REMKO AMT 45-E, AMT 85-E, AMT 65-E, AMT 115-E User Manual

Page 1
REMKO AMT
REMKO AMT 45-E to 115-E
Air dehumidifiers
Operation · Technology · Spare parts
Edition GB – D09
Page 2
Page 3
Contents
Air dehumidification
Safety notes
Intended use
Customer service and guarantee
Environmental protection and recycling
Unit description
Set-up
Commissioning
Shutdown
Transportation
Care and maintenance
Troubleshooting
Electrical wiring diagram
4
6
7
7
7
8
9
10
12
13
13
14
15
Exploded view of the AMT 45-E unit
Spare parts list AMT 45-E
Exploded view of the AMT 65-E and 85-E units
Spare parts list AMT 65-E and 85-E
Exploded view of the AMT 115-E unit
Spare parts list AMT 115-E
Maintenance protocol
Technical data
Carefully read this operating manual prior to commissioning/using the unit! This operating manual is a translation of the German original.
16
17
18
19
20
21
22
23
Made by REMKO
These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
Page 4
REMKO AMT
Air dehumidification
The correlations occurring when air is dehumidified are based on physical laws. These are depicted here in graphical form in order to provide you with a brief overview of the principles of air dehumidification.
The use of REMKO air dehumidifiers
– Even if windows and doors
are well insulated, water and moisture are still capable of penetrating thick concrete walls.
– The water required for setting
in the production of concrete, mortar and plaster etc. may only be diffused after 1-2 months.
– Even moisture trapped
in the masonry after high­water or a flood is released very slowly.
– The same is also true of
moisture contained in stored materials for example.
The moisture (water vapour) released from parts of a building or materials is absorbed by the surrounding air. As a result, the moisture content increases, which ultimately gives rise to corrosion, mould, rot, peeling of paint and other unwanted damage.
By way of example, the diagram shows the corrosion rate of metal in different levels of humidity.
It is evident that the corrosion rate below 50% relative humidity (RH) is low, and below 40% is negligible.
The corrosion rate increases significantly above 60% RH. This threshold for damage as the result of humidity also applies to other materials, such as powdery substances, packaging, wood and electronic units.
Buildings may be dried in a variety of ways:
1. By heating and
air exchange:
The air in the room is heated
in order for moisture to be removed and then this air is fed outside. All of the energy that is involved is lost together with the moist air that is released.
2. By air dehumidification:
The moist air that is
present within an enclosed space is continuously dehumidified according to the condensation principle.
With regard to energy consumption, air dehumidification has one distinct advantage:
Energy expenditure is limited exclusively to the air volumes present. The mechanical heat that is released by the dehumidification process is fed back into the room.
Under normal use, the dehumidifier 25% of the energy that is required for the ventilating" principle.
Relative air humidity
Our ambient air is a gaseous mixture which always contains a certain volume of water in the form of water vapour. This volume of water is specified in g per kg of dry air (absolute moisture content).
1m3 of air weighs approx. 1.2 kg at 20°C
Depending on the temperature, each kg of air is only capable of absorbing a certain volume of water vapour. Once this capacity has been reached, the air is referred to as "saturated" and has a relative humidity (RH) of 100%.
Relative humidity is understood to mean the ratio between the current quantity of water vapour in the air and the maximum possible quantity of water vapour at the same temperature.
The ability of the air to absorb water vapour increases as the temperature rises. I.e. the maximum possible (absolute) water content becomes greater as the temperature rises.
uses approximately
air
"heating and
4
Page 5
Temp. Water vapour content in g/m3 at humidity of
Verdampfer Kondensator
°C
30
25
20
15
% r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
Lufttemperatur
Luftfeuchte
Verlauf
Luftrichtung
°C 40% 60% 80% 100%
-5 1.3 1.9 2.6 3.3
+10 3.8 5.6 7.5 9.4
+15 5.1 7.7 10.2 12.8
+20 6.9 10.4 13.8 17.3
+25 9.2 13.8 18.4 23.0
+30 12.9 18.2 24.3 30.3
Drying of materials
Building materials and structures are capable of absorbing considerable volumes of water, such as brick 90-190 l/m³, heavy concrete 140-190 l/m³ and limestone 180-270 l/m³. The drying of moist materials such
■
The air containing water vapour
is constantly circulated through the REMKO air dehumidifier. The air is dehumidified and, slightly heated, leaves the unit in order to re-absorb water vapour
as masonry is effected as follows:
■
In this way, the moisture
■
The moisture moves from the inside of the material
contained in the material is reduced gradually.
