Instructions for
Installation, Operation
Care and Maintenance
For Single Interlock Preaction Systems
With Dual Solenoid Actuation
Of Pneumatic Pilot Release
Bulletin 739
Single Interlock
Preaction System
4"(100mm),
6"(150mm) & 165mm
Sizes with Trim
LPCB Approved
•
Redundant Solenoid Valve
•
Release
Rated to 175 psi (12.1 bar)
•
Externally Resetable
•
Clapper
One Main Drain
•
Bulletin 739
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
General Description
Reliable Single Interlock Preaction Systems are de
signed for water-sensitive areas that require protection
from inadvertent water flow into the sprinkler system pip
ing.
Sprinkler piping in single interlock systems can effec
tively be supervised by means of a Reliable Model A-2
Pressure Maintenance Device and a tank-mounted air
compressor. Loss of supervising pneumatic pressure,
due to a damaged sprinkler or sprinkler pipe will not
cause water to flow through the Model DDX Deluge
Valve and into the system piping. A significant loss of
pneumatic pressure will activate a trouble-annunciating
device when the system pressure falls below a predeter
mined pressure level.
When one electrical detector senses the presence of
fire, the electrical releasing control panel activates fire
alarm devices and energizes the two redundant, nor
mally-closed solenoid valves in the open position (
Arranging detectors in a cross-zoned pattern will require
operation of two detectors before the solenoid valves
can open). These solenoid valves, when closed, retain
sufficient AIR pressure in the Model LP Pilot Line Actua
tor, which in turn preserves sufficient WATER pressure in
the push rod chamber of the Model DDX Deluge Valve in
order to maintain it closed.
Energizing the solenoid valves relieves the air pressure
in the Model LP Dry Valve Actuator (see Fig. 8), thereby
releasing the water pressure that it was retaining. This is
turn relieves the pressure in the push rod chamber of the
Model DDX Deluge Valve. Venting this push rod chamber will open the Model DDX Deluge Valve and allow water to flow into the sprinkler system.
To fully operate a cross-zoned single interlock system,
two electrical detectors must activate and a sprinkler
head must open. During the early stages of a fire, smoke
or heat activates the first detector, which causes the control panel to produce a local alarm and an alarm at the
main fire alarm panel. Electrical relays inside the releas
ing control panel can be used to shut down airmoving
equipment or activate security doors and other electrical
devices. Subsequent activation of a second, nearby or
adjacent detector will cause the panel to energize the
solenoid valves open and release water into the sprinkler
system piping. Water flowing into the sprinkler system
piping will simultaneously produce water pressure that
causes the transfer of contacts in the pressure switch
mounted in the trim. This pressureswitch can electrically
initiate the shutdown or startup of equipment, such as
computers or other second alarm devices. This flow of
water into the sprinkler system piping effectively con
verts the dry system into a wet pipe system. In the event
that the fire subsequently produces sufficient heat to op
erate a sprinkler head, water will flow from that sprinkler,
controlling or suppressing the fire.
The major benefits of a single interlock preaction sys
tem, when compared with a wet pipe (deluge) system
are as follows:
Note:
-
-
-
-
-
-
-
A. A fire alarm sounds prior to the operation of a
sprinkler head, which may enable extinguishing
the fire by handheld means before the actual oper
ation of any sprinklers and subsequent water dam
age.
B. A trouble annunciator signals whenever the in
tegrity of the piping or sprinklers is accidentally or
intentionally disturbed; however, no water flow or
water damage will occur at that time.
C. Speedy detection and an early fire alarm are
provided by fire detectors, without the delay asso
ciated with water delivery time in the event of a fire.
with a wet pipe system, the fire alarm is de
Note:
layed until after water has begun flowing from an
operated sprinkler head.
At the heart of Reliable’s Single Interlock Preaction Sys
tem is the Model DDX DelugeValve. This Deluge Valve is
a hydraulically operated, straight-through-design, differ
ential-type valve (see Fig. 1). System maintenance is
simplified since priming water is not required and the
deluge valve can be reset externally without cover re
moval. This is accomplished by pushing in and turning
the external reset knob at the rear of the deluge valve
(see Fig. 1). This feature provides a significant system-restoration time advantage.
