Levalarm®Gold™ meets or exceeds all applicable specifications when shipped from the factory.
All units should be inspected upon receipt to ensure that no damage has been incurred during transit. If there is a
claim due to damage, it should be filed with the carrier immediately. Clark-Reliance
®
Boiler Trim products should be stored
in a dry and sheltered area prior to installation. The equipment provided may consist of electrical items that are intended for
either indoor or outdoor use. As a matter of good practice, dry storage will prevent the products from exposure to the
outdoor elements. This will eliminate the potential for water damage. The temperature of the storage area should not exceed
150 Deg. F (84 Deg. C) or drop below 32 Deg. F (0 Deg. C).
OPERATION
A stainless steel float is attached to the end of a rod with a stainless steel encapsulated magnet. The magnet travels
vertically in the pressure tube. The primary magnet on the float rod inside the pressure tube drives the secondary magnet,
which in turn drives the tertiary magnet. The tertiary magnet is mounted to the switch arm and activates the switch. See
Figure 1. The use of repelling magnetic fields creates a positive interlo cking switch that is both vibration resistant and
compensates for installation misalignment. A buoyed float will cause the reaction of the magnets to hold the switch open or
closed, depending on which terminals are used. As liquid falls in the chamber, the float drops and directs the magnets to the
opposite position which activates the switch in the opposite direction.
MAGNET SWITCH LAYOUT
INSTALLATION
Caution: Before proceeding, follow any and all plant lock out - tag out procedures required. Verify that all power is turned
off to the Levalarm®s. If under pressure, the equipment should be isolated, or the boiler should be shut down before
proceeding with the installation. Open drain valve to eliminate any trapped pressure. All inspection and installation steps
should be performed by a qualified technician and should be executed in accordance with all applicable national and local
codes
EA100G Series Levalarm
Standard connections for the EA100G Series Levalarm
connections. The Levalarm
®
dimensional information is available upon request.
®
should be installed with the reference arrow (switch point) at the level where the alarm or trip
is specified. Shut off valves above and below the Levalarm
However, these valves must be locked open when the boiler is in service. Also, a drain connection with a shut off valve
s are 1” FNPT for threaded connections or 1” FSW for socket weld
®
should be installed for safe inspection or repair of the unit.
clark-reliance.com
@
should be installed to a point of safe discharge to facilitate blowdowns. Below in Figure 2 is a typical arrangement for the
installation of the Levalarm
After the piping has been installed to the body of the Levalarm
®
. Verify that installation conforms to local and national Codes and Standards.
®
, the switch should be connected by following this
procedure:
1. Remove the switch cover in order to access the connections on the switch assembly by loosening the three button
head cap screws on the outside of the gold housing, do not remove screws completely. Pull upward on gold
housing to expose switch.
2. Use the ½” conduit opening in the switch housing assembly for connecting flexible or rigid conduit when wiring
the unit.
CAUTION: Make sure that all wire leads to the switch do not interfere with the action of the switch before
replacing the switch cover!
3. Example wiring diagrams for connecting the low water cutout, alarms (such as lights or and audible signal), etc,
are illustrated below:
4. After checking that all connections are tight and correct, replace the switch cover, as the unit is now ready to be put
Note that the frequency and method of blow-down may affect service life and performance of the Levalarm
The connection lines to the Levalarm
®
may be low. After performing the blow-down procedure, if the water level does not appear to return to normal promptly, the
connecting piping may be partially restricted and need to be cleaned.
can become restricted with sediment and indicate normal water levels when water
clark-reliance.com
@
Clark-Reliance
1. Close both the steam and water valves between the boiler drum and the Levalarm
2. Open the drain valve fully on the bottom of the Levalarm
®
suggests the following blow-down procedure:
®
piping.
®
unit.
3. Crack open the steam valve and allow a gentle rush of steam to pass through the device. The steam should not pass
through for longer than 20 seconds.
4. Close the steam valve.
5. Blow-down the water line.
6. Close the blow-down valve and simultaneously open the steam and water valves, slowly bringing the equipment back to a
normal operating level.
7. Water should enter the Levalarm
®
quickly when the blow-down valve is closed. Th is will indicate that the lines are free
of sludge, sediment, or scale buildup.
NOTE:
1. Any trip or alarm circuits that are actuated by the equipment being blown-down should be bypassed to prevent false
alarms during the blow-down process. A Clark-Reliance
®
Holding Switch model HS-0 or HS-1 can be used to by-pass the
Low Water Cutout to prevent a false trip during the blow-down procedure.