The material is dried!
to its surface
The accumulated condensate is
■
Evaporation occurs
on the surface =
collected in the unit from where
it is drained off. Transfer of water vapour to the ambient air
The condensation of water vapour
Because the capacity for the maximum possible volume of water vapour increases as the air is heated, the volume of water vapour contained remains constant and so relative humidity falls.
In contrast, because the capacity for the maximum possible volume of water vapour decreases as the air is cooled, the volume of water vapour contained remains constant and so relative humidity increases. If the temperature continues to fall, the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in the air. This temperature is referred to as the dew point. If the air is cooled to below the dew point, the volume of water vapour in the air will become greater than the maximum possible volume of water vapour. At this point, the water vapour begins to precipitate. It then condenses to water. Humidity is then removed from the air.
As it flows through or over the evaporator, the air stream is cooled to dew point. The water vapour condenses, and is collected in a condensate trap from where it is drained off.
Examples of condensation include steamed-up window panes in winter, or the moisture on the outside of a cold drinks bottle.
As the relative humidity of the air increases, so to does the dew point, making it easier for the temperature to fall below it.
5
Page 6
REMKO AMT
Condensation heat
The Energy transferred to the air from the condenser consists of:
1. the amount of heat derived beforehand in the evaporator.
2. the electrical drive energy.
3. the condensation heat released by the liquefying of the water vapour.
Energy must be supplied when liquid is converted into a gas. This energy is designated as evaporation heat. It does not cause any increase in temperature,
Safety notes
but is required to convert a liquid into a gas. Conversely, energy is released when gas is liquefied, this is designated as condensation heat. The amount of energy from evaporation heat and condensation heat is the same.
For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the condensation of water vapour causes a large quantity of energy to be released. With drying operations, a heat cycle is created,
whereby heat is consumed for evaporation and released for condensation.
Generally speaking, the time required for the drying process is not only dependent on the output of the unit, but is determined to a greater extent by the speed at which the material or building section loses its moisture.
The units were subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can result from the units if they are used improperly or not as intended by untrained personnel. The following notes must be observed in full:
■
The units may not be installed or operated in explosive environments
■
The units must not be installed or operated in atmospheres containing oil, sulphur, chlorine or salt
■
The units must be installed upright and in a stable position
■
An unobstructed air inlet and air outlet must be guaranteed at all times
■
The air-inlet grille must always be kept free of dirt and loose objects
■
The units must not be covered during operation
■
Never stick foreign objects into the units
■
The units must not be transported while they are running
■
The units must only be transported when the condensate container is empty and the evaporator is dry
■
Before each change of location, the condensate container must be emptied
!
ATTENTION
Extensions to the connection cable must only be conducted by authorised specialist electricians, taking into consideration the unit power consumption, cable length and local use.
!
ATTENTION
Work on the refrigerant system and on the electrical equipment must only be conducted by a specially­authorised specialist!
■
The units must not be exposed to direct jets of water
6
■
All electrical cables on the outside of the units must be protected against damage (e.g. by animals etc.)
Page 7
Intended use Environmental
The units are designed exclusively for drying and dehumidification purposes in industrial or commercial situations on the basis of their structural design and equipment.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
Customer service and Guarantee
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative complete and return the "certificate of guarantee" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units were tested at the factory several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
protection and recycling
Disposing of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in stable cardboard transport packaging and, if applicable, on a wooden pallet. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any liability and claim to guarantee expire.
!
ATTENTION
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended without the written authorisation of
REMKO GmbH & Co. KG
is prohibited.
NOTE
Adjustment and maintenance work may only be carried out by authorised qualified technicians.
Important information concerning recycling
The units are operated with environmentally-friendly and ozone-neutral R410A refrigerant. The mixture of refrigerant and oil within the unit must be disposed of properly in accordance with the statutory or locally-applicable regulations.
