.
Press the “Enter” key to confirm your selection.
The setting is now made and saved.
An active malfunction is now displayed in the alarm menu. After eliminating the cause of the error acknowledge the malfunction by pressing the “Alarm” key twice.
The malfunction is now acknowledged. The last 50 malfunctions can be found in the error memory for subsequent review
.
,
30
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Off
1 x
!
Main menu 1/8
B.Setpoint
C.Clock/Scheduler
A.On/Off Unit
Main menu 5/8
D.Input/Output
F.Board switch
E.Data logger
1 x
!
Data logger E17
ALF01 10:51 21/02/18 Fan Overload
Inlet Outlet
Plant: 17.0 C 17.2 C° ° Ext.T: 0.0 C° DHW: 0.0 C° Press:Hp 12.4 LP 0.0
Error memory
In the event of a malfunction, the error memory of the controller collects and stores the most impor­tant data such as time of the malfunction, designa­tion and error code of the malfunction, and meas­ured values of the sensors. This means that information on past malfunctions can also be retrieved at a later point in time.
The controller stores up to 50 malfunctions. If all 50 spaces are occupied, the oldest malfunction is deleted.
The error memory can be called up as follows:
To enter the main menu, press the “Menu” key on the start screen.
5 Installation instructions
for qualified personnel
Important notes prior to installation
Observe the instruction manuals for the indoor units and the chiller or heating system when instal­ling the entire system.
n Observe the operating manuals for the indoor
unit and the chiller or heating system when installing the entire system.
n The indoor units and chillers work independ-
. A connecting line between the two is not
ently necessary.
n Transport the unit in its original packaging as
close as possible to the installation location. You avoid transport damage by doing so.
n The units may only be moved as installed
(upright) using appropriate transport gear. Secure against tipping!
In the main menu, use the arrow keys to select the “E. Data Logger” submenu and confirm with the “Enter” key
Use the arrow keys to navigate in the error memory
.
31
Fig. 14: Upright unit transport
1
REMKO KWE
n The unit must be kept upright when trans-
porting to a higher elevation.
Fig. 15: Vertical unit transport
1: Pick-up point
n Check the contents of the packaging for com-
pleteness and check the unit for visible trans­port damage. Report any damage immediately to your contractual partner and the shipping company
n Select an installation location which allows air
to freely flow through the air inlet and outlet (see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
n Lift the unit only at intended lifting points.
Never place the medium or refrigerant piping under load.
n The medium connection lines, valves and con-
nections must have vapour density insulation. If necessary, also insulate the condensate drainage line. In dual systems with cooling and heating modes, the requirements of the current Energy Savings Ordinance (EnEV) are to be complied with.
n Seal off open lines to prevent dirt getting in and
never kink or crimp the lines.
n Avoid unnecessary bends. This minimises the
pressure loss in the lines.
n Install all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals. Otherwise there is a risk of fire.
n Comply with all regulations governing structural
and building requirements and conditions with regard to the installation site.
n In the selection of the installation site, pay
attention to the site itself and to any possible acoustic reflection from surrounding units.
.
o avoid the transmission of vibrations to the
n T
installation site, the units must be installed on vibration absorbing material or on vibration decoupled foundations. In doing so, make sure that the lines are also vibration decoupled
n If the installation site must fulfil special sound
emission requirements, these must be realised on-site when appropriate adjustments can be made. In these cases, please consult an appropriate acoustics expert.
Wall openings
e recommend that the inside of the opening
n W
be padded or lined for example with a PVC pipe to prevent damage to the lines.
n After installation, the wall opening should be
closed off by the customer with a suitable sealant. Do not use substances containing lime or cement!
Installation materials
The unit is fastened on vibration dampers (acces­sories) to the floor by means of bolts. The carrying capacity of the bracket and the wall must be taken into account when fastening to the wall.
Selecting the installation location
The unit is designed for horizontal installation on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over installed outside as well as inside a building. For external installation, please observe the following instructions to protect the unit from the influence of the weather.
Rain
The unit should be at least 10 cm off the ground when mounted on the roof or ground. A floor bracket is available as an accessory.
Increasing the installation height will also increase the heating capacity generated by the heating / cooling unit (only HP function).
. The unit can be
32
1
20 cm
1
Sun
The finned condenser gives of
f heat in cooling
mode.
Exposure to sunlight further increases the temper­ature of the fins and reduces the heat released by the finned heat exchanger.
The unit should, whenever possible, be installed on the north side of the building.
If necessary, take measures to provide sufficient shade (responsibility of customer).
This could be a small roof.
However, the discharging warm air flow must not be affected by the measures
Wind
If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the pre­vailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be pro­vided by the customer).
Ensure that the windbreak does not adversely affect the air intake to the unit.
Snow
The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20 cm above the expected level of snow to prevent snow from entering the outdoor unit.
Fig. 17: Minimum clearance to snow
1: Snow
Fig. 16: Windbreak
1: Wind
33
2
1
K
3
W
3
W
REMKO KWE
Installation inside buildings
n Ensure that heat can dissipate adequately when placing the outdoor unit in cellars, lofts, adjoining rooms
or halls (Fig. 18).
n Install an additional fan with a rated flow similar to that of the outdoor unit being installed in the room and
that can compensate any additional pressure loss in ventilation ducts (Fig. 18).
n Ensure a continuous and unobstructed air flow from outside, preferably using sufficiently large air intakes
located immediately opposite if possible (Fig. 18).
n Comply with any regulations and conditions affecting the statics of the building. If necessary, fit acoustic
installation.
Fig. 18: Outdoor installation inside buildings
K: Cold fresh air W: Warm air 1: Chiller 2: Additional fan 3: Air shaft
34
A
B
C
D
E
A
B
C
D
E
Minimum clearances
The following illustrations indicate the minimum clearances for trouble-free operation of the equip­ment.
The protective zones serve to provide unhindered air intake and outlet, as well as providing suf room for performing maintenance and repairs and preventing the unit from being damaged.
ficient
Minimum clearances (all measurements in mm)
KWE 150-220 KWE 250-440
A 1000 1000
B 1500 1000
C 1000 1500
D 1500 1500
E 500 2500
Fig. 19: Minimum clearances KWE 150-220
Fig. 20: Minimum clearances KWE 250-440
35
A
REMKO KWE

