Rehau VACUCLEAN 2000, VACUCLEAN 3000, VACUCLEAN 4000 Technical Information

dfsdfdsfdsf
REHAU-VACUCLEAN
The Central Vacuum Cleaner System
Technical information 885.600 Ex/e
Valid as from April 2005
Subject to technical modifications
Table of Contents
Safety recommendations and information on this document ............................................................................................. 5
1. Overview of REHAU-VACUCLEAN ............................................................................................................................ 7
1.1 System description ............................................................................................................................................................................7
1.2 Method of operation ..........................................................................................................................................................................8
1.3 Motor and performance .....................................................................................................................................................................8
2. Planning ................................................................................................................................................................... 9
2.1 Planning information ..........................................................................................................................................................................9
2.2 Planning stages .................................................................................................................................................................................9
3. Building types ........................................................................................................................................................ 11
4. Areas of use ........................................................................................................................................................... 13
4.1 Radio remote control system ...........................................................................................................................................................13
5. Installation and operation ...................................................................................................................................... 15
5.1 Safety recommendations .................................................................................................................................................................15
5.2 Suction socket .................................................................................................................................................................................16
5.3 Floor socket .....................................................................................................................................................................................19
5.4 Wall vacuum connection Vac-Pan ....................................................................................................................................................19
5.6 Central vacuum unit .........................................................................................................................................................................23
5.7 Connection to power supply ............................................................................................................................................................ 26
5.8 Repeater ..........................................................................................................................................................................................27
5.8.1 Programming ...................................................................................................................................................................................27
5.8.2 Help in case of faulty programming ..................................................................................................................................................28
5.9 Operation via control cable ..............................................................................................................................................................29
5.9.1 System components ........................................................................................................................................................................29
5.9.2 Installation information .....................................................................................................................................................................30
5.9.2.1 Control cable ...................................................................................................................................................................................30
5.9.2.2 Vacuum pipe ...................................................................................................................................................................................30
5.9.2.3 Suction socket .................................................................................................................................................................................32
5.9.2.4 Floor socket .....................................................................................................................................................................................33
5.9.2.5 Wall vacuum connection Vac-Pan ....................................................................................................................................................33
5.9.2.6 Connection to power supply ............................................................................................................................................................ 34
5.9.3 Block diagram .................................................................................................................................................................................35
5.10 Subsequent installation ....................................................................................................................................................................36
5.11 Information on operation ..................................................................................................................................................................36
5.12 Fire protection .................................................................................................................................................................................36
6. Troubleshooting ..................................................................................................................................................... 37
6.1 Eliminating malfunctions ...................................................................................................................................................................37
7. Service ................................................................................................................................................................... 39
7.1 Emptying the waste container ..........................................................................................................................................................39
7.2 Cleaning and replacing the cartridge filter ........................................................................................................................................39
7.3 Replacing the carbon brushes .........................................................................................................................................................40
7.4 Changing the battery of the radio sender unit ...................................................................................................................................40
7.5 Checking and cleaning the suction sockets and wall vacuum connection Vac-Pan ..........................................................................40
7.6 Information on disposal ....................................................................................................................................................................40
8. Technical specifications ........................................................................................................................................ 41
9. Acceptance / service report .................................................................................................................................. 43
Safety recommendations and information on this document
Intended use
The REHAU-VACUCLEAN central vacuum cleaner system may only be installed and operated in accordance with this technical information. Any other use is unintended and therefore impermissible.
General precautionary measures
Keep the work area clean and free of
impeding objects.
Provide sufficient lighting at the work area.
Keep children, house pets and
unauthorised persons away from tools and the installation sites. This is especially important in cases of renovation in inhabited areas.
Do not allow children near electronic
devices without supervision.
Use only the intended components for the
respective REHAU pipe system. Using components from other manufacturers or unsuitable tools for installation can lead to accidents and other dangerous situations.
Fire protection
Observe the applicable fire protection
regulations very carefully as well as the codes of building practice / building regulations that apply in each case, especially in relation to:
- Penetration through ceilings and walls.
- Rooms with special/greater requirements for preventative fire­protection measures (observe national regulations).
Personnel requirements
Allow only authorised and trained persons
to install our systems.
Work on electrical systems or pipe
sections may only be performed by persons trained and authorised for this purpose.
Work clothing
Wear protective glasses, suitable work
clothing, protective shoes, a protective helmet and, if you have long hair, a hairnet.
Do not wear loose clothing or jewellery, as
they can be caught by moving parts.
Wear a protective helmet when performing
installation work at head level or above your head.
When installing the system
Using a house's water drain pipes to double as exhaust air pipes is impermissible.
When shortening a pipe, maintain a safe
distance between the hand holding the object and the cutting tool.
Never put your hands near the area where
the tool is cutting or on moving parts.
When performing service, maintenance
and conversion work and when changing the installation site, always unplug the power plug of the tool and secure it against being switched on inadvertently.
When operating the system
Do not allow children to play with the
suction sockets.
Under no circumstances may liquids be
allowed to end up in the suction and exhaust air system.
Check the suction sockets regularly for
proper operation.
Keep small house pets away from the
suction sockets.
Notes on this technical information
Navigation
A detailed table of contents with hierarchical titles and the corresponding number of pages is found at the beginning of this technical information.
Pictograms and logos
Read the safety recommendations and
operating instructions carefully and completely for your own safety and for the safety of other people before starting the installation. Retain the operating instructions and keep them handy.
If you do not understand the safety
recommendations or individual installation regulations, or if they are unclear, contact your REHAU sales office.
Observe all national installation,
accident-prevention and safety regulations when installing piping systems and the notes in this technical information.
Areas of use not dealt with in this technical information (special applications) require consultation with our applications department.
Please contact your REHAU sales
office.
Safety recommendation
Legal note
Action to be performed
Important information
Information on the Internet
Advantages
Please check at regular intervals
whether a more recent version of this technical information is available for your own safety and to ensure correct usage of our products.
The date of issue of your technical information is always printed at the bottom right on the cover page (e.g. 3.04 for March 2004).
The current technical information is available from your REHAU sales office, specialist wholesaler as well as on the Internet as a download under:
www.REHAU.com
1. Overview of REHAU-VACUCLEAN
1.1
System description
The REHAU-VACUCLEAN central vacuum cleaner system consists of a central vacuum unit and the sound insulating RAUPIANO Plus pipe system laid in the building.
You can conveniently vacuum with the telescopic tube and the 6 m or 8 m suction hose without having to move a heavy appliance from room to room or over stairs. You simply insert the suction hose into the suction socket and switch on the central vacuum unit with the remote radio control system. The central vacuum unit starts powerfully drawing in air without any bothersome loud motor noises.
With the REHAU-VACUCLEAN central vacuum cleaner system, exhaust air no longer ends up in the room with you, as it is directed outside through filters. This is important for those with dust allergies and asthma, who would immediately notice the difference with common vacuuming methods.
The air full of debris is transported from the individual suction sockets to the central vacuum unit through the sound insulating RAUPIANO Plus pipe system.
This is installed in a lower room (e.g. cellar). Using a special filtering technique (cyclonic separation) and a downstream cartridge filter, the air sucked in is cleaned before being released outside.
Alternatively, a wall vacuum connection Vac­Pan can be installed instead of a suction socket for drawing in swept waste.
+ Easy handling, as just the suction hose
is moved
+ Strong and consistent suction
performance
+ Minimal noise generation
+ Diversion of microscopic dust into the
open
+ Smooth pipe interior
+ Maintenance-free, sound-insulating
RAUPIANO Plus pipe system
+ Resistant to abrasion
+ Low-pressure resistant
Fig. 1-1: REHAU-VACUCLEAN in a single-family dwelling
1.2
Method of operation
Working with the suction hose
Fig. 1-2: Connecting suction hose
Attach hose with telescopic tube and
nozzle to the suction socket (see Fig. 1-2).
Switch on central vacuum unit with the
"ON" button of the radio sender unit.
After vacuuming, switch off central
vacuum unit with the "OFF" button of the radio sender unit.
Do not switch on the central vacuum
unit until the suction hose is connected to the suction socket or the wall vacuum connection Vac-Pan is open.
Switch off the central vacuum unit
before the suction hose is removed from the suction socket or the wall vacuum connection Vac-Pan is closed.
For safety reasons, the central vacuum unit switches off automatically after 15 minutes of operation.
Switch on the central vacuum unit
again with the "ON" button of the radio sender unit.
