Reliable RFC30, RFC30LL, RFC43, RFC43LL, RFC49 User Manual

...
Features
• cULus Listed as Residential Sprinklers
• Push-On cover plate installation
• Low water flow requirements
Product Description
Bulletin 006 May 2019
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
cULus Listed
Model RFC43 & RFC43LLModel RFC30 & RFC30LL
Model RFC30 sprinklers have a 165°F (74°C) temperature rated fusible-link operating element. Model RFC43, RFC49, RFC58, and RFC76 sprinklers are offered with either a 165°F (74°C) or 212°F (100°C) temperature rated fusible-link oper­ating element. Sprinklers with a 165°F (74°C) temperature
Model RFC49 & RFC49LL Model RFC58
rating are ordinary temperature classification and are listed for use with a 135°F (57°C) temperature rated cover plate. Sprinklers with a 212°F (100°C) temperature rating are inter­mediate temperature classification and are listed for use with a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC cover plate. Model RFC cover plates may be installed by ei­ther pushing or threading the cover plate into the sprinkler cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2” (13 mm) of cover plate adjust­ment. Model RFC58 and RFC76 sprinklers allow 3/4” (19 mm) of cover plate adjustment. Model RFC cover plates are avail-
Model RFC76
able in a variety of finishes as listed in Table H.
Sprinkler Model
Nominal K-Factor
gpm/psi
1/2
(l/min/bar
Max. Coverage Area
1/2
)
ft x ft (m x m)
Listings & Approvals
Sprinkler Identification
RFC30 3.0 (43) 14 x 14 (4.3 x 4.3) cULus RA0611
RFC30LL 3.0 (43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211
RFC43 4.3 (62) 20 x 20 (6.1 x 6.1) cULus RA0612
RFC43LL 4.3 (62) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3212
RFC49 4.9 (71) 20 x 20 (6.1 x 6.1) cULus RA0616
RFC49LL 4.9 (71) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3216
RFC58 5.8 (84) 20 x 20 (6.1 x 6.1) cULus RA0613
RFC76 7.6 (109) 20 x 20 (6.1 x 6.1) cULus RA0618
cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service. LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
Model RFC Cover Plate
Table A
Number (SIN)
www.reliablesprinkler.com
Model RFC30 & RFC30LL Residential Sprinklers
Technical Specifications
Style: Flat Concealed Pendent Threads: 1/2” NPT or ISO 7-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy
Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel
Cover Plate Finishes (See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler 135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap) Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC30LL only) Watermark Certified (RFC30LL only)
RFC30: SINRA0611
RFC30LL: SINRA3211
Bottom View
Model RFC30 & RFC30LL Sprinkler Components and Dimensions
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area
ft. x ft.
(m x m)
12 x 12
(3.6 x 3.6)
14 x 14
(4.3 x 4.3)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
(2)
Flow gpm
(l/min)
9
(34)
10
(38)
(1)
Pressure
psi
(bar)
9.0
(0.62)
11.0
(0.76)
Figure 1
Table B
Bulletin 006 May 2019
www.reliablesprinkler.com
Page 2 of 8
Model RFC43 & RFC43LL Residential Sprinklers
Technical Specifications
Style: Flat Concealed Pendent Threads: 1/2” NPT or ISO 7-1R1/2 Nominal K-Factor: 4.3 (62 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy
Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
Ordinary: 165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate: 212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap) Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC43LL only) Watermark Certified (RFC43LL only)
RFC43: SINRA0612
RFC43LL: SINRA3212
Bottom View
Model RFC43 & RFC43LL Sprinkler Components and Dimensions
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area
(2)
ft. x ft.
(m x m)
15 x 15
(4.6 x 4.6)
16 x 16
(4.9 x 4.9)
18 x 18
(5.5 x 5.5)
20 x 20
(6.1 x 6.1)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Ordinary Temperature Intermediate Temperature
Flow gpm
(l/min)
12
(45)
13
(49)
18
(68)
21
(79)
Pressure
psi
(bar)
7.8
(0.54)
9.1
(0.63)
17.5
(1.21)
23.8
(1.64)
(1)
Flow gpm
(l/min)
12
(45)
13
(49)
-- --
-- --
Figure 2
Table C
Pressure
psi
(bar)
7.8
(0.54)
9.1
(0.63)
Bulletin 006 May 2019
www.reliablesprinkler.com
Page 3 of 8
Loading...