6 Installation

6.1 Unit installation

NOTICE!
Installation should only be performed by author­ised specialists.
Perform the unit installation as follows:
1. Install the vibration dampers (accessories) under the unit / medium storage tank (acces­sories).
2. Attach the unit to the building where structur­ally permitted.
3. Ensure that structure-borne sound is not transferred to parts of the building.
4. Connect the medium piping.
Disassembly of the transport pallets
The units are supplied with transport pallets for the purpose of transportation. Remove these before installation.
Connection of the medium piping
n The connection of the lines on-site takes place
on the front side of the unit.
n For the purpose of servicing, connections must
be equipped with shut-of medium flow rate adjusted using hydronic bal­ancing valves.
n Additional automatic bleed valves are to be
provided in the supply and return flow at the installation’s highest point.
n The medium piping may not exert any struc-
tural load on the unit.
n The line connections may not generate any
thermal or mechanical stresses on the unit. If necessary cool the piping or support with the second tool.
n If the unit is at first to be operated with only a
part of the entire system, the medium flow rate for the missing system components is to be simulated using a pipe leg regulating valve.
n The pipe sizing is to be designed so that the
flow rate does not fall below the required min­imum flow volume.
A permanently large medium flow rate must be ensured to realise the minimum flow volume.
f valves and the
A: Transport pallet
36
Installation diagrams
2
1
P
P
3
Fig. 21: Installation diagrams KWE 150-220
1: Standard design 2: Standard pump 3: Standard pump and storage tank
37
2
1
P
P
P
3
REMKO KWE
Fig. 22: Installation diagrams KWE 150-220
1: High-pressure or high-performance pump 2: High-pressure or high-performance pump with
storage tank
3: Standard pump and external medium storage
tank (hydraulic compensator)
38
2
1
3
P
P
P
Fig. 23: Installation diagrams KWE 250-440
1: Standard design 2: Standard pump 3: Standard pump and storage tank
39
2
1
3
P
P
P
REMKO KWE
Fig. 24: Installation diagrams KWE 250-440
1: High-pressure or high-performance pump 2: High-pressure or high-performance pump with
storage tank
3: Standard pump and external medium storage
tank (hydraulic compensator)
40
Minimum / maximum flow volume
The circulation pump of the chiller generates a constant medium flow rate; the result is a loss of pressure in the system and in the chiller
The differential pressure switch in the chiller meas­ures the medium pressure loss over the evaporator and switches the unit off if the flow rate drops below the minimum medium volume.
The medium flow rate limit may likewise not be exceeded (maximum flow volume).
A 3-way valve with bypass and a hydraulic com­pensator to establish a primary and secondary cir­cuit or a volume-dependent bypass are necessary to ensure a constant medium flow rate.
Minimum medium volume, per unit
As a consequence of the adaptive controller a storage tank is not mandatory. However, the flow rate shall not drop below the minimum medium volume in order to ensure trouble-free operation of the unit.
.
Medium piping
Medium piping can be made of copper, steel or plastic. T lined fittings should be used.
When designing the layout, the large medium flow rates in cold water systems, high pressure losses in connection with water-glycol mixtures and the chiller's minimum flow volume must be taken into account.
The lines are to be insulated against vapour diffu­sion and, if necessary, the current German Energy­Savings-Ordinance (EnEV) must be observed. UV resistance must be realised outdoors.
Pressure and temperature displays
The pressure and temperature displays to be installed on-site at the intake and outlet serve to set the medium flow rate. The display should be able to be shut off.
Temperature sensors are located in the chiller's medium inlet and outlet. Sensor values can be queried via the controller.
o minimise pressure losses, only stream-
NOTICE!
The product and safety data sheets of the glycol type used must be observed during use and disposal.
NOTICE!
Use the required type and mix ratio appropriate for the application area to ensure the freezing point.
To adjust the circulation pump, we recommend that a main hydronic balancing valve is pro­vided in the vicinity of the unit.
Valves for hydronic balancing
The calculated individual pressure losses in the pipeline network layout for each individual unit are adjusted to the entire system with hydronic bal­ancing valves to be provided by the customer. The nominal flow rates for the medium adjust to the values needed as a consequence of the pressure loss.
Anti-freeze protection (accessories)
A water glycol mix is generally used as the medium for a cold water system. Depending on the use to which the glycol type and quantity is put, the vis­cosity changes, the loss in pressure increases and the unit's cooling or heating capacity reduces. All system components must be approved for use with glycol.
As a rule, the addition to the water of ethylene glycol, in a proportion of 34%, with inhibitors for corrosion protection is recommended. This con­centration ensures anti-freeze protection to -20 °C; at lower temperatures, an ice porridge forms which has no explosive effect.
The toxicologically harmless propylene glycol should be used if there is a risk that the medium can come into contact with drinking water or food stuffs. To inhibit the explosive effects, a proportion of 38% is necessary as a rule.
41
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Off
1 x
!
Main menu 7/8
E.Data logger