Working with the wall vacuum connection Vac-Pan
Fig. 1-3: Wall vacuum connection
Vac-Pan
Open Vac-Pan.
Switch on central vacuum unit with the
"ON" button of the radio sender unit.
Sweep waste to be sucked up into the
Vac-Pan.
Switch off central vacuum unit with the
"OFF" button of the radio sender unit.
Close Vac-Pan.
1.3
Motor and performance
High air watt capacity at high efficiency is a deciding factor for the suction performance at the nozzle of the REHAU-VACUCLEAN central vacuum cleaner system.
The motors of the central vacuum unit from REHAU offer the best output and advantages in comparison to many of our competitors:
Air data for REHAU vacuum units in comparison to our competitors
Fig. 1-4: Air data for REHAU vacuum units in comparison to our competitors
REHAU
Competitors
η Efficiency
Volumetric flow
Do not switch on the vacuum unit if the
wall vacuum connection Vac-Pan is closed.
If the central vacuum unit is not
connected at the lowest point of the system, wait approx. 10 seconds after vacuuming for the vacuumed debris to be fully sucked up.
+ High-quality ball bearings
+ Automatic switch-off carbon brushes
+ High endurance
+ Electronic soft start-up
+ Thermal cut-outs prevent overheating
+ Long service life
+ Millions in use today
V
2. Planning
2.1
Planning information
Warning!
Risk of death!
Disregarding the fire-protection regulations and measures risks death and severe burns to users/tenants.
Observe fire-protection regulations and
building codes of practice/regulations.
It is not necessary to provide each room with a suction socket. The required number is determined during the planning phase.
The vacuum pipes may be mounted on or inside the wall.
Lay the pipe system as short and
straight as possible.
Install the suction sockets near doors
so as to cover several rooms. This installation location also ensures that the suction sockets are not blocked by furniture.
For garages, install suction sockets
near the garage door so that you can clean your car comfortably outside the garage.
Take an under-roof floor which can be
finished into account during planning and execution.
2.2
Planning stages
1. Acquire correct-scale ground plot diagrams of the building (scale 1:100).
Fig. 2-1: Drawing ranges
2. Draw the ranges (green lines) on the ground plot diagrams (see Fig. 2-1):
- Determine the working radius: For this
purpose, deduct 1 m from the length of the suction hose. Length of the suction hose: 6 m for Item No. 242483-001, 8 m for Item No. 242473-001.
- Draw the working radius from the outer
corners of the ground plot with the compass.
Fig. 2-2: Providing suction sockets
3. Provide suction sockets in the overlap areas (shaded green) (see Fig. 2-2):
- If two circles overlap: Install a suction
socket in each overlap area. For optimal use of the working radius of the suction hose: Select the final position of the suction sockets in such a way that the non-shaded areas are also covered with the suction hose.
- If all the circles in a common area
overlap, e.g. in small flats, a single suction socket is sufficient for each flat: Provide a suction socket in this area.
- If no overlap areas arise when planning
for larger structures: Provide additional suction sockets.
Fig. 2-3: Drawing working radius
4. Draw the working radius from the planned suction socket as a checking measure (see Fig. 2-3):
- Check whether all areas to be cleaned
are within the working radii.
- Check whether partition walls limit the
working radius.
5. Determine the installation site of the central vacuum unit:
- Always install the central vacuum unit
toward the bottom of the building.
- If suction occurs against the pull of
gravity in sections of the suction pipes: Comply with the usage limitations (see Chap. 4, Page 13).
6. Determine the design length to select the unit type:
- The design length corresponds to the
pipeline length from the central vacuum unit to the furthest suction socket plus the length of the exhaust air pipe.
- Take the following equivalent lengths
into account with the design length for each redirection (bend, branch): 45° bend: 0.5 m 90° bend: 1.0 m Branch: 0.5 m
7. Select the central vacuum unit with the appropriate performance using the calculated design length (see Table 4-1, Page 13).
10
Example
Fig. 2-4: Example design length calculation
1 Suction socket
2Branch
3 Central vacuum unit
4 Exhaust gas silencer
Suction pipe: 15.0 m
Exhaust air pipe: 3.0 m
45° bend: 3.5 m (seven pc., 0.5 m equivalent length each)
90° bend: 1.0 m (one pc., 1.0 m equivalent length)
Branch: 0.5 m (one pc.)
Design length: 23.0 m
Result: Central vacuum unit type 2000
5 m
1 m
2 x 45°
1 x 45°
1 x 90°
7 m
2 m
2 x 45°
2 m
2 x 45°
1 m
3
4
1
2
11
3. Building types
Single family dwelling
We recommend implementing distribution in the cellar when planning the pipe system.
If there is no cellar under the house, the central vacuum unit can be installed in a storage room.
The floors of the house are passed through with vertical pipelines and connected up to the suction sockets.
Multi-family dwelling
A pipe system and separate vacuum unit is provided for each flat in a multi-family dwelling. All central vacuum units can be installed on the cellar level.
The exhaust air pipes of the individual central vacuum units can be combined into a larger collection pipe (e.g. DN 110) downstream of the sound absorber and directed outside (see Fig. 3-2).
If each individual flat contains a storage room with the possibility to install an exhaust air pipe to the outside, the central vacuum unit can also be installed here.
Fig. 3-1: Example for single-family dwelling
Fig. 3-2: Example for multi-family dwelling
AFlat 1
BFlat 2
12
Hotels, offices and commercial use
Two suction sockets can be employed simultaneously if unit type 4000 is used.
Cleaning zones
The building can be divided into so-called cleaning zones. A cleaning zone represents the area cleaned by one person.
The suction sockets of a cleaning zone are linked with a pipeline and connected to the desired unit type.
With unit type 4000, two cleaning zones can be connected (see Fig. 3-3).
Only one suction socket may be used at a time without a drop in performance with unit types 2000 and 3000.
Cleaning personnel
The number of required cleaning persons (R) is calculated from the average cleaning performance (A = 200 m
2
/h), the area to be
cleaned (F) and the specified cleaning time (t):
R = F / (t x A)
Select central vacuum units, taking into
account the distance to the furthest suction socket (design length) and the number of simultaneous users.
Example:
R = 800 / (1.5 x 200) = 2.7
Result:
Three cleaning persons are required.
Cleaning zones 1 and 2
(two simultaneous users)
Design length up to 80 m:
Unit type 4000
Cleaning zone 3 (one user)
Design length up to 80 m:
Unit type 2000
We recommend unit types 3000 and
4000 for commercial use (see Chap. 4, Page 13).
Office building: F = 800 m
2
Three cleaning zones: t = 1.5 h
A = 200 m
2
/h
Fig. 3-3: Example for office building
A Cleaning zone 1
B Cleaning zone 2
C Cleaning zone 3
D Unit type 4000 (cleaning zones 1 and 2)
E Unit type 2000 (cleaning zone 3)
13
4. Areas of use
4.1
Radio remote control system
Operation of the remote radio control system may be limited or fully impeded by cellar floors made of reinforced concrete or if radio­blocking materials (e.g. metal rib mesh, floor heating with metal pipes, metal wall or ceiling cladding) are used.
Remote radio control of the central vacuum unit can be made possible in buildings with radio-transmission limiting properties by carrying out the following measures:
Place the radio receiver unit of the central vacuum unit in the cellar hallway or stairway. A 5 m connection cable is available for this purpose.
If this is not possible or insufficient on the customer side, the remote radio control system can be supported by the use of a repeater (see Chap. 5.8, Page 27). The repeater can also be used when upgrading existing systems.
Working frequency: 434 MHz, rolling-code method
The REHAU-VACUCLEAN central vacuum cleaner system was designed for vacuuming household dust in buildings.
When using REHAU-VACUCLEAN in commercial buildings or multi-family dwellings with larger areas or several floors, please contact our applications department for consultation.
Observe all national regulations when
using the remote radio control system and the notes in this technical information.
Unit type Area of use Maximum
suction height
1)
[m]
1)
Vertical difference between central vacuum unit and lowest suction socket
Maximum design length [m]
Maximum number of suction sockets
Maximum living space
2) 3)
[m
2
]
2)
Orientation for selection of the unit type
3)
For more than three floors, including the cellar, or for floor sizes > 140 m2, you should plan on using one or more repeaters.