Disposal of the old unit
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environmentally-friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point.
7
Page 8
REMKO AMT
Unit description
The units have been designed for universal and straightforward air dehumidification. Their compact dimensions allow the unit to be transported and set up with ease. The units operate in accordance with the condensation principle and are equipped with a hermetically sealed refrigerant system, low-noise and low­maintenance fan, operating hours counter and connection cable with plug. Fully-automatic electronic control, a condensate container with integrated overflow protection (not AMT 115-E) in addition to connection ports for direct condensate drainage help to ensure continuous fault­free operation.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations. The units are dependable and offer ease of operation.
Locations at which units are used
The units are used in all locations, where dry air is a must and where economic consequential damage (such as that caused by mould) must be prevented.
Operating sequence
Switching on the units puts the electrical control into operation. The green indicator light on the operating switch illuminates. Due to an automatic pressure equalisation, the units start with a time delay of around 10 seconds.
The fan extracts the moist room air through the dust filter, evaporator and the condenser behind.
Heat is removed from the room air on the cold evaporator. The air is then cooled to below dew point. The water vapour contained in the room air is then deposited as condensate or rime on the evaporator fins.
If the temperature sensor here measures a pre-set minimum, it activates a timer with a 30 minute delay. If the evaporator temperature stops increasing during this period, the cooling cycle switches to hot gas defrosting after the timer cycle.
The fan remains out of operation during the defrosting phase.
Schematic depiction of the workings of a REMKO air dehumidifier
As soon as the rime (ice) has been defrosted and the temperature at the probe has increased, the unit switches back to normal dehumidification mode.
If the room temperature is sufficiently high, the surface of the fins will not be cold enough for rime formation to occur, rendering defrosting unnecessary.
Therefore, the air dehumidifiers work economically.
The cooled and dehumidified air is re-heated by the condenser (heat exchanger), and blown back into the room through the outlet grille. The processed, dry, heated air then re-mixes with the room air.
Continuous circulation of the room air through the unit gradually reduces the relative humidity (% RH) in the room to the desired humidity level.
Depending on the room temperature and the humidity, only 30 - 40% electrical energy is required, in accordance with the output of the unit.
The units may be used for the drying and dehumidification of areas such as:
■
New buildings, industrial
buildings
■
Basements, storage rooms
■
Archives laboratories
■
Weekend homes, caravans
■
Bathrooms, wash rooms and
changing rooms etc.
8
Fan
Dehumidified
room air
Compressor
Condenser
Evaporator
Moist room air
Condensate container
Page 9
Set-up
For the best economic and safe use of the units, the following notes must be followed in full:
■
The units must be set up
in an upright and level position, to ensure that the condensate can drain freely
■
To ensure optimum air
circulation, the units should be set up in the centre of the room, where possible
■
It must be ensured that the air
can be sucked in on the front of the unit and blown out of the rear of the unit without obstruction
■
Observe a minimum clearance
of 50 cm from walls at all times
■
Units must never be set up
in the immediate vicinity of heaters or other sources of heat
■
The room being dried or
dehumidified must be closed to the neighbouring atmosphere
■
Air circulation is improved if
the unit is set up approx. 1 m above the ground
■
Avoid having opened windows
and doors etc., and avoid frequent entry to or exit from the room as much as possible
■
If the units are to be used
in dusty environments, appropriate care and maintenance measures should be taken according to the relevant conditions
■
The output of the unit is entirely
dependent on the conditions inside the room, room temperature, relative humidity and observance of the set-up instructions
■
The units may not be used
in environments containing a great deal of dust or chlorine, or in places with atmospheres containing ammonia
Electrical connection
■
The units are operated
with 230 V / 50 Hz alternating current
■
The electrical connection is
made using a built-in mains cable with earthed safety plug
NOTE
The electrical connection to the units must be made at feedpoints with residual current devices in accordance with VDE 0100, Section 704.
When installing the units in extremely damp environments such as laundry rooms, showers etc., the unit must secured with a residual current device provided by the customer in accordance with the regulations.
