Remak VCS Installation And Operating Instructions Manual

Řídicí systém pro vzduchotechnické jednotky
INSTALLATION AND OPERATING INSTRUCTIONS
Control units
11 /2018
1
Table of Contents
n e VCS control unit soware is the intellectual property
of REMAK a.s.
n VCS control units are manufactured in accordance with
valid Czech and European regulations and technical stan­dards.
n VCS control units must be installed and used only in accor-
dance with this documentation.
n The manufacturer is not responsible for any damage resul-
ting from use for purposes other than specified in this do­cumentation, and the customer bears the risks of such use.
n The installation and operating documentation must be
available for the operating and servicing staff. It is advi­sable to store this documentation close to the installed VCS control unit.
n When handling, installing, wiring, commissioning, repairing
or servicing the air-handling units, it is necessary to observe valid safety rules, standards and generally recognized technical rules.
n All equipment connections must comply with the respective
safety standards and regulations.
Introduction
Equipment characteristics .................................................................................................................................................................2
Design .......................................................................................................................................................................................................3
Documentation and Safety Measures ...........................................................................................................................................4
Handling, Transport and Location ................................................................................................................................................... 5
Commissioning ......................................................................................................................................................................................6
Control and Protection Functions ................................................................................................................................................... 8
Basic Operating Modes ...................................................................................................................................................................17
Additional Operating Modes and Functions ............................................................................................................................. 17
Temperature and Time Modes ......................................................................................................................................................19
Control (HMI-SG controller) ............................................................................................................................................................20
List of Data Points (HMI-SG controller) ...................................................................................................................................... 27
List of Failures (HMI-SG controller) ..............................................................................................................................................43
REMAK mobile app ...........................................................................................................................................................................47
Control (HMI-DM, HMI-TM and HMI@Web controllers) ........................................................................................................46
Control (HMI@Web – Installation and Connection to PC and LAN/WAN) ....................................................................51
SCADA (Supervisory Control and Data Acquisition) .............................................................................................................. 58
List of Data Points (HMI-DM, HMI-TM and HMI@Web controller) ...................................................................................59
List of Failures (HMI-DM, HMI-TM and HMI@Web controller) ............................................................................................ 68
Other Control ......................................................................................................................................................................................69
Connection to the Master System (LonWorks Standard) ................................................................................................... 70
Connection to the Master System (ModBus Standard) ....................................................................................................... 75
Connection to the Master System (BacNet Standard) ........................................................................................................95
POOL UNITS – descriptioon of control ...................................................................................................................................... 97
PLC Controller for Compressor Output Control ......................................................................................................................99
Electronic Expansion Valve Overheating Controller EC3-X33 ......................................................................................... 104
KHD-S1_ _.R Backup System Wiring Diagram....................................................................................................................110
Unit Activation ................................................................................................................................................................................. 111
Checks and Failures ........................................................................................................................................................................ 113
Troubleshooting .............................................................................................................................................................................. 114
Spare Parts and Service ...............................................................................................................................................................115
Disposal and Recycling ................................................................................................................................................................. 115
n Any changes or modifications to individual components of
the VCS control unit which could affect its safe and proper functioning are forbidden.
n Before installing and using the air-handling units, it is nece-
ssary to familiarize yourself with and observe the directions and recommendations included in the following chapters.
n The VCS control units, including their individual parts,
are not intended, due to their concept, for direct sale to end customers. Each installation must be performed in accordance with a professional project created by a qualified designer who is responsible for the proper selection and dimensioning of components concerning their suitability for a given application. Installation and commissioning may only be performed by an authorized company licensed in accordance with generally valid regulations.
n REMAK a.s. is not responsible for any damage, direct or
indirect, caused by unauthorized or unqualified used of the soware or hardware, or for any damage caused by ignoring the product's Operating Instructions.
Up-to-date version of this document is available at website www.remak.eu
2
Equipment characteristics
Application
VCS control units are compact control and power distribu­tors used for the decentralized regulation and control of air­handling systems.  ey provide the equipment with high stability and safety while allowing easy control, including the viewing of operating states. (STOP - OPERATION - AUTO).
Main Features
 e VCS control unit is intended for the following:
n Complex autonomous control of air-handling systems n Supply or room air temperature control (cascade control) n Supply and power actuation of air-handling systems n Protection and safeguarding of connected components
 is control unit provides air-handling systems with control and safety functions. It can be equipped with the necessary number of proportional inputs and outputs depending on the required functions. Sophisticated control algorithms ensure system stabil­ity, user-friendly control and energy savings. Another advantage is that the control unit's features also contrib­ute to energy savings in air-handling system operation:
n Option to set the unit to 2 temperature modes
• Comfort
• Economy n Time schedule setting options
(daily or weekly time schedules)
n Additional operating mode setting options:
• Optimized start
• Temperature start-up
• Night chilling n Precise drive control using data communications
(Modbus RTU protocol)
n Superior antifreeze protection with moderate heating of
the heat exchanger during standby mode
n Precise analogue control of controlled peripheral units
(according to the controlled component)
Unit Design
 ese control units are designed in accordance with ČSN EN 60204-1.  e unit's control and power parts are situ­ated in a single box.  e components, control and actuating elements, are fi tted on the DIN bars inside the control unit. Depending on the version, the VCS control unit can be provided in plastic (plastic switchboard) or in sheet-steel (sheet-steel switchboard). Both designs are equipped with transparent doors.  e controls are situated below these doors. Further, the VCS control unit can be produced as a built-in assembly and a part of an air-handling unit section, which must be designed for that purpose and meet specifi c requirements.
Controller HW and SW Concept
 e core of the VCS system is created by a powerful Siemens Climatix series PLC controller.  e control unit can be equipped with one of two POL4xx and POL6xx controller versions depending on the components used in the air-handling unit. Simultaneously, additional external input/output or commu­nication modules can be connected to the POL6xx controller.
Figure 1 – VCS control unit design
Control unit box Screws Circuit breakers Disconnecter Master switch HMI-SG controller
For local control, the HMI-SG POL822/60 hand controller can be used.  e control unit allows up to 8 basic control sequences to be used depending on the air-handling unit confi guration.  e order of some sequences can be changed (e.g. heating-mixing damper or cooling-fan cooling).  e heat pump or electric a er-heater can be separated from basic sequences in the so-called extra sequences. If this is the case, another sensor must be used in the air inlet, and a special set-point must be set for this type of control.  is feature can only be used a er prior consultation with the manufacturer.  ese units are delivered adapted to individual applications so they will provide exactly those features needed for the operation of a specifi c air-handling device.
Control
Local control
 e basic VCS controllers are devices (manual controllers with bus connection) for so-called local control of the control unit (see fi g. 2):
a) Room controller - HMI-SG (POL822/60) b) Comfortable universal alphanumeric driver
- HMI-DM nebo HMI-TM
Note: For details, see controllers instructions part of the manual.
Distant control
In addition to local VCS controllers, so-called remote control can be used. For this control, you need to connect VCS to LAN, WAN or Internet (For production, the control unit must be confi gured/ordered with the required functionality). a) HMI@WEB - You can use the HMI @ WEB controller via the web interface.  e controller fully complies with the local HMI-DM and TM controls. b) Mobile app (see fig. 3) - You can use simple touch application for smartphones or tablets with Google Android (v. 4.0.3 and higher). c) SCADA web interface Monitoring and operation using the device’s technological scheme with operating parameters, respectively using the tabular interface of an internet browser on a PC. For details, refer to page 58.
3
Figure 2 – HMI-SG (-DM, -TM) controllers
Figure 3 – Mobile application
HMI-SG
Figure 4 – VCS control unit internal structure
Other controls (technological)
For basic control (triggering, mode switching) from a technology or a very simple manual button / switch control, you can use "Other Controls". External control via one or two non-voltage contacts.
Control from parent system
When integrating HVAC with the VCS control unit into complex building management systems (BMS), it is also possible to connect to these systems. Subsequently, it is possible to control and monitor the HVAC through them.  e ModBus, LON, and BacNet standards can be used. The different types of control must be designed when designing (confi guring) VCS into the project and especially in production - the usability of remote control and connectivity to the BMS are dependent on the use of the corresponding controller.
Detailed descriptions of all controller types, control and their use - see separate sections / chapters of this manual.
HMI-TM
Control
HMI-DM
Power Part
 e power part, like the control part, is always "tailored" for a specifi c air-handling unit.
Connecting terminals
Connecting terminals
Controller Siemens Climatix
4
Design
Table 2 – List of connecting cables (example)
Cable No.
Figure 7 – Component wiring (example)
Figure 6 – Summary of connected components (example)
Boxes
Indoor VCS control units are built into plastic or sheet metal cabinets with front transparent doors under which controls are located.  e permissible ambient temperature is 0 ° C to + 40 ° C. VCS in exterior design are built into sheet metal cabinets with full front doors under which controls are located. In the confi guration so ware we can design: range of average temperatures -40 ° C to 35 ° C, cabinet mounting (hanging / stand), door design (le / right), lighting, service drawer (select according to customer's destination). A space of minimum 15 cm must be le on each side of the box to allow access for cooling air and for changing the fi lter which is fi tted in front of the fan. As a standard, we provide a door lock and a box for storing unit documents. Depending on the particular confi guration of the control unit, these enclosure dimensions are used (Table
1).  e electrical enclosure of the plastic case corresponds to
IP 65 with the door closed and IP 40 when the door is open.  e electrical cabinet cover is IP 55 or IP 66 (depending on enclosure type) when the door is closed and IP 20 when the door is open.  e metal enclosure with additional ventilation is IP54 with the door closed and IP 20 with the door open. The VCS control units can be mounted directly on the Flammability Levels A and B according to EN 13501-1. Additionally, the VCS control unit can be manufactured in an integrated design as part of the ventilation unit section. One of the options is a built-in section for assembled VZTs, which includes adjustments for the environment.  is section is used when designing VZT with IP44 protection as well for outdoor units (with heating or cooling of the control unit).
Table 1 – box dimensions in mm
If needed, the boxes, sized 2000 × 800 × 400 mm and 2000 × 1000 × 400 mm, can be fi tted with a ventilation set – a fan and a louver in opposite corners.
VCS
ACX36/RMK
Figure 5 – Installation in the XP unit section
Design
 e control system design is based on the selection of re­quired features and on its internal confi guration.  e design is performed automatically using the algorithm integrated into the design so ware also used for the air-handling unit design.  e design output provides an exact specifi cation of the control unit, including the following individualised lists for a specifi c device:
n Summary of connected components n Wiring diagrams of all components n List of all recommended cables for the connection of all
components (the cables must always be used in accord­ance with the electrical equipment project documenta­tion).
Version Height Width Depth Usual application
Plastic 610 340 160
Vento, FP, some XP (single-speed)
Plastic 610 448 160
Vento, FP, some XP (single-speed)
Plastic 842 448 160
Vento, FP, some XP (single-speed)
Sheet-steel 800 550 250 XP, sophisticated Vento assemblies Sheet-steel 1200 750 300 XP Sheet-steel 1600 750 300 XP Sheet-steel 2000 800 400 XP Sheet-steel 2000 1000 400 XP
(Recommended) cable type Power Supply Cable length Note
a) AeroMaster XP b) CAKE
5
Figure 8 – Example of access to the unit
max. 700 m
HMI-SG
Documentation
Control Unit Designation
 e control unit designation is always created by a unique code (generated by the AeroCAD design program for the control unit calculation and design), which is only included in the accompanying technical documentation (not on the control unit), and by the serial number (for communication with the manufacturer).
Documentation
VCS control systems can be installed and used only in accord­ance with the delivered documentation.
Documentation List
n Product Installation and Operating Instructions n Control system confi guration (summary of connected
components), terminal diagram and list of recommend­ed cables – device printout from the AeroCAD design program
Additional – General Documentation
 e system or device documentation also includes the oper­ating and inspection documentation kept during the device service life and the Service Regulations, for which the user is responsible.
Service Regulations
Before putting the air-handling device into permanent opera­tion, the device user in collaboration with the designer, or the supplier, must issue service regulations in accordance with local regulations. We recommend including the following in these service regulations:
n Air-handling device assembly confi guration, its intend-
ed use and a description of its operation in all operating modes
n Description of all safety and protective elements and
their functions
n Summary of the health protection principles, safety and
operating rules to be observed when operating the air­handling equipment
n List of requirements for operating staff qualifi cations and
training, nomenclature list of personnel authorized to op­erate the air-handling device
n Detailed emergency and accident instructions to be fol-
lowed by the operating staff
n Operating particularities in diff erent climatic conditions
(e.g. summer or winter operation)
n Inspection, checking and maintenance schedule, includ-
ing a list of checking steps, and their recording
Documentation Availability
 e documentation delivered with the control system (original) and operating documentation must be permanently available for the operating and service staff and stored near the air­handling equipment.  e Installation and Operating Instructions are also available at the website: https://www.remak.eu
Warning
 e manufacturer reserves the right to make changes and amend the documentation due to technical innovations and changes to legislation without prior notice. Information on
changes and updates are always available at the website https://www.remak.eu
Safety Measures
n VCS control units are manufactured in accordance with
valid regulations and technical standards.
n VCS control units must be installed and used only in ac-
cordance with this documentation.
n Any damage caused by improper use contrary to this
documentation is the responsibility of the subject who failed to observe the instructions included in this docu­mentation.
n When handling, installing, wiring, commissioning, repair-
ing or servicing the air-handling units, it is necessary to observe valid safety rules, standards and generally recog­nized technical rules.
n In particular, it is necessary to use suitable tools and per-
sonal protective work aids (e.g. gloves) because of sharp edges and corners, respectively voltage, when perform­ing any handling, installing, dismounting, repairing or checking.
n Any changes or modifi cations to individual components
of the VCS control unit which could aff ect its safe and proper functioning are forbidden.
n  e air-handling equipment confi guration and documen-
tation must not be changed without the prior consent of the manufacturer.
n  e VCS control units, including their individual
parts, are not intended, due to their concept, for di­rect sale to end customers. Each installation must be
performed in accordance with a professional project cre­ated by a qualifi ed designer who is responsible for the proper selection of equipment concerning its suitability for the given application.
n All connections of the equipment, including the VCS con-
trol unit, to the power mains must be performed in ac­cordance with applicable local wiring standards and reg­ulations.
n Wiring installation, commissioning, maintenance and re-
pairs may only be performed by a specialized assembly company, respectively an authorized person duly quali­fi ed in accordance with generally valid regulations.
n Before installing and using the air-handling units, it
is necessary to familiarize yourself with and observe the directions and recommendations included in the following chapters.
HMI-SG
6
Conditions for Handling
e device can only be commissioned, operated and serviced by qualified personnel.
n e VCS control unit can only be operated by person-
nel provably trained and warned about possible dangers (by the manufacturer or authorized representative of the manufacturer) in accordance with the applicable Service Regulations for the air-handling unit.
n It is forbidden to remove, bypass or disconnect the safe-
ty equipment, safety functions and guards.
n Only air-handling components in perfect condition can be
used. Failures affecting the equipment safety must be re­moved immediately.
n All safety measures against electrical accidents must be
strictly observed. Any action resulting in restriction, even temporary, of the safety and protection functions must be avoided.
n It is strictly forbidden to remove safety guards, casings
or other safeguards, operate the equipment or its com­ponents if the safeguards are disabled or restricted.
n Any action resulting in restriction of the prescribed insu-
lation of the safety voltage must be avoided.
n When changing fuses, it is necessary to ensure the non-
voltage state of the control unit and use only the speci­fied fuses and protection elements.
n It is necessary to eliminate electromagnetic interference
and the harmful effects of over-voltage on the signal, control and power cables, which could unintentionally ini­tiate dangerous actions and functions or cause destruc­tion of the electronic parts in individual components.
n Never work on the connected equipment under voltage!
Before starting work on the air-handling unit, switch off and lock the master switch to disconnect the supply volt­age. Use protective and work aids in accordance with the Service Regulations and standards applicable in the country where the unit is installed.
n If individual technical assemblies of the air-handling unit
are equipped with service switches, and if allowed by the Service Regulations, installation conditions and charac­teristics, then such assembly (e.g. heater, fan, etc.) can be disconnected by switching off and locking the corre­sponding service switch.
n Never use abrasive cleaners, cleaners unsuitable for plas-
tics or acid or alkaline solutions to clean to unit.
n Avoid splashing water, impacts and vibrations.
Each air-handling equipment component must always be installed in accordance with the appropriate installa­tion instructions. e manufacturer recommends fully ensuring the flaw­less condition and functioning of all protective elements and equipment. Aer failures, such as short circuits, have been removed, check the functionality of the automatic circuit breakers and protective elements, and verify the condition of the protective wiring interconnection and grounding.
To ensure safe operation, it is necessary to verify the con­ditions of the water heating/cooling pumps – perform manual pump turning and set the output curve (over-de­sign impairs the control quality).
Warning: If the remote control is used (including automatic schedule program), safety access must be ensured for each physical interference or entry into the air-handling unit (inspec­tion, maintenance or repair) – i.e. disconnect the power supply by turning off the switch – avoid remote initiation of the unit by other users when work is being performed on the unit.
Transport and Storage Before Installation
VCS control units are packed in cardboard boxes or installed in the corresponding air-handling unit section, if they are integrated into the air-handling unit. Measures for handling fragile goods must be taken when handling the unit. e units must be stored in rooms complying with the fol­lowing conditions:
n Maximum relative air humidity must not exceed 85%,
without water condensation
n Ambient temperature between –25°C and +60°C
Dust, water, caustics, corrosive agents or other materials negatively affecting the structure or the unit’s components (causing degradation of plastic parts and insulation) must not enter the unit.
Installation and Location
e VCS control unit location must provide good access for the operating personnel and easy connection of the cables. e installation site must be flat without rough spots. When planning the air-handling unit location, it is necessary to keep sufficient space for maintenance, service and operating. Check the completeness and intactness of the delivery in ac­cordance with the bill of delivery before installation. ese control units are designed for normal (indoor, dustless, dry, non-explosive) environments. ey can be mounted on A and B combustibility grade materials in accordance with EN 13501-1. Permissible ambient temperature: +0 °C to +40 °C (24h aver­age must not exceed +35 °C) e VCS control units in the switchboard boxes are mounted in the vertical position directly on the wall. e KAEDRA plastic switchboard box can also be partially embedded under plaster. e VCS unit installed in steel switchboard boxes can also be placed directly on the floor. e cables can be run along cable trenches, cable trays or under plaster. e power cables are connected from below. We recommend the wall-mounted units be fixed to the wall using dowels and screws suitable for the wall structure.
Manipulace, transport, umístění
n e air-handling equipment can only be operated in ac-
cordance with the applicable Service Regulations. e operating staff must comply with the requirements in­cluded in the Service Regulations, respectively with the manufacturer's requirements (authorisation for some service activities).
n To avoid unintentional unit start-up, the master switch
must be switched off and locked when repairing the VCS unit.
7
Note: As appropriate, the above-mentioned instructions ap­ply also for control units integrated into the air-handling unit while observing the control unit installation and operating instructions delivered with the air-handling unit.
Check the completeness and intactness of the delivery in ac­cordance with the bill of delivery before installation.
Commissioning
Fitting and Wiring Check
A careful check and verification of the wiring of all control system components in accordance with the attached unit wiring diagram must be performed before the first start-up. e system cannot be connected to the power supply until these checks have been performed. First of all, it is necessary to check the presence, locations and connections of the temperature sensors, fan thermo-contacts and heaters in accordance with the M&C project. Further, the connections of all error inputs must be checked. It is also essential to check the fans, electric heaters, heat ex­changers, filters and other parts of the connected air-handling unit for correct fitting in accordance with the air-handling accompanying documentation. e above-mentioned checks must include a functionality check of each component. Special attention must be paid to the check of the conduc­tive interconnection of all parts of the air-handling unit and associated devices.
Conditions for Connection
e connections must be performed in accordance with the applicable local wiring standards and regulations. Before put­ting the unit into operation, an initial wiring inspection must be performed in accordance with the national regulations.
Settings
e VCS control unit has been manufactured according to the customer’s requirements (the project), and the basic param­eters have been pre-set so that the unit is ready for operation. With these settings, the control unit will start and begin the control for the pre-set parameters providing the connection of the unit has been performed correctly. However, the professionals performing the unit commissioning must always check or adapt the air-handling unit’s operating parameters to the specific design and behaviour of the control system and operating or local conditions.
It is especially necessary to pay attention to the control constants and parameter, various correction values, temperature modes and time schedules, optional modes and functions.
e data points are accessible through the HMI control panel. Setting the user access levels is an important part of the settings procedure. e default factory settings must be re-set according to the user and service company needs. e Access passwords are the basic pre-set parameters which need to be reset when commissioning the unit, see the chapter Control (HMI-SG).
Additional Settings:
n To optimize the interaction between the control unit and
peripheral devices, it is necessary to set, using the HMI­SG controller (see the List of Data Points in the section Settings – Control Signal Characteristic), correspond­ing values of the analogue signals for heating, cooling, heat recovery and gas heating, optional from 0–10 V and 2–10 V (pre-set). e values 2–10V are suitable for REMAK or Belimo ac­tuators.
Room temperature Measuring Point Selection
n Up to two room temperature sensors can be installed in
the air-conditioned room (HMI-SG controller with an inte­grated temperature sensor plus one additional temper­ature sensor, or two HMI-SG controllers with integrated temperature sensors). e final room temperature val­ue for the control can be set as the minimum, maximum or average of both sensors (see the List of Data Points -
Temperature Measuring Point Selection). Selection of the specific point for adjusting or measuring the temperature value entering the control process results in more accurate setting of the room temperature.
Warning
e device parameters are structured and made available to users in accordance with their user roles (access levels). ese roles must be assigned to the users according to their expertise and responsibility for device operation.
Basic Application Parameterization
n Default and common operation parameterization is de-
scribed in the chapter Control (see particular controller).
General Overview of Parameters
For a general overview of parameters available in the menu and access authorization of users, refer to the chapter VCS – Parameter Overview and Default Factory Settings. For the menu with HMI controller parameters and default values, refer to the chapter Control (HMI-SG).
Important Notes
Correct assembly, installation, commissioning and proper control are the essential conditions for flawless and safe operation of the control unit. e components connected to the control unit must correspond with the specification in the control unit documentation. e procedures specified by the manufacturer in the unit documentation and the Service Regulations measures must be observed throughout the unit service life.
Commissioning
8
Location of Control System Sensors
Inlet Air Temperature Sensor (NS 120)
Control and anti–freeze sensors must always be situated behind the heater, respectively cooler – to measure the sup­ply air temperature. ey must not be situated in the room.
VO antifreeze protection sensor (NS 130R)
e return water temperature sensor must be situated in the return water line from the water heater so that it will be sufficiently bathed in water. e heating water circuit must ensure all the required functions for the water heater control and safety when the unit is shut down (filling the system with antifreeze mixture) as specified in the air-handling device project documentation. A capillary tube can be used as additional antifreeze protection. If it is not installed on the air-handling unit by the manufacturer, the capillary tube must be run (meandering way) through the entire cross-section of the water heater’s rear side.
Outdoor air temperature sensor (NS120)
Ideally, it should be situated in the outside environment – only then are the control system’s functions ensured even in the STOP mode or immediately aer unit start-up (e.g. moderate pre-heating of the exchanger based on the actual outside temperature, etc.). If the sensor is situated in the fresh air inlet duct inside the building, the measured temperature is only correct when the fans are switched on (air flows) and the starting conditions are negatively affected – which can endanger the air-handling device’s safety and even result in the water heat exchanger breaking down.
Outdoor Temperature Sensor – installed outside (NS110A)
e sensor (as with any thermometer) must be installed so that objective outdoor temperature measurement will be achieved. It must be protected against negative effects like sunshine, rainfall, frost deposits, e.g. situating it under a building’s roof, using outdoor VZT roofs, situating it in the inlet louvers, inlet ducts or separate covering roof.
Room Temperature Sensors
Optionally, a room (NS100), duct (NS120) or HMI-SG control­ler integrated sensor can be used by the designer.
Commissioning
EO Pre-Heating Control Temperature Sensor (NS 120)
To ensure correct control, the sensor must be situated behind the electric pre–heater (EO) – before other temperature adjusting components.
Flue Gas Temperature Sensor
e Pt 100 sensor is used to measure the flue gas tempera­ture. e sensor must be situated in a representative place within the flue gas installation.
Inlet Air Humidity Sensor
is is a duct sensor which must always be situated in an inlet branch aer the air-handling unit. e selected position must be representative enough for the measured value. It must not be situated in the room.
Room Humidity Sensor
Optionally, a room or duct sensor can be used by the designer.
n e room sensor must be situated in the room in a "rep-
resentative" place so that it will not be influenced by local effects (windows, doors, etc.)
n e duct sensor must be situated in the outlet duct from
the room – the advantage here is that the mean humidity of the room outlet air is measured.
TH 167 Gas Heating Safety ermostat
e sensor must be situated before the gas heater section behind the fan section. e thermostat must be situated so that it will start the fans to protect the air-handling compo­nents situated in front of the gas heater chamber if back air flow occurs.
Air Quality Sensor – CO2 (VOC, CO)
e air quality sensors are placed in the outlet air duct or in the "representative" spots, thus ensuring objective air quality value measuring.
Connection of the fan frequency inverters, heat exchanger to the Modbus bus
Safety Conditions
n Properly carried out transport, storage, installation, com-
missioning and careful handling is the main condition for correct and trouble-free operation.
n Protection, switching, wire routing and grounding must
fully comply with the local regulations applicable for wiring.
n e 230/400 V AC power wiring must be strictly separated
from the signal wiring (e.g. 24 V AC SELV)!
Figure 9 – Room sensor installation
•  e room sensor or HMI-SG controller with integrated room sensor must be situated in a spot "representing" the room tem­perature, and they must not be affected by local effects (heaters, windows, vertical temperature distribution in the room, etc.)
•  e duct sensor must be situated in the room outlet duct – the advantage in this is that the average temperature of the air flowing from the room is measured without being affected by local effects (and it is hidden).
Heat Exchanger's Antifreeze Protection Sensor (NS 130R)
e sensor must be situated in the outlet air duct behind the heat exchanger.
9
Control and Protection Functions
Wiring
n A shielded conductor must be used for the Modbus bus
connection.  e maximum conductor length depends on the communication speed. A maximum length of approx. 1000 m is recommended for the baud rate of 9600 Bd.  e recommended conductors are included in the documentation created by the AeroCAD design program.
n  e controller is connected to two terminals marked A+
and B- and to the REF signal detection reference voltage terminal, which must always be interconnected with other participants on the bus.
n To ensure correct functioning of the bus, the fi rst and last
device on the bus must be fi tted with a terminal resistor.  e fi rst device, i.e. the master controller, terminal resistor setting is performed using the so ware (ensured by REMAK in the factory).  e last device terminal resistor setting is performed on the last frequency inverter in the line connection. Refer to the Modbus bus wiring diagram.  e setting procedure of the last terminal resistor is described in the documentation for a corresponding frequency inverter. A 120 Ohm resistor connected between the communication can also be used to terminate the wiring.
Fan Failure Detection
n To detect any fan failure, the motor thermo-contact and
diff erential pressure sensor are connected to the frequency inverter inputs.  e information provided by these elements is transmitted through the Modbus communication line to the control system, where it is processed.
Modbus RTU Communication Settings
n Each frequency inverter connected to the bus must be
assigned a unique address as defi ned in the control system data points.
Pre-set Frequency Inverter Addresses – ModBus:
Inlet Fan
Inlet fan address =1 Backup or twin fan address =2 Backup twin fan 1 address =3 Backup twin fan 2 address =4
Outlet fan
Outlet fan address =5 Backup or twin fan address =6 Backup twin fan 1 address =7 Backup twin fan 2 address =8
Figure 10 – Inverter connection to the Modbus RTU
Figure 11 – Inverter association with a corresponding
section
terminal resistor
RS485
FM1
Master controller
FM2 FM3
Warning
e frequency inverter association cannot be exchanged between diff erent sections! For information about frequency inverter association with a corresponding section, refer to the fi gure.
Auxiliary Fan
Auxiliary fan address =9 Twin fan address =10
Rotary Heat Regenerator
RHR motor address =11
n  e data points of all frequency inverters for communica-
tion with the Modbus bus must be set in accordance with the VCS control unit:
•  Baud rate (9600 Bd – pre-set)
• Parity (none – pre-set)
• Number of stop bits (2 stop bits – pre-set)
• Response time limit
• Number of data bits (as standard, 8 bits – pre-set)
All data points for the used frequency inverters are available on our website: www.remak.eu
Corresponding
section number
Order
number
5
0064 / 5
00
64 / 5 64 / 5
0064 / 5
10
Main Control Feature and Protection Description
Using the appropriate sensors, the VCS control unit can provide comprehensive protection of the air-handling unit, such as active antifreeze protection, fan state monitoring, filter fouling or over-temperature detection of the required temperature. Any deviations from the defined states or parameters are monitored and signalled and simultaneously, safety features are activated. Depending on the failure consequence, the following happens:
n e failure is only signalled and safety features are automati-
cally activated. Once the failure has ceased, the unit will return to the standard mode without interference from the operator.
n If a serious failure occurs, the unit will be switched to
the STOP mode, and it can only be restarted after the failure has been removed and the operator's interference. e VCS control unit system enables the air-handling unit behaviour (fan action) to be set when fire is detected (external failure, inlet or outlet air high temperature). The settings can be as follows: the inlet or outlet fan is activated, both fans are activated or both fans are stopped (air-handling unit shutdown). e control unit is switched to the fire mode. e settings can be performed using the HMI controller in the List of Data Points, section Checks, System and Network Settings – Fire Alarm.
Heating Control
Control is based on the required temperature, i.e. the selected temperature mode and data from the supply air temperature sensors, outdoor temperature and the water heat exchanger return water temperature. Control can be affected by cor­rection values, maximum and minimum limits or antifreeze protection.
Water heating
It is controlled by the SUMX mixing set actuator using a 0–10V continuous control signal (working range of 2–10V).
Heating Mixing Set Pump Control
e mixing set pump is controlled depending on the outdoor temperature value and valve position (required heater output).
n If the air-handling unit is in the STOP and Run mode, the
pump is switched on when the outdoor temperature drops below 5°C and switched off when the outdoor temperature rises above 6°C. In this case, the pump is stopped without any run-down.
n If the air-handling unit is in the Run mode, the pump is
controlled by the valve actuator control algorithm. e pump is switched on when the request for the valve opening is higher than 5%.
n If the pump has not been used for 168 hours, it will be
switched on and turned for 60 seconds.
n Failures (electrical) of the pump are sensed by the pump
circuit breaker’s auxiliary contact even in the STOP mode.
Water Heater Antifreeze Protection Operation
e VCS control unit uses so-called active antifreeze protec­tion. It uses a three-stage concept. Antifreeze Protection Features:
Control and Protection Functions
Note: is chapter describes only the basic control functions – the detailed design, respectively compatibility, of the entire device is ensured by the configuration performed using the AeroCAD design soware. For more detailed information, contact the manufacture, REMAK a.s.
Main Control Features
e VCS control unit enables automatic control of the follow­ing basic functions for air temperature adjustment:
n Heating n Cooling n Mixing n Recuperation (Heat Recovery) n Dehumidification n PID controllers with pre-set control constants are as-
signed for all the above-mentioned functions. Basic settings of parameters are performed in the factory. e parameters can be changed using the HMI controller in the List of Data Points menu, item Control Constants.
n A check, respectively optimization, of the unit settings must
always be performed when commissioning the unit.
n Control ensures energy-saving operation. Cascade tem-
perature control – room temperature control or supply air temperature control.
n e required temperature for the air-conditioned room
can be set by selecting one of two temperature modes. Each mode has two pre-set temperature values to maintain the required temperature (an upper limit for heating and a lower limit for cooling). ese values can be changed using the HMI controller in the List of Data Points, section Settings – Tem­perature Modes.
n First, the control algorithm will start to control the functions
which don't require energy, i.e. heat-recovery and mixing (de­pending on the user option). If this is not enough to maintain the required parameters or these features are not included in the air-handling unit, heating and cooling functions will be ap­plied. If the heating or cooling control is not effective enough, an air output control will be added (heating/cooling-dependent fan speed compensation – user option). is control does not allow heating and cooling to be used at the same time, only one control sequence can be used at a time. is does not apply for special control application with controlled humidifi­cation where a cooler can be used for dehumidification and a heater for aer-heating to the required temperature.
Heat pump, water and electric heater or gas heater functions
can be connected to the heating control sequence. Heat pump, water cooler and condenser unit functions can be connected to the cooling control sequence.
Temperature Correction and Limitation
The control unit enables adjustment and settings of the restricting limits for maximum and minimum supply air temperatures. In addition, it is possible to set the supply air and room temperature limits, respectively other correction or comfort options (e.g. set-point value compensation or heat­ing/cooling-dependent fan speed compensation).