2000 Single-family dwellings and
flats
0 80 15 400
2.5 50
5.0 40
3000 Small multi-family dwellings
Pensions, offices, businesses
0 100 20 600
2.5 80
5.0 70
8.0 60
4000 One user in pensions,
small hotels, office buildings, places of business
0 120 25 800
2.5 90
5.0 80
8.0 70
4000 Two users in pensions,
small hotels, office buildings, places of business
0 80 25 800
2.5 50
Table 4-1: REHAU-VACUCLEAN areas of use
14
15
5. Installation and operation
5.1
Safety recommendations
When installing and servicing the system
Before attempting any work on the central vacuum unit, set the appliance switch to the "Off" position and then disconnect the mains plug from the socket of the radio receiver unit.
Never pull the mains plug from the socket of the radio receiver unit by the mains cable.
The electrical power circuit serving the earthed socket outlet must be protected by a fuse of sufficient rating and the socket outlet must have earthing contacts. Consult an electrician in this regard.
Only connect the central vacuum unit to a 220/230 V AC power supply.
Do not drag or carry the vacuum unit by the mains cable. The mains cable must not be pulled over sharp edges or corners and must always be prevented from contacting hot surfaces and liquid chemicals.
Do not carry out any modifications to the central vacuum units.
When operating the system
The system is only to be used for purposes described in these technical specifications.
- Use only for cleaning up dry
substances.
- Do not use the system for cleaning up
caustic or solvent-based substances or substances that present a health risk.
- Acetone, acids and solvents may attack
the central vacuum unit and pipelines.
- Do not use the system for cleaning up
water.
- Do not use the system for extracting
kitchen vapours.
Risk of injury to eyes and ears!
- Do not hold nozzles or pipes near your
head when the central vacuum unit is switched on.
- Do not vacuum people's clothing or
animal fur.
- Do not allow children to play near the
suction sockets.
Do not allow children to operate the vacuum cleaner system.
Risk of electric shock!
- Do not use the REHAU-VACUCLEAN
on wet surfaces.
- Never touch the mains plug, mains
cable or the central vacuum unit with wet hands or with wet cleaning cloths.
- Do not use the system for cleaning up
photocopier toner, printer toner or soot. Toner and soot may be electrically conductive.
Explosion and fire hazard!
- Do not use the system for cleaning up lit
cigarettes, hot ash, lit matches or similar materials.
- Do not use the system for cleaning up
flammable or combustible liquids, such as petrol, solvents or heating oil. The swirling action caused by the suction air may produce explosive mixtures.
- Do not operate the central vacuum unit
in rooms in which inflammable substances are stored or gases have built up.
Do not start the system if:
- the power supply cable is damaged or
- The central vacuum unit shows visible
damage.
Do not insert any objects into the suction sockets.
- Do not use suction sockets if they are
blocked.
- Keep openings free of dust, fluff, hair
and anything that may cause leakage and affect the flow of air.
Only operate the central vacuum unit with the standard-fitted cartridge filters.
- Before use, check that the cartridge
filter is properly seated.
Ensure that nobody is able to trip over the long suction hose.
- Exercise particular care when cleaning
stairs.
Do not twist or kink the suction hose. Pay particular attention to furniture edges, doors and radiators.
Damage to the central vacuum unit, accessories or mains cable must only be repaired by authorised customer service. Only use genuine replacement parts.
Protect the system from the effects of weather, moisture and heat sources.
Unplug mains plug:
- if malfunctions occur while using the
system
- before carrying out any cleaning or
servicing work on the system
- when changing the filter
Observe the provisions contained in
the regulations for the prevention of accidents, VDE provisions and the provisions issued by the employers' liability insurance association, the applicable code of building practice and the national building regulations.
Observe the applicable fire-protection
regulations very carefully, especially in regard to:
- Penetration through ceilings and walls.
- Rooms with special/greater requirements for preventative fire­protection measures (observe national regulations)
16
5.2
Suction socket
Install suction sockets at the same height
as the electrical outlets for a pleasing appearance.
Install suction socket connecting bend
DN 50 90° (Item No.: 243558-002, minimum installation depth is approx. 90 mm (see Fig. 5-1)) with the sleeve flush with the masonry.
Fig. 5-1: Suction socket connecting bend
Pull the suction socket adapter (black
rubber nipple, Item No. 243578-001) out of the suction socket connecting bend.
Attach suction socket connecting bend
onto the back of the mounting frame (Item No. 243352-001) in such a way that the holding plate runs in the groove of the bend.
Insert the pointed end of the connecting
bend into the sleeve of the suction pipe running in the wall slot.
Secure mounting frame vertically in the
wall.
Reinsert suction socket adapter.
Fig. 5-2: Installed mounting frame
Fig. 5-3: Mounting frame with plaster
cover
In order to plaster, attach the plaster cover
(Item No.: 242767-001) (see Fig. 5-3).
To remove the plaster cover, insert a
narrow screwdriver into the slot, press the clip toward the central bridge and pull off plaster cover.
Apply a sliding agent to insertion end of
suction socket (Item No. 128933-002) and press into the suction socket adapter.
Screw in and tighten socket at mounting
frame (Cover opening faces upward or downward).
Fig. 5-4: Fully installed suction socket
The alignment of the suction socket is defined by the vertical mounting of the mounting frame.
The opening direction of the suction socket cover is determined by the installation direction of the mounting frame (see mounting instructions of the mounting frame (Brochure No. 00F2075 d,e,f)).
17
Installation in solid walls
Install suction socket approx. 30 cm above
the finished floor.
Fig. 5-5: Installation in solid walls
1Solid wall
2Plaster
3 Mounting frame
4 Suction socket adapter
5 Suction socket
6 Suction socket connecting bend
DN 50 90° with suction socket adapter
1
min. 95
max. 20
min. 10
2
3
4
50
5
6
18
Installation in lightweight walls
Cladding with chip boards and gypsum plates
Install suction socket approx. 30 cm above
the finished floor.
Fig. 5-6: Mounting in lightweight walls, variation 1
Cladding with chip boards or gypsum plates
Fig. 5-7: Mounting in lightweight walls, variation 2
1 Lightweight wall
2Chip board
3Gypsum plate
4 Mounting frame
5 Suction socket adapter
6 Suction socket
7 Suction socket connecting bend
DN 50 90° with suction socket adapter
1
max. 20
min. 10
2
3
5
50
6
7
4
min. 95
1 Lightweight wall
2 Chip board or gypsum plate
3 Mounting frame
4 Suction socket adapter
5 Suction socket
6 Suction socket connecting bend
DN 50 90° with suction socket adapter
1
min. 95
max. 20
min. 10
2
3
4
50
5
6
19
5.3
Floor socket
Install floor socket in such a way that it is
not blocked by the planned furniture arrangement.
We recommend installation near a door.
Make an opening with a 70 mm diameter
in the floor.
Drill holes for the mounting screws of the
socket and insert plugs.
Lay and secure vacuum pipe in such a way
that the sleeve ends approx. 15 – 20 mm under the finished floor.
Close pipe opening, e.g. with a sleeve
plug, to protect from soiling.
Replace O-ring with suction socket
adapter (black rubber nipple, Item No. 243578-001).
After laying the floor covering, arrange it at
the installation site in such a way that the floor socket fully covers the hole.
Screw floor socket to the floor.
5.4
Wall vacuum connection Vac-Pan
The wall vacuum connection Vac-Pan (Item No. 243582-001) is used to suck up swept waste, e.g. in a kitchen. Installation is best in the baseboard of the kitchenette or in stud­frame walls.
When connecting the pipeline from the front:
Make an opening with a width = 165 mm,
and height = 95 mm for the vacuum pipe and use the accompanying cover blind (see Fig. 5-8).
Fig. 5-8: Connection of vacuum pipe
(with access from the front)
Position Vac-Pan.
Attach accompanying pipe bend, align it
and fit it to the pipeline.
Screw in Vac-Pan with cover blind at the
installation site (see Fig. 5-8).
Fig. 5-9: Installation from the front
When connecting the pipeline from the rear:
If the Vac-Pan is accessible from the rear when installed, an opening with a width = 165 mm and a height = 40 mm is sufficient.
The separate cover blind is not installed (see Fig. 5-10).
Fig. 5-10: Connection of vacuum pipe
(with access from the rear)
Position Vac-Pan.
Attach accompanying pipe bend, align it
and fit it to the pipeline.
Screw in Vac-Pan at the installation site
(see Fig. 5-10).
