REMKO ETS300 User Manual

Page 1
REMKO TANK SYSTEMS
ETS 300 Hot water tank
Operation · Technology
Edition GB-C05
Page 2
Page 3
Contents
Safety notes
Environmental protection and recycling
Warranty
Intended use
Description
Operation
Decommissioning
Care and maintenance
Installation instructions for qualified personnel
Installation
Electrical connection
Before commissioning
Commissioning
4
5
5
5
5-6
6
6
6-7
8-9
10-13
14
14
15
Made by REMKO
Unit dimensions
Technical data
These original instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
16
17
3
Page 4
REMKO ETS 300
Safety notes
Carefully read the operating manual before placing the unit in service for the first time. It provides useful tips notes and hazard warnings to prevent injury and material damage. Failure to follow the directions in this manual can endanger persons, the environment and the equipment itself and will void any claims for liability.
■ Keep this manual in the vicinity
of the units.
■ Only qualified personnel may
set up and install the units and components.
■ The set-up, connection, and operation
of the unit and its components must be in accordance with the operating conditions stipulated in this manual and comply with all applicable local regulations
■ Modification of the units
and components supplied by REMKO is not permitted and can cause malfunctions.
■ Units and components may not
be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
■ The electrical supply is to be adapted
to the requirements of the units.
■ The operational safety of units
and components is only assured if they are fully assembled and used as intended. Safety devices may not be modified or bypassed.
■ Do not operate units or components
if there are obvious defects or signs of damage.
■ The units and components must
be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
■ Installation, repair and maintenance
work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the equipment is disconnected from the power.
■ Take appropriate precautions when
performing installation, repair or maintenance work or cleaning the unit to make sure the unit does not pose a danger to persons.
4
Page 5
Environmental protection and recycling
Disposing of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposing of the components
The manufacturing process for the units is subject to continuous quality control. Only high-grade materials are processed, the majority of which are recyclable. Help protect the environment by only disposing of the components in accordance with local regulations and in an environmentally safe manner, e.g. through authorised disposal and recycling specialists or at collection points.
Warranty
The warranty conditions are listed in the "General terms and conditions". Please contact your direct contractual partner about this first instance.
Intended use
The tanks are used for the storage of hot water. Any different or additional use is a non­intended use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
Description
The tanks are used for the storage of hot water. The tank volume can be adapted to your particular needs by connecting several tanks to form batteries. The tank is enamelled and has a double­wound, smooth-pipe heat exchanger with an especially large heat exchanger surface area of 2.6 m2. In the inside tank a magnesium false anode is installed in accordance with DIN 4753. The insulation of the hot water storage tank ETS 300 is comprised of a 50 mm thick PUR insulation (CFC, HCFC and HFC free). The tank is encased in a foil casing (delivered separately for transport protection). A blank flange cover D180 is installed for the retrofitting of a finned tube heat exchanger or flange heating cartridge (legionella protection).
5
Page 6
REMKO ETS 300
The tank has connections for circulation (3/4" IG) as well as a cold water supply and hot water outlet (1" IG).
Operation
Manual operation is not necessary.
Decommissioning
Temporary shutdown
1. If necessary, disconnect the electrical
connection of the flange heating cartridge at all poles.
2. Drain the tank in areas where it is at risk from frost and before the onset of winter.
3. After closing the shut-off valve in the cold water supply, the water is drained through the drain valve of the safety combination while all the hot water valves of the service water fixtures are open. Partial emptying is also possible through the safety valve in the expansion water funnel (drip catcher). For this purpose the safety valve is turned to the "Test" position.
! ATTENTION
When placing the tank back into service, ensure that it is filled with water and that water which is free of bubbles is escaping from the valves!
Permanent decommissioning
Ensure that equipment and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
Care and maintenance
Care
■
Clean the units with a damp cloth. (adding, for instance, a liquid household cleaner). Do not use any caustic, abrasive or solvent-based cleaning products.
Maintenance
! ATTENTION
When emptying the tank, hot water may escape!
6
■
It is recommended that you take out a maintenance contract with an annual service from an appropriate specialist firm.
Page 7
NOTE
This will ensure that your equipment always operates reliably!
■
Regularly check the function
of the safety valve.
The expansion water amount at maximum heat (approx. 80°C) represents approx. 3.5% of the tank capacity. When the safety valve test knob is lifted or in the “Test” position, the water must flow unhindered out of the safety valve body into the drainage funnel.
! ATTENTION
This can cause the cold water supply and parts of the storage tank connection fitting to become hot!
If the tank is not heated or when warm water is removed, no water should be dripping from the safety valve. If this does occur, either the pressure in the water pipe is greater than the permitted value or the safety valve is defective. If the pressure in the water pipe is higher than permitted, a pressure relief valve must be used.
