The appliance shall be installed by a trained person. The Manual is intended for an informed person. The
contents of this Manual may change over time.
THE APPLIANCE OPERATES WITH VOLTAGE DANGEROUS TO HUMAN LIFE. PLEASE STICK TO SAFETY
INSTRUCTIONS GIVEN IN THIS GUIDE, PREVENTING THUS RISK OF ELECTRIC SHOCK.
IMPORTANT
Wrong wiring or handling may cause damage to the appliance itself or c onnected machines!
Prior to beginning with installation and start of the appliance, please read the Manual carefully and follow the
instructions meticulously!
These electrical appliances shall be grounded in compliance with the valid standards. The cross-sections of the power
supply cables and their current ratings shall conform to the nominal values on the label and to the specification of the
appliance as required by a respective rule valid for low-voltage electric appliances. Prior t o installation of this electric
appliance please make sure all circuit breakers and fuses ar e off.
Batteries may only be handled by trained, informed and experienced persons sticking to all applicable safety measures.
Before touching the battery clamps, all safety and switch-off elements at the appliance itself, batteries and their outlets
shall be switched off!
Do not put any tools, instruments or ot her, esp. metal items on batteries!
Do not push any objects into the appliance through the ventilation or other o penings!
Use a damp cloth to clean the casing. Take care not to let moisture or water into the appliance through the ventilation or
other openings!
The appliance shall be installed in a sufficiently spacious and ventilated room enabling good access. It shall never be
exposed to weather!
For any handling the battery and PG 600 SX, the backup power supply shall be turned off and disconnected from the
mains.
The appliance is not designed to be operated with an automotive starter b attery.
The backup time depends on the power drawn by the devices connected to PG 600 SX. The higher is t he power
consumption, the shorter is the backup time.
PLEASE RESPECT THE FOLLOWING INSTRUCTIONS
The appliance may be installed by authorized staff only!
When switching off the electric appliance fed by PG 600 SX do not forget to switch off the PG 600 SX itself as well.
Otherwise the PG 600 SX’s inverter c ontinues to supply electricity from its batteries and does not switch off until the
battery voltage drops below the set min. value.
Even if the appliance is turned off, the battery voltage is still present at the clamps.
No contact of the UPS outlet socket shall get connected to any lead of mains or any other electric wiring. The UPS is
designed for a closed circuit. If the UPS outlet got connected with the mains, there would be a danger of destroying the
connected appliances, the UPS itself, and even causing harm to health and property. The only lead that may be
connected outside the TN-S network is the protective yellow-green lead.
When testing a pump backup, never unplug the PG 600 SX from el. socket. Doing so would interrupt the PE line. De-
energizing shall be done by a circuit breaker or fuse.
PG 600 shall be always used with a battery connected.
Do not leave the appliance turned off for more than 6 months unless its batteries had been fully charged.
The appliance should be completely cleaned by a serviceperson at least twice a year. Cooling and heat exchange are
hindered by excess dus t inside and the appliance might get overheated.
Check annually that the battery terminals are properly tightened.
TAKING CARE OF YOUR BATTERIES
The appliance is equipped with maintenance-free lead acid batteries. The following rules shall be respected when using
them:
Avoid any mechanical stress, especially by a hit
Avoid any damage to the battery casing and do not attempt to open it. The acid inside is toxic, dangerous to skin and
eyes! In no case shall the battery be exposed to high temperatures or flames. There is a risk of explosion!
When the battery is to be replaced and a new one installed, its number, model, wiring manner and capacity set by the
manufacturer shall be maintained. Only an authorized serviceperson may do that.
In a room where the battery is pl aced the temperature shall be kept at 20 °C ± 5 °C. At temperatures above 20 °C t he
battery lifetime deteriorates, at temperatures below 20 °C the battery capacity deteriorates.
.
REGULUS - PG 600 SX - www.rgulus.eu
4
│
AFETY INSTRUCTIONS REGARDING THE
S
BATTERY
Never wire and charge very cold batteries (exposed to freezing temperatures).