Fig. 5-11: Installation from the rear
Information on operation
To use the Vac-Pan, open the suction flap,
start the central vacuum unit with the radio sender unit and sweep the debris into the opening.
After using the Vac-Pan, close the suction
flap again and switch off the central vacuum unit via the radio sender unit.
Cement suction pipe into unfinished
floor or (if sufficient insulation thickness is available) lay in the insulation between the screed and the unfinished floor (see Chap. 5.5, Page 20).
Ensure that other pipe systems, e.g.
floor heating, are not impaired here.
20
5.5
Vacuum pipe
Laying pipes in adjacent rooms (e.g. cellar, garage) can be done via mounting on the surface under the ceiling or on the wall. Use a surface mounted suction socket for this.
Laying in screed is not permissible, as it can shorten due to the temperature and impact sound insulation. This could cause leaks at the transition point of the vacuum pipe from the screed to the masonry.
Laying in the outer insulation of a building is not permissible.
Install vacuum pipes DN 50 in wall slots of
at least 80 x 80 mm.
Take static requirements of the masonry,
especially for horizontal slots, into account during planning and execution.
Make wall slots in such a way that the
pipeline can be laid without being tensioned.
Before plastering in, surround pipes and
fittings on all sides with flexible materials such as corrugated cardboard, mineral or glass wool or commercial insulation tubes.
Protect pipes and fittings from the effects
of high temperatures with appropriate measures (insulation) at points where temperatures over 100 °C are reached due to external influences.
When laying the pipes and fittings, ensure
that the sleeves point against the direction of flow.
If installed in a suspended ceiling, check
whether it runs through an inhabited area. If this is the case, attach additional insulation.
Laying in concrete
The static condition may not be impaired by laying in concrete.
Ask a professional for advice before
starting the work.
If cementing in is permissible, secure the
pipe sections in such a way that a change in position is prevented during cementing.
To prevent penetration of cement slurry,
close the sleeve gaps with tape.
Close pipe openings.
The total weight of the cement may not be supported by the pipeline. We strongly advise being very careful when committing the pipes and fittings to a position, e.g. during cementing.
Make provisions for the dissipation of the
load in accordance with technical guidelines, e.g. spacers for reinforced steels, carrying boxes (folded sheet-metal edges), consoles etc.
Fig. 5-12: Installation diagram for laying in concrete
Warning!
Risk of death!
Disregarding the fire-protection regulations and measures risks death and severe burns to users/tenants.
Observe fire-protection regulations and
building codes of practice/regulations.
Observe the national regulations for
cut-outs and slots in the masonry.
REHAU recommend acoustically decoupling the line from the main structure with commercially available, moisture-protective impact-sound insulation (S > 4 mm).
Use joints for the transition into the wall
slot.
1Wall
2 Unfinished floor
3Insulation
4 Screed
5Carpet
5
4
3
2
5
123 100 ø70
1
21
Laying in the insulation
Lay suction and exhaust air pipes in
sufficiently thick insulation only.
Take settling characteristics into account.
Fig. 5-13: Installation diagram for laying in the insulation
Laying with building joints
Install suitable protective sheathes if
suction pipes pass through expansion and building joints.
Use joints for the transition:
The pipe sleeve rests on the expansion joint.
Fig. 5-14: Installation diagram for building joints
1Wall
2 Unfinished floor
3Insulation
4 Screed
5Carpet
5
4
3
2
5
123 100 ø70
1
At low temperatures, RAU-PP (mineral reinforced) becomes brittle like any other material and is thus more sensitive to impacts.
Avoid sudden strains at temperatures
under 0 °C.
1 Expansion joint
2 Vacuum pipe
3 Protective sheath
250 250
2
3
1
22
Other installation sites
The following are also suitable installation sites for suction and exhaust air pipes:
Unused chimney flues
Wall slots
Hollow-beam ceilings
Compensating ballasts
Spaces between layers of insulation
Elevated floors
Lightweight walls
Sweat water formation
Sweat water will form in the pipelines in non­stainless areas.
For this reason, provide all pipelines in the building in which sweat water will form with diffusion-proof insulation material.
Closed-cell materials with high water vapour­diffusion resistance are suitable for this. If open-cell of fibrous insulation materials are used, they must have an impermeable outer layer that is firmly attached to the insulation material.
Close off impact, groove, cut and end
points with a permanent seal.
Cut out insulation in the area of
attachment.
Pull insulation material over the attached
section and permanently seal it to the neighbouring insulation material with adhesive.
Installation information
Avoid narrow radii with changes in
direction; 90º bends only immediately behind the suction sockets.
Along the rest of the pipe, use two 45°
bends or 45° branches with less flow resistance (see Fig. 5-15).
Fig. 5-15: Installation example
Shorten pipes with a fine-tooth saw and a
mitre box for a right-angle cut.
Deburr the cut area and lightly bezel it to
get rid of edges which could catch debris, dust or threads.
In unheated rooms, insulate the pipelines
to prevent condensation water from forming.
Clean the O-ring, sleeve interior and
pointed end before connecting the pipes.
Apply a sliding agent to the pointed end to
facilitate installation.
When installing the vacuum pipes, ensure
that the sleeve is always pointing against the direction of flow.
To protect against penetrating debris, e.g.
when plastering, vacuum pipes laid under plaster are to be covered with a protective sheath or the sleeve gaps are to be closed with tape.
Install branches upward or to the side only,
so that debris in transit does not fall into the suction pipe below (see Fig. 5-16 and Fig. 5-17).
Fig. 5-16: Downward branch – installed
properly
Fig. 5-17: Downward branch – installed
incorrectly
If a suction socket must be installed below
the suction pipe, first install the branch horizontally and then lead it downward with two 45° bends (see Fig. 5-16).
A gradient need not be provided for horizontal sections of the suction pipe.
23
Implementing pipe cleaning openings
Install a branch instead of a 45° bend at
redirection points.
Provide additional outlet with a dummy
plug (see Fig. 5-18).
Remove dummy plug for cleaning.
Fig. 5-18: Cleaning opening
Connecting central vacuum unit to vacuum pipes
Connect vacuum pipes to the central
vacuum unit with RAUPIANO Plus double sleeve.
Securing vacuum pipes
Recommended spacing of pipe brackets:
for horizontal pipes: up to 0.5 m
for vertical pipes: up to 1.0 m
Secure vacuum pipes with fixed brackets
or guide brackets mounted to the wall with hanger bolts and plastic plugs.
Attach fixed brackets directly after the
sleeve.
For lengths of 1 m or longer, use guide
brackets as well.
5.6
Central vacuum unit
The central vacuum unit may be installed in a basement, storage room, utility room or garage. The site selected should ensure that vacuum and exhaust air pipes can be kept as short as possible.
Demands on the site of installation:
Lowest room in the entire system
Room temperature between 5 °C and
25 °C all year round
Ventilate room well, ventilation aperture to the outside at least 150 cm
2
Mains power connection
Sufficient space for emptying collected dirt
and servicing work
Observe the following when installing the radio receiver unit:
Allow a distance of at least 2 m between
central vacuum unit and radio receiver unit.
Do not install central vacuum unit and
radio receiver unit behind steel doors. If this cannot be avoided, the radio receiver unit must be installed at a site with favourable reception outside the room with the steel door.
Do not install radio receiver unit in the fuse
box or in the vicinity of other wireless control units.
Mounting central vacuum unit
Fig. 5-19: Mounting wall mount
Fit vibration dampers (2) in the wall mount
(1).
Fix wall mount (1) to the wall at a height of
approx. 1.6 m using screws (3), washers (4) and wall plugs (5) (see also mounting instructions (Brochure No. 00F2064).
Using screw and wall plug, fix spacer (6) at
a distance of x below the centre of the wall mount (1).
Suspend central vacuum unit on wall
mount so that it hangs straight.
Checking the cartridge filter
The central vacuum unit comes pre-fitted with the cartridge filter.
Check that the cartridge filter is firmly in
place before starting the system.
Warning!
Risk of death!
Ignitable/explosive gasses and mixtures can cause death, severe burns and damage to property.
Ensure that no ignitable/explosive
gasses or liquids are found in the room.
Do not install central vacuum unit in
explosion-hazardous areas.
Warning!
Risk of death!
Short circuits at the central vacuum unit resulting from high humidity can cause death, severe burns and damage to property.
Do not install central vacuum unit in
rooms exposed to moisture.
Central vacuum unit Model
Distance x
2000 and 3000 17 cm
4000 33 cm
Caution!