F.Board switch
G.Service
+
!
Service menu 6/7
e.BMS config
f.Service settings
d.Working hours
+
Password entry
+
x 4
!
Service menu 3/4
b.Probe adjustment
c.Thermoregulation
a.Working hour set
Service menu 3/4
b.Probe adjustment
c.Thermoregulation
a.Working hour set
REMKO KWE
Frost
Glycol
con-
tent
Vol. % ° C
20 -9 0.981 0.988 1.012 1.040 1.19
35 -21 0.971 0.982 1.018 1.090 1.35
40 -26 0.968 0.981 1.019 1.105 1.51
*) We recommend using an ethylene glycol mixture. Observe the safety and product data sheets for the type of glycol used.
Configuration anti-freeze protection parameters
It can be necessary to reconfigure the anti-freeze protection parameters when using a water-glycol mixture. Adjustment is only possible after pass­word input. For this purpose, please contact REMKO.
Perform the configuration as follows:
protec-
tion
+-2 °C
0 0 1 1 1.012 1 1
capacity
Correction factors when using a mixture of glycol *) and water
Cooling
K
L
Compressor capacity
K
P cooling
K
P heating
Volume flow Pressure lossCooling Heating
K
V
K
D
Call up the main menu.
Select the “Service” menu.
Select the submenu “f. Service setting”.
Enter the 4-digit password.
42
+
!
Service menu 2/7
Thermoreg. Gfc16
Service menu 2/7
Thermoreg. Gfc16
Primary circuit
Primary cir.antifreeze
°C
Primary cir.antifreeze alarm diff.: 3.0°C
alarm setp.: 4.0
+
!
Service menu 2/7
Thermoreg. Gfc16
Service menu 2/7
Thermoreg. Gfc16
Primary circuit
Primary cir.antifreeze
°C
Primary cir.antifreeze
°C
alarm setp.: -15.0
alarm diff.: 3.0
+
!
Service menu 2/7
Thermoreg. Gfc16
Service menu 2/7
Thermoreg. Gfc16
Primary circuit
Primary cir.antifreeze
°C
Primary cir.antifreeze
°C-
alarm setp.: -15.0
alarm diff.: 4.0
2
1
4
3
Open the window “c. Thermal regulation”.
Set the frost protection alarm value.
The unit's standard equipment includes one dia­phragm expansion vessel. The preliminary pres­sure must be set on the system; an increase in volume or
, in the event of the realisation of a cooling-heating system, the installation of another diaphragm expansion vessel may be necessary.
Compensators
Compensators are used to connect lines to the unit to prevent vibration in the chiller from transmitting to other system components.
1: Static fastening 2: Shut-off valve 3: Compensator 4: Connection KWE
Set the value for the alarm difference. If the differ­ence is exceeded, the alarm is reset.
This completes the configuration.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations during standstill because of temperature changes, diaphragm expansion vessels filled with nitrogen (moisture neutral) must be integrated in the system.
Safety valves
Safety valves limit excess operating pressure due to excess warming or overfilling of the operating medium. The valve outlet requires unobstructed draining into a drain line. Applicable local disposal ordinances must be observed if glycol is used. The unit's standard equipment includes one safety valve.
Shut-off valves
As a rule, in cold water systems, shut-off valves with full admission should be used. For the pur­pose of servicing, medium inlet and medium outlet must be equipped with shut-of
f valves (if necessary
safety valves).
Air bleeding valves
The unit has manual air bleeding valves. The unit can be bled separately after the system has been filled. Automatic bleeding valves must also be installed at the highest point in the collector line.
NOTICE!
Glycol tolerant air bleeding valves are neces­sary when using media that contain glycol.
43
2
1
REMKO KWE
Fill and drain connection
A connection should be provided in an area safe from frost for the draining of pipe lines (especially if water is used as a medium). Applicable local dis­posal ordinances must be observed if glycol is used.
Dirt trap
A rinsable dirt trap must be installed upstream from the unit intake. The mesh size should not be less than 10 mesh/cm2. Shut-of installed upstream and downstream from the dirt trap.
NOTICE!
Improperly installed or missing dirt traps can cause fouling of the plate heat exchanger
External medium storage tank
If, for example, the necessary capacity of the cold water outlet is significantly less than the cooling capacity generated by the chiller, an increase in the medium content is recommended. As an example, the medium piping can be oversized or an additional storage tank installed to increase compressor operating time. A storage tank should, as a rule, be provided if the minimum medium volume is not reached.
f valves should be
.
7 Condensate drainage
connection and safe drainage
Condensate drainage connection
If the temperature falls below the dew point, con­densation will form on the finned condenser during heating mode.
A condensate tray should be installed on the underside of the unit to drain any condensate.
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of the customer proof insulation.
n When operating the unit at outdoor tempera-
tures below 4 , care must be taken that the condensate drainage line is anti-freeze pro­tected. The lower part of the housing and con­densate tray is also to be kept frost free in order to ensure permanent draining of the con­densate. If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the line is durably leak tight.
. If necessary, fit vapour-diffusion-
NOTICE!
Malfunctions can result if the flow rate drops below the minimum medium volume.
1: Condensate tray 2: Condensate drainage
Safe drainage in the event of leakages
Local regulations or environmental laws, for example the German W can require suitable precautions to protect against uncontrolled drainage in case of leakage to provide for safe disposal of escaping air conditioning fluid or hazardous media.
ater Resource Act (WHG),
44