■
Extensions
to the connection cable may only be carried out by authorised electricians, subject to the length of the cable, connected load of the unit and taking into consideration how the unit is used at its location
Keep windows and doors closed!
Wall clearance min. 0.5 m
Maintain adequate clearance from
heaters or other sources of heat.
!
ATTENTION
All cable extensions must only be used in fully un-reeled or reeled off condition.
9
Page 10
REMKO AMT
Commissioning
Before commissioning the unit or if local requirements dictate, the air­inlet grille and air-outlet grille must be checked for contamination.
NOTE
A contaminated grille or filter must be cleaned or replaced immediately.
Important notes prior to commissioning
■
All extensions to the electrical
connection must be of a sufficient cable size and must only be used fully rolled out or unrolled
■
Never use the power supply
connection cable as a pull cord
■
After being switched on,
the units operate fully­automatically until switched off by the float when the condensate container is full (not AMT 115-E)
■
The condensate container must
be inserted properly
Control panel
1
3
1 = Operating hours counter
2 = Operating switch with
"Indicator light"
3 = -YELLOW- indicator light
"Container full"
4 = -RED- indicator light
„Malfunction / overheating"
Starting the unit
1. Move the operating switch [2] to the "0" (off) position.
4
2
Operation with a humidity switch
The REMKO humidity switch (accessories) is supplied with a special adapter. The following procedure must be followed when commissioning units in conjunction with a humidity switch:
1. Insert the adapter into a properly fused mains socket.
2. Place the humidity switch in a suitable location within the room being dehumidified.
Not in the immediate vicinity of the units or sources of heat.
3. Insert the power plug (or a cable extension) into the adapter.
4. Set the desired air humidity on the humidity switch.
5. Move the operating switch [2] on the unit to position "I".
The units will switch on automatically when the air humidity in the room exceeds the pre-set level on the humidity switch.
■
In order to prevent damage
to the condenser, the units are equipped with a mechanism that prevents the compressor from being immediately switched back on after it is switched off
The compressor does not switch back on until after a waiting time of around one minute!
NOTE
In room temperatures below
10°C
and relative humidity below of the unit can no longer be guaranteed.
10
40%
, economical use
2. Connect the unit's power plug to a properly installed and fused mains socket.
230V/50 Hz
3. Move the operating switch [2]to the "I" (on) position.
The green indicator light on the switch [2] illuminates.
The units switch on with a time delay of around 10 seconds and then run in permanent operating mode.
The units will now operate fully­automatically until the desired relative humidity (% RH) has been reached or until the unit is switched off by the float when the condensate container is full (not AMT 115-E). In the event that this occurs, the yellow "Container full" indicator light will illuminate.
Page 11
Condensate
Depending on the air temperature and the relative humidity, condensed water will drip into the condensate trap or into the condensate container either continuously or only during the defrosting phases. The condensate is fed into the condensate container below via a connection nozzle (not AMT 45-E and AMT 115-E).
A float is located inside the condensate container. In the event that the container is full, the float will activate a water stop switch which will switch off dehumidification mode.
To guard against accidental stops caused by flooding water etc., this switch does not activate until after a time delay of 10 seconds. The unit will switch off and the yellow indicator light on the control panel will illuminate.
3. Place the container carefully outside the unit and open the sealing cover [F] of the pouring opening [E].
F
4. Pour the water into a drain.
Unit operation with hose connection
The condensate traps [K] of the AMT 65 and 85-E are equipped with a ½" connection nozzle [A]. After removing the condensate
E
container, a standard ½" water hose [S] may be connected to this.
The hose [S] is not provided from the factory.
A
K
S
In the AMT 45-E, the hose is connected directly to the ½" connection nozzle [D] of the condensate container.
To empty the condensate container, the following procedure must be followed:
1. Move the operating switch [2] to the "0" (off) position.
Otherwise, the AMT 65-E and AMT 85-E units would restart immediately after the container is removed.
2. Remove the condensate container. To do this, lift the container slightly using the embedded recessed grip and then pull it carefully forwards and out.
NOTE
Beware of dripping condensate. After switching off the units, the evaporator may continue to defrost under the influence of the ambient temperature.
5. Close the pouring opening [E] and carefully insert the condensate container back into the unit.
NOTE
After being emptied, the condensate container incl. float must be checked for damage, contamination etc.
