Regulus RGC 120 User guide

Page 1
www.regulus.eu
RGC 120 and RGC 170
FLOOR STANDING HOT WATER STORAGE TANKS
RGC 120 and RGC 170
Installation and Operation Manual
RGC 120 and RGC 170
EN
Page 2
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
CONTENTS
1 Description ..................................................................................................................................... 3
1.1 Models ............................................................................................................................. 3
1.2 Tank protection ................................................................................................................. 3
1.3 Thermal insulation ............................................................................................................ 3
1.4 Connection points on the tank .......................................................................................... 3
1.5 Packaging ........................................................................................................................ 3
2 General Information ....................................................................................................................... 3
3 Operation ........................................................................................................................................ 3
4 Technical Data and Dimensions .................................................................................................... 4
5 Example of Assigning Connection Points .................................................................................... 8
6 Installation and Commissioning ................................................................................................... 10
6.1 Connection to heat sources ............................................................................................. 10
6.2 Installation of an electric heating element ........................................................................ 10
6.3 Connection to water mains .............................................................................................. 10
6.4 Electronic anode rod installation ...................................................................................... 10
6.5 Commissioning ................................................................................................................ 10
7 Maintenance, Replacement of Magnesium Anode Bar .............................................................. 11
8 Disposal .......................................................................................................................................... 11
9 Warranty ......................................................................................................................................... 11
Page 3
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
1 - Description
RGC 120 and RGC 170 Hot Water Storage Tanks (further “tank“) with one enamelled heat exchanger (e.g. for connecting a heat pump), permitting installation of an electric heating element. In order to reach proper working of the tank, it is necessary to design optimum hydraulics of the whole system, i.e. position of circulation pumps for heat sources and heating circuits, valves, non-return valves etc.
1.1 - Models
The tanks are available in volumes of 114 and 166 litres.
1.2 - Tank protection
Enamelled inner surface of the tank and coil heat exchanger guarantee a long service life. Enamel is done according to DIN 4753 standard. Further qualitative improvement is reached thanks to a magnesium anode installed inside the tank.
1.3 - Thermal insulation
The tanks come with an ecologic polyurethane foam insulation 54 and 58 mm thick. Its outer mantle is made of white hard plastic. The insulation is not detachable.
1.4 - Connection points on the tank
2 connections with G 3/4“ M, to heat exchanger circuit 2 connections with G 3/4“ M, for cold water inlet and hot water outlet 1 connection with G 3/4“ M, for recirculation 1 connection with G 5/4“ F, for a magnesium anode rod 1 sheath, 15 mm diam. 1 connection with G 1/2“ F, for thermometer 1 connection with G 6/4“ M, for an el. heating element 1 connection with G 1/2“ F, universal inlet/outlet
1.5 - Packaging
Tanks are delivered standing, each screwed to its pallet, packed in a cardboard box. It is forbidden to transport and/or store the tanks in a horizontal position.
2 - General Information
The appliance shall be installed by a qualied person according to valid rules and Manufacturer‘s Manual.
This manual is an integral and important part of the product and must be handed over to the User. Read carefully the instructions in this manual as they contain important information concerning safety, installation, operation and maintenance. Keep this manual for later reference.
Using the tank for other purposes than stated above is forbidden and the manufacturer accepts no responsibi lity for damage caused by improper or wrong use.
3 - Operation
This tank is designed for operation in pressure circuits. Hot water is heated in the integrated hot-water heat exchanger (heating coil) inside the tank from several possible heat sources like heat pumps or various kinds of hot-water boilers. An electric heating element can be installed into the tank for DHW backup heating. Hot water temperature should be kept between 60 and 65 °C. This temperature guarantees the best operation and at the same time, it prevents formation of Legionella bacteria.
3
Page 4
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
4 - Technical Data and Dimensions of Hot Water Storage Tanks
- RGC 120
Dimensions
pos. description
DHW heating
W1 cold water G 3/4ʺ M 1075
W2 hot water G 3/4ʺ M 1075
W3 recirculation G 3/4ʺ M 1075
Auxiliary heat source
E1
electric heating element for DHW G 6/4ʺ F 235
Control and safety
C1
sheath Ø 15 mm 990
T thermometer G 1/2ʺ F 740
Heat sources
X1
X2 return to heat source G 3/4ʺ M 1075
Other
U1
universal inlet/outlet G 1/2ʺ F 100
A1 magnesium anode rod G 5/4ʺ F 960
connection
G 3/4ʺ M 1075
height [mm]
HEAT EXCHANGER PRESSURE DROP
Page 5
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
Main Features
Hot water tank with integrated heat exchanger and enamelled
non-detachable insulation and a magnesium anode rod that
Application
Code 19441
Standing loss 65 W
Storage volume 114 l
Technical Data
Ambient temperature 2 to 45 °C Max. relative humidity 80% Total volume 120 l Heat exchanger volume 6 l Max. working pressure in tank 6 bar Max. working pressure in heat exchanger 6 bar Max. temperature in tank 95 °C Max. temperature in heat exchanger 100 °C Heat exchanger surface area 1.4 m² Tank height 1045 mm Tank diameter Ø 457 mm Tank dimensions w. insulation Ø 565 mm Tipping height 1143 mm Empty weight 71 kg
protects its inner surface from corrosion. As an option, an electronic anode rod can be installed instead of the magnesium one, for the codes see the Accessories table. If desired, an electric heating element can be installed into the hot water tank.