2. Blow-down should be conducted on a weekly basis, or as necessary, based on water quality.
d. Examine the drain path to make sure water has a clear drain path.
e. Inspect magnets on the action of the switch to make sure no debris have stopped the action.
3. Test the unit for proper functioning
a. To test the switch assembly, set the unit in a vise and make sure that the switch housing is
vertical as if it were mounted on the boiler piping.
b. Attach an ohm meter to the common and normally open switch contact and manually move the
float up and down and verify the switch operates on both directions. The meter should indicate
continuity only when the switch is operated in the closed position.
c. Then, move the ohm meter terminal from the normally open terminal to the normally closed
terminal and repeat the test. The meter should indicate an open circuit only when the switch is in
the open position.
4. If the unit fails to test properly, contact Clark-Reliance
®
for further instructions to adjust the switch
mechanism or to obtain authorization to return the unit for factory inspection. If the switch tests OK,
return unit to service.
5. Reassemble the unit. Reinstall the Switch head assembly onto the body with a new gasket. Lubricate the
bolts with a Nickel based high temperature lubricant and torque to requirements in the Installation section.
6. Verify proper function.
Symptom Probable Cause
2) Float is stuck in the “down” position” a) Float encased in contamination
b) Failed float
c) Contaminants in Pressure Tube.
Possible remedies:
1. Inspect the internal portion of the Levalarm
a. Isolate the Levalarm
®
and make sure there is no pressure in the unit.
®
Chamber
b. Remove the flange head assembly
c. Remove, inspect the float assembly.
d. If the float contains water or shows signs of obvious damage, such as collapse or a crack near the
spud where the float rod attaches, replace the float and use Loctite or equal on the threads of the
float and float rod with a lock washer. Tighten the new float securely onto the float rod.
2. Test the unit for proper functioning
a. To test the switch assembly, set the unit in a vise and make sure that the switch housing is
vertical as if it were mounted on the boiler piping.
b. Attach an ohm meter to the common and normally open switch contact and manually move the
float up and down and verify the switch operates on both directions. The meter should indicate
continuity only when the switch is operated in the closed position.
c. Then, move the ohm meter terminal from the normally open terminal to the normally closed
terminal and repeat the test. The meter should indicate an open circuit only when the switch is in
the open position.
3. If the unit fails to test properly, contact Clark-Reliance
®
for further instructions to adjust the switch
mechanism or to obtain authorization to return the unit for factory inspection.
4. Reassemble the unit. Reinstall the Switch head assembly onto the body with a new gasket and apply a
Teflon based sealant to both sides of the gasket. Lubricate the bolts with a Nickel based high temperature
lubricant and torque to requirements in the Installation section.
a) The REA1351 switch is out of adjustment
b) The REA1351 switch has failed
1. Test the REA1351 Microswitch
a. Isolate the Levalarm
®
and make sure there is no pressure in the unit.
b. Remove the flange head assembly
c. Remove the Switch cover
2. Test the unit for proper functioning
a. To test the switch assembly, set the head assembly in a vise and make sure that the switch
housing is vertical as if it were mounted on the boiler piping.
b. Attach an ohm meter to the common and normally open switch contact and manually move the
float up and down and verify the switch operates on both directions. The meter should indicate
continuity only when the switch is operated in the closed position.
c. Then, move the ohm meter terminal from the normally open terminal to the normally closed
terminal and repeat the test. The meter should indicate an open circuit only when the switch is in
the open position.
3. If the unit fails to test properly, contact Clark-Reliance
®
for further instructions to adjust the switch
mechanism or to obtain authorization to return the unit for factory inspection. If the switch tests OK,
return unit to service.
4. Reassemble the unit. Reinstall the Switch head assembly onto the body with a new gasket and apply a
Teflon based sealant to both sides of the gasket. Lubricate the bolts with a Nickel based high temperature
lubricant and torque to requirements in the Installation section.
Warning: If this equipment is used in a manner not specified by Clark-Reliance
®
, the protection provided by the equipment
may be impaired. Only replacement parts manufactured by Clark-Reliance® should be used to ensure safety and reliable
operation.
The use of non-Clark-Reliance
Order genuine Clark-Reliance
®
parts will void the factory warranty and any agency approvals.
®
replacement parts at: http://parts.clark-reliance.com or contact your local Clark-Reliance®
Representative.
Any additional questions should be directed to your local Clark-Reliance