6. Switch the unit back on using the operating switch [2].
NOTE
The AMT 45-E units are only fully functional if the condensate container is inserted properly.
D
To operate the units, the condensate container must always be inserted correctly in the AMT 45-E.
In unattended permanent operating mode, the condensate should preferably be drained into a lower-level flow. If using a collection container (pan, bucket, etc.), the unit must be placed at a correct height.
For further suggestions, see the next page!
11
Page 12
REMKO AMT
AMT 115-E condensate drain
Due to their high dehumidification capacity, the AMT 115-E units are not equipped with an internal condensate container. The condensate drainage is to be provided by the customer in suitable containers via the exterior unit connection nozzles (½"). The following variants (for example) are available to drain the condensate water that arises:
Variant A
The water is collected in a container that is provided by the customer and that is of sufficient size. The container must be checked regularly and emptied if necessary.
There is no overflow protection!
Variant B
The water is first collected in a container and fed into a higher drain via a separate submerged pump or drained outside directly. This variant is suitable for installation locations with an insufficient incline or without a drain.
Shutdown
Move the operating switch to the "0" (off) position.
If the units are inactive for longer periods, disconnect them from the mains power supply.
Empty the condensate container and dry with a clean cloth.
Beware of dripping condensate!
When storing the unit, cover with a plastic sheet/foil if necessary and store in an upright position in a sheltered and dry location.
To save space when storing, the units can be stacked on top of one another. For this purpose, they are equipped with rubber pads on the base plate.
Variant C The water is fed into a lower drain via a ½“ hose pipe. This variant enables unattended permanent operating mode.
NOTE
These variants can also be used in the same way for continual condensate drainage for all other unit types.
12
!
ATTENTION
The units must be protected against falling down and unau­thorised access after stacking.
Page 13
Transportation
Care and maintenance
For easy transportation, the units are equipped with 2 large wheels and an ergonomic transportation and protective clamp. This can also be dismantled easily if required.
When transporting the units, observe the following:
1. Before each change of location, switch off the unit and remove the power plug from the mains socket.
2. Drain the condensate container.
3. If moisture remains on the evaporator or water remains in the condensate container, the units must only be transported in an upright position.
NOTE
Beware of dripping condensate. After switching off the units, the evaporator may continue to defrost under the influence of the ambient temperature.
NOTE
Regular care and maintenance is fundamental to a long service life and fault-free operation of the unit.
All moving parts have a low­maintenance permanent coat of lubricant. The refrigerant system is designed as a hermetically sealed system and may only be repaired by a specialist.
!
ATTENTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
■
Observe the regular care and
maintenance intervals
!
ATTENTION
Check the inlet and out­let grille for contamina­tion on a regular basis.
■
In accordance with
the operating conditions, the units must, if necessary, be checked at least yearly by a specialist to ensure that they are in a condition that is safe to use
■
Keep the units free of dust and
other debris
■
Only clean the units with a dry
or moistened cloth
■
Never subject to direct jets of
water.
e.g. pressure washers etc.
Cleaning the dust filter
!
ATTENTION
Check the inlet and outlet grille and the dust filter for contami­nation on a regular basis.
Slide the protection grid upwards slightly, then pull forwards and remove downwards.
Then remove the dust filter which has now been released. Light contamination of the dust filter may be remedied with careful blowing or suction.
Heavier contamination may be remedied by rinsing the filter in a lukewarm (max. 40°C) soap solution. Finally, always rinse the filter carefully with clear water and allow to dry!
Before refitting the dust filter, ensure that its fully dry and that no damage has been sustained.
NOTE
Heavily contaminated dust filters must be replaced with new parts. Only original replacement parts may be used.
The units may only be operated with the dust filter in place.
!
ATTENTION
The mains cable must never be used as a pull cord or fixing device.
■
Never use abrasive or solvent-
based cleaners
■
Use only suitable cleaners
for heavy contamination
13
Page 14
REMKO AMT
Cleaning the units
The unit housing must be opened to allow the inside of the unit to be cleaned and to provide access to electrical components.
NOTE
Adjustment and maintenance work may only be carried out by authorised qualified technicians.