Damage to property!
Defective cartridge filters can cause damage to property.
Only operate the system with
undamaged cartridge filter.
Check cartridge filter regularly.
x
1
3
4
2
5
6
24
Connecting DN 50 suction pipe
Fig. 5-20: Connecting suction and exhaust
air pipe
Route suction pipe (RAUPIANO Plus
DN 50) to left or right-hand connection port.
Directly connect suction pipe to central
vacuum unit with a double socket (included).
Close off unused connection port with
dummy plug (included).
Connecting DN 75 exhaust air pipe
The exhaust air is discharged into the open via exhaust air silencers.
Keep pipe length as short as possible and, wherever possible, do not use any 87° bends.
Choose a suitable site for positioning the exhaust air vent that leads into the open (e.g. not on patios)
For unit types 2000 and 3000, route
exhaust air pipe (RAUPIANO Plus DN 75) to the exhaust air port on the central vacuum unit (see Fig. 5-23).
For unit type 4000, route two exhaust air
pipes (RAUPIANO Plus DN 75) to the exhaust air port on the central vacuum unit (see Fig. 5-24).
Install an exhaust air silencer in each
exhaust air pipe between the central vacuum unit and the wall duct (see Fig. 5-23 and Fig. 5-24).
For unit types 2000 and 3000, connect the
exhaust air pipe (DN 75) to the wall duct (DN 110) via an adapter (see Fig. 5-21).
For unit type 4000, connect both exhaust
air pipes (DN 75) to the wall duct (DN 110) via a connector (see Fig. 5-22).
Fit an external air vent to the side of the
wall duct that leads into the open.
Fig. 5-21: Wall duct for
unit types 2000 and 3000
1 External air vent
Fig. 5-22: Wall duct for
unit type 4000
1 External air vent
If two riser pipes are used, you can connect the suction pipes to the left and right-hand connection ports.
DN 50
DN 75
Caution!
Damage to property!
Backup of exhaust air in the central vacuum unit can cause damage to property.
Install exhaust air pipes with a gradient
of at least 2% to the external air vent.
DN 75
DN 110
1
DN 75
DN 75
DN 110
1
25
Fig. 5-23: Mounting example showing central vacuum unit types 2000 and 3000
Fig. 5-24: Mounting example showing central vacuum unit type 4000
A Recommended spacing
A Recommended spacing
A= 1.8 m
min. 2 m – max. 5 m
max. 10 m
2 %
2 %
A= 1.8 m
min. 2 m – max. 5 m
max. 10 m
2 %
26
5.7
Connection to power supply
The central vacuum unit is controlled by a radio receiver unit that is plugged into an earthed socket outlet.
Program the radio sender unit in the radio receiver unit
Plug radio receiver unit into the earthed
socket outlet (see Fig. 5-25).
Fig. 5-25: Plugging in radio receiver unit
Hold radio sender unit against the dark
rear section of the radio receiver unit enclosure (see Fig. 5-26).
Press one of the two send buttons on the
radio sender unit and keep it pressed until the yellow LED lights up on the radio receiver unit.
Now remove the radio sender unit from the
radio receiver unit and press the same button once again.
The settings will be saved and the yellow LED will go out.
Fig. 5-26: Programming the radio sender
unit in the radio receiver unit
To program the radio receiver unit for
communication with further radio sender units, repeat the steps described above with each radio sender unit.
Connecting the central vacuum unit
Fig. 5-27: Appliance switch on the central
vacuum unit
IOn
0Off
Ensure that the central vacuum unit is
switched off at the appliance switch (see Fig. 5-27).
Connect the central vacuum unit's mains
plug to the radio receiver unit socket.
When the red LED lights up on the radio
receiver unit, press the "OFF" button on the radio sender unit.
The radio receiver unit interrupts the power supply for the central vacuum unit and the red LED goes out.
Switch on central vacuum unit at the
appliance switch.
To check whether the radio remote control
works, press the "ON" button on the radio sender unit.
The central vacuum unit starts.
The site at which the central vacuum unit is installed must be provided with an earthed socket outlet (230 V, 16 A Europe / 10 A CH) that is located at least 2 m but no further than 5 m from the central vacuum unit.
The earthed socket outlet with the radio receiver unit must be accessible at all times.
To avoid interference with the remote
radio control system: Keep a distance of at least 2 m between central vacuum unit and radio receiver unit.
The remote radio control system contained in the suction set (Item No.: 242333-001) or available as a system unit (radio receiver unit + radio sender unit, Item No.: 243532-001) are already programmed and can be installed straight away.
If transmission power is not sufficient in larger-type properties, we recommend using a repeater (see Chap. 5.8, Page 27).
27
5.8
Repeater
Unit description
The repeater extends the range of the remote radio control system.
Installation site
After programming the repeater is to be plugged into a socket within the area within which the remote radio control system still functions without the repeater (preferably about in the middle of the area).
Example
The radio receiver unit is positioned in the house cellar. The central vacuum unit can no longer be switched on and off using the radio sender unit as from the 2nd floor. The remote radio control only functions between the cellar and the 1st floor without a repeater. A repeater in to be plugged into a socket about in the middle of the area from the cellar to the 1st floor, for example in the ground floor.
5.8.1
Programming
Program the radio sender unit in the repeater
Plug the repeater into a socket near the
radio receiver unit.
Hold the radio sender against the repeater
housing so that it makes contact with it (see Fig. 5-28).
Fig. 5-28: Programming the radio sender
unit in the repeater
Press one of the two buttons on the radio
sender unit, and keep it pressed until the yellow LED lights up on the repeater.
Now remove the radio sender unit from the
repeater and press the same button once again.
The yellow LED at the repeater goes out. The radio sender unit is saved.
Repeat the steps described above in order
to program further radio sender units.
Remove the repeater from the socket.
Programming the repeater in the radio receiver unit and installing it
Plug the plug of an extension cable into a
socket near the radio receiver unit.
Hold the repeater against the housing of
the radio receiver unit so that it makes contact with it (see Fig. 5-29) and plug it into the extension cable in this position.
The yellow LED at the radio receiver unit lights up.
Fig. 5-29: Programming the repeater in the
radio receiver unit
Remove the repeater at least 10 cm from
the radio receiver unit, pull it out of the extension cable and plug it back into the extension cable immediately.
The yellow LED at the radio receiver unit goes out. The programming process has been completed.
Disconnect the repeater from the
extension cable and plug it into the selected socket (location with optimal radio reception, see "Installation site" on Page 27).
The central vacuum unit can now be started via the radio sender unit.
A maximum of 6 radio sender units can be connected to the repeater, i.e. programmed in the repeater.
When the 7th radio sender unit is programmed, the 6th radio sender unit is overwritten.
The following programming steps are required before the repeater is installed:
- Program the radio sender unit in the
repeater
- Program the repeater in the
radio receiver unit
Two valid signals must be received consecutively in order to program a radio sender unit.
If the second signal is not received within 30 seconds during programming, the programming process is aborted. This is signalled 3 seconds long by a rapidly flashing LED at the repeater. Programming has to be repeated.
Carry out the steps described below
within 30 seconds.
Otherwise the programming process is aborted. This is signalled 3 seconds long by a rapidly flashing LED at the radio receiver unit. Programming has to be repeated.
28
5.8.2
Help in case of faulty programming
If the remote radio control does not functions as desired, we recommend that you delete all the settings carried out at the repeater and at the radio receiver unit during the programming process and repeat programming.
Deleting the radio sender unit at the radio receiver unit
Hold the radio sender unit against the dark
rear section of the radio receiver unit enclosure so that it makes contact with it (see Fig. 5-30).
Press one of the two buttons on the radio
sender unit, and keep it pressed until the yellow LED lights up on the radio receiver unit and it goes out again after 5 seconds.
Remove the radio sender unit and release
the button.
The radio sender unit is now deleted, the central vacuum unit can no longer be switched on.
Fig. 5-30: Deleting the radio sender unit at
the radio receiver unit
Deleting the radio sender unit at the repeater
Procedure: see "Deleting the radio sender unit at the radio receiver unit" on Page 28 (however, read "repeater" instead of "radio receiver unit").
Deleting the repeater from the radio receiver unit
Plug the plug of the extension cable near
the radio receiver unit into a socket.
Hold the repeater against the radio
receiver unit so that it makes contact with it (see Fig. 5-29) and plug it into the extension cable in this position.