Control and Protection Functions
11
n Switching of the unit to the STOP mode n Switching off of the fans n Closing of the dampers n Freezing danger signalling n Mixing set control n Pump starting n If the air-handling unit is in the Run mode, then antifreeze
protection is activated when the outdoor temperature drops below 10 °C (factory settings) and the water heat exchanger return water temperature drops below 15 °C (factory set­tings). e extent of the mixing valve opening depends on the water heat exchanger’s return water temperature value. Antifreeze protection will be deactivated when temperatures rise above the limit parameters.
n If the air-handling unit is in the STOP - STAND-BY mode,
then antifreeze protection is activated when the outdoor temperature drops below 10 °C (factory settings) and the water heat exchanger’s return water temperature drops below 30 °C (factory settings). e extent of the mixing valve opening depends on the water heat exchanger’s return water temperature value. Antifreeze protection will be deactivated when temperatures rise above the limit parameters.
n e control unit continuously monitors the water heat
exchanger’s return water temperature. If the temperature is still falling and drops below 8°C (factory settings), the following protection actions will be immediately taken regardless of the outdoor temperature:
n e air-handling unit will be shut down, the dampers will
be closed, the fans will be switched off and the failure alarm will be activated.
n e mixing valve will be opened depending on the water
temperature, and the circulation pump will be switched on.
n e above-mentioned state will last until the operator
checks the air-handling system or removes the failure cause and confirms the air-handling system is free of failure and resets the failure.
n e control unit simultaneously monitors the supply air
temperature in the Run mode. If the supply air temperature drops below 6 °C (factory settings), the following protection actions will be immediately taken regardless of the outdoor temperature:
n e air-handling unit will be shut down, the dampers will
be closed, the fans will be switched off and the failure alarm will be activated.
n e mixing valve will be opened depending on the water
temperature, and the circulation pump will be switched on.
Pre-Start Unit Pre-Heating Functions
n To avoid false freezing danger assessment in winter or
during transition seasons, especially when the air-handling unit is being started, the control unit features a heating circuit pre-heating.
n Pre-heating is dependent on the outdoor temperature
value. If the outdoor temperature is higher than 10 °C, the value of the valve opening will be 0 %, and pre-heating will not be activated. Pre-heating will be activated when the outdoor temperature drops below 10 °C. e mixing set valve will be forced to open to the value which is derived from the outdoor temperature (factory settings: +10 °C = +10 %, -10 °C = 100 %) for 120
Control and Protection Functions
seconds. Once this time has elapsed, the valve will be closed, "ramped down", until the mixing set control signal for heat­ing is reached.
n If the air-handling unit is restarted within 5 minutes of the
moment the air-handling unit was shut down, pre-heating will not be activated.
n Antifreeze protection setting parameters can be accessed
through the HMI controller in the List of Data Points menu, sections Parameters and Control Constants.
Electric Heating
Electric heating can be controlled using the following options:
n Switching of the full EO, EOS heater output n Sequential switching of the EOSX electric heater’s indi-
vidual sections
n Sequential switching of the EO heaters n Control of the EOS electric heaters using a PV valve (up
to 45 kW)
Electric heater protection
n If electric heater overheating (failure) is signalled (the
temperature inside the heater exceeds +80 °C) by opening the emergency thermostat contacts in the heater, this signal is interpreted by the control unit.
n Electric heater control in the REMAK unit is doubled – the
heater thermostat failure signal is simultaneously sent to the controller and auxiliary module.
n e controller will interpret the failure signal and perform
appropriate safety functions; first, the control signal for electric heating is blocked and then the heater contactor is disconnected.
n e auxiliary safety module will mechanically disconnect
the EO/S/X circuit breaker (i.e. it will trip the under-voltage trigger of the circuit breaker). At the same time, control logic will ensure safe cooling of the heater when the air-handling unit is being shut down – transi­tion to the STOP mode. e controller will ensure run-down of the fans (optional) so that the heating core is cooled.
Gas heating
e gas heater is controlled using a burner output controller and a bypass damper (if the section is equipped with a BP damper). The required heating temperature is controlled depending on the required temperature (selected mode) and the readings from the inlet temperature, outdoor temperature and flue gas temperature sensors.
Gas Burner Output Control
n Single-stage ON/OFF control n Two-stage control (two output stages) n Modular (three-point), step-less control of the entire burner
output range Burner lighting is contingent on the fan operation.
At a 5 % request for heating, the 1st burner output stage is switched on. e minimum pre-set running time of this stage is 150 seconds. If the required temperature is not reached, the 2nd stage will be switched on at 70 % of the request for heating (two-stage output control). e second output stage is not restricted to the minimum running time, and will be switched off at 40 % of the request for heating.
12
Control and Protection Functions
Further re-lighting of the burner is possible once the protec­tion time of 150 seconds has elapsed. Modular control of the burner is step-less based on the actual requirement (set point) within the Min to Max output range of the gas burner.
e bypass damper (if included in the section) is controlled by a 0-10V signal (the operating range is 2–10 V depending on the required flue gas temperature (160 °C pre-set). e regulat­ing damper position controls the air flow coming through the gas section and bypass section so that a constant flue gas temperature is maintained. Accordingly:
n when T
flue gas
> T
flue gas required
the bypass damper closes
(closed = 0 V) n when T
flue gas
< T
flue gas required
the bypass damper opens
(open = 10 V)
Protection and Safety Functions:
e control unit ensures fan run-down to cool down the gas sec­tions (the pre-set run-out time is 180 s). e gas section tem­perature is monitored by the ESD3J triple safety thermostat, which ensures the following protection and safety functions:
n If the temperature exceeds 50 °C, the fans will be switched
on, even if in the STOP mode.
n If the temperature exceeds 80 °C in the Run mode, the
burner will be stopped, the fans switched to the run-down mode and then the unit STOPPED; if the temperature exceeds 110°C, the burner will be disconnected from the supply volt­age. If back air draw (chimney effect) occurs during the STOP mode and the air temperature in front of the gas section rises above 50 °C, the TH 167 thermostat will close and switch on the fans, open the inlet and outlet dampers, and thus the gas section will be cooled down.
n Fan malfunction – the unit is immediately switched to the
STOP mode without fan run-out (evaluated also during the STOP mode)
Heating and Cooling using Heat Pump
Two general control options are available for heat pumps. Control is not fixed to a specific heat pump type. e control option selection depends on the designer’s consideration and heat pump type. Two control contacts and an analogue output are used for control.
Option A
e first digital contact is used to define the air temperature adjustment type – cooling/heating. e second digital contact is used to define the process activation – off/on. e analogue output 0..10 V represents the proportion of the request for heating or cooling.
Option B
e first digital contact is used to define the heating process – heating off/heating on. e second digital contact is used to define the cooling process – cooling off/cooling on. Analogue output 0..10 V represents the proportion of the request for heating or cooling. e heat pump control is equipped with an outdoor tempera­ture-dependent blocking. e blocking alert is only informative and is not a failure state. e heat pump will be shut down if the outdoor temperature is equal to or lower than the refer-
Cooling Control
All cooling sources can be disabled depending on the outdoor temperature. Cooling is not disabled if the outdoor tempera­ture is higher than the pre-set cooling enable temperature (pre-set 12 °C).
Water Cooling
It is controlled the same way as water heating. e mixing set pump is switched depending on the control signal for the cooling valve. If the air-handling unit is in the Run mode, the pump will be switched on when the control signal for the cool­ing valve is higher than 5% and switched off when the control signal for the cooling valve is lower than 1%.
n Pump turning for 60 seconds is performed aer every 168
hours of pump inactivity..
Direct Cooling
Direct cooling is controlled by switching the condensing unit output or by step-less control of the inverter condensing unit. If a single-circuit condensing unit is used, it will be switched on when 20 % of the control signal is required and switched off at 10 % (10 % hysteresis) of the control signal. If a double-circuit condensing unit, respectively two single-circuit condensing units are used, two stages will be switched. e first stage will be switched on when 20% of the control signal is required and switched off at 10% (10% hysteresis) of the control signal. e second stage will be switched on when 70 % of the control signal is required and switched off at 60 % (10 % hysteresis) of the control signal. Frequent switching of the single-stage condensing unit is eliminated by repeated cooling blocking for a certain time depending on the setting. To eliminate the simultaneous switching of both stages at a sudden control signal increase, the timing (duration of the first stage) is set.
Inverter Cooling Unit
It is controlled using the start enable signal and step-less compressor output control signal. e minimum operating time can also be set. e condensing unit will be switched on when 20 % of the control signal is required and switched off at 10 % (10 % hysteresis) of the control signal. e unit compres­sor speed is controlled using a 0–10 V control signal.
ence temperature (see the Data Points). e heat pump will be started if the outdoor temperature is higher than the reference temperature (with hysteresis of 3 °C). Frequent switching of the heat pump is eliminated by blocking of the cooling/heating restart for 120 seconds. e minimum operating time of the heat pump can also be set. When cooling/heating is required, the heat pump will be switched on at 20% of the control signal and switched off at 10% of the control signal (hysteresis of 10%). e low reference signal on the analogue output (0-10V) can be set in a range from 0% to 50 % of the control signal (pre-set 30 %, i.e. a 3-10 V control). e unit can be equipped with a function blocking the air-handling unit operation when defrosting the heat pump. e shut-off state of the air-handling unit is indicated on controllers. Aer the heat pump defrosting process has been completed, the air-handling unit operation will automatically be resumed. Furthermore, it is possible changing behaviour of different control signals, e.g. AO signal inversion (see Data Points).
13
Control and Protection Functions
Inverter Unit and Single-Stage Condensing Unit Combination
When cooling is required, the inverter will be switched on first and then the output will be raised to the maximum. Consequently, the single-stage condensing unit is switched on while the inverter output is lowered to 30 % of the control signal. If the request for cooling is still rising, the inverter output will be increased from 30 % up to the maximum level of the control signal. If the request for cooling is decreasing, the inverter output will start to decrease and will be switched off at 0% of the control signal. e single-stage condensing unit is still in operation. In this phase of control, time blocking of the inverter is ap­plied and simultaneously the single-stage condensing unit is prevented from being switched off. If the request for cooling is still decreasing once this time has elapsed, the inverter will be switched on with a maximum control signal and the single-stage condensing unit will be switched off. When the single-stage condensing unit is switched off, the inverter output will be at the maximum. en the inverter output is reduced in accordance with the request. us step-less control is ensured in the entire cooling capacity range.
Direct Evaporator Protection
is protection is ensured using the CAP 2M capillary thermo­stat, which disconnects the control signal in the event of ice build-up on the evaporator. If two evaporators are used, each of them will have its own thermostat.
Heat Recovery Control
Heat Recovery control of the rotary heat regenerator is en­sured by step-less control using the heat exchanger frequency inverter through the Modbus communication bus. e plate heat exchanger, respectively plate heat exchanger bypass, is controlled using a 0–10 V (2–10 V) continuous signal. 100% of the step-less control signal equals 100 % heat recovery, i.e. maximum speed of the rotary heat regenerator or closed bypass of the plate heat exchanger. A digital output for two­point control (ON/OFF) is another option – thus, for example, the glycol circuit pump can be switched.
Heat Exchanger Antifreeze Protection
n Rotary heat regenerator protection is ensured using the
NS 120 temperature sensor situated in the outlet air duct behind the heat exchanger. If the temperature drops below the pre-set ice build-up threshold, the speed of the rotary heat regenerator will be reduced. If the speed reduction is not enough to de-freeze the heat exchanger, the heat exchanger will be stopped. e heat exchanger speed reduction depends on the PID controller’s constant setting.
n Similarly as the rotary heat regenerator, control of the plate
heat exchanger is ensured using the NS 120 temperature sensor and bypass actuator control. If the temperature behind the plate heat exchanger drops below the pre-set ice build-up threshold, the bypass damper actuator will be activated and the damper will stay open until the ice build-up melts from the heat exchanger. A pressure loss sensor or a CAP 3M capillary probe can also be used in some cases. Protection of the plate heat exchangers without bypass can be ensured by a fan speed reduction.
Plate heat exchanger – air-handling unit run-out
In some cases, the run-out will be performed when the air-handling unit is stopped. is will ensure drying of the heat-exchanger and prevent the creation of conditions for the growth of microorganism. Temperature and humidity sequences are active during this run-out. This feature is conditioned by previous operation of the heat recovery and the outside air temperature. As default, this feature is switched off. For the change in all values, refer to List of Data Points – Fans.
Mixing Damper Control
It is ensured by step-less control of the mixing damper actua­tors using a 0–10V (2–10V) continuous signal. e signal is directly proportional to the air circulation, i.e. 100 % of the signal corresponds to 100 % of the required air circulation (0 % of fresh air). e maximum level of air recirculation (when the fans are running) is limited by the minimum (hygienic) request for fresh air. If the device is in the STOP mode, the inlet and outlet duct dampers are closed and the circulation damper is open.
Heat Recovery and Mixing Economy Control
If the temperature in the room (in the outlet duct) is lower than the outdoor temperature and a request for cooling simultaneously exists, the heat recovery and air recirculation functions will be automatically switched on at the maximum level to minimize the energy demand for cooling. is hap­pens if the temperature difference reaches 3 °C (the room temperature is lower than the outdoor temperature) while the temperature in the room (in the outlet duct) is higher than the required temperature and the difference between these two temperatures is at least 2 °C. Heat recovery and mixing functions will be switched off when the outdoor temperature is lower or equal to the room (outlet air) temperature, or the room (outlet air) temperature is higher or equal to the required room temperature. Heat Exchanger control function activation settings are described in the chap­ter Additional Operating Mode and Function Setting Options.
Heat Recovery and Mixing Control at Air-Handling Unit Start-Up
e starting outdoor temperature and time are set for heat recovery and mixing (see Data Points). If the outdoor tem­perature is lower than the pre-set value at the air-handling unit start-up, the heat recovery and mixing functions will be switched on at the maximum level.
Mixing Sequence Selection
e mixing sequence for heating control is optional – the pre­set sequence for heating is as follows: first, the mixing function is applied and if the request for heating still increases, then the heating function will be applied (pre-set). is sequence can be changed according to user needs, see the chapter Additional Operating Mode and Function Setting Options.
Humidity Control
e control unit evaluates the control signal for humidification or dehumidification depending on the room and inlet humidity sensors and the required humidity selected by the user.
14
Control and Protection Functions
Humidification
Humidification control can be ensured by two methods. Depending on the technology used, control for the required humidity can be performed by the VCS control unit or by an autonomous control (e.g., integrated into the humidifier). In the first case, humidity control is ensured by the VCS control unit. Settings of humidity set-points and control parameters are included in the VCS control unit. e same applies for dehumidification. us, full accord of dehumidification and humidification control is ensured and unsuitable settings of set-points cannot be made. Furthermore, all the necessary parameters and information can be found in the control unit controllers. e control unit sends the start command, the request for humidification output to the humidifier, and monitors humidifier failures. If autonomous control is used, the control unit sends infor­mation on the air-handling unit operation to the humidifier. In this case, control for the desired humidity is fully ensured autonomously by a specific humidifier. e control unit has no information about the state or output of the humidifier.
Dehumidification
Air dehumidification is ensured by water or direct cooling. In case of dehumidification, aer-heating is ensured by the heater, which is situated aer the cooler. e control unit evalu­ates the control signal for the air cooler and heater depending on the room sensors and the required humidity selected by the user. e humidity in the room can be set from 20% to 95%. If the air-handling unit is equipped with a water cooler or a condensing unit with an inverter, the humidification process can be controlled using 0–10 V (2–10 V) step-less control. If the air-handling unit is equipped with a one-stage or a two­sage condensing unit, the humidification process is controlled using step control. When cooling is active due to a request for dehumidification, air aer-heating is allowed (exceptionally) using the heater situated aer the cooler. If the request for heating is increased above 90 %, the request for dehumidification cooling is gradually reduced until the required inlet air temperature, respectively zero value of the request for cooling (at 100 % request for heating), is achieved – temperature control is prioritised to humidification.
Auxiliary Control Functions
Pre-heating function
Pre-heating is switched ON/OFF depending on the pre-set outdoor temperature value (pre-set 5 °C). e electric pre-heater (EO) is switched using a contactor. It is controlled according to the pre-set (required) temperature and compared with the temperature behind the preheater (measured by the NS 120 sensor). If the air-handling unit is switched off when the EO pre-heater is active, run-down of the fans will be performed. Failures are evaluated similarly as with EO heaters but the system is not shut down. Water pre-heating is controlled by switching the pump (not included in the REMAK delivery) depending on the request for pre-heating. Antifreeze protection is ensured by a temperature sensor (NS130R) situated in the water heat exchanger return line. If the water temperature in the water heat exchanger’s return line drops below the pre-set value, the freezing alarm
Figure 12 – Actual set-points with compensation (shi)
Control signal for controller
heating
H shi
cooling
C shi
Room set-point
TH1 ......Basic set-point of the required temperature for heating – upper heating limit
TH2 ......Actual/current set-point of the required temperature for heating – upper heating limit = (TH1 - shi H)
TC1 ......Basic set–point of the required temperature for heating – upper cooling limit
TC2 ......Actual/current set-point of the required temperature for heating – upper cooling limit = (TH1 -shi C)
H shi for heating set-points (A negative shi causes a reduction in the required temperature for heating.) C shi for cooling set-points (A negative shi causes a reduction in the required temperature for cooling.)
will be activated, including safety functions, and the air­handling unit will be stopped.
Auxiliary Aer-Heating Function with EOS
is function is applied when the main heater output is not sufficient (e.g. when water heating is shut down during tran­sition seasons, etc.) It is possible to restrict the maximum electric after-heater output for each output stage. Thus correct cooling of the heating rods is ensured (see the Data Points). e electric aer-heating function can also work as an independent sequence with its own settings of required temperatures. e electric aer-heating function is disabled in the following cases:
n When night chilling is active n During temperature start-up
Heating Water Source Switching
If this auxiliary function is active and the controller detects the need for heating water (request for air heating), the output for the heating water source (boiler) will be switched on – if the device is started in advance before the fans have been switched on. is function will only be applied if the outdoor temperature is higher than the pre-set value (factory settings: 15 °C) otherwise the output is switched on permanently. Cor­rect operation of the assembly must be ensured by suitable settings of the device start-up sequence parameters. To enable the heating water source switching function’s correct opera­tion, the outdoor temperature sensor must be installed so it will be able to read the actual outdoor temperature.
Figure 13 – Set-Point Compensation (Shi) Description and Settings
T3 .....Starting point for heating compensation
T4 .....End point for heating compensation
c ........Max. compensation value (delta T)
x.........Actual outdoor temperature
y.........Required heating set-point shi
T1 .....Starting point for cooling compensation
T2 .....End point for cooling compensation
C ........Max. compensation value (delta T)
X ........Actual outdoor temperature
Y ........Required cooling set-point shi
delta T (K)
Outdoor temperature (°C)
Heating compensation settings Cooling compensation settings
15
Control and Protection Functions
Temperature Required Value Compensation
Temperature compensation is actually a correction (shi) of the required value (set point) of the controlled (room) tempera­ture according to the outdoor temperature sensor reading, which adjusts (in addition to other correction values) the temperature specified in the temperature mode settings. It is mainly used to reduce differences between outdoor and indoor temperatures (to eliminate thermal shocks) and the energy demand of device operation. On the other hand, it can increase differences ("aggressiveness") in control, if adjusted reversely.
Note: e data point values on the controller are described in full text (not using abbreviations like TH1, TC1, etc.). Generally, minus control is also possible.
Fan Speed Compensation
e VCS control unit system enables the pre-set fan speed to be adjusted depending on the air temperature, air quality or mixing damper position using fan speed compensations.
T3 .....Starting point for heating compensation
T4 .....End point for heating compensation
c ........Max. compensation value (delta T)
x.........Actual outdoor temperature
y.........Actual fan speed shi for heating
the supply air temperature and comparing it with the required supply air temperature and then followed by fan output compensation. e compensation will be activated if the difference between the required supply air temperature and the actual supply air temperature is greater than the pre-set temperature hysteresis. e actual correction extent is related to the settings of the PID controller constants.
n Heating Compensation: It reduces the fan output and
thus sufficient supply air heating is achieved based on the smaller air volume (used to eliminate insufficient output of the heat exchanger).
n Cooling Compensation: It increases the fan output (higher
air-flow rate) and thus makes the room environment more comfortable, if cooling is insufficient. is type of compensation also enables a change to the priority cooling – fan. So the change in the fan speed is applied first and then active cooling is applied as the request for cooling is rising. e settings can be performed using the HMI controller, refer to the chapter Additional Operating Mode and Function Setting Options.
Air Quality-Dependent Fan Speed Compensation
e fan output can be adjusted depending on the measured CO2 (VOC, CO) content and the pre-set required value. If the CO2 (VOC, CO) content is higher than the pre-set (permissible) value, the fan speed will be increased. e compensation ex­tent is affected by the settings of the PID controller constants. e measured value range must be set depending on the sen­sor used. Further, the sensor characteristic (Normal ascending for CO2 and VOC or Inverse descending for CO) must be set. For the settings, refer to the Data Points.
Air Quality-Dependent Damper Position Compensation
Functionality is similar and the settings are common with the air quality-dependent fan speed compensation. e fan output or mixing damper position can be affected by the difference between the measured and pre-set required CO2 (VOC, CO) concentration in the room. e volume of fresh air will be increased if the measured value is higher than the required value. e volume of circulated air will be decreased. e compensation extent is affected by the settings of the PID controller constants.
Humidity-dependent Damper Position Compensation
If dehumidification using cooling is not sufficient (or not available), humidity-dependent mixing damper position com­pensation is the next step. is is adjusted depending on the required humidity and measured humidity in the room. If the measured humidity is higher than the required humidity in the room, the compensation will be activated.
Humidity-dependent Fan Speed Compensation
e fan output is controlled depending on the required hu­midity and measured humidity in the room. If the measured humidity is higher than the required humidity in the room, the compensation will be activated. e compensation function can either be set to increase or reduce the fan output.
e compensation functions can be enabled using the HMI controller, refer to the chapter Additional Operating Mode and Function Setting Options.
e sum of individual compensations creates a so-called total compensation which affects the fan speed change.
Outdoor Temperature-Dependent Fan Speed Compensation
e compensation adjusts the fan speed in regards to high or low outdoor temperatures. e fan speed is adjusted de­pending on the maximum heating or cooling compensation settings. A positive compensation value represents a fan speed increase. A negative compensation value represents a fan speed reduction.
Note: To make the compensation effective, it is necessary to set a suitable maximum compensation value if only one compensation is used.
Room (Outlet) Temperature-Dependent Fan Speed Compensation
e fan output is adjusted depending on the required room temperature and the measured room (supply air) tempera­ture. e compensation will be activated if the measured temperature is lower than the required temperature. Using the compensation function, the fan speed can either be increased or reduced.
Heating/Cooling-Dependent Fan Speed Compensation
e request for heating or cooling is evaluated by measuring
T1 .....Starting point for cooling compensation
T2 .....End point for cooling compensation
C ........Compensation value (delta T)
X ........Actual outdoor temperature
Y ........Actual fan speed shi for cooling
delta speed (%)
Outdoor temperature (°C)
Heating Compensation Settings (Winter)
Cooling compensation settings (summer)
Figure 14 – Fan Speed Compensation Description
16
Control and Protection Functions
Fan Speed Control
e VCS control unit enables either soware or manual air output control, i.e. the speed of the following fans:
n Single-speed fans (ON/OFF control) n Two-speed fans (two-stage control) n Single-speed fans’ backup (ON/OFF control) n Five-stage TRN voltage controllers n Fan frequency inverters using the Modbus bus – five-stage
control A standard control can be completed with a 3rd auxiliary fan which is controlled from the outlet or inlet fan depending on the control unit configuration.
Two-Speed Fans
e two-speed fans are always started using the first stage at the air-handling unit start-up. e transition time from the first to second stage can be adjusted. e transition time can also be adjusted for the reverse transition from the second to the first stage.
TRN Voltage Controllers
e control unit enables the voltage controllers to be con­nected and controlled in five output stages. Depending on the request, inlet and outlet control can be common or independ­ent. e required output stage is always set in common. If the fans are controlled independently, it is possible to set the outlet controller correction against the inlet controller (see the Data Point Settings – TRN Correction). However, the control unit must be specially manufactured for this function (depending on the customer request). Either the same cor­rection can be set for all the speed stages or for each speed stage independently. For the correction settings, refer to the chapter Optional Function and Mode Settings.
Frequency Inverters
For five-stage control devices, the request for the inlet and outlet fan speed is set in common. However, for frequency inverters, the request for the inlet and outlet fan output (0-100%) can be set separately for each stage (1 to 5) (see the Data Point Settings – Fans).
Single-Speed Fan Backups (ON/OFF Control)
e backup motor is started if the main motor fails. e backup is used either for the inlet or outlet fan, respectively for both. e motors are equipped with thermal protection (thermo-contact) and current protection. If the backup mo­tor has been started, it is not possible to restart the main motor without resetting the failure. e main and backup motor current protection has a delay pre-set. Switching from the main to backup motor is immediate without delay if the main motor fails.
Backup fan control via Modbus communication bus
Using the Modbus communication bus, the five-stage fan control enables a backup fan or a pair of backup fans to start up if the main fan fails. If the backup fan or pair of backup fans fails, the air-handling unit will be shut down. Information about air-flow failures and motor overheating is sent via the Modbus communication bus and signalled accordingly.
e fan speed control parameters are available through the HMI controller in the List of Data Points in the section Settings – Fans (inlet fan backup, outlet fan backup, TRN correction).
Constant Air Flow/Pressure Control
When designing constant flow, pressure, overpressure and underpressure control, it is advisable to consider the overall design of the air-handling unit, respectively application of the mixing damper, and how the control behaviour can affect the measured pressure value.
Constant Air Flow Control
Fan speed is controlled depending on the desired air flow rate (m3/h). e air flow rate (air pressure in the diffuser recalcu­lated to the air flow rate using the "k-factor") is measured by a sensor; the control system evaluates this value and compares it with the required value. e resulting fan speed is controlled so that the required air flow rate will be reached at the point of measurement (fan diffuser).
It is necessary to set the following pressure sensor pa­rameters (see the Sensor Operating Manual):
n Mode (for CPG = Mode 5.00) n Measuring range: As needed
e correct range can be determined using a formula: (where k = "k-factor", Vmax = designed air flow rate of the device). e correct sensor range is then set according to the calculated pmax value.
n K-factor of the respective fan
It is necessary to set the following parameters of the VCS control Unit (see List of HMI Data Points):
n Air flow sensor measuring range – (maximum value from
the CPG air flow sensor in m3/h)
n is can be calculated using the formula or read from the
CPG sensor menu (see the Sensor Operating Manual).
n e maximum measured air flow rate can be calculated
according to the following formula: V
max
= k × DP
max
Example: K-factor = 308, Maximum sensor range Pmax = 2000 Pa, Vmax = 13774 m3/h. is value is then entered as the maximum range of the sensor in the VCS using HMI.
Note: In AC, the "Max. Air Flow Rate" is stated for the fan as­semblies. Attention! is is not the maximum range of the air flow sensor to be entered in the VCS control unit.
Dp
max
=
V
2
max
k
2
Figure 15 – Constant Pressure Control
17
Basic Information on VCS Operating Modes
Operating states
ere are three operating states defined for VCS control units (Stop, Run, Auto):
Stop – e device is in standstill mode (fans stopped). Impor­tant safety features like antifreeze protection and moderate pre-heating of the water heater are retained.
Run – e device is started in accordance with the pre–set temperature mode and fan speed.
Auto – Control is switched to the next operating mode with a lower priority. e Auto operating state cannot be set in the time schedule mode because it is a control type with the lowest priority.
e operating mode determines which operating state will be active according to priorities (see Operating Modes).
Operating Modes
e control unit’s operating state (i.e. whether the air-handling unit is in the Stop or Run state) is determined by one of the operating modes (manual control, external control, HMI-SG controller, BMS or time schedule modes). HMI-DM or HMI-TM controllers affect control in the manual control mode. External control is performed by single- or two-contact control. BMS control enables control of the control unit by the higher level control device (e.g. smart building control systems; Note: pending). To control air handling systems, the HMI-SG control­ler is connected to the control unit.
e operating mode which will determine the device’s oper­ating state (Run or Stop) is determined by the priority. Each operating mode is assigned a priority, i.e. the first option to control the control unit, to eliminate mutual interference. e operating modes are prioritized as follows, from the lowest to highest priority:
n Manual control
n External control
n Local HMI-SG controller
n BMS (pending)
n Time schedule
n Additional operating modes
e priorities and entire control system are shown in the diagram on the following page.
Control and Protection Functions
Figure 16 – Constant pressure control
Constant pressure control
Fan speed is controlled depending on the desired air pressure (Pa). e air pressure is measured by a sensor; the control system evaluates this value and compares it with the required value. e resulting fan speed is controlled so that the required air pressure will be reached at the point of measurement.
It is necessary to set the following air flow sensor param­eters (see the Sensor Operating Manual):
n Mode (for CPG = Mode 4.00) n Measuring range: As needed (200 Pa, příp. 1000 Pa)
It is necessary to set the following parameters of the VCS control Unit (see List of HMI Data Points):
n Air pressure sensor measuring range – (maximum value
from the CPG air pressure sensor in Pa)
n Required values (separately for the inlet and out-
let fans). 5 required values are available for selection.
Constant Air Flow + Overpressure in the Room Control
e inlet branch (fan) is adjusted to the constant air flow so that the required air volume is delivered to the room. e outlet branch is adjusted to the required difference in overpressure in the room. us, the outlet fan is adjusted to the required pres­sure (overpressure) depending on the pressure sensor location.
Application: Preventing dirt from entering the room.
Constant Air Flow + Underpressure in the Room Control
e outlet branch (fan) is adjusted to the constant air flow. e inlet branch (fan) is adjusted to the difference in under­pressure in the room. us, the inlet fan is adjusted to the required pressure (underpressure) depending on the pressure sensor location. Application: Preventing dirty air from entering the adjacent rooms
Note: When commissioning the system, it is necessary to perform the settings and regulation of the device (PID con­stants, FI ramp, etc.)
n Number of fans (for twins = 2). e air flow rate of one fan
is measured and is then multiplied by the number of fans.
n Required values (separately for the inlet and outlet fans)
5 required values are available for selection.
18
Air-Handling Unit Additional Operating Modes
If no operating mode is applied and the time schedule mode is in the Stop state, the air-handling unit can be started from additional operating modes. e user can use the following additional operating modes to start the air-handling unit:
n Night chilling n Temperature start-up n Optimized start
Additional operating modes can be activated by the HMI-SG controller in the List of Data Points in the section Settings – Additional Operating Modes, Functions.
Control Application Starting Algorithm
Air-handling system operation safety is assessed first (fire detection and operational safety of the air-handling devices). en the operating modes and their priorities are assessed (Manual, External, HMI-SG controller, BMS and time modes). If no control mode is currently used, the air-handling unit can, but may not, be put into one of the additional operating modes de­pending on the user's option. All the operating modes and their correlation are shown in the figure # 10 - "Operating modes". e current operating mode can be monitored through the HMI controller in the List of Data Points in the section Moni­tor – Current Modes. When the fans run and the air-handling unit is in operation, two basic groups of parameters are used to control operation:
n Temperature mode n Fan output (speed)
e fan output or speed can be set directly at levels corre­sponding to the air-handling system configuration:
n Single-speed motor fans:
>> Stage1
n Two-speed motor fans:
>> Stage1 / Stage2
n All five-stage controlled fans:
>> Stage1 / Stage2 / Stage3 / Stage4 / Stage5
See the chapter Fan Speed Control.
Figure 17 – Operating modes
Alarm A
State
Yes
No
Stop
Stop,Co1,EC1,...
Manual
Co1,EC1,Co2, ...
RUN
Co1,EC1,Co2, ...
HMI-SG (p. 125)
HMI TM, DM
Fans (stage 1-5)
Comfort/ Economy
Auto
Auto
Auto
Auto
Stop
Passive
Active
Passive
Active
Passive
Active
Passive
External
control
Optimized start
HMI-SG
contr.
BMS
Time
modes
Optimized
start
Temperature
start-up
Night
chilling
Night
turning
Temperature start-up
Night chilling
STOP
Night turning
Additional Operating Modes
19
Night Chilling
During night chilling, cold outdoor air is used to cool internal rooms of the buildings, thus excess heat accumulated in buildings during the day in summer months is removed. Night chilling minimizes the use of cooling devices and reduces the energy demand for temperature control day hours. During night chilling, the inlet and outlet dampers are fully open and fans run in the highest output stage. Night chilling start-up is enabled 12 hours before activation of the selected time schedule.