1. Remove the 2 fastening screws [B].
2. Lift the housing part and unhinge the front flaps.
B
B
3. Clean the condenser fins by blowing, with suction or using a smooth brush.
4. Clean the evaporator fins, for example with a lukewarm soap solution, or similar.
NOTE
When cleaning the exchanger, particular care must be taken because the fine aluminium fins bend very easily.
5. Never subject to direct jets of water.
6. Rinse with clean water to remove any remaining soap.
7. Clean the internal surfaces of the unit and the fan blade.
8. Clean the condensate trap and the connection nozzles.
9. Once cleaning has been completed, the unit should be dried. Take particular care with electrical components!
10. Re-install all dismantled components in reverse order.
11. Carry out a unit function check
and electrical safety check.
!
ATTENTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
Troubleshooting
The units are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However, if a functional fault should occur, the unit should first be checked in accordance with the following list.
The unit does not start
■
Check the setting of
the operating switch. The green indicator light should illuminate
■
Check the power supply and
the power fuse provided by the customer 230V/1~/50 Hz
■
Check the power plug and
the cable for damage
■
Check the level and correct
positioning of the condensate container (not AMT 115-E)
■
Check the setting of
the humidity switch (accessories). The pre-set value must be lower than the relative humidity in the room
■
Check the humidity switch
adapter for damage and correct positioning
The red indicator light (Malfunction) illuminates
■
The cooling cycle is overloaded
or overheated
■
Before starting the unit again,
first identify the cause of the malfunction. Note that the re-start is automatic after the cooling process is complete!
The unit runs but does not form any condensate
■
Check the room temperature
The operating range of the unit is between 3°C and 32°C
■
Check the humidity of the air,
min. 40% RH required
■
Check the dust filter
for contamination and clean or replace if necessary
■
Check the evaporator
and condenser fins for contamination and clean if necessary
■
Check the evaporator for ice or
rime formation. If ice has formed, check the functionality of the automatic defrost and the temperature sensor
■
If the unit fails
to function correctly after the checks have been carried out, an authorised specialist
!
ATTENTION
Work on the refrigerant system and on the electrical equipment must only be conducted by a specially­authorised specialist!
14
Page 15
Electrical wiring diagram
AMT 45-E to 115-E
3,15 A
Operating
stunden
hours
1,0 A
F
S1
PE
L NPE
230V/1~/50Hz
Control board
Steuerplatine
Compressor Changeover
KompressorBetriebs-
C R
M1 M2
Kompressor Ventilatormotor
Compressor Fan motor
C1
S
Umschalt-
ventil
valve
PE
Ambiente
Umluft-
ventilator
air fan
D
Lamp
Fühler °C
Probe °C
Verdampfer Kondensator
evaporator
PE
NTC NTC
PE
Fühler °C
Probe °C
condenser
Fühler
Probe °C
Wasser Stop
water stop
Not applicable
entfällt bei AMT 115-E
for AMT 115-E
Lampe
Wasser
H2 H3
Yellow Red
GelbSW
water
stop
Stop
Lampe
Fail
Störung
lamp
Rot
WHITE
WEISS
BLACK
1
2
3
4
Socket
Steckdose
am Gerät
on the unit
Plug
Stecker
2
3
VIOLET
VIOLETT
1
4
SCHWARZ
VIOLETT
VIOLET
Kondensatpumpe (optional)
Condensate pump (optional)
= Test button
D
The test button is only provided for maintenance and checking tasks carried out by the service personnel. When it is pressed, the defrosting timer settings are reduced.
not possible for AMT 115-E
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
15
Page 16
REMKO AMT
Exploded view of the AMT 45-E unit
50
49
48
1
4546
2
40
3
4
5
6
7
8
10
11
12
13
14
15
18
30
47
31
26 27
29
25
32
33
24
34
36
35
37
39
38
16
20
17
22 25
21
23
16
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Page 17
Spare parts list AMT 45-E
No. Description EDP no.