The yellow LED at the radio receiver unit lights up.
Remove the repeater from the radio
receiver unit.
After 30 seconds of continuous lighting the yellow LED at the radio receiver unit changes to rapidly flashing mode for approx. 3 seconds and then goes out.
The deleting process has been completed.
Disconnect the repeater from the
extension cable.
29
5.9
Operation via control cable
5.9.1
System components
It is imperative that the following components be used in order to ensure proper use.
The following specification applies for the operation of the system via control cable.
Article designation Item No. Information
VACUCLEAN suction socket 243302-002 Material: Aluminium
Colour: White, RAL 9003
VACUCLEAN surface-mounted housing 243362-003 Mounted completely
Colour: White
VACUCLEAN control cable 243472-001 2-core
Cross-section: 2 x 0.75 mm
2
Length: 15 m
VACUCLEAN control module 249900-002 Material: ABS
Colour: Grey
VACUCLEAN Basic suction set K 246290-001 Consists of:
Suction hose 8 meters
Hand tube with suction air regulation
Telescopic tube
Combination nozzle with protective attachment
Joint nozzle
Upholstery nozzle
Hose retainer
Control module
VACUCLEAN Basic set K 245577-001 For mounting in unfinished state (single-family dwelling)
Consists of:
3 suction sockets white, RAL 9003
3 plaster covers
3 mounting frames
10 RAUPIANO Plus bends DN 50 45°
1 external air vent
3 suction socket connecting bends DN 50 90°
(incl. Suction socket adapters)
Control cable
Table 5-1: Components for VACUCLEAN operation with control cable
30
5.9.2
Installation information
5.9.2.1
Control cable
The central vacuum unit is switched on and off via a control cable (that is laid parallel to the pipes). The control cable of the suction sockets is linked to the central vacuum unit by means of a parallel connection.
Let the control cable project approx.
20 cm at the mounting site of the suction socket.
Connect the control cable at the suction
socket. Connect with common lamp-wire connectors at branches and tape with insulating tape.
Fasten the control cable with at least
2 cable ties per meter of pipe or with adhesive tape.
At 24 V the control voltage lies within the low­voltage range. The control cable can therefore be laid by a layperson. REHAU nevertheless recommends that a qualified person be consulted.
5.9.2.2
Vacuum pipe
Laying pipes in adjacent rooms (e.g. cellar, garage) can be done via mounting on the surface under the ceiling or on the wall. Use a surface mounted suction socket for this.
Laying in screed is not permissible, as it can shorten due to the temperature and impact sound insulation. This could cause leaks at the transition point of the vacuum pipe from the screed to the masonry.
Laying in the outer insulation of a building is not permissible.
Install vacuum pipes DN 50 in wall slots of
at least 80 x 80 mm.
Warning!
Risk of death!
Disregarding the fire-protection regulations and measures risks death and severe burns to users/tenants.
Observe fire-protection regulations and
building codes of practice/regulations.
Observe the national regulations for
cut-outs and slots in the masonry.
Take static requirements of the masonry,
especially for horizontal slots, into account during planning and execution.
Make wall slots in such a way that the
pipeline can be laid without being tensioned.
Before plastering in, surround pipes and
fittings on all sides with flexible materials such as corrugated cardboard, mineral or glass wool or commercial insulation tubes.
Protect pipes and fittings from the effects
of high temperatures with appropriate measures (insulation) at points where temperatures over 100 °C are reached due to external influences.
When laying the pipes and fittings, ensure
that the sleeves point against the direction of flow.
If installed in a suspended ceiling, check
whether it runs through an inhabited area. If this is the case, attach additional insulation.
Laying in concrete
The static condition may not be impaired by laying in concrete.
Ask a professional for advice before
starting the work.
If cementing in is permissible, secure the
pipe sections in such a way that a change in position is prevented during cementing.
To prevent penetration of cement slurry,
close the sleeve gaps with tape.
Close pipe openings.
The total weight of the cement may not be supported by the pipeline. We strongly advise being very careful when committing the pipes and fittings to a position, e.g. during cementing.
Make provisions for the dissipation of the
load in accordance with technical guidelines, e.g. spacers for reinforced steels, carrying boxes (folded sheet-metal edges), consoles etc.
Fig. 5-31: Installation diagram for laying in concrete
1Wall
2 Control cable
3 Unfinished floor
4Insulation
5 Screed
6Carpet
REHAU recommend acoustically decoupling the line from the main structure with commercially available, moisture-protective impact-sound insulation (S > 4 mm).
Use joints for the transition into the wall
slot.
6
5
4
3
5
123 100 ø70
1
2
31
Laying in the insulation
Lay suction and exhaust air pipes in
sufficiently thick insulation only.
Take settling characteristics into account.
Laying with building joints
Install suitable protective sheathes if
suction pipes and control cables pass through expansion and building joints.
Use joints for the transition:
The pipe sleeve rests on the expansion joint.
If the cable does not lie in a separate cable
conduit, ensure permanent strain relief for the control cable by forming loops.
At low temperatures, RAU-PP (mineral reinforced) becomes brittle like any other material and is thus more sensitive to impacts.
Avoid sudden strains at temperatures
under 0 °C.
Fig. 5-32: Installation diagram for laying in the insulation
1Wall
2 Control cable
3 Unfinished floor
4Insulation
5 Screed
6Carpet
Fig. 5-33: Installation diagram for laying across building joints
1 Expansion joint
2 Control cable
3 Vacuum pipe
4 Protective sheath
6
5
4
3
5
123 100 70
1
2
250 250
3
4
1
2
32
5.9.2.3
Suction socket
Install suction sockets at the same height
as the electrical outlets for a pleasing appearance.
Fig. 5-34: Suction socket connecting bend
Pull the suction socket adapter (black
rubber nipple, Item No. 243578-001) out of the suction socket connecting bend.
Attach suction socket connecting bend
onto the back of the mounting frame (Item No. 243352-001) in such a way that the holding plate runs in the groove of the bend.
Insert the pointed end of the suction
connecting bend into the sleeve of the suction pipe running in the wall slot.
Secure mounting frame vertically in the
wall.
Reinsert suction socket adapter.
Fig. 5-35: Installed mounting frame and
control cable
Fig. 5-36: Mounting frame with plaster
cover
Let the control cable (Item No. 243472-
001) project approx. 20 cm (see Fig. 5-35).
In order to plaster, attach the plaster cover
(Item No.: 242767-001) (see Fig. 5-36), while laying the control cable into the cavity of the plaster cover.
To remove the plaster cover, insert a
narrow screwdriver into the slot, press the clip toward the central bridge and pull off plaster cover.
Connect the control cable at the suction
socket.
Apply a sliding agent to insertion end of
suction socket (Item No. 128933-002) and press into the suction socket adapter.
Screw in and tighten socket at mounting
frame (Cover opening faces upward or downward).
Press on the cover frame.
Fig. 5-37: Fully installed suction socket
The alignment of the suction socket is defined by the vertical mounting of the mounting frame.
The opening direction of the suction socket cover is determined by the installation direction of the mounting frame (see mounting instructions of the mounting frame (Brochure No. 00F2075 d,e,f)).
33
5.9.2.4
Floor socket
Install floor socket in such a way that it is
not blocked by the planned furniture arrangement.
We recommend installation near a door.
Make an opening with a 70 mm diameter
in the floor.
Drill holes for the mounting screws of the
socket and insert plugs.
Lay and secure vacuum pipe in such a way
that the sleeve ends approx. 15 – 20 mm under the finished floor.
Close pipe opening, e.g. with a sleeve
plug, to protect from soiling.
Replace O-ring with suction socket
adapter (black rubber nipple, Item No. 243578-001).
Install the control cable (Item No. 243472-
001) and let it project approx. 20 cm.
After laying the floor covering, arrange it at
the installation site in such a way that the floor socket fully covers the hole.
Connect the control cable to the suction
socket and tape the connection (e.g. lamp-wire connectors) with insulation tape.
Screw floor socket to the floor.
5.9.2.5
Wall vacuum connection Vac-Pan
The wall vacuum connection Vac-Pan (Item No. 243582-001) is used to suck up swept waste, e.g. in a kitchen. Installation is best in the baseboard of the kitchenette or in stud­frame walls.
When connecting the pipeline from the front:
Make an opening with a width = 165 mm,
and height = 95 mm for the vacuum pipe and use the enclosed cover blind (see Fig. 5-38).