Activation
When the following conditions are fulfilled simultaneously:
n T
VEN
> T
MIN
n T
VEN
< T
PRO
- ∆
n T
PRO
> T
ŽÁD
+ T
HYS
Termination
If one of the following conditions is fulfilled:
n Once minimum operating time has elapsed while no time
mode is active (Stop mode)
n T
VEN
> T
PRO
- 1
n T
PRO
<= T
ŽÁD
T
MIN
Minimum outdoor temperature;
T
VEN
Outdoor air temperature; ∆ Outdoor and indoor temperature difference T
ŽÁD
Required room temperature
T
HYS
Temperature hysteresis
Temperature Start-Up
is feature prevents the building from overheating or over­cooling. e energy used to maintain a constant temperature range and system temperature oscillations are lower than the energy consumption for overheated or overcooled room control. Air from the room is re-circulated through the air mix­ing section (mixing damper fully open). e fan speed is set to the highest output stage. During temperature start-up, it is possible to select whether the inlet and outlet dampers or dampers along with the outlet fan will be blocked. is can be performed using the HMI controller, refer to the chapter Additional Operating Mode and Function Setting Options.
Cooling
Activation
When the following conditions are fulfilled simultaneously:
n T
PRO
> T
S,CH
n Once the tBL time interval has elapsed
Termination
If the following condition is fulfilled:
n T
PRO
< T
S,CH
- T
HYS
Heating
Activation When the following conditions are fulfilled simultaneously:
n T
PRO
< T
S,O
n Once the tBL time interval has elapsed
Additional Operating Modes
Termination
If the following condition is fulfilled:
n T
PRO
> T
S,O
+ T
HYS
T
PRO
Required room temperature
T
S,CH
Starting temperature for cooling
T
S,O
Starting temperature for heating
T
HYS
Temperature hysteresis at the stop tBL Heating blocking time t
BEH
Time remaining to start the time schedule
Optimized Start
is feature is used to ensure the comfortable temperature to be reached before the time schedule has been activated. us possible initial temperature non-conformities aer the time schedule activation are removed. is feature includes the setting for the room ventilation to have the room temperature controlled as soon as possible. is is based on air recirculation within the room along with cooling or heating adjustment. e mixing damper is fully open. It is possible to select whether the inlet and outlet dampers will only be blocked or whether the outlet fan will be blocked as well.
Cooling
Activation When the following conditions are fulfilled simultaneously:
n T
PRO
> T
S,CH
+ T
HYS
n t
∆TP
< t
KOM
Termination
If the following condition is fulfilled:
n T
PRO
< T
S,CH
Heating
Activation When the following conditions are fulfilled simultaneously:
n T
PRO
< T
S,O
- T
HYS
n t
∆TP
< t
KOM
Termination If the following condition is fulfilled:
n T
PRO
> T
S,O
T
PRO
Required room temperature
T
S,CH
Required temperature set-point for cooling
T
S,O
Required temperature set-point for heating
T
HYS
Temperature hysteresis t
KOM
Pre-set interval before time program start-up t
∆TP
Time remaining to the time program start-up
Night Turning Feature
When the supply air temperature sensor is not present, the outlet air temperature is evaluated. As the temperature is measured in the outlet, the fans are started at specified time intervals and air from the room is drawn into the outlet duct. e night turning feature is used along with the night chilling or temperature start-up modes. Night turning can be specified by the turning start time, time remaining to next turning and turning duration time.
20
Temperature modes
e VCS control unit system offers the possibility to maintain the controlled room or supply air temperature using two user adjustable temperature modes:
n Comfortable (normal mode usually used for temperature
control)
n Economy (e.g. night moderate heating)
Temperature modes are defined by the levels and staging of the required temperature set-points, respectively the tem­perature difference (systems with heating and cooling) – i.e. according to the environment comfort. ey also affect the operating energy demand. Each temperature mode is defined by the temperature settings for heating (lower environment temperature limit – minimum temperature) and the tempera­ture settings for cooling (upper limit – maximum temperature). e area of maintained controlled temperature ("dead zone") lies between these temperature set-points. Of course, main­taining the pre-set temperatures is dependent on the correct dimensioning of heating or cooling systems. Temperature modes are correlated so that the less comfortable mode has the required temperature:
n For heating, the required temperature (lower limit) is
always lower than (or the same as) the more comfortable mode.
n For cooling, the required temperature (upper limit) is always
greater than (or the same as) the more comfortable mode For more comfortable modes in systems with both heating and
cooling, the environment temperature "dead zone" is always narrower (or the same). Temperature modes are pre-set, see Data Points, Setting – Temperature Modes.
Note: e system automatically monitors the above-men­tioned temperature correlation and immediately adjusts the information about the possible maximum and minimum of each value depending on the user settings.
Warning
Settings, respectively the control process, also affect the correction values.
Time modes
e VCS control unit system provides the possibility to control operation depending on pre-set time schedules (modes).
n Daily schedule – allows max. 6 changes per day (mode
with the lowest priority)
n Weekly schedule – allows max. 7 changes per week n Exception schedule – allows max. 10 changes per week
Switch-off schedule – allows max. 10 changes (mode with the highest priority) ese modes interact, applying the system priorities. At any time, the air-handling operation is always controlled by the time schedule with the highest priority provided that it has an active time interval for that moment. e weekly and daily schedules can be overridden by the exception schedule or switch-off schedule at any time. e daily schedule is arranged for each day of the week. e weekly schedule is the same for each week of the year. Requirements for specific days (e.g. holidays) must be sched­uled within the exception time schedule.
Temperature modes, Time modes
e following parameters are set for the weekly and daily schedules:
n Start time (= end of previous interval) n Fan output (speed) stages n Temperature mode
e exception and switch-off schedules can be set for:
n Date – day of the week n Range of days – a period (e.g. holiday) n Week – days of the week (Monday, Tuesday,…)
e default setting is weekly and daily time schedule. Temperature modes in weekly and daily time schedules can be set using the HMI-SG controller in List of Data Points in the Settings section – Temperature modes, the chapter Control (HMI-SG controller). e exception and switch-off schedules can be set using HMI-DM, HMI-TM or HMI@Web controllers.
Date
Starting day: *,01.01.12
1st January 2012 is the specific day of operation.
Starting day: Mo,*.*.**
Every Monday is the specific day of operation.
Starting day: *,*.Even.**
Every even month (February, April, June,…) is the specific month of operation in each year.
Range of Days
Starting day: *,23.06.12 End: *,12.07.12
Days from 23rd June 2012 to 12th July 2012 are the specific days of operation in the year.
Starting day: *,23.12.** End: *,31.12.**
Days from 23rd to 31st December are the specific days of operation in each year.
Starting day: *,23.12.11 End: *,01.01.12
Days from 23rd December 2011 to 1st January 2012 are the specific days of operation.
Starting day: *,*.*.** End: *,*.*.**
An exception time schedule or a switching off schedule is perma­nently active and the weekly program will not be applied!
Week
Day of the week: *,fri,*
Every Friday is the specific day of operation
Day of the week: *,Fri,Even
Every Friday in an even month (Febru­ary, April, June,…) is the specific day of operation
Day of the week: *,*,*
When the starting day is entered in this way, an exception time schedule or a switching off schedule is perma­nently active and the weekly program will not be applied!
Day of the week: 2.,*,*
e second week of every month is the specific day of operation.
Time Schedule Operating Settings
21
The HMI-SG (Human Machine Inter­face) enables full control and moni­toring of the equipment’s operating parameters. The air-handling unit parameters can be accessed through the List of Data Points, which is pro­tected by the password applicable for the corresponding access level.
Control (HMI-SG)
The HMI-SG (Human Machine Inter-
face) enables full control and moni-
toring of the equipment’s operating
parameters. The air-handling unit
parameters can be accessed through
the List of Data Points, which is pro-
tected by the password applicable
HMI-SG controller enables the following items to be reviewed:
n Room (outlet) temperature n Current air-conditioning process (cooling, heat recovery,
mixing or heating)
n Temperature mode (Economy, Comfort) n Current system time and day of the week n Fan output stage
Other information is available via the List of Data Points, see the chapter Data Point List Access and Editing.  e HMI-SG POL822.60/STD hand controller is used to control air­handling devices.  is controller can be connected to the POL 4xx or POL 6xx master controller (respective to the terminals ready in the control unit).
Operating conditions
Degree of protection: IP 30 Permissible ambient temperature: 5 °C to 40 °C Relative humidity < 85%
Warning:
To avoid unintentional unit start-up, the master switch must be switched off and locked when repairing the VCS unit.
Wiring and Installation
 e HMI-SG controller is connected to the Process Bus (KNX). A twin cable or a twisted pair of leads can be used to perform the connection to the KNX bus.
Function Buttons
 e room unit consists of the face plate and back cover, which can be separated.  ere are 8 function buttons on the controller's face plate.
Figure 14 – Connection to the control unit
Figure 19 – HMI-SG controller
Controller Description
Table 3 – Function Buttons description
Button
number
Icon Name Function description
T1 Power Air-handling unit start or stop T2 Presence not used
T3 Program
 e time schedule button: by holding this button, you can set the date; by pressing this button, you can set the desired temperature mode timing and required fan output stage
T4 Minus
Temperature correction – pre-set depending on the selected temperature mode
T5 Plus
Temperature correction – pre-set depending on the selected temperature mode
T6 OK
Confirmation of the date or time schedule settings
T7 Fan
Fan output (speed) stage setting; each button cyclically increases the setting by one stage.  e cur­rent output stage is displayed on the display
T8 Mode
Temperature mode selection (Auto, Comfort and Economy). By pressing the button, the modes can be cycled.  e currently selected temperature mode is indicated by an icon on the display
Master
controller
Process Bus
HMI-SG 1 HMI-SG 2
Local HMI-SG controller
Figure 18 – Wiring box installation
 e controller can be installed using a wall wiring box or embedded in plaster.  e maximum distance between the control unit and room controller is up to 700 m. HMI-SG controllers are connected to the master controller in series and wiring is always performed to one point.
Note:  e Installation Instructions are part of the HMI-SG controller delivery.
22
Designation
Level
Password
(factory setting)
S SERVICE 4444
A ADMINISTRATOR 3333
U USER 2222
G HOST 0000
Control (HMI-SG)
User Roles and General Specification
The device parameters (data points) are structured and made available to users in accordance with their user roles (access levels). ese roles must be assigned to the users by the system administrator according to their expertise and responsibility for device operation.
n Guest – allows only common parameters to be viewed. n User – allows common parameters to be viewed and
controlled, as well as start and stop of the device.
n Administrator – allows the system administrator to view
and control common and some special parameters, pre-set operating parameters and modes for the user.
n Service – an access level recommended only for the sup-
plier or authorized service provider. In addition to the admin­istrator's level, it allows the user to adjust highly specialised configuration parameters related to the air-handling system and its instrumentation, control constants, water heater protection parameters, etc.
HMI to VCS System Access Default (factory) Settings
A control using the HMI controller uses an access right struc­ture in accordance with the concept of structured access of the air-handling device, refer to the chapter Overview and List of Date Points, Factory Settings. e HMI controller allows only four passwords (always four­digit and numerical) to be set, each for a different access level. Factory set default rights to access the VCS control unit using the HMI controller:
Table 4 – Display description
Table 5 – access levels
Icon
Display Description
I1
Indication of room temperature or correction of the required temperature in °C or °F
Room temperature in °C (increment 0.1 °C)
Room temperature in °F
(increment 0.5 °F)
Required temperature correction in °C or °F
I2 Time
I3 Fan output (speed) stage
I4 Days of the week
I5 On/Off
I6 Mode Auto
I7 Temperature mode Economy
I8 Temperature mode Comfort
I9 Cooling sequence
I10 Heating sequence
I11 Humidification
I12 Fan Speed Compensation
I13
Mode Presence
(this mode is not used as standard)
I14
Recovery and mixing sequences – energy savings
I15 Alarm
I16 Data point editing
Warning:
n When commissioning the device, we strongly recom-
mend changing the factory settings according to user needs to maintain the safety of the device itself as well as the controlled process.
n It is advisable to note and store the Service and Adminis-
trator passwords in a suitable (confidential) place (or up­date them upon each change to settings) to have easy access to them and thus maintain access to the system at the Service and Administrator levels.
n If the Service password changed from the factory setting
is lost (forgotten), it is necessary to contact the man­ufacturer's representative. e lost Administrator lev­el password can be retrieved by the user of the Service level (usually the supplier, installer or M&C service com­pany).
n e changed password settings cannot be automatically
restored (reset, etc.) to the factory settings.
n e user of the SERVICE level can change the passwords
of all other user levels, the user of the ADMINISTRATOR level can change the passwords of the GUEST and USER levels while users of the USER or GUEST levels are not allowed to change any passwords.
23
Data Point List Access and Editing
An overview of the structure of parameters accessible via the HMI-SG controller is available in the List of Data Points upon logging in using the appropriate access right level. e data points for writing and reading are assigned different access right levels. e procedure for access for editing and reading of data points is as follows:
1) e edit mode is signalled by an icon (I16). is mode can be accessed by pressing the Plus (T5), Minus (T4) and Mode (T8) buttons simultaneously. e cur­sor flashes in the first position from the le, ready for the 1st password digit to be entered. Change the value of the digit by pressing the Plus (T5) or Minus (T4) button and confirm by press-
ing the Mode (T8) button and the cursor will move to the next position. e password is activated aer entering and confirm­ing the last digit of the password by pressing the T8 button.
2) Upon entering the correct password, the data points for the respective access level (pass­word) are displayed.
Note: If the entered password is wrong, "---" will be displayed.
3) Using the Plus (T5) or Minus (T4) buttons, select the first num­ber of the data point group and confirm the selection by pressing the mode (T8) button. en select a desired data point within the group in the same way as the first number of the data point group. e number on the first line rep­resents a data point code while the number on the second line represents its value.
4) If the parameter value is highlighted, the data point is only for reading. If the parameter value flashes, the data point can be edited in accordance with the access level you logged in at.
5) e value can be edited by the Plus (T5) or Minus (T4) but­tons. To confirm changes to the value, press the Mode (T8) button. Upon confirming the changes, the data point cursor will start to flash, and you can move to the next parameter in the group. Another group of parameters, i.e. return to a higher level, can be made by pressing the Power (T1) button.
Note: If no change is made within 1 minute, the data point editing mode will be exited.
Control (HMI-SG)
Communication Settings
Once the HMI-SG controller has been connected to the control unit, the communication between both devices will be set automatically. If two HMI-SG controllers have been connected to the control unit, it is necessary to set a new address for one of the controllers. An interface for the communication settings will be displayed on the controller, and then parameter #7 must be changed.
1) e interface for the communication settings is displayed by pressing and holding the Power (T1), Mode (T8), Minus (T4) and Plus (T5) buttons simultaneously. e cursor flashes in the first position from the le, ready for the 1st password digit to be entered. Change the value of the digit by pressing the Plus or Minus (T4) button and confirm by pressing the Mode (T8) button and the cursor will move to the next position. Changes to the parameter settings can only be made by the ADMINISTRATOR, SERVICE or USER role users.
2) Aer a correct password has been entered, press the Mode (T8) button to enter the interface for changes to
parameter settings.
3) Use the Plus (T5) or Minus (T4) buttons to browse the communication parameters. Press the Mode (T8) button to confirm selection of the desired parameter (parameters for communication settings are listed in the following table).
Table 6 – Communication settings
Parameter number/Description
001
KNX connection state
• OK – bus communication is OK
• NF – no bus communication
002
Physical address (X.1.1)
X…value range 0 to 15; generated automatically
003
Physical address (1.X.1)
X…value range 0 to 15; generated automatically
004
Physical address (1.1.X)
X…value range 0 to 252; generated automatically
005
Byte (program) address (X.1.1)
X…value range 0–126 (pre-set value is 5) is value needs to be changed if several master contro­llers are connected to the KNX bus by several controllers
006
Room (program) address (1.X.1)
X…value range 1 to 14 (pre-set value is 1)
007
Zone (program) address (1.1.X)
X…value range 1 to 15 (pre-set value is 1) is value must be changed from 1 to 2 if 2 control­lers are connected to the same master controller.
008
Network failure detection enabled
Network failure detection enabled or disabled; network failure is indicated by the word "NET".
009
Physical address automatic assignment (pre-set value is 1)
0…Room unit uses firmly defined physical address 1…automatic generation of the controller's address
24
Figure 20 – HMI-SG controller LCD display
I6
I3
I1
I2
I4
Operating the HMI-SG controller
If only one HMI-SG controller is connected to the control unit, it then serves as an operating controller for full setting and control of the control unit. During the first start-up of the air­handling unit, the manual operating mode (the highest priority) is set to the Stop state, and the HMI-SG controller does not interfere with control of the control unit. In the Manual operat­ing mode, it is necessary to change the state from Stop to Auto using data point #125 and thus move the priority from the control unit to the HMI-SG controller's operating mode.
First Control Unit Start-Up Using HMI-SG Controller
1) Press the Plus (T5), Minus (T4) and Mode (T8) buttons
simultaneously to display the log-in screen for the 4-digit password. Change the value of the digit by pressing the Plus (T5) or Minus (T4) button. Press the Mode (T8) button to confirm the entered digit and the cursor will move to the next position. Once the correct password has been entered, the data point screen will be displayed. Press the Power (T1) button to leave the log-in interface.
2) e first digit "0--" will be displayed. To change the first digit value, press the Plus (T5) or Minus (T4) button. To confirm the entered value, press the Mode (T8) button.
Use the Plus (T5) and Minus (T4) buttons to set the last two digits to get the string "125". To confirm the entered value, press the Mode (T8) button. To return to the previous step, press the Power (T1) button.
3) e flashing number on the second line represents a data
point value. Use the Minus (T4) buttons to change the data point value from "1" to "0" and confirm by pressing the Mode (T8) button. To return to the previous step, press the Power (T1) button.
e situation before initiating the control unit from the HMI-SG controller is illustrated in figure 16. e Stop operating mode is indicated by the Auto icon (I6). Current temperature (I1) and system time (I2) are displayed. e fans are not running (I3). e day of the week is indicated by digits (1–7) in the lower part of the display.
Note: 12h/24h system time format cam be changed using data point 898. e source of the displayed temperature can be selected using data point 887.
Control (HMI-SG)
4) e cursor with the communication parameter value will
start to flash. e parameter value can be changed by pressing the Plus or Minus (T4) buttons. Press the Power (T1) button to confirm the change to the communication parameter value.
5) To return to a higher level, press the Power (T1) button. If no change is made within 1 minute, the interface will be exited.
Note: If the air-handling unit is controlled by two HMI-SG controllers, the last change made from one of the control­lers will be valid.
System Date and Time Settings
Here, the actual VCS system date and time can be set – these setting are required for correct functioning of the time schedule programs. e procedure for system date and time setting is as follows: Aer long hold the Program (T3) button to set the date and time. Press the Plus (T5) and Minus (T4) buttons to change the date and time values. Press the OK (T6) button to confirm the changes and the cursor will move to the next item. e cursor cycles through the following items:
Hour → Minute → Month → Day → Year
Default Application Parameterization
To ensure comfortable and economy operation requiring mini­mum attendance, it is necessary to perform the main settings defining the parameters and air output, respectively the tem­perature control, and stability in the ventilated/air-conditioned room. Data points must be set for all the relevant parameters:
n Temperature modes n Time schedules n Control parameters n Correction values n Antifreeze Protection n Control constants n Optional modes and functions
e parameters are described in the chapter List of Data
Points, Factory Settings.
25
Control (HMI-SG)
Operating Screen (Examples)
Aer making the HMI-SG controller a service controller, it is possible to change the control unit settings. Use the Mode (T8) button to manually switch between the Run state with temperature modes (Comfort or Economy) and the Auto state. Use the Power (T1) button to put the air-handling unit into the Stop operating state, the display in the HMI-SG operating mode will only display the ON/OFF icon (I5).
Operating State Auto
e fan speed and temperature mode are set depending on the time schedule compilation. It is possible to set a correc­tion to the required temperature, see the chapter Required Temperature Correction. It is also possible to adjust the time schedule, see the chapter Daily (Weekly) Time Schedule.
e figure shows the Auto operating state display. e state
is signalled by an icon (I6). e air-handling unit is controlled in accordance with the time schedule. e moderate heating temperature mode (I7) with a cooling sequence (I9) is active. e fans are set to the second speed stage (I3). Apart from the cooling sequence, the heating (I10), heat recovery and mixing
(I14) icons can be displayed.
e figure shows the situation where a time schedule con-
trolled air-handling unit is in the Stop operating state. e fans are not running (I3). No temperature modes or heating or cooling sequences are active.
Warning: Current additional operating mode stats are not displayed but can be monitored
in the List of Data Points in the section Monitor – Current Modes – Current Modes – Current operating Mode.
Manual Operating Mode (Run)
In Manual operating mode, it is possible to select the required temperature mode, set any fan speed output stage and the required temperature correction.
This display shows the manually selected Comfort tem-
perature mode (I8) with a heating
sequence (I10) and the fourth fan
speed stage. In Manual mode, the
fan speed can be set using the Fan
button (T7). To manually switch
between the temperature modes,
use the Mode (T8) button.
Failure Detection
If a failure of external components
I6
I8
I3
I3
I9
I9
I7
connected to the device failure detection inputs (incorrect state of the contact) occurs, the VCS control unit will au­tomatically put out an alarm in accordance with an internal algorithm – indicating the faulty object and in case of severe failures stopping the air-handling unit. Each failure is more closely specified by a failure class. e failure class determines the severity of the failure. A class failures will shut down the air-handling unit. B class failures will deactivate some system functions (e.g. compensation if the temperature sensor fails) but they will not shut down the air-handling unit. Numerical failure codes specifying the failure events are listed in the chapter Failures. If more failure events occur, the number of the failure with the highest priority (the most serious failure) will be displayed.
Failure Screen (example)
If a failure occurs, the air-handling unit is put in the STOP state (respectively the Run mode is retained, B class failure). is is
indicated by flashing Auto (I6) and Alarm (I15) icons on the display. e failure class (I18) and number (I19) are displayed below the temperature indication. Indication of the alarm will cease shortly aer all failure events have been removed. e number shown on the display can also be accessed via data point 824.
Failure Reset
Failure reset can only be performed once the cause of the failure has been identified and removed. e failures are reset using data point 825.
Required Temperature Settings in Temperature Modes
Required temperature settings for the Comfort and Economy temperature modes are performed in the List of Data Points –Temperature Modes:
n 101 – Comfort cooling n 103 – Comfort heating n 105 – Economy cooling n 107 – Economy heating
Required Temperature Correction
The pre-set required temperatures in each temperature mode can be changed within ±3 °C directly from the HMI-SG controller. Use the Plus (T5) button to increase the required temperature or use the Minus (T4) button to decrease the required temperature. e one button pressing increment or decrement value can be set in data point 897. is tempera­ture adjustment is only valid for a current mode. Upon transi­tion between modes, this correction will be reset.
I6
I15
I19
I18
26
Control (HMI-SG)
Time Schedule Compilation Procedure
1) Press the Program (T3) button to enter the time schedule
configuration menu for each day of the week. B HMI SG displays the first day of the week, i.e. Monday. Up to 6 time windows ((1-1 to 1-6) can be set for each day.
3) e Mode (T8) button enables you to select a day by cycling through the week days (1-2-3-4-5-6-7-A). e "A" option is used to set the time schedule for business days (1 – 5) simultane­ously. If you make any change to the "A" time schedule, the settings of the "A" day will be copied to all business days.
4) e Power (T1) button is used to assign the selected time window with an operating mode (Stop-Economy-Comfort).
5) e Fan (T7) button is used to set the fan operation speed stage (st. 1 – st. 5).
6) e Minus (T4) and Plus (T5) buttons are used to set the beginning of the time window; to confirm the time setting, press the OK (T6) button.
7) Once the beginning of the time window has been set, move to the next settings in the time window.
8) If you set the beginning of the time window to "--:--", the window will be disabled.
9) Press and hold the OK (T6) button to go back one step in the time schedule settings within the set time.
10) Press and hold the Fan (T7) button to go back one step in the time schedule settings within the fan speed stage settings.
11) Press and hold the Mode (T8) button to move one step back (a weekday selection).
12) Press the Program (T3) or Presence (T2) button to exit the Time Schedule Settings menu.
13) If no settings are performed in the time schedule within 1 minute, the menu will be automatically le..
time window
fan speed stage setting (T7)
operating mode setup (T1)
time setup (T4), (T5)
Quick Menu:
is enables quick access to the temperature and selected value monitoring without editing. Use the Minus (T4) and Plus (T5) to switch between the temperature values. Use the Program (T3) or Presence (T2) buttons to exit the Quick Menu. Only those values which are included within the given version of the VCS unit are displayed. Briefly press the OK (T6) button to display the values listed below:
n Inlet temperature (Sply) n Outdoor temperature (Out)
Press and hold the OK (T6) button to display the values listed below:
n Comfort temperature mode (heating) n Economy temperature mode (heating) n Comfort temperature mode (cooling) n Economy temperature mode (cooling)
Lock/Unlock the SG II buttons
Press and hold the Presence (T2) button to lock/unlock the SG II controller in order to prevent unauthorised access to the device control.
n Return water temperature (Htr) n Outlet temperature (Rtrn) n Room temperature (Room)
27
Control (HMI-SG)
Additional Operating Modes and Function Settings
Additional operating modes and functions can be activated in the List of Data Points in the section Settings – Additional Operating Modes, Functions. Once the respective mode or function has been set, it is necessary to perform SW reset using a specific data point 211 (Reset aer the configuration of additional modes/functions).
Optional Additional Operating Modes
n Night Chilling n Temperature start-Up n Time mode start optimization
Optional additional functions
n Outdoor Temperature-Dependent Fan Speed Compensa-
tion
n Heating/cooling dependent fan speed compensation n Room (Outlet) Temperature-Dependent Fan Speed Com-
pensation
n Humidity-dependent Fan Speed Compensation n Air Quality-Dependent Damper Position Compensation n Heating/cooling–dependent fan speed compensation –
cooling sequence
n Cooling using heat recovery with rotary regenerator option
or using mixing damper
n Heating and mixing sequence order n Outlet fan correction – using five-stage control (TRN
controllers)
n Difference between required and actual temperature
monitoring
n Damper and outlet fan blocking n Room temperature measuring point selection
User Settings Backup and Recovery
It is advisable to perform backups especially before significant changes in control parameter settings (PID controller fac­tors, temperature setting for compensations or starting of the optional additional modes), or always when the control works optimally. Data backup or recovery can be performed using the HMI controller in the List of Data Points, section Checks – User Settings.
List of Data Points, Factory Settings
Warning:
e device parameters are structured and made available to users in accordance with their user roles (access levels). ese roles must be assigned to users by the system administrator according to their expertise and responsibility for device opera­tion. Access to the data points is also limited by the user role level – for levels lower than Service, not all parameters (data points) are displayed, respectively, they can be read without being able to change (save) them. e Parameter List with a combination of all possible air-handling unit applications is in­cluded in the List of data points under the highest access right.
28
List of Data Points (HMI-SG controller)
Monitor Temperature
°C 001 G Temperature in the inlet °C 002 G Temperature in the room 1 °C 003 G Temperature in the room 2 °C 004 G Room unit 1 °C 005 G Room unit 2 °C 006 G Temperature in the outlet °C 007 G Outdoor temperature °C 008 G Return water temperature °C 009 G Heat exchanger freezing temperature °C 010 G Electric preheater temperature °C 011 G Water preheater temperature °C 012 G Electric reheater temperature °C 013 G Flue gas temperature °C 014 G Final room temperature (controlled) °C
