Regin OPTIGO OP10, OPTIGO OP10-230 User Manual

i
EN
INSTRUCTION
OPTIGO OP10, OP10-230
Read this instruction before installation and wiring of the product
Controller with display
Technical data
Supply voltage OP10-230 230 V AC +10 / -15%, 50/60 Hz OP10 24 V AC ±15%, 50/60 Hz Internal consumption 6 VA Ambient temperature 0...50°C Ambient humidity Max. 95% RH Storage temperature -20...70°C Display Numeric / graphic. Background illumination.
Inputs Refer to connection illustrations and table below Terminal blocks Disconnectable, so-called lift type for cable cross-section 2.5 mm
2
Protection class IP00 Material, casing Polycarbonate, PC Weight OP10-230 370 g incl. terminals OP10 215 g incl. terminals Dimensions 122 x 120 x 64 mm (WxHxD incl. terminals)
Setpoints
Factory setting
Temperature supply air 10...80°C 21°C room 10...50°C 21°C tap hot water 10…80°C 55°C Neutral zone 0...10°C 1°C P-band 0…99°C 15°C I-time 0…990 s 60 s D-factor 0…99 0 P-band cascade 0.5…99 15 Min. at cascade 0…99°C 15 Max. at cascade 0…99°C 25
6762F
APR 08
Damper min. limit 0…99 10 Start of outdoor compens. -30…50°C 10°C Outdoor compensation at -20°C outdoor temp -10…10°C 5°C Supply temperature (water-heated radiator heating) at -20°C outdoor temp. 0…99°C 60°C at 20°C outdoor temp. 0…99°C 20°C Frost protection 7°C (xed) SP. Shutdown mode 25°C (xed)
Installation
OP10 can be mounted in a DIN-standard casing (minimum 7 modules) or in a cabinet, either on a DIN-rail or, using the two screw-pockets provided, by being screwed to any suitable at surface in the cabinet. The control­ler can also be mounted in a cabinet door or other control panel, using a suitable front-mounting kit. Optigo 10-230 must be installed in a casing (DIN-casing or similar) where it can be used without risk of electric shock and where it fullls the demands for the LVD-standard. See the section Installation in the “Optigo OP10 Manual”, which can be downloaded from www.regin.se.
Follow table 1 below for setting.
Table 1. I/O connection terminals
Terminal Designation Operation
1 G 24 V AC
2 G0
3
1 L 230 V AC
2
3 N
10 Common DO3
11 NO
12 NC
13 GDO Reference for DO1 and DO2
14 DO1 Digital output
15 DO2 Digital output
20 AGnd Reference for AO1 and AO2
21 AO1 0...10 V DC output
22 AO2 0...10 V DC output
40 DI2 Digital input
41 DI+ Reference for DI1 and DI2
42 DI1 Digital input
43 UI+ Reference for UI1
44 UI1 Universal input PT1000 or Digital
50 AGnd Reference for AI1
51 AI1 PT1000 temp. sensor input
52 AGnd Reference for AI2
53 AI2 PT1000 temp sensor input
Optigo 10 only
Optigo 10-230 only
Relay 230 V AC, 5 A
For best protection against disturbances, a shielded twisted-pair cable should be used for wiring the sensors. Ground the shield at one end.
Control modes
Optigo can be congured to any one of the following control modes:
Supply air temperature control 1. The supply air temperature is kept at the setpoint value by con­trolling the output signals on AO1 and AO2. A single PI control loop is used.
Supply air temperature control with outdoor compensation 2. The supply air temperature is kept at the setpoint value by con­trolling the output signals on AO1 and AO2. A single PI control loop is used. The setpoint is automatically adjusted according to the outdoor temperature.
1
Cascade connected supply air control with room / extract air 3.
\ / \ / \ \ / / \ / \ /
24 V AC
N
L
Extended running
Fan indication
Alarm
Y1
Y2
Supply air temp
Room / Extract air temp
High temp limit switch
G
G0
DI2 DI+ DI1 UI+ UI1
A
GND
AI1
AGND
AI2
1 2 3
40 41 42 43 44 50 51 52 53
10 11 12
13 14 15 20 21 22
COM NO NC
G
DO
DO1 DO2 A
GND
AO1 AO2
°C
°C
G0
G Y
0 +
DO3
Fan start
230 V AC
Extended running
Fan indication
Fan start
Supply air temp
Outdoor temp
Frost protection temp
DI2 DI+ DI1 UI+ UI1
A
GND
AI1
AGND
AI2
40 41 42 43 44 50 51 52 53
1 2 3
10 11 12
13 14 15 20 21 22
L
N
COM NO NC
G
DO
DO1 DO2 A
GND
AO1 AO2
°C
°C
°C
DO3
 
