Relay Engineering Services BTS Data Sheet

Relay Engineering Services Limited
Overview
Operation
Why Perform Automatic Testing?
Software Overview
System Concept
Specifications
Nominal V
Max I
24
100
48
100
110
100
220
50
www.relayeng.com
Power Systems Protection Test Equipment

BTS Battery Discharge Test Set

The BTS is an automatic battery discharge test set designed to enable unattended discharge tests to be performed on standby batteries. It is widely acknowledged that a capacity test as performed by a controlled const ant c urrent dis charge gives the best indication as to the health of a standby battery and its ability to perform to its spec i fication.

Tests all batteries from 24 to 240 V

Regulated constant current during entire test
Up to 100 A discharge current
Performs tests from 3 mins to 10 hours
Unattended operation
Non-volatile data logging voltmeter
10 second data record rate
Programmable alarm outputs
The BTS is essentially a microprocessor controlled solid-state electronic load bank together with a non-volatile data-logging voltmeter. The dis charge current is continually monitored and the load bank automatical ly adjusted so as to maint ain the discharge current constant.
A test is performed by entering on a PC the discharge current, discharge time, m inimum allowable batt ery voltage and the voltage measurement record rate. Alarm settings c an also be entered, the alarm outputs being connected into the local alarm scheme to notify the operator if attendanc e is necessary. Once the test has been initiated by the PC, the PC can be disconnected and the discharge unit will perform t he t est with no operator involvement. As the battery voltage falls during the discharge the unit adjust s the load on the battery such that the di scharge current is maintained constant. The disc harge continues until t he time lim it is reached or the battery voltage drops below that previously entered as the minimum. When the test has f inished the PC can be reconnected and the results, stored during the test in the discharge unit, downloaded to the PC for subsequent analysi s .
Compliance with quality management systems like ISO9000 requires documentary evidence that all essential plant and equipment (i.e. batt eries) are performing to specific ation. The BTS can facilitate this process by generating the required documentation. The simple-to-use results arc hiving software supplied with the BTS permits even technician-level staff to perform and automatically document a battery dis c harge test.
Alphanumeric and graphical pres ent ation of results
Full results archiving, di splay and printing facilities
Fully Automatic or Manual testing
Error and Trend analysis of test results
Results transfer to other Windows applicati ons
Test templates al l ows rapid test set up
Full traceability of resul ts to test set hardware, sof t ware
and calibration data
Full on line context sensit i ve hel p / operating manual
A free evaluation version of the BTS software can be downloaded
www.relayeng.com.
from

Discharge Ratings

Absolute Max Voltage 280 V Discharge Current Accuracy

0.5% or better regulation to set value
0.1 A Resolution

Discharge Time

3 minutes to 10 hours under software control

Contact Out

4x contact outputs, Rated 10 A @ 250 VAC / 1 A @ 120 VDC Individually programmable t o operat e/release at set battery/voltmeter voltages
Voltmeter #1 (Battery Terminal Voltage)

30, 150, and 300 Volt ranges - auto sel ected 10 second record rate, 0.5% bas i c accuracy.

Voltmeter #2 (Uncomm i t ted, floating)

30, 150, and 300 Volt ranges - user selected 10 second record rate, 0.5% bas i c accuracy.

Input Power

Fully auto universal input: 90 t o 260 V 45 to 65 Hz AC or DC 100 W, Electronic Active P ower Fact or Correc tion

Miscellaneous

Battery/Contact Out/ V ol tmeter connections are galvanically isolated from each other and chassis.

Protections

Multipoint temperature, overpower & out-of-regulation monitoring with software shutdown. Reverse polarity protection.

Interfaces

Isolated RS-232 interface Parallel interface for control from PC printer port 37-way expansion connector with 16 in+ 16 out TTL lines plus analog in and analog out.

Physical

510 x 270 x 520 mm, 28.5kg.
Environmental
0 to 45°C Operating Temperature CE Marked, Tested to EN50081-2 (emi ssions) & EN50082-2 (susceptibility)
Fax: 800-433-9971 E-mail: info@davis.com www.davis.com