Humidity
015 G Inlet air relative humidity %r.H. 016 G Room air relative humidity %r.H. 017 G Outdoor air relative humidity %r.H.
Pressure 018 G Pressure in the inlet Pa 019 G Pressure in the outlet Pa 020 G Air flow rate in the inlet m3/h 021 G Air flow rate in the outlet m3/h
CO2 (VOC, CO)
022 G CO2 (VOC, CO) concentration ppm
Performances 023 G Inlet fan output % (m3/h, Pa) 024 G Outlet fan output % (m3/h, Pa) 025 G 3rd fan output % 026 G Outlet level for the electric reheater % 027 G Heating mixing set valve position % 028 G Outlet level for cooling % 029 G Cooling output (stage) 030 G Electric preheater position % 031 G Outlet level for the electric heater % 032 G Heat pump output % 033 G Outlet position to the mixing damper % 034 G Heat exchanger control outlet position % 035 G Modulation burner outlet position % 036 G By-pass damper outlet position %
Operating states
037 G Fan state 0 -
1 Stage 1 2 Stage 2 3 Stage 3 4 Stage 4 5 Stage 5
038 G Electric pre-heater state 1 off
2 on
039 G Water pre-heater state 0 off
1 on
040 G Electric re-heater state 1 off
2 on
041 G Water heater pump state 0 off
1 on
042 G Pre-heating function of water heating 0 off
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
29
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
1 on
043 G Water cooler pump state 0 off
1 on
044 G Evaporator cooling stage 1 off
2 Stage 1 3 Stage 2
045 G Inverter cooling stage (inverter) 0 off
1 on
046 G Inverter cooling stage (step1+inverter) 0 off
1 on
047 G Heat pump operating state 0 out of operation
1 cooling 2 heating
048 G Electric heater operating state 1 off
2 on
049 G Gas Burner operating states (stages) 1 off
2 Stage 1 3 Stage 2
Current modes
050 G Fan output stages (external equipment) 0 Auto
1 off 2 Stage 1 3 Stage 2 4 Stage 3 5 Stage 4 6 Stage 5
051 G AHU current operating mode 0 Stop
1 Comfort 2 Economy 3 ­4 Optimized start 5 Night chilling 6 Temperature start-up 7 Night turning 8
9 Fire mode 10 Safety stop 11 Fan run-out 12 Start
Current temperature control values
052 G Calculated required temperature for heating with cascade control °C 053 G Calculated required temperature for cooling with cascade control °C 054 G Calculated required temperature for heating °C 055 G Calculated required temperature for cooling °C 056 G Current temperature-dependent control (inlet, room, outlet) 0 room
1 outlet
2 inlet
Current humidity values 058 G Calculated absolute inlet air humidity g/kg 059 G Calculated inlet air humidity enthalpy kJ/kg 060 G Calculated absolute room air humidity g/kg 061 G Calculated room air humidity enthalpy kJ/kg 062 G Calculated absolute outdoor air humidity g/kg 063 G Calculated outdoor air humidity enthalpy kJ/kg 064 G Request for dehumidification %
065 G Request for humidification %
30
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
066 G Humidifier state 0 off
1 on
Settings
Temperature modes
101 A 102 G Comfort - cooling 24.6 0 99 °C 103 A 104 G Comfort - heating 22.6 0 99 °C 105 A 106 G Economy - cooling 28 0 99 °C 107 A 108 G Economy - heating 20.6 0 99 °C 109 A 110 G Required temperature for cooling, Temperature start-up 15 -64 64 °C 111 A 112 G Required temperature for heating, Temperature start-up 25 -64 64 °C 113 A 114 G Required room temperature , Night chilling (control for inlet) 22 -64 64 °C 115 A 116 G Required room temperature , Boost (control for inlet) 20 -64 64 °C 117 A 118 G Required temperature for cooling, Boost 15 -64 64 °C 119 A 120 G Required temperature for heating, Boost 25 -64 64 °C
Cascade control limitation - limiter
121 S 122 A Max. difference between room temperature and inlet temperature 10 0 64 °C 123 S 124 A Min. difference between room temperature and inlet temperature 10 0 64 °C
Operation mode
125 A 126 G AHU manual control (Temperature mode, fan output stage) 0 Auto Stop
1 Stop 2 Economy; St1 3 Comfort; St1 4 Economy; St2 5 Comfort; St2 6 Economy; St3 7 Comfort; St3 8 Economy; St4
9 Comfort; St4 10 Economy; St5 11 Comfort; St5
127 A 128 G AHU start-up time-out aer power supply failure 10 0 9999 s
External control
129 U 130 G External contact function definition (Ext. control 1 contact) 0 Start function 0
1 Start and Stop function
131 U 132 G
Transition time from ext. control mode to AUTO mode (Ext. control 1 contact)
0 0 23 h
133 U 134 G Fan output stage setting (Ext. control 1 contact or 2 contacts) 0 Auto 2
1 off
2 Stage 1
3 Stage 2
4 Stage 3
5 Stage 4
6 Stage 5
135 U 136 G Temperature mode setting (Ext. control 1 contact or 2 contacts) 0 Comfort 0
1 Economy
137 U 138 G Fan output stage setting "Higher" (Ext. control 2 contacts) 0 Auto 5
1 off
2 Stage 1
3 Stage 2
4 Stage 3
5 Stage 4
6 Stage 5
139 U 140 G Temperature mode setting "Higher" (Ext. control 2 contacts) 0 Comfort 0
1 Economy
Fans - Modbus
Control limits
141 A Inlet fan output St1 setting 0.1 % (m3/h, Pa)
31
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
142 A Inlet fan output St1 setting (a factor of 10) % (m3/h, Pa) 143 A Inlet fan output St2 setting 25 % (m3/h, Pa) 144 A Inlet fan output St2 setting (a factor of 10) % (m3/h, Pa) 145 A Inlet fan output St3 setting 50 % (m3/h, Pa) 146 A Inlet fan output St3 setting (a factor of 10) % (m3/h, Pa) 147 A Inlet fan output St4 setting 75 % (m3/h, Pa) 148 A Inlet fan output St4 setting (a factor of 10) % (m3/h, Pa) 149 A Inlet fan output St5 setting 100 % (m3/h, Pa) 150 A Inlet fan output St5 setting (a factor of 10) % (m3/h, Pa) 151 A Outlet fan output St1 setting 0.1 % (m3/h, Pa) 152 A Outlet fan output St1 setting (a factor of 10) % (m3/h, Pa) 153 A Outlet fan output St2 setting 25 % (m3/h, Pa) 154 A Outlet fan output St2 setting (a factor of 10) % (m3/h, Pa) 155 A Outlet fan output St3 setting 50 % (m3/h, Pa) 156 A Outlet fan output St3 setting (a factor of 10) % (m3/h, Pa) 157 A Outlet fan output St4 setting 75 % (m3/h, Pa) 158 A Outlet fan output St4 setting (a factor of 10) % (m3/h, Pa) 159 A Outlet fan output St5 setting 100 % (m3/h, Pa) 160 A Outlet fan output St5 setting (a factor of 10) % (m3/h, Pa) 161 A 162 U 3rd fan output St1 setting 0.1 0.1 100 % 163 A 164 U 3rd fan output St2 setting 25 0.1 100 % 165 A 166 U 3rd fan output St3 setting 50 0.1 100 % 167 A 168 U 3rd fan output St4 setting 75 0.1 100 % 169 A 170 U 3rd fan output St5 setting 100 0.1 100 % 171 A 172 U Fan run-out aer unit stop shut-down 180 0 9999 s
570 A
Enabling the fan run-out according to DEV 0 No 1
1 Yes
571 A
Unit run-out – blocking by the minimum outside temperature -15 -64 64 °C
572 A
Unit run-out – blocking by the maximum outside temperature 5 -64 64 °C
573 A
Unit run-out – time 5 1 60 Min
Inlet backup – single-speed motors
173 A 174 U Failure flow evaluation time-out aer main fan start-up 180 0 9999 s 175 A 176 U Failure flow evaluation time-out aer backup fan start-up 180 0 9999 s
181 U Information – backup activation 0 non-activated
1 activated
Outlet backup - single-speed motors 177 A 178 U Failure flow evaluation time-out aer main fan start-up 180 0 9999 s 179 A 180 U Failure flow evaluation time-out aer backup fan start-up 180 0 9999 s
182 U Information - backup activation 0 non-activated
1 activated
TRN correction
183 A 183 A Common for all operating stages St 0 - 4 stages 0
1 - 3 stages 2 - 2 stages 3 - 1 stage 4 0 5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
184 A 184 A For operating stage St1 0 - 4 stage 0
1 - 3 stage 2 - 2 stage 3 - 1 stage 4 0
32
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
185 A 185 A For operating stage St2 0 - 4 stage 0
1 - 3 stage 2 - 2 stage 3 - 1 stage 4 0 5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
186 A 186 A For operating stage St3 0 - 4 stage 0
1 - 3 stage 2 - 2 stage 3 - 1 stage 4 0 5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
187 A 187 A For operating stage St4 0 - 4 stage 0
1 - 3 stage 2 - 2 stage 3 - 1 stage 4 0 5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
188 A 188 A For operating stage St5 0 - 4 stage 0
1 - 3 stage 2 - 2 stage 3 - 1 stage 4 0 5 + 1 stage 6 + 2 stages 7 + 3 stages 8 + 4 stages
TRN – fan start-up (without outlet for dampers)
189 S 189 S Forced fan start-up time setting to Stage 1 20 0 99 s
Two-speed motors 190 A 191 U Transition time interval from speed 1 to speed 2 15 0 999 s 192 A 193 U Transition time-out from speed 2 to speed 1 12 0 99 s
Inlet temperature limitation 194 S 194 S Minimum inlet air temperature 15 0 64 °C 195 S 195 S Maximum inlet air temperature 35 0 64 °C
Additional operating modes, functions 196 S 196 S Outdoor temperature dependent fan speed compensation 0 No 0
1 Yes
197 S 197 S Heating/cooling dependent fan speed compensation 0 No 0
1 Heating 2 Cooling
33
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
3 Heating + Cooling
198 S 198 S Air quality dependent fan speed compensation 0 No 1
1 Yes
199 S 199 S Room (outlet) temperature dependent fan speed compensation 0 No 0
1 Yes
230 S 230 S Humidity-dependent fan speed compensation 0 No 0
1 Yes
231 S 231 S Limitation of dehumidification during heating 0 No 0
1 Yes
201 S 201 S Difference between required and actual temperature monitoring 0 No 0
1 inlet 2 room 3 Inlet+room
202 S 202 S Air quality dependent damper position compensation 0 No 0
1 Yes
246 S 246 S Humidity-dependent mixing damper position compensation 0 No 0
1 Yes
247 S 247 S Max. limit of fresh air according to T outdoor (ventilation unit) 0 No 0
1 Yes
203 S 203 S Cooling using HR (RHE, BP PE, mixing damper) 0 without HR cooling 3
1 RHE, BP PE 2 mixing damper 3 RHE+ damper
204 S 204 S
Heating/cooling dependent fan speed compensation-cooling sequence
(fan, cooler)
0 fan+cooler 1
1 cooler+fan
205 S 205 S Mixing heating sequence (damper, heater) 0 damper+heater 0
1 heater+damper
206 S 206 S Night cooling 0 without chilling
1 with chilling
207 S 207 S Temperature start-up 0 N/A 0
1 heating 2 cooling 3 heating + cooling
208 S 208 S Time mode start optimization 0 N/A 0
1 heating 2 cooling 3 heating + cooling
209 S 209 S Damper and outlet fan blocking 0 N/A 0
1 dampers 2 dampers+fan
210 S 210 S Outlet fan correction type (TRN controllers) 0 separate stages 0
1 shared stages
211 S 211 S Reset aer configuration of additional modes/functions 0 without reset
1 reset
212 S 212 S Room temperature measuring point selection 0 average 3
1 minimum 2 maximum 3 room temp. sensor 1 4 room temp. sensor 2 5 HMI-SG 1 controller 6 HMI-SG 2 controller
Control signal characteristic
213 A 213 A Control signal 0-10 V or 2-10 V, heating 0 0-10V
1 2-10V 1
214 A 214 A Control signal 0-10 V or 2-10 V, cooling 0 0-10V
1 2-10V 1
215 A 215 A Control signal 0-10 V or 2-10 V, mixing damper 0 0-10V
1 2-10V 1
34
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
216 A 216 A Control signal 0-10 V or 2-10 V, heat exchanger by-pass damper 0 0-10V
1 2-10V 1
217 A 217 A Control signal 0-10 V or 2-10 V, chamber by-pass damper 0 0-10V
1 2-10V 1
Required inlet temperature extra set-point
218 A 219 G
Required inlet temperature extra set-point (applied when el. re-heating or
heat pump is removed from the main sequence)
20 0 99 °C
220 S 220 S Fan start-up delay (aer damper) 20 0 9999 s
221 S 221 S
Outdoor-dependent fan speed interlocking
-60 -64 64 °C
Control – Flow (Pressure)
222 A 223 U Setting range of flow sensor - inlet (a factor of 100) 8000 0 2*105 m3/h 224 A 225 U Setting range of flow sensor - outlet (a factor of 100) 8000 0 2*105 m3/h 226 A 227 U Setting range of pressure sensor - inlet (a factor of 100) 6000 0 7000 Pa 228 A 229 U Setting range of pressure sensor - outlet (a factor of 100) 6000 0 7000 Pa 232 A 233 U K factor – inlet 95 0 9999 234 A 235 U K factor – outlet 95 0 9999 236 A 237 U NunberInletFan 1 1 100 238 A 239 U NunberOutletFan 1 1 100
240 S K Factor - Enabled 0 No
1 Yes 1
Inputs configuration
241 S Reverse function of fault input for Cooling or Heat Pump 0 Normal 0
1 Reversed
Device configuration
270 U Regulation supply fan 0 none
1 1 stage 2 5 stage (TRN) 3 V10 4 V100 5 V10 + back-up 6 V100 + back-up 7 2xV10 8 2xV100 9 2xV10 + back-up
10 2xV100 + back-up
271 U Regulation exhaust fan 0 none
1 1 stage 2 5 stage (TRN) 3 V10 4 V100 5 V10 + back-up 6 V100 + back-up 7 2xV10 8 2xV100 9 2xV10 + back-up
10 2xV100 + back-up
272 U Regulation additional fan 0 none
1 1 stage 2 5 stage (TRN) 3 V10 4 V100 7 2xV10 8 2xV100
273 U Heating 0 no
1 water 2 electric 3 gas
35
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
274 U Heat pump 0 no
1 variation A 2 variation B
275 U Type of gas heating 0 1 stage
1 2 stage 2 modulation
276 U Byppas damper gas heater 0 no
1 yes
277 U Cooling 0 no
1 water 2 1 step 3 2 step 4 inverter 5 inverter + 1 step
278 U Heat recovery 0 no
1 plate 2 wheel 3 glycol
279 U Mixing 0 no
1 yes
280 U Preheating 0 no
1 water 2 electric
281 U Extra heating 0 no
1 electric
282 U Temperature control mode 0 supply
1 cascade - room 2 cascade - return
283 U Humidity control mode 0 no
1 room 2 supply 3 cascade - room
Control parameters
Temperature start-up 301 A 302 U Cooling trigger temperature 30 -64 64 °C 303 A 304 U Heating trigger temperature 25 -64 64 °C 305 A 306 U Hysteresis 1 0.1 64 °C 307 A 308 U Heating and cooling blocking time 30 0 999 min 309 A 310 U Operating time 0 0 999 min
Night colling
311 A 312 U Temperature hysteresis 3 0 64 °C 313 A 314 U Minimum outdoor temperature setting 12 -64 64 °C 315 A 316 U Outdoor temperature and room temperature difference 5 1 64 °C 317 A 318 U Minimum night chilling operating time 30 0 999 min
Boost function
319 A 320 U Pre-set interval before time program start-up 60 0 999 min 321 A 322 U Temperature hysteresis 0.5 -64 64 °C
Required temperature compensation 323 A 324 U Cooling initial point (outdoor temperature) 25 -64 64 °C 325 A 326 U Cooling end point (outdoor temperature) 30 -64 64 °C 327 A 328 U Maximum cooling compensation (required value) 2 -64 64 dK 329 A 330 U Heating initial point (outdoor temperature) 5 -64 64 °C 331 A 332 U Heating end point (outdoor temperature) -20 -64 64 °C 333 A 334 U Maximum heating compensation (required value) -1 -64 64 dK
335 U Required cooling value current shi -64 64 °C 336 U Required heating value current shi -64 64 °C
Outdoor temperature dependent fan speed compensation
337 A 338 U Cooling initial point (outdoor temperature) 25 -64 64 °C
36
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
339 A 340 U Cooling end point (outdoor temperature) 30 -64 64 °C 341 A 342 U Maximum cooling compensation (speed) 0 -100 100 % 343 A 344 U Heating initial point (outdoor temperature) 5 -64 64 °C 345 A 346 U Heating end point (outdoor temperature) -20 -64 64 °C 347 A 348 U Maximum heating compensation (speed) 0 -100 100 %
349 U Current cooling speed compensation -100 100 % 350 U Current heating speed compensation -100 100 %
Room (outlet) temperature dependent fan speed compensation 351 A 351 A Compensation function setting
0 increase 0 1 decrease
352 U
Actual compensation
0 100 %
353 A 353 A Required room temperature 20 0 99 °C
Heating/cooling dependent fan speed compensation 354 A 354 A Heating temperature hysteresis 1 0 20 °C 355 A 355 A Cooling temperature hysteresis 1 0 20 °C
356 U Heating compensation display 0 100 % 357 U Cooling compensation display 0 100 %
Air quality dependent compensation (damper position/fan speed) 358 A 359 U Compensation function setting (according to the sensor characteristics) 0 Normal 0
1 Inverted 360 A 361 U Required (allowable) value of the CO2, VOC, (CO) concentration 800(50) 0 3000 ppm 362 A 363 U CO2, VOC, (CO) sensor range setting 2000(300) 0 3000 ppm
364 U CO2, VOC (CO) compensation rate display 0 100 %
Sequence Heat pump - heating
365 A 366 U Outdoor temperature dependent heat pump blocking -8 -45 35 °C
367 A 368 U
Temp. hysteresis applied for outdoor temperature dependent heat pump unblocking
3 1 10 °C
369 A 370 U Minimum operating time for heat pump heating 60 0 9999 s 371 A 372 U Re-heating blocking 120 5 600 s 373 A 374 U Heat pump switching on 20 0 100 % 375 A 376 U Digital output opening hysteresis 10 1 100 %
377 U Information - outdoor temperature dependent heat pump heating blocking 0 inactive
1 active
Heat pump - cooling
378 A 379 U Outdoor temperature dependent heat pump blocking 14 -45 35 °C
380 A 381 U
Tep. hysteresis applied for outdoor temperature dependent heat pump unblocking
3 1 10 °C
382 A 383 U Minimum operating time for heat pump cooling 60 0 9999 s 384 A 385 U Re-cooling blocking 120 5 600 s 386 A 387 U Heat pump switching on 20 0 100 % 388 A 389 U Digital output opening hysteresis 10 1 100 % 390 A 391 U Heat pump low reference signal setting for A output 30 0 50 %
392 U Information - outdoor temperature dependent heat pump cooling blocking 0 inactive
1 active
Heat Pump - Special
260 S Inversion signal for Heat Pump – heating 0 Off
1 On
261 S Inversion signal for Heat Pump – cooling 0 Off
1 On
262 S Special signal 0-10V (Daikin) switchover 0 Off
1 On
263 S e difference between the demand and the real signal to determine St2 40 0 100 % 264 S Time needed to pass from 0 to 100% 120 0 500 s 265 S e signal voltage request of heating (Toshiba) 3.25 0 10 V 266 S e signal voltage request of cooling (Toshiba) 6.25 0 10 V 267 S e signal voltage request of STOP (Toshiba) 0 0 10 V
37
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
268 S e signal voltage request of START (Toshiba) 8 0 10 V
Cooling
393 A 394 U Outdoor temperature to enable cooling – all versions 12 -64 64 °C 395 A 396 U Minimum pump operating time – water version 180 0 9999 s 397 A 398 U Pump downtime to the pump turning activation – water version 168 0 9999 h 399 A 401 U Active pump turning time – water version 60 0 9999 s
397 A 398 U
Minimum operating time, single-stage condensing unit – version with single-stage condensing unit
60 0 9999 s
399 A 401 U Re-cooling blocking time – versions with single-, two-stage condensing units 120 5 600 s
402 A 403 U
Retention time during transition from Stage 1 to Stage 2 – version with two-stage condensing unit
360 5 600 s
404 A 405 U
Cooling request dependent evaporator Stage 1 switch-on – version with two-stage condensing unit
20 0 100 %
406 A 407 U
Cooling request dependent evaporator Stage 2° switch-on – version with two-stage condensing unit
70 0 100 %
408 A 409 U Hysteresis for transition from Stage 1 to Stage 2, two-stage condensing unit 10 0 20 % 410 A 411 U Minimum inverter operating time – version with inverter 10 0 9999 s
412 A 413 U
Inverter re-start blocking time – version with single-stage condensing unit + inverter
60 0 300 s
413 A
AO cooling signal inversion 0 Switched OFF
1 Switched ON
Water heating with pre-heating function
414 A 415 U
Outdoor temperature-dependent pump start-up in the AHU Stop and Run mode
5 -64 64 °C
416 A 417 U Minimum pump run time 180 0 9999 s 418 A 419 U Pump downtime to the pump turning activation 168 0 9999 h 420 A 421 U Active pump turning time 60 0 9999 s 422 A 423 U Active function preheating of water operation time 120 0 600 s 424 A 425 U Pre-heating function blocking time between AHU unit shut-down and restart 5 0 30 min 426 A 427 U Water heater circuit heating curve setting at the AHU start-up X1 -10 -30 5 °C 428 A 429 U Water heater circuit heating curve setting at the AHU start-up Y1 100 0 100 % 430 A 431 U Water heater circuit heating curve setting at the AHU start-up X2 10 0 50 °C 432 A 433 U Water heater circuit heating curve setting at the AHU start-up Y2 10 0 100 % 434 A 435 U Stop to Run mode switching delay AP trigger value 60 0 600 s 436 A 437 U Water heat exchanger dependent AP trigger value – AHU in Run mode 15 0 50 °C 438 A 439 U Water heat exchanger dependent AP trigger value - AHU in Stop mode 30 0 50 °C 440 A 441 U Inlet air dependent AP evaluation enabling delay aer the unit start-up 60 0 600 s 442 A 443 U Inlet air temperature dependent AP start-up – failure alarm A 6 -64 64 °C 444 A 445 U Inlet air temperature dependent AP start-up 8 -64 64 °C 446 A 447 U Maximum return water temperature 70 20 140 °C
Water pre-heating
448 A 449 U Outdoor dependent pre-heating (pump) start-up 5 -50 15 °C 450 A 451 U Pump downtime to the pump turning activation 168 0 9999 h 452 A 453 U Active pump turning time 30 0 9999 s 454 A 455 U Minimum pump run time 30 0 9999 s
Heating water source switching 456 A 457 U Limit value for heating 15 5 25 °C 458 A 459 U Start-up sequence delay 120 10 600 s
Gas heating
460 A 461 U Cooling sequence enabling 0 without cooling
1 with cooling 462 A 463 U Minimum burner run time 150 0 600 s 464 A 465 U Minimum burner downtime 150 0 600 s 466 A 467 U Burner restart protection time (burner Stage 1) 150 0 600 s 468 A 469 U Modulation burner opening/closing speed (burner Stage 1) 5 0 20 %/s 470 A 471 U Heating request value for the burner Stage 2 switch-off 40 10 100 % 472 A 473 U Maximum flue-gas temperature setting for alarm 230 210 400 °C 474 A 475 U Maximum flue-gas temperature 210 160 p.472 °C 476 A 477 U Requested flue-gas temperature 160 150 210 °C 478 A 479 U Minimum flue-gas temperature 150 100 160 °C
Electric heating 480 A 481 U Electric heating switching on – request for heating 20 0 100 % 482 A 483 U Electric heating hysteresis 10 1 100 %
38
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
Mixing
484 A 484 U Minimum fresh air value setting 20 0 100 % 484 A 484 U Minimum fresh air value setting – Comfort mode (pool unit) 20 0 100 %
485 A 485 A Minimum fresh air value setting – Economy mode (pool unit) 20 0 100 % 484 A 485 U Minimum fresh air flow rate setting 20 0 100 % 486 A 487 U Starting temperature for mixing damper wide-open position 15 -64 64 °C 488 A 489 U Starting time for mixing damper wide-open position 60 0 600 s
490 U Mixing damper control signal recurrence vale (normal/inverse) 100 0 100 %
Max. limit of fresh air function (ventilation unit)
563 A 564 U Max. limit of fresh air according to T outdoor 40 0 100 % 565 A 566 U T outdoor from which the Max. limit of fresh air is activated -10 -100 100 °C
567 U Information about the Max. limit of fresh air activation 0 Inactive
1 Active 491 A 492 U Required temperature for pre-heating -20 -50 10 °C 493 A 494 U Outdoor dependent electric pre-heating blocking -30 -50 10 °C 495 A 496 U Heating request dependent el. –pre-heating switch-on 20 0 100 % 497 A 498 U Hysteresis for electric pre-heater switch-off 10 0 100 %
Electric reheating 502 A 503 U Heating request dependent electric re-heating start-up for Stage 1 20 0 100 % 504 A 505 U Hysteresis for electric re-heating switch-off 10 1 100 % 506 A 507 U Fan stage dependent outlet limitation ST1 100 0 100 % 508 A 509 U Fan stage dependent outlet limitation ST2 100 0 100 % 510 A 511 U Fan stage dependent outlet limitation ST3 100 0 100 % 512 A 513 U Fan stage dependent outlet limitation ST4 100 0 100 % 514 A 515 U Fan stage dependent outlet limitation ST5 100 0 100 %
Heat recovery
516 A 517 U Freezing determination temperature exchanger 1 -64 64 °C 518 A 519 U Start temperature for maximum - HRE speed/volume open BP PE 15 -64 64 °C 520 A 521 U Start time for maximum - HRE speed/volume open BP PE 60 0 600 s 522 A 523 U Heat recovery request dependent HRE run enabling 38 0 100 % 524 A 525 U Hysteresis for HRE run stop 5 0 100 %
526 U Information - antifreeze protection start-up 0 inactive
1 active
Night turning
527 A 528 U Time to next turning 3 0 9999 h 529 A 530 U Active turning time 300 0 9999 s
Humidification
531 A 532 U
Relative set-point of relative humidity - Comfort 40 0 100 %r.H. 535 A 536 U
Relative set-point of humidity - Economy 30 0 100 %r.H. 541 A 542 U
Humidification blocking in summer 0 Ne 0
1 Ano
545 U Humidification output % 550 G
Calculated current humidification set-point in the cascade
Dehumidification
533 A 534 U
Dehumidification relative set-point - Comfort 60 0 100 %r.H.
537 A 538 U
Dehumidification relative set-point - Economy 70 0 100 %r.H. 533 A 534 U Dehumidification required relative value 60 0 100 %r.H.
537 A 538 U Dehumidification required absolute value 12 0 100 g/kg 539 A 540 U Maximum humidity required value 80 0 100 %r.H.
543 U Current humidity value 544 U Maximum humidity % 546 U Dehumidification output % 547 U Dew point °C
548 A 549 U Dew point deviation 1 -64 64 °C
551 G Calculated current dehumidification required value for cascade control %r.H.
Humidity-dependent fan speed compensation 552 A 553 U Humidity required value for compensation 50 0 100 %r.H. 554 A 555 U Fan speed compensation function 0 increase 0
39
List of Data Points (HMI-SG controller)
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
List of Data Points (HMI-SG controller)
1 decrease
556 U Compensation display %
Humidity-dependent mixing damper position compensation
560 A 561 U Fan speed compensation function 0 Increase 0
1 Decrease
562 U Compensation display %
Control constants
Cooling factors (all versions) 601 S 602 A Proportional factor -5 603 S 604 A Integrating factor 60 s 605 S 606 A Derivative factor 0 s
Heat pump factors - heating 607 S 608 A Proportional factor 5 609 S 610 A Integrating factor 300 s 611 S 612 A Derivative factor 0 s
Heat pump factors - cooling 613 S 614 A Proportional factor -5 615 S 616 A Integrating factor 300 s 617 S 618 A Derivative factor 0 s
Room (outlet) temperature dependent fan speed compensation 619 S 620 A Proportional factor 20 621 S 622 A Integrating factor 0 s 623 S 624 A Derivative factor 0 s
Heating dependent fan speed compensation 625 S 626 A Proportional factor 5 627 S 628 A Integrating factor 120 s 629 S 630 A Derivative factor 0 s
Cooling dependent fan speed compensation 631 S 632 A Proportional factor -10 633 S 634 A Integrating factor 120 s 635 S 636 A Derivative factor 0 s
Air quality CO2 (VOC,CO) dependent compensation (damper position/
fan speed) 637 S 638 A Proportional factor -0.3
639 S 640 A Integrating factor 300 s 641 S 642 A Derivative factor 0 s
Mixing
643 S 644 A Proportional factor 7 645 S 646 A Integrating factor 45 s 647 S 648 A Derivative factor 15 s
Heat recovery RHE/BP PE 649 S 650 A Proportional factor 3 651 S 652 A Integrating factor 60 s 653 S 654 A Derivative factor 1 s
Heat recovery – antifreeze protection 655 S 656 A Proportional factor 20 657 S 658 A Integrating factor 150 s 659 S 660 A Derivative factor 0 s
Electric reheating 661 S 662 A Proportional factor 1 663 S 664 A Integrating factor 60 s 665 S 666 A Derivative factor 0 s
Electric pre-heating 667 S 668 A Proportional factor 5 669 S 670 A Integrating factor 120 s 671 S 672 A Derivative factor 0 s
Water heating with pre-heating function 673 S 674 A Proportional factor – AP from return water 20 675 S 676 A Integrating factor - AP from return water 90 s
40
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
List of Data Points (HMI-SG controller)
677 S 678 A Derivative factor - AP from return water 0 s 679 S 680 A Proportional factor - AP from inlet air 50 681 S 682 A Integrating factor - AP from inlet air 0 s 683 S 684 A Derivative factor - AP from inlet air 0 s 685 S 686 A Proportional factor - AP from max. return water temperature -3 687 S 688 A Integrating factor - AP from max. return water temperature 300 s 689 S 690 A Derivative factor - AP from max. return water temperature 0 s 691 S 692 A Proportional factor - from temperature request 5 693 S 694 A Integrating factor - from temperature request 150 s 695 S 696 A Derivative factor - from temperature request 0 s
Electric heating
697 S 698 A Proportional factor 2 699 S 701 A Integrating factor 60 s 702 S 703 A Derivative factor 0 s
Gas heating
704 S 705 A Proportional factor - burner 5 706 S 707 A Integrating factor - burner 60 s 708 S 709 A Derivative factor - burner 0 s 710 S 711 A Proportional factor - bypass damper -5 712 S 713 A Integrating factor - bypass damper 120 s 714 S 715 A Derivative factor - bypass damper 0 s 716 S 717 A Proportional factor - maximum temperature of flue gas 10 718 S 719 A Integrating factor - maximum temperature of flue gas 120 s 720 S 721 A Derivative factor - maximum temperature of flue gas 0 s 722 S 723 A Proportional factor - minimum temperature of flue gas -10 724 S 725 A Integrating factor - minimum temperature of flue gas 120 s 726 S 727 A Derivative factor - minimum temperature of flue gas 0 s
Cascade temperature control
728 S 729 A Proportional factor 10 730 S 731 A Integrating factor 1200 s
Cascade humidity control
732 S 733 A
Proportional factor 4
734 S 735 A
Integrating factor 0 s
Humidification
736 S 737 A
Proportional factor 5
738 S 739 A
Integrating factor 120 s
740 S 741 A
Derivative factor 0 s
732 S 733 A Proportional factor 4 734 S 735 A Integrating factor 0 s
Dehumidification
742 S 743 A Proportional factor -2 744 S 745 A Integrating factor 240 s 746 S 747 A Derivative factor 0 s
Humidity-dependent fan speed compensation
748 S 749 A Proportional factor -5 750 S 751 A Integrating factor 0 s 752 S 753 A Derivative factor 0 s
Constant Air Flow/Pressure Control - inlet
754 S 755 A Proportional factor 0.3 756 S 757 A Integration factor 30 s 758 S 759 A Differentiation factor 0 s
Constant Air Flow/Pressure Control - outlet
760 S 761 A Proportional factor 0.3 762 S 763 A Integration factor 30 s 764 S 765 A Differentiation factor 0 s
Checks, system and network settings
Humidity-dependent mixing damper position compensation
766 S 767 A Proportional factor -2 768 S 769 A Integrating factor 45 s
41
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
770 S 771 A Derivative factor 0 s
Difference between required and inlet temperature monitoring 801 A 802 G Maximum difference (±°C) 10 0 99 °C 803 A 804 G Minimum limit (°C) 10 0 99 °C 805 A 806 G Time delay aer AHU start-up (s) 60 0 9999 s
Difference between required and room (outlet) temperature monitoring 807 A 808 G Maximum difference (±°C) 10 0 99 °C 809 A 810 G Minimum limit (°C) 10 0 99 °C 811 A 812 G Time delay aer AHU start-up (s) 600 0 9999 s
Remote fault
813 A 814 G Failure class selection to digital output 0 Failure A 1
1 Failure A+B
815 G Alarm message (generated depending on priorities) 0 Normal
1 Alarm
Fire mode
816 A 817 G Fan behaviour during fire selection 0 Stop 0
1 Inlet fan 2 Outlet fan
3 Both fans 818 A 819 G Fan output during fire selection 80 0 100 % 820 A 821 G Fire alarm activation inlet temperature 70 0 99 °C 822 A 823 G Fire alarm activation outlet temperature 50 0 99 °C
Alarm number for HMI
824 U Alarm number
System settings - control unit
825 A 825 A Failure acknowledgement (reset of all failures aer they have been removed) 0 No
1 Yes 826 S 826 S Soware reset of the controller 0 without reset
1 reset 827 S 827 S Control unit location building physical address 0 0 15 828 S 828 S Control unit location floor physical address 0 0 15 829 S 829 S Control unit device address 0 0 250
SD card
830 S Application load from SD card 0 No change
1 Loading 834 S Parameter save to SD card 0 Passive
1 Active
835 S Parameter save to SD card - successful 0 No
1 Yes 836 S Parameter load from SD card 0 Passive
1 Pasrtial
2 Full
837 S Parameter load SD card - successful 0 No
1 Yes 831 S 831 S Data point recovery (factory settings) 0 No
1 Yes
User settings
832 A 832 A Data point saving (user settings) 0 without saving
1 with saving 833 A 833 A Data point recovery (user settings) 0 No
1 Yes
ModBus
838 S Alarm 0 OK
1 Error 839 S 839 S Failure flow activation delay (at fan start-up) 45 0 600 s 840 S 840 S Failure flow activation delay (during fan run) 5 0 600 s 841 S 841 S ermo-contact (TK) failure activation delay (fans) 2 0 600 s 842 S 842 S Frequency inverter failure activation delay 2 0 600 s
42
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
843 S 843 S Number of message repeating during error transfers 2 844 S 844 S Number of error transfers for communication failure evaluation 6 845 S 845 S Frequency inverter 1 address, inlet fan 1 846 S 846 S Frequency inverter 2 address, inlet fan backup or second inlet fan 2 847 S 847 S Frequency inverter 3 address, inlet fan twin backup 3 848 S 848 S Frequency inverter 4 address, inlet fan twin backup 4 849 S 849 S Frequency inverter 5 address, outlet fan 5 850 S 850 S Frequency inverter 6 address, outlet fan backup or second outlet fan 6 851 S 851 S Frequency inverter 7 address, outlet fan twin backup 7 852 S 852 S Frequency inverter 8 address, outlet fan twin backup 8 853 S 853 S Frequency inverter 9 address, 3rd auxiliary fan 9 854 S 854 S Frequency inverter 10 address, second 3rd auxiliary fan 10 857 S 857 S Frequency inverter 11 address, rotary heat exchanger 11 858 S 858 S Control unit Modbus resistance terminal 0 inactive
1 active
Network connection configuration (Aer setting – the reset is required !!)
859 A DHCP 0 passive
1 active
860 A Settings IP[w] 192 0 255 861 A Settings IP[x] 168 0 255 862 A Settings IP[y] 1 0 255 862 A Settings IP[z] 199 0 255
864 U Actual IP[w] 865 U Actual IP[x] 866 U Actual IP[y]
867 U Actual IP[z] 868 A Settings mask [w] 255 0 255 869 A Settings mask [x] 255 0 255 870 A Settings mask [y] 255 0 255 871 A Settings mask [z] 0 0 255
872 U Actual mask [w]
873 U Actual mask [x]
874 U Actual mask [y]
875 U Actual mask [z] 876 A Settings gateway [w] 0 0 255 877 A Settings gateway[x] 0 0 255 878 A Settings gateway [y] 0 0 255 879 A Settings gateway [z] 0 0 255
880 U Actual gateway [w]
881 U Actual gateway [x]
882 U Actual gateway [y]
883 U Actual gateway [z]
System settings - room unit
884 S 884 S Transition to time program delay 1 0 23 h 885 A 885 A Byte address, Diagnostic mode – byte address 5 886 A 886 A Alarm mode 0 N/A 2
1 only aer alarm 2 constantly
887 S 887 S Room temperature display, combined or inlet temperature 0 Temp. from HMI-SG 0
1 Temperature average 2 Outlet Temperature 3 Temperature in the inlet
895 U 895 U Temperature unit display settings °C/°F 0 °C 0
1 °F 896 A 896 A Required value compensation setting +/- 3 0 12 °C 897 A 897 A Required value increment 0 Increment per 0.1 0 °C
1 Increment per 0.5 °C
43
898 A 898 A Displayed time format - 12h/24h 0 24 h
1 12 h
Passwords
899 S 899 S Password for Service level access 0 9999 901 A 901 A Password for Admin level access 0 9999 902 U 902 U Password for User level access 0 9999 903 G 903 G Password for Guest level access 0 9999
Comunication with Building management system (BMS) - (Aer settings - reset required !!) LON
921 S 921 S Send heart beat (s) 2700 0 9999 s 922 S 922 S Receive heart beat (s) 3600 0 9999 s 923 S 923 S Min send intervall (s) 5 0 9999 s 924 S 924 S Service pin 0 inactive
1 active
925 S 925 S Out temperature value 0 of application 0
1 of communication
926 S 926 S Fire alarm (external) 0 of application 0
1 of communication
Modbus RTU - Slave (BMS)
925 S 925 S Out temperature value 0 of application
1 of communication
926 S 926 S Fire alarm (external) 0 of application
1 of communication
931 S 931 S Modbud Slave1 0 inactive
1 active
932 S 932 S Address Slave1 1 933 S 933 S Baud rate Slave1 default 9600 b/s
2400 (factor 10) 4800 (factor 10) 9600 (factor 10) 19200 (factor 10) 38400 (factor 10)
934 S 934 S Stop bits Slave1 0 One stop bit 1
1 Two stop bits
935 S 935 S Parity Slave1 0 Even 2
1 Odd
2 None
936 S 936 S Termination (resistor) Slave1 0 inactive 0
1 active
937 S 937 S Response timeout Slave1 5 0 3600 s
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level
44
List of Failures (HMI-SG controller)
Failure
Description
Class
Failure
Number
Failure Causes
Reduced humidifi­cation output
B 10
Reduced humidification output due to the temperature priority (swimming-pool unit) – an information message.