The Reliable Single Interlock Preaction System trim set
(see Fig. 2) provides all of the necessary equipment for
connections to the Model DDX Deluge Valve’s pushrod
chamber inlet and outlet ports, the 2” (50mm) main
drain, alarm devices, air supply, water supply, and required pressure gauges. This trim set is available in individual parts, in time-saving, segmentally assembled kit
forms, or fully assembled to the Model DDX Deluge
Valve.
-
-
-
-
-
-
-
-
Listing & Approvals
The 4” (100mm), 6’ (150mm) and 165mm Single Inter
lock Preaction Systems shown in this bulletin must only
be used in the combination described herein to be Loss
Prevention Certification Board (LPCB) approved. Instal
lation of these systems must be according the require
ments of Technical Bulletin TB21:1994:1.
The majority of the system’s components are individu
ally Listed by Underwriters Laboratories Inc. and Fac
tory Mutual Approved.
-
-
-
-
-
-
-
-
2.
Loss Prevention Certification Board
(LPCB) Installation Requirements of
Preaction systems Include:
1. Solenoid valves shall be installed in parallel.
2. Solenoid valves shall function in pneumatic condi
tions only, and be protected by a strainer.
3. LPCB Certified detectors compatible with the control
and indicating equipment shall be used.
4. Suitable electrical detection, control and indicating
equipment and pneumatic systems shall be used.
The control and indicating equipment shall be LPCB
approved / certificated.
5. Connecting cables shall comply with BS 6387:1983,
classification C, W, Z evidenced by LPCB certifica
tion.
6. Pre-action systems shall be electrically monitored to
demonstrate that they are in a ‘ready to operate’
state at all times.
7. Clear dry air shall be used. Compressor tank must
have provision for draining.
8. Pre-action system equipment shall be installed, oper
-
-
ated and maintained as prescribed in the firm’s instal
lation , operating and maintenance manual.
9. Pre-action systems shall be configured in accordance
with the manufacturer’s defined specifications.
10.Pre-action systems shall comply with the details spec
ified in the relatedLPC Technical Bulletin (Ref. TB21).
11.The firm responsible for the complete pre-action sta
tion, including electrics, shall be identified.
12.Normally un-energized solenoids may be used, pro
vided that they are continuously monitored for ‘open’
and ‘short circuit.’
-
-
-
-
-
Fig. 1
3.
Fig. 2
3.
SINGLE INTERLOCK PREACTION SYSTEM PARTS LIST (REFER TO FIG. 2)
ITEM
NO.
1
278653004
398048000
498048015
598048022
698048025
792056809
892056810
992056811
1092056702
1192056704
1298085666
1398050004
1498174400
1598174403
1698174401
1798174404
1898174405
1998174402
2096920912
2198240006
2298240101
236304000100
2478653000
2571030010
2694616917
2798543222
2898543266
2998543213
3098543223
3198543210
3298543216
3398543209
3498543230
3598543237
3698543226
PART
NUMBER
6103040026
6103060028
DESCRIPTION
MODEL DDX VALVE,
ASSEMBLY, 4" (100MM)
MODEL DDX VALVE,
ASSEMBLY, 6" (150MM)
MODEL DDX VALVE,
ASSEMBLY, 165 MM
ASSEMBLY, VALVE CAUTION
STATION, 1/2"
BUSHING, REDUCER,
1/2" x 1/4", GALV.
BUSHING, REDUCER,
2" SPIGOT x 1" NPTF, PVC
BUSHING, REDUCER,
3/4" X 1/2", GALV.
BUSHING, REDUCER,
3/4" X 1/4", GALV.