In hard water areas, the limescale which forms in the tank internal boiler and the floating deposits of limescale must be removed by a specialist after one to two years of operation. Cleaning is performed through the flange opening.
1.. Remove the heating flange.
2. Clean the tank.
3. Refit the flange, using a new seal. Tighten the bolts in a crosswise pattern to a torque of 20 Nm.
The special enamelled inner tank of the water heater must not come into contact with scaling solvent. Do not use a descaling pump!
4. Thoroughly rinse out the unit.
5. Observe the heating process as per initial operation.
The installed false anode must be checked by a specialist at least once every 2 years of operation and this inspection must be documented. If servicing tasks are performed, the cleaning and servicing flange should be opened, and the tank inspected for any infiltration or soiling.
Only with the use of an external current anode: The control lamp of the external current anode must be monitored regularly. The following applies: green = system OK red flashing = malfunction (in this case contact customer service). For a faultless function, the tank must be filled with water.
7
Page 8
REMKO ETS 300
Installation instructions for qualified personnel
General instructions prior to installation
■
Ensure that the area in which the unit is to be operated is free of frost and easily accessible for required maintenance, repairs and even for the possible replacement of the unit (e.g. avoid overly narrow thoroughfares and doorways).
■
When installing the tank in unusual locations, such as in lofts, residential units with floors that are sensitive towater, storerooms, etc. take account of the possibility of leaking water, and ensure that a facility is in place to catch the water, including appropriate drainage methods.
■
The unit may only be positioned and operated on level surfaces.
■
When planning the unit's installation surface and selecting the installation location, note the total weight of the tank, including the weight of the water (the nominal capacity), in order to ensure that the statics of the load-bearing surface are not exceeded.
■
Ensure proper clearance from firing systems.
■
Make sure that units with enclosures,
which are installed in small, tight
spaces or in suspended ceilings
have the connection block (water
and electric connections and heater
installation) still freely accessible and
that there us no buildup of heat.
■
Leave at least 500mm of space
free for the removal of the heating
flange.
Assembly
NOTE
Installation should only be performed by authorised specialists. Preparation of the hot water must be in compliance with the applicable standards.
■
Check the contents of the packaging for completeness and check the unit for visible transport damage. Immediately notify your contract partner of any deficiencies.
■
In the selection and/or sequence of the installation materials used for the plant, any possible electrochemical processes must be taken into consideration in accordance with the recognised good practices (mixed-metal installations!).
8
Page 9
The potential equalisation of the piping must take place in accordance with DIN 50927. This type of corrosion results in the formation of corrosion cells. Voltage is present in corrosion cells between the anode and cathode area. The processes are dependent on oneanother, however, their separation from one another can vary greatly. Corrosion cells can appear as a result of different potentials, as the case is with contact corrosion. Different metals are in conductive contact with one another through an ion-conducting medium (water). All metal plug-in (built-in) components with large metal surfaces (e.g. condenser plug-in heat pumps, fin-tube heat exchangers, electric heaters) must be electrically insulated from the tank. For the protection of the above­mentioned plug-in (built-in) components against the current-induced corrosion, we recommend installing a defined contact resistance of approx. 600 Ohm (insofar as it has not already been installed in the components at the factory).
■
When installing a fin-tube heat exchanger it must be absolutely ensured that the corrosion protection in the tank remains intact. Therefore, when a fin-tube heat exchanger is fitted, an appropriate external current anode or magnesium anode must be installed if the magnesium anode is removed with the flange plate from the tank.
■
The hot water tanks may not be transported with the fin-tube heat exchanger installed.
■
The unit must be assembled on site.
■
For all connecting sockets, ensure that the thread is fully engaged.
9
Page 10
REMKO ETS 300
Installation
General Information
■
If aggressive water is an issue, please
note that special models of the tank can be tested. (address all queries to your contractual partner)
■
In hard water areas, connect
a standard descaling device upstream of the tank.
■
Drinking water quality is required
for the proper operation of the hot water tank.
Units with electrically powered flange heating cartridges
Such units are equipped with a safety temperature limiter which stops heating the storage tank at a temperature of max. 130°C. The choice of connection components (connecting pipes, circulation, safety valve combination, etc.) must be such that, in the event of a malfunction of the temperature control, the connection components will withstand temperatures of 130°C, avoiding possible damage.
Water-side connection (pressure-tight)
The hot water heaters are pressure­tight tanks for which pressure-tight connections can be made. If the line pressure is higher, a customer­provided pressure reducing valve must be installed in the cold water supply. Only pressure-tight fittings may be used.
The component-tested safety equipment must be installed in the cold water line (see the diagram on the following page).