8 Electrical wiring

8.1 General connection and safety instructions

DANGER!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
n The power supply is made at the chiller; a con-
trol line to the indoor unit is not necessary.
n An all-pole separating switch, which discon-
nects individual phase conductors in the event of a malfunction, must be installed in the supply line upstream from the unit.
n Electrical wiring must be carried out as fixed
connections in accordance with the applicable regulations!
n Check all terminal points for stability. n The supply line must be adequately insulated
on-site and the voltage drop may not exceed permissible values.
n Make sure that the electrical system is ade-
quate for the operation of the unit and can supply the operating current necessary for other units already installed.
n Determine before installation, when connecting
to existing system components, whether the unit's service connection is adequately sized for the unit's rated power consumption.
n The connection of the units must always be
carried out with adequately sized, low-resist­ance earth conductors, and, if necessary, car­ried out several times (especially with plastic pipes).
n When installing the units on flat roofs, lightning
protection measures may be necessary.
n All electrical connections such as network
supply, cable remote control etc. must be car­ried out in the unit's switch cabinet.
n The lines to be installed are to be fed into the
switch cabinet through the cable glands pro­vided.
n An electrician must determine the sizing and
selection of the fuses and the cross section of the lines to be installed. Note that starting cur­rent max. may be up to 10 times nominal cur­rent
Carry out the following electrical wiring:
n Connection to the power supply n Possible enabling contact for the set mode or
standby.
n Possible operating mode contact for cooling or
heating mode (units with HP function).
n Possible connection of a winter pressure con-
troller (accessory).
n Possible connection of crankcase heating
(accessory).
n Possible connection of cabled remote control
(accessory).
n Possible connection of a heater for anti-freeze
protection medium (accessory, factory installa­tion only).
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. T
Power supply
The unit requires a fixed three phase current con­nection. The mains power supply is to be con­nected to the L1, L2, L3, N and PE terminals.
ighten as required.
.
45
2
1
XU
XU-9
XU-5
XU-4
XU-3
XU-2
XU-11
XU-10
XU-6
REMKO KWE