Fig. 5-38: Connection of vacuum pipe
(with access from the front)
Connect the control cable.
Position Vac-Pan.
Attach accompanying pipe bend, align it
and fit it to the pipeline.
Screw in Vac-Pan with cover blind at the
installation site (see Fig. 5-38).
Fig. 5-39: Installation from the front
When connecting the pipeline from the rear:
If the Vac-Pan is accessible from the rear when installed, an opening with a width = 165 mm and a height = 40 mm is sufficient.
The separate cover blind is not installed (see Fig. 5-40).
Fig. 5-40: Connection of vacuum pipe
(with access from the rear)
Connect the control cable.
Position Vac-Pan.
Attach accompanying pipe bend, align it
and fit it to the pipeline.
Screw in Vac-Pan at the installation site
(see Fig. 5-40).
Fig. 5-41: Installation from the rear
Cement suction pipe into unfinished
floor or (if sufficient insulation thickness is available) lay in the insulation between the screed and the unfinished floor (see Chap. 5.9.2.2, Page 30).
Ensure that other pipe systems, e.g.
floor heating, are not impaired here.
Vac-Pan automatically starts the vacuum unit when the flap is opened and switches it off when the flap is closed.
34
5.9.2.6
Connection to power supply
The central vacuum unit is started via the control module (Item No. 249900-002) with contact plug. The control module is plugged into an earthed socket outlet.
Fig. 5-42: Appliance switch on the central
vacuum unit
IOn
0Off
Fig. 5-43: Plugging in the control module
Ensure that the central vacuum unit is
switched off at the appliance switch (see Fig. 5-42).
Connect the control cable to the contact
plug and fasten it with screws.
Plug the control module into the earthed
socket outlet (see Fig. 5-43).
Plug the contact plug into the control
module (bottom) and fastened it with screws.
Power the power plug of the central
vacuum unit into the control module.
Switch on central vacuum unit at the
appliance switch.
In order to start the suction process plug
the suction hose into a suction socket.
The location of the central vacuum unit must be equipped with an earthed socket outlet (230 V, 16 A Europe/10 A CH).
The earthed socket outlet with the control unit must be accessible at all times.
35
5.9.3
Block diagram
Fig. 5-44: Block diagram control cable
1 Cable connection, e.g. through lamp-wire
connectors
A Under-roof floor
2 Suction socket B Upper level
3 Control cable, 2-core C Ground floor
4 Control module D Cellar level
5 Central vacuum unit
36
5.10
Subsequent installation
A subsequent installation of REHAU­VACUCLEAN is possible, for example, using existing installation shafts for pipe extension. The pipes can also be faced with gypsum plaster boards, for example.
5.11
Information on operation
The system was designed for vacuuming household dust.
Vacuum dry surfaces only. Damp dust can stick to the pipes and filter and cause blockages.
If sand, cold ashes, shavings or other coarse debris is to be vacuumed up, preliminary separators (Ash-Pot, Item No.: 243282-001) must be used.
The central vacuum unit must always be able to suck up sufficient air for motor cooling.
The central vacuum unit is equi pped with a suction relief valve for safety purposes, i.e. to prevent excessive suction in the system.
The check light (LED) on the radio receiver unit may not illuminate.
Safety function: The central vacuum unit switches off automatically after 15 minutes of operation (not in case of operation via control cable). To restart the central vacuum unit, press the start button on the radio sender unit again.
If the radio receiver unit does not respond to a switching command, e.g. in niches and corners, change your position in the room and press the button of the radio sender unit again.
Larger-type properties may require the use of a repeater (see Chap. 5.8, Page 27).
5.12
Fire protection
Fire-protection measures may be necessary in conjunction with piping systems.
Observe the national regulations
regarding fire protection.
37
6. Troubleshooting
6.1
Eliminating malfunctions
Minor malfunctions can often be traced back to operating errors and can usually be eliminated by the user.
Warning!
Risk of death!
Energised unit parts can cause death and severe burns via electric shock.
Switch off the central vacuum unit and
pull the mains plug before performing maintenance.
Only clean central vacuum unit with a
dry cloth.
If the malfunction cannot be
eliminated, contact your dealer or the REHAU sales office directly.
Keep the information on the rating
plate handy here.
Malfunction Possible cause Remedy
Sudden interruption in operation The central vacuum unit was switched off
automatically after 15 minutes of operation by the safety function.
Press the start button of the radio sender
unit again.
Central vacuum unit switches off automatically, e.g. due to a blockage or overload.
Allow motor of the central vacuum unit to
cool down; remove clog if necessary, then switch on again.
Central vacuum unit does not start Central vacuum unit is not switched on. Switch on central vacuum unit.
Battery of radio sender unit empty. Replace battery (12 V, type A23).
Areas of non-reception. Change position in room.
Insufficient transmission power. Use a repeater (see Chap. 5.8, Page 27).
Radio receiver unit not connected. Connect radio receiver unit.
No signal at radio receiver unit. Program the radio sender unit again to the
radio receiver unit (see Chap. 5.7, Page 26).
Position radio receiver unit at least 2 m from
the central vacuum unit.
Sudden drop in suction Kink in hose. Undo kink.
Sucking in of air from somewhere else, e.g. through another opened suction socket.
Close other air source.
Cover of a suction socket not closed air-tight. Clean seal.
–or–
Replace suction socket
Suction socket blocked by coarse objects. Remove block.
Customer-side exhaust air vent blocked at the exterior wall, e.g. by vegetation.
Remove block.
Cartridge filter soiled. Clean cartridge filter.
Waste container full. Empty waste container.
Table 6-1: Malfunctions, causes and remedies
38
39
7. Service
7.1
Emptying the waste container
Switch off central vacuum unit and unplug
mains plug.
Hold waste container firmly.
Open both latch closures (see Fig. 7-1).
Fig. 7-1: Removing waste container
Remove and empty waste container.
Reattach waste container at housing and
secure it by closing the latch closures.
7.2
Cleaning and replacing the cartridge filter
Switch off central vacuum unit and unplug
mains plug.
Open latch closures on the central vacuum
unit, remove waste container and set it down below the central vacuum unit (see Fig. 7-1).
Release clamping lever at cartridge filter
and fold securing clamp forward (see Fig. 7-2).
Fig. 7-2: Installing and removing cartridge
filter
Pull cartridge filter downward at the
handle.
Insert cleaned or new cartridge filter in
such a way that the handle is aligned centrally horizontally.
Close securing clamp and lock clamping
lever.
Reattach emptied waste container at
housing and secure it by closing the latch closures.
Warning!
Risk of death!
Energised unit parts can cause death and severe burns via electric shock.
Switch off the central vacuum unit and
pull the mains plug before performing maintenance.
Only clean central vacuum unit with a
dry cloth.
The motor does not need to be lubricated due to its construction type.
Caution!
Damage to property!
Defective cartridge filters can cause damage to property.
Only operate the system with
undamaged cartridge filter.
Check cartridge filter regularly.
REHAU recommend emptying the waste container for hygienic reasons when checking the cartridge filter.
Due to the cyclone principle, the cartridge filter need only be cleaned twice annually or after 150 operating hours.
Replace the cartridge filter every two to
three years or after 300 operating hours.
40
7.3
Replacing the carbon brushes
Switch off central vacuum unit and unplug
mains plug.
Loosen both Allen screws of the noise-
insulation hood.
Remove noise-insulation hood.
Fig. 7-3: Removing housing
Remove upper protective hood by
loosening the three Phillips-head screws (see Fig. 7-3).
Fig. 7-4: Replacing carbon brushes
Pull off cable lug.
Pull out carbon brushes from the side (see
Fig. 7-4).
Change and secure carbon brushes.
Installation is carried out in reverse order.
7.4
Changing the battery of the radio sender unit
Slightly lift battery compartment cover and
push it away.
Remove used battery and insert new
battery, paying attention to correct polarity.
Dispose of used battery in an
environmentally conscious manner, e.g. via your dealer or public collection facilities.
7.5
Checking and cleaning the suction sockets and wall vacuum connection Vac-Pan
Regularly remove dirt which clings inside
the suction sockets and Vac-Pan.
Check suction sockets for damage and
have damaged suction sockets replaced.
7.6
Information on disposal
Turn over used radio receiver units, radio
sender units and batteries separately to a public collection location or your dealer.
Cut off all mains cables to prevent misuse.
Dispose of the other system components
and the packaging material with a disposal company in accordance with the applicable regulations.