Auxiliary Fan B 15
1.) Communication error between control unit and the auxiliary fan frequency inverter (Modbus data bus) – inverter internal error; wrong settings of the frequency inverter data points – bus communication protocol, data transfer rate, parity, number of stop-bits, com­munication timeout; poor connection of the bus cable to the frequency inverter terminals; bus terminal resistance settings on the last frequency inverter has not been performed.
2.) Auxiliary fan failure (Modbus data bus) - thermo-contact, flow sensor
Auxiliary Fan - twin B 16
1.) Communication error between control unit and the auxiliary fan twin frequency inverter (Modbus data bus) – inverter internal error; wrong settings of the frequency inverter data points - bus communication protocol, data transfer rate, parity, number of stop-bits, com­munication timeout; poor connection of the bus cable to the frequency inverter terminals; bus terminal resistance settings on the last frequency inverter has not been performed.
2.) Auxiliary fan twin failure (Modbus data bus) - thermo-contact, flow sensor
Backup fans in the inlet
B 18
Main inlet fan failure (backup fan activated) - thermo-contact, flow sensor A Class failure – inlet backup fan shutdown
Backup fans in the outlet
B 19
Main outlet fan failure (backup fan activated) - thermo-contact, flow sensor A Class failure - outlet backup fan shutdown
Communica­tion, Modbus
B 23
Communication error between control unit and the fan or ROV frequency inverter (Modbus data bus) - inverter internal error; wrong settings of the frequency inverter data points – bus communication protocol, data transfer rate, parity, number of stop-bits, commu­nication timeout; poor connection of the bus cable to the frequency inverter terminals; bus terminal resistance settings on the last frequency inverter has not been performed.
Process com­munication KNX
B 23 Communication error between control unit and HMI-SG controller (KNX bus)
Room unit 1 ­Temperature
B 24 Disconnected or damaged HMI-SG1 controller
Room unit 2 ­Temperature
B 24 1) Disconnected or damaged HMI-SG2 controller
2) Wrong HMI-SG2 controller communication address setting (the same address with the HMI-SG1 controller)
Outdoor tem­perature
B 25 Disconnected or damaged outdoor temperature sensor
Room temperature B 26 Disconnected or damaged room temperature sensor Outlet tem-
perature
B 28 Disconnected or damaged outlet temperature sensor
Inlet temperature difference
B 32
Information message on the difference between inlet and required temperatures, provid­ing the Inlet and Required Temperature Difference Monitoring has been activated (in the data point 201). If the temperature difference is higher than pre-set Maximum Difference (data point 801) or if the inlet temperature drops below the pre-set minimum threshold (data point 803), an information message is displayed.
Room tempera­ture difference
B 33
Information message on the difference between room/outlet and required temperatures, providing the Inlet and Required Temperature Difference Monitoring has been activated (in the data point 201). If the temperature difference is higher than pre-set Maximum Difference (data point 807) or if the room/outlet temperature drops below the pre-set minimum threshold (data point 809), an information message is displayed.
45
List of Failures (HMI-SG controller) (continuation)
Failure
Description
Failure
Class
Failure
Number
Failure Causes
Outdoor temperature dependent heat pump blocking
B 35 Information message – e heat pump blocked due to outdoor temperature
Heat pump B 36 Heat pump failure – contact
Humidification B 37 Humidifier failure - contact
Filters B 39 Filter failure - contact Fan operat-
ing hours
B 40
e pre-set fan operating hours have been exceeded; operating hours are set using the HMI-DM, TM or HMI@Web controllers.
Cooling B 41 Cooling failure (direct expansion evaporation, inverter condensing unit) -contact
ZZT (antifreeze protection)
B 42
1.) Lost communication between control unit and ROV frequency inverter - inverter internal error; wrong settings of the frequency inverter data points (bus communication protocol, data transfer rate, parity, number of stop-bits, communication timeout; poor connection of the bus cable to the frequency inverter terminals; bus terminal resistance on the last frequency inverter has not been performed)
2.) Antifreeze protection ROV/DEV has been activated due to drop in temperature below the pre-set value (data point 516).
ZZT (ROV) B 43 Belt - rotary heat exchanger
Inlet air rela­tive humidity
B 46
1.) Inlet air humidity sensor disconnected or damaged
2.) Humidity > 100%
Outdoor air rela­tive humidity
B 47
1.) Outdoor air humidity sensor disconnected or damaged
2.) Humidity > 100%
Room air rela­tive humidity
B 48
1.) Room air humidity sensor disconnected or damaged
2.) Humidity > 100%
Air quality (CO, CO2)
B 49
1.) Air quality sensor disconnected or damaged
2.) Air quality > 3000 ppm
Back draught protection (TH)
B 55 Back draught protection for the chamber aer cooling – thermostat TH 167 or ES3M-T3.
Flue-gas high temperature, heater shut down
B 56 Flue-gas temperature sensor disconnected or damaged
Flue-gas high temperature, VZT shut down
A 57
1.) Flue-gas temperature sensor disconnected or damaged
2.) Flue-gas temperature is higher than the pre-set temperature (data point 472).
Burner failure A 58 Burner internal failure - contact
Electric preheater A 59 Temperature behind the electric pre-heater < -50°C
B 59
1.) Temperature sensor behind the electric heater disconnected or damaged
2.) Electric pre-heater failure - thermostat
Temperature in the inlet
A 60
1.) Inlet air sensor disconnected or damaged
2.) Inlet air temperature is higher than the pre-set temperature (data point 442) – water heating antifreeze protection (PMO) is active.
Heat exchanger freezing
B 61 Temperature sensor behind ROV disconnected or damaged
Electric heating A 62 Electric heater failure - thermostat
46
Electric reheating A 63 Electric aer-heater failure - thermostat Water heater
pump
A 65 Water heater pump failure - contact
Water heating ad­ditional antifreeze protection (PMO)
A 65 Electric heating additional PMO - thermostat
Inlet fan A 66 Backup inlet fan error - thermo-contact
Inlet fan (air­flow failure)
A 66
1.) Backup inlet fan error - flow sensor
2.) Single-speed fan error - flow sensor Outlet fan A 67 Backup outlet fan error - thermo-contact Outlet fan (air-
flow failure)
A 67 Backup outlet fan error - flow sensor
Air flow sen­sor (pressure)
- inlet fan
A 69 Unconnected or damaged air flow sensor (pressure) - inlet fan
Air flow sen­sor (pressure)
- outlet fan
A 70 Unconnected or damaged air flow sensor (pressure) - outlet fan
Fan (inlet, outlet) A 71
1.) Communication error between control unit and the inlet/outlet fan frequency inverter
(Modbus data bus) - inverter internal error; wrong settings of the frequency inverter data points – bus communication protocol, data transfer rate, parity, number of stop-bits, com­munication timeout; poor connection of the bus cable to the frequency inverter terminals; bus terminal resistance settings on the last frequency inverter has not been performed.
2.) Inlet/outlet fan error - thermo-contact
Fan (inlet, outlet) – flow failure
A 72
1.) Lost communication between control unit and fan frequency inverter - inverter internal
error; wrong settings of the frequency inverter data points - bus communication protocol, data transfer rate, parity, number of stop-bits, communication timeout; poor connection of the bus cable to the frequency inverter terminals; bus resistance terminal settings on the last frequency inverter has not been performed.
2.) Inlet/outlet fan error - flow sensor
Water pre-heating A 74
1.) Temperature sensor disconnected or damaged
2.) Water temperature in the water heat exchanger return pipe > 140 °C, or water tem-
perature in the water heat exchanger return pipe < 5 °C
Outlet tempera­ture-dependent fire alarm activation
A 81 Fire alarm triggered due to exceeded pre-set outlet air temperature (data point 820)
Inlet temperature­dependent fire alarm activation
A 81 Fire alarm triggered due to exceeded pre-set inlet air temperature is (data point 821)
Fire alarm (external failure)
A 81
1.) Fire alarm triggered by the fire dampers - contact
2.) External failure - contact
Water heater re­turn water
A 82
1.) Temperature sensor disconnected or damaged
2.) Water temperature in the water heat exchanger return pipe > 140 °C, or water tem-
perature in the water heat exchanger return pipe < 8 °C
List of Failures (HMI-SG controller) (continuation)
Failure
Description
Class
Failure
Number
Failure Causes
47
Remak Mobile App
Introduction
REMAK Application is a touchscreen application for mobile phones (smartphones) and tablets running Google Android (from v. 4.0.3) in installations / applications where you can use Wi-Fi LAN and / GSM mobile data to connect to the Internet. Mobile applications such as HMI to VCS serve as a user-friendly driver for basic HVAC control - triggering desired mode (+ switching off), setting (user-friendly parameters only) and simple operation overview (feedback).
Function
Mobile application brings control/monitoring capabilities easily and from anywhere- where a mobile device can be connected via wifi or GSM mobile data to a computer network, of the Internet (ie provided the network's functionality (availability) is no longer necessary, and no other operating mode is required). It does not include full service setup/commissioning, but with the mobile application, the standard HMI @ WEB interface is also available - including via the mobile application menu (but standard sign-in required) - which must be used for commissioning of the whole device and basic network communication and password settings for the safe operation of the mobile application to control the HVAC. An example of a mobile application for setting the setpoints is shown in Figure 22.
Note: The VCS control unit must be equipped (factory­configured) with a LAN connection, incl. License (or Configuration ID) to use Remak - Inthouse. If the application licence is ordered = configured in the project, configuration IDs (two "codes") for the mobile application and the licence for the respective VCS, or controller, are included in the accompanying VCS documentation and printed on the stickers attached directly to the controller.
Security
Use of the application is security with an adjustable password in the controller. Security against unauthorized access to the LAN must be provided with standard IT resources (see also on page 54 of this manual).
Note: Setting your own PLC password for Remak (as well as JSON communication) as well as for HMI@ EB is one of the necessary safeguards against unauthorized operation!
Further, the application (in the Settings menu) provides an extended log-in option for the "Advanced" user role using a "special" constant password (this is not a security password) allowing some specific elements for experts, i.e., more detailed information about automatic operation or the control mode (otherwise accessible on the HMI@WEB interface) to be displayed. This information can be rather confusing for ordinary users. Note: e RMKDEV user role is not intended for standard use, it is used only for development/test purposes of the manufacturer.
Additional information
Additional user information (basic features, questions and answers, application installation information) can be found on the product web page: https://www.remak.eu"
Figure 21 – mobile app GUI
48
Control (HMI-DM,HMI-TM controllers)
HMI-DM (HMI-TM) control devices ensure communication between the VCS control unit and the user.  ey are intended for air-handling device control, handling and service.  e HMI control device can be connected to the POL4xx or POL6xx controllers. During controller operation, a single HMI control device can be connected or disconnected and alternatively (in sequence) used to control multiple control units (controllers).
Connection
 e HMI-DM controller can be connected using a serial inter­face (4-wire, twisted pair) with two RJ45 connectors.  e cable length is 1.5 m (the cable is included in the delivery). When installed on a wall, the HMI-DM controller can be con­nected using a shielded 8-wire UTP cable with two RJ45 connectors.  e maximum distance is up to 50 m.  e HMI-TM controller can be connected to the control unit using a 4-wire cable (twisted pair) with one RJ45 connector and one slim connector.  e cable length is 2.5 m (the cable is included in the delivery).
Warning
A er connecting the controller to the control unit, it is nec­essary to route the cable through the PG16 grommet.  us degree of protection IP20 is ensured. If a higher level of protec-
tion of the distribution board cas­ing is required, the grommet will have to be resealed. An optional grommet with an RJ 45 connector can be used to make it easy to con­nect (disconnect) the HMI control­ler (an extra order is required, not included in the standard delivery).  en the RJ45 connector must be connected to the RJ45 socket on the controller. For the socket marking, see the fi gure.
Button (Name)
Activity Description
Scrolling knob
Turning
- Selection from the menu
- Selection from the param­eters or change to a value
Press - Selection/confi rmation
Hold
- When logged in, press and hold for at least 3 s to go to the log-in/log-out page.
- When not logged in at any access level, the log-in page is displayed.
Esc
Press - Cancels the change to
the parameter value
-Returns to the upper level of the menu/previous page
- Returns to the last active page before accessing the Pass­word Administration page
- Returns to the last active page before accessing the Home page using the Info button.
Hold - Goes to the Start Menu
Info
Press - Goes to the Main Menu from
the current menu page
- Goes to the Start Menu page from the Main Menu
Flashing green
- Air-handling unit start-up sequence
Green light - Air-handling unit operation
Failures
Press - Every time you press this button,
you will cycle through the following pages → List of Failures → His­tory of Failures → Alarm Settings (failure confi rmation and reset)
Flashing red
- Active unconfi rmed failures
Red light - Active confi rmed failures
Figure 22
Figure 23 – HMI-DM cotroller
Table 1 – Function Buttons
HMI-DM controller
Operating conditions
Degree of protection: IP 31. Permissible ambient temperature:
-40 °C to 70 °C. Relative humidity <95 %.
Device Description
 e controller consists of two separate parts – the face plate with a display and the rear plate. Dimensions of the HMI-DM controller are 144x96x26 mm and the integrated LCD display resolution is 208x96 pixels.  e display can show 8 lines.  e HMI-DM controller is equipped with three function buttons, INFO, FAILURE and ESC, and one scrolling knob. The scrolling knob and buttons are used to navigate within the menu and to change the parameters and control values.  e INFO, FAILURE and ESC buttons are equipped with LEDs to indicate operating states.  e controller can also be delivered in a version for free loca­tion.  e magnets on the rear side of the HMI enable the con­troller to be attached to metal parts (e.g. the air-handling unit).
Info
Failure
ESC
Scrolling knob
For fi xed mounting, the controller is equipped with threaded holes on its rear side to screw it to the mounting plate.
49
Control (HMI-DM,HMI-TM controllers)
HMI-TM controller
Operating conditions
Degree of protection: IP 65 (version with magnetic fi xation). Permissible ambient temperature: -20 °C to 60 °C. Relative humidity: 5 % to 95 %.
Device Description
Dimensions of the HMI-TM controller are 173x95.5x21.6 mm.  e LCD display resolution is 128x96 pixels.  e HMI-TM con­troller is equipped with 6 function buttons, INFO, FAILURE, ESC, UP, DOWN and ENTER.  e INFO, FAILURE and ESC buttons simultaneously indicate operating states (Stop – fail­ure, operation).  e UP, DOWN and ENTER buttons are used to navigate through the menu.  e magnetic plate on the rear side of the HMI enables free attachment to metal objects.
Figure 24 – Installation on a Wall
Figure 25 – HMI-TM controller
Table 2 – Function Buttons
Button
(Name)
Activity Description
Up
Press
- Scrolling the list upwards
- Increases the parameter value
Hold
- Hold this button longer than 1.5 s to speed up the list scrolling upwards
- Increases the parameter values in higher grades
Down
Press
- Scrolling the list downwards
- Decreases the parameter values
Hold
- Hold this button longer than 1.5 s to speed up the list scrolling downwards
- Decreases the parameter values in higher grades
Enter
Press Selection/confi rmation
Hold
- When logged in, press and hold for at least 3 s to go to the log-in/ log-out page.
- When not logged in at any access level, the log-in page is displayed.
Info
Press
- Goes to the Main Menu from the current menu page
- Goes to the Start Menu page from the Main Menu
Flashing green
- Air-handling unit start-up sequence
Green light - Air-handling unit operation
Failures
Press
- Every time you press this button, you will cycle through the following pages → List of Failures → His­tory of Failures → Alarm Settings (failure confi rmation and reset)
Flashing red - Active unconfi rmed failures
Red light - Active confi rmed failures
Esc
Press
- Cancels the change to the parameter value
- Returns to the upper level of the menu/previous page
- Returns to the last active page before accessing the Pass­word Administration page
- Returns to the last active page before accessing the Home page using the Info button.
Hold - Moves to the HMI Settings page
Info
Failure
ESC
Up
Down
Enter
50
Control (HMI-DM,HMI-TM controllers)
a The user log-in is graphically indicated by the key
symbol in the page heading. The access levels are distinguished by the following symbols.
b Page Heading c Current line from the total number of lines on the page d The page also includes the line above the current
display e The page also includes the line below the current display
f Access to the Main Menu from the current menu page g Current line of the selection
Access to the Submenu
e cursor marks the selection of parameters on a correspond­ing line. e arrow indicator in the right part of the display indicates the option to access a submenu.
n Turn the knob (or use the Up and Down buttons) to select
the required line.
n Press the knob (Enter) to access the submenu.
If only the value description is highlighted on the line, the value on the line is intended only to be displayed, refer to Temperatures.
Value Settings
If the description and value of the parameter is highlighted on the line, the highlighted value can be changed.
n Turn the knob (or use the Up and Down buttons) to select
the line.
n Press the knob (Enter) to confirm the page selection. n Turn the knob (or use the Up and Down buttons) to change
the parameter values.
n Press the knob (Enter) to confirm the value change. n Press the Esc button to exit the page.
Setting the Selection from Multiple Parameters
n e current parameter selection is marked. n Turn the knob (or use the Up and Down buttons) to select
a new parameter.
n Press the knob (Enter) to confirm the selection or press
the Esc button to retain the original value as valid.
Setting the Continuous Value using the Knob
e scale displays minimum and maximum values.
n Set the arrow on the respective number n By turning the wheel, the number can be changed
from 0 to 9.
n e cursor is moved to the following item automatically n Press the knob to confirm the selection or press the Esc
button to retain the original value as valid
Setting the Continuous Value using the Up and Down Buttons
n Press (hold) the Up or Down button to set the required
value.
n Press Enter to confirm the selection or press the Esc but-
ton to retain the original value as valid.
Display Layout
User Icon
GUEST
USER
ADMINISTRATOR
SERVICE
Table 3 – access levels
Figure 26 – LCD isplay
a
b
d
c
e
g
f
51
Control (HMI@Web – Connection to PC and LAN/WAN)
Installation and Connection to PC and LAN/WAN
Basic Requirements
e HMI@Web controller is intended to operate the VCS control unit using an internet browser. is controller is a more convenient variant of HMI DM, TM controllers featuring remote control and PC control. However, it is not equipped with comfort features like data collection and filing, e-mail messages on system failure events. User access is the same as with HMI DM, TM controllers. No administration of users or their roles is created. e PC must be equipped with an Ethernet network card with the RJ-45 connector, or connected to the LAN network - the HMI@Web system can be connected directly to (one) PC or integrated into the LAN, resp. WAN network, and is acces­sible from any computer (access authorization is needed) in the network. e TCP/IP protocol must be installed on your PC (to install the TCP/IP protocol, refer to your operating system manual).
Figure 27 – Network connection settings
Warning
Before putting the HMI@Web controller operated by PC, respectively via LAN network, into operation, the installation of the controlled air-handling unit must be checked to see whether it has been performed in accordance with its Instal­lation and Operating Instructions (installation, inspections, safety precautions, heating media, etc.)! Refer to "Location and Installation".
Default HMI@Web IP Address Setting
During production, the HMI@Web unit was assigned the fixed IP address: 192.168.1.199, mask 255.255.255.0, and the default port 0.0.0.0.
Notice
If this address cannot be used in LAN, it is necessary to change the setting from the computer (directly connected PC as described below) before connecting it to the network.
HMI@Web controller Start-up Procedure
1. Step: HMI@Web controller connection:
* is cable is not part of delivery.
Notice – Proxy server settings
o ensure proper interoperation of the internet browser on your PC directly connected to the HMI@Web unit, it is necessary to disable proxy server! In Internet Explorer 8: Go to "Tools" / "Internet Options" >> "Connections" >> button / "Local network options" / "Specify" … lower half of the window = "Proxy server" box – must not be checked (see figure).
Figure 28 – HMI@Web unit connected directly to PC
HMI@Web
HMI@Web + stand-alone PC = HMI@Web controller connected directly to PC
Using the Ethernet crossed cable* (UTP cable, RJ-45 connec­tors) connect the HMI@Web unit ("LAN" socket on the upper side of the controller) to the network card of your computer.
Figure 29
Attention: Connector RJ-45 marked BSP, BUS cannot be used! It is intended for HMI controller – refer to "HMI Con­troller Operating Instructions".
Max. length of the cable be­tween the HMI@Web and com­puter can be 100 m; however,
we recommend 80 m. Switch the HMI@Web main switch on. If a greater distance between the PC and the VCS control unit controlled by the HMI@Web controller is desired, it will be necessary to use a structured network (Ethernet) including active network elements – see below, or contact a specialized PC and IT supplier.
52
Control (HMI@Web – Connection to PC and LAN/WAN)
Connection of the VCS control unit with the HMI@Web controller to the LAN
Warning
If the default IP address of the HMI@Web unit cannot be used in the LAN network – i.e. a different address range is used in the LAN network (e.g. 10.0.0…, 192.168.10…..), or the existing PC within the LAN network has already been assigned the IP address …199 (can be verified by the "ping + IP address" com­mand) which must be retained - it is necessary to change the HMI@Web IP address setting from the computer (as described above) before connecting it to the network. If you are not an administrator of the LAN network, you will have to contact your LAN administrator. e same applies if you are not an administrator of your computer. Using the Ethernet cable (not included in the HMI@Web delivery) connect the HMI@Web unit to the LAN network connecting point in the same way as any other LAN device. e same conditions as in step 1 (connecting points, cable lengths) apply for connection to LAN. To set the addresses, it is possible to use other controllers like HMI SG, TM and DM. Maximum HMI@Web unit distance from an active network element must comply with the Ethernet network conditions.
Notice: e HMI@Web unit can also be connected to the LAN network via the wi-fi access point in the client mode, etc. – consult your network administrator.
Figure 30 – HMI@Web connected to local network
HMI@Web
HMI@Web
To be able to operate the HMI@Web unit, a unique IP address within the network range (see fig. # 8) must be assigned to the HMI@Web unit. Go to "Connection" >> "LAN connection" (refer to Step 4: Activation). Always restart the HMI@Web unit aer assigning a new IP address – the new setting is applied aer restart. Attention! Always consult your network administrator if con­necting the HMI@Web to LAN.
2. Step: Computer Configuration - TCP/IP Settings
Warning
In this step, settings of the PC using Microso Windows® XP are described; if you use other operating systems you will have to perform corresponding settings of your computer in accordance with your operating system user manual, or ask an expert for help. is setting procedure is needed only for a permanent direct connection to PC, or to change the HMI@ Web settings before its integration into the LAN network.
Aer setting the HMI@Web unit (following the below de­scribed procedure), and when the HMI@Web default address complies with network addressing, it is only necessary to en­able new hardware in the infrastructure administration – there is no need to make any other adjustments to individual PCs.
Adjust PC network card settings in Windows:
Go to "Start" >> "Settings" >> "Control Panel" >> "Network connection"). Click (right mouse button) on "Local network connection", then on "Properties", and display "Internet pro­tocol (TCP/IP)" properties“.
Figure 31 – TCP/IP settings
If the protocol is not found in the list of items (it is not installed), add the item to the system. Click the "Install" button, select the "Internet protocol (TCP/IP)", and follow the instructions on the screen. Select item "Use the following IP address". Type "192.168.1.3"** into the "IP address" box and "255.255.255.0" into the "Net­work mask" box. Do not type anything into the item boxes of the second part of the window (leave them blank). If you are prompted by the system to restart, confirm the restart immediately.
Connection, resp. TCP/IP Protocol Verification
To verify the settings and connection, type the HMI@Web address into the URL box of the internet browser (the HMI@ Web system must be switched on); it should start functioning in 0.5 – 3 minutes - the time needed to initialize the webserver.
Aer sending the request, and if the settings and connecting are correct, the HMI@Web unit is ready to be configured, and the login window is displayed on the screen requesting the user name and password.
Figure 32 – IP address entry
** Any number from 1 to 254 except 199 (which is assigned to the HMI@Web controller) can be used in the first place of the IP address.
53
Control (HMI@Web – Connection to PC and LAN/WAN)
3rd Step Setting the Web@HMI for Connection
The Web@HMI controller can be configured from the web interface (the same one which serves for normal operation of the system). Enter the following IP ad­dress http://192.168.1.199 in the address field in the web browser and confirm with the "Enter" button. Note: The Web@HMI configuration for the con­nection itself is not dependent on the browser used. Enter log-in data in the fields of the Web Server dialog box – see the figure:
User name: WEB (or ADMIN)* Password: SBTAdmin!
Figure 33 – Web Server dialog box
Figure 34 – Start screen
Figure 35 – Log-in screen
Figure 36 – Password dialog box
ere is an account for one user on the HMI@Web Web Server. e Web Server user log-in name and password can be changed in the menu: Connection >> LAN Connection. Upon successful log-in to the HMI@Web Web Server, the Start screen is displayed.
To access the Main Menu, it is necessary to log in at the cor­responding access level. Upon selecting the link on the first line the log-in dialog box to enter the password is displayed.
e input field for entering the password is at the bottom of the browser. Enter log–in data to the fields of the dialog box – see the figure above; enter password – 4444. (factory pre-set access password to the HMI@Web – for the first start-up.
Attention – it is only valid until changed. ese log-in data correspond to the highest level user authori­sation (role: service) – they should only be reserved for the supplier performing the installation or the service provider. It is advisable to change the log-in data as soon as upon first log-in (Passwords >> Password change – actual or lower access level password change is offered). e dialog box to enter a new password is displayed at the bottom of the browser. Press the Save button to confirm and save the changes to the settings.
Warning
Once the changes have been made, it will no longer be possible to use the original data to log in. Keep your log-in data safely stored (keep them confidential). If you lose them, contact the manufacturer or authorized service representative. Apart from the service log-in data, it is also necessary to modify other user pre-set log-in data to enable access to the HMI@Web for the operating staff – rename them according to the actual authorised users and change the correspond­ing passwords:
Role Pwd Level number
SERVICE 4444 2 ADMINISTRATOR 3333 4 USER 2222 6 GUEST 0000 8
Note: If the user settings are not performed within this phase of commissioning, it is necessary to perform them at the lat­est during training of the operating staff or device handover to the end user.
* ADMIN only if the WEB log-in is non-functional (for older systems)
54
Control (HMI@Web – Connection to PC and LAN/WAN)
Figure 37 – LAN connection settings
4th Step: How to Change the HMI@Web Controller IP Address
e HMI@Web controller IP address for operation in your network can be changed from the following page: Connection >> LAN connection
e lines allowing entries of values are marked with a red button. Once the button of the respective line has been activated, enter the new value in the dialog box at the bottom of the browser. Press the button to confirm and save the changes. Progressively enter and save all the items "Enter …" (Address, Mask or Gate). Finally, restart the HMI@Web controller using the option "Ap­ply + Reset". Aer the restart, the device starts reporting on the new address (once the initiation has been completed – it takes about 3 minutes).** To resume communication (if the network segment has been changed), it may be necessary to readjust the network connection settings on your PC so that they are compatible with the HMI@Web controller (respectively LAN); the HMI@Web controller with the modi­fied setting can be alternatively connected to the LAN. It is necessary to enter the correct network address in the browser to enable log-in.
5th step: LAN Connection Setting Warning
Any changes to the settings must be performed cautiously and carefully at each step. Each modifiable parameter (Address, Mask or Gate) must be carefully checked and saved separately.
en it is necessary to send (plan) the change entry – aer that, the settings must be finished using the option "Apply + +Reset". (Warning: Do not perform the restart by switching off or disconnecting the device – when saving the changes using the "Apply + Reset" option, the settings are simultane­ously stored in an archive which is needed for restart of the device aer a power supply failure - otherwise, there is a risk of uncontrolled changes to the settings.)
Note: Control start-up after device restart takes several seconds – it does not to do anything with the Web Server initiation. at is because of the standard start-up sequences that are being performed during the connected air-handling system start-up, i.e. opening of dampers, pre-heating and fan start. We strongly recommend not using the configuration with the address assigned by the DHCP server; instead, use the fixed IP address.
Warning
If the IP address of the given device happens to get lost (e.g. once the LAN setting have been changed) and it is not pos­sible to establish the connection (no response to the "ping" command, etc.), it is possible to use the HMI-DM or HMI-TM controllers to set the required parameters and restart the device directly.
Note: In extreme cases, the device can be looked up within the network using the MAC address (indicated on the name plate) – contact the network administrator.
Internet Integration
By connecting the WebClima system to the local network via the above-mentioned setting of the IP address and au­thorization of users, the basic (direct-interactive) monitoring and operating possibilities within the local network or by PC are enabled. To enable access to the WebClima system via internet, it is necessary to ensure direct access to the device from internet.
Notice: is is necessary especially if supervision (operation, service) outside the company is required.
To connect your HMI@Web unit to the internet, contact your network administrator.
Figure 39 – connection to the WAN network
HMI@Web
WAN
HMI@Web
Obrázek 38 – password setup for LAN connection
55
Control (HMI@Web – Connection to PC and LAN/WAN)
e network administrator in this case has at their disposal 2 public static IP addresses for the HMI@Web control unit:
88.100.1.1 and 88.100.1.2 e administrator can set the IP address translation at the router, for example, as follows:
Public IP address Inner IP address
88.100.1.1 192.168.1.4
88.100.1.2 192.168.1.5
or (to minimize the need for public addresses) leading through only one public IP address and communication port.
Warning to the network administrator
To enable access via internet it is necessary to enable access to the inner IP address via port 80 (http). Other communication ports must be DISABLED to keep the operation secure!
REMAK does not bear any responsibility for any misuse of the HMI@Web soware (Windows CE) or unauthor­ized penetration of the inner LAN network due to insuf­ficient inner network security.
Internet Browser Settings to operate the HMI@Web controller
Support of JavaScript and cookies must be enabled to ensure correct functioning of the browser interface on each PC connected to the HMI@Web controller. JavaScript is used to update values in the right (information) panel and for programming time schedules, and cookies are used for login. Further, file opening in new windows must also be enabled. As the parameters are measured on-line, we also recommend adjusting the temporary files retention (cache settings) in the internet browser (this is essential especially for MS Internet Explorer). e browser must verify the actual page version in every access to the page. Otherwise, saved not current values of parameters can be presented. If you have any doubts whether the read data are correct, refresh the page by clicking on the refresh icon on the browser menu bar, or use shortcut keys CTRL+F5 – forced page loading outside cache. e HMI@Web graphic user interface is optimized for Micro­so Internet Explorer 6.0/7.0 and FireFox 2.0. Other web browsers' settings must be checked in accordance with the following instructions.
Internet Explorer 8.0 and above
Internet Explorer JavaScript Support:
Go to the Internet Explorer menu "Tools" / "Internet Options" >> "Security" >> "Custom Level" >> "Scripting" – must be enabled.
Figure 40 – JavaScript support settings
In doing so, we recommend the following:
nImplement the HMI@Web unit into the secured inner net-
work aer the router / network firewall. e direct access to the unit must be ensured by further directing.
nTo increase security, we recommend locating the device
in the reserved network (DMZ) which is not a part of the company's LAN network, or accessing the device via the company's VPN.
Setting the Network Elements to enable HMI@Web Access via Internet
Ask your local network administrator to perform these activities!
56
Control (HMI@Web – Connection to PC and LAN/WAN)
Internet Settings (Explorer Cookies):
Go to the Internet Explorer menu "Tools" / "Internet Options" >> "Privacy" >> "Advanced" >> "Accept Cookies" (see fig. # 16)
Figure 41 – Cookies settings (IE)
Temporary Files' Settings
Go to the Internet Explorer menu "Tools" / "Internet Options" >>, "General >> "Temporary Internet files" >> "Settings...".
