1.2 Tank protection .................................................................................................................................. 3
2 General Information ...................................................................................................................................... 3
3 Technical Data and Dimensions .................................................................................................................. 4
6 Installation and Commissioning .................................................................................................................. 8
7 Installing Insulation on the Tank .................................................................................................................. 9
PS E+ Accumulation Tanks are intended for accumulation and subsequent distribution of thermal energy from solid-fu-
el red boilers, heat pumps, solar collectors, electric boilers etc. No heating coils can be installed into these tanks,
just an el. heating rod. Heating rods of 2-12 kW output can be installed directly into the 6/4” sleeves that are power
supplied either with 230V or 3x230V/400V. Tanks are tted with four side sleeves, one top sleeve and two sleeves for
sensor sheaths. 100mm thick insulation for these tanks is sold separately.
1.1 - Models
Five models of 473 l, 756 l, 927 l, 1038 l and 1260 l capacity.
1.2 - Tank protection
The inner surface has no nish, no anticorrosion protection, the outer surface is lacquered in gray.
1.3 - Thermal insulation
Tank insulation is available as a separate item, installed on the tank on the spot for easier handling. The insulation is
made of 100 mm thick eece and tted with a zippered outer PU leather jacket.
1.4 - Connection points on the tank
4 side sleeves, G 6/4“ F
1 top sleeve, G 6/4“ F
2 side sleeves for sensor sheaths, G 1/2“ F
1.5 - Packing
Tanks are delivered standing, each screwed to its pallet, packed in bubble wrap.
2 - General Information
This Owners Manual is an integral and important part of the product and must be handed over to the User. Read carefully the instructions in this Manual as they contain important information concerning safety, installation, operation and
maintenance. Keep this Manual for later reference. The appliance shall be installed by a qualied person according to
valid rules and Manufacturer‘s Instructions.
This appliance is designed to accumulate heating water and distribute it subsequently. It shall be connected to a heating system and heat sources.
Using the accumulation tank for other purposes than above described is forbidden and the manufacturer
accepts no responsibility for damage caused by improper or wrong use. The accumulation tank shall not be
used as a DHW tank!
The appliance shall be installed by a qualied person according to valid rules, otherwise the warranty becomes null
Storing and subsequent distribution of heat from solid fuel boilers, heat pumps or other heat sources.
Energy Efciency (EC Regulation 812/2013)
PS 500 E+
with insulation
PS 750 E+
with insulation
PS 1000 E+
with insulation
PS 1100 E+
with insulation
PS 1250 E+
with insulation
Energy Efciency Class C -- --
Storage volume92 W118 W131 W139 W156 W
Storage volume473 l756 l927 l1038 l1260 l
Technical Data
Total tank volume473 l756 l927 l1038 l1260 l
Max. working temperature in
95 °C95 °C95 °C95 °C95 °C
tank
Max. working pressure in tank 4 bar4 bar4 bar4 bar3 bar
Material
Tank materialS235JRS235JRS235JRS235JRS235JR
Dimensions, tipping height, weight
Tank diameter600 mm750 mm800 mm850 mm950 mm
Tank diameter with insulation800 mm950 mm1000 mm1050 mm1150 mm
Total tank height1915 mm1975 mm2080 mm2080 mm2065 mm
Tipping height without insulation 1940 mm2020 mm2120 mm2130 mm2120 mm
Max. length/output of heating el. 680 mm / 9 kW 755 mm / 9 kW 815 mm / 12 kW 815 mm / 12 kW 955 mm / 12 kW
Empty weight68 kg90 kg106 kg124 kg125 kg
Accessories
Insulationcode 16330code 16338code 16344code 16347code 16 351
Safety valve 3 bar, 1/2" M-F, included
El. heating elementmodels ETT-A, C, D, E, F, G, K, L
Tipping height without insulation1940 mm2020 mm2120 mm2130 mm2120 mm
Marking
Connec-
tion
Height
[mm]
Connec-
tion
Height
[mm]
Connec-
tion
Height
[mm]
Connec-
tion
Height
[mm]
Connec-
tion
Height
[mm]
Heating system
H1
H2
G 6/4"1915G 6/4"1975G 6/4“2080G 6/4"2080G 6/4"2065
G 6/4"225G 6/4"225G 6/4“300G 6/4"255G 6/4"300
Control, safety
C1
C2
G 1/2"1545G 1/2"1575G 1/2“1620G 1/2"1665G 1/2“1620
G 1/2"505G 1/2"535G 1/2“580G 1/2"535G 1/2“580
Universal inlet/outlet
U1
U2
U3
G 6/4"1625G 6/4"1655G 6/4“1700G 6/4"1745G 6/4“1700
G 6/4"975G 6/4"955G 6/4“1050G 6/4"1045G 6/4“1000
G 6/4"375G 6/4"405G 6/4“450G 6/4"405G 6/4“450
Tank dimensions [mm]
V - Tank height19151975208020802065
Ø Di - Tank diameter600750800850950
Ø De - Diam. with insulation800950100010501050
5
│
4 - Operation
In the accumulation tank heating water is heated up from several heat sources like various types of hot-water boilers,
renewable energy sources (heat pumps, solar collectors), or electric heating rods.