A battery represents a serious threat to human health and the environment. It shall be disposed of in compliance with a
valid legislation.
Be extremely careful when using metal items and tools near the battery.
When working with the appliance, refrain from smoking and using open flame! Do not use water to extinguish eventual
fire, danger of explosion!
Gases develop in all lead acid batteries during charging. In traditional unsealed batteries these gases escape into the
air. In batteries with pressure valves most of these gases recombine inside the battery and just a very small portion
escapes into the air.
Always ensure good ventilation for battery cabinets or rooms (at least 1 l of air per hour). Hydrogen gas may explode
ause serious injuries and fire.
and c
Acid lead batteries suffer from reduced capacity when used for a long time. This is quite normal. In order to be sure
about its proper working, test its backup function at least once a year and verify if its backup time is sufficient.
Should the battery get very hot, start making sounds or inflating, leave the room immediately!
A
CID BURN INJURY
Should the acid get in contact with skin, take off immediately all
contaminated clothing, and wash immediately with plenty of
water, use sterile gauze bandage and special medical aids.
In case of contact of acid with eyes, rinse immediately with
plenty of water and call emergency and ambulance. In all
emergency, life-threatening situations contact a doctor asap.
.
.
HOW TO EXTEND THE SERVICE LIFE OF YOUR BATTERY:
Never store a discharged battery. Storing a discharged battery will cause its definite destruction!
Always charge a battery prior to storing and disconnect all leads from its poles. The battery may be stored for a longer
time in this manner only. At the same time, it is recommended to charge it every 3 months. Older batteries shall be
checked more frequently.
Should the UPS be disconnected from the mains for a longer time, it is unconditionally necessary to disconnect also the
battery from the UPS.
REGULUS - PG 600 SX - www.rgulus.eu
5
│
1.ESSENTIAL INFORMATION - USE, FEATURES, DESCRIPTION
-
PG 600 line UPSis intended preferably to power supply circulation pumps in heating systems.
-
The consumption of connected equipment shall not exceed the max. inverter output power.
-
Use exclusively acid lead batteries purchased from Regulus intended for backup power supplies.
-
The appliance is des igned for indoor use. Do n ot expo se it to adv erse weat her condit ions (direc t sunshi ne, rain) and
ncreased moisture level. Protect from dust!
i
-
The ON/OFF button on PG 600 SX does not disconnect electrically the internal circuitry. In order to de-energize the
P
G 600 SX, it is necessary to disconnect the power supply at the respective terminal - by pulling out the power cor
and
disconnecting the battery.
-
Do not put anything onto PG 600 SX.
-
Do not expose the appliance to high temperatures.
-
Do not open the cover of PG 600 SX when any of its internal circuits are energized; this may apply even if the power
supply at the input terminal is disconnected. In no case any repair on internal parts of PG 600 SX may be perform
b
y a user.
-
The front panel is designed for manual control; do not use sharp or pointed items.
-
PG 600 SX is not designed for operation in explosive environment.
-
PG 600 SX and the battery shall be placed in a sufficiently ventilated space. Ventilation openings shall not be covered
and air intake shall not be obstructed. The min. free space around the PG 600 SX see the Fig.
-
When PG 600 SX is in operation, its fan is running. Its switching is controlled (by its inner temperature).
1.1 GENERAL DESCRIPTION
d
ed
When the unit is power-supplied from the grid, the electricity runs via its internal bypass directly to its outlet socket. At
the same time, the battery is being charged. In case of a power failure, the inverter turns on and the load is fed from the
battery.
A battery connects to PG 600 SX using cables fitted with cable lugs. Max. battery capacity for PG 600 SX is 100 Ah.
During charging, the temperature of the unit may rise to circa 45°C (normal operation state).