Figure 42 – Temporary Files' Settings (IE)
In the following window "Setting" >> "Check fro newer ver­sions of stored files >> select "Every visit to the page" >> set "Amount of disk space to use:" to the minimum (8 MB). en save the settings clicking the "OK" button.
Figure 43 – Temporary Files' Settings (IE)
Mozilla Firefox
Mozilla Firefox JavaScript support
Go to menu "Tools" / "Options" >> bookmark "Contents" >> Enable JavaScript should be checked.
Note: e control setting with Mozilla Firefox is the same as with Microso Windows and Linux systems.
Mozilla Firefox Cookies Settings
Go to menu "Tools" / "Options" >> bookmark "Private" >> menu Cookies >> cookies should not be blocked, if so, enable servers to set cookies.
Other browsers can be set similarly (however, the HMI@Web manufacturer does not guarantee their proper functionality).
Proxy servers
e proxy severs must be disabled if direct connection PC <-> HMI@Web is used.
Disabling proxy servers - Internet Explorer: Go to "Tools" / "Internet Options" >> "Connections" >> "Local network options" >> uncheck the box "Proxy server"
Disabling proxy servers - Firefox: Go to menu "Tools" / "Op­tions" >> … >>"Expanded>> bookmark "Network" >> Settings >> check the "Direct network connection".
If access is made within LAN, contact your LAN/PC ad­ministrator to perform the settings.
57
Control (HMI@Web – Connection to PC and LAN/WAN)
HMI@Web Environment Description
 e Web controller HMI@Web is controlled using the fol­lowing buttons:
Button/Icon Description
Press:
- Go to Main menu from the current page in the menu
- Go to the Home Menu page from the Start menu Flashes green - Startup sequence for HVAC Glows green - HVAC Run
 e Info icon icon indicates the access level to which the user is logged in a er the correct password; the icon is a link to opt-out from the HMI @ Web menu
Trouble-free status; the
icon is the link to go to the malfunctions page
Signaling one or more
alarms a er a fault has been acknowledged (the bell does not move); the icon is the link to go to the malfunctions page
Signaling a new fault before
confi rming it (the bell moves); the icon is the link to go to the malfunctions page
Link to main menu page from
anywhere in the menu
Go back one step, return to the
previous page in the menu
Reload the current
page in the menu
Go to the next page
in the menu
Set value or selection
from the menu
Cancel the newly entered value
or parameter selections before her confi rmation - remains original value or selection
Confi rm new value or
selection from the menu
Note: glows red
Note: Icon with green tinting
Note: Icon with red tinting
Note:  ashesred
Basic HMI@Web Operation Settings – Recapitulation
The basic HMI@Web system commissioning settings to prepare it for operating staff :
n Assigning authorization groups to users and their setting
before putting the unit into operation (to ensure unit security against unauthorized access).
n System time setting*
Required Settings in Temperature Modes:
Required temperature settings are performed from the page Settings >> Temperature Modes.
Clicking the red
button at the respective temperature you
will display a dialog box for a new temperature entering.
Save the new temperature using the SAVE button. To return to the previous page in the menu, click the CANCEL button. To go to the Main Menu, click the HOME button.
Weekly (Daily) Time Schedule Settings
Weekly time schedule can be set from the page Settings >> Time Modes >> Time Schedule. An exception time schedule can also be set in the weekly time schedule.
58
Control (HMI@Web – Connection to PC and LAN/WAN)
* HMI@Web controller automatically switches between summer and winter time according to European customs.
An exception time schedule can also be set in the weekly time schedule. It is possible to set maximum 6 time chan­ges and program states for each day of the week. Clicking the red button you will display a dialog box at the bottom of the browser window:
SCADA VCS – control (visualization and data collection)
it is a tool that extends the user's ability to control HMI @ Web. SCADA (Supervisory Control and Data Acquisition) "Dispatch Control and Data Collection". SCADA VCS enables above all the comfort and control of the HVAC equipment.
n clear list of failures / history n visualization of HVAC devices n Clear schedules and calendar settings n Tracking HVAC behavior using trends (current / archive) n includes the HMI @ WEB driver
(access to all data points)
e VCS is equipped with a web server running SCADA VCS. Just connect the VCS to the LAN / WAN and then use the Internet browser to connect to the VCS control unit with the SCADA. e connection is done in the same way as for HMI @ WEB control, part of the manual - Controls (HMI @ Web - connection and installation to PC and LAN / WAN).
Login credentials for access verification to the SCADA server:
user name: WEB password: SBTAdmin!
This tool will be appreciated by service and assembly companies to regulate the operation of HVAC equipment. Users will quickly orient themselves in the HVAC device assembly and appreciate the ease of setting user parameters.
Save the new time value using the SAVE button. Each time is assigned with a desired program state (fan speed stages and temperature mode). e program state can be entered using the dialog box displayed aer clicking the red
button on the row of the respective program state:
Confirm the new program state using the SAVE button.
e time assigned with *:* characters and Stop program state will not be applied. For the detailed description of the time schedule settings, refer to the chapter "Temperature and Time Modes".
59
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Monitor Monitor
Current modes Current modes
ActStateEquipment Current device state FanStageExtCnt Fan output stage (external control) FanStatus Fan state Actual time schedule Current time schedule
CalendarWeek Weekly time schedule CalendarExcept Exception time schedule CalendarO Switch-o time schedule
NumbOfFailures Current number of failures
Temperatures Temperatures
Supply Inlet air temperature °C Room Room temperature °C Room unit 1 Temperature (HMI-SG1) °C Room unit 2 Temperature (HMI-SG2) °C Return air Outlet air temperature °C Outdoor Outdoor air temperature °C Return water heat Return water temperature from the water heater °C Air heat exchanger Outlet air temperature behind the heat exchanger °C Air electric preheat Temperature behind the electric pre-heater °C ReturnWaterPreheating Return water temperature from the water pre-heater °C ExtraElectricHeating Temperature behind the electric after-heater °C Flue gas Flue gas temperature °C ValidRegulationRoom Room temperature (for control) °C
Humidity Humidity
Supply air relative Inlet - relative %r.H. Supply air absolut Outlet - absolute g/kg Supply air enthalpy Inlet - enthalpy kJ/kg Room relative Room - relative %r.H. Room absolut Room - absolute g/kg Room enthalpy Room - enthalpy kJ/kg Outs air relative Outdoor - relative %r.H. Outs air absolut Outdoor - absolute g/kg Outs air enthalpy Outdoor - enthalpy kJ/kg
Flow (Pressures) Flow (Pressures)
SupplyPress SupplyPress Pa ReturnPress ReturnPress Pa SupplyFlow SupplyFlow m3/h ReturnFlow ReturnFlow m3/h
Air quality Air quality
CO2 (VOC,CO)
CO2
(VOC,
CO) ppm
Outputs Performances
Fan supply output Inlet fan output % Fan exhaust output Outlet fan output % Fan additional output Auxiliary fan output % ExtraElectricalHtgPos Outlet level for the electric reheater % Heating valve Heating mixing set valve position % Cooling valve Cooling valve position % Cooling 2 Cooling valve position 2 % Cooling 3 Cooling valve position 3 % Electrical preheating Electric pre-heater outlet position % ElectricalHeatingValve Electric reheater outlet position % Heat pump output Heat pump outlet position % Heat Pump 2 Heat pump outlet position 2 % Heat Pump 3 Heat pump outlet position 3 % Mixing section position Outlet position to the mixing damper % Heat exchanger position Heat exchanger control outlet position % Gas heating out level Outlet level for the gas heater % BypassDamperPosition Outlet position for gas heater's BP damper % Request humidity Request for humication % Request dehumidity Request for dehumidication %
Working states Operating states
FanSupplyStatus Inlet fan state FanExhaustStatus Outlet fan state FanAdditionalStatus Auxiliary fan state ElectPreheat Electric pre-heater state WaterPreheat Water pre-heater pump state ElectReheating Electric re-heater state PumpOfWaterHeating Pump of water heating StateHeatExchanger Rotary exchanger State PrehtgFunctionsWaterHtg Pre-heating functions (water heating) WaterCoolPump Water cooler pump state CoolingStDXCool Cooling stage (2St) CoolInverter Cooling stage (inverter) ChlazInverter 2 Cooling stage (inverter) 2 ChlazInverter 3 Cooling stage (inverter) 3 Cool1Step Cooling state (1 St + inverter) HeatPump Heat pump state ElectricHeater Electric heater state GasHeater Gas heater state
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
60
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
StateHumidier Humidier state %
Settings Settings
Date and Time
Date
and
time
TimeValidity System time validity
Temp modes Temperature modes
Comfort - Heating Comfortable heating 22.6 0 99 °C Comfort - Cooling Comfortable cooling 24.6 0 99 °C Economic - Heating Economy heating 20.6 0 99 °C Economic - Cooling Economy cooling 28 0 99 °C ExSpvSupplyTmp Extra required inlet air temperature 20 0 99 °C
Manual mode Manual mode Time schedules Time modes
CalendarWeek Weekly time schedule CalendarExcept Exception time schedule CalendarO Switch-o time schedule
Control humidity Humidity control
DehumSpvRel Dehumidication required relative value 60 0 100 %r.H. DehumSpvAbs Dehumidication required absolute value 12 0 100 g/kg HumMaxSpv Maximum humidity required value 80 0 100 %r.H. ActualValueHum Current humidity value ActCascSpvDeh Calculated current dehumidication required value in cascade control HumMaxCtlr Maximum humidity % HumidityCtrl Humidication output DeHumidityCtrl Dehumidication output % Dewpoint Dew point current value °C DewpointDedZone Dew point deviation 1 -64 64 °C
Fans Fans
RegulFans-Flow(Press) RegulFans-Flow(Press)
SupplyPrsRangeSnsr SupplyPrsRangeSnsr ReturnPrsRangeSnsr ReturnPrsRangeSnsr SupplyFlowRangeSnsr SupplyFlowRangeSnsr ReturnFlowRangeSnsr ReturnFlowRangeSnsr SupplyKFactor SupplyKFactor ReturnKFactor ReturnKFactor NmbrOfSplyFans NmbrOfSplyFans NmbrOfRtrnFans NmbrOfRtrnFans Enable - K Factor Enable - K Factor
FanSupplyOutputSetpointVal Inlet fan output
Fan output 1. stage % Output settings St1 Fan output 2. stage % Output settings St2 Fan output 3. stage % Output settings St3 Fan output 4. stage % Output settings St4 Fan output 5. stage % Output settings St5
FanExhaustOutputSetpointVal Outlet fan output
Fan output 1. stage % Output settings St1 Fan output 2. stage % Output settings St2 Fan output 3. stage % Output settings St3 Fan output 4. stage % Output settings St4 Fan output 5. stage % Output settings St5
FanAddOutputSetpointVal Additional fan output
Fan output 1. stage % Output settings St1 Fan output 2. stage % Output settings St2 Fan output 3. stage % Output settings St3 Fan output 4. stage % Output settings St4 Fan output 5. stage % Output settings St5
TRN Correct Outlet fan speed TRN correction
ValueOfCorrection For all stages FanOutputSt1 TRN correction for stage 1 FanOutpuSt2 TRN correction for stage 2 FanOutputSt3 TRN correction for stage 3 FanOutputSt4 TRN correction for stage 4 FanOutputSt5 TRN correction for stage 5
Back-up supply fan Single-speed inlet fan backup
StrtUpDlyFlowMain Failure ow evaluation time-out after main fan start-up 180 0 9999 s StrtUpDlyFlowBackUp Failure ow evaluation time-out after backup fan start-up 180 0 9999 s SupplyFanBackUp Active main fan backup
Back-up exhaust fan Single-speed outlet fan backup
StrtUpDlyFlowMain Failure ow evaluation time-out after main fan start-up 180 0 9999 s StrtUpDlyFlowBackUp Failure ow evaluation time-out after backup fan start-up 180 0 9999 s ExhaustFanBackUp Active main fan backup
Fan run-out to DEVV Fan run-out according to DEV
Enable Enable run-out TeplotaVenkovníMin Blocking by the MIN outdoor temperature -15 -64 64 °C TeplotaVenkovníMax Blocking by the MAX outdoor temperature 5 -64 64 °C
Fan run-out Fan run-out 5 1 60 min Fan run-out Fan run-out 180 0 9999 s MinStOnTimeTrans Time transition to 2St speed – two-speed fans 15 0 999 s
61
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
RundownTmTrans Time transition to 1St speed - two-speed fans 12 0 99 s BlckHighSpeedFan Outdoor temperature-dependent fan speed interlocking -60 -64 64 °C ForceStrtTimOn1St Forced fan start-up to 1St speed (TRN – damper output absent) 20 0 99 °C DelayStartFan Fan start-up delay (after damper) 20 0 9999 s FanRunDwn Fan run-out 180 0 9999 s FlowActDelayStrtErr Failure ow activation delay (at fan start-up) 45 0 600 s FlowActDelayRunErr Failure ow activation delay (during fan run) 5 0 600 s erContActDelayTmErr ermo-contact (TK) failure activation delay (fans) 2 0 600 s FreqInvActSetDelayTmErr Frequency inverter failure activation delay 2 0 600 s
Control Parameters Control parameters
ValueOfTemperatureRegulation Temperature control values
MaxDevRmSplyTemp Maximum dierence between room and inlet temperatures 5 0 64 °C
MinDevRmSplyTemp Min. dierence between room and inlet temperatures 5 0 64 °C
ActCascSpvHeating Calculated required temperature for heating with cascade control °C
ActCascSpvCooling Calculated required temperature for cooling with cascade control °C
ActMainSpvHeating Calculated required temperature for heating °C
ActMainSpvCooling Calculated required temperature for cooling °C
ActualTempControlMode Current temperature-dependent control (inlet, room, outlet) SplyTempLimitation Inlet temperature limitation
SplyMinLimit Minimum inlet air temperature 15 0 64 °C
SplyMaxLimit Maximum inlet air temperature 35 0 64 °C Sequences Sequence
WaterHtgWithFunctionPreHtg Water heating with pre-heating function
PmpStrtOutTmp
Outdoor temperature-dependent pump start-
up in the AHU Stop and Run mode 5 -64 64 °C PmpMinRunTime Minimum pump run time 180 0 9999 s PmpKickTm Pump downtime to the pump turning activation 168 0 9999 h PmpKickTmOn Active pump turning time 60 0 9999 s PreHtgTm Active water pre-heating operation time 120 0 600 s PreHtgTmO Function blocking time between AHU unit shut-down and restart 5 0 30 min PreHtgEquCurX1 Water heater circuit heating curve setting at the AHU start-up X1 -10 -30 5 °C PreHtgEquCurY1 Water heater circuit heating curve setting at the AHU start-up Y1 (%) 100 0 100 % PreHtgEquCurX2 Water heater circuit heating curve setting at the AHU start-up X2 10 0 50 °C PreHtgEquCurY2 Water heater circuit heating curve setting at the AHU start-up Y2 (%) 10 0 100 %
StrtDelaySwtchAntiFreeze Stop to Run mode switching delay AP trigger value 60 0 600 s StrtAntiFreezeInRun Water heat exchanger dependent AP trigger value - AHU in Run mode 15 0 50 °C StrtAntiFreezeInStop Water heat exchanger dependent AP trigger value - AHU in Stop mode 30 0 50 °C DlyEvalSplyAntiFreeze Inlet air dependent AP evaluation enabling delay after the unit start-up 60 0 600 s StrtSplyAntiFreezAlmA Inlet air temperature dependent AP start-up – failure alarm A 6 -64 64 °C StrtSplyAntiFreez Inlet air temperature dependent AP start-up 8 -64 64 °C MaxTempReturnWater Maximum return water temperature 70 20 120 °C
Electric heating Electric Heating
ActiveElectricalHtg Electric heating switching on – request for heating 20 0 100 % HystOElectricalHtg Electric heating hysteresis 10 1 100 %
Gas heating Gas heating
EnableSequenceCool Cooling sequence enabling MinOnTime Minimum burner run time 150 0 600 s MinOTime Minimum burner downtime 150 0 600 s BlckTmAgainStrt1StBurner Burner restart protection time (burner Stage 1) 150 0 600 s RampModulationBurner Modulation burner opening/closing speed (%/s) (burner Stage 1) 5 0 20 %/s MinLoadO2StBurner Heating request value for the burner Stage 2 switch-o (%) 40 10 100 % SetPointAlarmTmpFlueGas Maximum ue-gas alarm temperature 230 210 400 °C MaxTempFlueGas Maximum ue-gas temperature 210 160 230 °C SetPointTempFlueGas Requested ue-gas temperature 160 150 210 °C MinTmpFlueGas Minimum ue-gas temperature 150 150 160 °C
Electrical preheating Electric pre-heating
SetPointPreHtgTmp Required temperature for pre-heating -20 -50 10 °C BlckElPreHtgOutTmp Outdoor dependent electric pre-heating blocking -30 -50 10 °C ActiveElPreHtg Heating request-dependent electric pre-heating switch-on 20 0 100 % HystOPreHtg Hysteresis for electric pre-heater switch-o 10 0 100 %
Water preheating Water pre-heating
PreheatPumpStpt Outdoor dependent pre-heating (pump) start-up 5 -50 15 °C PmpKickTm Pump downtime to the pump turning activation 168 0 9999 h PmpKickTmOn Active pump turning time 30 0 9999 s PmpMinRunTime Minimum pump run time 30 0 9999 s
Extra electrical heating Electric reheating
ActiveExtraElHeating St1 heating request dependent electric re-heating start-up 20 0 100 % HystOExtraElHeating Hysteresis for electric re-heating switch-o 10 1 100 % MaxPowExtraHtgForFanSt1 Fan St1 dependent outlet limitation 100 0 100 % MaxPowExtraHtgForFanSt2 Fan St2 dependent outlet limitation 100 0 100 % MaxPowExtraHtgForFanSt3 Fan St3 dependent outlet limitation 100 0 100 % MaxPowExtraHtgForFanSt4 Fan St4 dependent outlet limitation 100 0 100 % MaxPowExtraHtgForFanSt5 Fan St5 dependent outlet limitation 100 0 100 % Heat Pump, H, Heat Pump 2, Heat Pump 3
HeatPump - heating Heat pump - heating
StptBlckOutTmp Outdoor temperature dependent heat pump blocking 5 -45 35 °C StptHysOutTmp Temp. hysteresis for outdoor temperature dependent heat pump unblocking 3 1 10 °C
62
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
MinRunTm Minimum operating time for heat pump heating 60 0 9999 s BlckTmAgainStrt Re-heating blocking 120 5 600 s ActiveHeatPump Heat pump switching on 20 0 100 % HysOHeatPump Digital output opening hysteresis 10 1 100 % AlarmFromOutTmp Information - outdoor temperature dependent heat pump heating blocking StartAnalogVal Heat pump analogue signal lower level 30 0 50 %
HeatPump - cooling Heat pump - cooling
StptBlckOutTmp Outdoor temperature dependent heat pump blocking 14 -45 35 °C StptHysOutTmp Temp. hysteresis for outdoor temperature dependent heat pump unblocking 3 1 10 °C MinRunTm Minimum operating time for heat pump cooling 60 0 9999 s BlckTmAgainStrt Re-cooling blocking 120 5 600 s ActiveHeatPump Heat pump switching on 20 0 100 % HysOHeatPump Digital output opening hysteresis 10 1 100 % AlarmFromOutTmp Information - outdoor temperature dependent heat pump cooling blocking StartAnalogVal Heat pump analogue signal lower level 30 0 50 %
HeatPump - special HeatPump - special
Invert signal heating Signal inversion - HeatPump heating mode Invert signal cooling Signal inversion - HeatPump cooling mode DaikinSpec0-10V 0-10V special signal switching (Daikin) DierSt1-St2SigDaikin % dierence between request and St2 real signal 40 0 100 % ChangeTimeToMaxSigDaikin Time needed for signal bypass 0–100% 120 0 500 s StartAnalogVal Heat pump analogue signal lower level 30 0 50 %
Heat recovery Heat recovery
HeatExFreezAlarm Freezing determination heat exchanger 1 -64 64 °C HeatExTmpMaxSpeed Start temperature for maximum - HRE speed/volume open BP PE 15 -64 64 °C HeatExTmMaxSpeed Start time for maximum - HRE speed/volume open BP PE 60 0 600 s SetStartRequestHeatEx Heat recovery request dependent HRE run enabling 38 0 100 % SetHysHeatEx Hysteresis for HRE run stop 5 0 100 % InfoStrtAntiFreez Information - antifreeze protection start-up
Mixing Mixing
MinFreshAir Minimum fresh air ow rate 20 0 100 % MinFreshAir - Comfort Minimum fresh air ow rate - Comfort (pool unit) 20 0 100 % MinFreshAir - Econom Minimum fresh air ow rate - Economy (pool unit) 20 0 100 % MixDampTempFullOp Starting temperature for mixing damper wide-open position 15 -64 64 °C MixDampTmFullOp Starting time for mixing damper wide-open position 60 0 600 s ValueOfMixing Mixing damper control signal recurrence vale (normal/inverse) (%) 100 0 100 % ActMaxFrshAirLim Information about the Max. limit of fresh air activation (vent. unit) MaxFrshAir Max. limit of fresh air according to T outdoor (vent. unit) ToutActMaxFrshAir T outdoor from which the Max. limit of fresh air is activated (vent. unit)
Cooling Cooling
ClgBlckOutTmp Outdoor temperature-dependent blocking 12 -64 64 °C MinRumTmPump Minimum pump operating time 180 0 9999 s PmpKickTm Pump downtime to the pump turning activation 168 0 9999 h PmpKickTmOn Active pump turning time 60 0 9999 s MinRunTm1StDXClg Minimum operating time; 1St condensing unit 60 0 9999 s BlckTmAgainStrtDXCool Re-cooling blocking; 1St (2St) condensing unit 120 5 600 s TmRemainIn1StDXCool Minimum dwell time in condensing unit's 1St; 2St condensing unit 360 5 600 s DXCoolStage1On Condensing unit’s 1St switch-on 20 0 100 % DXCoolStage2On Condensing unit’s 2St switch-on 70 0 100 % DXCoolHysO1St Hysteresis for 1St - 2St transition, 2St condensing unit 10 0 20 % MinRunTmInverter Minimum operating time; inverter 10 0 9999 s BlckTmAgainDXCool+Inv Re-cooling blocking, 1St + condensing unit 60 0 300 s Cooling signal inversion Signal Inversion for Heat Cooling Pump OmezDleVlhkProst Cooling limited by room air humidity 65 0 100 %
Cooling 2
NastBlokOdVenkTep Outdoor temperature-dependent blocking of cooling 12 -64 64 °C MinDobaProvČerpadla Minimum pump operating time 180 0 9999 s Inverze signal chlazení Signal Inversion for Heat Cooling Pump
Cooling 3
NastBlokOdVenkTep Outdoor temperature-dependent blocking of cooling 12 -64 64 °C MinDobaProvČerpadla Minimum pump operating time 180 0 9999 s Cooling signal inversion Signal Inversion for Heat Pump Cooling DemandHtg Heating Water Source Switching StptTmpDemandHtg Heating-water heating start-up 15 5 25 °C StptDlyStrtSeq Start-up sequence delay 120 10 600 s
CompensationRequestTemperatur Required temperature compensation
ClgCompStart Cooling initial point (outdoor temperature) 25 -64 64 °C ClgCompEnd Cooling end point (outdoor temperature) 35 -64 64 °C MaxValCompClg Maximum cooling compensation (required value) 2 -64 64 dK ActShiftReqTempClg Required cooling value current shift -64 64 °C CompHStart Heating initial point (outdoor temperature) 0 -64 64 °C CompHEnd Heating end point (outdoor temperature) -20 -64 64 °C MaxCompHtg Maximum heating compensation (required value) -1 -64 64 dK ActShiftReqTempHtg Required heating value current shift -64 64 °C
FanCompensationOutTemperature Outdoor temperature-dependent fan speed compensation
ClgCompStart Cooling initial point (outdoor temperature) 25 -64 64 % ClgCompEnd Cooling end point (outdoor temperature) 30 -64 64 °C MaxValCompStgClg Maximum cooling compensation (speed) 0 -100 100 % ActValComStgFanClg Current cooling speed compensation -100 100 % CompHStart Heating initial point (outdoor temperature) 5 -64 64 °C
63
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
CompHEnd Heating end point (outdoor temperature) -20 -64 64 °C MaxValCompStgHtg Maximum heating compensation (speed) 0 -100 100 % ActValComStgFanHtg Current heating speed compensation -100 100 %
FanCompensationRoomExhaustTmp Room (Outlet) Temperature-Dependent Fan Speed Compensation
FunctionComp Compensation function setting SpvTempInRoom Required room temperature 20 0 99 °C ActValCom Actual compensation 0 100 %
FanCompensationSequenceHtg Heating dependent fan speed compensation
HysTempHeating Heating temperature hysteresis (°C) 1 0 20 °C ActValCom Heating compensation display (%) 0 100 %
FanCompensationSequenceClg Cooling dependent fan speed compensation
HysTempCooling Cooling temperature hysteresis (°C) 1 0 20 °C ActValCom Cooling compensation display (%) 0 100 %
Compensation air quality Air quality dependent compensation (damper position/fan speed)
SetFuncAirQuality Compensation function setting (according to the sensor characteristics) SpvValueConcentration Required (allowable) value of the CO2, VOC, (CO) concentration
800(50)
0 3000 ppm
SettingRangeSensor CO2, VOC, (CO) sensor range setting
2000(300)
0 3000 ppm
ActValComp CO2, VOC (CO) compensation rate display, % 0 100 %
Humidity fan compensation Humidity-dependent fan speed compensation
FanCmpHumSpv Humidity required value for compensation 50 0 100 %r.H. Func compensation Fan speed compensation function ActValComp Compensation display %
Humidity Hrec Damp compensat Humidity-dependent mixing damper compensation
Func compensation Fan speed compensation function ActValComp Compensation display %
TemperatureStart Temperature start-up
StrtTmpHeating Heating trigger temperature 25 -64 64 °C SpvTmpHeating Required temperature for heating 25 -64 64 °C StrtTmpCooling Cooling trigger temperature 30 -64 64 °C SpvTmpCooling Required temperature for cooling 15 -64 64 °C Temperature hysterese Hysteresis 1 0.1 64 °C BlckTmAgainStart Heating and cooling blocking time 30 0 999 min MinRunTm Minimum operating time 0 0 999 min
Night Cooling Night chilling
SpvTmpRoom Required room temperature, inlet-dependent control 22 -64 64 °C HysTmpRoom Temperature hysteresis 3 0 64 °C MinOutTmp Minimum outdoor temperature setting 12 -64 64 °C OutRoomOnDiTmp Outdoor temperature and room temperature dierence 5 1 64 °C MinRunTm Minimum operating time 30 0 999 min
Boost Optimized start
PreStrtTmTimeSchedul Pre-set interval before time program start-up 60 0 999 min SpvTmpRoom Required room temperature - inlet-dependent control 20 -64 64 °C HysTmp Temperature hysteresis 0.5 -64 64 °C SpvTmpHeating Required temperature for heating 25 -64 64 °C SpvTmpCooling Required cooling temperature 15 -64 64 °C
Night kick Night turning
DateTime Turning time TmToNextKick Time to next turning (h) 3 0 9999 h TmOn Active turning time (s) 300 0 9999 s
Control factors Control constants
TempCascade Cascade control factors
PropFactor Proportional factor 10 IntegFactor Integrating factor 1200 s
AntiFreezeRetWatHeat Return water AP factors
PropFactor Proportional factor 20 IntegFactor Integrating factor 90 s DierFactor Derivative factor 0 s
AntiFreezeSplyTemp Inlet air AP factors
PropFactor Proportional factor 50 IntegFactor Integrating factor 0 s DierFactor Derivative factor 0 s
MaxRetWatHeat Maximum return water temperature factors
PropFactor Proportional factor -3 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
SetpointTempWaterHeating Water heating required temperature factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 150 s DierFactor Derivative factor 0 s
Electrical heating Electric heating factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
BurnerFactors Gas burner factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 60 s DierFactor Derivative factor 0 s
Bypass damper Gas heater bypass damper factors
PropFactor Proportional factor -5 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
64
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
GasHeatingMaximalTempFlueGas Maximum temperature of ue gas
PropFactor Proportional factor 10 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
GasHeatingMinimumTempFlueGas Minium temperature of ue gas
PropFactor Proportional factor -10 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
Electrical preheting Electric pre-heating factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
Extra electrical heating Electric after-heating factors
PropFactor Proportional factor 1 IntegFactor Integrating factor 60 s DierFactor Derivative factor 0 s
Heat pump - heating Heat pump factors - heating
PropFactor Proportional factor 5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat pump - cooling Heat pump factors - cooling
PropFactor Proportional factor -5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat pump 2 - heating Heat pump factors 2 - heating
PropFactor Proportional factor 5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat pump 2 - cooling Heat pump factors 2 - cooling
PropFactor Proportional factor -5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat pump 3 - heating Heat pump factors 3 - heating
PropFactor Proportional factor 5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat pump 3 - cooling Heat pump factors 3 - cooling
PropFactor Proportional factor -5 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
Heat recovery Heat recovery RHE/BP PE
PropFactor Proportional factor 3 IntegFactor Integrating factor 60 s DierFactor Derivative factor 1 s
Heat exchanger freeze Heat recovery AP factors
PropFactor Proportional factor 20 IntegFactor Integrating factor 150 s DierFactor Derivative factor 0 s
Mixing Mixing factors
PropFactor Proportional factor 7 IntegFactor Integrating factor 45 s DierFactor Derivative factor 15 s
Cooling Cooling factors
PropFactor Proportional factor -5 IntegFactor Integrating factor 60 s DierFactor Derivative factor 0 s
Humidication Humidication factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
Dehumidity Dehumidication factors
PropFactor Proportional factor -2 IntegFactor Integrating factor 240 s DierFactor Derivative factor 0 s
Humidity cascade Humidity cascade control factors
PropFactor Proportional factor 4 IntegFactor Integrating factor 0 s
FanCompensationSequenceHtg Heating-dependent fan speed compensation factors
PropFactor Proportional factor 5 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
FanCompensationSequenceClg Cooling-dependent fan speed compensation factors
PropFactor Proportional factor -10 IntegFactor Integrating factor 120 s DierFactor Derivative factor 0 s
FanCompensationRoomExhaustTmp Room (outlet) temperature-dependent fan speed compensation factors
PropFactor Proportional factor 20 IntegFactor Integrating factor 0 s DierFactor Derivative factor 0 s
FanCompensationHumidity Humidity-dependent fan speed compensation factors
65
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
Menu HMI-DM,HMI-TM a HMI@WEB
Menu Meaning
Factory settings
Value Min Max
Units
PropFactor Proportional factor -5 IntegFactor Integrating factor 0 s DierFactor Derivative factor 0 s
HrecDampCompHumidity Humidity-dependent mixing damper position compensation factors
PropFactor Proportional factor -2 IntegFactor Integrating factor 45 s DierFactor Derivative factor 0 s
CompensationAirQuality
Air quality CO2(VOC,CO)-dependent compensa-
tion (damper position/fan speed) factors
PropFactor Proportional factor -0.3 IntegFactor Integrating factor 300 s DierFactor Derivative factor 0 s
SplyFanVarCtlr SplyFanVarCtlr
PropFactor PropFactor -0.3 IntegFactor IntegFactor 30 s DierFactor DierFactor 0 s
ExhFanVarCtlr ExhFanVarCtlr
PropFactor PropFactor -0.3 IntegFactor IntegFactor 30 s DierFactor DierFactor 0 s
Device conguration Device conguration
Aplication info Application information Device Info Device information
Unit °C → °F Change units from Metric to imperial Version OS OS version InternTempRegulator Controller internal temperature Operating Hours Operating hours Type of device Device type
Inputs conguration Inputs conguration
HeatPumpAlm Heat Pump Fault Cooling alarm Cooling Fault
Output conguration Output conguration
Signal type heating Control signal 0-10 V or 2-10 V, heating Signal type cooling Control signal 0-10 V or 2-10 V, cooling Signal type mix damper Control signal 0-10 V or 2-10 V, mixing damper SignalTypByPassHeatRec Control signal 0-10 V or 2-10 V, heat exchanger by-pass damper
SignalTypeByPassBurn Control signal 0-10 V or 2-10 V, chamber by-pass damper RegulationSupplyFan Type of regulation supply fan RegulationExhaustFan Type of regulation exhaust fan RegulationAddtionalFan Type of regulation additional fan Heating Heating Heat pump Heat pump Gas heat type Type of gas heating GasHeaterBypassDamp Byppas damper gas heater Cooling Cooling Heat recovery Heat recovery Mixing Mixing Preheating Preheating Extra heating Extra heating TemperatControlMode Temperature control mode HumidityControlMode Humidity control mode RemoteFault-ClassFault Remote fault - choice class fault Version SW-HMI SW-HMI version
AditionalOperModeAndFunction Additional operating modes, functions
TemperatureMeasurePointSelect Room temperature measuring point selection FanCompensationOutTemperature Outdoor Temperature-Dependent Fan Speed Compensation Fan compensation sequence Heating/cooling dependent fan speed compensation Fan compensation air quality Air quality-dependent fan speed compensation FanCompensationRoomExhaustTmp Room (outlet) temperature-dependent fan speed compensation Temperature deviation alarm Dierence between required and actual temperature monitoring AntiFreezeDEV DEV Water Heater Antifreeze Protection Variant HeatRecoveryCompensationAirQ Air quality-dependent damper position compensation Heat recovery cooling Cooling using ZZT (ROV, BP, DEV, mixing damper)
Fan cooling sequence
Heating/cooling dependent fan speed compen-
sation-cooling sequence (fan, cooler) HeatRecovery­DamperSequence Mixing heating sequence (damper, heater) Night coolling Night chilling Temperature start-up Temperature start-up Boost Time mode start optimization BlockedDamper­AndExhaustFan Damper and outlet fan blocking Type corrrect TRN exhaust fan Outlet fan correction type (TRN controllers) LimitationDeHu­midiForHeating Limitation of dehumidication during heating Humidity fan compensation Humidity-dependent fan speed compensation Humidity HrecDampCompensation Humidity-dependent mixing damper position compensation
66
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
ActiveMaxFrshAirDHrec
Function activation - Max. limit of fresh air ac-
cording to T outdoor (vent. unit) Apply + Reset Reset after conguration of additional modes/functions
HMI-SG HMI-SG
DisplayedRoomTemp Room temperature display, combined or inlet temperature SetpoitRangeCorr Required value compensation setting +/- 3 0 12 °C SetpointIncrement Required temperature increment setting (0.5/0.1) (°C) 0.1 0.1 0.5 °C TimeFormat Displayed time format (12h/24h) 24 12 24 h
External Control External control
ToggFuncInp1 External contact function denition (Ext. control 1 contact) DelayOfTmToAUTO Transition time from ext. control mode to AUTO mode (Ext. control 1 contact) 0 0 23 h FanOutputStg1 Fan output stage setting (Ext. control 1 contact or 2 contacts) FanOutputStg2 Fan output stage setting "Higher" (Ext. control 2 contacts) TmpMod1 Temperature mode setting (Ext. control 1 contact or 2 contacts) TmpMod2 Temperature mode setting "Higher" (Ext. control 2 contacts) FanStageExtCnt Fan output stages (external control)
Identication device Device identication
Name of device Equipment name Number of devices Device number Location of the installation Device location
Checks Checks
Save / Restore Saving and recovery
UpgradeStart Application loading from SD card SaveDataOnSDCard Data saving to SD card SaveDataFromSDCard Data loading from SD card RestoreFactorySetting Factory settings recovery Restore settings Settings recovery Save settings Save settings
Operating hours Operating hours
Supply fan Operating hour counter - inlet fan Exhaust fan Operating hour counter - outlet fan Additional fan Operating hour counter – 3rd auxiliary fan Operating hours settings fans Fan operating hours settings
OperationHoursAlm Fan operating hour alarm state EnblOperHoursAlm Alarm enable fan operating hour OperHoursLimit Operating hours for alarm activation 17520 0
999999
h Water preheating Operating hour counter – water pre-heating ElectricPreheating Operating hour counter - electric pre-heating Heating water Operating hour counter - water heating Electrical heating Operating hour counter - electric heating Cooling water Operating hour counter - water cooling CoolingCondenUnit Operating hour counter – condensing unit ChlazKondJednotka 2 Operating hour counter – condensing unit 2 ChlazKondJednotka 3 Operating hour counter – condensing unit 3 ExtraElectricalHtg Operating hour counter - electric after-heating TepČerpadlo-ohřev Operating hour counter – Heating Pump - heating TepČerpadlo-chlaz Operating hour counter – Heating Pump - cooling TepČerpadlo2-ohřev Operating hour counter – Heating Pump 2 - heating TepČerpadlo2-chlaz Operating hour counter – Heating Pump 2 - cooling TepČerpadlo3-ohřev Operating hour counter – Heating Pump 3 - heating TepČerpadlo3-chlaz Operating hour counter – Heating Pump 3 - cooling
SetpointAndSupplyTmpDeviation Dierence between required and inlet air temperature monitoring.
