![](/html/df/dfb5/dfb5dd8f201e8bf2f9c678b09732f924396d07d04933bbb9542f73e62614d70e/bg1.png)
Features
• cULus Listed as Residential Sprinklers
• Push-On cover plate installation
• Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in accordance with UL 1626. In addition, Model RFCLL Series
sprinklers are cULus Certified for Health Effects to NSF/ANSI
standard 61 Annex G (LL) and Australian WaterMark Certified
(WMCS).
Bulletin 006 May 2019
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
cULus Listed
Model RFC43 & RFC43LLModel RFC30 & RFC30LL
Model RFC30 sprinklers have a 165°F (74°C) temperature
rated fusible-link operating element. Model RFC43, RFC49,
RFC58, and RFC76 sprinklers are offered with either a 165°F
(74°C) or 212°F (100°C) temperature rated fusible-link operating element. Sprinklers with a 165°F (74°C) temperature
Model RFC49 & RFC49LL Model RFC58
rating are ordinary temperature classification and are listed
for use with a 135°F (57°C) temperature rated cover plate.
Sprinklers with a 212°F (100°C) temperature rating are intermediate temperature classification and are listed for use with
a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by either pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and
RFC49LL sprinklers allow 1/2” (13 mm) of cover plate adjustment. Model RFC58 and RFC76 sprinklers allow 3/4” (19 mm)
of cover plate adjustment. Model RFC cover plates are avail-
Model RFC76
able in a variety of finishes as listed in Table H.
Sprinkler Model
Nominal K-Factor
gpm/psi
1/2
(l/min/bar
Max. Coverage Area
1/2
)
ft x ft (m x m)
Listings &
Approvals
Sprinkler Identification
RFC30 3.0 (43) 14 x 14 (4.3 x 4.3) cULus RA0611
RFC30LL 3.0 (43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211
RFC43 4.3 (62) 20 x 20 (6.1 x 6.1) cULus RA0612
RFC43LL 4.3 (62) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3212
RFC49 4.9 (71) 20 x 20 (6.1 x 6.1) cULus RA0616
RFC49LL 4.9 (71) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3216
RFC58 5.8 (84) 20 x 20 (6.1 x 6.1) cULus RA0613
RFC76 7.6 (109) 20 x 20 (6.1 x 6.1) cULus RA0618
cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service.
LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
Model RFC Cover Plate
Table A
Number (SIN)
www.reliablesprinkler.com
![](/html/df/dfb5/dfb5dd8f201e8bf2f9c678b09732f924396d07d04933bbb9542f73e62614d70e/bg2.png)
Model RFC30 & RFC30LL Residential Sprinklers
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC30LL only)
Watermark Certified (RFC30LL only)
RFC30: SINRA0611
RFC30LL: SINRA3211
Bottom View
Model RFC30 & RFC30LL Sprinkler Components and Dimensions
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area
ft. x ft.
(m x m)
12 x 12
(3.6 x 3.6)
14 x 14
(4.3 x 4.3)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
(2)
Flow
gpm
(l/min)
9
(34)
10
(38)
(1)
Pressure
psi
(bar)
9.0
(0.62)
11.0
(0.76)
Figure 1
Table B
Bulletin 006
May 2019
www.reliablesprinkler.com
Page 2 of 8
![](/html/df/dfb5/dfb5dd8f201e8bf2f9c678b09732f924396d07d04933bbb9542f73e62614d70e/bg3.png)
Model RFC43 & RFC43LL Residential Sprinklers
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC43LL only)
Watermark Certified (RFC43LL only)
RFC43: SINRA0612
RFC43LL: SINRA3212
Bottom View
Model RFC43 & RFC43LL Sprinkler Components and Dimensions
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area
(2)
ft. x ft.
(m x m)
15 x 15
(4.6 x 4.6)
16 x 16
(4.9 x 4.9)
18 x 18
(5.5 x 5.5)
20 x 20
(6.1 x 6.1)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Ordinary Temperature Intermediate Temperature
Flow
gpm
(l/min)
12
(45)
13
(49)
18
(68)
21
(79)
Pressure
psi
(bar)
7.8
(0.54)
9.1
(0.63)
17.5
(1.21)
23.8
(1.64)
(1)
Flow
gpm
(l/min)
12
(45)
13
(49)
-- --
-- --
Figure 2
Table C
Pressure
psi
(bar)
7.8
(0.54)
9.1
(0.63)
Bulletin 006
May 2019
www.reliablesprinkler.com