CONNECTOR ASSEMBLY,
NO-LOSS, 3/8 x 1/2 NPT
CONNECTOR,
3/8" ID TUBE x 1/2" NPT
CONNECTOR,
3/8" ID TUBE x 1/4" NPT
CONNECTOR,
3/8" TUBING x 1/4" NPT
CONNECTOR, ELBOW,
3/8" ID TUBE x 1/2" NPT
REDUCER, 1/2" x 1/4"
DRAIN CUP, PVC
ELBOW, STREET, 1/2"
ELL, 1"
ELL, 1/2"
ELL, 1/4"
ELL, 2"
ELL, 3/4"
FLEX LINE, 12"
GAUGE, WATER PRESSURE
(16 BAR) W/ CONNECTOR
GAUGE, WATER PRESSURE
(6 BAR) W/ CONNECTOR
MOD. A-2 AUTO AIR
MAINTENANCE DEVICE, 10PSI
MODEL B MANUAL
EMERGENCY STATION
MODEL LP
DRY VALVE ACTUATOR
NAMEPLATE,
SINGLE INTERLOCK
NIPPLE, STEEL, 1" X 3-1/2"
NIPPLE, STEEL, 1" X 6"
NIPPLE, STEEL, 1" X CLOSE
NIPPLE, STEEL, 1/2" X 1-1/2"
NIPPLE, STEEL, 1/2" X 2-1/2"
NIPPLE, STEEL, 1/2" X 3-1/2"
NIPPLE, STEEL, 1/2" X 2"
NIPPLE, STEEL, 1/2" X 3"
NIPPLE, STEEL, 1/2" X 8"
NIPPLE, STEEL, 1/4" X 1-1/2"
NO
REQ'D
16103060024
1
4
1
1
2
1
1
1
1
1
4
1
1
1
1
1
1
2
1
2
2
1
1
1
1
1
1
1
17
1
1
2
1
1
21
ITEM
NO.
3798543225
3898543244
3998543220
4098543243
4198543227
4298543208
4398543238
4498543215
4598543233
4698543232
4798543279
4899080002
4998750003
5098604406
5198614403
5298614401
5398681630
5478650201
5598727607
5696556922
5796606627
5896606607
5998761649
6098761651
6196606608
6296606612
6396606601
6489141112
6598815204
6698815200
6798815201
6898815202
6998840160
7098840101
7198840100
7278653100
7398840110
7498840144
7598840145
7698840181
7798840171
786871020010
796871020000
8098840193
8196686722
8296686756
PART
NUMBER
DESCRIPTION
NIPPLE, STEEL, 1/4" X 2-1/2"
NIPPLE, STEEL, 1/4" X 2"
NIPPLE, STEEL, 1/4" X 3"
NIPPLE, STEEL, 1/4" X 4"
NIPPLE, STEEL, 1/4" X CLOSE
NIPPLE, STEEL, 2" X 3"
NIPPLE, STEEL, 2" X CLOSE
NIPPLE, STEEL, 3/4" X 1-1/2"
NIPPLE, STEEL, 3/4" X 2-1/2"
NIPPLE, STEEL, 3/4" X 2"
NIPPLE, STEEL, 3/4" X CLOSE
PAD-ADHESIVE
PIPE CROSS, 1/2"
PLUG, SQ. HD., 1/2"
PLUG, SQ. HD., 1/4"
PLUG, SQ. HD., 3/4"
REGULATOR, AIR LINE
STRAINER, 1/2" NPT
STRAINER, 1/4"
SWITCH, PRESSURE,
BAILEY & MACKEY
TEE, GLVN, 2 X 2 X 1
TEE, GLVN., 1/2 X 1/2 X 1/4
TEE, GLVN., 1/2 X 1/4 X 1/2
TEE, GLVN., 1/2"
TEE, GLVN., 1/4 X 1/4 X 1/4
TEE, GLVN., 3/4 X 1/2 X 1/2
TEE, GLVN., 3/4"
TIE, RETAINING
UNION, "O" RING SEAL, 1/2"
UNION, 1/2", IRON, G.J., GALV.
UNION, 1/4", IRON, G.J., GALV.
UNION, 3/4", IRON, G.J., GALV.