8.2 Unit connection

Proceed as follows to connect:
1. Open the control box covers by removing the fixing screws and lifting of
2. Feed the voltage-free cable through the glands into the switch cabinet and clamp the cable to the strain relief.
3. Then connect the cable in accordance with the connection diagram.
4. Ensure a correct rotating field.
5. Mount all removed parts.
f the covers.
General alarm signal (standard equipment)
The connection of a potential-free general alarm signal, for example, for signalling or for further pro­cessing to a building control system is possible as standard equipment. Use the respective connec­tion diagram for this purpose and pay attention to the maximum contact loads.
Fig. 26: External potential-free contacts
1: Unit 2: User
2-3 = Enable operation / disable (potential-free)
4-5 = External alarm code (max. 230V~, 2A)
Fig. 25: Control box cover KWE 250-440
External enabling contact Operation / Standby
In addition to being operated with the controller or the cable remote control, the unit can be switched on (normal operation) and switched of via an external potential-free contact (program­mable as normally-open or normally-closed).
The controller must be configured if a normally­open contact is used for the external enable (see section “External enabling configuration”).
This enable is used for example to realise standstill times at night or for the activation / deactivation of a building control system.
f (Stand-By)
Winter pressure controller (accessory)
It serves for the expansion of the operating range in cooling mode from +15 to -15. The set con­sists of crankcase heating and the pressure con-
. Use respective installation instructions for
troller this purpose.
Crankcase heating compressor (standard / accessory)
The heating serves for the expansion of the oper­ating range in cooling mode from +15 to -5. For this purpose, use the respective installation instructions.
Cabled remote control (accessory)
The cable remote control is used, for example, for the querying, programming or operation of the unit from a remote location. Use respective installation instructions for this purpose.
46
External enabling configuration
!
12:22 19/02/18 Unit:01
Ou tside T: - - -- C° Sy stem T: 1 9.5 C°
STATUS: Off
1 x
!
Main menu 8/8
F.Board switch
G.Service
H.Manufacturer
+
!
Manufacturer menu 2/5
b.I/O Configuration
c.Factory settings
a.Configuration
+
Password entry
+
x 4
!
I/O Config. Hb04
Digital inputs
ID07
ID08 Remote On/Off: NC
General alarm: NC
+
!
I/O Config. Hb04
Digital inputs
ID07
ID08
General alarm: NO
Remote On/Off: NC
+
!
I/O Config. Hb04
Digital inputs
ID07
ID08
General alarm: NO
Remote On/Off: NO
With the use of a normally open contact as an external contact, a controller parameter must be reconfigured. The parameter “Id08” must be switched from “NC” to “NO”. If this does not happen, the controller does not recognise the external contact as a normally closed contact. The “Id08” parameter can be changed in the “I/O Con­figuration” menu item. The following program sequence must be programmed.
Enter the 4-digit password.
Call up the main menu.
Select the following submenu:
Set the alarm contact.
Set the external enabling contact.
Open the window “b . I/O Configuration”.
47
This completes the configuration.
REMKO KWE

8.3 Electrical components

Electrical components and safety equipment
Pressure switch cooling cycle HP and LP
There is a high pressure switch (HP) in the hot gas line within the cooling circuit to for switching of chiller in the event of insufficient heat dissipation. A low pressure switch (LP) in the suction pipe or in the compressor switches off the chiller if the fill level for the refrigerant is too low.
Differential pressure switch
The differential pressure switch is installed parallel to the evaporator in the medium cycle. It measures the pressure differential between the inlet and outlet pressure and switches the unit off when the flow rate drops below the minimum flow volume or with extremely large medium flow rates.
Condenser fan thermal contacts
The condenser fan's thermal contacts prevent overheating of the motors.
f the

9 Leak testing

The leak test is carried out after the connection has been made.
1. Flush the system twice with tap water
2. Clean the sieve insert on the dirt trap.
3. Fill the system with water again and bleed
the unit at the manual bleed valves.
4. Adjust the test pressure to at least 200 kPa (2.0 bar).
5. Check the connections after a period of at least 24 hours for leaking water visible, the connection has not been estab­lished properly. Tighten the connection or establish a new connection.
6. After a successful leak test, remove the excess pressure from the medium piping if a water-glycol mixture is used or adjust the non-circulating pressure to the required system pressure.
.
. If water is
Compressor thermal contact
The thermal contact is located within the com­pressor and limits its hot gas end temperature.
Phase sequence relay
The phase sequence relay controls the direction of rotation for the power supply. The controller will not be enabled if the direction of rotation is wrong.
Probe B4 medium inlet
The probe is located at the unit's medium inlet (system return flow). It serves to capture the cur­rent temperature to control the target value.
Probe B7 medium outlet
The probe is located at the unit's medium outlet (system inlet). It serves to capture the current tem­perature and regulate the anti-freeze protection temperature.
48
A
A
B
C