A type-examination tested safety group in accordance with DIN 1988 must be installed in the water connection of the cold water line (cold water supply) for closed hot water heaters.
The water connection may only take place through a tested diaphragm safety valve or a diaphragm safety valve/ connection fitting combination (not a piston valve) for pressure-tight tanks! A safety valve combination is comprised of a shut-off, testing, return, drain and safety valve with expansion water drain and is installed between the cold water supply and cold water feed of the tank in the sequence shown on the following page:
10
Page 11
Tank connection according to DIN 1988
Tank
Consumers
In order to ensure the faultless function of the connection fitting, it may only be installed in frost-protected rooms. The discharge of the safety valve must be open and observable and the discharge line from the drip catcher (expansion water funnel) must be routed to the sewer so that neither frost nor back-ups from dirt or the like can cause a fault.
There may not be a shut-off valve or any other type of flow restrictor installed between the safety valve and the cold water feed of the tank. The safety valve must be set to a triggering pressure which is below the nominal pressure of the tank.
Drain valve
Testing
Safety
valve
Backflow
preventer
After the conclusive connection of the tank, the cold water supply line must be rinsed out.
After the water connection is made and the bubble-free filling of the tank takes place, the connected fitting must be tested for function. When lifting or turning (venting) the safety valve test knob, the water must be able to flow out properly without being hindered by the expansion tank drain funnel. In order to check the return flow valve the shut-off valve is closed and no water may flow out of the open testing valve. The testing of the safety valve must take place in accordance with DIN 1988-8.
valve
Pressure reducing valve
Shut-off valve
If applicable:
11
Page 12
REMKO ETS 300
The operation of the tank takes place through the hot water valve of the service water fixture (mixing tap). Therefore, the tank is under continuous line pressure. In order to protect the internal boiler against excessive pressure when heating up, the accumulating expansion water is discharged through the safety valve.
The return flow valve prevents the return flow of the hot water into the cold water network during a pressure drop in the line and thereby protects the boiler from heating up without water.
With the shut-off valve the tank can be disconnected from the cold water network and thus its pressure and can be emptied through the drain valve if necessary.
Circulation connect
Due to significant energy loss, a circulation connection should be avoided when possible. If a highly branched service water network requires a circulation line, this must be well insulated and the circulation pump controlled via a timer and thermostat. The switching temperature of the thermostat should be kept low (45°C). The circulation connection piece has an external thread.
Flange installation port
Depending on the system design, flange heating cartridges or fin-tube heat exchangers can be attached at the boiler flange Ø180 (clear diameter Ø117 mm, hole circleØ150 mm, 8xM12).
■
Install the flange heating cartridges
in such a way that the sensor of the
temperature regulator is positioned
at the top.
■
First tighten the nuts by hand.
■
Then tighten the nuts,
in the sequence specified below, to
a torque of 20 Nm to max. 25 Nm.
Fitting the flange installation port
Flange ring
Seal
Supporting disc
Flange plate
12
Page 13
Central heating connection
Before being placed into service, the register must be flushed in order to remove any soiling (e.g. scale) from the heating circuit.
Tank with register
The registers (heat exchangers) built into the tank are suitable for connecting to a water heater at any pressure and temperature shown on the specification label of the hot water tank.
Forced circulation through a pump is required.
When installing a tank with a register, a shut-off member must be installed in the flow line to prevent back-heating into the heating circuit when the central heating and heat pumps are turned off or in the case of electrical operation.
Corrosion protection
The enamelled boiler is protected with a standard magnesium rod-type anode. This anode is self-consuming and therefore must be inspected every 2 years and replaced as necessary (for this purpose, see DIN 4753). A maintenance-free external current anode (accessory) can be installed on some models using a reducing threaded connector IG 5/4"-IG 3/4" (accessory).
Temperature display, temperature regulation for charging pump
With the installation of third-party control units it must be ensured that the boiler temperature cannot exceed 95°C during operation.
NOTE
Installation should only be performed by authorised specialists.
! ATTENTION
However, under no circumstances may the supply and return lines be blocked, as otherwise the water in the register will not have room to expand and there is a risk of damage to the heat exchanger!
13
Page 14
REMKO ETS 300
Electrical connection of the flange heating cartridge
■
The hot water tank must be filled
with water before being put into service.
■
A mains connection must be installed
and appropriately fused according to the circuit diagram affixed in the terminal box for the unit.
■
A residual current circuit breaker with
a tripping current of I∆N ≤ 30mA must be located upstream from the supply circuit.
■
All cables and wires to and from
the unit must be fixed in place.
■
The electrical installation must
have an upstream-connected isolating device for all poles, with a contact opening of at least 3mm. (e.g. in the form of a circuit breaker)
■
The electrical protection
of the equipment should be implemented according to the information provided in the technical data.