N
L
230 V AC
Pump start
Supply temp
Outdoor temp
Room temp
DI2 DI+ DI1 UI+
UI1
A
GND
AI1
AGND
AI2
40 41 42 43 44 50 51 52 53
1 2 3
10 11 12
13 14 15 20 21 22
L
N
COM NO NC
G
DO
DO1 DO2 A
GND
AO1 AO2
°C
°C
°C
DO3
 
N
L
230 V AC
24 V AC
Y1
Supply water temp
'
'
$) $) $)
5)
5) !
'.$
!)
!
'.$
!)
  
        
  
     
#/­./ .#
'
$/
$/ $/ !
'.$
!/ !/
²#
'
' 9
$/
temperature inuence An offset in room temperature will adjust the supply air tempera­ture setpoint so as to eliminate the room temperature offset. Control loops with PI-control are used. The supply air tempera­ture is minimum and maximum limited.
Radiator circuit control with outdoor curve 4. The water temperature setpoint is changed according to the outdoor temperature. A single PI control loop is used. A room temperature sensor can be added to give corrective action if the room temperature differs from the setpoint.
Domestic hot water control 5. The water temperature is kept constant by controlling the output signal on AO1. A single PID control loop is used.
Control modes 1, 2 and 3
For control modes 1, 2 and 3, the analogue outputs can be congured to the following combinations:
AO1 AO2 Display symbols
1
Heating
2
Cooling
3
Heating
4
Heating
5
Cooling
6
Heating
7
Cooling
-
-
Cooling Heating Cooling
Damper Damper
Figure 2. Wiring example: OP10-230 with water heating, 3-position output. Supply air control with outdoor compensation.
Control mode 4
Figure 3. Wiring example: OP10-230 with 3-position actuator and room temperature sensor
The display menu system
The display menu system is divided into three levels, the congura­tion level (10-second level), the clock and scheduler level (3-second level) and the basic level.
The conguration level (10-second level)
This level is shown the rst time the unit is connected. It is reached from the Base Display (see the section The basic level below) by holding the encoder button depressed for 10 seconds. The 10-second level holds all the conguration menus. Note: The controller must display the Base Display when pressing the encoder knob to reach the 10-second level.
Table 2 below shows how the 10-second level is organised. When you enter the 10-second level, you will see menu level 0. Here, you choose the control mode. You navigate through the menus and con­trol modes by turning and clicking on the encoder knob.
Table 2. Display menus in the 10-second level
Menu
level
0
1
Supply
air temp.
control
Supply
air temp. contr. with outd. com-
pensation
2
Control modes
3
Cascade
control
4
Radiator
control
with
outdoor
curve
5 Domestic hot water
control
Note: For control modes 1, 2 and 3, the input for fan indication (DI1)
must be connected in order to start the control function.
Figure 1. Wiring example: OP10 with electric heating (for example via PULSER-X/D or TTC25X) and damper. Cascade control.
Control mode 5
Figure 4. Wiring example: OP10 with 0...10 V actuator
1
2
3
4
Output type
alt.
Output
signal
Neutr. zone
P-band
Output type
Output
signal
Neutr. zone
P-band
alt.
Output type
Output
signal
Neutr. zone
P-band
alt.
Output type
P-band
alt.
- -
- -
-
P-band
2
I-time
5
Damper
minimum
position
6
6 - -
Function for
input UI1
alt.
7
8 -
9 -
11
Menu
OK
alt.
alt.
I/O
I-time
Damper
minimum
position
Function for
input UI1
alt.
alt.
alt.
Startpoint
for outdoor
compen-
sation
Maximum
compen-
sation
I/O I/O I/O I/O
I-time
Damper
minimum
position
P-band
cascade
Function for
input UI1
alt.
alt.
alt.
Supply air
min limit
Supply air
max limit
I-time
0°C
tempera-
ture boost
- -
Pump
exercise
Low tem-
perature
setpoint
High tem-
perature
setpoint
I-time
D-factor
Over-
heating
-
-
Choose control mode in menu level 0 by clicking on the knob so the “Menu holds changeable values” symbol (see the section Display symbols below) starts ashing, and then turning the knob. When the control mode you want to choose is displayed, click once more on the knob so the “Menu holds changeable values” symbol stops ashing.
When you have chosen the control mode, you move between the menu levels by turning the knob when the “Menu holds changeable values” symbol is not ashing.
In some cases, making a certain choice in one menu will mean that you will only see certain other menus.