10 Before commissioning

Filling the system
The system is filled at the customer-provided filling and draining connections.
Anti-freeze protection for the medium
If a water-glycol mixture is used, it is to be pre­mixed before being put in the system. The desired concentration is then to be checked.
Unit preliminary pressure for the medium
The preliminary pressure of the medium (without operation of the circulation pump) varies within the system. From the highest point, the pressure increases by approx.10 kPa (0.1 bar) per metre dif­ference in altitude (geodetic altitude). The value measured at the highest point is identified as the non-circulating pressure.
The position of the unit in the system is decisive in the calculation of the unit's preliminary pressure (pressure of the manometer on the unit installed by the customer). The pressure must be set to at least 70 kPa (0.7 bar).
n If the unit is positioned at the lowest point in
the system, the unit preliminary pressure (=standstill pressure+geodetic system altitude) must be set to at least 70 kPa (0.7 bar) + 10 kPa (0.1 bar) x geodetic system altitude.
n If the unit is positioned at the highest point in
the system, the unit preliminary pressure (=non-circulating pressure) must be set to at least 70 kPa (0.7 bar). Please note that the system pressure at the lowest point is increased by the geodetic system altitude! (See Fig. 27)
Fig. 27: Unit preliminary pressure
A: Unit preliminary pressure B: Geodetic system altitude C: Non-circulating pressure
Bleeding the system
n Air may still be in the pipe lines after the leak
testing. This is carried during operation of the circulation pump to the automatic bleeding valves or to the cold water drain. It is neces­sary to bleed again here.
n Also bleed the pump if necessary. n The non-circulating pressure must then be
adjusted to the required system pressure.
NOTICE!
During manual bleeding, any glycol mixtures which escape must be disposed of separately Do not feed them into the condensate tray!
.
49
REMKO KWE
Diaphragm expansion vessel
n The preliminary pressure for the diaphragm
expansion vessel must be adjusted individually to the system layout, the volume of the medium and the installation site.
n If necessary
this, the manufacturer's authorisation is required.
Valves for hydronic balancing
n The calculated excess pressure in the pipe net-
work layout at the individual cold water outlets must be adjusted with the hydronic balancing valves.
Safety valve
n The safety valves and their correct function
must be checked.
n The drain line for the valves is to be checked
for function and leak tightness.
n If necessary
this, the manufacturer's authorisation is required.
, change the installation site. For
, change the installation site. For
Checking the cooling circuit
n Checking the cooling circuit for adequate oil /
refrigerant.
n Checking the cooling circuit for leak tightness. n Checking the medium cycle. n Setting the circulation pump's nominal flow
rate.
The units are equipped with a phase sequence relay which prevents the operation of the con­troller if the direction of rotation of the electric power supply is wrong. The rotary field must be replaced if the controller is not activated during commissioning of the unit.
Additional checks
General checks
n Checking that minimum clearances are correct. n Checking the possibility of transferring cooling
and heating capacity via the cold or hot water consumer (indoor unit).
Electrical checks
n Checking electrical connections for correct
phase sequencing.
n Function check of the cooling mode / heating
mode enable (option).
n Function check of the enable Operation /
Standby (option).
Checking the medium cycle
n Checking the circulation pump for freedom of
movement.
n Checking whether all valves are open. n Checking the medium cycle. n Setting the circulation pump's nominal flow
rate.
50

11 Commissioning

NOTICE!
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued.
NOTICE!
Observe the manuals for the unit and all other components when commissioning the entire system.
Function test for cooling operating mode
1. Switch the power supply on.
2. Open all shut-of
3. Switch on the chiller and the corresponding
circulation pump. The outlet temperature must be between +4 and +18 °C.
4. Switch the unit on and select the cooling operating mode. If the return temperature is warmer than the setting, the compressor dis­play will flash and the compressor will begin to work after approx. 3 to 5 minutes.
5. Please note that the inlet temperature at the nominal flow rate of the medium lies approx. 5 K below the return temperature.
- If the inlet temperature falls below the fac­tory setting of 4 °C, an alarm triggers. If this is the case, a higher return temperature must be selected. If the spread is too great or too small, the medium flow rate must be checked.
- The circulation pump starts and the con­troller checks the medium flow rate via the dif
ferential pressure switch. If the volume is insufficient, a fault shut-off will be carried out and the cooling cycle will not be enabled.
6. Measure and record all the required values in the commissioning report and check the safety functions.
7. Check the unit control system using the func­tions described in the "Operation" chapter
f valves if necessary.
.
Final tasks
n Mount all removed parts. n Familiarise the operator with the system.
The delivery of the unit from the factory takes place with standard parameterisation of the output control. If necessary during commis­sioning a system-specific parameterisation must be carried out by authorised personnel.
51
REMKO KWE

12 Shutdown

Temporary shutdown
1. Shut down the indoor units using the remote
control.
2. Switch the unit of the chiller (or using the remote control).
3. Check the percentage concentration of glycol.
4. Check the unit for visible signs of damage and clean it as described in the “Care and maintenance” chapter
5. As much as possible, cover the unit with a plastic foil to protect it against the weather
f via the internal controller in
.
.
NOTICE!
If only water and not a mixture of water and glycol is used, in regions subject to freezing, water must be drained from components when these are at standstill. The drained water volume must be replaced when components are put back into operation!
Permanent shutdown
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
52