Warning!
Risk of death!
Energised unit parts can cause death and severe burns via electric shock.
Allow only an electrician to perform
service.
Check carbon brushes once a year
and replace if heavy wear is evident.
Change the battery (12 V, type A 23) at
regular intervals to ensure sufficient transmission power.
41
8. Technical specifications
Unit type
Item No.
2000
243502-001
3000
243512-001
4000
243522-001
Number of simultaneous users 1 1 2
Max. recommended No. of suction sockets 15 20 25
Max. design length [m] 80 100 120 (one user)
80 (two users)
Remote radio control system, 434 MHz, rolling-code method
Yes Yes Yes
Maximum wattage
1)
[W] 1350 1600 2 x 1600
Operating voltage [V] 220/240 220/240 220/240
Frequency [Hz] 50 50 50
Appliance fuse [A] 10 (preferably 16) 10 (preferably 16) 16 (individual)
Protection class I I I
Marking KEMA, GS, CE KEMA, GS, CE KEMA, GS, CE
Air watts
1)
530 580 2 x 580
Maximum vacuum1) [kPa]
1)
Motor values (average values from three measurements) at 230 V measurement voltage without allowing for tolerances.
28 32 32
Maximum volumetric flow
1)
[m3/h] 220 240 2 x 240
Thermal cut-out Yes Yes Yes
Vacuum valve Yes Yes Yes
Running hours meter No Yes Yes
Cyclone filter Yes Yes Yes
Cartridge filter [cm2] 2500 2500 8000
Noise level (at 1 m distance) [dB(A)] 65 69 75
Dust collector volume [dm3] 30 45 45
Unit dimensions (D x W x H) [cm] 39 x 44 x 92 39 x 44 x 104 39 x 44 x 116
Packaging dimensions (D x W x H) [cm] 47 x 48.5 x 99 47 x 48.5 x 111 47 x 48.5 x 123
Recommended area of use
2)
2)
Vacuum cleaner type with suitable rating.
Flat / single-family dwelling Multi-family dwelling Small hotel
Small office building
Table 8-1: Technical specifications for REHAU-VACUCLEAN unit types 2000, 3000 and 4000
(all figures are approximations)
The figure given in "air watts" is the decisive criterion on which to assess the suction performance.
42
43
9. Acceptance / service report
Template for photocopying
REHAU-VACUCLEAN central vacuum cleaner system
Acceptance report
Service report
1. System details
Name of operator:
Street address:
Town/city/postcode:
Central vacuum cleaner type:  2000  3000  4000
Serial number:
System installed on:
2. System check and servicing
Check-list for central vacuum cleaner system
Check main switch for proper working order
Check proper functioning of system with remote control
Unplug the central vacuum cleaner unit at the mains plug before carrying out the following work.
Check and service the carbon brushes on vacuum cleaner motor
Check and clean cartridge filter
Check and, if necessary, empty the waste collector
Check-list for suction sockets
Check that suction sockets are free from residue
Check that suction socket covers close completely
Check-list for suction hose
Check that suction hose is not cracked
3. Deficiencies established and rectified:
Servicing conducted on:
Company stamp / customer service signature
Warning!
Risk of death!
Energised unit parts can cause death and severe burns via electric shock.
Switch off the central vacuum unit and
pull the mains plug before performing maintenance.
Only clean central vacuum unit with a
dry cloth.
When conducting servicing work, observe the instructions given in the latest Technical
Information, the regulations for the prevention of accidents, VDE provisions, the provisions issued by the employers' liability insurance association and the national regulations.
Check system in accordance with check-lists below.
Rectify any deficiencies established and record in Section 3.
Tick inspection box after completing inspection step if system is found to be in proper
working order.
Insofar as the intended application deviates from that described in this Technical Information brochure, the user must consult REHAU and must receive express written consent from REHAU before commencing this utilization. The user fails to do so, the sole responsibility for the utilization shall lie with the individual user. In this case, the application, use and processing of products are beyond our control. Should a case of liability arise, however, this shall be limited to the value of the goods delivered by us and used by you in all cases of damage. Claims arising from granted guarantees shall become invalid in the case of intended applications that are not described in the Technical Information brochures.
This document is protected by copyright. All rights based on this are reserved. No part of this publication may be translated, reproduced or transmitted in any form or by any similar means, electronic or mechanical, photocopying, recording or otherwise, or stored in a data retrieval system.
www.REHAU.com RAUNET@REHAU.com
AUS: Adelaide:
3 Lloyd St., St. Mary’s 5042, Tel.: 8/82 99 00 31  Brisbane: 27 Deakin Street, Brendale Queensland 4500, Tel.: 7/38 89 75 22  Melbourne: 9-11 Endeavour Way, Braeside Victoria 3195, Tel.: 3/9587 55 44 Perth: Unit 2/4 Brolo Court, O’Connor WA 6163, Tel.: 8/93 37 23 00 Sydney: 91 Derby Street, Silverwater New South Wales 2128, Tel.: 2/97 48 17 88 CDN:  Moncton: 327 Murray Road, Little Shemogue, New Brunswick E4M 3P3, Tel.: 506/5 3823 46
Montr
eal: 625 Lee Avenue, Baie d’Urfé, Quebec, H9X 3S3, Tel.: 5 14/4 5733 45 St. John’s: 13 Sagona Avenue, Donovan’s Industrial Park, Mt. Pearl, Newfoundland, A1N 4P8, Tel.: 7 09/7 47 39 09 Toronto: 1149 Pioneer Road, Burlington, Ontario, L7M 1K5, Tel.: 905/3 35 32 84 Vancouver: 26620 56th avenue, Unit # 102, Langley, BC, V4W 3X5, Tel.: (6 04) 6 26 46 66 W
innipeg: 11 Plymouth Street, Unit 100, Winnipeg, Manitoba, R2X 2V5, Tel.: 2 04/6 97 20 28 GB: Birmingham: Tameside Drive, Holford Way, Witton, Birmingham, B6 7AY, Tel.: 1 21/3 4423 00 Glasgow: Phoenix House, Phoenix Crescent, Strathclyde Business Park Bellshill, North Lanarkshire, ML4 3NJ, Tel.: 0 16 98/50 37 00 Manchester: Brinell Drive, Irlam, Manchester, M44 5BL, Tel.: 161/77 77-4 00 Slough: Waterside Drive, Langley, Slough, SL3 6EZ, Tel.: 1753/58 85-00
For the automotive sector, please contact the Ross-on-Wye Sales Office: Hill Court, Walford, Ross-on-Wye, Herefordshire HR9 5QN, Tel.: 1989/76-26 00 HK: Hongkong: 22/F, Silver Tech Tower, 26 Cheung Lee Street, Chai Wan, Tel.: 28 98 70 80 IRL: Dublin: 9 Saint John’s Court Business Park, Swords Road, Santry, Dublin 9, Tel.: 1/81 65 02-0 NZ: Auckland:
60b Cryers Road, East Tamaki, Auckland, Tel.: 9/2 72 82 24 SGP: Singapore:
1 King George’s Avenue, # 06-00 REHAU Building, Singapore 208557, Tel.: 63 92 60 06 USA:
Chicago: 901 S. Route 53, Suite H, Addison, Illinois 60101 Tel.: (6 30) 3 17 35 00  Dallas: 3224 Highway 67 East, Suite 205, Mesquite, Texas 75150, Tel.: 9 72/2 70 23 22 Detroit: 33533 West Twelve Mile Rd., Suite 305, Farmington Hills, Michigan 48331, Tel.: 2 48/8 48 91 00
Grand Rapids: 5075 Cascade Rd. S.E., Suite A, Grand Rapids, Michigan 49546, Tel.: 6 16/2 85 6867
Greensboro: 2606 Phoenix Drive, Suite 810, Greensboro, North Carolina 27406, Tel.: 3 36/852-20 23
Los Angeles: 1501 Railroad Street,
Corona, California 92880-2501, Tel.: 9 51/5 49 90 17
Minneapolis: 7710 Brooklyn Blvd. Suite 207, Brooklyn Park, Minnesota 55443, Tel.: 7 63/5 85 13 80 For European exporting companies and if there is no sales office in your country please contact: REHAU AG+Co, Export Sales Office, P.O. Box 30 29, 91018 Erlangen/Germany, Tel.: +49 (0) 91 31 92 50, Export.Sales.Office@REHAU.com
885.600 Ex/e 4.05
Loading...