Water (tank), water, water–glycol mixture (max. 1:1) or water–glycerine mixture (max. 2:1) (heat exchanger).
C
Hot water heating from 10 to 45°C at heating water temp. of 60°C
Heat exchanger 570 l/h (23 kW)
Materials
Tank S235JR, inner surface enamelled (DIN 4753-3) Heat exchanger S235JR+N, outer surface enamelled (DIN 4753-3) Outer mantle hard plastic Insulation PU foam
Accessories
El. heating element models ETT-A, D, F, P, M Heating element max. length 370 mm Electronic anode rod code 9176
Spare parts (magnesium anode rods)
Magnesium anode rod, l = 500 mm code 448
5
Page 6
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
- RGC 170
Dimensions
pos. description
DHW heating
W1
cold water G 3/4ʺ M 1030
W2 hot water G 3/4ʺ M 1030
W3 recirculation G 3/4ʺ M 1030
Auxiliary heat source
electric heating element for DHW G 6/4ʺ F 345
E1
Control and safety
sheath Ø 15 mm 980
C1
T thermometer G 1/2ʺ F 630
Heat sources
X1
X2 return to heat source G 3/4ʺ M 1030
Other
universal inlet/outlet G 1/2ʺ F 110
U1
A1 magnesium anode rod G 5/4ʺ F 930
connection
G 3/4ʺ M 1030
height [mm]
HEAT EXCHANGER PRESSURE DROP
Page 7
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
Main Features
Hot water tank with integrated heat exchanger and enamelled
non-detachable insulation and a magnesium anode rod that
Application
Code 19196
Standing loss 80 W
Storage volume 166 l
Technical Data
Ambient temperature 2 to 45 °C Max. relative humidity 80% Total volume 173 l Heat exchanger volume 7 l Max. working pressure in tank 6 bar Max. working pressure in heat exchanger 6 bar Max. temperature in tank 95 °C Max. temperature in heat exchanger 100 °C Heat exchanger surface area 1.6 m² Tank height 1030 mm Tank diameter Ø 600 mm Tank dimensions w. insulation Ø 715 mm Tipping height 1210 mm Empty weight 98 kg
protects its inner surface from corrosion. As an option, an electronic anode rod can be installed instead of the magnesium one, for the codes see the Accessories table. If desired, an electric heating element can be installed into the hot water tank.
Water (tank), water, water–glycol mixture (max. 1:1) or water–glycerine mixture (max. 2:1) (heat exchanger).
C
Hot water heating from 10 to 45°C at heating water temp. of 60°C
Heat exchanger 600 l/h (24 kW)
Materials
Tank S235JR, inner surface enamelled (DIN 4753-3) Heat exchanger S235JR+N, outer surface enamelled (DIN 4753-3) Outer mantle hard plastic Insulation PU foam
Accessories
El. heating element models ETT-A, D, F, P, M Heating element max. length 500 mm Electronic anode rod code 9176
Spare parts (magnesium anode rods)
Magnesium anode rod, l = 500 mm code 448
7
Page 8
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
5 - Example of Assigning Connection Points
- RGC 120
Example:
With a hot-water boiler
KEY
1 – heating system expansion vessel
2 – RGC 120 hot water storage tank
3 – DHW expansion vessel
4 – safety kit for HW storage tank
5 – pump station for DHW recirculation – CSE TV ZV
6 – boiler (natural gas, electric...)
SV – cold water
TV – hot water
CV – hot water recirculation
ÚT – central heating (heating system)
KK – ball valve
ZV – check valve
AOV – automatic air vent valve
PTR – pressure temperature relief valve
REDV – pressure reducing valve (optional)
VK – drain valve
SVE – expansion vessel service valve
PV-ÚT – safety valve for heating system
MFB – Magnet Filterball
Page 9
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
- RGC 170
Example:
With a hot-water boiler and RegulusBOX
KEY
1 – Regulus heat pump (RTC, CTC)
2 – RGC 170 hot water storage tank
3 – DHW expansion vessel
4 – safety kit for HW storage tank
5 – pump station for DHW recirculation – CSE TV ZV
6 – heating system expansion vessel
7 – RegulusBOX indoor unit
SV – cold water
TV – hot water
CV – hot water recirculation
ÚT – central heating (heating system)
KK – ball valve
ZV – check valve
AOV – automatic air vent valve
PTR – pressure temperature relief valve
REDV – pressure reducing valve (optional)
VK – drain valve
SVE – expansion vessel service valve
PV-ÚT – safety valve for heating system
MFB – Magnet Filterball
BRAIDED HOSE
COMPENSATOR
9
Page 10
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
6 - Installation and Commissioning
Installation must meet valid rules and may be done only by qualied staff. The tank shall be placed on the oor, as close to the heat source as possible.