F
EATURES
•
Automatic switching from grid to battery and vice versa
•
High efficiency inverter
•
Smart two-step battery charging with overcharge protection
•
Battery overload and complete discharge protection
•
Backlit LCD screen, sound signals
•
Inner temperature controlled fan
•
Smooth output sine wave
REGULUS - PG 600 SX - www.rgulus.eu
6
│
1.2 FRONT PANEL
Tone
Condition
Short, 0.5 sec.
PG 600 SX switching on.
Switching off by pressing OFF
discharged battery.
battery).
overload threshold.
Input
Grid power present
Output
T
here are 2 pushbuttons on the front panel. OFF and ON. Further there is a screen showing current condition of PG 600.
The screen should look like the pic. (right, below).
isplej
D
Input voltage from grid (approx. value)
PG 600 SX output connected to power grid
PG 600 SX output runs from battery, inverter working
Output voltage
Battery condition in %
PG 600 SX works within boundary values
Alarm
G 600 power output usage
P
Displayed
Load
0-20 %21-40 %41-60 %61-80 %81-100 %
1.2 REAR PANEL
The rear panel involves:
1.
Coiled power supply cable for PG 600 SX (INPUT)
2.
two 230 V power socket (OUTPUT)
3.
Fuse holder w. 10 A fuse (FUSE)
4.
Battery cables ( + - )
1.3 ACOUSTIC SIGNALS
Continuous, 2 sec.
Repeating, 0.5 sec. Alarm (overload, discharged
Intermittent short, 0.5 sec. The load reaches PG 600 SX
button, or automatic due to a
REGULUS - PG 600 SX - www.rgulus.eu
7
│
2. INSTALLATION
1.
Read the entire Manual incl. safety information and how to take care of your battery.
2.
Make sure the power grid voltage corresponds to the voltage PG 600 SX is designed for.
3.
Connect the battery using M6 bolts (44Ah and 100Ah batteries) or M5 bolts (18Ah battery). MIND THE POLARITY, +
red / - blue or black. The max. torque is shown on the batteries (usually 5-7 Nm). Fit plastic caps onto the battery
terminals. Mind the right polarity!
4.
Plug the power supply cord of PG 600 SX into the a wall socket. WARNING – PG 600 SX will start running and from
the moment on the batteries are being charged. At the same time, the internal cooling fan also starts running.
5.
Connect your pump or another load by plugging its cable into the socket of PG 600 SX. It is necessary to stick to a
wiring system.
TN-S
6.
Press ON/OFF push button to turn PG 600 SX on. A signal will sound. The green LED will stay lit,
indicating that PG 600 SX is running (standard mode, ready for backup).
7.
Nyní můžete spustit čerpadlo nebo jinou zátěž a odzkoušet provoz ze sítě bez střídače. Střídač se zapneautomaticky
při ztrátě napětí na vstupu.
2.1 RECOMMENDED WIRING
- it is recommended to use solely an installation contactor with a 230 VAC coil, 2x NO + 2x NC.
- it must be ensured that the PE lead cannot be disconnected (e.g. by pulling out the coiled power supply cable from
PG 600 SX)!
- unconditional separation of the circuit fed from PG 600 SX from the mains shall be respected
REGULUS - PG 600 SX - www.rgulus.eu
8
│
2.2 TURNING PG 600 SX ON WITH NO GRID POWER
Press the ON push button to turn PG 600 SX on. It takes the inverter about 30sec. to reach the proper voltage. The
screen shows battery operation (a battery shall be connected). After the power supply from the grid is restored, mains
voltage will appear on the screen and PG 600 SX will work normally, charging the battery.
2.3 TURNING PG 600 SX OFF
PG 600 SX can be turned off by pressing and holding the OFF push button for at least 3 sec. WARNING! The battery is
not being charged any more. In case of a power failure PG 600 SX will not provide any backup but it will switch on by
itself as soon as the power supply is restored. Complete turn off shall be done by disconnecting the mains.
Warning
•For safety reasons, it is strongly recommended not to modify the cables supplied.
•Make sure the power supply to PG 600 SX is safely earthed.
REGULUS - PG 600 SX - www.rgulus.eu
9
│
•A mains socket or circuit breaker shall be located close to the appliance and shall be easily accessible.