Example: To set the I-time for control mode 3 (Cascade connected room / extract air temperature control), go to menu 3.5. Click on the encoder knob. The “Menu holds changeable values” symbol will start ashing. Change the value by turning the knob and conrm the change by clicking on the knob. To exit the 10-second level, go to Menu OK and click on the encoder knob. The Time and Scheduler level will be displayed. To exit the Time and Scheduler level, go to the OK menu after the scheduler menus, and click on the encoder knob. You will be returned to the Base Display. There is also a time-out function that will automatically exit the congura­tion level after 5 minutes of inaction.
Storage of settings
All conguration settings become valid as soon as they are entered by clicking the encoder knob. They are however not written to the ash memory until you exit the conguration level either via the OK menu or via the time-out function. To exit the conguration level without saving the changes to ash memory, cut the supply voltage when still in the conguration level. All values will be kept as they were before you entered the conguration level.
See the “Optigo OP10 Manual” for more information about the conguration menus in the 10-second level. The manual can be downloaded from www.regin.se.
The clock and scheduler level (3-second level)
This level is reached from the Base Display by holding the encoder button depressed for 3 seconds. The 3-second level holds all menus for setting the clock and scheduler program. The scheduler function is only avail­able for control modes 1, 2, 3 and 4. Note: The controller must display the Base Display when pressing the encoder knob to reach the 3-second level.
This sample display shows that the time is 13:48 on a Friday, the fth day of the week. To set the clock, click the knob and the day-of-the-week number will start ashing. Turn the knob until the correct day is shown, Monday is 1, Tuesday 2 etc, and then click the knob again to acknowl­edge the choice. Now the hours will ash. Set them in the same way and then nally the minutes. After conrming the minutes the menu will change to show the rst of the scheduler menus. Note: The clock is not year- or date-based and does not have automatic summertime adaption.
There are 4 ON-points and 4 OFF-points. Each point has its own menupage where 0.1, 0.3, 0.5 and 0.7 are ON-points and 0.2, 0.4, 0.6 and 0.8 are OFF-points.
Control modes 1, 2 and 3 For control modes 1-3, the ON-points will start the unit and the OFF­points will shut it down. Example: You wish the unit to run Monday to Friday between 07:30 and 18:00, Saturday 8:00 to 14:00. Set the rst on-time to day 8 (which corresponds to every day Monday through Friday) and 7:30, the rst off-time to day 8 and 18:00. Set the second on-time to day 6 (the sixth day of the week) and 8:00 and the second off-time to day 6 and 14:00. Set all other menus to day -- (unused menus). After the eight switching point menus there is a ninth, 0.9. There the present output status of the scheduler is shown and you can manu­ally override the setting. If, for example, the switch is shown as ON and you change it to OFF it will remain off either until you manually change it to On again or until the next timer ON-point is reached. After the scheduler menus there is a nal menu, OK. A click on the encoder knob will exit the Time and Scheduler level and return you to the Base Display.
Control mode 4 Control mode 4 uses the scheduler for switching to economy mode (ECO) where the temperature is lowered by a settable number of degrees. The ON-points will switch ECOnomy period on and the OFF­points will switch back to comfort temperature. Example: Every weekday morning you want the temperature to start rising at 06:00 and remain at comfort level until 21:00. On Saturday and Sunday you want high temperature from 07:00 to 23:30. Set rst on-time to day 8 and 21:00, the rst off-time to day 8 and 06:00. Set the second on-time to day 6 and 23:30 and the second off­time to day 6 and 07:00. Set the third on-time to day 7 and 23:30 and the third off-time to day 7 and 07:00. After the eight switching point menus there is a ninth, 0.9. In this menu you set the number of degrees you wish to lower the room tem­perature setpoint during the economy periods. If no room sensor is connected the supply water setpoint will be lowered by 3 times the set value. After the scheduler menus there is a nal menu, OK. A click on the encoder knob will exit the Clock and Scheduler level and return you to the Base Display.
The basic level
The Base Display is shown when there is no operator activity.
3
Loading...
+ 5 hidden pages