SYMPTOM
1. POWER ON/OFF
circuit breaker
trips or fuses
clear when power
is applied.
2. Drive motor does
not start.
3. In non-revers-
ing, controllers
only ••• ·
Controller's M
contactor not
picking up when
START switch is
pressed (closed,.
4.
In reversing con-
trollers
only . ..
Controller's M
contactor not
picking up when
$TART switch is
pressed
(closed,.
Table 6.C
TROUBLESHOOTING SUGGESTIONS FOR THE COMPLETE CONTROLLER
PROBABLE CAUSE
Incorrect wiring connections to controller;
from controller to
motor; in motor.
Short in Power Cube.
Short in Field Supply Kit.
Main a-c line disconnect not closed; or fuse
blown; or no power
applied ahead of
disconnect.
Drive interlocks preventing operation.
Drive motor thermostat
wires not connected
on FlexPak Plus controller terminals 32 and
132on 2TB.
External overload
wires not connected on
FlexPak Plus controller
terminals 32 and 132
on 2TB.
FORVVARD/REVERSE
switch malfunction.
Mcontactor
malfunctioning.
RECOMMENDED PROCEDURES
DANGER
IF CIRCUIT BREAKER HAS TRIPPED OR FUSES HAVE CLEARED. USER MUST
DETERMINE IF A FIELD SUPPLY KIT IS PRESENT. (SEE FIGURE 5.15.) IF FIELD
SUPPLY KIT IS PRESENT. THE FIELD SUPPLY
KIT AND 1TS WIRING MUST OE
INSPECTED FOR DAMAGE. AFTER HE-APPLYING POWER TO THE DRIVE. THE
FIELD VOLTAGE MUST BE RE-CHECKED FOR PROPER VOLTAGE AT MOTOR
TERMINALS F1. F2. IF THIS VOLTAGE IS BELOW 90% OF THE FIELD VOLTAGE
SPECIFIED ON THE MOTOR NAMEPLATE, THE DRIVE MUST NOT BE STARTED
UNTIL PROPER VOLTAGE IS OBTAINED. FAILURE TO FOLLOW THIS PROCEDURE COULD RESULT IN OVERSPEEDING THE MOTOR ANO/OR THE MACHINERY COUPLED TO THE MOTOR SHAFT ANO POSSIBLE FATAL INJURY.
a Remove a-c power at the disconnect.
a Remove leads to L1. L2. A1. A2 and, if used, F1, F2. on incoming side of controller's 1TB and
2TB. (Refer to Figure
3.4.,
a Open the power disconnect switch.
a Check for a ground condition at L1/181, L2/182. A1. A2. F1 and F2. Do this at controller
(internal, side of 1TB and 2TB. If a ground is discovered, check wiring connections on POWER
ON/OFF circuit breaker or fuse block and power disconnect. Also check connection to Power
Cube and motor field terminals F1 and F2.
a If no ground exists, examine the controller Chassis for loose wires and/or foreign objects.
a If no ground exists and if no foreign objects are discovered. reconnect the incoming conductors
A 1, A2 and, if used, Fl and F2. Then check for grounds at these terminals.
0 If a ground is found, it is in the conductors to the motor or in the motor itself.
a Disconnect the motor from the conductors at the drive motor.
a Test A 1, A2, F1 and F2 conductors for a ground. (If one exists, examine connections and insula-
tion for areas where shorts could occur.,
a If no grounds are found in the conductors, check the motor for a ground condition. If a ground is
located here,
examine and/or replace the motor, as necessary.
a Replace Power Cube.
a Replace Diode Bridge in Field Supply Kit. Inspect wires and connections to Field Supply Kit.
Replace all damaged wires and connectors.
a Check disconnect switch, fuses in it, and voltage on line.
0 Verify that all user-installed interlocks are in a state (physical condition and wiring connections,
to allow a start.
-------- ----------- --
a Check connections to thermostat: at drive motor P1, P2; at controller 32. 132.
0 Check for open thermostat inside motor. Make a resistance check of thermostat. (It should read
a short, or low resistance, if it is
closed.)
a Check connections to external overload.
0 Check for open overload. Make a resistance check to overload. (It should read a short, or low
resistance, if it is closed.)
a Open the power disconnect switch.
0 Examine M contactor for firm seating.
0 On the M contactor, connect an ohmmeter on the brown (location 38, and black (location 65, wires.
A short should be read.
0 Connect the ohmmeter on the orange (location 139, and yellow (39, wires. The reading should be
approximately 230 ohms.
a If these readings cannot be obtained, replace the M contactor. (Refer to Table 7.A.)
D Examine Remote Operator Adapter on Regulator Module for firm seating and proper wiring and pin
connections. (Refer to Figure 6.4.)
D Test FORVVARO/REVERSE switch. Use basic technique outlined above for the START /STOP
switch. Here test 39 (purple) against 66 (blue, and 65
(white, against 67 (gray,.
a On the Auxiliary M pins located on the Regulator Module, connect an ohmmeter. Place it on the pin
39 and pin 67.
0 Place the FORVVARD/REVERSE switch in the FORVVARD position. The reading should be
approximately 500 ohms if it is operating properly.
a Without changing test points. place the switch in the REVERSE position. The reading should be
about 500 ohms
if it is operating properly. If a short is observed, remove jumper J9 and repeat the
test.
0 If a 500-ohm resistance reading cannot be obtained when the switches are open, the M contactor
is malfunctioning and must be replaced.
40
V
r
V