13 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly as detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Trouble­shooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Possible causes Checks Remedial measures
Display is not illuminated.
. However, if malfunctions should occur, please check the functions
Check the power connec-
tions on the general supply No power supply, power failure, device fuse / main switch switched of tive
f / defec-
terminals and the voltage
values. Check the unit fuse,
the main switch and the
fuses on the secondary side
of the additional trans-
former.
The unit does not start
The unit works at reduced cooling capacity
The display lights up and shows “Phase sequence error”.
Display shows status: “Off”.
The controller emits an acoustic signal.
The compressor icon is dis­played, but the unit does not start.
Thermal load too high.
Inlet temperature too high.
Air in the medium cycle.
Condenser temperature too high.
Incorrect phase sequence. The phase sequence relay did not issue an enable signal.
The unit is deactivated. Change the operating status in the “A. On / Of Unit” submenu
One or more protective devices have tripped. A malfunction is present.
Compressor or compressor contactor defective.
Thermal load was increased.
Return flow temperature set too high.
Medium cycle not bled, no automatic bleeding valves installed.
Slats dirty, exposed to strong sunlight.
f
Swap the phase conductors
of the power supply on the
terminal block on the con-
trol panel.
Check error messages, rec-
tify the malfunction,
acknowledge the malfunc-
tion (see chapter “Error indi-
cation”).
Have specialist replace
contactor or compressor
If possible, reduce the
thermal load.
Reduce return temperature.
Manually bleed or install
automatic bleeding valves
at the highest point.
Clean fins, provide shade
for the unit, adhere to oper-
ating limits.
.
Pulse mode because of too little demand.
53
System may be over­dimensioned
Increase medium flow rate
with the installation of a
storage tank.
REMKO KWE
Malfunction Possible causes Checks Remedial measures
Drop formation at connec­tion points of the pipeline.
Medium outlet
Condensate formation
Operational malfunctions (continued)
Mal­function
ALA04 Medium inlet probe defective Check resistance at B4 Replace defective probe.
ALA06
ALA07
ALA08
ALA09
Possible causes Checks Remedial measures
Outside temperature probe fault (optional)
Medium outlet sensor defec­tive
Suction gas temperature probe fault (optional)
Hot gas temperature probe fault (optional)
Leakage of the joint Seal the joint.
Uninsulated cables or com­ponents, defective insula­tion.
Check resistance at B6 (optional)
Check resistance at B7 Replace defective probe.
Check resistance at B8 (optional)
Check resistance at B9 Replace defective probe.
Attach or repair the insula­tion.
Replace defective probe.
Replace defective probe.
ALA11 High-pressure probe fault Check resistance at B11 Replace defective probe.
ALA12
ALB01
ALB02
ALB03
ALB04
ALC01
ALP02
ALP03 Medium flow disturbance
Low-pressure probe fault (optional)
High-pressure switch, high­pressure alarm
High-pressure probe high­pressure alarm
Low-pressure probe low-pres­sure alarm
Low-pressure switch low-pres­sure alarm
Compressor overload (optional)
Overload circulation pump (optional)
Check resistance at B12 (optional)
Condenser lined, dirty or exposed to excessive sun­light? Condenser fan defec­tive?
Cooling cycle OK? Check the flow sensor
Motor overload protection switch triggered? Compressor power consumption too high?
Motor overload protection switch triggered? Circulation pump power consumption too high?
Check: Air in the medium piping -Open shut-of Medium pressure -Circulation pump capacity -Switching behaviour of the differential pressure switch -Medium flow rate
f devices -
Replace defective probe.
Clear condenser, clean, shade, have condenser fan checked by specialist per­sonnel.
Have the cooling cycle checked by a specialist com­pany
, replace the flow sensor.
Check motor overload protec­tion switch (setting range), have the compressor checked by a specialist company
Check motor overload protec­tion switch (setting range), have the pump checked by a specialist company
-Bleed the medium cycle
-Open shut-off valves
-Raise medium pressure
Have the circulation pump, dif­ferential pressure and medium flow rate checked by a spe­cialist company.
.
.
54
Mal­function
ALF01 Fan motor overload
ALT01 Compressor maintenance
ALT04 Pump maintenance
ALU02 Frost protection malfunction
ALD01 EEPROM malfunction
ALG01
Possible causes Checks Remedial measures
Motor overload protection switch triggered? Fan power consumption too high?
Compressor maintenance interval has been reached
Pump maintenance interval has been reached
Inlet temperature lower than 4 °C?
Mains current has incorrect direction of rotation
Check the phase sequence relay
Check motor overload protec­tion switch (setting range), have the fan checked by a specialist company
After maintenance by a spe­cialist company operating hours. See chapter “Resetting the operating hours”.
After maintenance by a spe­cialist company operating hours. See chapter “Resetting the operating hours”.
Raise return flow temperature, increase medium flow rate, adjust antifreeze temperature to the operating medium.
Swap the phase conductors of the power supply on the ter­minal block on the control panel.
.
, reset the
, reset the
55
REMKO KWE
Error indication by code
Mal­function Possible causes
ALA04
ALA06
ALA07
Medium inlet probe defective
Outside temperature probe fault (optional)
Medium outlet sensor defective
Suction gas tempera-
ALA08
ture probe fault (optional)
ALA09
ALA11
ALA12
ALB01
ALB02
Hot gas temperature probe fault (optional)
High-pressure probe fault
Low-pressure probe fault (optional)
High-pressure switch, high-pressure alarm
High-pressure probe high-pressure alarm
Reset Input type
l
l
l
l
l
l
l
l l l
l
5)
ReactionAuto. 1)Man. 2)Digi. 3)Ana. 4)Soft.
l
l
l
l
l
l
l
System deactivated
Dynamic setting disa­bled (optional)
System deactivated
System deactivated
System deactivated
System deactivated
System deactivated
System deactivated
l
System deactivated
ALB03
ALB04
ALC01
ALP02
ALP03
Low-pressure probe low-pressure alarm
Low-pressure switch low-pressure alarm
Compressor overload (optional)
Overload circulation pump (optional)
Medium flow disturb­ance
ALF01 Fan motor overload
ALT01
Compressor mainte­nance
ALT04 Pump maintenance
ALU02
Frost protection mal­function
ALD01 EEPROM malfunction
Mains current has
ALG01
incorrect direction of rotation
l
l
System deactivated
l l
l l
l l
l l
l l
l
l
l
l
System deactivated
System deactivated
System deactivated
System deactivated
System deactivated
Only alarm signal
l
Only alarm signal
l
System deactivated
l
System deactivated
l
System deactivated
l
1)
Auto. = automatic,
2)
Man. = manual,
3)
Digi. = digital,
4)
Ana. = analogue,
5)
Soft. = Software parameters
56

