6 - Installation and Commissioning
Installation must meet valid rules and may be done by qualified staff only. The tank shall be placed on the
floor, as close to the heat source as possible.
Warning: Defects caused by improper installation, use or handling are not covered by warranty.
6.1 - Connection to heat sources
Connect the heating circuits to the inlet to and outlet from heating coil using G 1” nipples.
6.2 - Connection to a solar system
The tank can be used with a solar system. In such a case, the inlet for hot heat-carrying liquid coming from the
solar system shall be connected to the G 1” upper sleeve of the heating coil and the lower outlet to the return
piping to the solar system. Insulate all the piping between the tank and the solar system.
6.3 - Heating rod installation
The G 6/4“ side sleeve is designed to accommodate an electric heating rod. Heating rods of output up to 6 kW
can be used (depending on the tank diameter and rod length), connected either directly to the mains (thermostat-equipped rods), or to a heating system controller. The installation may be done by qualified staff only.
Warning: All electric heating elements shall be protected by a safety thermostat.
6.4 - Connection to water mains
DHW piping shall be done according to valid rules. G 3/4” threaded couplers are used to connect the tank to a
cold water inlet and hot water outlet. A 6bar safety valve shall be installed at the cold water inlet, installation of
a reducing valve is recommended. If the pressure from water mains exceeds 6 bar, a reducing valve is necessary. In order to prevent water loss, an expansion tank should be installed at the cold water inlet as well (8l
volume for RDC 160 and RDC 200, 12l volume for RDC 300).
Should the water be too hard, install a water softener before the tank. In case the water contains mechanical
impurities, install a strainer.
A suitable thermostatic mixing valve should be installed at the hot-water outlet from the tank, preventing too
hot water from entering the taps.
Install a drain valve to the lowest point of the tank.
Complete DHW piping shall be properly insulated.
6.5 - Electronic anode rod installation
A so called electronic anode rod can be used instead of the magnesium one for RDC 300 tanks. Its principle advantage is that it doesn’t need to be taken out for function check. In this case, just visual check of the
electronic anode indication lamp is sufficient. RDC 160 and RDC 200 tanks are not designed for use of an
electronic anode rod.
The electronic anode kit mounts in place of the magnesium one. In order to install (replace) the electronic anode rod, a space is needed between the tank top and ceiling that corresponds to the anode rod length shown
in the table below. In order to protect the tank properly and meet its warranty conditions, the anode from the
table below shall be used.
Kit for RDC 300 storage water heater.
Should an electronic anode rod or ran electric heating rod be installed, an interconnection shall be done, i.e.
the metal mantle of the storage tank shall be wired to the protective neutral.
6.6 - Commissioning
Fill the heating circuit with the appropriate fluid and air-bleed the entire system.
Fill the tank with cold water following this sequence:
- open the shut-off valve at the tank inlet
- open the hot water tap/outlet point, as soon as hot water starts flowing, filling is complete; close the
tap
- check all connections for leaks and the system pressure
Code Anode rod length [mm] For tanks
9174 500 (350/150) RDC 300