! ATTENTION
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
Before commissioning
Before being placed into service, the register must be flushed in order to remove any soiling (e.g. scale) from the heating circuit.
The smooth pipe heat exchanger (register) must be rinsed out properly before the initial installation is carried out (we also recommend the installation of a dirt filter). If the smooth pipe heat exchanger is not used while operating the tank (e.g. only electric heating), it must be filled completely with an appropriate glycol mixture in order to prevent corrosion from the accumulating condensation water. The filled glycol heat exchanger may not be closed on both sides after filling (temperature-based pressure expansion).
Before the warm water tank is connected to the mains electricity supply and put into service for the first time, it is vital that it is filled with water. During initial filling, the discharge valve must be open. The storage tank is fully filled, when water which is free of bubbles starts to run out of the discharge pipe of the valve.
14
Page 15
Commissioning
NOTE
Commissioning should only be performed and documented by specially trained personnel.
1.
Check all connections, even those
which were sealed at the factory (flange, anode sleeve), for leak­tightness.
2
.
Then check all pipes for any leaks
and, if necessary, fix them.
3
.
Test the safety group and valves
between the cold water supply and hot water tank for proper function.
During initial filling, the discharge valve must be open. The warm water tank is completely full when water, bubble free, runs out of the valve's discharge pipe.
Heating the water in the tank causes its volume to increase. While heating up, the expansion water generated in the internal boiler should drip out of the safety valve. This dripping is necessary to the function of the unit, and must not be prevented by retightening the valves.
4
.
Test the self-actuating shut-off of
the system, any installed electrical heating attachments and/or the boiler.
! ATTENTION
The warm water drain pipe as well as parts of the safety equipment may become hot.
Once the water has been heated successfully, the set temperature, the actual temperature of the water produced and that shown on any temperature indicator should be approximately the same.
15
Page 16
REMKO ETS 300
Unit dimensions
ETS 300
We reserve the right to modify the dimensions and design as part of the ongoing technical
Model
ETS 300 1797 610 263 985 1313
Model
ETS 300 1870 450 2.60 17.0 140
* Energy consumption in standby according to DIN 44 532 with 50°C tank temperature and 45°C tap temperature ** Screw-in heater installation depth
H ø D A B C E F G I
Tip
dimen-
sion
[mm]
Max.
installa-
tion
length
[mm]
development process.
Dimensions in mm
Register
heating
surface
[m²]
Register capacity
[l]
305
Weight
[kg]
- - -
BEVB*
number
[
kWh/d]
DIN 4708
2.2
NL
acc. to
[-]
10 500
ETE**
[mm]
16
Page 17
Technical data
Model
Type designation
Capacity (net) L 286
Max. operating temp., drinking water °C 95 Max. operating pressure, drinking water bar Max. operating temp., hot water °C 100 Max. operating pressure, hot water bar Max. heating capacity kW Heat exchanger surface m² 2.6 Register capacity L BEVB in kW/h / 24h kWh
NL number 10
Max. issue quantity with drawing at 45°C
Serial number 789C5...
Cycle outputs ETS 300
Supply temperature °C 50 50 50 50
Hot water temperature °C 45 45 45 45
Cold water temperature °C 10 10 10 10
Heating circuit flow rate l/h 500 1000 3000 4500
Cycle output kW
l/min
10.6 15.1 20.9 22.4
ETS 300
ETS 300
10
10 92
17
2.2
37
Supply temperature °C
Hot water temperature °C 45 45 45 45
Cold water temperature °C 10 10 10 10
Heating circuit flow rate l/h 500 1000 3000 4500
Cycle output kW
Supply temperature °C
Hot water temperature °C 45 45 45 45
Cold water temperature °C 10 10 10 10
Heating circuit flow rate l/h 500 1000 3000 4500
Cycle output kW
70 70 70 70
22.9 35.5 55.6 62.1
80 80 80 80
28.3 44.9 73.1 82.2
17
Page 18
REMKO ETS 300
Aufheizzeiten (45°C) zu HR 300
Ablesebeispiel:
Heizwasserdurchflussmenge 3000 l/h Heizwasservorlauftemperatur 50 °C Kaltwassertemperatur 10 °C Aufheizung von 10 °C auf 45 °C ergibt eine Aufheizzeit von 31 min
0
10
20
30
40
50
60
70
80
90
0 1000 2000 3000 4000 5000
Aufheizzeit in min
50/45
70/45
80/45
90/45
Heizwasserdurchflussmenge in l/h
Warm up-times at 45°C
18
Page 19
19
Page 20
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 e-mail [email protected] Website www.remko.de
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...