The accumulation tank shall be connected to a heat source through G 6/4” threaded ttings. Should the tank be connected to a solar system, this must be done via a heat exchanger because solar systems are not lled with heating
water. Individual connection points are assigned according to the circuits to be connected. There is a wide choice of
combinations, just some examples are described in the following chapter.
5 - Typical Installation Examples
Example I.
Solid fuel boiler and el. heating rod.
HW
CW
PS E+
Example II.
Gas red boiler and hydronic replace.
GAS
BOILER
HW
CW
PS E+
6
│
6 - Installation and Commissioning
Defects caused by improper installation, use or handling are not covered by warranty.
Defects caused by improper installation, use or handling are not covered by warranty.
After the tank is installed and connected to an existing heating system, it is recommended to clean the entire heating
system using a suitable cleaning agent, e.g. MR-501/R or some other supplied by Regulus.
Anti-corrosion protective liquid should be also used, e.g. MR-501/F or F1.
6.1 - Connection to heat sources
Place the tank on the oor, as close to your heat source as possible. Mount the insulation, cf. Installing Insulation on
the Tank. Connect the heating circuits to inlets and outlets respecting the thermal stratication in the tank. Install a
drain valve at the lowest point of the tank. Install an air vent valve at the highest point of the system. Insulate all the
connecting piping.
6.2 - Connection to a solar system
The tank can is not primarily intended for use with a solar system but if needed, this can be done via a heat exchanger between the solar system and the tank. In such a case, insulate well all the piping between the tank and the solar
system.
6.3 - Heating rod installation
The tank may be tted with electric heating rods up to 9 kW (12 kW) output. They can be power-supplied either directly (elements with built-in thermostat) or via a controller for the entire heating system.
All electric heating elements shall be protected by a safety thermostat.
Electric heating rods shall be installed by an authorized person only.
6.4 - Commissioning
This tank is not designed for DHW heating.
The tank shall be lled up together with the heating system, respecting valid standards and rules. In order to minimize
corrosion, special additives for heating systems should be used. The quality of heating water depends on the quality of
lling water at commissioning, on the top-up water and on the frequency of topping up. This has a strong inuence on
the lifetime of heating systems. Poor quality of heating water may cause problems like corrosion or incrustation, esp.
on heat transfer surfaces.
Fill the heating circuits with the appropriate uids and air-bleed the entire system. Check all connections for leaks and
verify the system pressure. Set the heating controller in compliance with the documentation and manufacturer’s recommendations. Check regularly proper function of all control and adjusting elements.
7
│
7 - Installing Insulation on the Tank
Instructions
Product description
Fleece thermal insulation with PU leather surface.
Warning
Insulation installation shall be done in two or three persons, depending on its size. The zippered eece insulation
must not be installed at temperatures below 20°C. If this cannot be avoided, the insulation shall be pre-warmed in
another room to at least 20°C. It is impossible to install insulation of lower temperature, there is a risk of damage, esp.
to the zipper.
Do not use any tools for installation.
Keep away from open re.
How to install soft foam insulation with a PVC layer
1. Fix the tank following installation instructions.
2. Wrap the insulation around the tank carefully. Check that the insulation adheres to its body perfectly. This can be
reached by rubbing and patting the insulation by hand from its center evenly in both directions until the insulation
adheres to the tank’s surface completely and no bubbles are left.
3. Use the holes for sleeves as a rest during the insulation installation.
4. At least one person presses the insulation to the tank, pulling both ends together. The other person closes the
zipper.
5. Put on the upper insulation and cover.
6. Push on the covering plastic rosettes depending on the size of sleeves, or put on the ange plug(s) with insulation.
7. Finish the tank installation in compliance with the respective instructions and valid standards and rules.
Warranty on insulation
The insulation is covered by a 24-month warranty. This period starts the next day after the insulation is sold.
□ Warranty shall become null and void if:
○ the procedure described in the Installation Manual was not respected,
○ the product was used for other purposes than intended.
□ Warranty does not cover:
○ usual wear and tear,
○ damage caused by re, water, electricity or a natural disaster,
○ defects caused by failure to use the product in compliance with its intended purpose, by improper use and
insufcient maintenance,
○ defects caused by mechanical damage to the product,
○ defects caused by tampering or incompetent repair.
8
│
Návod na instalaci měkké izolace s koženkovým povrchem
Installation instructions for soft insulation with PU leather surface
12/
2015
REGULUS spol. s r.o.
Do Koutů 1897/3 http://www.regulus.cz | http://www.regulus.eu143 00 Praha 4 E-mail: obchod@regulus.cz | E-mail: sales@regulus.euČESKÁ REPUBLIKA | CZECH REPUBLIC
9
│
8 - Maintenance
If the tank is tted with a heating element, disconnect it from the mains rst. Clean the exterior of the tank with a soft
cloth and a mild detergent. Never use abrasive cleaners or solvents.
Check all connections for leaks.
9 - Disposal
Packing shall be disposed of in compliance with the valid rules. When the product reaches the end of its life, it shall
not be disposed of as household waste. It shall be dropped off at a Local Waste Recycling Center. Insulation shall be
recycled as plastic and the steel vessel as scrap iron.
10 - Warranty
This product is covered by warranty under the conditions listed in this Manual and in compliance with the Warranty
Certicate. A Warranty Certicate is an integral part of this accumulation tank scope of supply.