14 Care and maintenance

Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
DANGER!
Prior to performing any work, ensure the equip­ment is disconnected from the voltage supply and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
n Clean the fins on the unit prior to long shut-
down periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an appropriate specialist firm.
This enables you to ensure the operational reli­ability of the plant at all times!
NOTICE!
Statutory regulations require a leak test for the cooling cycle dependent on the refrigerant capacity. Inspection and documentation of the work performed is to be carried out by specialist technicians.
Type of task
Checks / maintenance / inspection
General
Check voltage and current
Check function of compressor / fans
Dirt on condenser / evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
see note
Commis-
sioning Monthly Half-yearly Yearly
l
l
l
l l
l
l
l
l
l
l
l
l
l
l
l
l
l
1)
57
REMKO KWE

15 Index

A
Air bleeding valves ...................... 43
Anti-freeze protection .................... 41
C
Cabled remote control ....................46
Care and maintenance ................... 57
Characteristic curves ............ 20,
Commissioning ......................... 51
Compensators ..........................43
Compressor thermal contact ............... 48
Condensate drainage connection ........... 44
Condenser fan thermal contacts ............ 48
Configuration anti-freeze protection parameters 42
Connection of the medium piping ........... 36
Cooling capacity .................. 16, 17, 18
Crankcase heating, compressor ............ 46
Customer service ....................... 53
21, 22, 23
D
Description of the unit .................... 24
Diaphragm expansion vessel .............. 50
Diaphragm expansion vessel (MAG) ......... 43
Differential pressure switch ................ 48
Dirt trap ............................... 44
Disassembly of the transport pallet .......... 36
Disposal of equipment .....................6
Drain connection ........................ 44
E
Electrical components .................... 48
Electrical components and safety equipment .. 48
Electrical unit connection ..................46
Electrical wiring ......................... 45
Environmental protection ...................6
Error indication by code ...................56
External enabling configuration ............. 47
External enabling contact Operation / Standby . 46
External enabling, configuration ............ 47
External medium storage tank ..............44
F
Fill and drain connection .................. 44
Fill the system .......................... 49
Filling the system ....................... 49
Frost protection parameters, configuration .... 42
Function test for cooling operating mode ......51
G
General alarm signal ..................... 46
H
Hydraulic unit construction ................ 25
I
Installation .............................36
Installation diagrams ............ 37, 38, 39, 40
Installation location, selection .............. 32
Installation materials ..................... 32
Intended use ............................ 5
L
Leak testing ............................48
M
MAG - Diaphragm expansion vessel ......... 43
Maintenance ........................... 57
Malfunctions
Checks .............................53
Possible causes ...................... 53
Remedial measures ................... 53
Medium piping ..........................41
Medium piping, connection ................ 36
Medium storage tank, external ............. 44
Minimum / maximum flow volume ........... 41
Minimum clearances ..................... 35
Minimum medium volume, per unit .......... 41
O
Operational malfunctions ...............53
, 54
P
Phase sequence relay ....................48
Power supply .......................... 45
Pressure and temperature displays ..........41
Pressure loss .......................... 20
Pressure switch cooling cycle HP and LP ..... 48
Probe B4 medium inlet ................... 48
Probe B7 medium outlet .................. 48
R
Refrigeration unit construction ..............25
S
Safe drainage in the event of leakages ....... 44
Safety
Dangers of failure to observe the safety
notes ............................... 4
General ............................. 4
Identification of notes ................... 4
Notes for inspection .................... 5
Notes for installation ....................5
Notes for maintenance .................. 5
Personnel qualifications ................. 4
Safety notes for the operator ............. 5
Safety-conscious working ................4
Unauthorised modification ...............5
Unauthorised replacement part manufacture . 5
Safety valve ........................... 50
Safety valves ...........................43
Selecting the installation location ........... 32
Shut-off valves ......................... 43
Shutdown
Permanent .......................... 52
Temporary .......................... 52
Sound pressure level .................... 19
System layout .......................... 24
58
System pressure available,
High-performance pump ................23
High-pressure pump ...................22
Standard pump ...................... 21
System pressure, available
High-performance pump ................23
High-pressure pump ...................22
Standard pump ...................... 21
T
T
ransport pallets ........................ 36
Troubleshooting and customer service ....... 53
U
Unit description ......................... 24
Unit installation ......................... 36
V
V
alves for hydronic balancing ........... 41, 50
W
Warranty ............................... 5
Winter pressure controller (accessory) ....... 46
59
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 6 06-0 Telefax +49 5232 6 06-260 E-mail info@remko.de Website www.remko.de
Loading...