MaxDeviation Maximum dierence (±°C) 10 0 99 °C MinLimit Minimum limit (°C) 10 0 99 °C DlyOnTmEvalAfterStart Time delay evaluation after AHU start-up (s) 60 0 9999 s
SetpointAndRoomTmpDeviation Dierence between required and room (outlet) air temperature monitoring.
MaxDeviation Maximum dierence (±°C) 10 0 99 °C MinLimit Minimum limit (°C) 10 0 99 °C DlyOnTmEvalAfterStart Time delay evaluation after AHU start-up (s) 600 0 9999 s
FireAlarmActivityFans Fan behaviour during re alarm FireAlarmFansOutSpv Fan output during re alarm 80 0 100 % SplyTmpFireLmt Fire alarm activation inlet temperature 70 0 99 °C ExhstTmpFireLmt Fire alarm activation outlet temperature 50 0 99 °C
Connection Connection
Modbus Master ModbusMaster
AdrFreqInv1SplyFan Frequency inverter 1 address, inlet fan 1 AdrFreqInv2SplyFan Frequency inverter 2 address, inlet fan backup or second inlet fan 2 AdrFreqInv3SplyFan Frequency inverter 3 address, inlet fan twin backup 3 AdrFreqInv4SplyFan Frequency inverter 4 address, inlet fan twin backup 4 AdrFreqInv5ExhFan Frequency inverter 5 address, outlet fan 5 AdrFreqinv6ExhFan Frequency inverter 6 address, outlet fan backup or second outlet fan 6 AdrFreqInv7ExhFan Frequency inverter 7 address, outlet fan twin backup 7 AdrFreqInv8ExhFan Frequency inverter 8 address, outlet fan twin backup 8 AdrFreqInv9AddFirst Frequency inverter 9 address, 3rd auxiliary fan 9 AdrFreqInv10AddSec Frequency inverter 10 address, second 3rd auxiliary fan 10 AdrFreqInv11RotHeatExch Frequency inverter 11 address, rotary heat exchanger 11 ResistiveTerminatBus Control unit Modbus resistance terminal NumberRepeatErrMess Number of message repeating during error transfers 2 NumberOfErrMess Number of error transfers for communication failure evaluation 6
LAN Connection LAN connection
DHCP DHCP ActIPAdr Current IP address ActMaskAdr Current mask address
67
List of Data Points (HMI-DM, HMI-TM and HMI@WEB controllers)
ActGatewayAdr Current gate address GivenIPAdr IP address input GivenMaskAdr Mask address input GivenGateAdr Gate address input HostName Host name MACAdrress MAC address Web user name HMI@WEB user name: Web user name HMI@WEB password Apply+Reset Apply+Reset
LON LON
OutTmpCommunicat Outdoor temperature from the bus ExtAlarmCommunicat External failure form the bus
Modbus - CommModul Modbus communication module LON - CommModul LON communication module
OutTmpCommunicat Outdoor temperature from the bus ExtAlarmCommunicat External failure form the bus
BACnet/IP BACnet/IP communication module Language Language
Current Language Current language
Passwords Passwords
Login Log-in Log Out Log-out Change password Password change
Password:SERVICE Password: SERVICE Level:SERVICE Level: SERVICE Password:ADMIN Password: ADMINISTRATOR Level:ADMIN Level: ADMINISTRATOR Password:USER Password: USER Level:USER Level: USER Password:GUEST Password: GUEST Level:GUEST Level: GUEST
Function button – Fault
1x Alarm list detail Last failure digital description 2x Alarm list: List of failures
Acknowledge Failure reset
3x Alarm history: Error history
Acknowledge Failure reset
4x Alarms Failures
Alarm list: List of failures Reset Reset Alarm history: Error history Reset Reset
68
List of failures (HMI-DM, HMI-TM and HMI@WEB controllers)
Failure name Failure Description
SupplyTmpSnsr Inlet air temperature sensor RoomTmpSnsr Room air temperature sensor HMI-SG1 Local HMI-SG1 controller HMI-SG2 Local HMI-SG2 controller ReturnAirTmpSnsr Outlet air temperature sensor OutTmpSnsr Outdoor temperature sensor HtgFrstTmpSnsr Return water temperature sensor FrostTmpSnsrHeatEx Antifreeze protection temperature sensor PreElHtgTmpSnsr Temperature sensor aer the el. pre-heater PreWtrHtgTmpSnsr Pre-heating antifreeze protection temperature sensor ExtraSupplyTmp Temperature sensor aer the el. aer-heater BrnrFlueTmpSnsr Flue gas temperature sensor AirQualitySnsr Air quality sensor SupplyHumSnsr Inlet air humidity sensor RoomHumSnsr Room air humidity sensor OutHumSnsr Outdoor air humidity sensor Supply fan Inlet – 1st fan SplyFanInfBckUp Inlet fan backup information SplyFanBckUpOrTwn Backup or twin – 2nd inlet fan TwnSplyFanActBckUp Twin inlet fan backup information SplyFanBckUpFrsTwn 1st inlet fan twin backup SplyFanBckUpSecTwn 2nd inlet fan twin backup Exhaust fan Outlet fan – 1st fan ExhFanActBckUp Outlet fan backup information ExhFanBckUpOrTwn Backup or twin - 2nd outlet fan ExhFanBckUpFrsTwn Twin backup – 1st outlet fan TwnExhFanActBckUp Twin outlet fan backup information ExhFanBckUpSecTwn Twin backup – 2nd outlet fan Fan additional Auxiliary 3rd fan FanTwinAdditional Auxiliary 3rd twin fan Supply fan - flow Supply fan air-flow fault Exhaust fan - flow Exhaust fan air-flow fault AdditionalFan-Flow Additional fan air-flow fault WaterHeatingPump Water heat pump fault Heat pump Heat pump fault BlockHeatPumpFromOutTmpHeating Blocking the heat pump from outer temperature - heating BlockHeatPumpFromOutTmpCooling Blocking the heat pump from outer temperature - cooling Fan Fa n Filter Filter fouling Electric heating Electric heater Fire Fire OverHeatFlueGas Flue gas temperature exceeded HighFlueGasTemp High flue gas temperature
69
Failure name Failure Description
List of failures (HMI-DM...)
BackdraProtec Gas heater thermostat
switching ON Burner Gas heater ElectricPreheating Electric pre-heating ExtraElectricalHtg Electric aer-heating CondensingUnit Condensing unit FreqInvRotHeatEx ROV failure AntiFreezeHeatEx Heat exchanger
antifreeze protection SplyFanMainTK Main inlet fan - ermocontact SplyFanBckUpTK Backup inlet fan -
ermocontact SplyFanMainDifPr Main inlet fan - pressure
deference sensor SplyFanBckUpDifPr Backup inlet fan - pressure
deference sensor SupplyFanBack-up Active inlet fan twin backup ExhFanMainTK Main outlet fan - ermocontact ExhFanBckUpTK Backup outlet fan -
ermocontact ExhFanMainDifPr Main outlet fan - pressure
deference sensor ExhFanBckUpDifPr Backup outlet fan - pressure
deference sensor ExhaustFanBack-up Active outlet fan twin backup CommunicatioModbus Modbus communication FanOperHours Fan operating hours StptSplyTmpDev Difference between
required and inlet air
temperature monitoring. StptRoomTmpDev Difference between required
and room (outlet) air
temperature monitoring.
HeatPumpDefrost Heat pump defrosting function
Inlet Pressure Unconnected or damaged
pressure sensor - inlet fan
Outlet Pressure Unconnected or damaged
pressure sensor - outlet fan
Inlet Air Flow Unconnected or damaged flow
sensor - inlet fan
Outlet Air Flow Unconnected or damaged flow
sensor - outlet fan
Humidifier Humidifier fault
Reduced humidification output
Reduced humidification output due to the temperature priority (swimming-pool unit) – an information message
Operating mode 1st contact 2nd contact
Auto Off Off
Lower stage On Off
Higher stage Off On
Stop On On
Setting of the Run operating state (temperature mode and fan output stage) and timer (only for one specific device) is performed using the HMI-SG controller in the List of Data Points in the section Settings – External Devices.
Other Ways of Control
External control
is enables the control unit to be connected to other technology using single- or two-contact control. e Auto operating state of the air-handling unit is always the default state for external control.
Single-Contact Control
is type of control can be performed in two ways (Start (default) or Start and Stop functions) depending on the data point setting. Start function: By activating the switch (switching 1/0), the air-handling unit is put into the Run operating state (fan output stage and temperature mode). e control unit time in the Run state is always given by the timer settings. Another activation of the switch will prolong the control unit time in the Run state for a pre-set time in the timer. Once the pre-set time has elapsed, the unit will go into the Auto operating state. If the timer is set to zero, the contact input is ready for the switch action (on-off, switching 1) – if the switch is in the "On" position, the air-handling unit is in the Run operating state; aer switching to the "Off" position, the air-handling unit will go into the Auto state. Start and Stop function: By activating the switch "Start function" (switching 1/0), the air-handling unit is put into the Run operating state (fan output stage and temperature mode) for the timing period. Upon activation of the switch "Stop function" in the active timing interval, the pre-set operating mode will be stopped and the unit will go into the Auto state. e air-handling unit will also go into the Auto state once the timing interval has elapsed. If the timer is set to zero, the contact input is ready for the switch action (on-off, switching 1) – if the switch is in the "On" position, the air-handling unit is in the Run operating state; aer switching to the "Off" position, the air-handling unit will go into the Auto state.
Two-Contact Control
is enables the selection of two Run mode operating states (Higher and Lower). Each Run operating state is set in a different temperature mode and fan speed stage. By combining the Stop or Auto operating modes, it is possible to set the required state of the Run mode. e contact states can be combined as follows:
Remote Signalling
e VCS Control unit can optionally be equipped with one or two outputs for remote signalling. Depending on the configuration, the following:
n Only failure (non-potential contact, max. load 230 V/1 A) n Failure and operation (2 non-potential contacts, max. load
230 V/1 A).
70
Connection to the Master System (LonWorks Standard)
LonWorks Network
e VCS control unit enables integration of the centralized BMS (Building Management System) using the LonWorks communication bus. Using the suitably integrated system, it is possible to control the air-handling device operating state. For a specic description of the variables to be used for the integration, refer to the section "Description of Pre-dened Variables in the LONWorks Network". e nal functionality, monitoring and control options will be dependant on the integrator used to ensure connection to the master BMS system.
Network Interface
Connection to the network is ensured by a galvanically sepa­rated FTT-10A transceiver. is Free Topology Transceiver has been designed for the LonWorks network with a TP/FT-10 type transmission channel. is transmission channel uses a free topology network, a twisted pair and baud rate of 78 kbps. Applicable network topologies to be used along with the FTT-10A transceiver:
• Freetopology (including the star and circular topology) – Free topology
• Bustopology
– Line (Bus) topology
Each device in the LonWorks network is identied by a unique neuron ID identier. e unique neuron ID identier assigned by the manufacturer can always be found on the Climatix controller which is a part of the VCS control unit.
For more information on the LonWorks Standard refer to: www.echelon.com www.lonmark.org
Data Point Settings for Application of Some Network Input Variables
Using the controllers along with the VCS control system, it is possible to make changes in the assignment of the functions to some network input variables (SNVT). For some input variables like outdoor temperature and re alarm (exter­nal failure), it is necessary to select if the value is to be used from the communication or from the application in the Controller Menu. us it can be determined if the outdoor temperature sensor is connected directly to the VCS control unit or its temperature reading is sent through the communication (LonWorks).
Description of Pre-dened Variables in the LonWorks Network
is section includes description of SNVT variables (Standard Network Variable Types) according to assigned REMAK data points. e list below includes specications of variables for all the VCS control system vari­ants. For example, if the VCS control system (air-handling device) was not equipped with gas heating it is not possible to use these variables.
Input Variables
Network Variable: nviTemps Description: Req. heating temperature (Comfort)
Req. cooling temperature (Comfort) Req. heating temperature (Economy) Req. cooling temperature (Economy) Minimum supply air temperature Maximum supply air temperature Object: SNVT_temp_Setpt Remark: Structured Variable
Network Variable: nviTemp01 Description: Not used Object: SNVT_temp_p
Network Variable: nviTemp02 Description: Outdoor temperature Object: SNVT_temp_p
Network Variable: nviAHum00 Description: Humidication Reference Value Object: SNVT_abs_humid Remark: For absolute and relative
Network Variable: nviAHum01 Description: Dehumidication Reference Value Object: SNVT_abs_humid Remark: For absolute and relative
Network Variable: nviPpm00 Description: Air quality Reference Value Object: SNVT_count
Network Variable: nviPress_Flow00 Description: Not used Object: SNVT_count
Network Variable: nviPress_Flow01 Description: Not used Object: SNVT_count Network Variable: nviPress_Flow02 Description: Not used Object: SNVT_count
Network Variable: nviPress_Flow03 Description: Not used Object: SNVT_count Network Variable: nviPress_Flow04 Description: Not used Object: SNVT_count
Network Variable: nviPress_Flow05 Description: Not used Object: SNVT_count
Network Variable: nviResetAlarm Description: Failure reset Object: SNVT_switch Values: 0 Normal 1 Reset >1 Not dened State: 0: Inactive
71
Connection to the Master System (LonWorks Standard)
1: Active Default: Value: 0 State: 0 Remark: e State must be set to "1" to be used for the Value
Network Variable: nviOpMode Description: Stav zařízení požadovaný z BMS Object: SNVT_switch Values: 0 Auto (interní časový program) 1 Stop 2 Economy, 1St 3 Comfort, 1St 4 Economy, 2St 5 Comfort, 2St 6 Economy, 3St 7 Comfort, 3St 8 Economy, 4St 9 Comfort, 4St 10 Economy, 5St 11 Comfort, 5St >11 Not dened State: 0: Inactive 1: Active Remark: e State must be set to "1" to be used for the Value
Network Variable: nviControl Description: External control Object: SNVT_state (16 bit) Bits: Bit [0 ...15] Binary: *Reverse: 0 15 External control 1 1 14 External control 2 2 13 3 12 4 11 5 10 6 9 Fire alarm 7 8 "0"=Fau lt, "1" No fault 8 7 9 6 Bit [0 ...15] Binary: *Reverse: 10 5 11 4 12 3 13 2 14 1 15 0
Remark: *The bit name order can be reversed in some LON software tools.
Output Variables
Network Variable: nvoTemps Description: Req. heating temperature (Comfort)
Req. cooling temperature (Comfort) Not used Req. heating temperature (cascade, inlet) Req. cooling temperature (cascade, inlet) Not used Object: SNVT_temp_Setpt Remark: Structured Variable
Network Variable: nvoTemp01 Description: Inlet temperature Object: SNVT_temp_p
Network Variable: nvoTemp02 Description: Return water temperature Object: SNVT_temp_p
Network Variable: nvoTemp03 Description: Outdoor temperature Object: SNVT_temp_p
Network Variable: nvoTemp04 Description: Room temperature (for control) Object: SNVT_temp_p
Network Variable: nvoTemp05 Description: Outlet temperature Object: SNVT_temp_p
Network Variable: nvoTemp06 Description: Temperature behind the heat exchanger Object: SNVT_temp_p
Network Variable: nvoTemp07 Description: Flue gas temperature Object: SNVT_temp_p
Network Variable: nvoTemp08 Description: Temperature behind electric pre-heating or Return water temperature form the water heater Object: SNVT_temp_p
Network Variable: nvoPpm00 Description: Air quality Object: SNVT_count
Network Variable: nvoPress00 Description: Inlet pressure Object: SNVT_press_p
Network Variable: nvoPress01 Description: Outlet pressure Object: SNVT_press_p
72
Connection to the Master System (LonWorks Standard)
Network Variable: nvoPress02 Description: Not used Object: SNVT_press_p
Network Variable: nvoPress_Flow00 Description: Current request for the inlet fan Object: SNVT_ow Remark: %, Pa or l/s
Network Variable: nvoPress_Flow01 Description: Current request for the outlet fan Object: SNVT_ow Remark: %, Pa or l/s
Network Variable: nvo_Flow00 Description: Inlet air-ow Object: SNVT_ow
Network Variable: nvo_Flow01 Description: Outlet air-ow Object: SNVT_ow
Network Variable: nvoPerc00 Description: Heater output Object: SNVT_lev_count
Network Variable: nvoPerc01 Description: Cooling output Object: SNVT_lev_count
Network Variable: nvoPerc02 Description: Heat exchanger output Object: SNVT_lev_count
Network Variable: nvoPerc03 Description: Mixing output Object: SNVT_lev_count
Network Variable: nvoPerc04 Description: Not used Object: SNVT_lev_count
Network Variable: nvoPerc05 Description: Electric heater output Object: SNVT_lev_count
Network Variable: nvoPerc06 Description: Inlet fan output Object: SNVT_lev_count
Network Variable: nvoPerc07 Description: Outlet fan output Object: SNVT_lev_count
Network Variable: nvoPerc08 Description: Not used Object: SNVT_lev_count
Network Variable: nvoPerc09 Description: Air humidity in the inlet Object: SNVT_lev_count
Network Variable: nvoPerc10 Description: Air humidity in the room Object: SNVT_lev_count
Network Variable: nvoPerc11 Description: Outdoor air humidity Object: SNVT_lev_count
Network Variable: nvoPerc12 Description: Humidication output Object: SNVT_lev_count
Network Variable: nvoPerc13 Description: Dehumidication output Object: SNVT_lev_count
Network Variable: nvoPerc14 Description: Electric after-heater output Object: SNVT_lev_count
Network Variable: nvoAHum00 Description: Absolute humidity in the inlet Object: SNVT_abs_humid
Network Variable: nvoAHum01 Description: Absolute humidity in the outlet Object: SNVT_abs_humid
Network Variable: nvoOpMode Description: Current device state Object: SNVT_switch Values: 0 Stop 1 Operation (Comfort) 2 Operation (Economy) 3 Not used 4 Optimized start 5 Night chilling 6 Temperature start-up 7 Night turn-over 8 Not used 9 Fire 10 Safety stop 11 Fan run-down 12 Start >12 Not dened State: 0: Inactive :Mode Auto 1: Active :Mode OS Default: Value: 0 State: 0
Network Variable: nvoSwitch00 Description: Current fan state Object: SNVT_switch Values: 0 Stop 1 1St 2 2St
73
Connection to the Master System (LonWorks Standard)
3 3St 4 4St 5 5St >5 Not dened State: 0: Inactive 1: Active
Network Variable: nvoState Description: Alarm classes, Control mode Object: SNVT_state_64 (64 bit) Bits: Bit [0 …63] Binary: *Reverse: Alarm class - danger (A) 0 63 Alarm class - critical (A) 1 62 Alarm class - low (B) 2 61 Alarm class - warning (B) 3 60 4 59 5 58 6 57 7 56 8 55 9 54 10 53 Current control temperature - room 11 52 Current control temperature - outlet 12 51 Current control temperature - inlet 13 50 Current control humidity - room 14 49 Current control humidity - inlet 15 48 . . . . . . 63 0
Remark: *The bit name order can be reversed in some LON software tools
Network Variable: nvoDO Description: Digital outputs Object: SNVT_state_64 (64 bit) Bits: Bit [0 …63] Binary: *Reverse: Inlet damper 0 63 Outlet damper 1 62 Fire damper 2 61 3 60 Inlet Fan - Run 4 59 Inlet Fan - Stop 5 58 6 57 7 56 8 55 Outlet Fan - Run 9 54 Outlet Fan - Stop 10 53 11 52 12 51 13 50 14 49 15 48 Cooling - pump 16 47 Cooling DX, Stop 17 46 Cooling DX, 1st 18 45
Cooling DX, 2st 19 44 20 43 21 42 Heat recovery 22 41 23 40 Water heating - pump 24 39 25 38 Electric heating, Stop 26 37 Electric heating, 1st 27 36 28 35 29 34 30 33 31 32 Heat pump DO 2 32 31 33 30 34 29 35 28 36 27 37 26 Heat pump DO 1 38 25 39 24 Electric after-heating, Stop 40 23 Electric after-heating, 1st 41 22 42 21 43 20 44 19 Request for humidication 45 18 Humidier pump 46 17 47 16 48 15 49 14 Gas heating, st1 50 13 Gas heating, st2 51 12 Gas heating, Mod+ 52 11 Gas heating, Mod- 53 10 54 9 55 8 Alarm output (A failures) 56 7 Alarm output (B failures) 57 6 58 5 59 4 60 3 Request for boiler room 61 2 Water pre-heating 62 1 Electric pre-heating 63 0 Remark: *The bit name order can be reversed in some LON software tools.
Network Variable: nvoDI Description: Digital Inputs Object: SNVT_state_64 (64 bit) Bits: Bit [0 …63] Binary: *Reverse: 0 63 External input 1 1 62 External input 2 2 61 . . . . . . . .
74
Connection to the Master System (LonWorks Standard)
Pressure dierences (air-ow), outlet 49 14 50 13 Outdoor air humidity 51 12 Air humidity dierence, inlet 52 11 Air humidity dierence, room 53 10 Dew point 54 9 55 8 Air quality 56 7 57 6 58 5 59 4 60 3 61 2 62 1 63 0
Remark: *The bit name order can be reversed in some LON software tools
63 0 Remark: *The bit name order can be reversed in some LON software tools
Network Variable: nvoDO Description: Alarms Object: SNVT_state_64 (64 bit) Bits: Bit [0 …63] Binary: *Reverse: Dampers 0 63 Fire dampers 1 62 Burner failure 2 61 Inlet fan 3 60 Outlet fan 4 59 Fans – operating hours 5 58 Back-up inlet fan 6 57 Back-up outlet fan 7 56 Cooling 8 55 Flue-gas high temperature
- AHU shut down 9 54 Heat recovery 10 53 11 52 Heat recovery (antifreeze protection) 12 51 13 50 Mixing 14 49 Flue-gas high temperature
- heater shut down 15 48 Heating, pump 16 47 Water heating 17 46 Electric heating 18 45 Back draught protection (TH) 19 44 Heat pump Cooling 20 43 21 42 Heat pump, heating 22 41 23 40 Electric after-heating 24 39 25 38 Humidier, pump 26 37 Humidication 27 36 28 35 Fire 29 34 Electric pre-heating 30 33 Filters 31 32 Outdoor temeprature 32 31 Inlet temperature 33 30 Return water temperature 34 29 Room temperature 1 35 28 Room temperature 2 36 27 Outlet temperature 37 26 38 25 39 24 40 23 41 22 42 21 43 20 44 19 Temperature, HMI SG 1,2 45 18 Inlet temperature dierence 46 17 Room temperature dierence 47 16 Pressure dierences (air-ow), inlet 48 15
75
Connection to the Master System (ModBus Standard)
Modbus RTU Slave (BMS)
e VCS control unit enables integration of the centralized BMS (Building Management System) using the Modbus communication bus. Using a suitably integrated system, it is possible to control the air-handling device operating state. Specifications of the variables (data points) used for integra­tion are described in the section Description of Pre-defined Variables in the Modbus Network. e final functionality, monitoring and control options will be dependent on the inte­grator used to ensure connection to the master BMS system.
Generally
Modbus is a worldwide recognized standard defined by Modbus Organization, Inc. e Modbus Organization is a group of independent suppliers of automation devices. e Modbus Organization administers and develops communication systems for distributed auto­mation systems. It also provides information to obtain and share information about the protocols, their application and certification to simplify implementation by users with the aim to reduce expenses for communication. For detailed information on the Modbus RTU protocol, refer to www.modbus.org.
Trademarks and Copyright
e trademarks used in this document are listed on the back page, including their owners. ese trademarks are quoted from Siemens materials.
Modbus RTU Protocol
e Modbus communication protocol works using the Master/ Slave principle. e Slave function is used for the VCS control unit communication with the master system. us, the VCS control unit behaves like a Slave during communication and expects requests from the Master (master system). ere are two variants of the Modbus protocol serial transfer mode. e VCS control unit uses the RTU (Remote Terminal Unit) mode. erefore, a unique Modbus RTU identification is very important. e RS 485 standard is used to transfer the data through a half-duplex twin-lead. e transfer lead (cable) must be selected depending on this standard and other conditions. For more information, refer to www.modbus.org Correct wiring must be carried out to ensure proper operation – 115/230 V AC must be strictly isolated from 24 V SELV AC. ere are three terminals, "+", "-" and reference voltage ter­minal "REF", available in the control unit to connect the VCS control unit to the bus. To ensure correct functioning of the bus, the first and last device on the bus must be fitted with a terminal resistor. erefore, it is possible to perform soware settings of the terminal resistor in the VCS control unit for the Modbus Slave (see the Data Points in the VCS Installation and Operating Instructions). It is also necessary to set other communication parameters in the VCS control unit data points (section – Communication with Modbus RTU Master System).
Default values of the data points for the Slave Modbus RTU:
• Slave address – 1
• Baud rate – 9600 Bd 
• Parity - None 
• Number of stop bits – 2
• Response time limit – 5 s
For more information, refer to the List of Data Points Note: Once these data points have been set, the device must be re­started. Aer the restart, the device is ready to communicate in accordance with the set parameters.
Modbus Registers
e Modbus registers are divided according to their properties. For a general description and explanation of the registers, refer to the table below:
Data types used to transfer the values:
16-bit for real values (Unsigned Word) 16-bit for status values (Signed Word) 1-bit for status values like 0=Off (switched off) and 1=On (switched on) 1-bit for alarm values like 0=Alarm and 1=Normal (OK)
Divisor (Multiplier):
e so-called Divisor (Multiplier) is used for values which need the decimal numbers to be transferred. For example, for tem­peratures the value Divisor (Multiplier) of 10 is used to enable a one decimal place value to be transferred. For example, a temperature of 23.2°C is transferred by the Modbus as 232. e number must be divided by 10 to get the correct value. For information indicating this fact, refer to the note for a particular data point.
ModbusType Reference Description
Coil Status 0xxxx
Read/Write Discrete Out­puts or Coils.
Input Status 1xxxx Read Discrete Inputs.
Input Register 3xxxx Read Input Registers.
Holding Reg­ister
4xxxx
Read/Write Output or Holding Registers.
Table 8 – Modbus registers
76
Connection to the Master System (ModBus Standard)
Description of Pre-defined Variables in the Modbus Network
is section includes a description of variables (registers) according to the assigned REMAK data points. e list below includes specifications of variables for different VCS control system variants at the discretion of REMAK a.s. For example, if the VCS control system (air-handling device) has not been equipped with gas heating, it will not be possible to use these variables.