Warning: Defects caused by improper installation, use or handling are not covered by warranty.
6.1 - Connection to heat sources
Connect the heating circuit to the inlet to and outlet from the heat exchanger (connection points marked X1 and X2) using G 3/4” fittings.
6.2 - Installation of an electric heating element
The G 6/4“ side tapping marked E1 is designed to accommodate an electric heating element. The hot water storage tank can be equipped with an el. heating element depending on the tank diameter and the heating element length. It can be controlled either directly (thermostat-equipped elements), or by a heating system controller.
Warning: All electric heating elements shall be protected by a safety thermostat.
The installation of an electric heating element may be done by qualied staff only.
6.3 - Connection to water mains
DHW piping shall be done according to valid rules. Connect the tank to a cold water inlet (connection point marked W1), inlet from hot water recirculation (connection point marked W3) and to DHW outlet (connection point marked W2) using G 3/4” ttings. A 6bar safety valve shall be installed at the cold water inlet. Installa­tion of a reducing valve to the tank inlet is recommended. If the pressure from water mains exceeds 6 bar, a reducing valve is necessary. In order to prevent water loss, an expansion tank o fat least 5 l volume should be installed at the cold water inlet as well. Should the water be too hard, install a water softener before the tank. In case the water contains mechanical
impurities, install a lter.
A suitable anti-scald valve shall be installed at the hot-water outlet from the tank that prevents too hot water from entering the taps. Install a drain valve to the connection point U1 of the tank. Complete DHW piping shall be properly insulated.
6.4 - Instalace elektronické anody
A so called electronic anode rod can be used instead of the magnesium one. Its principle advantage is that it does not need to be taken out for check. Just a visual check of the electronic anode is sufficient.
Kit for hot water storage tanks of RGC 120 and RGC 170 series
Code El. anode length [mm] For hot water tanks
9176 600 (350/250) RGC 120 and RGC 170
Should an electronic anode rod or an el. heating element be installed, it is necessary to make a connection between the metal tank casing and the PE line.
6.5 - Commissioning
Ground the tank before commissioning. Fill the heating circuit with the appropriate fluid and air-bleed the entire system. Fill the tank with cold water, following this procedure:
- open the shut-off valve at the tank inlet
- open a hot water tap, as soon as water starts flowing out, tank filling is finished, close the tap
- check all connections for leaks, check the system pressure
10
Page 11
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
Table of limit values for total dissolved solids in hot water
Description pH Total dissolved
solids (TDS)
Max. value 6.5 - 9.5 600 mg/l 40 mg/l 100 mg/l 20 mg/l 200 mg/l 0.2 mg/l
Hot water quality must meet the conditions shown in the following table. Set the heating controller in compliance with the documentation and manufacturer’s recommendations. Check regularly a proper function of all control and adjusting elements.
Ca Chlorides Mg Na Fe
7 - Maintenance, Replacement of Magnesium Anode Bar
If the tank is tted with a heating element, disconnect it from the mains rst.
Clean the exterior of the tank with a soft cloth and a mild detergent. Never use abrasive cleaners or solvents. Check all tank connections for leaks.
The tanks come equipped with an anti-corrosion sacrice magnesium anode rod as standard; it protects its
inner parts against corrosion. The anode rod shall be chec ked within 12 months after commissioning and subsequently always not later than 12 months after the last check. In locations where water contains more ferrites or calcites, it is recommended to check the anode rod every 6 months. If more than 1/3 of its total volume is consumed, the anode rod shall be replaced with a new one. Disregarded of its state, the magnesium anode rod (code 448) shall be replaced with a new one within 24 months from commissioning. In case an electronic anode rod is used, the above described procedures are not necessary. Then only a visual check of its indication lamp is necessary every 3 months. The indication of proper working of the electronic anode rod is described in its Manual. If damage to a tank occurs due to neglected replacement of a magnesium anode rod or a non-working electronic anode rod, the warranty cannot be claimed.
8 - Disposal
Packaging shall be disposed of in compliance with the valid rules. When the product reaches the end of its life, it shall not be disposed of as household waste. It shall be dropped off at a Local Waste Recycling Centre. Insulation shall be recycled as plastic and the steel vessel as scrap iron.
9 - Warranty
This product is covered by warranty according to the conditions described in this Manual and according to the Warranty Certicate. A Warranty Certicate is an integral part of the supply. Tank transport or storing in a horizontal position is considered warranty violation!
11
Page 12
©2023 We reserve the right to errors, changes and improvements without prior notice.