Situation
Cause
Solution
The screen is not lit
The screen is lit but the
connected load (pump) is not
running
●
PG 600 SX has been switched off,
●
Check battery condition and connection
Grid voltage is present but PG
600 SX displays zero grid
voltage and works in the battery
mode.
●
PG 600 SX gets no grid power.
●
Check the circuit breakers/fuses.
●
Faulty fuse
●
Replace the fuse
Battery capacity may be reduced:
●
Let the battery charge for about 8 hours
●
Overload
●
Check what is connected to PG 600 SX
Sound alarm (signal)
●
Discharged battery
●
Restore power supply and let the battery
•Never disconnect the 230 V power supply to PG 600 SX when it is running - the earth protection of bot
P
G 600 SX and the connected load would be interrupted.
h
•Check that when all loads are connected, the total earth leakage current does not exceed 2.7 mA (EN
62040-1-1).
•After PG 600 SX gets connected to the power grid, the battery recharging starts. At this point also th
e
cooling fan starts. After the battery is fully charged and the inner temperature in PG 600 SX does not
rise any more, the fan will not start again.
•In case of a power supply breakdown, the fan turns on, cooling the inverter if needed.
•When power supply is restored, the timer turns on and the cycle is repeated.
3. OPERATING STATES OF PG 600 SX
Power grid operation
The input voltage is shown on the screen, the battery is being recharged or is already fully charged.
attery operation
B
The screen shows no power grid voltage. The symbol of battery operation is shown. PG 600 SX will provide backup
until either power supply is restored or the battery completely discharged. When the threshold of 24% is reached, the
battery starts making intermittent alarm sound. From the moment on, the PG 600 SX may turn off any time depending
on the load level. After the power supply is restored, it takes at least 12 hours (preferably 24) to fully charge the battery.
arm
Al
The alarm symbol is shown and PG 600 SX makes a sound. When overloaded, PG 600 SX will disconnect the output
and make a continuous sound. Until the load is disconnected and PG 600 SX turned off and on again, it will not fulfil its
backup function. The sound alarm will start when the battery level falls to 24%.
4. TROUBLESHOOTING
PG 600 SX does not serve
the expected backup time
●
PG 600 SX is off.
●
No grid power, discharged battery.
●
Defect battery.
disconnecting the load.
●
Fault
●
Electrical socket is defect
●
Too long storage time
●
Overload
●
Battery lifetime over
●
Repeated frequent power
failures when the battery
does not get fully charged
again
●
Press and hold ON push button,
switching PG 600 SX on.
●
Restore power supply and let the battery
recharge. Eventually check the fuse.
●
Replace the battery.
●
Contact service staff
●
Check the el. Socket.
●
Disconnect excess load
●
Replace the battery
Sound alarm (signal)
sounds every 0.5 sec.
sounds continuously and
then PG 600 SX turns off
and disconnect excess load.
recharge.
For conditions not descri bed in this Manual, turn off PG 600 SX, disconnect the load, pull out the
Technical data
Backup power supply
PG 600 SX-18, PG 600 SX-44 a PG 600 SX-100
nominal voltage
230 V 50 Hz
voltage range
230 V (+25 % / 35 %) 50 Hz ± 10 %
Max. inverter power output
300 W
Nominal voltage
230 V
Voltage range (backup mode)
230 V (± 10 %)
Frequency
50 Hz
Frequency tolerance (backup
mode)
Waveform (backup mode)
smooth sine wave
Dimensions (D x W x H)
140 x 182 x 380 mm
Weight
6.3 kg without batteries
Ambient working temperature
0 - 35 °C
Ambient working humidit y
0 - 90 % non-condensing
Noise level
< 60 dB
power cable fr om the el. socket and disconnect the battery terminals. Then contact y our service
provider.
5. TECHNICAL SPECIFICA TIONS
Input
Output
± 0.5 Hz
Others
1 m long battery cables are included in the supply.