Coil status (Read/Write)
Input states (Read)
Adress Description Values/Units Remarks
0x0001 Alarm acknowledge 0-1 Off*On
0x0002
0x0003
0x0004
0x0007
0x0011
0x0012 Ext control input 1 0-1 Off*On
0x0013 Ext control input 2 0-1 Off*On
0x0014
0x0015 Fire alarm 0-1 OK*Alarm
Adress Description Values/Units Remarks
1x0001 Alarm class danger (A) 0-1 Off*On
1x0002 Alarm class critical (A) 0-1 Normal*Alarm
1x0003 Alarm class low (B) 0-1 Normal*Alarm
1x0004 Alarm class warning (B) 0-1 Normal*Alarm
1x0005
1x0011
1x0012 Ext control input 1 0-1 Off*On
1x0013 Ext control input 2 0-1 Off*On
1x0014
1x0015
1x0020
1x0021
1x0022
1x0023
1x0024
1x0026 Fan alarm 0-1 OK*Alarm
77
1x0027 Supply fan alarm 0-1 OK*Alarm
1x0028 Supply fan fdbk 0-1 OK*Alarm
1x0029 Sply fan deviation 0-1 Passive*Active
1x0030 Exhaust fan alarm 0-1 OK*Alarm
1x0031 Exhaust fan fdbk 0-1 OK*Alarm
1x0032 Exhaust fan deviation 0-1 Passive*Active
1x0033 Fan op hours alarm 0-1 Passive*Active
1x0036 Cooling DX alarm 0-1 OK*Alarm
1x0037
1x0038 Cooling pump alarm 0-1 OK*Alarm
1x0039 Ice build-up on the heat pump evaporator 0-1 OK*Alarm
1x0040 Heat recovery alarm 0-1 OK*Alarm
1x0041
1x0042
1x0043 Hrec frost monitor 0-1 OK*Alarm
1x0044
1x0045 Htg pump alarm 0-1 OK*Alarm
1x0046
1x0047 Htg frost monitor 0-1 OK*Frost
1x0048 El htg alarm 0-1 OK*Alarm
1x0049 Heat pump blocking by outdoor temperature 0-1 Passive*Active
1x0050 Heat pump blocking by pressure in the plate
heat-exchanger
0-1 Passive*Active
1x0051 Heat pump operation blocking 0-1 OK*Alarm
1x0052
1x0053
1x0054
1x0055
1x0056 El heating 2 alarm 0-1 OK*Alarm
1x0057 Sply tmp deviation 0-1 Passive*Active
1x0058 Room tmp deviation 0-1 Passive*Active
1x0059
1x0062
1x0063
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
Input states (Read) (continuation)
78
1x0064
1x0065
1x0066
1x0067
1x0070 Filter alarm 0-1 OK*Alarm
1x0071 Supply filter alarm 0-1 OK*Alarm
1x0072 Exh filter alarm 0-1 OK*Alarm
1x0073 Fire alarm 0-1 OK*Alarm
1x0074 Supply tmp fire alm 0-1 OK*Alarm
1x0075 Exh tmp fire alarm 0-1 OK*Alarm
1x0076 Inlet temperature (antifreeze protection) 0-1 OK*Alarm
1x0077
1x0078 Modbus comm alarm 0-1 OK*Alarm
1x0080 Outside air temp °C OK*Alarm
1x0081 Supply air temp °C OK*Alarm
1x0082 Heating frost tmp °C OK*Alarm
1x0083 Room temperature °C OK*Alarm
1x0084 Room temperature 2 °C OK*Alarm
1x0085 Return air temp °C OK*Alarm
1x0086 Exhaust air temp °C OK*Alarm
1x0087
1x0088
1x0089
1x0090
1x0091
1x0092 Outdoor air humidity relative) %r.H. OK*Alarm
1x0093 Inlet air humidity (relative) %r.H. OK*Alarm
1x0094 Room air humidity (relative) %r.H. OK*Alarm
1x0095 Inlet air flow rate m3/h OK*Alarm
1x0096 Outlet air flow rate m3/h OK*Alarm
1x0097 Inlet air pressure Pa OK*Alarm
1x0098 Outlet air pressure Pa OK*Alarm
1x0099
1x0100 Air quality ppm OK*Alarm
Adress Description Values/Units Remarks
Input states (Read) (continuation)
79
Connection to the Master System (ModBus Standard)
1x0101
1x0102 RmUTmp1 °C OK*Alarm
1x0103 RmUTmp2 °C OK*Alarm
1x0104 BrnrFlueTmp °C OK*Alarm
1x0105 PreElHtgTmp °C OK*Alarm
Adress Description Values/Units Remarks
Input register (Read)
1x0106 PreEtrHtgTmp °C OK*Alarm
Unsigned Word
3x0001
General status (Word 1)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Alarm class danger (A)
Bit1 Alarm class critical (A)
Bit2 Alarm class low (B)
Bit3 Alarm class warning (B)
Bit4
Bit5
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11 Actual control temp, room
Bit12 Actual control temp, exh
Bit13 Actual control temp, sply
Bit14
Bit15
Unsigned Word
3x0005
Digital inputs (Word 1)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0
Bit1 External control 1
Bit2 External control 2
Bit3
Bit4
Bit5
Input states (Read) (continuation)
Adress Description Values/Units Remarks
80
Connection to the Master System (ModBus Standard)
Input register (Read) (continuation)
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
3x0006
Digital inputs (Word 2)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
Unsigned Word
3x0009
Digital outputs (Word 1)
0-65535
Bit0 Supply (Exhaust) dampers
Bit1
Bit2
Bit3
Bit4 Supply fan, running
Bit5 Supply fan, off
Adress Description Values/Units Remarks
81
Connection to the Master System (ModBus Standard)
Bit6
Bit7
Bit8
Bit9 Exhaust fan, running
Bit10 Exhaust fan, off
Bit11
Bit12
Bit13
Bit14
Bit15
3x0010
Digital outputs (Word 2)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Cooling pump
Bit1 Cooling DX, off
Bit2 Cooling DX, stage 1
Bit3 Cooling DX, stage 2
Bit4
Bit5
Bit6
Bit7
Bit8 Heating pump
Bit9
Bit10 Electrical heating, off
Bit11 Electrical heating, st1
Bit12
Bit13
Bit14
Bit15
3x0011
Digital outputs (Word 3)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Heat pump DO 2
Bit1
Bit2
Bit3
Bit4
Bit5
Input register (Read) (continuation)
Adress Description Values/Units Remarks
82
Bit6 Heat pump DO 1
Bit7
Bit8 Extra el heating, off
Bit9 Extra el heating, stage 1
Bit10
Bit11
Bit12
Bit13 Request for humidification
Bit14
Bit15
3x0012
Digital outputs (Word 4)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0
Bit1
Bit2 Burner heating, st1
Bit3 Burner heating, st2
Bit4 Burner heating, Mod+
Bit5 Burner heating, Mod-
Bit6
Bit7
Bit8 Alarm output, high
Bit9 Alarm output, low
Bit10
Bit11
Bit12
Bit13 Heating demand
Bit14 PreWtrHeating
Bit15 PreEl.Heating
Unsigned Word
3x0013
Alarms (Word 1)
0-65535
Bit0
Bit1
Bit2 Burner failure
Bit3 Supply fan
Bit4 Exhaust fan
Bit5 Fan operating hours
Bit6 Supply back up
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
Input register (Read) (continuation)
83
Bit7 Exhaust back up
Bit8 Cooling
Bit9 OverHeat Burner heating
Bit10 Heating recovery
Bit11
Bit12 Heating recovery frost
Bit13
Bit14 Heating recovery damper
Bit15 Flue-gas high temperature, heater shut down
3x0014
Alarms (Word 2)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Heating pump
Bit1
Bit2 Electrical Heating
Bit3 Burner fan overrun TH
Bit4 Heat pump cooling
Bit5
Bit6 Heat pump heating
Bit7
Bit8 Extra Electrical Heating
Bit9
Bit10
Bit11 Humidification
Bit12 PreWtrHeating
Bit13 Fire Alarm (external alarm)
Bit14 Electric pre-heating
Bit15 Filter Alarm
3x0015
Alarms (Word 3)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Out temperature
Bit1 Supply temperature
Bit2 Heating frost temperature
Bit3 Room1 temperature
Bit4 Room2 temperature
Bit5 Exhaust temperature
Bit6 Extract temperature
Bit7
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
84
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13 Room unit 1,2 - temperature
Bit14 Supply temperature deviation
Bit15 Room/Exh temp deviation
3x0016
Alarms (Word 4)
0-65535
0-1 for each bit or counted binary to a decimal number
Bit0 Supply press/flow deviation
Bit1 Exhaust press/flow deviation
Bit2
Bit3 Outdoor air humidity
Bit4 Inlet air humidity
Bit5 Room air humidity
Bit6 Dew point
Bit7
Bit8 Air quality
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
Unsigned Word
3x0017 Act operating mode 0-12 Present value
0=Off
1=On/Comfort
2=Economy
3=Na
4=Osstp
5=NightClg
6=UnOcc
7=NightKick
9=Fire
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
85
10=Stop
11=OverRun
12=StartUp
12=Start
3x0018 Act fan step 0-5 Off*Stage1*Stage2*St
age3*Stage4*Stage5
3x0019
3x0020 Op mode man st/tmp 0-11 Auto*Off*Eco St1*Comf
St1*Eco St2*Comf St2*Eco St3*Comf St3*Eco St4*Comf St4*Eco St5*Comf St5
3x0021
3x0022 TSP steps/tmp 0-10 Off*Eco St1*Comf
St1*Eco St2*Comf St2*Eco St3*Comf St3*Eco St4*Comf St4*Eco St5*Comf St5
3x0023 Act Opmode ext ctrl 0-6 Auto*Off*Stage
1*Stage 2*Stage 3*Stage 4*Stage 5
3x0024
3x0025 Supply (Exhaust) air damper cmd 0-1 Off*On
3x0026
3x0027
3x0028 Supply fan cmd 0-6 Off*Stage 1*Stage
2*Stage 3*Stage 4*Stage 5
3x0029 Sply fan outp sign 0-100%
3x0030 Exhaust fan cmd 0-6 Off*Stage 1*Stage
2*Stage 3*Stage 4*Stage 5
3x0031 Exh fan outp signal 0-100%
3x0032
3x0033 Cooling outp signal 0 - 100%
3x0034 Cooling pump cmd 0-1 Off*On
3x0035 Cooling DX cmd 0-2 Off*Stage 1*Stage 2
3x0036 Hrec outp signal 0 - 100%
3x0037
3x0038 Hrec dmpr outp sign 0 - 100%
3x0039 Inlet/outlet damper swimming pool unit 0 - 100%
3x0040 Heating outp signal 0 - 100%
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
86
3x0041 Htg pump cmd 0-1 Off*On
3x0042 El htg outp signal 0 - 100%
3x0043 El heating cmd 0-1 Off*On
3x0044 Heat pump Cooling 0 - 100%
3x0045 Heat pump 0 - 100%
3x0046 Heat pump state 0-2 None*Cooling*Heating
3x0047 Heat pump Heating 0 - 100%
3x0048 Heat pump (heating) 0-1 None*Heating
3x0049 El htg 2 outp sign 0 - 100%
3x0050 El heating 2 cmd 0-1 Off*On
3x0051
3x0052 Humidification 0 - 100%
3x0053 Humidification (state) 0-1 Off* On
3x0054
3x0055 Dehumidification 0 - 100%
3x0057
3x0058
3x0059
3x0060 Alarm output 0-1 Normal*Alarm
3x0061
3x0062
3x0064 Act airquality comp 0 - 100%
3x0065 Act fan clg value 0 - 100%
3x0066 Act fan htg value 0 - 100%
3x0067 Act fan comp tmp 0 - 100%
3x0068 Current fan speed compensation (humidity) 0 - 100%
3x0069
3x0070
3x0071 Current mixing compensation (humidity) 0 - 100%
3x0072 Outside air temp `-x.y - +x.y °C (factor 10)
3x0073 Supply air temp `-x.y - +x.y °C (factor 10)
3x0074 Heating frost tmp °C (factor 10)
3x0075 Valid room tmp °C (factor 10)
3x0076 Return air temp °C (factor 10)
3x0077 Exhaust air temp °C (factor 10)
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
87
Connection to the Master System (ModBus Standard)
3x0078
3x0079
3x0080
3x0081
3x0082
3x0083
3x0084 Outdoor air humidity - relative %r.H.
3x0085 Outdoor air humidity - absolute `-x.y - +x.y g/kg (divider 10)
3x0086 Outdoor air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0087 Inlet air humidity - relative %r.H.
3x0088 Inlet air humidity - absolute `-x.y - +x.y g/kg (divider 10)
3x0089 Inlet air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0090 Room air humidity - relative %r.H.
3x0091 Room air humidity – absolute `-x.y - +x.y g/kg (divider 10)
3x0092 Room air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0093 Dew point `-x.y - +x.y g/kg (divider 10)
3x0095 Inlet air flow rate 0 - x m3/h
3x0096 Outlet air flow rate 0 - x m3/h
3x0097 Inlet air flow rate 0 - x Pa
3x0098 Outlet air pressure 0 - x Pa
3x0099
3x0101 Air quality 0 – x ppm
3x0102
3x0104 Act heating stpt `-x.y - +x.y °C
3x0105 Act cooling stpt °C
3x0106 Act sply htg stpt °C
3x0107 Act sply clg stpt °C
3x0108 Current required value of humidity -
humidification
0 - x.y %r.H. (divider 10)
3x0109 Current required value of humidity -
dehumidification
%r.H. (divider 10)
3x0110 Current humidification required value for
cascade control
%r.H. (divider 10)
3x0111 Current dehumidification required value in
cascade control
%r.H. (divider 10)
3x0112 Act sply fan stpt 0-100% (0 - x l/s)
Input register (Read) (continuation)
Adress Description Values/Units Remarks
88
3x0113 Act exh fan stpt 0-100% (0 - x l/s)
3x0114
3x0115
3x0116
3x0117
3x0120 Hour
3x0121 Minute
3x0122 Second
3x0123 Year
3x0124 Month
3x0125 Day
3x0130 Burner flue temp °C (factor 10)
3x0131 PreEl. heating temp °C (factor 10)
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
3x0132 PreWater heating temp °C (factor 10)
3x0133 Burner damper 0-100%
3x0200 RoomUnitsActRmUMode 0-3 Auto*Comf*StBy*Eco
3x0210 RoomUnitsActSpvShi °C
3x0211 RmUTmp1 °C
3x0212 RmUTmp2 °C
Unsigned Word
4x0001 Control bits 0-65535
Bit0
Bit1 External control 1
Bit2 External control 2
Bit3
Bit4
Bit5
Bit6
Bit7 Fire alarm (external alarm)
Bit8
Bit9
Bit10
Bit11
Bit12
Holding register (Read/Write) [03:H]
Adress Description Values/Units Remarks
89
Bit13
Bit14
Bit15
Unsigned Word
Present value
4x0005
Control state required by BMS (variant without air temperature conditioning)
0-6 Auto*Off*St1*St2*St3*
St4*St5
4x0006
Device state – BMS request 0-11
Auto*Off*Eco St1*Comf St1*Eco St2*Comf St2*Eco St3*Comf St3*Eco St4*Comf St4*Eco St5*Comf St5
4x0007
4x0008 Control state required by Manual control
(variant without air temperature conditioning)
0-6 Auto*Off* St1* St2*
St3* St4* St5
4x0009 Op mode man st/tmp 0-11 Auto*Off*Eco St1*Comf
St1*Eco St2*Comf St2*Eco St3*Comf St3*Eco St4*Comf St4*Eco St5*Comf St5
4x0010
4x0011
4x0012
Signed Word
PresentValue
4x0020 (factor 10)
4x0021
4x0022 Comfort htg stpt °C
4x0023 Comfort clg stpt °C
4x0024
4x0025
4x0026 Economy htg stpt °C
4x0027 Economy clg stpt °C (factor 10)
4x0028
4x0029
4x0030
4x0031
4x0032
Holding register (Read/Write) [03:H] (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
90
4x0033
4x0034
4x0035
4x0036 Sply max limit `-x.y - +x.y °C (factor 10) Higt limit
4x0037 Sply min limit `-x.y - +x.y °C (factor 10) Low limit
4x0039 Set-point of relative humidity - Comfort 0 - x %r.H.
4x0040 Dehumidification relative set-point - Comfort 0 - x %r.H.
4x0041 Set-point of relative humidity - Economy 0 - x %r.H.
4x0042 Dehumidification relative set-point –
Economy
0 - x %r.H.
4x0043
4x0044
4x0045
4x0046
4x0047
4x0048
4x0049
4x0050 Sply fan st1 stpt 0 - x l/s %, Pa or l/s
4x0051 Sply fan st2 stpt
4x0052 Sply fan st3 stpt
4x0053 Sply fan st4 stpt
4x0054 Sply fan st5 stpt
4x0055
4x0056 Exh fan st1 stpt 0 - x l/s %, Pa or l/s
4x0057 Exh fan st2 stpt
4x0058 Exh fan st3 stpt
4x0059 Exh fan st4 stpt
4x0060 Exh fan st5 stpt
4x0061
4x0062 Air quality stpt CO 0 - x ppm
4x0063 Air quality stpt CO2, VOC 0 - x ppm
TrackingValueCOM
4x0064 Outside air temp `-x.y - +x.y °C (factor 10)
4x0065 Air relative humidity - room %r.H. (divider 10)
4x0066 Room temperature °C
4x0067
Holding register (Read/Write) [03:H] (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
91
Advanced mode
Signed Word
PresentValue
4x0070
4x0071
4x0072
4x0073
4x0074
4x0075
4x0076
4x0077
4x0078
4x0079
4x0080
4x0081
4x0082 CaseFlowLimtMinDev °C (factor 10)
4x0083 CaseFlowLimtMaxDev °C (factor 10)
4x0084
4x0085
4x0086
4x0087
4x0088
4x0089
4x0090 Minimum fresh air flow rate (%) - Economy 0 - 100%
4x0091 Minimum fresh air flow rate (%) – Comfort 0 - 100%
4x0092
4x0093
4x0094
4x0095
4x0096
4x0097
4x0098
4x0099
4x0100
4x0101
4x0102
4x0103
Holding register (Read/Write) [03:H] (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
92
4x0104
4x0105
4x0106
4x0107
4x0108
4x0109
4x0110
4x0111
4x0112
4x0113
4x0114
4x0115
4x0116
Control constants
4x0201 Cooling (factor 100) Gain - Signed Word
4x0202 Cooling 0 - x sec Integral - Unsigned Word
4x0203 Cooling 0 - x sec Differential - Unsigned Word
4x0204 Heat recovery (factor 100) Gain - Signed Word
4x0205 Heat recovery 0 - x sec Integral - Unsigned Word
4x0206 Heat recovery 0 - x sec Differential - Unsigned Word
4x0207 Hrec frost protect (factor 100) Gain - Signed Word
4x0208 Hrec frost protect 0 - x sec Integral - Unsigned Word
4x0209 Hrec frost protect 0 - x sec Differential - Unsigned Word
4x0210
4x0211
4x0212
4x0213 Hrec damper (factor 100) Gain - Signed Word
4x0214 Hrec damper 0 - x sec Integral - Unsigned Word
4x0215 Hrec damper 0 - x sec Differential - Unsigned Word
4x0216 Water heating (factor 100) Gain - Signed Word
4x0217 Water heating 0 - x sec Integral - Unsigned Word
4x0218 Water heating 0 - x sec Differential - Unsigned Word
4x0219 Htg frost protect (factor 100) Gain - Signed Word
4x0220 Htg frost protect 0 - x sec Integral - Unsigned Word
4x0221 Htg frost protect 0 - x sec Differential - Unsigned Word
4x0222 Electrical heating (factor 100) Gain - Signed Word
Holding register (Read/Write) [03:H] (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
93
Holding register (Read/Write) [03:H] (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
4x0223 Electrical heating 0 - x sec Integral - Unsigned Word
4x0224 Electrical heating 0 - x sec Differential - Unsigned Word
4x0225 Burner (factor 100) Gain - Signed Word
4x0226 Burner 0 - x sec Integral - Unsigned Word
4x0227 Burner 0 - x sec Differential - Unsigned Word
4x0228 Burner Damper (factor 100) Gain - Signed Word
4x0229 Burner Damper 0 - x sec Integral - Unsigned Word
4x0230 Burner Damper 0 - x sec Differential - Unsigned Word
4x0231
4x0232
4x0233
4x0234 El. reheating (El. heating 2) (factor 100) Gain - Signed Word
4x0235 El. reheating (El. heating 2) 0 - x sec Integral - Unsigned Word
4x0236 El. reheating (El. heating 2) 0 - x sec Differential - Unsigned Word
4x0237
4x0238
4x0239
4x0240
4x0241
4x0242
4x0243
4x0244
4x0245
4x0246
4x0247
4x0248
4x0249
4x0250
4x0251
4x0252
4x0253
4x0254
4x0255 Supply fan (factor 100) Gain - Signed Word
4x0256 Supply fan 0 - x sec Integral - Unsigned Word
4x0257 Supply fan 0 - x sec Differential - Unsigned Word
4x0258 Exhaust fan (factor 100) Gain - Signed Word
4x0259 Exhaust fan 0 - x sec Integral - Unsigned Word
94
4x0260 Exhaust fan 0 - x sec Differential - Unsigned Word
4x0261 Humidification (divider 100) Gain - Signed Word
4x0262 Humidification 0 - x sec Integral - Unsigned Word
4x0263 Humidification 0 - x sec Differential - Unsigned Word
4x0264
4x0265
4x0266
4x0267 Dehumidification (divider 100) Gain - Signed Word
4x0268 Dehumidification 0 - x sec Integral - Unsigned Word
4x0269 Dehumidification 0 - x sec Differential - Unsigned Word
4x0270 Air quality (factor 100) Gain - Signed Word
4x0271 Air quality 0 - x sec Integral - Unsigned Word
4x0272 Air quality 0 - x sec Differential - Unsigned Word
4x0273 Casc controller tmp (factor 10) Gain - Signed Word
4x0274 Casc controller tmp 0 - x sec Integral - Unsigned Word
4x0275 Humidity cascade control (Factor 10) Gain - Signed Word
4x0276 Humidity cascade control 0 - x sec Integral - Unsigned Word
4x0277 HeatPumpHtg (factor 100) Gain - Signed Word
4x0278 HeatPumpHtg 0 - x sec Integral - Unsigned Word
4x0279 HeatPumpHtg 0 - x sec Differential - Unsigned Word
4x0280 HeatPumpClg (factor 100) Gain - Signed Word
4x0281 HeatPumpClg 0 - x sec Integral - Unsigned Word
4x0282 HeatPumpClg 0 - x sec Differential - Unsigned Word
4x0283 ElPreHtg (factor 100) Gain - Signed Word
4x0284 ElPreHtg 0 - x sec Integral - Unsigned Word
4x0285 ElPreHtg 0 - x sec Differential - Unsigned Word
4x0283 WtrPreHtg (factor 100) Gain - Signed Word
4x0284 WtrPreHtg 0 - x sec Integral - Unsigned Word
4x0285 WtrPreHtg 0 - x sec Differential - Unsigned Word
Holding register (Read/Write) [03:H] (pokračování)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks
95
List and Description of Basic Data Points
Connection to the Master System (BacNet Standard)
BACnet/IP (BMS)
e VCS control unit enables integration of the centralized BMS (Building Management System) using the BACnet/IP communication standard. Using a suitably integrated mas­ter system, it is possible to control the air-handling device's operating state.
Generally
BACnet is a standard communication protocol for Building Automation and Control Networks developed by ASHRAE (American Society of Heating, Refrigerating and Air-condition­ing Engineers). e main goal was to create a protocol which enables the integration of systems from different manufactur­ers intended for building automation. For detailed information on the BACnet protocol, refer to the following websites:
www.bacnet.org www.bacnetinternational.net
BACnet/IP Protocol
ere are several variants of the BACnet protocol. e VCS control system uses BACnet/IP for the Ethernet network. The BACnet communication protocol works using the Master/Slave principle. e Server function is used for VCS unit system communication with the master system. is means that the VCS control unit behaves like a Server in the communication. Protocol settings can be performed using one of the follow­ing controllers: HMI, DM, TM or Web. Switching on and off,
restart and other settings of the BACnet server can be carried out through the web page (calling the address set in the VCS control unit). For detailed information on the BACnet/IP Stand­ard (EDE file and others) settings and application, refer to the Siemens BACnet/IP Communication Module documentation available on the REMAK website.
e following table includes a list of basic data points which can be used for this communication and their description. e list includes specifications of variables for different VCS control system variants.
For example, if the VCS control system (air-handling device) has not been equipped with gas heating, it will not be possible to use these variables. e final functionality, monitoring and control options will be dependent on the integrator used to ensure connection to the master BMS system.
Data point name Meaning
Device Device Diagnostic Diagnostics SystemClock System time AirQuality Air quality RoomTmp Room temperature RmUTmp1 HMI-SG1 RmUTmp2 HMI-SG2 ValidRoomTmp Temperature in the room aer control ReturnAirTmp Outlet air temperature SupplyTmp Inlet air temperature OutTmp Outdoor temperature HtgFrstTmp Return water temperature (water heater) ExhaustTmp Outlet air temperature aer the heat exchanger PreElHtgTmp Temperature, electric pre-heating PreWtrHtgTmp Return water temperature (water pre-heating) BrnrFlueTmp Flue gas temperature RoomHum Air humidity in the room - relative SupplyHum Inlet air humidity - relative OutHum Outdoor air humidity - relative RmHumAbs Absolute air humidity in the room SplyHumAbs Absolute inlet air humidity OutHumAbs Absolute outdoor air humidity RmEnth e room - enthalpy OutEnth Outdoor enthalpy ActOpMode Current state of the device ActFanStep Current state of the fans OpModeAutoManSt.Swtch Manual mode (control) OpModeAutoManStTmp.Swtch Manual mode (control)
96
Connection to the Master System (BacNet Standard)
OpModeBmsTimeSt.Swtch BMS control mode (control, master system) OpModeBmsTimeStTmp.Swtch BMS control mode (control, master system) TmpSpv.CoSpvHtg Required value for heating - Comfort TmpSpv.CoSpvClg Required value for cooling - Comfort TmpSpv.EcSpvHtg Required value for heating - Economy TmpSpv.EcSpvClg Required value for cooling - Economy HumSpvRel.SpvHum Required value for humidification (relative) HumSpvRelSpvDehum Required value for dehumidification (relative) AirQSpv Required value for air quality ScheduleSt Weekly time schedule ScheduleStTmp Weekly time schedule CalendarEx Exception time schedule CalendarOff Switch-off schedule ActCascSpvHtg Current required heating temperature (cascade) ActCascSpvClg Current required cooling temperature (cascade) ActCascSpvDeh Current required value for dehumidification (cascade) ActCascSpvHum Current required value for humidification (cascade) Heating.Pos Heating node valve outlet position ElectricalHtg.Pos Electric heating outlet position Cooling.Pos Cooling valve outlet position ExtraElHtg.Pos Electric aer-heating outlet position Hrec.Pos Heat exchanger control outlet position HrecDamp.Pos Mixing damper outlet position aoHeatPumpHtg.Pos Heat pump outlet position - heating aoHeatPumpClg.Pos Heat pump outlet position - cooling HumidityCtrl.Pos Humidification current value DeHumidity.PrVal Dehumidification current value AirQCmp.PrVal Air quality compensation current value SplyFan.Cmd.St Current stage, inlet fan ExhFan.Cmd.St Current stage, outlet fan Heating.Pmp.Cmd.OnOff Heating pump state ElectricalHtg.CmdSt.St Electric heater state ExtraElHtg.CmdSt.St Electric aer-heater state Cooling.Pmp.Cmd.OnOff Water cooler pump state Cooling.CmdDx.St Cooling state, inverter cooling unit Damper.Exh.OnOff Damper, outlet Damper.Sply.OnOff Damper inlet AlmOutHigh Alarm, output A AlmOutLow Alarm, output B AlmCl0 Alarm, class A AlmCl1 Alarm, class A AlmCl2 Alarm, class B AlmCl3 Alarm, class B FireAlm External alarm AckAlmPls Failure release
List and Description of Basic Data Points ((continuation))
97
POOL UNITS – description of control
e VCS also allows the control of air-conditioning units designed to ventilate swimming pools (swimming pools, water parks, rehabilitation complexes with water procedures, etc.). As the ventilation needs of these spaces are different from the needs of ventilation of common areas (offices, restaurants, etc.), the control system needs to be optimized according to these requirements. erefore, the behavior of the control system has been modified to create a unique control and control system for pool units. is section of the manual supplements the VCS control system information from the perspective of HVAC pool control. Regarding regulation, pool units are divided into two basic variants. S and without integrated heat pump. e unit without a "ventilating" heat pump only uses outside air to achieve the desired humidity. e integrated heat pump unit uses both the outdoor air and the circulation mode and the integrated heat pump to achieve the desired humidity. Other modifications only complement these two basic variants. For example, additional cooling, reheater, etc.).
Unit operation modes
n Comfort (used for normal operation of air conditioning
systems to provide a comfortable environment for people in the wind). In this mode, the minimum amount of fresh air is preset to 30%..
n Economical (used for HVAC mode to ensure economical
operation when there is no need to provide comfortable conditions - there are no persons in the ventilated area). In this mode, the minimum amount of fresh air is preset to 0%. For each mode, the set room temperature, the maximum humidity in the room and the minimum amount of fresh air are set separately. e behavior of the control system is also different in these modes and is optimized for maximum energy-efficient operation of the unit. In Comfortable mode, emphasis is placed on reaching the desired values with respect to the need to supply fresh air for people in the ventilated area. In Economical mode, people are not expected to be in the windspace. at is why other management procedures can be used in this mode to achieve the desired values for economical operation and energy savings.
Temperature control
For pool units, room temperature control with limitation of supply air temperature is used. e set room temperature is set to Comfort and Economy. e supply air temperature is not directly regulated but its intervention in the regulation is in case of deviation from the set limits. e minimum and maximum supply air temperature values are set in the control. See Settings. list of data points. Temperature control is superior to humidity control. In some situations, the dehumidification performance may exceptionally be reduced due to the higher priority of temperature control. is state is signaled on the controllers.
Humidity control (Dehumidification)
For pool units, room moisture control is used. Desired humidity is achieved in various ways according to the type of HVAC pool units.
Pro-Vapor Pool Unit (Units without Integrated Heat Pump)
- e required humidity is achieved by mixing. By supplying a sufficient amount of outdoor dry air. In addition, fan speed control is used to increase the required power.
Pool unit with integrated heat pump and circulation flap - the method of achieving the desired humidity varies according to the selected unity mode:
Comfort Mode
1st stage of dehumidification - mixing + 2nd stage of fan speed 2nd degree of dehumidification - 100% mixing + 3rd stage of fan speed
Economy Mode
1st dehumidification stage - circulation mode + running of the heat pump + raising the speed to 2 degrees. 2nd stage dehumidification - mixing + 2nd stage of fan speed
Fan speed control:
for pool units, a constant flow rate control is usually used in three preset steps. e transition between stages is fully automated and is controlled according to temperature and humidity requirements. e user has the option to switch the unit on any power level. However, if it switches the unit to maximum speed, it automatically blocks the possibility of increasing the speed and optimizing the operation of the HVACfrom an energy point of view. e ability to switch on unity to the maximum speed is primarily possible for service purposes and exceptional operational requirements. e unit increases fan speed when dehumidifying. It can also increase fan speeds in case of sufficient power of heating components. is increases the heating power.
HVAC components control
regulation of individual components (mixing, water heating, etc.) is based on the standard HVAC control. However, for a pool unit there are some differences that are described below:
n Mixing damper and inlet/outlet damper
e dampers are continuously controlled according to the temperature requirement. Furthermore, the position is affected by the requirement for humidity. e mixing valve may no longer be coupled with the inlet / outlet dampers. eir mutual functions may be different in some situations for pool units. For example, when the plate heat recovery is active (pool units with integrated cooling). Extreme temperature protection - at an outside temperature of T <-10 ° C, the maximum amount of fresh air is limited to 40%. is ensures greater control stability. Settings and signaling see data. mixing points.
98
POOL UNITS – description of control
n Circulating damper
Enabled in economy mode heating or dehumidification stage
1. If the circulation damper is open, the inlet and outlet valves are closed. e outdoor unit is not circulating and 100% circulates it. e mixing valve is further regulated according to temperature and humidity.
n Heat Pump
Activated and continuously controlled on request from temperature control. However, during circulation, it is not controlled by temperature but is activated based on the requirement of humidity control. Restriction of operation: Heat pump operation is blocked if one of these situations occurs:
1. outdoor temperature is out of set limits
2. the pressure differential on the heat exchanger is out of range ∆P
min
– ∆P
mid
To set all parameters, see list of data points.
n Plate Heat Exchanger
Power regulation is ensured by continuous bypass control. Pro-Vapor Pool Unit (Units without Integrated Heat Pump).
Anti-freeze protection – standard (for the plate heat exchanger without integrated mixing):
Intervention and bypass control according to the standard regulation of the standard HVAC based on the measured exhaust air temperature aer the recuperator - part of the manual for frost protection of the heat exchange.
Anti-freeze protection – option (for a plate heat exchanger with integrated mixing)
Additionally, over the standard, following is supplemented:
n when activating this bypass, the inlet/outlet dampers are
preferably fully opened + the mixing valve is closed
n Reduced speed of the intake fan to stage 1
Pool unit with integrated heat pump and circulation damper:
Anti-freeze protection – standard
is ensured by monitoring the state of the differential pressure transmitter ∆Pmax (min. state 60s), while monitoring the outdoor temperature below -5 ° C and the state when the unit is supplying fresh air. If these conditions occur, the unit will activate the antifreeze protection: e unit switches to the preset time (default 15 minutes, if ∆Pmax lasts longer) to the antifreeze mode (Economy mode, dehumidification of 1st stage - circulation, bypass closed). When the antifreeze mode is complete, re-activation is blocked.
Anti-freeze protection – option
It is used in exceptional cases where the standard is very active and reduces dehumidifying power and fresh air frequently. Switching between variants is possible with HMI. The activation is the same as the standard option. The
intervention is the same, except for the inlet and outlet dampers, which are controlled according to the humidity requirement (Economy mode, dehumidification of the 1st stage - circulation, bypass closed, mixing valve is closed, supply / exhaust flaps regulated).
n Pump for pool water heating
e pump discharges excess heat that is generated during the dehumidification and operation of the HVAC unit. It is triggered under the condition of dehumidification requirement and sufficient supply air temperature. Furthermore, there is a requirement for dehumidification and the required room air temperatures and active heat pump operation.
Additional control functions
Further, all other features based on the standard HVAC application are fully available. ese are described in the relevant paragraphs for a standard application. Like:
n Recovery and mixing at the start of the HVAC n Start optimization n Night cooling
Loading...