1 Air-inlet grille 1105601 2 Dust filter 1105602 3 Transportation bracket 1105603 4 Fixed base cpl. 1105604 5 Evaporator fin package cpl. 1105905 6 NTC evaporator probe 1105606 7 NTC condenser probe 1105607
8 Fan housing 1105608 10 Fan blade 1105609 11 Engine mounting cpl. 1105610 12 Drive clutch 1108455 13 Fan motor 1108077 14 Solenoid valve 1105715 15 Coil for solenoid valve 1105714 16 Dry filter 1105908 17 Compressor, cpl. 1105909 18 Operating condenser 1105910 20 Inspection housing part cpl. 1105618 21 Completion panel 1105619 22 Base plate 1105956 23 Axle 1105621 24 Base plate rubber stop (set) 1105622 25 Wheel 1102155 26 Hubcap 1101623 27 Locking ring 1101622 29 Strain relief 1101267 30 Mains cable with plug 1105624 31 Insulation 1105625 32 Switch cabinet housing 1105911 33 Control board cpl. 1105913 34 Indicator light, yellow 1105611 35 Indicator light, red 1105612 36 Operating hours counter 1105515 37 Operating switch with indicator light 1105628 38 Housing cover 1105912 39 Water stop probe 1105723 40 Support frame 1105914 45 Container seal 1105632 46 Magnetic float 1105633 47 Sealing cap 1105634 48 Condensate container cpl. 1105635 49 Stand rubber stop (set) 1105636 50 Stand 1105637
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
17
Page 18
REMKO AMT
Exploded view of the AMT 65-E and 85-E units
4
52
51
49
45
47
2
3
5
6
7
8
10
11
14
12
13
46
15
16
1
48
30
50
17
18
39
32
31
35
29
25
2726
3433
40
38
37
36
22 25
23
20
21
18
24
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Page 19
Spare parts list for the AMT 65-E and 85-E units
No. Description AMT 65-E AMT 85-E
EDP no. EDP no.
1 Air-inlet grille 1105659 1105659
2 Dust filter 1105660 1105660
3 Fixed base cpl. 1105661 1105661
4 Transportation bracket 1105662 1105662
5 Evaporator fin package cpl. 1105711 1105731
6 NTC evaporator probe 1105606 1105606
7 NTC condenser probe 1105607 1105607
8 Fan housing 1105712 1105712 10 Fan blade 1105665 1105665 11 Engine mounting cpl. 1105666 1105666 12 Drive clutch 1101155 1101155 13 Fan motor 1105667 1105667 14 Temperature valve ---------- 1105732 15 Dry filter 1105713 1105733 16 Coil for solenoid valve 1105714 1105714 17 Solenoid valve 1105715 1105715 18 Compressor cpl. 1105716 1105734 20 Inspection housing part cpl. 1105671 1105671 21 Completion panel 1105647 1105647 22 Base plate 1105957 1105957 23 Axle 1105673 1105673 24 Base plate rubber stop (set) 1105622 1105622 25 Wheel 1102155 1102155 26 Hubcap 1101623 1101623 27 Locking ring 1101622 1101622 29 Strain relief 1101267 1101267 30 Mains cable with plug 1105624 1105624 31 Insulation 1105651 1105651 32 Switch cabinet housing 1105717 1105717 33 Indicator light, yellow 1105611 1105611 34 Indicator light, red 1105612 1105612 35 Operating switch with indicator light 1105628 1105628 36 Housing cover 1105718 1105718 37 Control board cpl. 1105719 1105719 38 Operating hours counter 1105515 1105515 39 Operating condenser 1105720 1105735 40 Water stop probe 1105723 1105723 45 Support frame 1105721 1105721 46 Hose connection nozzles ½" 1105567 1105567 47 Condensate trap 1105722 1105722 48 Magnetic float 1105633 1105633 49 Container seal 1105632 1105632 50 Condensate container cpl. 1105657 1105657 51 Stand rubber stop (set) 1105636 1105636 52 Stand 1105676 1105676
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
19
Page 20
REMKO AMT
Exploded view of the AMT 115-E unit
49
1
2
47
46
3
4
5
6
7
8
9
10
11
15
16
17
18
19
20
22
36
30
48
31
29
35
45
37
38
24
44
43
42
4039
41
25
26 29
27
20
28
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Page 21
Spare parts list AMT 115-E
No. Description EDP no.