VALVE, 3-WAY, 1/4"
VALVE, ANGLE, 1/4"
VALVE, ANGLE, 2"
VALVE, BALL DRIP, 1/2"
VALVE, BALL, 1/4"
VALVE, CHECK GAUGE
VALVE, CHECK, 1"
VALVE, CHECK, 1/2"
VALVE, GLOBE, 1/2"
VALVE, SOLENOID ASCO
VALVE, SOLENOID SKINNER
VALVE, SPRING CHECK, 1/4"
TUBING, COPPER,
3/8" O.D. X 2 FT
TUBING,PVC,3/8"I.D.x6FT
NO
REQ'D
1
1
2
1
1
2
1
1
1
1
3
1
2
1
5
3
1
1
1
1
1
1
2
2
3
1
2
3
1
2
3
1
4
1
1
1
1
2
1
1
1
1
1
2
1
1
3.
Fig. 3
System Operation
To fully operate a Reliable Single Interlock Preaction System, two independent events must coexist beforewater flow
will occur.One electrical detector (two detectors in a
cross-zoned system) must activate and a sprinkler head
must open. Operation of either one of these items will only
cause an alarm to annunciate, but will not cause water to
discharge from the sprinkler system piping.
When set correctly for service, the Model DDX Deluge
Valve is hydraulically established to withhold the supply wa
ter from the sprinkler system piping. The Reliable Model
DDX Deluge Valve is shown in both closed and open posi
tions in Fig.1. In the closed position, the supply pressure
acts on the underside of the clapper and also on the push
rod through the push rod chamber’s inlet restriction. The re
sultant force due to the supply pressure acting on the push
rod is multiplied by the mechanical advantage of the lever
and is more than sufficient to hold the clapper closed
against normal supply pressure surges.
When a fire is detected, the energized solenoid valves vent
the air from the Model LP Dry Valve Actuator (see Fig. 8),
which in turn vents the push rod chamber to atmosphere
through the chamber’s outlet. Since the pressure cannot be
replenished through the inlet restriction as rapidly as it is
vented, the pushrod chamber pressure falls instanta
neously. When the pushrod chamber pressure approaches
approximately one-third of the supply pressure, the upward
force of the supply pressure acting beneath the clapper
overcomes the lever-applied force thereby opening the
clapper.
Once the clapper has opened, the lever acts as a
latch, preventing the clapper from returning to the
closed position. Water from the supply flows through
the deluge valve into the system piping. Water also
flows through the deluge valve alarm outlet to the
alarm devices.
After system shutdown, resetting the Model DDX De
luge Valve is quite simple. Doing so only requires
pushing in and turning the reset knob at the rear of the
valve (see Fig.1). The external reset feature of the
Model DDX Deluge Valve provides a means for sim
ple, economical system testing, which is one essential
facet of a good maintenance program.
The external reset feature does not, however, elimi
nate another important facet of good maintenance,
namely, periodic cleaning and inspection of the inter
nal valve parts. In the event that water builds up inside
the valve due to condensate from the air supply sys
tem or water left inside from valve system testing, a
drain is available for venting. After closing the main
supply valve, a small valve over the drain cup can be
opened slightly until the water inside the valve body
and the main pipe column has drained. See the sec
tion titled “Draining Excess/Condensate Water From
System” in this bulletin for the detailed procedure.
The Model B Manual Emergency Station (see Fig. 3)
is also included in the trim set. It consists of an aluminum nameplate mechanically attached to a ball valve.
The valve handle in its OFF position is guarded
against accidental turning to the ON position (and
system discharge) by a nylon cable tie provided with
each trim kit. The cable tie is inserted, as shown in Fig.
3, after the system has been restored for operation.
The nylon cable tie is designed to allow, in case of an
emergency, forceful turning of the valve handle to the
ON position. As an alternative to the Model B Hydraulic Manual Emergency Station, the Model A Hydraulic
Manual Emergency Pull Box (see Reliable Bulletin
-
506) is also available and can be provided as an option.
-
Whenever ambient temperature conditions are high,
the water temperature in the Model DDX Deluge
Valve’s pushrod chamber could possibly increase,
-
thereby increasing the pressure in the chamber to val
ues exceeding the rated pressure of the system. In an
indoor installation where standard room temperatures
are exceeded, a pressure relief kit may be needed.
Pressure relief kit, P/N 6503050001, can be installed
into the pushrod chamber’s releasing line to limit the
pressure to 175 psi (12,1 bar).
-
-
-
-
-
-
-
-
6.
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.