1 Air-inlet grille 1105677
2 Dust filter 1105678
3 Transportation bracket 1105679
4 Fixed base cpl. 1105680
5 Fin evaporator 1105740
6 Fin condenser 1105741
7 NTC evaporator probe 1105606
8 NTC condenser probe 1105607
9 Temperature valve 1105742 10 Dry filter 1105743 11 Fan housing 1105950 15 Fan blade 1105686 16 Engine mounting cpl. 1105687 17 Drive clutch 1101155 18 Fan motor 1105555 19 Solenoid valve 1105715 20 Coil for solenoid valve 1105714 22 Compressor, cpl. 1105746 24 Inspection housing part cpl. 1105689 25 Completion panel 1105690 26 Base plate 1105951 27 Axle 1105692 28 Base plate rubber stop (set) 1105622 29 Wheel 1101621 30 Hubcap 1101623 31 Locking ring 1101622 35 Strain relief 1101267 36 Mains cable with plug 1105624 37 Insulation 1105693 38 Switch cabinet housing 1105952 39 Operating hours counter 1105515 40 Indicator light, red 1105612 41 Operating switch with indicator light 1105628 42 Housing cover 1105953 43 Control board cpl. 1105719 44 Operating condenser 1105954 45 Support frame 1105955 46 Condensate trap 1105697 47 Hose connection nozzles ½" 1105698 48 Stand rubber stop (set) 1105636 49 Stand 1105699
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
21
Page 22
REMKO AMT
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Fan housing cleaned
Condenser cleaned
Evaporator cleaned
Fan function checked
Air-inlet grid with filter cleaned
Unit checked for damage
Safety devices checked
All fastening screws checked
Electrical safety check
Test run
✍
Comments: .....................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
22
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
Page 23
Technical data
Series AMT 45-E AMT 65-E AMT 85-E AMT 115-E
Operating range, temperature °C 3-32 3-32 3-32 3-32
Operating range, humidity % RH 40-100 40-100 40-100 40-100
Dehumidification capacity max. l/day 42 64 80 119
at 30°C/80% RH
at 20°C/70% RH
at 10°C/60% RH
l/day (DER) 37.4 (2.32) 56.8 (2.96) 70.8 (3.07) 106.4 (3.47)
l/day (DER) 21.2 (1.73) 31.7 (2.06) 40.1 (2.26) 60.7 (2.57)
l/day (DER) 6.9 (0.78) 9.4 (0.93) 13.2 (0.89) 18.0 (1.01)
Max. airflow volume m3/h 280 590 650 970
Condensate container capacity Litres 8/7 18/15 18/15 without
Compressor / condenser Configuration Rotary piston
Refrigerant
1)
R410A R410A R410A R410A
Refrigerant quantity g 480 580 750 1270
Power supply V/Hz 230/1~/50
Max. rated current consumption A 3.2 4.0 4.8 6.7
Max. power consumption kW 0.730 0.890 1.020 1.385
at 20°C/70% RH kW 0.510 0.640 0.740 0.986
Customer-provided electrical protection A 16 16 16 16
Sound pressure level LpA 1m
2)
dB (A) 58 60 63 67
Depth mm 490 530 530 605
Width mm 480 615 615 710
Height mm 640 795 795 895
Height incl. transportation bracket mm 950
Weight kg 34 45.5 49.5 65
EDP no. 617400 617550 617800 617900
(DER) = Dehumidification output figure in accordance with DIn EN 810
1)
Contains greenhouse gas according to Kyoto protocol
2)
Noise level measurement DIn 45635 - 13 - KL 3
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
23
Page 24
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail [email protected] Internet www.remko.de
Consulting
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation of
being more than just an excellent,
reliable supplier:
REMKO, a partner who helps
to solve problems.
Sales
REMKO offers not just a well-
established sales network both
nationally and internationally,
but also has exceptionally highly-
qualified sales specialists.
REMKO employees in the field
are more than mere salespeople:
above all, they must be
advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely and
reliably. However, in the event
of a malfunction REMKO customer
service is quickly on the scene.
Our comprehensive network
of experienced dealers guarantees
quick and reliable service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...